GE AM8, AM9 Installation Guide

GE
g
READ THOROUGHLY BEFORE INSTALLING
Lighting Solutions
Edison® IV /
Americana
GEH-5835
INSTRUCTIONS
®
Luminaire
WARNING
Risk of electric shock
Turn power off before servicingsee instructions
GENERAL
This luminaire is designed for use in outdoor applica­tions and must adhere to 25° C Max ambient temperature limitation. Install and maintain it according to the follow­ing recommendations.
CAUTION
Unit will fall if not installed properly
Follow installation instructions
Caution: only globes equivalent in weight to those of polycarbonate are recommended for use with this fixture. If a heavier globe, such as glass is used, it must be removed before swinging base open to access photo control, ballast & etc.
These instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with installation, operation or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to GE Lighting Solutions.
WIRING
Make all electrical connections in accordance with
the National Electrical Code and any applicable
local code requirements
Verify that supply voltage is correct by comparing it
to nameplate.
IF SINGLE VOLTAGE:
All single voltage ballasts are pre-wired such that user need only connect the supply conductors.
IF MULTIVOLT: (120/208/240/277 volts)
Connect the ballast lead with the insulated terminal to the desired voltage terminal as indicated on the ballast terminal nameplate.
IF MULTIWATT:
Multiwatt ballasts are available in various combinations of wattage. See wiring instructions on wiring tag inside the luminaire.
LAMPS
CAUTION
Risk of burn
Allow lamp/fixture to cool before
handling
Use only lamps specified on nameplate. Observe
lamp manufacturer’s recommendations and restric-
tions on lamp operation, particularly ballast type,
burning position, etc.
LAMP TIGHTNESS: The lamp should be securely inserted to NEMA-EEI specified torque of 35 inch­pounds, which is best achieved by very firmly tightening to insure application of sufficient torque. Tightening must be sufficient to fully depress and load center contact of socket.
MAINTENANCE
Clean globe by washing with mild nonabrasive detergent solution. Rinse with clean water.