Welcome to the GE family. We’re proud of our quality products and we are committed
to providing dependable service. You’ll see it in this easy-to-use Owner’s Manual and
you’ll hear it in the friendly voices of our customer service department.
Best of all, you’ll experience these values each time you use your air conditioner.
That’s important, because your new air conditioner will be part of your fkrnily for
many years. And we hope you will be part of ours for a long time to come.
We thank you for buying GE. We appreciate your purchase, and hope you will
continue to rely on us whenever you need quality appliances for your home.
GE& You,A Service Partnemhip.
FOR YOUR RECORDS
MWationInstructions
Electrical Requirements . . . . . . . .13
Location . . . . . . . . . . . . . . . . . . ..l4
Indoor Unit Installation . . ...1516
Connection of Pipes . . . . . . . .17–22
Check Connection . . . . . . ...23-26
TestRun . . . . . . . . . . . . . . . . . ...27
Installation Templates . . . ...2829
lFoub/eshooting71ps
Before You
CallForService. . . . . . . . . . . ...30
Normal Operating Sounds . . . ...30
d
6
.
Write the model and serial numbets hem for the indoor and
outdoor units:
Indoor model #
Outdoor model #
You can fmd them on a label on the side of each unit,
Staple sales slip or cancelled check here.
Proof of the original purchase date is needed to obtain service
under the
~ty.
Serial #
Serial #
READ THIS MANUAL
Inside you will find many helpful hints on how to use and maintain
your air conditioner properly.Just a little preventive care on your
part can save you a great deal of time and money over the life of
your air conditioner.
You’ll fmd many answers to common problems in the Before YoU
Ca// For Service section. Ifyou review our chart of Troubleshooting
~ps first, you may not need to call for service at all.
CustomerSeNice
Warranty . . . . . . . . . . . . . . . . . ..3l
Service Telephone
Numbers . . . . . . . . . . . .Back Cover
2
IFYOU Nf..ll SED~IIfi~
~.:
~If You do need sem-ice, You can relax knowing help is only a phone
i!i!i!i
cd away. A listof toll-free customer sefice num~ers is ~cl;dedin
the back section. Or, you can always call the GE Answer Center@ at
800.626.2000,24hours a day, 7 days a week.
For anyservicewhichrequiresentryinto the
refi-igerantsealedsystem,Federalregulations
requiretheworkbe performed byatechnician
havinga ClassII or Universalcertification.
button. Each time the button ispressed, the operation mode is shifted in the arrow direction.
l~Jr_17
Cooling
Auto
Dehumidify
Heating
(Heat pump only)
Close the door on the remote control.
13J
Set the tem~erature lower than the room
temperatu& The temperature can be set
within am.nge of64°F–860 Fin 2° F
increments.
l’==-)
J
-----5-
L
Heating Operation (Heat pump model only)
“F
H
Q“
e(4?
I
4A
*5
v
To lower the
)
temperature
To raise the
temperature
Set the fan speed again with the door of the
❑
remote control still closed. You can select the
fan speed in four steps-low, medium, high or
AlKU. Each time the button is pressed, the fa
speed mode is shifted.
Q*<
J
Km
bY
%@%J&>
“F
a
Press the Start/Stop button. The unit will respond with a beep.
Selection button. Each time the button is pressed, the operation mode is shifted in the arrow direction.
Cooling
Close the door on the remote control.
Set the temperature higher than the room
tempemture. The temperature can be set
witl& a range of 60° F:86” Fin 2° F
increments.
LA
v
&
To raise the
temperature
Tolower the
temperature
Auto
[~Jl~J
Dehumidify
Set the fim speed again with the door of the
❑
remote control still closed. You can select the
fan speed in four steps-low, medium, high or
A(m). Each time the button is pressed, the fian
speed mode is shifted.
Heating
(Heat pump only)
How to use the OperationMode Selection button.
Auto Operation
A
Press the Start/Stop button. The unit will respond with a beep.
El
~Open the door on the remote control. To select auto opemtion, press the Operation Mode Selection
Each time the button is pressed, the operation ‘mode is s&fted in th; arrow direction.
“E!!wM3E!!3
Cooling
The temperature and fan speed are
H
automatically setby the electronic controls
based on the actual room tempemture. lfyou
want to change the settempemture, close the
door on the remote control and press the Room
Tempemture Settingbuttons. The cooler or
warmer you feel, the more times (up to two
times) you should press the button. The set
tempemture will then be changed automatically.
Q
---rV
L__l
Dehumidi@ Operation
A
“g
1A
@
To lower the temperature
Auto
Toraise the
temperature
Dehumidify
l)uring Auto Operation:
.’ You cannot switch the indoor fim speed. Ithas
already been set by the electronic control.
. If the system is not operating as desired,
manually switch to another mode. The system
will not automatically switch from the cooling
mode to the heating mode, or from heating to
cooling, itmust be done manually. Reset using
the Operation Mode Selection button.
‘ During Auto Operation, pressing the Airflow
Direction Start/Stop button makes the horizontal
louvers swing up and down automatically. Ifyou
want to stop auto-swin
Direction Start/Stop button again.
Heating (Heat pump only)
press the Airflow
%
()
Press the Start./Stop button. The unit will respond with a beep.
Selection button. Each time the button ispressed, the operation mode is shifted in the arrow direction.
(==--)
\/l—
Close the door on the remote control. Setthe
tempemture higher than the room
tempemture. The temperature can be setwithin
am.nge of 64° F–86° Fin 2° Fincrements.
8
[
Cooling
I
I
)
J*
v
&
[
Tocaisethe
temperature
To lower the temperature
Auto
I
)
(
During l)ehumid~ Operation:
‘~~The indoor fim speed isautomatically set to low
and cannot be adjusted.
‘ The indoor fim may stop during this opemtion if
the electronic control detects over=cooling.
Dehumidify
I
J
Heating (Heat pump only)
1
J
Additional features.
S/eep Mode
Press the Sleep Mode Auto button..
to set the time you want the unit to
automatically turn off.
Make sure the Sleep Mode Auto I.XD lights up.
The Timer isprogrammed in one-hour
increments by pressing the Sleep Mode Auto
button 1 to 7’times.
Setting the llme
Time can be set only when you have pressed the
Reset button. Ifyou havejust replaced the batteries,
the Reset button should be pressed to reset the time.
Press the Start./Stop button.
pJ
Press the Time Setting buttons until the
❑
desired time is set.
*
m
To cancel the Sleep Mode, press the Sleep Mode
Auto button several times until the star (*)
disappean from the opemtion display.
N07E: TheSleep Mode will be operated at low fan
speed (cooling) or medium fan speed (heat pump only)
for quiet sleeping.
IN COOIJNGMODE: The temperature will
automatically rise by 2° Fover the next 30 minutes
and by 4° Fin 1 hour for comfortable sleeping.
Press the Timer SETbutton.
❑
NU7E:Check the indicator for
A.M. and PM.
SET
75
Delay Star@re-Set Stop
Make sure the time is set correctly on
the remote control display.
Press the ON/OFF Timer
buttons to turn Timer on
or off.
mom
(x!?
N07E: Select one of the following four ~pes of operation.
k
Delay OFFTmer
b
Delay ON Tmer
Press the Time Setting buttons until the desired
❑
time is set.
~Store the selected on/offsetting
uby pressing the Timer SET butt&.
With the unit runnina.”
k
Delay OFFand ONTmer
Delay ONand OFFTimer
SET
75
9
Additional features.
Aitilow Direction (Indoor unit)
The up/down airflow can be adjusted by using the
remote control.
Press the Start/Stop button to startthe unit.
El
Open the door on the remote control. Press the
PJ
Airflow Direction Start/Stop button and the
louvers will swing up and down. Press it again
and the louvers will stop at the desired setting.
..
(-
.,
%
Air Circulation Mode
Circulates the room air without cooling or heating.
NOIES:
“ Always use the remote control to adjust the
up/down airflow direction. Moving the louvers
by hand could cause operational errors or
darnage the unit.
~When the unit is shut off, the up/down airflow
direction louver will close the air outlet vent of
the system.
Toadjust leiWight direction:
Adjust the leftiright airflow direction by hand.
Press the Start/Stop button. The unit will respond with a beep.
control. Now each time that you press the Indoor Fan Speed Selector, the fan speed isshifted from low
to medium to high to lWTO, and then back to low again.
fjf--f-q+~.
-+
Fanspeed is on low.
N07ES:
‘~<’
The fan speed of the indoor unit will automatically cycle depending on the room temperature.
;; AUTO economizes power consumption and prevents overcooking. The fin speed is automatically
changed from medium to low or vice versa, depending on the ambient temperature.
Fanspeed is on medium.
Fanspeed is on high.
AUTOAir
Manual Operation
If the remote control will not operate the unit, open the front panel upward and press the Manual
Operation button.
Use a pencil to press
the button.
Ifyou want to stop operation, raise the front panel and press the Manual Operation button again.
During Manual Operation, the opemting conditions are automatically set asfollows:
Operating Mode
Indoor Fan Speed
Setting Temperature
holing Only
Model
Cooling
I
High
I
72° F
I
Heat Pump Model
Room Temp.Room Temp.
above X“ FZYFttm/ 76°F
I
I
I
Cooling
High
72” F
I
I Fan turns on/oti automaticallyIHigh
Air intake temperature
I
Dehumidify
Room Temp.
below 7V0F
I
I
Heating
76° F
I
I
I
77
Careand cleaning of the air conditione~
CAIMON: Before performing any maintenance, turn off the main power to the system.
Indoor Unit
Grille, Caseand Remote Control
Turn the system off before cleaning. To clean, wipe
with a soft, dry cloth. Do not use bleach or abrasives.checked and cleaned at least eve~ 30 days or more
Air intake vent
~ ‘‘‘‘‘““’‘““-‘“
Air outlet vent Horizontal louver Vertical louverAirfilters
Air Filters
The two air faltersbehind the front grille should be
often if necess~.
Lift the fi-ont access panel and pull the filter tab
slightly forward to remove the filter. Clean the filter
with a vacuum or warm, soapy water. Rinse and let
the falterdry before replacing it.
GAWUIN: DO
becausedirtandlint will clog it andreducepetiormance.
Outdoor Unit
The heat exchanger coils and panel vents of the
outdoor unit should be checked regularly. If
clogged with dirt or debris, the heat exchanger and
panel vents may be professionally steam cleaned, a
service available through your GE service outlet.
+ Supply power must be disconnected before cleaning the
outdoor unit.
.,..
‘:’ Dirty or clogged coils will reduce the operating efficiency of
the system and cause higher operating costs.
Air intake vent
Air outlet vent
If you’re closing up for the season.. .(cooling-only models)
Operate the system in the Air Circulation mode
❑
for 2 hours. This will dry out the system.
Remove the batteries horn the remote control.
❑
Cover the outdoor unit with a protective cover.
❑
NOToperate the systemwithout a fifter
72
Installation ilKtrUCtiOllSm
Parts included
Type A screws
b:.L----Jfi@--==; [
(PD-l-+-J@--
‘;;:-J;‘Cref.jr’ro’
Installation plate
\n
\M/
READ THEINSTALLA770N INSR?UCRONS CAREFUUYAND COMPLETELYBEFORE YOU BEGIN.
IMPORZANTN07ES:
Follow National Electiic Codes (NEC) andjor local codes and ordinances.
For personal safe~ this system must be properly grounded.
Protective devices (fuses or circuit breakers) acceptable for installation are specified on the
nameplate of each unit
Servicing and installation of the refrigerant system must be petiormed only by a licensed, tiVAC
cetified technician.
Make sure to avoid wiring or plumbing inside the wall when installing.
Type B~ ‘
!
G9@’”
Outdoor unit
N07E: Optional tube kits—which
contain pre-flared insulated tubing,
wiring, etc., to complete system
installation requirements—are
available from General Electric.
Indoor unit
. \\ I
II1
hr any sem-ce which requin?sentry into the refrigerant sealed system, hderal regulations mquim tie
work be performed by a technician having a Class II or Univemal certification.
●//CAUTION
Electrical Requirements
Be certain all wiring complies with local building codes and NEC and that the supply voltage for this
system is correct The system supply voftage is connected to the outdoor unit only
Check the rating nameplate on side panel of outdoor unit for required circuit protection rating and
required supply voltage.
Use Underwriters-approved electrical branch circuit disconnect for providing supply voltage to split
system outdoor unit Locate disconnect within sight and readily accessible from outdoor unit.
The sphl system indoor unit requires low voftage (D.C.)supplied from the outdoor unit via
interconnecting wiring. The interconnecting wiring between indoor and outdoor units of this
system must be 18-4 wiring, 18-gauge (minimum), 300-volt rating, type SJO–WA or STO–WA.
Be ceflain there is an uninterrupted, unbroken electrical ground connection.
Electric drill
Carpenter$ stud finder (recommended)
2 Y–3” diameter hole saw
Phillips-head screwdriver
‘z Pencil
;,
“ Crescent wrench
N07E: A licensed, certified (to hand/e refrigerant-22,
recovety etc.) technician is required for installation of
these split air conditioning or heating pump systems.Is
Installationinstructions.
Read completel~ then follow step by step.
Select the Best Location
Indoor Unit
El
X Do not have any heat or steam near the unit.
“ ~Select a place where there are no obstacles in
front of the unit.
~ Make sure that condensate drainage can be
conveniently routed away.
“ Do not install near a doorway.
:’ Ensure that the space around the left and right
of the unit is more than 2”. The unit should be
installed as high on the wall as possible, allowing a
minimum of 3“ from ceiling.
: Use a stud finder to locate studs to prevent
unnecessary damage to the wall.
-.
5 RooftopInstallations:
If the outdoor unit is installed on a roof structure,
be sure to level the unit. Ensure the roof structure
and anchoring method are adequate for the unit
location. Consult local codes regarding rooftop
mounting.
❑pipin!lhn@andElevatio..
Indoor unit mounted above outdoor unit
Model
(Cooling
Capacity)
18K
I
9K, 12K
I
* Both gas and liquid interconnecting pipes must be insulated,
Pipe Size*
I 5/8” I
I 1/2” I
3/8”
1/4”
Max.Max.
*,
I
*,
I
Elevation
B
26’
I
26’
I
I
I
More than 2“
*
Install h
OutdoorUnit
El
M Ifan awning is built over the unit to prevent direct
sunlight or rain exposure, make sure that heat
radiation from the condenser is not restricted.
;~ Ensure that the space around the back and sides
is more than 4“. The front of the unit should have
more than 28” of space.
More than
More than 2”
*
A (Max. length)
Outdoor
4
Outdoor unit mounted above indoor unit
Model
(Cooling
Capacity)
18K5/8”
9K, 12K
* Both gas and liquid interconnectingpipes must be insulated.
Outdoor
unit
Pipe Size*
Gas
1/2”
liquid
3/8”
1/4”
Max.
Length
A
4$J,
40’26’
I
r
unit
I
7
Max.
Elevation
B
26’
:~:~Construct and anchor a strong and level
mounting base or pad for the outdoor unit.
~~~Use the provided rubber grommets between
the unit’s four mounts and the base or pad.
ii Anchor the outdoor unit through its four
mounts using bolts.
b
* Both gas and liquid interconnectingpipes must be insulated.
B
1
A (Max. length)
1-
41
Indoor
unit
N07E: These instructions do not coverall
installations. However, the typical installation will be
to secure the installation plate to wall studs 16” apart.
Itis recommended that a stud finder be used to
locate the wall studs.
Measure the wall and mark the centerline. It is
El
also important to use caution concerning the
location of the installation plate-routingof
the tigto power outlets is through the walls
typically. Drilling the hole through the wall for
piping connections must be done safely.
Mount the installation plate on the wall with
El
four type A screws. If mounting the unit on a
concrete wall, use anchor bolts.
Mount the installation plate horizontally by
El
aligning the centerline using a level.
Drill the piping hole with a 2%–3” hole core
E
drill. Drill the piping hole ateither the right or
the left with the hole slightly slanted to b-e
outdoor side (see illustration below).
Installation plate
Left rear piping
--.-. -.--. -.--11. .. ..-. -.-J -.JI
. .!,
TypeA screw
NOIES:
‘ For right rear piping, draw a line in the direction of
the arrow marked “A” and make another line
extending from the bottom line of the installation
plate. The meeting point of the two lines is the
center of the hole.
For left rear piping, draw a line extending left
from the bottom line of the installation plate.
This is the centerline of any hole for the left rear
installation.
center
(See templates in the back of this manual for hole location relative
to the installation plate.)
2%–3” dia. piping hole
:door
+~-‘----T.
I
75
Installationinstructions.
Refrigerant Piping and Condensate Drain–Indoor lJnit
Optional tubing kits are available which consist
El
of all interconnecting copper lines, wiring
needed to connect indoor to outdoor units,
and a plastic sleeve endcap to enhance the
installation wall hole sealing. You may also
purchase the tubing, insulation, wiring, etc.,
locally for the installation. See chart on page
for tubing diameter sizes required for the
different models.
N07E Since therefrigerant metering device is
located in the outdoor unit, both the gas and the
liquid tubing line setsmust be insulated. Amn@ex
material is recommended.
Gaslineinsu\~ionWZtion
*For heat pump models, heat-resistant insulation material
with minimum rating of 230° Fis required.
14
See chart on page 14 for maximum lengths of
El
tubing for interconnecting units. The indoor
and outdoor units are provided with flare nuts.
See the brass fittings on the indoor/outdoor
sections.
N07E:The indoor unit is shipped from the factory
with a nitrogen holding charge to prevent moisture
contamination during shipment. Remove the flare
nuts on the indoor unit to vent the nitrogen
(environmentally friendly) into the atmosphere.
Measure distance between indoor and outdoor
❑
units, considering the routing for the piping
and wiring. Cut tubing to lengths, insert the
N07E: If the drain hose will be routed in the room,
insulate the hose with an insulation material* so
that dripping from “sweating” (condensation) will
not damage fi.wniture or floors.
*Foamed polyethylene or equivalent is
recommended.
Taping
Indoor/outdoor
connecting cable ~
4
Installation instructions.
Indoor unitinstallation.
❑
Hook the indoor unit onto the upper
portion of the installation plate. (Engage
the two hooks of the rear top of the indoor
unit with the upper edge of the installation
plate.) Ensure that the hooks are properly
seated on the installation plate by moving it
left and right.
1.-.1
Press the lower left and right sides of the unit against
the installation plate until the hooks engage with their
slots (clicking sound).
hmedngthepipkgs to theindoor unit
El
1 Align the center of the pipings and
sufficiently tighten the flare nut by hand.
Drain h&e
Wrap theinsulationmaterialaround the
El
connectingportion.
UJ770N:Be careful to arrange the pipings, drain hose
and cables as shown on page 17 by connecting them to the
indoor unit.
Isulation material
netting
e
Wrap insulation material around the connecting portion.
2 Tighten the flare nut with a wrench.
af-
Indoor umt tubing
Flare nut
Piping
78
Connection of the Pipes
RJRLEFTREARPIPING:
Route theindoor tubingwiththedrainhose
Izl
throughthepipinghole inthe desiredposition.
w
To remove the retainec press
the bottom of chassis near the
retainer upward and pull the
tab out of its hole.
Insertthe pipings,power supplycord and the
El
connectingcableintothe piping hole.
G
Tubing
holding
retainer
@
Pull
Tape the tubq, drainhose and the connecting
❑
cable.
●.**
@i!!i!s
I
Indoor unitimtallation.
El
Hook the indoor unit onto the upper
portion of the installation plate. (Engage
the two hooks of the rear top of the indoor
unit with the upper edge of the installation
plate.) Ensure that the hooks are properly
seated on the installation plate by moving it
left and right.
Gas side piping
Liquid side piping
Drain hose
,—
Outside
Piping
~
Connecting cable
Indoor
Inserttheconnectingcable intotheindoor unk
El
1 Do not connect the cable to the indoor unit.
2 Make a small loop with the cable for easy
comectionlater.
N07E: Wiring must comply with local and NEC
codes. The interconnecting wiring between
indoor and outdoor units of this system must be
18-4 wiring, 18-gauge (minimum), 3oo-volt mting,
type SJO-WA or STO-WA.
Conneet the pipingsto the indoor unit.
❑
Align the center of the pipings and
sufficiently tighten the flare nut by hand.
79
Installation instructions.
Piping and Condensate Drain Line—Indoor
C#lUllON: Be careful to arrange the pipings, drain hose and
cables as shown on page 17 by inserting them into the indoor
unit and reattaching the tubing retaine[
Isulation material
Wrap insulation material around the connecting portion.
Reroute thepipingsand the connectingcable
•1
acrosstheback of the ehassk.
Indoor unitinstallation.
•l
Hook the indoor unit onto the upper
portion of the installation plate. (Engage the
two hooks of the rear top of the indoor unit
with the upper edge of the installation
plate.) Ensure that the hooks are properly
seated on the installation plate by moving it
left and right.
Press the lower left and right sides of the unit against
the installation plate until the hooks engage with their
slots (clicking sound).
netting
e
Drain hose
20
Piping
/
r
Tubing holding
retainer
s
=L
~\ ~Hook
@ Push
L
e
sufficiently tighten the fl&e nut by hand.
Z Tighten the flare nut with a wrench.
o
c
ndoor UnitOutdoor Unit
Terminal
(4P)
@
@
@
@
I
Terminal
(6P)
II
\
@
Q
@
@
11 @
12 @
@
--- ---
Liquid side piping
(smallerdia.)
Connecting cable (low voltage)
Power supply @
1
1
1
I
I
I
!--------->Ground
access cover
ide piping
r dia.)
18
gauge
300 volt
Terminal block
Outdoor unit
.
Lowvoltage wiring
/
w-&,--Y
/
d
Q
Cover control
WARNING
; Be sure
wire fi-om the indoor unit to the outdoor unit
(size ofwire and wiring method, etc.).
~:’Everywire must be cormected securely.
‘~ No wire should be allowed to touch refi-igerant
tubing, the compressor or any moving parts.
12K
18K
to comply with local codes to route the,>,.
9KI15V14
60Hz - lPh
60Hz - lPh
230/208V1418
60Hz -1 Ph
/
Y
115V14
Conduit panel
upply voltage
onnection
1815 amps
18
20 amps
15 amps
I
NOES:
~;!~shows field wiring (low voltage).
;:;; Oshows power source wiring.
~~~Separately wire the high and low voltage lines.
~~<Use heat-proof electrical wiring capable of
withstanding tempemtures of up to 167° F.
‘~:Use outdoor and waterproof connection cable
rated more than 300V for the connection
between indoor and outdoor units. (For
example, Type SJO-WA.)
Installationinstructions.
Connecting wiring to outdoor unit:
1
Remove the wiring access cover on the
outdoor unit.
2
Drill a hole through the plastic plug cap
appropriate for the passage of connecting cable
(for low voltage line).
3
Pass the connecting cable through hole.
4
Properly connect the wire onto the terminal
block.
5
Fix the connecting cable with the clamp cord
provided on the unit to avoid strain at the
terminal when the connecting cable is pulled
outside by up to a 35-pound weight.
Wmd vinyl tape over the connecting cable for
6
sealing between the surface of the connecting
cable and cap.
7
Mount the taped part of the cable on the cap.
Mount the holed cap with the wound cable on the
8
conduit panel.-
\
11
\
\
, Terminal block
How to connect wiring to the terminals:
For solid corewiring (or Fable)
~~’~
1
Cut the wire end with a wire cutter or wirtiutting
pliers, then strip the insulation to expose the solid
wire about 15/16”.
2
Using a screwdriver, remove the terminal
screw(s) on the terminal plate.
Using pliers, bend the solid wire to form a loop
3
suitable for the terminal screw.
4
Shape the loop wire properly, place it on the
terminal plate and tighten securely using a
screwdriver.
‘m
~
n
.—
~
w
‘!r
;
Forstrandwiring
Cut the wire end with a wire cutter or wire cutting
1
pliers, then strip the insulation to expose the
strand wiring about 3/8”.
Solid wire
Loop
Q
Insulation
Clamp cord
!
Cap
(resuse)
4
Hole
(for low
voltage line)
J
Taping
(for sealing)
Low voltage line
(connectingcable)
/1
W!AR/U/NG:Loose
Conduit panel
wiringmay cause the terminal to
overheat or result in unit malfimction. A fwe hazard
may also exist. Be sure all wiring is ti~htlv connected.
Lock nut
- Cap
(remove)
Power supply line
(10, 230/208V or
115V, depending
on model)
2
Using a screwdriver, remove the terminal
screw(s) on the terminal plate.
3
Using around terminal fmtener or pliers,
securely clamp each stripped wire end with a
round terminal.
Position the round terminal wire, and replace
4
and tighten the terminal screw using a
screwdriver.
Stranded wire
, Screw with
/ sDecial washer
terminal
Wi
al plate
I I
Screw with
special washer
Round terminal
22
the open position (horizontally) by hand.
2 Remove 3 screws that retain the front grille.
Pull the lower left and right sides of the grille
toward you and lift itoff.
,
Remove screws
—
@
(3 places)
e
Gmect thecable to theindoor unitby
❑
connectingthe wirestothe termkak
control board individuallyaccording tothe
outdoor unitconnection.
1 Ensurethat the color of the wires of the
outdoor unit and the terminal No. are the
same as those of the indoor unit. (Refer to
the Wiring diagram on page 21.)
g
a’
on the
Check thedrainage.
El
1 Pour a glass of water on the evapomtor.
2 Ensurethat water flows through the drain
hose of the indoor unit without any leakage
and goes out the drain exit.
WARNING:
>’.Be sure to refer to the wiring diagram-seeMini
Manual. Improper tigcan cause the unit to
opemte incorrectly and result in a tie hazard.
~~Check local electrical codes and any spec~led
wiring instructions or limitations.
~Attach thegrilleonto thecabimzt
-
Grasp the lower part of the left and right
1
sides of the grille and engage the four tabs
on the top inside edge of the chassis.
2
Press the grille toward the chassis until it
clicks back into place.
Reinstall the (3) retaining screws.
3
4 Close grillefront.
/f-
23
Installationinstructions.
Form thepipings bywrappingtheconnecting
El
portion of the indoor unitwithinsulation
matexial andsecure
(for the rightpipings).
If you want to connect an additional drain
hose, the end of the drain outlet should be
routed above the ground. Secure the drain line
appropriately.
;: If the outdoor unit is being installed below the
positionof theindoor unk
1
Tape the pipings, drain hose and connecting
cable fi-om down to up.
2
Form the pipings gathered by taping along the
exterior wall and fix them onto the wall by
saddle or equivalent.
around pipings with
a gum type sealer.
itwithtwoplasticbands
the outdoor unitis being installedabove the
!’: H
positionof theindoor uniti
1 Tape the pipings and connecting cable horn
down to Up.
2 Form the pipings gathered by taping along the
exterior wall. The trap should be formed up to
prevent water from entering into the room.
3 Fix the pipings onto the wall by saddle or
equivalent.
Seal small openings
around pipings with
a gum type sealer.
●Trap is required to prevent water from
entering into electrical parts.
Drain hose
A plasticdrainelbow isprovided withthe
❑
outdoor heatpump unitfor routingany
condensationawayfi-om the outdoor unit
basepan.Attach the elbow to the basepan
nearthecompressor and then attacha hose
(thatyouprovide) to the other end to route
thewateraway.
24
~t;Pressure in the system rises,
@ Operating current rises,
..<
“ Cooling (or heating) efficiency drops.
~’~Moisture in the refrigerant circuit may freeze and
block capillary tubing.
‘~’”Water may lead to corrosion of parts in the
refrigemnt system.
The indoor unit and tubing between the indoor
and outdoor units must be leak-tested and the
system evacuated to remove any noncondensables
and moisture.
N0712 The outdoor unit contains /?22 chatge for the
total system.
❑ ~P*~*a=mwpwp.
Preparation:
Check that each tube (both liquid and gas side
tubes) between the indoor and outdoor units has
been properly connected and all wiring for the test
run has been completed. Remove the valve caps
fi-om both the gas and the liquid side semice valves
on the outdoor unit. Note that both liquid and gas
side service valves on the outdoor unit are kept
closed at this stage.
N07E: The outdoor unit contains /?22 charge for the
total system.
4 After the system is found to be free of leaks,
relieve the nitrogen pressure by loosening the
charge hose connector at the nitrogen cylinder.
When the system pressure is reduced to normal,
disconnect the hose from the cylinder.
Indoor unit
Pres
Charge hose
Leak Test:
Connect a manifold valve (with pressure gauges)
1
and dry nitrogen gas cylinder to the suction
semice port.
2 Pressurize the system to no more than 150
P.S.I.G. with&y nitrogen gas and close the
cylinder valve when the gauge reading reaches
150 P.S.I.G. Next, test for leaks with liquid soap.
lYURION: Toavoid nitrogen entering the refrigerant system
in a /iquid state, the top of the cy/inder must be higher than its
bottom vvhenyou pressurize the system. Usuall~ the cylinder
is used in a vertical standing position.
3 Do a leak test of alljoints of the tubing (both
indoor and outdoor) and both gas and liquid side
sewice valves. Bubbles indicate aleak. Be sure to
wipe off the soap with a clean cloth.
Nitrogen gas cylinder
(in vertical standing
position).
r
25
Installation instructions.
Evacuation:
Connect the charge hose end described in the
preceding steps to the vacuum pump to evacuate
the tubing and the indoor unit. Confirm that the
“Lo” knob of the manifold valve is open. Run the
vacuum pump, The operation time for evacuation
varies with the tubing length and capacity of the
pump.
Allow the pump to operate until the system has
been evacuated down to 300 microns. Allow the
pump to continue running for an additional 15
minutes, Turn off the pump and leave the
connections secured to the two service valves. After
5 minutes, if the system fails to hold 500 microns or
less, check all connections for tight fit and repeat
the evacuation procedure.
Finishing the Job:
With a service valve wrench, turn the valve stem of
1
the liquid side valve counterclockwise to fidly
open the valve.
Turn the valve stem of gas side valve counter-
2
clockwise to folly open the valve.
3
Lmosen the charge hose connected to the gas side
service port slightly to release the pressure, then
remove the hose.
Pressure
gauge
Manifold valve
Indoor unit
~
-
I
4
Replace the flare nut and itsbonnet on the gas
side semice port and fasten the flare nut securely
with an adjustable wrench. This process is very
important to prevent gas leaks in the system.
5
Replace the valve caps at both gas and liquid side
se&ice valves and fro-ten them securely and
tightly.
This completes air purging with a vacuum pump.
The system is now ready to test run.
For anyservicewhichrequiresentry
rntothe refrigerantsealedsystem,
Federalregulationsrequirethework
be performed by atechnicianhavinga
ClassII or Universalcertification.
Vacuum pump
26
2 Check that the gas and liquid side semice valves
are fully open.
Opemte the system for 15-20 minutes. Check the
system refi-igerant charge:
1 Measure the pressure of the gas side service valve.
2 Measure the outside ambient air tempemture.
N07E: Refer to the Mini-Manual supplied with the unit for
the systems operating amperage and evaporator discharge air
temperature at the various ambient levels. At a ~pical outdoor
ambient temperature of 95° ~ the gas (suction)pressure at the
outdoor unit should be 70-75 PS.I.G. in cooling mode.
For anysavice whichrequiresentry
intotherefrigerantsealed system,
Federalregulationsrequirethework
be performed by a technicianhavinga
ClassII or Universalcertifkation.
27
u
Installationinstructiontemplates.
LeftSideInstallation
T
-
.
.
■
I
‘q
-
.
I
●
I
■
I
—.—.—.—.—.—.—.—.
Installation plate
28
I
----------.
Installation plate
RightSideInstallation
--
-
AS ICD09
ASIRD09
AS1CD12
ASIRD12
n
m
I
■
I
■
I
I
.
I
.
+
■
I
Piping hole
-
0 2-3/4”
ASICD18
ASIRD18
29
Beforeyou call for service...
hbf%m,‘ ‘:,:::’;”’;:’‘ :;’,’,::
the Systm
Possible Causes
‘Ihe fbse isblown/circuit● Check the house fuse/circuit breaker box and replace
doesnotstartbreaker istripped.
The Timer operation
is not set comedy.
tit does not
The
operate when restarted.
7hesystemdoesAirflow isrestricted.
notcoolorheatas
it should
The temperature control may● Turn to a lower or higher setting. The lowest setting
not beset highor lowenough.
/
l%eairfikerisdi
The room may havebeen hot
or cold.
Cold or warm air is escaping.
rty.
Theremote controlThe batteries may be dead.
display is faint orshows
no dispiay at all
The batteries are inserted
incorrectly.
What ToDo
thefme or reset the breaker.
● ~eck the Tier f~ctions ad make s~e hey we
setto the desired settings.
● This is normal. Wait about 3 minutes and the unit
will restart.
● M~e Swe thereme no ~~s,b~ds or~i~re
blocking the front of the system.
provides maximum cooling. The highest setting provides
maximum heating (heat pumps only).
● Clean the filter at least eveq 30 days.See the Operating“
Instructions section.
● When the system isfirst turned on you need to allow
tine for the room to cool down or warm up.
● Check for open furnace floor registers and cold
air returns.
● Replace the batteries.
● Check the position of the batteries. They should be
inserted in the opposite (+) and (—) direction.
30
Normal Operating Sounds
You may hear a sound like water flowing. This is
the sound of refrigerant flowing inside the system,
‘ A noise that sounds like air being released isa
design feature of dehumidifjingwaterbeing
processed inside the system.
You may hear a clicking noise when you start or
stop the unit. This sound isthe expansion or
contraction of the unit due to changes in the
tempemture.
Split System Warranty
All warrantyserviceprovidedby our FactoryServiceCenters,
an authorizedCustomerCare@ technician.For service,
or
a
Etr ZhePeriod OkGE Will Replace, At No Charge To You:
call 800-GE-CARES.
One Year
From the date of theDuring this fidl one-year
original purchase
Five Yea=Any part of the sea/ed retiigerating system (the compressor, condenser, evapomtor and internal
From the date of the
original purchasefive-year warra~,GE will also provide, ikee of charge, all labor and in-home service to replace
/%r each of the shove warranties: Transportation expense to and from a service shop and shop service labo~ if required,
will be free of charge.
Anypart of the split system air conditioner which fids due to a defect in materials or workmanship.
warrantyGE will also provide, free of charge, all labor and in-home
service to replace the defective part.
connecting tubing) which fails due to a defect in materials or workmanship. During this
the defective part.
What GE VW, Not Cuvec
Servicetripstoyour home to teachyou how to use theReplacement of house fuses or resettingof circuit
productibreakers.
Improper kstallation. If youhavean installationproblem,
or if thesplitsystem airconditioneris of improper cooling
capacityfor the intended use, contactyour dealeror
installer.You are responsible for providing adequate
electricalcomectingfacilities.
Failureof theproduct resultingfrom modifkations to tbe
product or due to unreasonableuseincludingfailure to
providereasomble and necesszuymaintenance.
Incommercial locations, labornecessaryto move the
unitto a location where itis accessiblefor serviceby a
technician.
Failuredue to corrosionon models not coxrosionprotected.
Damage to the product or systemleakscaused by
improper field-ktalled interconnectingtubing between
indoor and outdoor units,improper power supply voltage,
acciden~ fwe, floods or acts of God.
Incidentalor consequential damage topersonal
property caused by possible defects withthissplit
@emairconditioner.
This warrantyis extendedto the original purchaserand any succeedingowner for productspurchasedfor home
use within the USA. In Alaska, the warranty excludesthe cost of shippingor service calls to your home.
Some states do not allow the exciusionor limitationof incidentalor consequentialdamages.This warrantygives
you specificlegal rights, and you may also have other rights which vary from state to state. To know what your
legal rights are, consult your local or state consumeraffairs office or your state> AttorneyGeneral.
Warrantor: General
Electric Company. Louisville, KY 40225
37
2
Q
1-
Sewice TelephoneIVumbem
%
~
●-
3
*
<.,.,,.!$,~,~;,z~,l.,,,,
s
‘GEAnswerCente?auMm20m
The GE Answer Center@ is open 24 hours a day, 7 days a week.
Special Needs Service muiazmo
8fM-TDD-G&4C (MUM?MH2)
c-
*-
%
&
‘“%Service Contracts 8wizw224
%jZjzj+e
&~,,
~;;$~;<,<
g‘;’’”
●%
~o
al
*
]~[~;’:::1.
,~,i,:>,$,;,:
GE offers, free of charge, a brochure to assist in planning a barrier-free kitchen for persons
with limited mobility.
Purchase a GE service contract while your
substantial discount. GE Consumer Service will still be there after your
warranty is still in effect and you’ll receive a
warmnty expires.
Parts and Accessories m-=-=
Individuals qualified to service their own appliances can have parts or accessories sent directly
to their homes (VISA, MasterCard and Discover cards are accepted).
~
w
*
i
~
I
Servicing and installation of the refi-igerant system must be performed only by a licensed,
HVAC cefiledtechnician.
Instructions contained in this manual coverprvcedures tobe perfbrmed by any usez (lthersem”cing
generally should be retiwmd to qualified service pemonnel. Caution must be exemised, since
imprvper sem-cing may cause unsafa operation.
E
g)
~-
~
J
br anysem-ce which requires entry into the retiigemntsealed system, hderal regulti-ons
requim the work be pehrmed by a technician having a ClassII or Universal certification.
\
Service Satisfaction
Ifyou are not satisfied with the service you receive from GE:
Fi~ contact the people who semiced your appliance.
NeX ifyou are still not pleased, write all the details-includingyour phone number-to:
Manager, Consumer Relations
GE Appliances
Appliance Park
Louisville, KY40225
finall~ ifyour problem is still not resolved, write:
Major Appliance Consumer Action Progmrn
20 North Wacker Drive
Chicago, IL 60606
Printed in the United States
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.