GE 3100 Series Use and Care Manual

Page 1
I Use&~~~6’&ndlns
tallatiohGuide
Zoneline@
Conten@
Air Filter Appliance Registration
Aufiliary Care
Central Desk Control 4 Condenser Coils
Consumer Services
Ener~-Saving Tips
Fan Cycle Stitch 4 Freeze Sentinel 4
Installation Instructions Master Controls
Model and Serial Numbers Problem Solver
Controls
and Cleaning
15 11
6-10
11
Air Conditioner
2 4
5
3 2
Room cabinet and Case Safety Instructions
Thermostat Control Ventilation Control 4
a
Pup
Back Cover
Model
Warranty
GE Answer Center
800.626.2000
Zoneline@
Heat
3100 Series
GE Appliances
3
Page 2
Help us
bpotint
Stiety
help you...
Before using your air conditioner, read this book carefully.
It is
intended
and maintain your new conditioner properly.
Keep it handy for answers to your questions.
If you don’t understand something or need more help, write (include your phone number):
Consumer Affairs GE Appliances Appliance Park Louisville, KY 40225
Write down the model and serial numbers.
You’ll find them on a label behind
the room cabinet. These numbers are also on the
Consumer Product Ownership Registration Card that came with your
air
sending in this card, please write these numbers here:
to help you operate
air
conditioner. Before
Instmctions
Read all instructions before using this appliance.
When using this air conditioner, always exercise basic safety precautions, including the following:
Use this air conditioner only for
its intended purpose as described in this Use and Care Book.
This air conditioner must be
properly installed in accordance with the Installation Instructions before it is used.
Never use an extension cord
with this air conditioner.
Unplug or disconnect the unit
at the fuse box or circuit breaker before making any repairs. Note:
We strongly recommend that any servicing be performed by a qualified individual.
For your safety ... Do not store
or use combustible materials, gasoline or other flammable vapors or liquids in the vicinity of this or any other appliance.
HYOU
To obtain service, see the Consumer Services page in the back of this book.
We’re proud of our service and want you to be pleased. If for some reason you are not happy with the service you receive, here are three steps to follow for further help.
FIRST, contact the people who serviced your appliance. Explain why you are not pleased. In most cases, this will solve the problem.
NEXT, if you are still not pleased, write all the details—including your phone number—to:
Manager, Consumer Relations GE Appliances Appliance Park Louisville, KY 40225
FINALLY, if your problem is still not resolved, write:
Major Appliance 20 North
Chicago, IL 60606
Need
Consumer Action Panel
Wacker
Sefice
Drive
Model Number
Serial Number
Use these numbers in correspondence or service concerning your
If you received a damaged air conditioner, immediately contact
the
dealer
(or
builder) that sold you
the air conditioner.
Save time and money. Before you request service, check the
Problem Solver in the back of this book. operating problems that you can correct yourself.
It
lists causes of minor
any
calls
air conditioner.
2
SAVE THESE
~STRUCTIONS
Page 3
Operating the Controls
THERMOSTAT
56
+
4+/*—@\
&
:3@/
(
28
/+
1
$
1 %0
‘/. as
I
79
10
Thermostat Control
The thermostat knob is used to control the room temperature. The unit automatically cycles on and off to maintain room temperature.
A comfortable temperature will be maintained in control is set at about “5” or “6.”
For cooler temperatures, turn the
control to a higher number. For warmer temperatures, turn the
control to a lower number.
mos{
rooms when the
STOP FAN
LO HEAT
HI HEAT
@
8
LO COOL
HI COOL
Operation Switch
HI HEAT provides heating with
high fan speed operation. LO HEAT provides heating with
low fan speed operation.
STOP
setting stops heating or
cooling.
connected to the unit
Freeze Sentinel still functions. FAN provides fan operation
without cooling or heating. HI COOL provides cooling with
high fan speed operation. LO COOL provides cooling with
low fan speed operation.
However, power remains
and the
About Your Heat Pump...
Heat pumps can save money by removing heat from the outside air—even when the outside temperature is below and releasing that heat indoors.
To get the best from your heat pump, don’t change the room thermostat very often. Raising the heat setting 2-3 degrees may cause the to use its electrical heating elements in order to reach the new temperature setting quickly.
The electric heating elements use much more electricity than heat pumps and cost more to operate.
Zoneline
freezing—
heat pump
Discharge Air Louvers
The angling of the discharge air may be adjusted from the factory setting of 37° off vertical, to a setting 20° off vertical.
37°0FF VERTICAL
NOTE: For high mounted Room Cabinet.
20°0FF VERTICAL
Zonelines
where greater room cabinet louver adjustments are required, order the
To reposition the louvers, remove the room cabinet and remove the 2 screws that hold the louver section in
place,
rotate the louver section 180° (end for end), replace the screws and put the room cabinet back air conditioner. Textured face of louver section must be toward the room side.
LOUVER SCREWS
/\
on
RAF45
the
3
Page 4
Autitia~
Controls
Additional controls are located
behind the room cabinet. Access to the controls is obtained
by removing the room cabinet.
To remove the room cabinet,
grasp it at both sides, pull it out to release it from the tabs. Then lift it up and pull forward.
To replace the room cabinet,
position tabs at top of room cabinet over the rail at top of chassis. Push the room cabinet inward until it snaps into place.
Ventilation Control
The ventilation control lever is located at the lower left side of the unit, behind the room cabinet.
This knob is set at CLOSE at the
factory. When in this position, the vent door is closed and only indoor air is circulated by the air conditioner.
Switching the knob to OPEN opens the vent door to allow outdoor air to enter the room. However, leaving the vent door OPEN reduces heating or cooling effectiveness and increase operating costs.
-
CLASS 2 REMOTE
-m
BY
WGRC
=
The CLASS 2 REMOTE and CDC terminals are located behind a cover
auxilia~
controls. To remove the plate, remove and save the screws that hold the plate to the unit.
IMPORTANT: completed, replace the plate to prevent damage to the unit or personal
Afier
@ate
the wire connections are
CDC
above the
inju~.
Fan Cycle Switch
This switch is set at the factory to provide continuous fan operation in cool or heat
modes. Leaving the switch in the
CONT setting allows continuous
circulation of room air and will result in a more balanced temperature throughout the room. If you want the fan to cycle on and off with the compressor or resistance heater, set the switch at CYCLE.
CONT
at
Unit Power Switch
This switch controls power to the cool, heat or fan modes. When set at ON it allows the unit to operate in the cool, heat or fan modes.
If this switch is set at OFF, the unit will not operate in any modes but the Freeze Sentinel will still function.
Caution: The Unit Power Switch
is not a power disconnect. If
power must be disconnected from the unit, remove the line cord plug from the wall outlet, or remove the fuses, or turn off the circuit breakers at the power panel.
all
Freeze Sentinel
The Freeze Sentinel sensor helps prevent plumbing damage due to sub-freezing temperatures—even
if you have turned the operation
switch to STOP. The sensor automatically turns on the heater and fan if the room temperature falls to about
40°F.
You do not have to do anything to activate the Freeze Sentinel. It will work as long as power to the unit has not been interrupted.
Remote Control
The unit may be controlled either by the controls on the unit or by changing the CONTROL switch to REMOTE and connecting the unit to a remote thermostat.
See Installation Instructions.
Central Desk Control (CDC)
The unit may be connected to a Central Desk Control system by connecting the wires from the central control system to the CDC terminals located on the panel behind the room cabinet. These terminals may also be used interface for other systems used to control the unit such as infrared detectors, key-activated systems, etc. The Freeze Sentinel remains in an active mode to
help
against low temperature damage even though the unit may be OFF at the central control location.
See Installation Instructions.
as
protect
an
4
Page 5
Care and Cleating
Temperature Limiter
The normal range of the thermostat control is approximately to
85°F.
The control range may be narrowed by the use temperature limiting screws located behind the control panel.
Stop
Scre~s
● ● Knob Shaft
4
the
u’
left
of the knob shaft
w
To set the limiting screws:
1.
Remove the room cabinet.
2. Pull both THERMOSTAT knob and the OPERATION knob shafts and remove the control panel.
3. Remove and relocate either or both stop screws on the exposed control box cover.
[War;est)
To limit the maximum heating temperature, move the stop screw
at
clockwise. To limit the minimum cooling temperature, move the stop screw on the right counterclockwise. Make sure the stop arm is between the stop screws as shown.
Because actual room temperature can be affected by location and installation as well as outdoor weather conditions, you may want to experiment to determine the stop screw locations that best meet your temperature requirements.
After adjusting the limiting screws, reinstall the control panel,
knobs and room cabinet.
of the
60°F.
stop
Arm
off
the
(Cotiest)
For peak operating efficiency and durability of your air conditioner follow these necessary Care and
Cleaning instructions regularly.
~rn
the
Zoneline
before cleaning.
off
Room Cabinet & Case
Wash the room cabinet and case finish with mild soap or detergent and lukewarm water.
Outdoor Coil
The
coil
on the outdoor side of the unit should be checked periodically and cleaned if clogged with dirt or soot from the atmosphere. If extremely dirty, it may need to be professionally steam cleaned, a service available through many GE service outlets.
Base Pan
In some installations dirt or other foreign matter may be blown into the unit from the outside and settle in the base pan (the bottom of the unit).
Check the base pan periodically and clean it out, if necessary.
Air Filters
The
Zoneline
should be cleaned at least every 30 days.
The two air filters are located in front of the air louvers.
\
To remove the air filters, grasp the top of the filters and straight up and out of their slots.
Vacuum the filters on the dirty side or wash them with running water.
cleaner side of the filter to drive out dust and lint. Allow the filters to dry thoroughly before replacing them.
Note: Do not operate the air conditioner without the filters in place. If a filter becomes torn or damaged it should be replaced immediately Operating
without the filters in damaged filters will allow dirt and dust to reach the indoor coil and reduce the efficiency of the unit.
Replacement filters are available from your GE Dealer, Factory Service Center or authorized Customer
To reinstall the air filter after cleaning, make sure the word FRONT is facing out. Insert the bottom of each filter in their slots and push down into place.
air filters inside
pull
Run water through from the
t;e
unit
place
or with
Care”’
servicers.
5
Page 6
BEFORE YOU BEGIN
Read these instructions completely and carefully.
lMPORTANT–Observe
ordinances.
lNSTALLER—Be
sure to leave these instructions
with the Consumer. CONSUMER—Keep these instructions for future
reference.
all governing codes and
CAUTION
Before starting the installation, the power to the direct connect wiring should be OFF.
THE GE
Exterior Grille/Louver**
ZONELIN~
Room Cabinet*
ELECTRICAL REQUIREMENTS
FOR PERSONAL SAFETY:
FOIIOW
National Electrical Code (NEC) and local codes, ordinances and regulations. All wiring — including installation of receptacle, must be in accordance with these codes.
This unit must be properly grounded.
Do
not use an extension cord with this unit.
NEC
requires permanent connection for
installations over 250 volts.
NEC requires units controlled by NEC Class 2 low voltage remote controls to be permanently connected.
protective devices
installations are specified on the nameplate of
each.
Aluminum
problems—consult a qualified electrician.
Disconnect power to the air conditioner before
servicing by:
1.
Removing the power cord from the wall
receptacle, if it has one.
2. Removing the branch circuit fuses or turning
the circuit breakers off at the panel.
building wiring may pose special
acceptable for
Zoneline
Wall Case
Chassis
Power
Connection
* Shipped with the chassis
** Check essential elements list on chassis
*** Line cord connection shown only as example
WALL CASE & GRILLE
1.
The
RAB
70 or 77 Wall Case must be properly
installed per instructions packed with the case.
2. Remove the corrugated stiffener and the outdoor protective panel. Use the slit in the outdoor panel as a handhold and push out.
Protective Panel
Slit
/
TOOLS NEEDED
Phillips screwdriver Flat Blade screwdriver
6
/
Stiffener
H/
3. Install the Exterior Grille from the room side
per instruction packed with the grille.
Page 7
I
INSTALLATION INSTRUCTIONS
(cont,nue,)
I
NEWDUCTEDINSmLLAVON
If
this unit is to be installed in a new ducted
application using a duct adaptor kit, the kit must
be installed before the chassis is placed in the wall case. The Installation Instructions are packed with the kit.
MISVNGDUCTEDINSWILAVON
Replacement of an existing ducted unit may require different components. Request this information
from your sales representative.
I
INSMLLATION
1. Remove the room cabinet by pulling out at the bottom to release it, then lift it up to clear the rail along the chassis top.
lNS~LLATION
3. Reinstall the room cabinet by hooking the top
over the rail along the chassis top, then pushing it in at the bottom.
POWER
The power connection kit must be used to supply power to the is determined by the voltage, the means of electrical connection and the amperage of the branch circuit.
Connections of 208 or 230 volt circuits maybe with a line cord kit or a permanent connection kit. Connections of 265 volt circuits must be with a permanent connection kit.
Electrical Wiring Wall
Outlets 230/208 volt
CONNECVON
Tandem 15 amp
(continued)
Zoneline chassis. The appropriate kit
2.
Slide the chassis into the wall case and secure
with four screws through the chassis flange holes.
Case
:
o
Perpendicular 20 amp
.:
o
Lsrge
tandem 30 amp
.:
PERMANENT
CONNECTION KIT
&
%
o
NEC requires permanent connection for
installations over 250 volts.
All wiring, including installation of the receptacle,
must be in accordance with the National Electrical
Code and local codes, ordinances and regulations.
(continued next page)
7
Page 8
I
INSTALLATION INSTRUCTIONS
(contln.e,)
POWER
230/208 Volt
Line Cord Kits RAK315 Tandem
RAK320 RAK330*
230/208 Volt Permanent
Connection Kits RAK41 5/415L
RAK420/420L RAK430/430L*
Kits ending in “L” have flexible conduit to reach from the kit to the knockout hole (above right side inspection plate) in the RAK 203 Sub-Base.
265 Volt Permanent Connection Kits
RAK51 5/515LF
RAK517/517LF 15 Amp TD Fuse
RAK520/520LF RAK530/530LF*
Kits ending in plate) in the
*Not recommended for use on 6000
of 3.45
CONNEC70N(continue@
Wall Plug Configuration
Perpendicular Large Tandem
Circuit Protective Device
15 Amp 20 Amp TD Fuse or Breaker 30 Amp TD Fuse or Breaker
Circuit Protective Device
15 Amp
20 Amp TD Fuse 30 Amp TD Fuse 5.00
“LF”
have flexible conduit to reach from the kit to the knockout hole (above right side inspection
RAK203
KW
at 230 volts and 3.7 KW at 265 volts.)
Sub-Base and have an Integral Fuse.
TD Fuse or Breaker
TD Fuse
BTUH Units. (If this connection kit is used it will provide a maximum heat
Circuit Protective Device
15 Amp 20 Amp 30 Amp Fuse or Breaker
TD Fuse or Breaker
TD fuse or Breaker
Heater Wattage
@
230/208 Volts
2.55/2.09
3.45/2.82
5.00/4.10
Heater Wattage
@
265 Volts
1.70
KW
KW
3.00
3.70
KW KW
KW KW
KW
Heater Wattage
@
230/208 Volts
2.55/2.09
3.45/2.82
5.00/4.10
KW KW
KW
ADJUSTMENTS AND AUXILIARY CONTROLS AVAILABLE WITH THE ROOM CABINET REMOVED
DISCHARGEAIRLOUVERS
The angling of the discharge air maybe adjusted from the factory setting of 37° off vertical, to a setting 20° off vertical.
37 ‘OFF VERTICAL
NOTE: For high mounted Zonelines where greater room cabinet louver adjustments are required, order the
I
RAF45
Room Cabinet.
20:OFFVERTICAL””
To reposition the louvers, remove the room cabinet
and remove the 2 screws that hold the louver section in place, rotate the louver section 180° (end for end),
re~lace the screws and ~ut the room cabinet back on
the air conditioner. Textured face of louver section
must be toward the room side.
LOUVER SCREWS
/\
Page 9
I
INSTALLATION INSTRUCTIONS
(cont,nue,)
TEMPERATURE LIMITING
The normal range of the thermostat control is approximately
may be narrowed by the use of the temperature
limiting screws located behind the control panel.
Repositioning the screw on the left will limit the
maximum temperature about in a clockwise rotation; the screw on the right will limit the minimum temperature when moved counterclockwise. Limiting the maximum and minimum settings prevents users from turning the controls to extreme positions. Restrictions to full rotation of the thermostat knob may require explanation to the room occupant that unit will provide comfortable conditions at settings allowed.
To access the limiting screws, remove the room cabinet, remove the Thermostat knob and the Operation knob by pulling each knob off its shaft and removing the control panel. Set the limiters to
the desired setting, replace the control panel and the control knobs. If the original settings do not
allow sufficient room temperature control the limiter screws may have to be repositioned.
stop
Link
‘warm:)%
If the temperature limiters are used it is recommended that the limiters be set no higher
than the second hole from the original bottom
position. This provides an operating range between approximately maximize the benefit of the temperature limiting it may be necessary to adjust the limiter screws
seasonally to allow unoccupied rooms to be
maintained at moderate temperatures (i.e., heating
season temperatures limited between
75°F.;
between
k
cooling season temperatures limited
60°F.
to
85°F.
/Tapped
7:o’~:Tos’at
Stop location as shipped
66°F.
85°F.
and
65°F.).
The control range
3°F. for each hole
Holes (10)
and
79°F.
In order to
60°F.
and
VENTILATION CONTROL
The VENTILATION control lever is located at the
lower left side of the unit, behind the room cabinet.
This lever controls the vent door and is set in the
CLOSE position at the
factory so outdoor air will
not enter the room through the unit and only indoor air is circulated by the
air conditioner.
Moving the lever to OPEN opens the vent door and
draws outdoor air through the air conditioner and into the room. Leaving the vent door OPEN during extreme temperature conditions reduces heating or cooling effectiveness and increases operating
costs.
WATER DRIPPAGE
Water dripping from the wall case during heat
pump operation is to be expected. In heat pump operation, water condenses on the outdoor coil and frost melts, causing drippage.
It can be eliminated by attaching a drain kit to the unit and routing the water through a drain system.
If the unit has an Internal Condensate Removal (lCR) feature, the drippage should be minimal.
Installation of a drain system is recommended if no drippage of condensate to the outdoors is allowable.
9
Page 10
3100 SERIES
Auxiliary Control Panel
CLASS 2 REMOTE
e@Oe
BY
FAN
CYCLE
-1
CYCLE CONT OFF ON NORMAL REMOTE
E
The CLASS 2 REMOTE and CDC terminals are located behind a cover plate above the controls. To remove the plate, remove and save the screws that hold the plate to the unit.
IMPORTANT: After the wire connections are completed, replace the plate to prevent damage
to
the unit or personal injuy.
WGRC
80
POWER
m]
uNIT
Coc
me
CONTROL
m
auxiliay
REMOTE CONTROL – 3100 SERIES
The unit may be controlled either by the unit
mounted controls or by changing the “CONTROL” switch located behind the room cabinet to “REMOTE” and connecting the unit to a 6 wire Class 2 remote thermostat (GE Model or RAK 152A or equivalent) the unit may be converted to remote thermostat control.
2
STAGE HEAT
1 STAGE COOL
MANUAL THERMOSTAT
RAK147A
CENTRAL DESK CONTROL
The unit may be connected to a switch at the front desk. When the switch is OPEN the unit is operable. When the switch is CLOSED, the unit is made inoperable. Connect the wires from the central control system to the “CDC” terminals located on the panel behind the room cabinet. Follow the recommended wire sizing in the table below. Two wires must be used from each CDC switch to each individual unit. Do CDC wiring. A 24 volt transformer is contained within the unit and no external voltage should be applied to the unit through the CDC terminals. These terminals may also be used as an interface for other systems used to control the unit, such as infrared detectors, key-activated systems, etc. The Freeze Sentinel remains in an active mode to help protect against low temperature damage even though the unit may be “OFF” at the central control location.
Recommended
Control Installation Wire Size #
#24
#22 #20
#18 #16
not use a common buss in the
Wire Size for Central Desk
AWG
Maximum Allowable Length
400 ft.
600 ft. 900 ft.
1500 ft.
2000 ft.
I
BY
WGRC
CLASS 2 REMOTE
LOW VOLTAGE
TERMINAL ON ZONELINE
FREEZE SENTINEL
The unit is equipped with a sensor that automatically turns on the resistance heater and fan if the room temperature, as sensed at the unit, drops to approximately 40° F. and will shut the
heater off when the temperature reaches about
520 F. The Freeze Sentinel system helps prevent damage due to sub-freezing temperatures and will operate regardless of the mode setting of the unit.
Freeze Sentinel is active as long as power to the unit has not been interrupted.
FAN CYCLE SWITCH
This switch is set at CONT at the factory to provide continuous fan operation in cool or heat modes.
Leaving the switch in the CONT setting allows
continuous circulation of room air and will result in a
more uniform temperature throughout the room. Setting the switch at CYCLE will cause the fan to cycle on and off with the compressor or resistance heater.
UNITPOWER SWITCH
This switch controls power to the cool, heat and fan modes. It is set in the ON position at the factory to allow the air conditioner to operate in these modes.
If this switch is set in the OFF position the air conditioner will not operate in any modes but the Freeze Sentinel will still function.
Caution: The UNIT POWER switch is not a power disconnect.
disconnected from the unit remove the line cord plug from the outlet, or remove the fuses, or turn off the circuit breakers at the building power panel, or unplug the power connector from the chassis.
If all power must be
10
Page 11
Energ-Saving
Tips
Keep the air filter clean.
(See Care and Cleaning section.)
For most efficient operation,
keep vent in closed position.
Don’ t
too cold. Whenever possible, turn the unit on before the room heats up or cools off. If you don’t, the air conditioner will take longer to produce the desired comfort condition.
Keep windows and doors
closed. Conditioned air escapes when they’re open.
Keep furnace floor registers and
cold air returns closed when cooling is desired. Conditioned air can easily escape through them.
Don’t let drapes or furniture block the front of the air conditioner. This will restrict air
is operating.
It’s best to operate your air
conditioner at high speed during extremely hot or cold weather.
Keep outdoor condenser coil
clean. (See Care and Cleaning section.)
Turn air conditioner off during
vacations or extended absences.
let
the room get too hot or
flow
when the unit
~
~
Questions?
Use This Problem Solver
~
PROBLEM
AIR CONDITIONER DOES NOT OPERATE
AIR CONDITIONER “DOES NOT COOL OR HEAT AS IT SHOULD”
“BURNING” ODOR AT START OF
HEATING
OPERATION OPERATING SOUNDS
POSSIBLE CAUSE
Power cord not plugged in, fuse
blown,
or
circuit breaker tripped.
Unit is waiting for compressor overload
protector to reset.
Curtains, blinds or furniture blocking the front
of the air conditioner will restrict air flow.
Thermostat Control may not be set high
enough. Turn the control to a lower or higher number. (Note: In some installations, the Thermostat Control cannot be turned all the way to “1“ or “10.” This is normal. Do not attempt to force the control beyond its stopping points.)
Dirty air filter blocking air flow. Filter
should be cleaned at
least
every 30 days. See
instructions in cleaning section.
Room may have been very hot or very cold
when the air conditioner was first turned on.
Allow time for it to cool down or warm up.
Ventilation control may be set at OPEN
position, allowing outside air to enter the room.
Dust on the surface of the heating element can cause “a burning” odor at the beginning of the heating operation. This odor should quickly fade.
Relay clicks may be heard when the
compressor or fan cycles on and off. This is normal.
Fan runs continuously when the unit
is operating unless the Fan Cycle Switch behind the room cabinet is set at CYCLE. Then the fan cycles on and off with the heater.
OUTDOOR WATER DRIPPING DURING HEATING OPERATION
Water dripping from the outside of the
heat pump is normal during heating operation. Drain kits are available. Water can be routed through a drain system to eliminate the problem.
If you need more help.. call, toll free:
GE Answer Center
(p
800.626.2000 consumer information service
11
Page 12
Page 13
Notes
13
Page 14
Notes
Page 15
Wdll
With the purchase
Be There
ofyour
new GE appliance, receive the
assurance that if you ever need information or assistance
from GE, we’ll be there. All you have to do is call–toll-free!
GEAnswer Center@
8006262000
In-Home Repair Service
80ME$ARES
(80M32-2737)
AGEconsurner selwi[:eI>rofkssion:~l”
will provide scheduled
for
you. Many
company-operated” locations you service today or tomorrow, or at your convenience
weekdays, days). know your appliance inside and out­so most repairs
(me
visit.
expert
repair service,
at a time
9:()()
Our
f’actory-trained technicians
that.’s
convenient
(;E (lonsunler
(7:()()
a.m. to
a.m. to
2:()()
p.m. Satur-
can be handled in just
Semice
offer
7:()()
p.m.
Service Contracts
80&626-2224
YOLI
can have the secure fkeling
(;E (lonsunler
there
after your warranty expires. l)ur-
chase a ranty is still in a substantial year
conl.ract, you’re
service at today’s prices.
Service will still be
(;E
contrac[ while your war-
efi’ect and you’ll receive
discount. With a nlultiple-
2issLncd offuture
Lhat
Whatevcryoul rnaj( )r
appliance,
inf;)rnlat.ion ser~i(e is available to
help.
Your call–and
will he answered promptly
coLlrteously.” time.
(;E
open
24
Telecommunication
question
(;E1
And you can call any
Answer
hours a day, 7 days a week.
(lenter”
Detice
aboLll
Answer
yOLn- question-
ancl
service is
for
tie
(lentel
Deaf
any(;
Patis andAccessories
80&626-2002
Individu~ qufified o-
appliances
parts or accessories sent directly to their
home.
‘I-he (1E
vides access all
(;E (Jenuine fidly warranted. VISA, Master(;ard
and Discover cards are accepted.
User maintenance instructions contained in this dures intended to be performed by any user. Other servicing
shodd
vice personnel. Caution must be exercised, since improper servicing may cause unsafe operation.
to over
be referred to
to service their
can
have needed
parts system pro-
47,()()()
parts.. and
Renewal Parts arc
boo~et cover proce-
generdy
qudfied
ser-
s,cmoNA.A
...,.. .,-..,..,,..,.,-.=..
... W. L.. LW.S”..,”C,..,.
kr
Customers With
.“.,.
..., =,.,
Special Needs...
Upt)n request, controls”
and a
brochure barriel--free kitchen for persons with
limited
fi-c>c
or speech who have access to a TDD
01- a conventional Teletypewriter
call 800-TDD-(;MC;”
to requesl
mobility. T()
of’rharge,
(lonsumers with impaired hearing
C;E
will provide Braille
for a variety
to
assisl
call
800.tj26.2000.
infk~rmation
of’(;E
appliances,
in planning a
obt>~in
these items,
(800-833-4:322)”
or service.
may
Page 16
YOUR GE ZONELINE AIR CONDITIONER
WARRANTY
Save
I
proof of original purchase date such as
your sales slip or
cancelled
check to establish warranty period.
WHAT IS COVERED
FULL ONE-YEAR WARRANTY
For one year from date of original purchase, we will provide, free of charge, parts and on-site service labor to repair or replace
the
room air conditioner that
of
~a~~:~tecause
FULL-FIVE YEAR WARRANTY
For five years from the date of original purchase, we will provide, free of charge, parts and on-site
sewice labor to repair or replace
anypati
system
evaporator and all connecting tubing) that fails because of a
manufacturing defect.
of a manufacturing
of the sealed refrigerating
(the compressor, condenser,
any part
This warranty is extended to the original purchaser and any succeeding owner for products purchased for use in the 48 mainland states, Hawaii and Washington, warranty is the same except that it is LIMITED because you must pay to ship the product to the service shop or for the travel costs to your home.
All warranty provided by our Factory Service Centers or by our authorized Customer normal working hours.
Call I-800-GE CARES (1-800-432-2737).
D.C. In Alaska the
sewice technician’s
sewice will be
Care” sewicers during
For each of the above warranties:
Transportation expense to and from a service shop and shop service labor if required will be free of charge.
WHAT IS NOT COVERED
Service trips to teach you
how to use the product.
Read your Use and Care material.
If you then have any questions about operating the product please contact your dealer or our Consumer Affairs office at the address below, or call, toll free:
GE Answer Center
800.626.2000 consumer information service
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion
may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which
To know what your legal rights are in your state, consult your local or state consumer affairs office or your state’s Attorney General.
(o
Improper installation.
If you have an installation
problem,
or if the air conditioner is
of improper cooling capacity for the
intended use, contact your dealer or installer. You are responsible for providing adequate electrical connecting facilities.
Replacement of house fuses or
resetting of circuit breakers.
In commercial locations labor
necessa~ to move the unit to a
location where it is accessible for service by an individual technician.
Failure of the product resulting
from modifications to the product or due to unreasonable use including failure to provide reasonable and necessary maintenance.
Failure due to corrosion on
models not corrosion-protected.
c
Damage to product caused by improper power supply voltage, accident, fire, floods or acts of God.
WARRANTOR IS RESPONSIBLE FOR CONSEQUENTIAL DAMAGES.
va~
from state to state.
NOT
I
Pub.
6/92
No.
CG
49-7251
Warrantor: General Electric Company
If further help is needed concerning this warranty, write:
Manager—Consumer Affairs, GE Appliances, Louisville, KY 40225
Zoneline(’)
Heat Pump
31OO
serie~
Loading...