AZ55H12D—GE Zoneline® Premium Series Heat Pump Unit
Wall Case Dimensions
Maximum Cord Extension (in inches)
RAB71 Wall Sleeve
Heavy-gauge galvanized steel, with insulation.
A – 42", B – 13-3/4", C – 16"
RAB77 Wall Sleeve
Molded SMC fiberglass-reinforced polyester compound.
A – 42-1/8", B– 13-7/8", C – 16-1/4
230/208 Volt Line Cord Connected Units
Line Cord
Kit
RAK3153 8,600/7,100 2,550/2,090 11.6/10.6 15
RAK3203 11,700/9,600 3,450/2,820 15.5/14.1 20
RAK3303 17,000/13,900 5,000/4,090 22.3/20.3 30
230/208 Volt Sub-Base Connected Units
Sub-Base
RAK204D15P 8,600/7,100 2,550/2,090 11.6/10.6 15
RAK204D20P 11,700/9,600 3,450/2,820 15.5/14.1 20
RAK204D30P 17,000/13,900 5,000/4,090 22.3/20.3 30
Specification Revised 4/06
390592
Electric Heat
(Btuh)
Electric Heat
(Btuh)
Electric
Heater Watts
Electric
Heater Watts
Electric
Heat Amps
Electric
Heat Amps
Min. Circuit
Protection
Min. Circuit
Protection
Wall Opening Dimensions
Add 1/4" to A and C dimensions for all cut-out size.
RAB71 16-1/4" Min. H x 42-1/4" Min. W
RAB71 available in 16", 24", 28" and 31" depths
RAB77 16-1/2" Min. H x 42-3/8" Min. W
(Amps)
(Amps)
Electrical Wiring
All wiring, including installation of receptacle, must be made in
accordance with local electrical codes and regulations.
Note: Aluminum wiring may pose special problems – consult
a qualified electrician.
Grille Options
Stamped Aluminum Grille – RAG60
Exterior Architectural Louvers Durable Polycarbonate:
RAG61 or RAG64 (Beige) RAG63 or RAG66 (Bittersweet)
RAG62 or RAG65 (Maple) RAG67 (Extruded Aluminum)
Retrofit Kits:
RAK901L – Wall Case Insulation for use with heat pumps.
RAK40 – Deflector Kit to adapt chassis for use with existing
exterior architectural louvered grilles.
Ducted Applications
2800 and 3800 series can be used with ductwork to heat or
cool more than one room. RAK6052 Duct Adaptor is applied
to top of case over air discharge/RAK601 Duct Extension is
applied to right or left of adaptor. Locally fabricated ductwork
may be added to extend to maximum recommended distance
of 15 feet.
Electrical Connection
230/208 volt units may be plugged into a receptacle. 265 volt
units are provided with a junction box and require direct
connection. (NEC Requires 265V Direct Connection) See
Architects and Engineers Design Data Manual for electrical
connection information including use of sub-base for direct
connected units. Installation must comply with local electrical
codes and regulations.
Power Connection kits required on all Zoneline chassis.
For answers to your Monogram,® GE Profile™ or
GE® appliance questions, visit our website at
ge.com or call GE Answer Center® service,
800.626.2000.
GE Appliances
AZ55H12D—GE Zoneline Premium Series Heat Pump Unit
Features and Benefits
• Cooling with Heat Pump and Electric Heat Back-up
• 230/208V Model
• 11,800/11,600 BTUH (Cooling)
• 10,900/10,700 BTUH (Reverse Cycle Heat)
• 10.9 EER/3.3 COP
• 3.6 Dehumidification (pts/hr)
• 330/310 CFM Indoor Fan
• Electronic Microcomputer Controls
• TactileTouch Pad Controls with LED
• Solid State Thermostat Control
• Up-Front Filters For Easy Access and Cleaning
• Two Fan Motors For Indoor and Outdoor Section to Assure Quiet Operation
• Simultaneous Supplemental Heat Allows Unit to Decide If BOTH Heat Pump
and Electric Heat are Needed For Desired Room Temperature
• Reverse Cycle Defrost By Monitoring Operating Conditions
• Hidden Manual Vent Control For Fresh Air Introduction
• Hidden Fan Cycle Switch
• Freeze Sentinel
• Staged Heating
• Electronic 7-Step Temperature Limiting to Prevent Overcooling or Overheating
of Room
• Remote Control Compatibility For Wall-Mounted Thermostats
• Model AZ55H12DAB - Base Model
• Model AZ55H12DAD - Internal Condensate Removal System
™
Protects Unoccupied Rooms Against Freeze-Up
Specification Revised 4/06