Safety Instruc_tions ........... 2
Operating Instructions
Air Direction ................ 4
Auxiliary Controls .......... 5-9
Controls .................... 3
To Remo_e the Room Cabinet . .4
Vent Control ................ 4
Care and Cleaning
Air Filters .................. 11
Base Pan .................. 10
Outdoor Coils .............. 10
Room Cabinet and Case ...... 10
Vent Filter ................. 10
Installation Instruc_tions
Electrical Supply ......... 14-17
Installing the Zoneline .... 18, 19
Optional Drain Kit .......... 20
Preparation ................ 12
Replacing an Existing Unit? . . .13
Troubleshooting Tips .... 21,22
Normal Operating Sounds .... 23
ge.com
Heat/Cool Modal 2800
Heat Pump Model 3800
Espa_ol
For a Spanish version of this
manual, visit our _Yebsite at
Be.com.
Para consultar una version
en espaflol de este manual
de instrucciones, visite
nuestro sitio de internet
w_v.GEAppliances.com.
Fran_aise
For a French version of this
manual, visit our V¢ebsite at
w_v.GEAppliances.com.
Pour une version fiangaise de
ce manuel d'utilisation, veuillez
visiter notre site web _ l'adresse
w_v.GEAppliances.com.
®
Consumer Support
Consumer Support . . .Back Cover
Product Registration ...... 25, 26
*¢\,_rranty .................. 27
©
Write the model and serial
numbers here:
Model #
Serial #
Find these numbers on a label
behind the room cabinet on the
base pan.
TINSEA471JBRZ 49-7538 12-05JR
IMPORTANTSAFETYINFORMATION.
READALLINSTRUCTIONSBEFOREUSING.
WARNING!
Foryour safe_ the information in this manual must be followed to minimize the risk of fire or
explosion, electric shock, or to prevent property damage, personal injury, or loss of life.
SAFETYPRECAUTIONS
• This Zoneline must be properly
installed in accordance with tile
Installation Instructions before it is
used. See the Installation Instructions
ira tile hack of this manual.
• Replace immediately all electric service
cords that have become flaved or
otherwise damaged. A damaged power
supply cord must he replaced with a
new power supply cord ohtained flom
the mamffacturer and not repaired.
Do not use a cord that shows cracks
or ahrasion damage along its length
or at either tile plug or connector end.
• Unplug or disconnect tile Zoneline at
tile fllse box or circuit hreaker before
making any repairs.
NOTE: ¼:e strongly recommend that any
servicing be performed hv a qualified
individual.
Replacing an existing unit?
For details, see the Installation
Instructions in this manual.
READANDFOLLOWTHISSAFETYINFORMATIONCAREFULLY.
SAVETHESEINSTRUCTIONS
2
Aboutthe controlsonyourZoneline. ge.com
[,
%
TEMPCONTROL
@
TempControl
The temp control is used to maintain the
Co trols
I'00111 telllpei'attli'e. The coi/li)i'essoi" will
c_cle on and off to kee I) the room at the
same comfort level. _]_en you tm'n the
knob to COOLER(blue), the indoor air
will become coole_: Tm'n the knob to
WARMER (red) and the indoor air will
become war/nei:
3800Series only
_]_en the outdoor temperatm'e is lower
than 90°E heat is provided b)' the electric
heater in the air conditioner insmad of bv
the heat I)ump.
MODECONTROL
@
Mode Control
HIGH COOLand LOW COOLpr_vi(le cooling
with different tim speeds.
HIGHHEATand tOW HEATprovide heating
with different tim speeds.
LOWFAN or HIGH FAN provides air
circulation and filtering without cooling
or heating.
NOTE:If youmove the switch from a cool orheat
setting to STOPorto a fan setting, the unit hasan
automatic3-minute delaybeforea//owlbg the
compressortorestart in thecool or heat mode.
About YourHeat Pump (3800 Series only)
Heat l)mnps can save money by removing heat
fl'om the outside ai_e\'en when the outside
temperature is below fl'eezing--and releasing
that heat indom_,
To get the best perlommnce fl'om ):our heat
pmnp, don't change the room them_ostat ve_T
often. Raising the heat setting 2-3 degrees will
cause the Zoneline to use its electric heating
elements in order to reach the new temperatm'e
setting quickly.
There is a three mimlte minimum compressor
run time at any setting to prevent short cycling.
The indoor tim motor starts beli)re the
COllll)I'essoI" and stops aJ[teI" the cOI/ll)I'essoI"
cycles off'.
The electric heating elements use much
more electricit_ than heat pmnps and cost
II/OI'e to operate.
3
Otherfeaturesof yourZoneline.
Ventilation Control
The xentilation control lexer is located at the
upper lett side of the Zoneline unit, behind
the room cabinet.
_,_q_en set at the closed position, onE' the air
inside the room is circulated and filtered.
X,_]_en set at the open position, some outdoor
air will be drawn into the room. This will
reduce the heating or cooling efficiency.
Energy Tip: Kee I) the vent control at the closed
position. The room air will be filtered and
circulated.
NOTE:Twoshiww screwsmustberemovedfromthe
ventdoorbeforeuse.Seethe/nstal/afionInstructions
in thebackofthismanual
ToRemovethe RoomCabinet
Additional controls are located behind the
I'OOIll cabinet.
To remove:Pull out at the bottom to release it
fl'om the tabs (l). Then lift up (_2).
Open
position
Vent
control Closed
(shownin position
middle
position)
To replace: Place the tabs oxer the top rail ( l ).
Push imvard at the bottom tmtil it snaps into
place (2).
Air Direction
To a(!iust the air direction, remove the room
cabinet. Remove the 7 louver screws that hold
the louver insert in place. Flip the louver insert
180°, replace the screws and the room cabinet.
Louverscrews
Louverscrews
4
Removethe room cabinet and flip the louver
insert to change the air direction.
Puxi/iaq Controls onyour Zonefine. ge.com
Auxifiaq Controls--Dip Switches
Tile au_liary dip switch controls are located
behind tile ro()m cabinet, through an opening
in the control panel.
Remove tile room cabinet. See tile 7"0Remove the
Room Cabinet section.
Tile ti_ctoi y settings will be in tile DOWN position.
Tile owner is responsible fin" checking switches
and ensuring they are in tile desired position.
ALLRR(AllElectric Heat)--
(3800Series models only)
C: FAN CN(Coo%g-Smart Fan)
H: FAN CY(Heating-Smart Fan)
CLASS2 (RemoteThermostat)
LOADSHEDDING(CDC)
FREEZSen (FreezeSentinel)
CONSTFAN(Constant ON Fan)
OCCUPIED(OccupancySensor)
DOWN
uP
-- _' LHEAT BOOST
(3800Series modelsonly)
/
--Heat Sentinel
TL1(H)(Temp.Limit 1-Heat)
TL2(H)(Temp.Limit 2-Heat)
TL3(H)(Temp.Limit 3-Heat)
TL1(C)(Temp.Limit 1-Cool)
TL2(C)(Temp.Limit 2-(;ool)
TL3(C)(Temp.Limit 3-(;ool)
DipSwitches
AccessCover
All Electric Heat
This electric heat option flmcfions only on tile
3800 Series models. _]/en this switch is enabled
(UP), heat pump operation is locked out, causing
tile unit to provide only electric resistance heat.
Cooling--Smart Fan
X_l/en this switch is enabled (UP),it allows tile
indoor fire to cycle on/offwith tile compressor:
\,_l/en this switch is disabled (DOWN),it allows
tile indoor Jim to Fun contintlOtlslv.
Heating--Smart Fan
\,_]/en this switch is enabled (UP),it allo_vs tile
indoor tim to run continuousl): When this
switch is disabled (DOWN), it allows tile indoor
fire to cycle on/off with tile heat pure I) or
heater oi)ei'ation.
L ALLFR(All Electric Heat)
° °[B?BBBBBBBBBBBBB
C: FAN CN (Cooling-Smart Fan)
° °IBB BBBBBBBBBBBBB
i-.-H: FAN CY (Heating-SmartPan)
Auxiliary controlsonyourZoneline.
Remote Thermostat--Class 2
_._q_en this switch is enabled (UP}, it allows the
unit to operate with a Class 2 Remote Control
Wall Them_ostat. The refit controls are disabled.
LoadShedding(CentralDesk Control)
This featm'e is active only if the refit is in
CDC mode. When this switch is enal)led (UP),
the indoor tim can be tin'ned ON or OFF with
the refit controls.
Freeze Sentinel
_._l_en this switch is enabled (UP), it turns OFF
the fl'eeze sentinel protection ieatm'e. With the
switch disabled (DOWN),the fl'eeze sentinel is
acti\_ted, which automatically provides heat
without user inte_ti_ce. This helps to prevent
plumbing damage by turning the heater and
indoor tim ON at 41°F and OFF at 46°E
°_'_"BBBI_BBBBBBBBBBBB°_'_°
L CLASS 2 (Remote Thermostat)
°_:"BBBB_BBB BBBBBBBB°_:"
L_ LOAD SHEDDING(CDC)
°_"[BBBBB@BBJBBBBBBBB °"_"
t FREEZESen(Freeze Sentinel)
Constant ON Fan
"_._q_en this switch is enabled (UP),it allows the
indoor tim to run continuously at high speed,
exen if the trait is in the STOP position.
Occupancy Sensor
_,_l_en this switch is enabled (UP),it allows the
refit to utilize an infl'ared motion sensor and
a door switch fl)r occupancy detection. This
leattlre allo_vs an energy ii/anagelllent systeI/l
to be installed and operated in coqitmction
with the tmit.
°_BBBBBB@B BBBBBBBB °"'_°
t DONST FAN(Constant
ON Fan)
°_"_"BBBBBBB_ BBBBBBBB "_"_'"
OCCUPIED
(Occupancy Sensor)
Temperature Limiting
Temperature limiting can reduce energy' costs
by limiting the lowest temperature that can be
set fl)r cooling and the highest temI)erature that
can be set fin" heating, Temperature limiting is
controlled by the second six au_liarv switches,
ge.com
The fit_t three switches are used to select tile
cooling limits, and the remaining three switches
are used to control the heating limits, This
teatm'e is not available with the Remote
Them_ostat--Class 2.
° qBBBBBBBBi BBBBBBB
TL1/C)(Temp.Limit 1 Cool)_
TL2(C)(Temp.Limit2 Cool)
TL3(C)(Temp.Limit3 Cool)
Temperature limiting during COOLmode
(all temperatures shown in °F)
UP DOWN Minimum Maximum
NONE 1,2,3 60° 85°
1 2,3 64° 85°
1,2 3 66° 85°
2 1,3 68° 85°
2,3 1 70° 85°
1,2,3 NONE 72° 85°
1,3 2 74° 85°
3 1,2 76° 85°
Heat Sentinel
_,_]/eil this switch is enabled (UP), it turns ON
the heat sentinel protection teatm'e. _,_]th the
switch disabled (DOWN), the heat sentinel is
de-actiw_ted. This teatm'e automatically provides
cooling without user intedhce. This helps to
prevent an excessively hot room by turning the
air conditioner ON at 85°F and OFF at 80°E
° °iBBBBBBBBiIBBB
TL1(H)(Temp.Limit 1 Heat)
TL2(H)(Temp.Limit2 Heat)
TL3(H}(Temp.Limit3 Heat)
Temperature limiting during HEATmode
(all temperatures shown in °F)
UP DOWN Minimum Maximum
NONE 4, 5,6 60° 85°
4 5,6 60° 80°
4,5 6 60° 78°
5 4,6 60° 76°
5,6 4 60° 74°
4,5,6 NONE 60° 72°
4,6 5 60° 70°
6 4,5 60° 65°
oo%qaBBBBaBB]laaaaaaa,ale,,.
Heat Sentinel J
Heat Boost (AZ3800only)
_&]/en this switch is enabled (UP) and outdoor
teml)eratures are between 20°F and 46°E heat
pmnp only operation is locked out. This setting is
used to provide SUl)plementa_ T heat to tile heat
pmnp operation in conditions where tile heat
pmnp only operation is not sufficient to maintain
a consistent, coi//ti)rtable i'OOlil tei//l)ei'at/li'e.
NOTE."ThisisanauxilbryswitchforAZ2800modelsand
mustremabb the(DOWN)position.
BOOST(Heat Boost Operation) J
Auxiliary controlsonyourZoneline.
Auxiliary Controls--Terminal Connections
Tile auMlim_' controls are h)cated behind tile
rooiil cabinet beneath tile access coxei;
_] Remoxe tile room cabinet, See tile
ToRemove the Room Cabinet section.
_ Rei/loxe tile screw tl'Oill tile }l('('ess ('o_ei;
To make wiring, connections, inse_L tile wires
] ) ) 0 0 S o"
inU tile b( tt m f tile temfinalr and fi_hten
screws securelx.
[_Mter all desired cmmections have been
Illade, replace tile access coxer }lll(l rooi//
cabinet.
oi Ioo I_ _1 _ I_ _ ° _ _ °
DoorSensor
ExternalFan
CentralDeskControl
The owner is responsible fi)r making all
c(mnections and setting tile appropriate
dip switches.
A CAUTION:
hnproper wiring may damage tile Zoneline
electronics. No common busing is pemfitted.
Damage or erratic operation may result.
A separate wire pair illtlst be rtm from each
separate controlling switch to each individual
Zoneline.
LCommon-Ground
-- White -Heater
Yellow- Compressor
Black- Solenoid
Green-HighSpeedFan
Green- LowSpeedFan
Red-24V AConly
Motion Sensor(Obtainedlocally)
_41/en connected, tile wall mounted motion
sensor will detect motion in tile room and
automatically set back tile ro()m temperature.
The door and motion sensm_ work together
to automaticalh' set back tile room temperature.
Tile appropriate dip switch m list be enabled.
h_[_J MotionSensor
8
Door Sensor (Obtained locally)
_]/en connected, tile door sensor will detect
when tile door in tile i'OOill w;Is opened or
closed. This teatm'e must be used in coI_junction
with tile motion sensor:
Tile door and i/lotion sensoi3 work together
to automaticallx set back tile room temperature. L_ DoorSensor
External Fan(Obtainedlocally)
_4]/en connected, an auxiliary or external tim
can be controlled with tile indoor tim motor
on tile Zoneline. Com_ections provide 24 V AC
to energize a remote relay, turning on tile
external tim.
e! Je_o Ii _J J
I__1
L- ExternalFan
Central Desk Control
ge.com
o
X4]/en connected, tile trait can be turned ON
or OFF with a switch located at the Central
Control Panel. A separate wire pair must be
rtm fl'om each separate controlling switch to
each individual Zoneline.
Remote Thermostat
X_q/en connected, tile trait _fill be controlled
bv a i'elllote thermostat.
NOTE'The number 4 dip switch must be in tile
enabled (UP) position to activate the remote
them_ostat. (See tile installation instructions
supplied with tile remote them_ostat).
IMPORTANT:
Tile Zoneline them/ostat connections
provide 24 V AC only.
If using a digital/electronic wall them_ostat,
you must set it to tile 24 V AC setting.
See tile Installation Instructions fin" tile
wall them/ostat.
[mJ
L CentralDeskControl
Red- 24VAConly
Green-LowSpeedFan ] ]
Green-Hig_hk! Ps_2nFc__ I
Yellow- Compressor
White- Heater
Common-Ground
A CAUTION:
Damage to a wall them_ostat or m tile
Zoneline electronics can result fl'om improper
com_ections. Special care nlust be used in
cmmecting the wires. No line voltage
connections should be made to anv circuit.
Isolate all wires in building fl'om line voltage.