GE AZ85W18DACM1, AZ85W12DACW1, AZ85W09DACW1, AZ85H18EACM1, AZ85H12EACW1 Owner’s Manual

...
GEAppliances.com
Safety Instructions ........... 2
O1
@
®I
N
U
0
0_
Operating Instructions
Controls--Dip Switches ......... 3-5
Controls--Terminal
Connections ................... 6, 7
On/Off Switch .................... 8
Ventilation Control ............... 8
Care and Cleaning
Air Filters ........................ 9
Base Pan ........................ 9
Exhaust Coils..................... 9
Installation Instructions
Electrical Supply.............. 11-13
Installing the Zoneline ........ 14-21
Preparation ..................... 10
Servicing........................ 22
Troubleshooting Tips ....... 23
Normal Operating Sounds ....... 24
Consumer Support
Consumer Support ...... Back Cover
Warranty ....................... 27
Cool Only, Heat/Cool and
Heat Pump Hodels
8500 Series
Espaflo! For a Spanish version of this manual, visit our
Website at GEAppliances.com.
Para consultar una version en espahol deeste manual de instrucciones, @site nuestrositio
de intemet GEAppliances.com.
Frangaise For a French version of this manual, visit our
Website at GEAppliances.com.
Pour une version franqaise de ce manuel d'utilisation, veuillez visiter notre site web 8 I'adresse GEAppliances.com.
Write the model and serial numbers here:
Model #
!
Serial #
You can find them on a label on the front case panel.
Printed in China TINSEA612JBRZ 49-7639 01-10 GE
IMPORTANT SAFETY INFORMATION.
READ ALL INSTRUCTIONS BEFORE USING.
A WARNING!
Riskof electric shock. Can cause injury or death. For your safety, the information in this manual must be followed to minimize the risk of fire, electric shock or personal injury.
SAFETYPRECAUTIONS
[]
This Zoneline must be properly installed in accordance with the Installation
Instructions before it is used. See the Installation Instructions in the back of this manual.
[]
Replace immediately all electric service cords that have become frayed or otherwise damaged. A damaged power supply cord must be replaced with a new power supply cord obtained from the manufacturer and not repaired.
Do not use a cord that shows cracks or abrasion damage along its length
or at either the plug or connector end.
[]
Product must be operated with the electrical plug supplied with the
product. Do not replace the electrical
plug supplied with the product.
[]
If the receptacle does not match the plug, the receptacle must be changed out by
a qualified electrician.
[] Unplug or disconnect the Zoneline
at the fuse box or circuit breaker before making any repairs.
NOTE: We strongly recommend that any servicing be performed by a qualified
individual. [] All air conditioners contain refrigerants,
which under federal law must be
removed prior to product disposal. If you are getting rid of an old product
with refrigerants, check with the
company handling disposal about
what to do.
[]These R410A Air Conditioner Systems
require contractors and technicians to use tools, equipment and safety standards
approved for use with this refrigerant. DO NOT use equipment certified for R22
refrigerant only.
READAND FOLLOW THISSAFETYINFORMATION CAREFULLY.
SAVE THESE INSTRUCTIONS
Controls-dip switches. GEAppliances.com
Controls-Dip Switches
Thedip switch controls are located behind the front case panel, through an opening
on the front of the unit. Toaccessthe dip switches, removethe front
case panel by removing the filter,taking out the four front screws,the upper two screws from
the top of the panel and the shipping screws on each side, ifpresent.(Discardthe four sideshipping
screws,if present).
NOTE:Theowner isresponsiblefor setting
the appropriate dip switches and connecting terminals.
Side
---._shipping screw
,/
TL3 (C)(Temp. Limit 3-Cool) TL2 (C)(Temp. Limit 2-Cool) TL! (C)(Temp. Limit i-Cool)
ALL 12R(All Electric Heat)(Heat-pump models only)
FREEZ S (Freeze Sentinel)
CONST FAN (Constant ON Fan)
All Electric Heat (Heat pump models only)
When this switch is enabled (UP),heat pump operation is locked out, causing the unit to provide only electric resistance heat.
TL! (H)(Temp. Limit 1-Heat)
_TL2 (H)(Temp. Limit 2-Heat)
_TL3 (H)(Temp. Limit 3-Heat)
DOWN
_J I J I [ j_N°Functi°n(Reservedf°rfutureuse)_DUCT(BlowerFan)
OCCUPIED(OccupancySensor)
[BBBBBBII BBBBBIooO .
hALL 12R(AllElectricHeat)
Controls-dip switches.
Freeze Sentinel (Requiresroom air sensor kit-RAVRMS)
When this switch is enabled (UP),itturns OFF the freeze sentinel protection feature. With the
switch disabled (DOWN),the freeze sentinel is activated which automatically provides heat
without userinterface. This helpsto prevent plumbing damage by turning the heater
and fans ON at 4! ° F and OFF at 46° F.
Constant ON Fan
When this switch is enabled (UP),it allowsthe fan to run continuously.
Occupancy Sensor (FieldSupplied)
[BBBBBBiIBITIBBBBI
I
FREEZES (Freeze Sentinel)
IBBBBBBIIBB BBBI
I
CONST FAN (Constant
ONFan)
When this switch is enabled (UP),it allowsthe unit to utilize an infrared motion sensor and a door
switch for occupancy detection. Thisfeature combined with field devicesautomatically cycles
the unit between normal operation and a preset energy management operation.
Duct
Theduct selectfunction allows the indoor fan to be operated at two variable fan speeds.
When this switch is enabled (UP),the unit automatically selectseither high or middle fun speed (for longer ductwork applications).When
set in the down position,the unit is automatically operated in either the middle or low fun speed
(forshorter ductwork applications).
I
OCCUPIED
(OccupancySensor)
rBBBBBBIiBBBB al
I
DUCT
(BlowerFan)
Temperature Limiting (Requiresroom air sensor kit-RAVRMS)
Temperature limiting can reduce energy costs by limiting the lowesttemperature that can be
set for cooling and the highest temperature that
of auxiliary controls. Thefirst three switchesare usedto select the cooling limits.The next three
switches are usedto control the heating limits. can be set for heating. Temperature limiting is controlled by switches 1-6 on the top block
GEAppliances.com
TL3(C)(Temp. Limit S-Cool) TL2(C)(Temp. Limit 2-Cool) TL! (C)(Temp. Limit Z-Cool)
Temperature limiting during COOL mode
(oil temperatures shown in °F)
UP DOWN
NONE !, 2, 3
1 2,3
1,2 3
2 1,3
2,3 1
!, 2, 3 NONE
1,3 2
3 1,2
Minimum Maximum
60 ° 85 ° 64 ° 85 ° 66 ° 85 ° 68 ° 85 ° 70 ° 85 ° 72 ° 85 ° 74 ° 85 ° 76 ° 85 °
I-L! (H)(Temp. Limit !-Heot)
_]-L2 (H)(Temp. Limit 2-Heot)
_TL3 (H)(Temp. Limit 3-Heot)
Temperature limiting during HEAT mode
(oil temperatures shown in °F)*
UP DOWN Minimum Maximum
NONE 4, 5, 6 60° 85 °
4 5, 6 60° 80 °
4, 5 6 60° 78 °
5 4, 6 60° 76 °
5,6 4 60° 74 °
4, 5, 6 NONE 60° 72 °
4, 6 5 60° 70 °
6 4, 5 60 ° 65 °
* Not opplicoble to Cool-Only models
5
Controls-terminal connections.
Controls-Terminal Connections
Theterminal connections are located behind the front case panel through an opening
on the front of the unit. Toaccessthe terminal connections, remove
the front panel byremoving the filter, taking out the four front screws,the upper two screws from the top of the panel and the shipping screws on
each side,if present.(Discordthe four side shipping screws,if present.)
Insertthe building hook-up wires into the bottom of the terminals and tighten screws securely
to make the desired connections. Routethe wiresfrom the terminal connections
through the unit wire guides and out through the case wire guide.
NOTE:Theowner isresponsible for setting the appropriate dip switches and connecting
terminals.
A CAUTION:
Improper CDCwiring may damage the Zoneline electronics or cause erratic Zoneline operation.
Nocommon busing is permitted. A separate wire pair must be run from each separate controlling
switch to each individual Zoneline.
through wire guides
connections
+®®®®®®®®®®++®®
e-_l _ le_ I _oIo >___
=:< _ o X=zo zo .+_ :
Room Air Sensor
Motion Sensor
Door Sensor
Central Desk Control
Room Air Sensor (Requiresroom air sensorkit - RAVRMS)
When connected, the room air sensor will allow utilization of the temperature limiting and freeze
sentinel features. NOTE:If GEthermostat RAK148D1,RAK148P1
or RAK164D1,RAK164P1isusedwith the unit, the room sensor kit isnot needed for temperature
limiting since this feature isincorporated in the thermostats.
em+l + 1ore l m lo -_ _ o_
=< _ m z + z o >m
L_= _ "< "< _ u _ 8
Hydronic Heating (RequiresHydronicHeating Kit - RAVHW!,RAVHW2or RAVHW3)
Requiredconnections for hydronic heating kit. NOTE:R,W, Cterminal connections will
alsobe connected to the remote thermostat ifapplicable.
@@@@@@@@@@@@@
om_le_ leo_ _ I_ Io _ _o_
=< _ o z + z + >m
LL
RoomAir Sensor
-- 2::_
z o
Common-Ground White-Heater Yellow-Compressor
Black-ReversingValve Green-HighSpeedFan Green-LowSpeedFan
Red-24VAConly
o >_,o, ..+>_o_+,+,,_o
_ ,,< ,,< _ u x o
HydronicHeating
I
Notion Sensor (Obtainedlocally)
TheOccupancy Sensor dip switch must be in the up position to usethis feature.
When connected, the wall mounted motion sensor will detect motion in the room and automatically cyclethe unit between normal operation and
energy management operation. Thedoor and motion sensors work together
to automatically cyclethe unit between normal operation and energy management operation.
Door Sensor (Obtainedlocally)
TheOccupancy Sensor dip switch must be in the up position to use this feature.
When connected, the door sensorwill detect when the door in the room is opened or closed.
Thisfeature must be used in conjunction with the motion sensor.
Thedoor and motion sensors work together to automatically cyclethe unit between normal
and energy management operations.
GEAppliances.com
L_ _ ,,< ,,<_ o _ o
Notion
Sensor
[°®®®°®®®®®®®®®®1
Central Desk Control
When connected, the unit lock-out is released and it can be turned ONor OFFwith a switch
located at the Central DeskControl.A separate wire pair must be run from each separate
controlling switch to each individual Zoneline. A 24VACcircuit powers the CDCsystem. Noexternal power isrequired.
Remote Thermostat
Theunit will be controlled by o remote
thermostat.
IMPORTANT:
TheZoneline thermostat connections provide 24V AConly.
If using a digital/electronic wall thermostat,
you must set it to the 24VACsetting.Seethe
Installation Instructions for the wall thermostat.
NOTICE:
Damage to a wall thermostat or to the Zonelineelectronics can result from improper
connections. Exerciseextra attention when connecting blue and black wires. No line voltage connections should be made to any circuit
in the thermostat. Isolateall wires in building from line voltage.
e_le_ le_ I _ I_ o, _ d _ _ o_
[®®1®®®®®®®®®®®®®_
e_;le_ le o I _ I_ o, _ _ _ _ o_
I I
Red-24VAConlyJ I
Green-LowSpeedFan
Green-HighSpeedFan
Black-ReversingValve
Yellow-Compressor
White-Heater
Common-Ground
___J
Other features of your Zoneline.
On/Off Switch
Theunit on/off switch islocated on the front of the Zoneline.
Toturn on the unit, pressthe top of the switch in. Toturn off the unit, pressthe bottom
of the switch in. NOTE:The on/off switch does not remove power
from the unit.
Ventilation Control
Theventilation control leveris located on the left sideof the Zoneline unit, behind the front case panel.
Toaccessthe ventilation control lever,remove the front panel byremoving the filter, taking out the four front screws,the upper two screws from
the top of the panel and the shipping screws on each side,if present.(Discardthe four side shipping
screws,if present). When the lever isin the CLOSEposition,only the air
insidethe room iscirculated and filtered. When the lever isin the OPENposition, some
outdoor air will be drawn into the room. This will reduce the heating or cooling efficiency.
Toclose the vent, push the vent lever handle down, pull it forward and lock it up in place.
Toopen the venL pushthe vent lever handle down, push it back and lock it up in place.
ON/OFF
switch
Open
O
Vent control (push
lever down and
pull forward or
back to operate)
Energy Tip: Keepthe vent control in the CLOSE position.The room air will be filtered and circulated.
NOTE:Ventilation openings are not intended to be
the source of make-up air for building ventilation
systems due to the additional heating and cooling loadsgenerated.
About Heat Pumps (onsome models)
Heat pumps can reduce operating costs by exchanging heat from the outside air-even
when the outside temperature is below freezing- and releasingthat heat indoors.
Toget the best economic benefit from your heat pump, don't change the room thermostat setting
very often. Raisingthe heat setting 2-3 degrees will cause the Zoneline to useits electric heating
There is a three minute minimum compressor run time at any setting to prevent short cycling.
The indoor fan motor starts before the compressor
and stops after the compressor cycles off.
Theelectric heating elements use much
more electricity than heat pumps and cost more to operate.
elements in order to reachthe new temperature setting quickly.
Do Not Operate the Air Conditioner (cool mode) in Freezing Outdoor Conditions
Airconditioners are not designed for use when freezing outdoor conditions exist. They must not be
used in freezing outdoor conditions.
Care and cleaning. GEAppliances.com
Turn off the Zoneline and disconnect the power supply before cleaning.
Indoor/Outdoor Coils
Theexhaust coils on the Zonelineshould be checked regularly. If they are clogged with dirt
or soot, they may be professionallysteam cleaned byyour GEservicecenter. Youwill need to remove
the unit from the case to inspectthe coils because the dirt build-up occurs on the exhaust side.
-- Outdoor coils
Have the coils cleaned regularly.
Drain
Cleanthe drain system regularly to prevent clogging.
Base Pan
In some installations, dirt or other debris may be blown into the unit from the outside and settle
in the basepan (the bottom of the unit).
Air Filters
To maintain optimum performance, change the filter at least every 50 days.
Themost important thing you can do to maintain the Zoneline isto change the filter at least every
30 days. Dirtyfilters reduce cooling, heating and air flow.
Changing the filter will'.Decreasecost of operation, saveenergy, prevent clogged heat
exchanger coils and reducethe risk of premature component failure.
Insome areas of the United States,a "gel-like"
substance may be present in the basepan. Checkit periodically and clean, if necessary.
Toremove and replace
the filter:
NOTICE: Do notoperate
the Zoneline without the filter in place. Ira filter becomes torn or damaged, it should be replaced
immediately.
Operating without the filter in place or with a damaged filter will allow dirt and dust to reach the indoor coil and reduce the cooling, heating,
airflow and efficiency of the unit.
Remove filter
filter
Filter
Replacement filters should be purchased from your local retailerwhere air conditioner
and furnace accessories are sold. Filtersizerequired is20"x 20" x 1".
Filter
Return air grille Access-panel with
return air grille 9
Installation
Zoneli
e
Air
Instruction
i Questions? Visit our Website at: GEAppliances.com or call 800.GE.CARES (800.432.2737). i
BEFORE YOU BEGIN
Readthese instructions completely and carefully.
IMPORTANT ELECTRICAL
SAFETY-READCAREFULLY
Co iti
r$
. IMPORTANT - Savetheseinstructions
for local inspector's use.
" IMPORTANT - Observe all governing
codes and ordinances.
. Note to Installer - Be sure to leave these
instructions with the owner,
. Note to Owner - Keepthese instructions
for future reference.
. Proper installation is the responsibility of the installer. . Product failure due to improper installation is not
covered under the Warranty.
. You MUSTuse all supplied parts and use proper
installation procedures as described in these instructions when installing this air conditioner.
TOOLS YOU WILL NEED
Phillipsscrewdriver
Saw
Adjustablewrench
Hammer
A WARNING: RISKOFELECTRICSHOCK.
. All electrical connections and wiring MUST
be installed by a qualified electrician.
. Follow the National Electrical Code (NEC)
and/or local codes and ordinances. For personal safety, this Zoneline unit and case must
be properly grounded. Protective devices (fuses or circuit breakers)
acceptable for Zoneline installations are specified on the nameplate of each unit.
o
Do not use an extension cord with this unit.
o
Aluminum building wiring may present special problems-consult a qualified electrician.
When the unit is not running there is still voltage to the electrical controls.
Disconnect the power to the unit before servicing by:
1. Removing the power cord (if it has one) from the wall receptacle.
OR
2. Removing the branch circuit fuses or turning the circuit breakers off at the panel.
Tope measure
,_WARNING: RISKOF ELECTRICSHOCK.
Can cause injury or death. This appliance must be
properly grounded. Where a 2-prong wall outlet is encountered, it is your responsibility and obligation to have it replaced with a properly grounded 3-prong
outlet.
10
Installation Instructions
ELECTRICAL REQUIREMENTS
Use ONLYthe wiring size recommended for single outlet branch circuit.
Proper current protection is the responsibility of the owner.
Recommended branch circuit wire sizes*
Nameplate
maximum circuit AWG Wire
breaker size size**
!5A 14 20A 12
30A 10
AWG- AmericanWireGauge * Singlecircuitbreakerfrommainbox
** Basedoncopperwire,singleinsulatedconductorat60° C
NOTE: Use copper conductors only.
2:30/208 VOLT
ELECTRICAL SUPPLY
A power supply kit must be usedto supply power to the Zonelineunit.Theappropriatekit isdetermined
bythe voltage, the means of electrical connection
and the amperage ofthe branch circuit. Seethe
POWERCONNECTIONCHARTon page 1:3to select the
appropriate kit.
FOR 230/208 VOLT CORD
CONNECTIONS ONLY
1. Removethe front panel by taking out the four front screws, the upper two screws from the top
of the panel andthe shipping screws on each side, if present. (Discardthe four sideshipping screws, if present.)
Side
-..._ shipping screw
/
2. Removethe junction box cover and the junction box and discard.
Remove
junction box
and cover
Power supply kit
All wiring, including installation of the receptacle,
must be in accordance with the NECand local codes,
ordinances and regulations.
@ @ @
Tandem Perpendicular Large Tandem
15 Amp 20 Amp 30 Amp
230/208 volt receptacle configuration
3. Connectthe power cord, with a loop, through the strain relief.
relief
III PORTANT: Powercord must
havea loop.
11
Installation Instructions
DIRECT CONNECT APPLICATIONS
FOR 230/208 VOLT DIRECT CONNECT
APPLICATIONS ONLY
Directconnection to branch circuit wiring inside the providedjunction box must be made by connecting asfollows in steps 1-3 below.
m
l-_ REMOVE JUNCTION BOX COVER
. RemovethejunctJon box cover by taking out the front
two screws.
FOR 265 VOLT DIRECT CONNECT
APPLICATIONS ONLY
IMPORTANT:Connection of a 265VACproduct
to a branch circuit MUSTbe done by direct connection
in accordance with the National ElectricalCode. Plugging
this unit into a building mounted exposed receptacle
isnot permitted by code.
These models must be installed using the appropriate
GEpower supply kit for the branch circuit amperage and the electrical resistance heater wattage desired.
Seethe POWERCONNECTIONCHARTon page 13
to selectthe appropriate kit.
It isthe responsibility of the installer to ensure
the connection of components isdone in accordance with electrical codes.
Direct connection to branch circuit wiring inside
the providedjunction box must be made by connecting
asfollows in steps 1-3 below.
[] ATTACH CONDUIT
Usethe round knockout hole at the top of the junction boxto install conduit coming from the branch circuit. Install and clamp the conduit
through the conduit clamp and bring wire leads into thejunction box. Leave8"of wire freefrom the end
of the conduit.
Junction box
box cover
Conduit
II _Conduit clamp
12
Installation Instructions
DIRECT CONNECT APPLICATIONS
MAKE WIRE LEAD CONNECTIONS INSIDE THE JUNCTION BOX
!, Makeall wire connections by usingappropriate UL-listed electrical connectors and techniques.
2. Selectthe applicable wiring situation and follow the instructions accordingly: 1-Phase 220-240 VAC
Whenconnecting theZoneline to a single-phase circuit for 230Vapplications:
Connectthe white and black leads of the Zoneline power supply kit to the branch circuit L1and L2 leads,
(Thewhite lead of the power supply kit should be identified bythe installer using electrical tape with some
color other than green or white.)Connectthe green lead of the power supply kit to the power supply and branch
circuit ground. 3-Phase 208 VAC
Whenconnecting theZoneline to a three-phasecircuit for 208Vapplications:
Connectthe white and black leads of the Zoneline power supply kit to the branch circuit L1and L2 leads.
(Thewhite lead of the power supply kit should be identified bythe installer using electrical tape with some
color other than green or white.)Connectthe green lead of the power supply kit to the power supply and branch
circuit ground.
3.
Besurethat all wire leads are insidethe junction box and not pinched between the box and the unit. Thegreen insulated ground wire from the Zoneline MUSTbe connected to the branch circuit ground wire,
4.
Plugthe 9-pin connector into the 9-pin receptacle in thejunction box.
5,
Replacethejunction box cover by replacing the two screws removed earlier.
3-Phase 208 VAC with "Crazy Leg"
Whenconnecting theZoneline to a three-phasecircuit with "CrazyLeg"for 208V applications:
Connectthe white and black leads of the Zoneline power supply kit to the branch circuit Neutral and LZ
leads.(Thewhite leadof the power supply kit should be connected to neutral.)Connect the green lead of
the power supply kit to the power supply and branch
circuit ground. 3-Phase 253-277 VAC
Whenconnecting theZoneline to a three-phasecircuit for265V applications:
Connectthe white and black leads of the Zoneline power supply kit to the branch circuit Neutral and L!
leads.(Thewhite leadof the power supply kit should be connected to neutral.)Connect the green lead of
the power supply kit to the power supply and branch
circuit ground.
Makewire lead
connections
POWER CONNECTION CHART
230/208 Volt
Power Supply Kits
RAK3202 RAK3152 1
RAK3302
230/208 Volt
Power Supply Kits j
RAK4207
RAK4157 I RAK4307
265 Volt
Power Supply Kits
RAK5207
RAK5157 I RAK5307
Wall Plug
Configuration
Perpendicular
Tandem J
Large Tandem
Heater Wattage
@ 230/208 Volts
2.55 KW/2.09 KW
3.45 KW/2.82 KW
5.00 KW/4.10 KW
Heater Wattage
@ 265 Volts
Power Cord Connections
Circuit Protective Device
15-Amp Time-Delay Fuse or Breaker 20-Amp Time-Delay Fuse or Breaker
30-Amp Time-Delay Fuse or Breaker
Direct Connections
2.55 KW
3.45 KW
5.00 KW
Heater Wattage
@ 230/208 Volts
2.55/2.09 KW
3.45/2.82 KW
5.00/4.10 KW
Circuit Protective Device
!5-Amp Time-Delay Fuse or Breaker 20-Amp Time-Delay Fuse or Breaker
30-Amp Time-Delay Fuse or Breaker
Circuit Protective Device
!5-Amp Time-Delay Fuse or Breaker 20-Amp Time-Delay Fuse or Breaker
30-Amp Time-Delay Fuse or Breaker
13
Installation Instructions
ZONELINE COMPONENTS
Case
Zoneline unit
REQUIRED ACCESSORIES
(Checkthe "Essential Elements" label on the unit.)
Front Case Panel
Cutout
Dimensions:
20" W x 32_"H
Wall Plenum
RAVWP6 - 6"D x 19¾"W x 32"H
Architectural Louver
RAVAL1
RAVWP8 - 8"D x 19s/J'W x 32"H RAVWP12 - 12"D x 19¾"W x 32"H RAVWP15 - 15"D x 19¾"W x 32"H
Cutout
Dimensions:
28"W x 48"H
Access Panel with OR
Return Air Grille
22½"
RAVRG1
t
Wall Thermostat
Model Type Mechanical Thermostat Electronic Thermostat Heat/Cool Models 4-wire g-wire
Heat Pump Models 6-wire 6-wire
Check the thermostat instructions for correct wiring and installation requirements.
Cutout
Dimensions:
20sA"Wx 20_"H
Return Air Grille
RAVRG2
14
Installation Instructions
TYPICAL UTILITY CLOSET AND DIMENSIONS
(FOR REFERENCE ONLY)
UNIT INSTALLED THROUGH FRONT OF CASE
Top View
Architectural Louver
4" min.
Door/access panel
UNIT INSTALLED THROUGH SIDE OF CASE
Side View
Inside wall ductwork z
Flexible or
I I J rigidduct [...........
,4" rain. from front of case - Unit I J J Air discharg_
installed through FRONTof case. I J I outlet ..... _i
5" min. from front of case - Unit installed through SIDEof case. _ i r,
3" rain. from two sides of case. Unit Wall (S"for side install). ] Wall plenum
divider
Option 1
Access panel wit_-------_
return air grille
Option 2 Return air grille
plenum
Top View
Architectural Louver
11_"
2C
dt _ Door/access panel
Unit front 5" min.
Outside wall
14" min. - Required only if optional Hydronic Heating Kit (RAVHW1, RAVHW2, RAVHWS)is to be installed. Clearance
for installation should be taken into consideration if this kit is to be used.
Plenum cutout 52¼" H Exterior/Outside x 20" W
L Bottom of case approx. 2"
5" min.
8"min. Platform: 23¼" x 23¼" square
for drain Min. load capacity: 17S Ibs.
access
B
A Minimum recommended access door width: 30"
B Minimum recommended access door height: 50"
15
above bottom of plenum
}_
Bottom of case approx. 2" above bottom of plenum
Outside wall
Field supplied outer flashing
Installation Instructions
UTILITY CLOSET CONNECTION LOCATIONS
IMPORTANT: Plan and locate plenum, wall plug, drains and
thermostat carefully to avoid interference. Hard-to-reach locations will make installation and service difficul!!
Use rigid duct for
90° bends and tees
Flex duct may be used
for transitions only
Outside wall
230/208 VAC wall receptacle F
or G conduit
for direct connection
Reference Dimensions
A Thermostat cable: 9½" long
B Power cord: 60" long
C Case width and depth: 23½"
D Case height: 31" E Condensate drains: 3/4" connector
, Primary Drain - Centerline of cutout is
approximately 51A''from left case wall and 8½" from back case wall.
, Secondary Drain - Centerline of cutout is
approximately 61/2"from left case wall and 5¼" from back case wall.
Typical wall plug: 6"-12" above case
Room air sensor kit: 10' long
D
Platform
16
Installation Instructions
RETURN AIR GRILLE INSTALLATION OPTIONS
The room return air grille may be installed toward the front or either side of the unit. Improper return air arrangements will cause performance problems.
There are three indoor return eir grille instellotion options. Choose the option that best suits your installation requirements. Follow the Installation Instructions provided with the return air grille accessory for installation details.
NOTE:Use only one filter in the installation. The filter may be installed on the unit or in the access panel/door.
Outside wall
RAVRGI - Access panel with
return air grille
Unit-mounted filter with a field-supplied return
air grille and access doorlpanel
Option 3
Option 1
RAVRG2 - Return air grille
Filter
Option 2
17
Installation Instructions
WALL PLENUM AND ARCHITECTURAL LOUVER INSTALLATION
Install the appropriate wall plenum through the exterior wall in accordance with the Installation Instructions provided with the plenum,
IMPORTANT: The wall plenum is not designed to carry structural loads.
Proper wall header construction is required. The plenum requires proper flashing,
shim and caulk for a weather resistant installation.
Proper header for structural support. Apply proper caulking and flashing.
Properly square
and level plenum.
Architectural
Louver--RAVAL1
Exterior/Outside Wall
RAVWP6 - 6"D x 19_"W x 32"H
RAVWP8 - 8"D x !9_"W x 32"H RAVWP!2 - !2"D x !9_"W x 32"H RAVWP!B - !B"D x !9sA"W x 32"H
[_ BUILD AND INSTALL THE ZONELINE
BASE PLATFORM
.
Construct u 23¼" min.x 23¼" min. square platform with legs to raisethe platform a minimum of 8",
NOTE:The platform must have a loud-bearing capacity of 175 Ibs.minimum.
Left side of platform Back of platform
23¼" '5¼" min.
for
f
drain access
NOTE:Specific cutout size for drain connections needs
to be determined by the installer for the given installation situation.
Cutout for drain connection(s)
(see NOTEbelow)
Wall Plenum
2. Make drain hole cutout(s): . Primary Drain - Centerline of drain is
approximately 5¼" from left platform edge and 8½" from back platform edge.
. Secondary Drain - Centerline of drain
isapproximately 6½" from left platform edge
and S¼" from back platform edge,
3. Place the platform in the utility closet
with the following clearance between it and the interior surface of the walls/door/panel:
. 4" rain. from front of the case-
Unit to be installed through FRONTof case
. 5" rain. from front of the case-
Unit to be installed through SIDEof case
. 3" rain. from two sides of the case (5" for side
installation).
4. Align the platform with the opening of the wall plenum and secure to the floor
using appropriate brackets and bolts.
18
Installation Instructions
[]_]INSTALL THE DRAIN{S)
An externaloran internaldrainmustbeattached totheprima_ drainconnector.A secondarydrain
issuppliedifrequiredby stateand localcodes.Refer tothelocalcodesforproperinstallationofthedrains.
Ifthesecondarydrainisnotused,sealitsdrainport
witha3/4"MNPT plug.
External Drain
Attach a 90° PVCelbow to the unit's female 3/4" NPT drain connector. Usethe other end of the elbow to run
a 3/4" Sch.40 PVCpipethrough the knockout holes of both the wall plenum and the architectural louver to the
outside.Sealthe gap between the plenum hole and PVC tube. Seethe Installation Instructions in the RAVAL1.
Inside wall Side View
ii !i!
PVC
xternal drain)
Internal Drain
Attach PVCto the unit'sfemale 3/4" NPTdrain connector. Seethe Installation Instructions
in the RAVAL!.Local codes may apply.
Inside wall Side View
DUCTWORK
%
Prepare the closet ductwork for later connection to the case.
Thetotal flow rate (CFM)and external static pressure (ESP)available can be estimated from the chart below.
Usethese charts to select your fan speedsetting. The collar on top of the case accepts standard 10" duct. Pullall duct tight. Extra duct slackcan greatly increase
static pressure.
NOTICE:Fie×duct con collapseand cause
airflow restrictions. Do not use flex duct for 90° bends or unsupported runs of 5 ft. or more,
Airflow - CFM@230Voltsand@265 Volts
IndoorFanCFM
DUCTSELECTSWITCH
UP i DOWN
High
CFM
52O 500 480
440 4OO 590 570 550 480
410
Medium Medium
CFM CFM
460 460 415 415
370 370
265 265
160 160
500 500 465 465
430 430
345 345 260 260
520 520 400 485 485 340
450 450 280 375 375 300 300
ESP
(in,water)
8 o.o
0.1
0.2
8 o.s
< 0./4
8 o.o
04
z 0.2
0.3
0.4
0.0 600
0.i 585
z 0.2 570
0.3 510
0.4 450
Tocorrectfor208volts:0.91
Your airflow should be balanced based on many factors, such as available ESP,room CFH,and ductwork.
Consultan HVACengineer for proper applications. External static pressure (ESP)can be measured with a manometer or pitot tube. Oncethis ESPisestablished, you can calculate the CFHusing the above chart.
Low CFM
36O 29O 22O
380
325 27O
-- PVC (Internal drain)
19
CFM Recommendations
9,000 BTU 12,000 BTU
390 415 440 440 465 490
e e
= Recommended Mid Range
18,000 BTU
435 485 535
e
Higher CFHstend to increase Sensiblecapacity, enhance room circulation and increase duct noise,
while lower CFMstend to increase Latent capacity and reduce noise.
Installation Instructions
[_JINSTALL AND CONNECT THE CASE
1.Removethe front case panel and pull the unit out of the case.Placethe empty case onto the platform in the closet with the outdoor sidefacing the wall plenum opening. Align the case with plenum
opening and attach with six field-supplied sheet metal screws (corrosion-resistant screws recommended).
2. Adjust all four leveling legs untilthe case is level.
Inside
Air discharge
outlet
Leveling legs
[_]INSTALL AND GROUND
THE UNIT TO THE CASE
UNIT INSTALLED THROUGH FRONT OF CASE
1. Slidethe back of the unit into the case, Pushthe unit all of the way into the case until it stops,
NOTE:Eitherof the case sides may be removed
to enable the unit to be slid into the case.
2. Ground the unit to the case by installing the front case-to-unit hex-bolt and discard the two case-to-unit
sidescrew.
Side screw jay
3. Using field-supplied screws, bolt the case to the platform.
4. Connect the internal or external drain(s)asnecessary.
Secondary _/' drain
iiiiiiii iiiiiiii iiiiiiii iiiiiiii
iiiiiiii iiii iiii
iiii
NOTE:Piping is not supplied with the unit. Obtain locally.
option. If not used,
Bolt case
to platform
: "_------------_---- Internal
-%
iiiiiiiiiiiiiiii_i_
External drain
OR
drainls)
[_]INSTALL AND GROUND
THE UNIT TO THE CASE
UNIT INSTALLED THROUGH SIDE OF CASE
1. Slidethe side ofthe unit into the case.Pushthe unit all of the way into the case until it stops.
NOTE:Eitherof the case sides may be removed
to enable the unit to be slid into the case.
2. Attach the case side panel to the main case.
3. Ground the unit to the case by installing the front unit-to-case hex-bolt and discard the two case-to-
unit side screw.
_
_
Side screw (may be
installed on either side)
Side screw
Hex bolt
20
Installation Instructions
J_ MAKE UNIT ELECTRICAL
CONNECTIONS
1.Connect the thermostat wires to the unit and set the dip switchesto the appropriate settings.
NOTE:Seethe Controls-Terminal Connections
and Controls-Dip Switches sections of this manual and the manual with
the separate thermostat for proper connections and settings.
Maximum Wiring Length for Thermostat
Connection to the Unit
66 ft. for AWG 18 60 ft. for AWG 20 40 ft. for AWG 24
AWG - American Wire Gauge
-7] CONNECT THE TOP DUCT
!. Install the duct onto the air discharge outlet.
Inside wall
Air/
discharge outlet
Unit Connections
2. Hake power connections to the unit. NOTE: See the ELECTRICALREQUIREMENTSand
DIRECTCONNECTAPPLICATIONSsections, as appropriate, of this manual for proper
connections.
3. Replace the case front panel by replacing the four front screws and the two top screws.
2. Securethe top duct to the unit byturning the four case top duct adjusting screws until they are tight. Use a field suppliedclamp to lock the top duct
to the case.
Top duct
Clamp
Case top duct adjusting screws
21
Installation Instructions
m
FINAL CHECK
Reviewthis Checklist before restoring power.
. Correct line voltage?
Singlecircuit only? HVACRtype breaker/fuse7
Ductwork connected? Caseand unit level7
Wall plenum caulked7Level7Flashing7 Drain connected?
Wall thermostat wired correctly? Unit wired correctly7 Hydronic plumbing connections (ifapplicable) Hydronic wiring connections (ifapplicable)
CONNECT POWER
1.If all the above items are correct,turn the power on at the main servicepanel.
2. Turn the unit power switch, on the front of the unit, to ON by pressingthe top of the switch in.
SERVICING
WARNING:Risk ofElectricShock,
can cause injuryor death. Beforeservicing,
switch power off at the service panel and lock the area to prevent power from being switched
on accidentally. When the area cannot be locked, securely fasten u prominent warning device, such as a tag, to the service panel.
NOTE:We strongly recommend that any servicing
be performed by a qualified individual.
Forease of service,the unit can be removed from the case:
1. Removethe front case panel.
2. Unplug the power cord and disconnect the wall thermostat connections.
3. Raisethe top duct by turning allfour case top duct adjusting screws counterclockwise.
4. Removethe front and/or sidecase-to-unit grounding screw, if present.
5. Slidethe unit out of the case.
22
Before YouCall For Service... GEAppliances.com
Troubleshooting Tips
Problem Possible Causes What To Do Zoneline does The unit isunplugged. * Makesure the Zonelineplug ispushed completely
not start into the outlet.
Thefuse isblown/circuit * Checkthe house fuse/circuit breaker box and replace breaker istripped, the fuse or reset the breaker.
The unit iswaiting for * Thisis normal.TheZonelinewill start again after it resets. the compressor overload
protector to reset. Power failure. . There isa protective time delay (upto 3 minutes) to
prevent tripping of the compressor overload. Forthis reason,the unit may not start normal heating or cooling
for 3 minutes after it isturned back on.
Zoneline does not cool Indoor airflow is restricted. . Makesure there are no curtains, blinds or furniture or heat as it should blocking the air discharge grille or the return air grille.
Outdoor airflow is restricted or redrculated.
, Makesure the architectural louver isnot restricted.
Thiscan cause the unit to cycle off due to the compressor overload.
, Outdoor grille must have a minimum of 65% free area.
Non-GEgrilles may be too restrictive for proper
performance. Consultyour salespersonfor assistance.
Burning odor at the start
of heating operation
The air is not always cool or hot during operation
The air does not feel warm enough during heating operation
The air filter is dirty. . Changethe filter at least every 30 days.
Seethe Cure and Cleaning-Air Filterssection.
The room may have been hot or cold.
Outdoor air is
. When the Zoneline isfirst turned on you needto
allow time for the room to cool down or warm up.
, Set the vent control to the CLOSE position.
entering the room.
Dust is on the surface
of the heating element.
The heat pump is not producing hot air.
, This can cause a "burning" odor at the beginning of
the heating operation. This odor should quickly fade.
, Thisis normal.The heat pump will produce warm air
but not as hot as air produced when the higher-cost electric heat is used.
The fan switch may be set at continuous fan.
This causes the fan to blow room temperature air even when the compressor or heater cycles off.
The continuous air movement provides better overall temperature control.
The heat pump alone produces air that feels
cooler than desired.
Usethe Electric Heat Option. This turns off the heat
pump and warms with electric heat only.
NOTE:Use of this option will result in increased energy consumption.
23
Things that are normal.
Normal Operating Sounds
PING!
i
\\, , //J
You may hear a pinging noisecaused bywater being picked up and thrown against the condenser on rainy
days or when the humidity ishigh. This designfeature helps remove moisture and improve efficiency.
"5
"CLICK"
DRIP
6
WHIR!
._.,x)\e"
You may hear relays click when the controls cycle on and off or are adjusted to change the room temperature.
Water will collect in the base panduring high humidity or on rainy days.The water may overflow and drip
from the outdoor sideof the unit.
Theindoor fan runscontinuously when the unit is operating in the cooling mode,unless the fan switch
behind the case front panel isset at fan cycle (up). Thiswill cause the fan to cycle on and off with
the compressor. You may also hear a fan noise stop and start.
You may notice a few minutes delay in starting if you try to restart the Zonelinetoo soon after turning it off or if you adjust the thermostat right after
the compressor has shut off.This isdue to a built-in restart protector for the compressor that causes
a 3-minute delay.
Duringthe defrost cycle,both indoor and outdoor
fans stop and the compressor will operate in the cooling mode to remove frost from the outdoor coil. After defrost, the unit will restart in electric heat to
quickly warm the room to the desired comfort level.
24
COMPRESSOR
PROTECTION
Toprotect the compressor and prevent short cycling, the unit is designed to run for a minimum of 3 minutes
after the compressor starts at anythermostat setting.
Notes.
GEAppliances.c0m
-(3
c(D
oo Q
@.
tn
-m
c N
0 09
0
d)
-m
o
tn
-m
c N
0 09
c(D
c(D
-(3
-(3
N Q
@
Q Q_
N d)
Q
-4
-m
0 c CY
d) tn
_-7 0
0
-4 09
N 0
tn r
3
d) O0
C
0
25
m
co Notes.
E 0
,i
u
L
co t-
o
u')
co
c-
O
,i
u
L
co ci
r-
,i
o
L
c_
O
O3
C-
,i
c- o
(D
i
u
-o c- o
o
u
co
.i
F--
r'-
,i
O O ci
co (D
i
O
L
F--
O Q_
U3
L
E
co c- O
u
26
Vertical Zoneline Warranty.
All warranty service provided by our Factory Service Centers, or an authorized Customer Care®technician. To schedule service, on-line, visit
us at GEAppliances.com,or call 800.GE.CAREf(800.¢32.2737).For service in Canada, contact Gordon Williams Corp.at 2_.888.209.0999.Pleasehave serial number and model number available when calling for service.
For The Period Of:
One Year From the date of the
original purchase
Five Years From the date of the
original purchase
Five Years From the date of the
original purchase
What GE Will Not Cover:
[] Service trips to your site to teach you how to use []
the product.
[] Improper installation, delivery or maintenance.
If you have an installation problem, or if the air
conditioner isof improper cooling or heating capacity [] for the intended use, contact your dealer or installer. You are responsible for providing adequate electrical
connecting facilities.
[] In commercial locations, labor necessary to move
the unit to a location where it is accessible for service []
by an individual technician.
[] Failure or damage resulting from corrosion due []
to installation in an environment containing corrosive
chemicals. []
[] Replacement of fuses or resetting of circuit breakers. [] [] Filters.
GE Will Replace: Any part of the Zoneline which fails due to a defect in materials or workmanship. During this
limited onecvear warrantv, GEwill also provide,free of charge, all labor and related service
to replacethe defective part. Anv part of the sealed refrigerating system (thecompressor, condenser, evaporator
and all connecting tubing) which fails due to a defect in materials or workmanship. During this four-year limited additional warranty, GEwill also provide,free of charge,
all labor and related service to replace the defective part. Forthe second through the fifth year from the date of original purchase,GEwill replace
certain parts that fail due to a defect in materials or workmanship. Partscovered are fan motors, switches,thermostats, electric resistance heater, electric resistance heater protectors,
compressor overload, solenoids,circuit boards, auxiliary controls, thermistors, frost controls, ICRpump, capacitors, varistors and indoor blower bearing. Duringthis fourcvear limited
additional warranty, you will be responsiblefor any labor or on-site service costs.
Failure of the product resulting from modifications
to the product or due to unreasonable use including failure to provide reasonable and necessary
maintenance. Failure or damage resulting from corrosion due
to installation in a coastal environment, except for models treated with special factory-applied
anti-corrosion protection asdesignated in the model number.
Damage to product caused by improper power supply
voltage, accident, fire, floods or acts of God.
Incidental or consequential damage caused by possible defects with this air conditioner.
Damage caused after delivery. Product not accessible to provide required service.
Stapleyour receipt here.
Proof of the original purchase
date is needed to obtain service
under the warranty.
EXCLUSIONOFIMPLIEDWARRANTIES-Yoursole and exclusive remedy is product repair as provided in this Limited Warranty. Any implied warranties, including the implied warranties of merchantability or fitness for a particular purpose, are limited
to oneyear or the shortest period allowed by law.
i
This warranty is extended to the original purchaser and any succeeding owner for products purchased for use within the USA and Canada. If the product is located in an area where service by a GEAuthorized
Servicer is not available, you may be responsible for a trip charge or you may be required to bring the product to an Authorized GE Service location for service. In Alaska, the warranty excludes the cost of shipping or service calls to your site.
Some states or provinces do not allow the exclusion or limitation of incidental or consequential damages. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state or province to province. To know what your legal rights are, consult your local, state or provincial consumer affairs office or your state's Attorney General.
Warranton General Electric Company. Louisville, KY 40225
27
Consumer Support.
GEAppliances Website G EAppliances.corn
Have a question or need assistancewith your appliance?Try the GEAppliancesWebsite 24 hours a day, any day of the year! Forgreater convenience and faster service,you can now download Owner's Manuals,
order parts or even schedule service on-line.
ScheduleService
Expert GErepair service isonly one step away from your door. Geton-line and schedule your service at your convenience any day of theyear! Or call 800.GE.CARES(800.432.2737)during normal businesshours.
Forservice in Canada,contact Gordon Williams Corp.at 1.888.209.0999.
G EAppliances.corn
Real Life Design Studio GEAppliances.com
GEsupports the Universal Designconcept-products, servicesand environments that can be used by people of all ages,sizesand capabilities. We recognizethe needto designfor a wide range of physical and
mental abilities and impairments. Fordetails of GE'sUniversalDesignapplications, including kitchen design ideasfor people with disabilities,check out our Website today. Forthe hearing impaired, pleasecall 800.TDD. GEAC(800.833.4322).
Partsand Accessories
Individuals qualified to servicetheir own appliances can have parts or accessoriessent directly to their homes (VISA,IViasterCardand Discovercards are accepted).Order on-line today, 24 hours every day or by phone
at 800.626.2002 during normal businesshours.
Instructions contained in this manual cover procedures to be performed by any user. Other servicing generally should be referred to qualified service personnel. Caution must be exercised, since improper
servicing may cause unsafe operation.
G EAppliances.corn
Contact Us
If you are not satisfied with the service you receivefrom GE,contact us on our Website with all the details including your phone number, or write to: GeneralManager, Customer Relations
GEAppliances,Appliance Park Louisville,KY40225
GEAppliances.corn
Register Your Appliance GEAppliances.corn
Register your new appliance on-line--at your convenience! Timely product registration willallow for enhanced
communication and prompt service under the terms of your warranty, should the need arise. You may also mail in the pre-printed registration card included in the packing material.
Loading...