GE AZ85W18DACM2, AZ85H18EACM2, AZ85H18DACM3, AZ85H18DACM2, AZ85E18EACM2 Owner’s Manual

...
GEAppliances.com
O1
@
®I
N
U
0
0_
Operating Instructions
Controls--Dip Switches ......... 3-5
Controls--Terminal
Connections ................... 6, 7
On/Off Switch .................... 8
Ventilation Control ............... 8
Care and Cleaning
Air Filters ........................ 9
Base Pan ........................ 9
Exhaust Coils..................... 9
Installation Instructions
Preparation ..................... 10
Electrical Supply .............. 11-13
Installing the Zoneline ........ 14-21
Servicing ........................ 22
Troubleshooting Tips ....... 25
Normal Operating Sounds....... 24
Consumer Support
Consumer Support ...... Back Cover
Warranty ....................... 27
Cool Only, Heat/Cool and
Heat Pump Hodels
8500 Series
Write the model and serial numbers here:
Model #
!
Serial #
You can find them on a label on the front case panel.
Printed in China TINSEA612JBRZ 49-7639-1 03-12 GE
IMPORTANT SAFETY INFORMATION.
READ ALL INSTRUCTIONS BEFORE USING.
A WARNING!
Riskof electric shock. Can cause injury or death. For your safety, the information in this manual must be followed to minimize the risk of fire, electric shock or personal injury.
SAFETYPRECAUTIONS
[]
This Zoneline must be properly installed in accordance with the Installation
Instructions before it is used. See the Installation Instructions in the back of this manual.
[]
Replace immediately all electric service cords that have become frayed or otherwise damaged. A damaged power supply cord must be replaced with a new power supply cord obtained from the manufacturer and not repaired.
Do not use a cord that shows cracks or abrasion damage along its length
or at either the plug or connector end.
[]
Product must be operated with the electrical plug supplied with the
product. Do not replace the electrical
plug supplied with the product.
[]
If the receptacle does not match the plug, the receptacle must be changed out by a qualified electrician.
[] Unplug or disconnect the Zoneline
at the fuse box or circuit breaker before making any repairs.
NOTE: We strongly recommend that any servicing be performed by a qualified
individual. [] All air conditioners contain refrigerants,
which under federal law must be
removed prior to product disposal. If you are getting rid of an old product
with refrigerants, check with the
company handling disposal about
what to do.
[]These R410A Air Conditioner Systems
require contractors and technicians to use tools, equipment and safety standards approved for use with this refrigerant. DO NOT use equipment certified for R22 refrigerant only.
READAND FOLLOW THISSAFETYINFORMATION CAREFULLY.
SAVE THESE INSTRUCTIONS
Controls-dip switches. GEAppliances.com
Controls-Dip Switches
Thedip switch controls are located behind the front case panel,through an opening
on the front of the unit. Toaccessthe dip switches, remove the front
case panel by removing the filter, taking out the four front screws, the upper two screws from
the top of the panel and the shipping screws on each side, if present. (Discard the four side shipping
screws,if present).
NOTE:Theowner is responsiblefor setting
the appropriate dip switches and connecting terminals.
Side
---._shipping screw
,/
TL3 (C)(Temp. Limit 3-Cool) TL2 (C)(Temp. Limit 2-Cool) TL! (C)(Temp. Limit !-Cool)
ALL 12R(All Electric Heat)(Heat-pump models only)
FREEZ S (Freeze Sentinel)
CONST FAN (Constant ON Fan)
All Electric Heut (Heat pump models only)
When this switch isenabled (UP),heat pump operation is locked out, causing the unit to provide only electric resistance heat.
fL! (H)(Temp. Limit !-Heat)
_TL2 (H)(Temp. Limit 2-Heat)
_TL3 (H)(Temp. Limit 3-Heat)
OCCUPIED(OccupancySensor)
(BBBBBBiImBBBBBIooO °
hALL FR(AllElectricHeat)
Controls-dip switches.
Freeze Sentinel (Requiresroom air sensor kit-RAVRPtS)
When this switch isenabled (UP),itturns OFF the freeze sentinel protection feature. With the
switch disabled (DOWN),the freeze sentinel is activated which automatically provides heat
without userinterface. Thishelpsto prevent plumbing damage by turning the heater
and fans ON at 4! ° F and OFF at 46° F.
Constant ON Fan
When this switch isenabled (UP),it allowsthe fan to run continuously.
Occupancy Sensor (FieldSupplied)
[BBBBBBI
IBBBBBBI°°L_°
I
FREEZES (Freeze Sentinel)
IBBBBBBIIBB BBBI
J
CONST FAN (Constant
ONFan)
When this switch isenabled (UP),it allowsthe unit to utilize an infrared motion sensor and a door
switch for occupancy detection. Thisfeature combined with field devicesautomatically cycles
the unit between normal operation and a preset energy management operation.
Duct
Theduct select function allows the indoor fan to be operated at two variable fan speeds.
When this switch isenabled (UP),the unit automatically selectseither high or middle fan speed (forlonger ductwork applications).When
set in the down position,the unit isautomatically operated in either the middle or low fan speed
(forshorter ductwork applications).
iBBBBBBiiBBBmBBI
I
OCCUPIED
(OccupancySensor)
iBBBBBBiiBBBBBBioo_o
J
DUCT
(BlowerFan)
Temperature Limiting (Requiresroom air sensorkit-RAVRMS)
Temperature limiting can reduce energy costs by limiting the lowest temperature that can be
set for cooling and the highest temperature that
of auxiliary controls, Thefirst three switches are usedto select the cooling limits.Thenext three
switches are used to control the heating limits. can be set for heating. Temperature limiting is controlled by switches 1-6 on the top block
GEAppliances.com
TL3(C)(Temp. Limit S-Cool) TL2(C)(Temp. Limit 2-Cool) TL! (C)(Temp. Limit Z-Cool)
Temperature limiting during COOL mode
(all temperatures shown in °F)
UP DOWN Minimum Maximum
NONE !, 2, 3 60 ° 85 °
! 2, 3 64° 85°
1, 2 3 66 ° 85 °
2 !, 3 68 ° 85 °
2,3 ! 70 ° 85 °
1, 2, 3 NONE 72° 85 °
!, 3 2 74 ° 85 °
3 1, 2 76° 85 °
[L! (H)(Temp. Limit !-Heat)
_TL2 (H)(Temp. Limit 2-Heot)
_TL3 (H)(Temp. Limit 3-Heot)
Temperature limiting during HEAT mode
(all temperatures shown in °F)*
UP DOWN Minimum Maximum
NONE 4, 5, 6 60° 85 °
4 5, 6 60° 80 °
4, 5 6 60° 78 °
5 4, 6 60° 76 °
5,6 4 60 ° 74 °
4, 5, 6 NONE 60° 72 °
4, 6 5 60° 70 °
6 4, 5 60° 65 °
* Not opplicable to Cool-Only models
5
Controls-terminal connections.
Controls-Terminal Connections
Theterminal connections are located behind the front case panel through an opening
on the front of the unit. Toaccessthe terminal connections, remove
the front panel by removing the filter, taking out the four front screws, the upper two screws from the top of the panel and the shipping screws on
each side,if present.(Discardthe four sideshipping screws,if present.)
Insertthe building hook-up wires into the bottom of the terminals and tighten screws securely
to make the desired connections. Routethe wires from the terminal connections
through the unit wire guides and out through the case wire guide.
NOTE:Theowner isresponsible for setting the appropriate dip switches and connecting
terminals.
A CAUTION:
Improper CDCwiring may damage the Zoneline electronics or cause erratic Zoneline operation.
Nocommon busing ispermitted. Aseparate wire pair must be run from each separate controlling
switch to each individual Zoneline.
through wire guides
connections
e-_l n le_ I _ Io s _ _ _ _ _
_:< g o X'_zo zo >+, ,_+'
_ "< "< _ _Common-Ground
Room Air Sensor
Motion Sensor
Door Sensor
Central Desk Control
Room Air Sensor (Requiresroom air sensorkit - RAVRMS)
When connected, the room air sensor will allow utilization of the temperature limiting and freeze
sentinel features. NOTE:If GEthermostat RAK148D1,RAK148P1
or RAK164D1,RAK164P1is used with the unit, the room sensor kit isnot needed for temperature
limiting since this feature isincorporated in the thermostats.
Hydronic Heating (RequiresHydronicHeating Kit - RAVHWff,RAVHW2or RAVHW3)
Requiredconnections for hydronic heating kit. NOTE:R,W,Cterminal connections will
alsobe connected to the remote thermostat ifapplicable.
ommIo+ I++ I _ Io =+ _ +
L_+ _ "< "< #: u _ 8
RoomAir Sensor
O+:le+ e+ + _ o, + >_+ + o_
+_ + o +ii,=+.+°++°_+_+._+=++
White-Heater Yellow-Compressor
Black-Reversing Valve Green-High Speed Fan Green-Low Speed Fan
Red-24V AC only
L '! r
HydronicHeating
t
Notion Sensor (Obtainedlocally)
TheOccupancy Sensor dip switch must be in the up position to usethis feature.
When connected, the wall mounted motion sensor will detect motion in the room and automatically cyclethe unit between normal operation and
energy management operation. Thedoor and motion sensors work together
to automatically cyclethe unit between normal operation and energy management operation.
Door Sensor (Obtainedlocally)
TheOccupancy Sensor dip switch must be in the up position to use this feature.
When connected, the door sensorwill detect when the door in the room is opened or closed.
Thisfeature must beused in conjunction with the motion sensor.
Thedoor and motion sensors work together to automatically cyclethe unit between normal
and energy management operations.
GEAppliances.com
L_ _ ,,< ,,<_ o _ o
Notion
Sensor
e+;le m le o I _ I_ s _ _ _ _ +
+"°9_ oorfol+°
Central Desk Control
When connected, the unit lock-out is released and it can be turned ONor OFFwith a switch
located at the Central DeskControl.A separate wire pair must be run from each separate
controlling switch to each individual Zoneline. A 24VACcircuit powers the CDCsystem. Noexternal power isrequired.
Remote Thermostat
Theunit will be controlled by u remote thermostat.
IMPORTANT:
TheZoneline thermostat connections provide 24V AConly.
If using a digital/electronic wall thermostat,
you must set it to the 24VACsetting. Seethe
Installation Instructions for the wall thermostat.
NOTICE:
Damage to a wall thermostat or to the Zonelineelectronics can result from improper
connections. Exerciseextra attention when connecting blue and black wires. No line voltage connections should be made to any circuit
in the thermostat. Isolate all wires in building from line voltage.
B®®d+®®®®®®®®®®
e_;Io+ le ° I _ I_ s _ d _ _ o_
"" _ g L_ _e::r aii::k _ itlol °
emile+ Io_ I _ Io _ _ +
= _ ,,< ,,< ore°_ o
I I
Red-24VAConlyJ I
Green-LowSpeedFan
Green-HighSpeedFan
Black-ReversingValve
Yellow-Compressor
White-Heater
Common-Ground
__J
Other features ofyour Zoneline.
On/Off Switch
Theunit on/off switch islocated on the front of the Zoneline.
Toturn on the unit, pressthe top of the switch in. Toturn off the unit, pressthe bottom
of the switch in. NOTE:The on/off switch does not remove power
from the unit.
Ventiletion Control
Theventilation control lever is located on the left sideof the Zoneline unit, behind the front case panel.
Toaccessthe ventilation control lever,remove the front panel by removing the filter, taking out the four front screws, the upper two screws from
the top of the panel and the shipping screws on each side,if present.(Discardthe four side shipping
screws,if present). When the leverisin the CLOSEposition,only the air
insidethe room iscirculated and filtered. When the leverisin the OPENposition,some
outdoor air will be drawn into the room. This will reduce the heating or cooling efficiency.
Toclose the vent, push the vent lever handle down, pull it forward and lock it up in place.
Toopen the vent, push the vent lever handle down, push it back and lock it up in place.
ON/OFF
switch
Open
g
Vent control (push
lever down and
pull forward or
back to operate)
Energy Tip: Keepthe vent control in the CLOSE position.The room air will be filtered and circulated.
NOTE:Ventilation openings are not intended to be
the source of make-up air for buildingventilation
systems due to the additional heating and cooling loadsgenerated.
I
I
I
About Heet Pumps (onsome models)
Heat pumps can reduce operating costs by exchanging heat from the outside air-even
when the outside temperature is below freezing- and releasing that heat indoors.
Toget the best economic benefit from your heat pump, don't change the room thermostat setting
very often. Raisingthe heat setting 2-3 degrees will cause the Zoneline to use its electric heating
elements in order to reachthe new temperature setting quickly.
Do Not Operate the Air Conditioner (cool mode) in Freezing Outdoor Conditions
Air conditioners are not designed for usewhen freezing outdoor conditions exist.Theymust not be
used in freezing outdoor conditions.
There isa three minute minimum compressor run time at any setting to prevent short cycling.
The indoor fan motor starts before the compressor
and stops after the compressor cyclesoff.
Theelectric heating elements use much
more electricity than heat pumps and cost more to operate.
Care and cleaning. GEAppliances.com
Turn off the Zoneline and disconnect the power supply before cleaning.
Indoor/Outdoor Coils
Theexhaust coils on the Zonelineshould be checked regularly. If they are clogged with dirt
or soot, they may be professionally steam cleaned byyour GEservicecenter.Youwill need to remove
the unit from the case to inspectthe coils because the dirt build-up occurs on the exhaust side.
-- Outdoor coils
Have the coils cleaned regularly.
Drain
Cleanthe drain system regularly to prevent clogging.
Base Pan
In some installations, dirt or other debris may be blown into the unit from the outside and settle
in the base pan (the bottom of the unit).
Air Filters
To maintain optimum performance, change the filter at least every 50 days.
Themost important thing you can do to maintain the Zonelineisto change the filter at least every
30 days. Dirty filters reduce cooling, heating and air flow.
Changing the filter will'.Decreasecost of operation, saveenergy, prevent clogged heat
exchanger coils and reduce the risk of premature component failure.
Insome areas of the United States,a "gel-like"
substance may be present in the base pan. Checkit periodically and clean, if necessary.
Toremove and replace
the filter:
NOTICE: Do notoperate
the Zoneline without the filter in place. Ifa filter becomes torn or damaged, it should be replaced
immediately.
Operating without the filter inplace or with a damaged filter will allow dirt and dust to reach the indoor coil and reduce the cooling, heating,
airflow and efficiency of the unit.
Remove filter
filter
Filter
Replacement filters should be purchased from your local retailer where air conditioner
and furnace accessoriesare sold. Filtersize required is20" x 20" x 1".
Filter
Return air grille Access-panel with
return air grille 9
Loading...
+ 19 hidden pages