GE 5100 User Manual

Page 1
3
Important Safety Information
10
Installation Instructions
Important Electrical Safety Adjustments and Auxiliary Controls
4
Operating Instructions
The Controls on Your Zoneline
19
Helpful Information
Things That Are Normal
20
If Something Goes Wrong
Before You Call For Service GE Service Numbers Warranty
GE Appliances
Zoneline
®
Owner’s Manual
Zoneline Heat Pump Model
5100 Series
GE Answer Center
®
800.626.2000
49-7350
Page 2
Welcome to the GE family. We’re proud of our quality products and we believe in dependable service. You’ll see it in this easy-to-use manual and you’ll hear it in the friendly voices of our customer service department.
Best of all, you’ll experience these values each time you enjoy the comfort of your Zoneline. That’s important, because your new Zoneline will be part of your family for a long time.
Welcome
Staple your receipt to the inside back cover of this manual. You will need it to obtain service under warranty.
Write down the model and serial numbers here.
They are on a label
behind the room cabinet.
Model number
Serial number
Date of purchase
Before using your Zoneline
Need Help?
Before you call for service, there are a few things you can do to help us serve you better.
Read this manual.
It contains instructions to help you use and maintain your Zoneline properly.
Save time and money.
Check the section titled “If Something Goes Wrong” before calling. This sec­tion was designed to solve common problems that might occur.
If you do need service, you can relax knowing help is only a phone call away. Toll-free customer service numbers are included in the back of this manual. Or call the
GE
Answer Center
®
at 800.626.2000,
24 hours a day, 7 days a week.
Help us help you
800.626.2000
2
Start Here!
Page 3
This Zoneline must be properly
installed in accordance with the Installation Instructions before it is used.
Repair or replace immediately
all electric service cords that have become frayed or otherwise damaged.
Unplug or disconnect the
Zoneline at the fuse box or circuit breaker before making any repairs.
NOTE:
We strongly recommend that any servicing be performed by a qualified individual.
SAVE THESE INSTRUCTIONS
3
Replacing an existing unit?
For details see the Installation Instructions in the back of this manual.

IMPORTANT SAFETY INFORMATION

READ ALL SAFETY INFORMATION BEFORE USING
Page 4
COOL
For cooling
HEAT
For heating
FAN
For fan-only operation
The fan control sets the fan operation for
HIGH,
LOW
or
AUTO
speed. When set at
AUTO
, it auto-
matically switches between
LOW
and
HIGH
as
room temperature changes.
The temp control is used to maintain the room temperature. The compressor will cycle on and off to keep the room at the same level of comfort.
COOLER
For cooler temperatures
WARMER
For warmer temperatures
STOP/ON
—Stops heating, cooling and fan opera­tion. Power remains connected to the Zoneline and the Freeze Sentinel still functions.
The
CALL SVC
(call service) indicator will light if the compressor fails to start. If the control is set at
COOL
, the compressor stops and the fan
operates alone. If set at
HEAT
, it continues in the
HEAT
setting. Call for service as soon as possible.
4

Operating Instructions

The controls on your Zoneline

2
2
1
Mode Control Temp Control
1
MODE
COOL FAN HEAT
FAN
HIGH LOW AUTO
COOLER WARMER
CALL
SVC
STOP/ON
TEMP
Page 5
5
Energy Tips
Keep the vent control at
CLOSE
. The room air will be filtered and circulated.
Set the
FAN
at
AUTO
. It switches
between low and high to adjust for room temperature changes.
Adjust the air louvers as shown to get the most hot or cool air into the room.
The ventilation control lever is located at the lower left side of the Zoneline unit, behind the room cabinet.
When set at
CLOSE
, only the air inside the room
is circulated and filtered. When set at
OPEN
, some outdoor air will be drawn into the room. This will reduce the heating or cooling efficiency.
43
3 4
Ventilation Control Air Direction
OPEN
CLOSE
Adjust the air louvers by moving them with your fingers. To get the most hot or cool air into the room, set the louvers as shown above.
Vent control
Air flow
Page 6
Operating Instructions
Other Zoneline features
Additional controls are located behind the room cabinet.
To remove:
Pull out at the bottom to
release it from the tabs. Then lift up.
To replace:
Place the tabs over the top rail. Push inward at the bottom until it snaps into place.
To Remove the Room Cabinet
6
Heat pumps can save money by removing heat from the outside air—even when the outside temperature is below freezing— and releasing that heat indoors.
To get the best from your heat pump, don’t change the room thermostat very often. Raising the heat setting 2–3 degrees may cause the Zoneline heat pump to use its electrical heating elements in order to reach the new tempera­ture setting quickly.
The electric heating elements use much more electricity than heat pumps and cost more to operate.
Generally, when the outdoor tem­perature is above 45
°F., only the
heat pump will warm the room. Below 25°F., the resistance heater will warm the room.
When the air is between 25°-45°F., the unit will automatically deter­mine the best source of heat to use.
About Your Heat Pump
1
2
1
2
Page 7
The Freeze Sentinel feature automatically turns on the resistance heater and fan if the room temperature (sensed at the unit) drops to approximately 40°F. It will turn the heater off when the temperature reaches about 45°F.
The Freeze Sentinel helps prevent plumbing damage in the room due to sub-freezing temperatures.
The Freeze Sentinel is active as long as power to the unit is on.
Freeze Sentinel
7
The fan switch 9 is located behind the room cabinet.
This switch is set at continuous fan (down) at the factory to provide continuous fan operation in cool or heat modes. Leaving the switch in the continuous fan setting allows continuous circulation of room air and will result in a more balanced temperature throughout the room.
If you want the fan to cycle on and off with the compressor or with the heater, move the switch to cycle fan (up).
Fan Switch
9
ON
OFF
ON
OFF
Fan switch
Down/Off—Continuous Fan Up/On—Cycle Fan
Auxiliary Controls
Page 8
8
Operating Instructions
Care & Cleaning
Turn the Zoneline off and discon­nect the power supply.
To clean, use water and a mild detergent. Do not use bleach or abrasives.
Room Cabinet and Case
The coils on the outdoor side of the Zoneline should be checked regularly. If they are clogged with dirt or soot they may be profes­sionally steam cleaned, a service available through your GE service outlet. You will need to remove the chassis to inspect the coils because the dirt build-up occurs on the inside.
Outdoor Coils
In some installations, dirt or other debris may be blown into the unit from the outside and settle in the base pan (the bottom of the unit).
Check it periodically and clean it out, if necessary.
Base Pan
Clean the outside coils regularly.
Grille
Coils
Page 9
Turn the Zoneline off before cleaning.
The most important thing you can do to maintain the Zoneline is to clean the filter at least every 30 days. Clogged filters reduce cool­ing, heating and air flow.
Keeping these filters clean will:
Decrease cost of operation.
Save energy.
Prevent clogged heat exchanger
coils.
Reduce the risk of premature
component failure.
To clean the air filters:
Vacuum off the heavy soil.
Run water through the filters.
Dry thoroughly before replacing.
To remove the air filters:
To replace the air filters:
CAUTION: DO NOT operate the Zoneline without the filters in place. If a filter becomes torn or damaged it should be replaced immediately.
Operating without the filters in place or with damaged filters will allow dirt and dust to reach the in­door coil and reduce the cooling, heating, airflow and efficiency of the unit.
Replacement filters are available from your salesperson, GE dealer, GE Service and Parts Center or authorized Customer Care® servicers.
Air Filters
9
Pull up
Push down
2 air filters
Operating Tip: To maintain optimum performance, clean the filters at least every 30 days.
Dirty filter–Needs cleaning
Clogged filter–Greatly reduces cooling, heating and airflow.
FRONT
FRONT
Page 10
10

Installation Instructions

Read carefully
If you have any questions, call the GE Answer Center at
800.626.2000.
Use the correct wall case.
This chassis is designed to be installed in an insulated wall case. This minimizes condensation from forming on the room side of the case. If the current wall case is not insulated, you can reduce the pos­sibility of condensation forming by installing insulation kit RAK901L, available where you purchased the chassis.
Use the correct outdoor grille.
You should use the outdoor grilles shown on the “Essential Elements” label on the top of the chassis.
If an existing grille is not
replaced, capacity and efficiency will be reduced and the unit may fail to operate properly or fail pre­maturely. A deflector kit, RAK40, may be used with grilles that were not designed for current AZ Series GE Zonelines. The RAK40 contains air deflectors and gas­kets that mount to the chassis to direct the hot exhaust air away from the air intake to allow the unit to function properly. The grille must have a 65% free area.
Any vertical deflectors in
the existing grille should be removed to decrease condenser air recirculation which can cause the unit to “short-cycle” and lead to premature component failure.
Replacing a ducted chassis.
CAUTION: The Zoneline 5100 series is not approved for use in a ducted installation. (A normal ducted chassis has a duct adapter and duct extension connected to the unit to direct some of the air into an adja­cent room.)
• Replacing 230/208 volt units.
See page 12.
• Replacing 265 volt units.
The National Electrical Code (NEC) requires units connected to a power source over 250 volts to be permanently connected.
GE power connector kits required for this model are listed on the “Essential Elements” label on top of the new chassis.
Power connector kits with an “L” or “LF” suffix include a length of conduit designed for use with RAK203 sub-base.
If you are using a different sub­base, order a kit without the “L” or “LF” suffix. You will have to supply the proper length of conduit and the necessary conduit connectors.
If the existing sub-base has a recep­tacle or connector inside, remove it. Using a GE power connection kit, reconnect the unit wiring to the building wiring via conduit. This wiring must be contained in conduit to comply with the NEC.
Replacing an existing unit?
Check the “Essential Elements” label for important information.
Page 11
Follow the National Electrical
Code (NEC) or local codes and ordinances.
For personal safety, this Zoneline
must be properly grounded.
Protective devices (fuses or circuit
breakers) acceptable for Zoneline installations are specified on the nameplate of each unit.
CAUTION:
Do not use an extension cord with this unit.
Aluminum building wiring may present special problems— consult a qualified electrician.
When the unit is in the STOP position there is still voltage to the electrical controls.
• Disconnect the power to the unit
before servicing by: 1 Removing the power cord
(if it has one) from the wall receptacle.
or—
2 Removing the branch circuit
fuses or turning the circuit breakers off at the panel.
Important Notes
Important electrical safety—read carefully
Zoneline Components
Exterior grille/louver** Wall case** Zoneline unit Room cabinet*
Universal power cord kit**
*Shipped with the Zoneline unit
**Check the “Essential Elements” list on the unit
Installer: Leave these instructions with the air conditioner.
Owner: Keep these instructions for future use.
YOU WILL NEED:
• Universal power connector kit.
• Phillips screwdriver.
11
Page 12
12
Installation Instructions
A power connection kit must be used to supply power to the Zoneline unit. The appropriate kit is determined by the voltage, the means of electrical connection and the amperage of the branch circuit.
Connections of 208 or 230 volt circuits may be with a universal power cord kit or a permanent connector kit.
All wiring, including installation of the receptacle, must be in accor­dance with the NEC and local codes, ordinances and regulations.
230/208 Volt Electrical Supply
TTaannddeemm 15 Amp.
PPeerrppeennddiiccuullaarr 20 Amp.
LLaarrggee TTaannddeemm 30 Amp.
Electrical wiring wall outlets 230/208 volts.
Universal power cord kit
Permanent connector kit
OR
Typical universal power connector kits
All 265V units must be direct­connected using a universal power connector kit.
The electrical rating marked on the Zoneline must not exceed the supply branch circuit.
The unit provides for the connec­tion of 1
2trade-size electrical
conduit and provision for connec­tion to a wiring system in accor­dance with the NEC, ANSI/NFPA No. 70-1993. The NEC prohibits connecting this unit with a flexible power cord.
How to Connect 1
Remove the room cabinet.
2
Install the power connector kit per instructions in the kit.
3
Reinstall the room cabinet.
265 Volt Electrical Supply
Electrical junction box
Wire nut
Inner conductors
Mounting plate
Cover plate with screws
Power supply conductors
Page 13
13
1
The RAB71 or RAB77 wall case must be properly installed per instructions packed with the case.
2
Remove the corrugated stiffener and the outdoor protective panel. Use the slit in the out­door panel as a handhold and push out.
3
Install the exterior grille from the room side following instruc­tions packed with the grille.
Insulated Wall Case
This chassis is designed to be installed in an insulated wall case. This minimizes condensation from forming on the room side of the case.
The RAB71 wall case is insulated. Insulation kit RAK901L is available for use with RAB77 or existing uninsulated wall cases when needed.
Install the Wall Case and Exterior Grille
Protective panel
Slit
Stiffener
230/208 Volt Universal Power Wall Plug Heater Wattage Cord Kits Configuration Circuit Protective Device @ 230/208 Volts
RAK315 Tandem 15 Amp TD fuse or breaker 2.55/2.09 KW RAK320 Perpendicular 20 Amp TD fuse or breaker 3.45/2.82 KW RAK330* Large Tandem 30 Amp TD fuse or breaker 5.00/4.10 KW
230/208 Volt Permanent Heater Wattage Connection Kits Circuit Protective Device @ 230/208 Volts
RAK415/415L 15 Amp TD fuse or breaker 2.55/2.09 KW RAK420/420L 20 Amp TD fuse or breaker 3.45/2.82 KW RAK430/430L* 30 Amp TD fuse or breaker 5.00/4.10 KW Kits ending in “L” have flexible conduit to reach from the kit to the knockout hole (above right side inspection plate) in the RAK203 sub-base.
265 Volt Permanent Heater Wattage Connection Kits Circuit Protective Device @ 265 Volts
RAK515/515LF 15 Amp TD fuse 1.70 KW RAK517/517LF 15 Amp TD fuse 3.00 KW RAK520/520LF 20 Amp TD fuse 3.70 KW RAK530/530LF* 30 Amp TD fuse 5.00 KW
Kits ending in “LF” have flexible conduit to reach from the kit to the knockout hole (above right side inspection plate) in the RAK203 Sub-Base and have an Integral Fuse.
*Not recommended for use on 6000 BTUH units. (If this connection kit is used it will provide a maximum
heat of 3.45 KW at 230 volts and 3.7 KW at 265 volts.)
Power Connection Chart
Page 14
14
Installation Instructions
1
Carefully remove shipping tape, if there is any, from the room cabinet and vent door.
2
Remove the room cabinet by pulling it out at the bottom to release it, then lift it up to clear the rail along the unit top.
Remove Shipping Tape and Room Cabinet
Shipping tape
Slide the unit into the wall case and secure with four screws through the unit flange holes.
If an insulated wall case is needed, see Install the Wall Case and Exterior Grille section on the previous page.
Install the Unit into the Wall Case
Reinstall the room cabinet by hooking the top over the rail along the unit top, then pushing it in at the bottom.
Replace the Room Cabinet
2
1
1
2
Page 15
Low Voltage Connectors & Auxiliary Controls
The Boost Heat Option increases the Zoneline air temperature by adding electric heat to supplement the heat pump. It automatically turns on when the outside tempera­ture is between 25
°F. and 45°F.
To set the Boost Heat Option, move switch 8 to the ON(up) position.
If the Zoneline is controlled by a wall thermostat, the Boost Heat Option provides
ALL
the heat
when the outside temperature is below 45°F.
The Boost Heat Option is more expensive than heating with the heat pump only.
Boost Heat Option
The Electric Heat Option increases the Zoneline air temperature by using electric heat only. The heat pump is not used to produce any heat.
If you want warmer air from the Zoneline, and the Boost Heat Option is not warm enough, this option will provide the hottest air available.
To set the Electric Heat Option, move switch 7 to the
ON
(up)
position. Using the Electric Heat Option is
much more expensive than heating with the heat pump only.
Electric Heat Option
7
ON
OFF
ON
OFF
Auxiliary Controls
Auxiliary Controls
15
8
ON
OFF
ON
OFF
Page 16
16
Installation Instructions
The Zoneline can be controlled by using the controls on the unit or by a wall thermostat.
Detailed wiring instructions are packed with the low-voltage con­nectors in the recessed connection space on the Zoneline chassis.
To switch to a wall thermostat, move switch 10 to the
ON
(up) position (see illustration B at left). Connect the unit to a 6-wire Class 2 Remote Thermostat (GE Model RAK147 or equivalent), as shown in illustration C at left.
For some applications, it may be desirable to operate on low fan speed. Moving the auxiliary switch 11 to the
ON
(up) position will pro­vide low fan speed in both heating and cooling modes.
No external voltage may be applied to the unit through the Remote Thermostat terminals.
IMPORTANT: After the wire connections are completed, replace the metal cover to prevent damage to the unit or personal injury.
Remote Control/ Wall Thermostat
10 11
ON
OFF
ON
OFF
RED
GRY
BLK
YEL
WHT
BLU
+24V
FAN MOT.
SOL. COIL
COMP.
HEATER
GND
1
Class 2
Remote
Thermostat
Low fan speed
with Class 2
Remote
Thermostat
Auxiliary Controls
Class 2 Thermostat
RAK147 or equivalent
R C T’Stat terminalsG B YW
Wire nut 6 PCS
6P Plug
Insert
B
C
A
Metal cover over recessed connection space
Page 17
The Zoneline can be connected to a switch at the front desk that allows you to turn the unit on or off without going to each unit.
When the front desk switch is open the Zoneline is on. Turn the switch to closed to turn it off.
For load shedding,
the CDC auxiliary
switch 9 must be in the
OFF
(down) position and auxiliary switch 12 must be in the
ON
(up) position. This provides fan operation while the compressor or heater is turned off.
NOTE: The Freeze Sentinel remains active to help protect against low temperature damage even though the unit may be off at the central control location.
IMPORTANT: After the wire connections are completed, replace the metal cover to prevent damage to the unit or personal injury.
Central Desk Control
Recommended wire size
for Central Desk Control
installation
Wire Size
Maximum
# AWG
Allowable
Length
#24 400 ft. #22 600 ft. #20 900 ft. #18 1500 ft. #16 2000 ft.
DO NOT use a common buss in the CDC wiring.
Good wiring practices (e.g. twisted pairs, separation from power circuits) must be followed to minimize induced voltages which may harm the control system.
CDC
Load shedding
Auxiliary Controls
Follow the recommended wire sizing in the table. Two wires must be used from each CDC switch to each individual unit.
A 24-volt transformer is contained within the unit and no external voltage should be applied to the unit through the CDC terminals. These terminals may also be used as an interface for other systems used to control the unit, such as infrared detectors, key-activated systems, etc.
Metal cover over recessed connection space
17
9 12
ON
OFF
ON
OFF
Page 18
18
Installation Instructions
Temperature limiting can reduce energy costs by limiting the lowest temperature that can be set on cooling and the highest tempera­ture that can be set on heating. Temperature limiting is controlled by setting the first six auxiliary switches.
The first three are used to select cooling range limits and the next three are used to select heating range limits.
Temperature Limiting
1 2 3 4 5 6
ON
OFF
ON
OFF
COOLING LIMITS
Limit Switch Temp Range
Up/On F.
NONE 62 to 85
1 64 to 85
1 & 2 67 to 85
2 69 to 85
2 & 3 71 to 85
1 & 2 & 3 73 to 85
1 & 3 75 to 85
3 77 to 85
HEATING LIMITS
Limit Switch Temp Range
Up/On F.
NONE 60 to 85
4 60 to 80
4 & 5 60 to 76
5 60 to 74
5 & 6 60 to 73
4 & 5 & 6 60 to 71
4 & 6 60 to 69
6 60 to 67
The Zoneline has a diagnosis feature. When switch 13 is moved to the
ON
(up) position, the unit will go through an operations check of all components which takes about two minutes. This diag­nostic tool is intended for use by a qualified technician.
Diagnosis Switch
Auxiliary Controls
Auxiliary Controls
ON
OFF
ON
OFF
13
Page 19
19

Helpful Information

Things that are normal

Noise Explanation
3-Minute
Delay
You may hear a pinging or popping noise caused by water being picked up and thrown against the condenser on rainy days or when the humidity is high. This design feature helps remove moisture and improve efficiency.
You may hear relays click when the controls cycle on and off or are adjusted to change the room temperature.
Water will collect in the base pan during high humidity or on rainy days. The water may overflow and drip from the outdoor side of the unit.
The indoor fan runs continuously when the unit is operating in the cooling mode, unless the fan switch behind the room cabinet is set at cycle fan (up). This will cause the fan to cycle on and off with the compressor. You may also hear a fan noise stop and start.
You may notice a few minutes delay in starting if you try to restart the Zoneline too soon after turning it off or if you adjust the thermostat right after the compressor has shut off. This is due to a built-in restart protector for the compressor that causes a 3-minute delay.
The compressor shuts off before and after the defrost cycle. Full resistance heat comes on during the defrost cycle to maintain room comfort.
PIN
G
!
POP!
“CLICK”
D R I P
WHIR!
SILENCE
Page 20
20
Zoneline Doesn’t Start
Zoneline Does Not Cool or Heat as it Should
The unit is unplugged Make sure the Zoneline plug is
pushed completely into the outlet.
The fuse is blown/circuit Check the house fuse/circuit breaker breaker is tripped box and replace fuse or reset the
breaker.
The unit is waiting for the This is normal. The Zoneline will start compressor overload again after it resets.
protector to reset
Problem Possible Causes What to Do
Airflow is restricted • Make sure there are no curtains, blinds
or furniture blocking the front of the Zoneline.
The temp control may Turn the control to a lower or higher not be set high or low number.
NOTE: The temperature limiter may
enough
be limiting the temperature range.
The air filter is dirty Clean the filter at least every 30 days. The room may have been When the Zoneline is first turned on
hot or cold you need to allow time for the room to
cool down or warm up.
Air is escaping Set the vent control in the
CLOSE
position.

If Something Goes Wrong

Before you call for service

Page 21
21
Problem Possible Causes What to Do
CALL SVC Indicator Light
The compressor Move the control to
STOP
and then
may have failed restart the unit. If the light reappears
within 30 minutes, call for service as soon as possible.
Burning Odor at the Start of Heating Operation
Dust is on the surface of This can cause a “burning” odor at the the heating element beginning of the heating operation. This
odor should quickly fade.
The Air is Not Always Cool or Hot During Operation
The heat pump is not This is normal. The heat pump will producing hot air produce warm air but not as hot as air
produced when the higher-cost electric heat is used.
The fan switch may be set This causes the fan to blow room at continuous fan (down) temperature air even when the
compressor or heater cycles off. The continuous air movement provides better overall temperature control.
The Air Does Not Feel Warm Enough During Heating Operation
The heat pump alone Use the Boost Heat Option to warm the produces air that feels air. This adds electric heat to the heat cooler than desired pump when the outside temperature is
between 25
°F. and 45°F.
Use the Electric Heat Option. This turns
off the heat pump and warms with electric heat only.
NOTE:
Use of either of the above options will result in increased energy consumption.
Page 22
22
Notes
Page 23
800.626.2000 TDD
800-833-4322

GE Service Numbers

We’ll be there!
Open 24 hours a day, 7 days a week.
GE Answer Center
®
800-GE-CARES (800-432-2737)
We provide expert repair service, scheduled at a time that’s convenient for you.
Our factory-trained technicians know your air conditioner inside and out—so most repairs can be handled in just one visit.
On-Site Repair Service
800-626-2002
Individuals qualified to service their
own air conditioner can have parts or accessories sent directly to their home.
VISA, MasterCard and Discover cards are accepted.
Care and cleaning instructions con­tained in this manual cover proce­dures to be performed by any user. Other servicing generally should be referred to qualified service person­nel. Caution must be exercised, since improper servicing may cause unsafe operation.
Parts and Accessories
If for some reason you are not happy with the service you receive, here are three steps to follow for further help.
First,
contact the people who ser­viced your
air conditioner
. Explain
why you are not pleased.
Next,
if you are still not pleased, write all the details—including your phone number—to:
Consumer Relations GE Appliances, Louisville, KY 40225
Finally,
if your problem is still
not resolved, write: Major Appliance
Consumer Action Program 20 North Wacker Drive Chicago, IL 60606
Further Service
23
Page 24
What is Not Covered
FULL ONE-YEAR WARRANTY
For one year from date of original purchase, we will provide, free of charge, parts and on­site service labor to repair or replace any
part
of the room air conditioner that fails because of
a
manufacturing defect.
FULL FIVE-YEAR WARRANTY
For five years from the date of original pur­chase, we will provide, free of charge, parts and on-site service labor to repair or replace any part of the sealed refrigerating system (the compressor, condenser, evaporator and all connecting tubing) that fails because of a manufacturing defect.
LIMITED 2ND THROUGH 5TH YEAR PARTS WARRANTY
This limited 2nd through 5th year parts war­ranty applies only to units purchased after January 1, 1995. For the second through the fifth year from date of original purchase, General Electric will provide, free of charge, parts that fail as a result of a manufacturing defect. Parts covered are fan motors, switches, thermostat, heater, heater protectors, com­pressor overload, solenoids, circuit boards,
auxiliary controls, thermistors, Freeze Sentinel, frost controls, ICR pump, capaci­tors, varistors, and indoor blower bearing. This is a limited parts only warranty, and does not include labor or transportation to and from the service shop.
************************************** This warranty is extended to the original
purchaser and any succeeding owner for products purchased for use in the 48 main­land states, Hawaii and Washington, D.C. In Alaska the warranty is the same except that it is LIMITED because you must pay to ship the product to the service shop or for the service technician’s travel costs to your home.
All warranty service will be provided by our Factory Service Centers or by our authorized Customer Care®servicers during normal working hours.
Should your appliance need service, during warranty period or beyond, call 800-GE-CARES (800-432-2737).
Staple sales slip or cancelled check here. Proof of original purchase date is needed to obtain service under warranty.
AIR
CONDITIONER

WARRANTY

What is Covered
Printed in Singapore
1-97 CG
Pub. No. 49-7350
Zoneline 5100 Series
Service trips to to teach you how to use the
product. Read your Owner’s Manual. If you then
have any questions about
operating the
product, please contact
your dealer or our Consumer Affairs office at the address below, or call, toll free:
GE Answer Center®
800.626.2000
consumer information service
Improper installation.
If you have an installation problem, or if the air conditioner is of improper cooling or heating capacity for the intend­ed use, contact your dealer or installer. You are responsible for providing adequate electrical connecting facilities.
Replacement of fuses or resetting
of
circuit breakers.
In commercial locations, labor necessary
to move the unit to a location where it is accessible for service by an individual technician.
Failure of the product resulting from
modifications to the product or due to unreasonable use including failure to provide reasonable and necessary maintenance.
Failure due to corrosion on models not corrosion-protected.
Damage to product caused by improper power supply voltage, accident,
fire, floods
or acts of God.
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state. To know what your legal rights are in your state, consult your local or state consumer affairs office or your state’s Attorney General.
Warrantor: General Electric Company If further help is needed concerning this warranty, write:
Manager—Consumer Affairs, GE Appliances, Louisville, KY 40225
WARRANTOR IS NOT RESPONSIBLE FOR CONSEQUENTIAL DAMAGES.
Loading...