Note: All relays must be powered up at least once per year to avoid
deterioration of electrolytic capacitors and subsequent relay failure.
GE Power Management
215 Anderson Avenue, Markham, Ontario
Canada L6E 1B3
Tel: (905) 294-6222 Fax: (905) 294-8512
Internet: http://www.GEindustrial.com/p m
Manufactured under an
ISO9002 Registered system.
These instructions do not purport to cover all details or variations in equipment nor provide for every possible contingency
to be met in connection with installation, operation, or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purpose, the matter should be referred to the
General Electric Company.
To the extent required the products described herein meet applicable ANSI, IEEE, and NEMA standards; but no such
assurance is given with respect to local codes and ordinances because they vary greatly.
Before attempting to install or use this relay, it is imperative that all WARNINGS and CAUTIONS in this ma nual are reviewed to help prevent personal injury, equipment damage, and/or downtime.
NOTE
Unpack the relay, the mounting brackets, and the hardware for attaching the mounting brackets to the sides of the relay.
Examine the rela y for an y dam age sustained in t rans it , and if damage is ev id ent, no tify the shipping c om pa ny an d the nearest GE Power Management sales office immediately.
Prior to applying power, ensure that the model number of the relay listed on the front panel corresponds to the model
ordered. Make sure that the DC supply power matches the rated voltage listed on the front panel. Refer to the elementary
diagrams on pages 1–49 to 1–52 for the locations of the DC power inputs
Instructi ons o n using the keypad to c hange s etti ngs an d put t he rel ay in to te st mode can b e fo und in Secti on 4.1 .7: SE TTING CHANGES on page 4–3. Complete instructions on operating the keypad are found in Chapter 8: LOCAL USER
INTERFACE.
GE Power Management contact information:
GE Power Management
215 Anderson Avenue
Markham, Ontario
Canada L6E 1B3
Telephone:Toll Free North America:(800) 547-8629
Europe+34 94 485 88 54
Other Areas(905) 294-6222
Emergency(416) 414-4941
Fax:(905) 201-2098
Email:info.pm@indsys.ge.com
Home Page:www.GEindustrial.com/pm
1
1.1.2 PASSWORDS, FACTORY SET
The ALPS requires passwords to change settings or perform actions. No password is required to obtain information from
the relay, including viewing the existing settings. The relay is shipped from the factory with the following MMI passwords:
SETTINGS: 123.
ACTIONS: 456.
MASTER: 789.
The decimal point following the digits is part of the password. Factory passwords MUST be changed
before the user can modify settings or initiate Actions.
NOTE
In order to change the default password, follow these steps:
1.Press the ACTIONS key [ACT].
2.Press the ENTER key [ENT].
3.Scroll to the CHANGE PASSWORD option.
4.Select the Password Privilege level to be changed.
5.Press [ENT].
6.Enter the factory password (for example: 789. for Master Password).
7.Enter your password.
8.Re-enter your password.
9.Press [END], press [ENT], and then press [CLR].
The keypad passwords stored in the relay may be viewed, in encoded format, via remote communications.
GE Power Management
ALPS Advanced Line Protection System1-1
1.1 GETTING STARTED1 PRODUCT DESCRIPTION
1.1.3 REMOTE COMMUNICATIONS VIA LOCAL PC
1
To communicate with the relay through a PC, connect the relay to a serial port of an IBM-compatible computer with a
null-modem cable. Connection can be made either to the 25 pin D-connector on the back of the relay (PL2A), or the 9 pin
D-connector on the front (PL1). Cable diagrams are shown in the following:
•Figure 8–2: MODEM CABLE on page 8–23
•Figure 8–3: 25-PIN NULL MODEM CABLE on page 8–23
•Figure 8–4: 25-PIN NULL MODEM CABLE on page 8–27
•Figure 8–5: NULL MODEM CABLE FOR PORT PL1 on page 8–27
The communications software required to access the relay, ALPS-Link, is included on the enclosed Products CD. Follow
instructions in Section 11.1.5 SOFTWARE INSTALLATION on page 11–3 to load ALPS-Link onto the PC.
1.1.4 ALPS-LINK QUICK REFERENCE
The ALPS relay requires the use of passwords to obtain information from the relay, to change Settings, or to perform
Actions. The relay is shipped from the factory with the following communications passwords:
The exclamation point following the letters is part of the factory password. The factory passwords MUST
be changed before the user can modify Settings or initiate Actions. The user can log into the relay at any
NOTE
password level. After logging into the relay, the password can be changed under the ACTION menu by
selecting CHANGE PASSWORD.
The user must logout from the ALPS before changing another password. The remaining passwords can then be changed
by logging into the ALPS using another default password. The communications passwords may be viewed, in an encoded
format, via the [INF] (information) key.
To log into the relay, follow the instructions in Section 4.1.9: USING COMMUNICATIONS (OPTIONAL) on page 4–4. Any
one of the factory passwords can be used to log on to the relay. The relay UNITID (General Setting 101) is factory set to
"0".
1-2ALPS Advanced Line Protection System
GE Power Management
1 PRODUCT DESCRIPTION1.1 GETTING STARTED
1.1.5 ORDERING
Table 1–1: ORDER CODES
ALPS * * * * * * * * * * * * – *
Base Unit
Distance Relay
Revision
Tripping Logic
Current Rating
Series
Capacitors
Battery
Voltage
Trip Outputs
Comm Ports
Mounting
Oscillography
ALPS
|||||||||||| |
D
| | || | | | | || ||
A
|||||||||| |
B
|||||||||| |
1
| | || | | | |||
3
| | || | | | |||
1
|||||||| |
5
|||||||| |
U
| | || | | ||
C
| | || | | ||
0
|||||| |
1
|||||| |
2
|||||| |
1
| | || ||
2
| | || ||
3
| | || ||
4
| | || ||
2
|||| |
3
|||| |
H
| | ||
V
| |||
S
E
OST / Positive
Sequence
Overvoltage
Recloser
Protocol
† These options are applicable to Revision A models only.
|| |
|| |
0
||
1
||
2
||
3
||
N
R
S
Base Unit
Distance Relay
ALPS Revision A
ALPS Revision B
Single Phase Tripping Logic
Three Phase Tripping Logic
1 Ampere rated current
5 Ampere rated current
For applications without series capacitors
For Applications with series capacitors
48V DC battery voltage
110/125 V DC battery voltage
220/250 V DC battery voltage
SCR trip outputs & contact channel interface
Contact trip outputs & contact channel interface
SCR trip outputs & 5V / 20mA channel interface
Contact trip outputs & 5V / 20 mA channel interface
Front RS232 port & 1 settable RS232/RS485 rear port (GEmodem/ASCII)
Front RS232 port & 2 settable RS232/RS485 rear ports (GEmodem/ASCII)
Horizontal mounting
Vertical mounting
Standard oscillography memory
Extended oscillography memory
No out-of-step tripping or positive sequence overvoltage
With out-of-step tripping
With positive sequence overvoltage units
With positive sequence overvoltage units & out-of-step tripping
No recloser
|
Recloser
|
Recloser with sync check
|
AC
Modbus RTU communication
†
†
†
†
†
EXAMPLE: ALPSDA35U122VE1N = ALPS Digital Line Protection Distance Relay; revision A; three phase tripping logic;
rated at 5 amperes; without series capacitor protection; 110/125 VDC supply; contact tripping outputs; 2 communications
ports; vertical mounting; with extended memory; without OST functions; and no recloser.
1
†
GE Power Management
ALPS Advanced Line Protection System1-3
1.2 INTRODUCTION1 PRODUCT DESCRIPTION
1.2 INTRODUCTION1.2.1 DESCRIPTION
1
The Advanced Line Protection System (ALPS) is a microprocessor-based digital relay system that uses waveform sampling with appropriate algorithms to provide three phase or single phase tripping schemes for transmission line protection,
fault location, and related features. The models covered by this instruction book are intended for either three phase or single phase tripping applications. The relay samples the current and voltage inputs from the power system 64 times per
cycle. Protection algorithms process this sampled data in sets of four, sixteen times per cycle. The ALPS uses advanced
Fourier calculation techniques and adaptive measuring functions to achieve high-speed tripping for severe faults.
The ALPS is packaged in a compact 3 Rack Unit high (one RU = 1.75 Inches) 19-in ch rack moun t cas e and is ava il abl e for
either horizontal or vertical mounting. The case outline and mounting dimensions are shown in Figure 3–2: FRONT AND
REAR VIEW on page 3–2.
All models include a f ull ke yp ad a nd a liquid crystal displa y (LCD ) for local access to re lay da ta an d s etti ngs . In add iti on, up
to three communicatio n po rts are pro vided for both l ocal and rem ote ac cess with a PC. Each port may be indepe ndentl y set
for ASCII or GEmodem protocols.
1.2.2 APPLICATION
The models covered by this instruction book are designed to be used on transmission lines of any voltage level, with or
without series capacitor compensation, where either single or three-phase tripping is required. Detailed application considerations are described in this chapter and in Chapter 2: CALCULATION OF SETTINGS.
The ALPS can provide high speed detection and clearing of power system faults, and includes logic for step distance and
five standard pilot tripping schemes. The scheme logic is described in Section 1.8: PROTECTION SCHEMES on page 1–
23. The external connections for the ALPS are shown in the elementary diagrams on pages 1–49 to 1–52.
The ALPS is available with either a contact interface to the pilot channel equipment or an electronic (5 V, 20 mA) interface
so that the relay may b e appl ied with a wi de vari ety of chann el equ ipmen t. Typical cha nnels incl ude: AM and FSK via po wer
line carrier (PLC), FSK via microwave, and multiplexed fiber optic cable.
1.2.3 PROTECTION FUNCTIONS
The measurement functions are listed in Table 1–2: ALPS MEASUREMENT FUNCTIONS on page 1–5.
The Zone 1 distance functions provide secure high-speed tripping for all fault types over most of the protected line. The
Zone 1 ground distance functions can be selected to be either ground variable-Mho distance functions, or ground-reactance distance functions. The ALPS also offers ground quadrilateral distance functions as Zone 1 ground distance functions. A unique adaptive reach for the supervising Mho characteristic is used when ground-reactance functions are
selected.
Overreaching Zone 2 p has e and ground distance func tio ns are us ed fo r pi lot tripping schemes. G ro und -directional overcurrent functions can be selected to replace or supplement the overreaching zone (Zone 2) ground-distance functions in any
of the pilot schemes. The ALPS also offers Zone 2 ground quadrilateral characteristics. The Zone 2 phase and ground distance functions are provided with independent timers for time delayed backup protection.
Overreaching Zone 3 phase and ground distance functions are provided with independent timers for time delayed backup
protection. The ALPS also has the option for quadrilateral ground-distance functions.
The Zone 4 variable-Mho distance functions can be reversed in direction when a reversed or blocking function is required.
When the POTT 2, Blocking or H ybrid scheme i s selected, Zon e 4 is automatic ally set to the rev erse directi on, because
these schemes require a reverse-looking blocking function. The Zone 4 phase and ground distance functions are provided
with independent timers for time delayed backup protection. The ALPS with three phase tripping also has the option to use
Zone 4 ground quadrilateral distance functions for time-delayed backup protection.
When both phase and ground distance functions are used for a zone of protection, six individual measuring functions are
available: three fo r pha se dis tan ce and thre e for ground distance. The alg orit hm that im ple me nts the variable-Mho measuring functions is derived from designs that have evolved through several different families of static analog and digital relay
systems which have accumulated decades of dependable and secure in-service experience.
An instantaneous overcurrent tripping function (50G) provides direct tripping for severe phase-to-ground faults. Time-overcurrent tripping (51G) provides time-delayed backup tripping for phase-to-ground faults. Either or both of these groundovercurrent functions can be controlled by the NT negative-sequence directional trip unit, at the customer’s discretion.
1-4ALPS Advanced Line Protection System
GE Power Management
1 PRODUCT DESCRIPTION1.2 INTRODUCTION
Table 1–2: ALPS MEASUREMENT FUNCTIONS
ZONE OR TYPEFUNCTIONS
Zone 1•3 Variable-Mho phase-distance functions
•3 Variable-Mho ground-distance functions
•3 Reactance ground-distance functions with “adaptive reach” Mho supervision
3 Quadrilateral ground-distance functions (Revision B relays only).
Zone 2 (Pilot Zone)•3 Variable-Mho phase distance functions
Phase Undervoltage•Three fixed pickup phase undervoltage detectors
Phase Over / Undervoltage•T hree adjustable over or under voltage detectors with time delay
Positive-Sequence Voltage
Detectors
Out of Step Tripping (OST)•3 Variable-Mho positive sequence-distance functions
•V1,
•V1 compensated
and/or
or
or
or
1
1.2.4 GROUND DISTANCE QUADRILATERAL CHA RACTERISTICS
The ALPS relay has been modified to include the option to use either quadrilateral characteristics or variable Mho characteristics for all zones of ground distance protection. The model numbers affected by this modification are: ALPSDB
XXXXXXXXX
(where X may be any valid character) with firmware version V0005.00AA00 or higher. A new version of
ALPS-Link may be required to access the new settings via remote communications (ALPS-Link must be version 3.5 or
higher). If required, the updated version of ALPS-Link may be downloaded from the GE power Management website at
www.GEindustrial.com/pm
.
Many protective re la y engineers prefer to us e a qua dri late r al (p oly gon al ) c hara ct eris tic f or grou nd di stance functions to p rovide more fault resistance coverage than the circular mho characteristic. A typical quadrilateral characteristic is shown in
Figure 1–1: GROUND DISTANCE QUADRILATERAL CHARACTERISTIC. The characteristic is comprised of four straight
lines; the trip zone is the inside area bounded by all four characteristics. The upper boundary, the reactance characteristic,
may also be used with a variable mho function. The variable mho provides both directional supervision for reverse faults.
and resistive limits to prevent operation on load.
In the ALPS r el ay t he fo ur strai ght line s of th e qu adri lat eral cha rac teri sti c are deve lop ed b y a combin ati on of th e fo llo wing
three characteristics:
1.Reactance characteristic (section 1). The tilt of the reactance characteristic is determined by the characteristic timer
setting. The range of the setting is 80° to 155° in 1° steps.
2.Restricted directional characteristic (sections 2 and 4)
3.Ri ght (pos iti ve ) resist ive bli nder (section 3)
The following definitions pertain to all of the distance functions:
I
= phase A current at relay
A
I
= phase B current at relay
B
I
= phase C current at relay
C
I
= zero-sequence current at relay
0
V
= phase A to ground voltage at relay
A
V
= phase B to ground voltage at relay
B
V
= phase C to ground voltage at relay
C
X
= positive-sequence component of
1
X
= negative-sequence component of
2
= memory (pre-fault) value of
X
M
Z
x
= Zone x positive-sequence reach setting:
1
Z
x
= Zone x zero-sequence reach setting:
0
Note: The magnitudes of
K
1 = Zone 1 zero-sequence compensation factor: Z1K0
0
K
= zero-sequence compensation factor
0
Zx
X
1
and
X
X
ZxR
∠ POSSEQANG
ZxR
∠ ZERSEQANG
Zx
are identical - these quantities differ in phase angle only.
0
a) REACTANCE CHARACTERSTIC
The reactance characte ris tic us ed f or the ground quadrilateral is the si mi lar a s th e ex is tin g ne gat ive / zero sequence phase
angle comparator reactance characteristic. The function has been modified by the addition of a fourth comparator input
(Pol. #3). The operate and polarizing signals used in this function are:
Operate:
Pol.# 1:
Pol.# 2:
Pol.# 3:
where:
Iφ′Z
–
Vφ
I0Z
1
I2Z
1
I
Z
1
F
1
Iφ′Z
is the compen sated IZ product
Z
is the positive sequence replica impedance
1
Vφ
is the phase to ground voltage
I
is the zero sequence current component
0
I
is the negative sequence current component, referenced to the proper phase.
2
I
is the fault component of the positive sequence current component, referenced to the proper phase.
1
F
The pre-fault load current is removed from this quantity.
1-6ALPS Advanced Line Protection System
GE Power Management
1 PRODUCT DESCRIPTION1.2 INTRODUCTION
All zones of ground reac tan ce ch arac teri st ics w il l ha ve a c hara cte ris tic tim er wi th a pic ku p ran ge of 90 to 1 55° i n s teps of 1.
The characteristic timer setting will be used to “tilt” the reactance characteristic (Tent) to prevent over-reach on non-homogeneous systems, as shown below. Note that the “tent” is not the same as tilting the reactance because it also tilts down to
the left of the maximu m re ach bal anc e point. By adjusting the an gle of the phase angle comparator rat her th an the angle of
“maximum torque”, the transient over reach is not increased.
X
“TENT” CHARACTERISTIC
1
4
R
3
2
TENTCHAR.CDR
Figure 1–2: TENT CHARACTERISTIC
For the Zone 1 ground function, the signals are:
I
-
I
)·Z11 +
K
1·
I
·Z10 –
·Z10 –
·Z10 –
V
V
A
B
V
C
Phase A:(
Phase B:(
Phase C:(
I
A
I
0
I
A1F
I
I
B
I
0
I
B1F
I
I
C
I
0
I
C1F
A
2
·Z1
-
B
2
·Z1
-
C
2
·Z1
·Z1
·Z1
I
·Z1
·Z1
·Z1
·Z1
0
1
0
1
I
0
1
1
1
)·Z11 +
1
1
)·Z11 +
1
1
0
0
K
1·
I
0
0
K
1·
I
0
0
1
b) RESTRICTED DIRECTIONAL CHARACTERISTIC
The restricted directional characteristic for the ground quadrilateral requires a separate directional unit for each phase. No
settings are required for this characteristic. The input signals to the comparator are:
Phase A:
Phase B:
Phase C:
I
·
ZD
A
V
A
I
·
ZD
B
V
B
I
·
ZD
C
V
C
where ZD is the angle of “maximum torque” and is equal to 65°.
The characteristic timer angle will be fixed at 115°. That is, the function will operate when the input signals are within ±65°
of each other.
If the faulted p has e vo lta ge magnitude is too low (as fo r a c los e-i n Zon e 1 fault), the phase d ire cti ona l fun cti on w il l n ot op er-
ate. This might also occur for a remote fault when the relay is located near a strong source. Therefore, if the phase voltage
is less than the minimum threshold voltage, the positive-sequence memory voltage from the ground Mho functions is used
in place of the phase voltage to polarize the directional function.
GE Power Management
ALPS Advanced Line Protection System1-7
1.2 INTRODUCTION1 PRODUCT DESCRIPTION
c) RIGHT RESISTIVE BLINDER
The right resistive blinder is a two input phase angle comparator. The input signals for the comparator are:
1
Operate:
Polarize:
Iφ′·RB
Iφ′·RB
1 1
Vφ
where:
The magnitude of
RB
1 (Right Blinder for Zone 1) is the point at which the characteristic intersects the R
axis. The range of adjustment will be 0.1 to 500.0 ohms in 0.1 ohm steps.
The angle of RB1 is be fixed based on the positive sequence line angle, the zero sequence line angle,
The characteristic timer angle will be fixed at 90°. For the Zone 1 ground function, the operate and polarizing signals are:
Phase A:
Phase B:
Phase C:
I
′·RB1 –
A
I
′·RB1
A
I
′·RB1 –
B
I
′·RB1
B
I
′·RB1 –
C
I
′·RB1
C
V
A
V
B
V
C
where:
I
I
I
K
A
B
C
0
′ = (
′ = (
′ = (
1 = |
I
-
I
) +
K
1·
A
0
I
-
I
) +
B
0
I
-
I
) +
C
0
K
1| – (ZERSEQANG – POSSEQANG)
0
I
0
0
K
1·
I
0
0
K
1·
I
0
0
1.2.5 LINE PROTECTION SCHEMES
The ALPS provides four zones of distance protection with overcurrent backup functions. The ALPS is a highly flexible system: along with predefined protection schemes, it also has the ability to be programmed by the user. The custom programmability of the ALPS is discussed in the next section.
The ALPS pilot protection schemes are as follows:
•Permissive Underreach Transfer Trip (PUTT)
•Permissiv e Overreach Transfer Trip (POTT1)
•Permissiv e Overreach Transf er Trip with blocking functions (POTT2)
•Blocking
•Hybrid
•Phase Identified Channel
In addition, each of the above schemes includes up to four zones of step distance backup with individual timers for phase
and ground zones.
1-8ALPS Advanced Line Protection System
GE Power Management
1 PRODUCT DESCRIPTION1.3 CUSTOM PROGRAMMABILITY
WARNING
1.3 CUSTOM PROGRAMMABILITY1.3.1 INTRODUCTION
The ALPS offers a high degree of custom programmability. Custom programming of the ALPS is accomplished using
Xpression Builder. Xpression Builder is a Windows based program that allows the user to design programmable logic and
make I/O (Input/Output) assignments for the ALPS and other GE Power Management relays. Xpression Builder is included
with ALPS software suite on the GE Power Management CD. A complete description of Xpression Builder is included in
Chapter 13: XPRESSION BUILDER.
1.3.2 PROGRAMMABLE LOGIC
In addition to the pre-programmed line protection schemes and configurable I/O, the ALPS relay includes the capability for
the user to design c ustom lo gic. This l ogic may be use d to suppl ement or to repl ace the built-i n sche me lo gic. Th e program mable logic includes the following: up to 40 logic gates (AND, OR, NOT), each with up to 4 inputs; 8 programmable timers
each with a settable pickup and dropout delay; 8 counters; and 8 latches.
1.3.3 CONFIGURABLE INPUTS
All of the contact converters (Digital Inputs) in the ALPS are user configurable. However, each ALPS relay is shipped with
Default Contact Converter Assignments as shown below and on the default elementary diagrams on pages 1–49 to 1–52.
Each configurable input can be assigned only one flag – assigning more than one flag to a configurable
input may cause maloperation!
Table 1–3: ALPS DEFAULT CONTACT CONVERTER ASSIGNMENTS: SINGLE PHASE MODEL
All of the output relays in t he AL PS, ex ce pt for the alarm output relays , are us er-c onf igu r abl e. Ho w ever, each ALPS re la y i s
shipped with Default Output Relay Assignments. These are shown below and in Figure 1–28: ELEMENTARY DIAGRAM
WITH DEFAULT I/O (THREE PHASE TRIPPING) on page 1–50 for the three phase model and Figure 1–27: ELEMENTARY DIAGRAM WITH DEFAULT I/O (SINGLE PHASE TRIPPING) on page 1–49 for the single phase model.
Table 1–5: ALPS DEFAULT OUTPUT CONTACT ASSIGNMENTS: SINGLE PHASE MODEL
RELAYDESCRIPTIONMNEMONICINDEX NO.
T1TRIP BUS PHASE ATRIPA33
T2TRIP BUS PHASE ATRIPA33
T3TRIP BUS PHASE ATRIPA33
T4TRIP BUS PHASE ATRIPA33
T5TRIP BUS PHASE BTRIPB34
T6TRIP BUS PHASE CTRIPC34
A1M ANUAL CLOSE BREAKER 1MNCLS158
A2M ANUAL CLOSE BREAKER 2MNCLS259
A3TRIP BUS PHASE ATRIPA33
A4TRIP BUS PHASE ATRIPA33
A5THREE PHASE RECLOSE INITIATERI-3P37
A6THREE PHASE RECLOSE INITIATERI-3P37
A7RE CLOSE CANCEL OUTPUT FROM SCHEME LOGICCANCL38
A8 to A12UNASSIGNED-----KT1KEY TRA N SMITTER 1 / CARRIER START #1KEY139
KT2KEY TRA NSMITTER 2 / CARRIER STOP #1KEY24 0
KT3KEY TRA N SMITTER 1 / CARRIER START #1KEY139
KT4KEY TRA N SMITTER 2 / CARRIER START #2KEY240
C1NON-CRITICAL ALARMNCALM52
C2PT FUSE FAILURE ALARMFF115
Table 1–6: ALPS DEFAULT OUTPUT CONTACT ASSIGNMENTS: THREE PHASE MODEL
RELAYDESCRIPTIONMNEMONICINDEX NO.
T1TRIP CIRCUIT #1TRIPA33
T2TRIP CIRCUIT #2TRIPA33
T3TRIP CIRCUIT #3TRIPA33
T4TRIP CIRCUIT #4TRIPA33
A1MANUAL CLOSE CIRCUIT BREAKER #1MNCLS158
A2MANUAL CLOSE CIRCUIT BREAKER #2MNCLS259
A3BREAKER FAILURE INITIATE #1TRIP A33
A4BREAKER FAILURE INITIATE #2TRIP A33
A5RECLOSE INITIATE #1RI_3P37
A6RECL OSE INITIATE #2R1_3P37
A7RECLOSE CANCELCANCL38
A8RECLOSE CANCELCANCL38
KT1KEY TRA N SMITTER 1 / CARRIER START #1KEY139
KT2KEY TRA NSMITTER 2 / CARRIER STOP #1KEY24 0
KT3KEY TRA N SMITTER 1 / CARRIER START #1KEY139
KT4KEY TRA N SMITTER 2 / CARRIER START #2KEY240
C1NON-CRITICAL ALARMNCALM52
C2PT FUSE FAILURE ALARMFF115
Because a distance o r di rectio nal fun ction ma y o perate fo r a full or parti al los s of AC po tentia l caus ed by one or m ore blo wn
fuses, PTFF is provided to block distance and directional function tripping when a fuse failure is detected. If the backup
overcurrent functions 50, 50G, and 51G are not directionally controlled, they are allowed to trip during a potential fuse failure condition. If any of the backup, overcurrent functions, 50, 50G or 51G, is directionally supervised, then that function is
not allowed to trip. Rather, a second overcurrent function, 50_FF, 50G_FF, or 51G_FF is placed in service during the fuse
failure condition. The pickup level setting of these functions is independent from the normal pickup setting. The PTFF functional logic is shown below.
If AC potential is los t o n one or more phases, th e An y Phase Under Voltage signal pro duc es a lo gic 1 out put, and the upper
input is present at AND1. The phase undervoltage pickup setting is fixed at 75% of nominal and the pickup-to-dropout ratio
is virtually 100%. Th e lower in put to AND1 is d epende nt upon wheth er the fa ult dete ctor FD ha s opera ted or whethe r one or
more phases of the protected line are de-energized (open). When one or more phases of protected line are open, PTFF is
disabled.
PHASE
VOLTAGE
DETECTOR
CURRENT
DETECTOR
FAULT
DETECTOR
PHASE
VOLTAGE
DETECTOR
CURRENT
DETECTOR
PHASE
VOLTAGE
DETECTOR
VA
IB-A
FD
VB
IB-B
VC
1A
SINGLE PHASE TRIPPING MODELS:
1A
1B
1C
1B
2
2
3~
TL1
2
3
PTFF
0
1
CURRENT
DETECTOR
IB-C
1C
THREE PHASE TRIPPING MODELS:
3~
TL1
2
2
PTFF
0
PTFF3.VSD
VOLTAGE
DETECTOR
CURRENT
DETECTOR
FAULT
DETECTOR
ANY PHASE
OPEN
V1
IB
FD
1
1
1
Figure 1–3: POTENTIAL FUSE FAILURE LOGIC DIAGRAMS
If AC potential is lost for any reason, including a blown fuse or fuses, and there is no disturbance on the power system that
operates the fault detector, the AND1 output causes timer TL1 to time out and produce a PTFF output via OR2. The output
of OR2 is route d t o AND2 to seal-in the P TF F o utp ut, ba sed on the Any Phas e Unde r Voltage signal, s o that PTFF output is
maintained as long as th e pote ntial is below normal. Setti ng 714: FUSEFAIL determines whether PTFF operation blocks
distance/directiona l tr ipping (FUSEFAIL = YES) or merely is sues an eve nt (FUSEFAIL = NO). When t he pote ntial r eturns to
normal, the Any Phase Under Voltage signal resets to remove the seal-in, allowing the PTFF output to reset.
When a fault occurs, with an atte ndant d rop i n poten tial, th e Any Pha se Unde r Voltage signa l pick s up, but t he fa ult det ector
operates to prevent an output from AND1. PTFF does not operate on fault conditions.
The Line Pickup (close-onto-fault) logic provides tripping in the event that the breaker is closed into a zero-voltage bolted
fault, such as occurs if the grounding chains were left on the line following maintenance. For this three phase zero voltage
fault, the Mho distance functions can not operate because they do not have a source of polarizing voltage. The logic is
shown below:
OVERREACHING PHASE OR
GROUND DISTANCE
I1 CURRENT
DETECTOR
ALL PHASES OPEN
ALL PHASE VOLTAGES
HIGH
MT
MTG
I1
TL402
40
401
45
5
TL401
150
90
0
FAST
RESET
402
TIMER
BYPASS
TL403
403
401
LINE PICKUP
TRIP
Figure 1–4: LINE PICKUP LOGIC DIAGRAM (THREE PHASE TRIPPING)
When the line is de-energized, the open breaker is detected by the All phases Open signal as shown in the above logic.
The resulting output causes timer TL401 to pickup 150 ms later. Consequently, when the line is energized and a fault current higher than the setting of I1 exists, current detector I1 picks up and AND402 produces an output. If the Timer Bypass
setting is set to YES, AND403 im medi ate ly prod uc es an o utp ut t o in itiate trip pin g of the bre ake r. If the Timer Bypass setting
is set to NO, then tripping occurs after the 45 ms pickup delay of timer TL403. Line Pickup is primarily intended to trip for
closing into zero-voltage bolted faults where the distance functions connected to line-side potential will not operate. However, regardless of the I1 pickup setting, it can also be used to trip on any type of permanent fault along the entire line
length that produces voltage at the relay location that is sufficient to operate a Zone 2 distance function, but not enough to
pickup the All Phase Voltages High s ignal . This i s acco mpli shed by routin g Zone 2 p hase-d istan ce or ground -distan ce function outputs to AND401. The step distance backup timers are bypassed by the Line Pickup logic.
If the line is energized and no fault exists, the all Phase Voltages High signal picks up and timer TL401 will begin timing; 40
ms later the output of TL402 resets timer TL401 via the fast reset input. AND401 and AND402 have their lower input
removed at that time to take the three phase Line Pickup out of service.
Timer TL403 is provided for those cases where simultaneous high-speed reclosing is employed at both ends of the line,
and where the I1 function must be set to pick up below the maximum load current that can occur at that time. TL403 then
allows time for the voltage to return to normal and take Line Pickup out of service before it can trip on load current. If simultaneous high-speed reclosing is not used, timer TL403 can be permanently bypassed.
b) SINGLE PHASE TRIPPING
Logic is included to provide high speed tripping when a single phase reclose onto a permanent fault occurs. When a phase
of the circuit breaker is open, the associated timer (TL404, TL405, and TL406) picks up to provide one input to an AND
gate (AND404, AND405, or AND406). This AND gate allows the associated Zone 2 ground distance function to trip without
time delay, and without receiving a permissive channel signal from the remote terminal. The single phase line pickup logic
will be blocked 90 ms after the breaker pole has been closed by the dropout of the timer.
Figure 1–5: LINE PICKUP LOGIC DIAGRAM (SINGLE PHASE TRIPPING)
MT
MTG
I1
TL404
150
TL405
150
150
90
90
TL406
90
TL402
40
MTG A
MTG B
MTG C
401
45
5
TL401
150
90
0
FAST
RESET
404
405
406
402
TIMER
BYPASS
402
TL403
403
401
LINE PICKUP
TRIP
1
1.4.3 REMOTE-OPEN DETECTOR
The Remote-Open Detector (ROD) function issues a trip signal when the remote breaker opens during an unbalanced
internal fault. This function detects that the remote breaker has opened by recognizing charging current on one or more
phases following opening of the remote breaker. As shown in the functional logic diagram of Figure 1–6: REMOTE-OPEN
DETECTOR LOGIC (ROD), the ROD output trips via OR2, AND1, OR2, AND2, OR3, and AND4. The Remote-Open Detector will not operate when a balanced three-phase fault is present.
ROD speeds up tri pp ing at the end of the line tha t o therwise would be th e s lo west to respond in a seq ue ntia l-tri pp ing c ond ition. In a Step Distance scheme, ROD tripping is beneficial for any unbalanced internal fault not detected by Zone 1. In a
Blocking scheme, ROD tripping is beneficial where system conditions are such that the fault current redistribution following
breaker opening at one end is normally required before the other end(s) operates. The ROD function should not be considered as a replacement or substitute for pilot schemes.
Figure 1–6: REMOTE-OPEN DETECTOR LOGIC (ROD) is a functional logic diagram of the ROD function. The sequence
of events that results in an ROD output is as follows:
1.No charging current is detected prior to the fault – logic 0 output from AND2.
2.A fault is detected – logic 1 output from OR3.
3.The remote breaker opens – logic 1 output from AND3.
4.The fault is still present, so the two inputs to AND4 persist for the time-delay setting of timer TL20.
If charging current is initially detected but the fault detector (FD) is not picked up, indicating no fault on the power system,
then OR1 and AND1 produce outputs. AND2 produces an output and seals-in on the output of OR1 via OR2. AND3 is now
blocked from pro duc in g a n outp ut as lo ng as charging current is dete cte d, regardless of whethe r FD is picked up or not. If a
subsequent fault occurs and the remote breaker opens, ROD is prevented from producing an output.
If sufficient load current is flowing prior to the fault there is no output from OR1, indicating that no charging current is
detected, and AND3 is not blocked, since there is no output from AND2. If an unbalanced fault subsequently occurs, FD
blocks AND1 to prevent an AND2 output. AND3 is allowed to produce an output when the remote breaker opens, provided
there is sufficient charging current to operate one or more of the three charging-current-detectors that are the inputs to
OR1. The capacitive cha rging cu rrent must be 60 mA or mo re (se condary ph ase cur rent) to assure operatio n of ROD. If the
fault is still present as indicated by an output from OR3, an ROD trip follows the expiration of the TL20 security time delay.
1.4.4 OUT-OF-STEP BLOCKING
Figures 1–7: OSB R-X DIAGRAM and 1–8: OSB LO GIC D IAGRAMS rep resent the funct ional l ogic di agrams for out-of -step
blocking and an R-X diagram depicting an assumed swing-impedance locus superimposed on the associated distance
relay characteristics. For an out-of-step condition, the impedance locus will first enter the MOB characteristic, then later
enter the MT (phase-distance trip function) characteristic.
When MOB (A-B) picks up durin g the power s wing , it applies the middle input to AND 20 1. The top i npu t is p res ent fro m th e
NOT via OR202, since MT (A-B) has not operated yet. The bottom NOT input of AND202 is satisfied, since it is assumed
that no phase is open, and the AND202 output energizes timer TL1.
If the impedance stays between the MOB and MT characteristics for the pickup time of TL1, an OSB output results. The
OSB output is routed back to the top input of AND202 via OR202 to seal-in the OSB output for as long as MOB is picked
up. The OSB output resets 50 ms after the swing-impedance locus leaves the MOB characteristic. The same logic is
repeated for the distance functions associated with phase pairs B-C and C-A. OSB can be selected to block tripping of:
For selections 2 an d 3, each of the fou r distan ce zones (Zone 1, 2 , 3, or 4) ma y be ind ividu ally s elect ed to be bl ocke d or not
via Protection Settings 1604 through 1607 (BLOCKZ1, BLOCKZ2, BLOCKZ3, and BLOCKZ4).
Timer TL1 has an adaptive pickup feature with an initial pickup setting of 30 ms for the first slip cycle; the pickup delay
becomes progressively lower during successive slip cycles. This improves the capability to maintain the out-of-step output
during the increasing slip frequencies typically encountered after the first slip cycle.
The program code resides in Flash memory rather than EPROM. This new technology provides the same functionality during normal operations of the relay. The advantage to the Flash Memory is it can be changed for software upgrades without
opening the relay. The contents can be overwritten through the communications ports already provided in the relay. The
ability to change the cont ents requires special sof tw are an d do es no t come with any of the standa rd co mm uni ca tio ns pack ages available for the ALPS.
1.5.2 LINE OVERLOAD
The Line Overloa d fu nct ion pro vid es an event and a programmabl e s ig nal . Thi s signal can be used to p rov ide al arm ind ic ation (contact closure) that the load current on the protected line has exceeded a set level for a set time interval. Two alarm
levels are included. Level 1 is generally set with a lower pickup setting and a longer time delay than level 2.
1.5.3 CURRENT UNBALANCE DETECTION
If the Fault Detector remains picked up for 60 seconds, a non-critical alarm is issued and an event message generated.
This function indicates sustained unbalanced current conditions such as a shorted or open current transformer.
1.5.4 FAULT LOCATION
A separate algorithm provides fault-loca tio n in form ati on , whi ch is pres en ted as mi les, kilometers, or perce nt of l ine from th e
relay location to the faul t. Th e d is tanc e t o th e fault is based on a li ne l eng th p rov ide d by the user as a setting. Fault location
output is displayed on the front panel liquid crystal display as part of the target information following a relay trip, and it is
also contained in the Fault Report described below.
1.5.5 FAULT REPORT
When a fault or oscillography trigger occurs, pertinent information, consisting of unit ID, date and time, operating time, prefault currents, fault currents and voltages, fault type, trip type, distance to fault, and selected events, is stored in memory.
The number of fault ev ents that are stored is selectable by the user. A relay with sta nda rd m em ory op tio n m ay be s et for: 2,
4, 8, or 12 fault reports. A relay with extended memory option may be set for 6, 12, 24, or 36 fault reports. Each fault report
is associated with an oscillography data file. See Section 8.2.3: REQUEST FAULT INFORMATION on page 8–17 for
obtaining a fault report through the local user interface and Section 11.6: INFORMATION on page 11–14 for fault reports
using ALPS-Link.
1.5.6 OSCILLOGRAPHY
Oscillography data are stored in memory each time the ALPS issues a trip and, optionally when an internal oscillography
trigger flag is set or an external contact is closed. Protection Setting 2026: CONFOSC, allows a configurable oscillography
trigger to be assigned by Xpression Builder. Note that OSC Trigger stores oscillography data, but does not necessarily set
t = 0, the time sample that delineates between prefault and postfault oscillography cycles. The term
defined as the numbe r of cy cl es of o sc il log raph y d ata (prefault plus postfault) as de term in ed by General Setting 301: NUM-FAULTS. If the internal Fault Detector, FD, comes up initially and OSC Trigger follows within the disturbance period, oscillography data are stored whether or not the ALPS issues a trip.
If the ALPS issues a trip, then a normal fault report is stored as part of the oscillography data. If the ALPS does not issue a
trip, a pseudofault report is created. The trip type is listed as OSC, the trip time is set to when the OSC Trigger occurred,
the operating time is set to zero, and the fault type and location are computed, based on post-OSC Trigger data. The local
LCD display does not show target information, but an event message and fault report are stored in memory. In either case
above, t = 0 is determined by the internal Fault Detector (FD).
If OSC Trigger comes up initially and FD follows within the disturbance period, the same actions occur and FD determines
t = 0. If only OSC Trigger occurs, then a pseudofault report is created and OSC Trigger determines t = 0. This arrangement
assures that the oscillography function always captures an ALPS trip, with FD determining t = 0, regardless of whether an
optional internal or external trigger is used.
disturbance period
is
1-16ALPS Advanced Line Protection System
GE Power Management
1 PRODUCT DESCRIPTION1.5 OTHER FEATURES
Oscillography data include station and line identification, a complete list of the active relay settings, the fault report, internal
flags, and a selectable number of prefault and postfault data samples. Further information on reading oscillography with
ALPS-Link is found in Section 11.6.5: OSCILLOGRAPHY REPORT on page 11–15. The ALPS does not store flags for
functions that are disabled. For example, if Protection Setting 104: Z1GROUND = NO and a Z1 ground fault is applied, the
Zone 1 ground flag will not operate or be stored.
1.5.7 PLAYBACK
The ALPS has the ability to replay stored digital current and voltage signals from oscillography files through the protection
algorithms. The currents and voltages may be obtained from a factory stored file, from any oscillography file currently
stored in the relay, or from an oscillography file stored on a PC. See Section 8.1.20: PLAYBACK on page 8–13 for a complete description of the Playback feature.
1.5.8 SEQUENCE OF EVENTS
This function time tags and stores the last 150 events in memory. The resolution of the time-tagging is 1 millisecond. The
event list contains power system events, operator actions, and self-test alarms. The sequence of events can be accessed
remotely via the front panel port, PL-1 or PL-2, and a PC. A full event list contained in Section 8.2.7: EVENT INFORMATION on page 8–19.
1.5.9 EQUIPMENT DUTY
When the ALPS is applied with a single breaker, it incorporates the ability to monitor the number of breaker operations and
the breaker duty. Alarm levels can be set for both the total number of breaker operations and the total equipment duty. See
Section 2.2.4: EQUIPMENT DUTY on page 2–6 for a complete description of the Equipment Duty feature.
1
1.5.10 SELECTABLE GROUPS OF SETTINGS
Four separate groups of protection settings may be stored in nonvolatile memory. Only one group can be active at a given
time, but the active group may be selected by external contacts, by a command issued from the local keypad, or remote
communication software. If the selection is to be made by an external switch, then two of the digital inputs (contact converters) are used for this purpose. A four position SB1 or SBM switch with two stages (two effective contacts) could be used to
select the active group of settings, as shown Figure 1–9: SWITCH SELECTION OF ACTIVE SETTING GROUP below.
For this example, CC5 has been assigned to “CGST2” (Change Setting Group Input, Bit 1) and CC6 has
been assigned to “CGST1” (Change Setting Group Input, Bit 0). Other contact converters may be assigned
NOTE
to these functions.
GE Power Management
ALPS Advanced Line Protection System1-17
1
1.5 OTHER FEATURES1 PRODUCT DESCRIPTION
Figure 1–9: SWITCH SELECTION OF ACTIVE SETTING GROUP
1.5.11 TIME SYNCHRONIZATION
The ALPS includes a clock that can run freely from the internal oscillator or be synchronized from an external signal. An
unmodulated IRIG-B signal connected to the IRIG-B terminals, located on terminal block “D” on the rear panel, may be
used to synchronize the clock. The clock in a given ALPS is synchronized to within ±1 ms of any other ALPS clock, if the
two relays are wired to the same synchronizing signal.
1.5.12 TRIP BUS CHECK
After a settings change is made in the active settings group, the ALPS automatically returns to its normal protection-on
mode following storage of the new setting values in nonvolatile memory.
A Trip Bus Check to determine that the changed settings have not caused any of the trip functions to operate for system
conditions (that is, current and voltage at the relay) at that instant. A Trip Bus Check also occurs before a newly selected
settings group is allowe d to become the active settings group. If Trip Bus Check finds a pi cked-up trip function , protect ion is
turned off and a critical alarm is issued.
This check provides a degree of confidence in the new settings, but it does not guarantee that one or more trip functions
might not operate as system co nd itio ns chan ge. For example, a subsequent increase in load current might cause the Zone
3 phase-distance function to operate, even though it did not operate at the instant the Trip Bus Check was made.
1.5.13 TRIP CIRCUIT MONITOR
Within the ALPS relay system the DC battery voltage across each of the open trip contacts (or SCRs) may be continuously
monitored to determine if the associated trip circuit is intact. If the monitored DC voltage drops to zero, then the trip circuit
has failed to op en, or the bre ak er 5 2/a contact, which is no rma ll y wi red in series with the trip c oil , h as op ene d. This function
is intended to replace the red light indicator typically used for trip-circuit monitoring, and it can be selectively disabled for
each breaker.
1-18ALPS Advanced Line Protection System
GE Power Management
Loading...
+ 336 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.