GE AZ65H15DAB, AZ65H12DAD, AZ65H07DAB, AZ65H09DAD User Manual

®
Zoneline
Safety Instructions ...........2-4
Operating Instructions
Controls ...........................5
Air Direction. . . . . . . . . . . . . . . . . . . . . . . . 6
To Remove the Room Cover ........6
Ventilation Control .................6
Auxiliary Controls ...............7-11
Remote Thermostat ...............11
Care and Cleaning
Base Pan .........................12
Outdoor Coils .....................12
Room Cover and Case .............12
Ventilation Filter ...................12
Air Filters .........................13
Owner’s Manual and
Installation Instructions
AZ45 AZ65
Español
For a Spanish version of this manual, visit our Website at www.zoneline.com.
Para consultar una version en español de este manual de instrucciones, visite nuestro sitio de internet www.zoneline.com.
Installation Instructions
Preparation .......................14
Replacing an Existing Unit .........15
Electrical Connection ...........16-18
Installing the Zoneline .........19, 20
Optional Drain Kit .................21
Troubleshooting Tips .....22, 23
Normal Operating Sounds .........24
Consumer Support
Ownership Registration ........25, 26
Warranty .........................27
Consumer Support ........Back Cover
Write the model and serial numbers here:
Français
For a French version of this manual, visit our Website at www.zoneline.com.
Pour un version français de ce manuel d’utilisation, veuillez visiter notre site web à l’adresse www.zoneline.com.
Air Conditioners
Model # ___________________
Serial # ____________________
49-7756 02-16 GE
IMPORTANT SAFETY INFORMATION READ ALL INSTRUCTIONS BEFORE USING
SAFETY INFORMATION
This is the safety alert symbol. This symbol alerts you to potential hazards that can kill or hurt you and others. All safety
messages will follow the safety alert symbol and the word “DANGER”, “WARNING”, or “CAUTION”. These words are defined as:
DANGER
Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
WARNING
For your safety, the information in this manual must be followed to minimize the risk of fire or explosion, electric shock, or to prevent property damage, personal injury, or loss of life.
SAFETY PRECAUTIONS
This Zoneline must be properly installed in accordance with the Installation Instructions before it is used. See the Installation Instructions in the back of this manual.
Immediately replace all electric service cords that have become frayed or otherwise damaged. A damaged power supply cord must be replaced with a new power supply cord obtained from the manufacturer and not repaired. Do not use a cord that shows cracks or abrasion damage along its length or at either the plug or connector end.
Unplug or disconnect the Zoneline at the fuse box or circuit breaker before making any repairs.
NOTE: We strongly recommend that any servicing be performed by a qualified individual.
These R410A air conditioning systems require contractors and technicians to use tools, equipment and safety standards approved for use with this refrigerant. DO NOT use equipment certified for R22
refrigerant only.
Replacing an existing unit?
For details, see the Installation Instructions in this manual.
READ AND FOLLOW THIS SAFETY INFORMATION CAREFULLY.
SAVE THESE INSTRUCTIONS
2
CONSIGNES DE SÉCURITÉ IMPORTANTES LISEZ TOUTES LES INSTRUCTIONS AVANT L’UTILISATION
SAFETY INFORMATION
Ce symbole représente une alerte de sécurité. Ce symbole vous avise de dangers potentiels pouvant causer, à vous ou au-
trui, des blessures graves ou fatales. Tous les messages de sécurité seront précédés du symbole d’alerte de sécurité ainsi que des mots « DANGER », « AVERTISSEMENT » ou « ATTENTION ». Ces messages sont les suivants :
DANGER
AVERTISSEMENT
ATTENTION
Signale une situation qui présente un danger imminent et qui, si elle n’est pas évitée, entraînera des bless­ures graves, voire fatales.
Signale une situation qui présente un danger imminent et qui, si elle n’est pas évitée, peut entraîner des bles­sures graves, voire fatales.
Signale une situation qui présente un danger imminent et qui, si elle n’est pas évitée, peut entraîner des bles­sures légères ou modérément graves.
AVERTISSEMENT
Pour votre sécurité, veuillez observer les consignes de ce manuel afin de réduire le risque d’incendie, d’explosion, de choc électrique, de dommages à la propriété ou de blessures, graves ou fatales.
MESURES DE SÉCURITÉ
Avant son utilisation, ce climatiseur Zoneline doit être installé correctement en conformité avec les instructions d’installation. Consultez les instructions d’installation au dos de ce manuel.
Remplacez immédiatement tous les cordons électriques usés ou autrement endommagés. Un cordon électrique endommagé ne doit pas être réparé, il doit être remplacé par un cordon neuf acquis auprès du fabricant. N’utilisez pas un cordon qui présente des fissures ou des marques d’abrasion sur sa longueur, sa fiche ou sa connexion.
Vous remplacez un climatiseur existant?
Pour de plus amples renseignements, veuillez consulter les instructions d’installation de ce manuel.
Débranchez le climatiseur Zoneline ou coupez le courant à la boîte de fusibles ou au disjoncteur avant d’effectuer une réparation.
REMARQUE : Nous recommandons vivement que les réparations soient effectuées par une personne qualifiée en la matière.
Les outils, les équipements et les normes de sécurité utilisés par les entrepreneurs et les techniciens doivent être approuvés en fonction du fluide frigorigène dont le système de climatisation R410A du Zoneline est équipé. N’UTILISEZ PAS d’équipements
certifiés relativement au fluide frigorigène R22 seulement.
VEUILLEZ LIRE ET OBSERVER CES CONSIGNES DE SÉCURITÉ ATTENTIVEMENT.
CONSERVEZ CES INSTRUCTIONS
3
INFORMACIÓN IMPORTANTE DE SEGURIDAD LEA TODAS LAS INSTRUCCIONES ANTES DE USAR
INFORMACIÓN DE SEGURIDAD
Éste es el símbolo de alerta de seguridad. El mismo alerta sobre potenciales riesgos de muerte o lesiones tanto para usted
con para otras personas. Todos los mensajes de seguridad estarán a continuación del símbolo de alerta de seguridad y con la palabra “PELIGRO”, “ADVERTENCIA” o “PRECAUCIÓN”. Estas palabras se definen como:
PELIGRO
Indica una situación de riesgo que, si no se evita, resultará en la muerte o en lesiones graves.
ADVERTENCIA
Indica una situación de riesgo que, si no se evita, puede resultar en la muerte o en lesiones graves.
Indica una situación de riesgo que, si no se evita, puede resultar en lesiones menores o moderadas.
PRECAUCIÓN
ADVERTENCIA
Para su seguridad, se debe seguir la información de este manual para minimizar el riesgo de incendio o explosión, descargas eléctricas, o para evitar daños a la propiedad, lesiones personales o la muerte.
PRECAUCIONES DE SEGURIDAD
Antes de iniciar su uso, el acondicionador de aire Zoneline debe instalarse correctamente según las Instrucciones de instalación. Ver las Instrucciones de instalación en la parte trasera de este manual.
Reemplace inmediatamente todos los cables eléctricos que se haya pelado o que se hayan dañado de alguna otra manera. Un cable de corriente dañado no debe repararse, sino que debe ser sustituido por uno nuevo que se adquiera del fabricante. No use un cable eléctrico que muestre evidencias de deterioro o daños de abrasión en su superficie o en cualquiera de sus enchufes o extremos.
Desenchufe o desconecte el Zoneline desde la caja de fusibles o el disyuntor antes de realizar cualquier tipo de reparación.
NOTA: Recomendamos enérgicamente que cualquier servicio llevado a cabo en este equipo lo realice un individuo calificado.
Los sistemas de acondicionador de aire R410A requieren que los contratistas y técnicos utilicen herramientas, equipamiento y normas de seguridad aprobadas para su uso con este refrigerante.
NO utilice equipamiento certificado sólo para refrigerante R22.
¿Desea reemplazar una unidad ya instalada?
Para más detalles, ver las Instrucciones de instalación en este manual.
LEA Y SIGA ESTAS INSTRUCCIONES DE SEGURIDAD CUIDADOSAMENTE.
GUARDE ESTAS INSTRUCCIONES
4
About the controls on your Zoneline
Controls
Temp Control
The temp control is used to maintain the room temperature. The system will cycle on and off to keep the room at the same level of comfort.
Press the + pad to raise the temperature. Press the - pad to lower the temperature. NOTE: The display shows the set temperature, not the room
temperature.
Fan, Mode and Operation Control
)$1³Sets the fan operation for HIGH or LOW. 02'(³&22/³For cooling
)$1³For fan-only operation +($7³For heating
2))³Turns the unit off. Power remains connected to the
Zoneline. The Freeze/Heat Sentinel features still function if active. See the Freeze/Heat Sentinel section on page 8.
Quick Heat Recovery
Activates each time the thermostat is switched from OFF or COOL mode to HEAT mode. Electric heaters are energized until
the thermostat set point is reached. On heat pump models, the heat pump operation will resume at the next call for heat.
86(:$//7+(50267$7³ This LED will light up when the unit is controlled by a wall thermostat. See page 9 for details.
Control Lock Out
The control panel can be locked out to prevent users from changing the operation mode of the unit.
While the unit is in the desired operating mode, press and hold the DISPLAY SHOW/HIDE button for 10 seconds to lock the control and the desired setting. Any key press after that will result in the mode LED and temperature that was locked to flash 5 times and then go dormant.
To unlock the control lock out feature, press the DISPLAY SHOW/ HIDE button for 10 seconds to unlock and resume normal operation.
NOTE: The temperature display will flash if the control panel is locked (see Control Lock Out section).
NOTE: When switching between modes, it may take several minutes to completely change operation.
About Your Heat Pump (AZ65 only)
Heat pumps can save money by removing heat from the outside
DLU³HYHQZKHQWKHRXWVLGHWHPSHUDWXUHLVEHORZIUHH]LQJ³DQG
releasing that heat indoors. To get the best energy performance from your heat pump, don’t
change the room thermostat by more than one degree at one time. Raising the heat setting 2–3 degrees will cause the Zoneline to use its electric heating elements in order to reach the new temperature setting quickly.
The electric heating elements use more electricity than heat pumps and cost more to operate.
There is a 3-minute minimum compressor run time at any setting to prevent short cycling.
The fans start before the compressor and stop after the compressor cycles off.
When the outdoor temperature is lower than 25°F, heat is provided by the electric heater instead of by the heat pump.
5
Other features of your Zoneline
To Remove the Room Front
Additional controls are located behind the room cover. To remove: Pull out at the bottom to release it from the holding
tabs on the sides (1). Then lift up (2).
Air Direction
To change the air direction, remove the room cover. Remove the 4 louver screws that hold the louver insert in place. Rotate the louver 180°, reinstall and replace the screws and the room cover.
To replace: Align and place the top rail of the room cover over the chassis (1). Push inward at the bottom until it snaps into place (2).
Factory Shipped Louver Orientation
Louver screws
(airflow @ 45° from horizontal)
Ventilation Control*
NOTE: Two shipping screws must be removed from the vent door
before use. See the Installation Instructions in the back of this manual. If you do not plan to use the ventilation feature, leave the two screws in place.
The ventilation control lever is located at the lower left side of the Zoneline unit, behind the room cover. The position of the lever can be adjusted with the wing nut.
When set at the closed position, only the air inside the room is circulated and filtered.
When set in an open position, some outdoor air will be drawn into the room. This will reduce the heating or cooling efficiency.
Energy Tip: Keep the vent control in the closed position to prevent unconditioned air from entering the room.
* Not on Make Up Air Module
6
Modified Louver Orientation
(airflow @ 85° from horizontal)
Remove the shipping screws (if operation is desired)
Vent Control
Auxiliary controls on your Zoneline
$X[LOLDU\&RQWUROV³$X[6HW%XWWRQ
While the unit is preset to what most customers prefer, the auxiliary controls located behind the room cover, below the control panel.
Remove the room cover. See the To Remove the Room Cover section.
If the owner modifies the auxiliary controls it is then the owner is responsible for ensuring the auxiliary controls are set to the desired function. There are 10 different modes that can be set using the auxiliary set button.
To change operating or set up parameters, first go to the mode control and turn the unit off, then, press the red AUX SET button (“AU” appears on the display).
Press the mode button on the control pad until the first digit in the display shows the number corresponding to the mode you are choosing and the correct HEAT/COOL LED is lit.
Press the +/- button to make the mode setting selection where applicable (shown in the second digit of the display).
Temperature Display
Red Aux Set Button
MODE 1
Press the red AUX SET button to lock in the selection, and exit AUX SET mode.
(AZ65 Only)
(AZ65 Only)
6PDUW)DQ³&RROLQJ+HDWLQJ
Press MODE until a 1 appears in the first digit of the display for Smart Fan cool mode. The COOL LED light on the main control will be on. To change to heat mode, press MODE again. The HEAT LED light on the main control will be lit.
Press the - pad to set the indoor fan to cycle on/off in the heating or cooling mode selected “ .”
Press the + pad to set the indoor fan to run continuously in the heating or cooling mode selected “ .”
Press AUX SET to confirm your selection and exit AUX SET mode, or press MODE to continue setting other functions.
The default setting for Mode 1 is as follows: Cooling: Continuous (ON) Heating: Cycle (OFF)
*Note: In cyclic cooling mode, the indoor fan will activate occasionally to verify air temperature in the room. In cyclic heating mode, the fan will continue to operate for several seconds after the heating function has stopped in order to increase unit efficiency.
7
Auxiliary controls on your Zoneline
MODE 2
MODE 3
Fahrenheit / Celsius
This feature allows the individual to switch the temperature units between Fahrenheit and Celsius on the display.
Press MODE until a 2 appears in the first digit of the display for Fahrenheit/Celsius mode.
Press the - pad to select Celsius or the + pad to select Fahrenheit. The individual will see an F for Fahrenheit or a C for Celsius in the second digit of the display based on the selection.
The default setting for Mode 2 is Fahrenheit.
Freeze Sentinel/Heat Sentinel
With power to the unit and Freeze Sentinel activated, the unit automatically provides heat without user interface. This prevents potential plumbing damage by turning the heater and indoor fan ON at 41ºF and then OFF once the room temperature reaches 46ºF.
When Heat Sentinel is activated, the unit automatically provides cooling without user interface. This prevents an excessively hot room by turning the air conditioner ON at 85ºF and then OFF once the room temperature reaches 80ºF.
Press MODE until a 3 appears in the first digit of the display for Freeze Sentinel mode. The COOL LED light on the main control will be on. Press MODE again to change to the Heat Sentinel. The HEAT LED light on the main control will be on. Press the - pad for OFF “ “ or the + pad for ON “ “. This is shown in the second digit of the display. Press AUX SET to lock in your selection, and exit AUX SET mode, or press MODE to continue setting other functions.
In the default setting for Mode 3, Heat Sentinel is off,
Freeze Sentinel is on. NOTE: These functions are active whenever the unit is
plugged in, even if the unit is turned off.
° F
Freeze Sentinel OFF
Freeze Sentinel ON
Heat Sentinel OFF
Heat Sentinel ON
° C
MODE 4
8
Constant ON Fan
Press MODE until a 4 appears in the first digit of the display to set the fan to run continuously at high speed - even if the unit is turned off.
Press the - pad for OFF “ “ or the + pad for ON “ .” This is shown in the second digit of the display.
Press AUX SET to lock in your selection and exit AUX SET mode, or press MODE to continue setting other functions.
The default setting for Mode 4 is OFF.
Constant
Fan OFF
Constant
Fan ON
Auxiliary controls on your Zoneline
MODE 5
Temperature Limiting
Temperature limiting is a feature that reduces energy costs by limiting the lowest temperature that can be obtained in cooling and the highest temperature that can be obtained in heating.
Press MODE until a 5 appears in the first digit of the display for Temperature Limiting cool mode. The COOL LED light on the main control will be lit. To change to heat mode, press MODE again and the HEAT LED light on the main control will be lit.
To set the temperature limits, press the + or - pad . The second digit of the display will be between 0 and 7 depending on the limit you want to set. The chart shows the limits available. Press AUX SET to lock in your selection and exit AUX SET mode, or press MODE to continue setting other functions.
 7HPSHUDWXUHOLPLWV³&RRO 7HPSHUDWXUHOLPLWV³+HDW
0 = 60°F to 85°F 0 = 60°F to 65°F 1 = 64°F to 85°F 1 = 60°F to 70°F 2 = 66°F to 85°F 2 = 60°F to 72°F 3 = 68°F to 85°F 3 = 60°F to 74°F 4 = 70°F to 85°F 4 = 60°F to 76°F 5 = 72°F to 85°F 5 = 60°F to 78°F 6 = 74°F to 85°F 6 = 60°F to 80°F 7 = 76°F to 85°F 7 = 60°F to 85°F
The default setting for Mode 5 is as follows: Cool: 2 (66ºF to 85ºF) Heat: 5 (60ºF to 78ºF)
Temperature Limiting Cool – Limit 2
Temperature Limiting Heat – Limit 5
MODE 6
MODE 7
Use Wall Thermostat
Setting this mode to ON will allow the unit to operate with a Class 2 Remote Control Wall Thermostat.
Press MODE until a 6 appears in the first digit of the display for Class 2 mode.
Press the + pad to turn the option OFF “ .” Press the
+ pad to turn this option ON “ ”. This is shown in the
second digit of the display. Press AUX SET to lock in your selection and exit AUX SET mode, or press MODE to continue setting other functions.
The default setting for Mode 6 is OFF. When this mode is active, the display will show “Use Wall
Thermostat” when any key is pressed.
Duct Mode
This setting is used when the unit is installed with a duct adapter kit. If the unit is ducted, the Duct Mode needs to be set to ON. This increases the fan speed to ensure proper circulation.
Press MODE until a 7 appears in the first digit of the display. Press the + or - pad to set this switch to OFF “ “ or ON “ .” This is shown in the second digit of the display. Press AUX SET to lock in your selection and exit AUX SET mode.
For Model AZ65, press MODE to continue setting other functions. Pressing MODE on Model AZ45 will return you to AUX SET mode and an “AU” will appear in the display.
The default setting for Mode 7 is OFF.
Class 2 OFF
Duct Mode OFF
Class 2 ON
Duct Mode ON
9