These instructions do not purport to cover all details or variations in equipmentnor provide for every possible contingency tobe metin connection with instal-lation, operation,or maintenance. Should further information be desired orshould particular problems arise which are notcovered sufficiently for thepur-
chaser’spurpose,the matter should be referred to theGeneral Electric Company.
To the extent required the products described herein meet applicable ANSI, IEEE, and NEMA standards;but no such assurance is given withrespecttolocal codes and ordinances because they vary greatly.
239INSTRUCTION MANUAL 1 OVERVIEW1.1 239 RELAY FEATURES
The GE Multilin 239 relay is designed to fully protect three phase AC motors against conditionswhich can cause damage. In addition to motorprotection, the relayhas features thatcanprotectassociatedmechanical equipment, give an alarm before damage results from a process malfunction,diagnose problems after a faultand allow verification of correct relay operation duringroutine main-tenance. Using the ModBus serial communications interface, motor starters throughout a plant canbe connected to a central control/monitoring system for continuous monitoring and fast fault diagno-sis of a complete process.
One relay is required per motor. Since phase current is monitored through current transformers,motors of any line voltage can be protected. The relay is used as a pilot device to cause a contactoror breaker to openunder faultconditions;thatis, itdoes not carrythe primarymotor current.Whenthe over temperature option isordered, up to 3 RTDs can be monitored. These can all be in the sta-tor or 1 in the stator and 2 inthe bearings. Installing a 239 in a motor starter for protection and moni-toring of motors willminimize downtime due toprocess problems.
PROTECTION
•Overload (15 selectable curves)
•Short circuit
•Locked rotor
•Stall / mechanical jam
•Repeated starts (Mod 505)
•Single phase /unbalance
•Ground fault
•Overtemperature (Thermistor& 3 RTDs)
•Undercurrent
•Overload warning
•Breaker failure
FEATURES
•Status/current/temperature display
•Fault diagnosis
•Trip record
•Memory lockout
•Thermal capacity / load%/ RTD analogoutput
•Trip / alarm / auxiliary / service relay out-puts
Versatile features and simple programming controlsmakethe 239 an ideal choice for motor andequipment protectionin a wide rangeof applications. Inaddition to basicelectrical protection formotors, the 239 can protectagainst commonfaultsdue toprocessproblems, such as:
1.Mechanical protection ofpumps using theundercurrent feature to detect loss of suction or aclosed discharge valve.
2.Personnel safetyand mechanical protection of fansagainst loss ofair flow in mines or flow insteam generating boilers using the undercurrent feature.
3.Electrical protection of compressor motors from excessive run up time caused by an open outletusing the start timer.
4.Mechanical protection of gears, pumps,fans, saw mill cutters, and compressors against mechan-ical jam using the mechanical jam trip feature.
5.Safety to personnel from shock hazard using the ground fault feature to detect winding shorts orleakagecurrents from moisturein mines.
6.Protection of motors and equipmentfrom operatorabuse using the thermal memory lockout
Cost savings are provided usingversatile features such as:
1.Diagnostic information after a trip to identify problems and bring the process back on line quickly.
2.Fault indication of ground fault without shutdown to warn that corrective maintenance is required.
3.Simplified spare parts stocking and initial specification designusing one universal model formany motorsizes, applicationsand settings.
1
4.Serial communication using the popularModbusprotocol toremotely monitorallvalues, programsetpoints,issue commands and diagnose faults to minimize process disruptions.
5.Output of motor current suitable for programmable controller interface (4 to 20 mA).
GE Multilin239 Motor Protection Relay1-5
Page 12
1 OVERVIEW1 OVERVIEW
1
a) MODIFICATIONS
1.3 ORDER CODE
•MOD 500:Portable test/carrying case
•MOD 501:20 to 60 V DC/ 20 to 48 V AC control power
•MOD 504:Removable terminal blocks
•MOD 505: Enhanced start protection
•MOD 506:Custom programmable overload curve
•MOD 509: Directional ground sensing with 120 V AC polarizing voltage
•MOD 512:1 AMP Ground CTinput
•MOD 513: Class1 Division 2 operation
•MOD 517: Australian Mines approval
b) ACCESSORIES
•239PC Windowssoftware (free upon request)
•Phase and ground CTs
•RS232 toRS485 converter (required toconnect a computer to the239 relay(s)torun 239PC
•RS485 Terminating Network
•2.25”collar for limited depth mounting(1009-0068)
•Large size (8.5 x 11”)instruction manual (free upon request)
c) CONTROL POWER
•90 to300 V DC / 70 to 265 V AC standard
•20 to60 V DC / 20 to 48 V AC (MOD 501)
1-6239 Motor Protection RelayGE Multilin
Page 13
1 OVERVIEW1 OVERVIEW
1.4 SPECIFICATIONS
PHASE CURRENT INPUTS
CONVERSION:true rms, 16 samples/cycleCT INPUT:1 A and 5 A secondaryRANGE:0.1 to 11× phase CT primaryFREQUENCY:20 to 300 HzACCURACY:±2% of full scale
GROUND CURRENT INPUTS
CONVERSION:true rms, 16 samples/cycleCT INPUT:5 A secondary and 50:0.025RANGE:0.03 to 1.4×CT primary (5A CT)
0.05 to 16.0 A (50:0.025 CT)FREQUENCY:20 to 300 HzACCURACY:
5A CT:±2% of full scale (5A CT)50:0.025 CT:±0.03 A (0 to 0.49 A)
±0.07 A (0.50 to 3.99 A)±0.20 A (4.00 to 16.00 A)
OVERLOAD CURVES TRIP TIME
CURVES:15 curves, fixed shapeOVERLOAD PICKUP INHIBIT: 1.00 to 5.00 × FLCPICKUP LEVEL:1 to 1500 AACCURACY:
PICKUP:± 1% of Displayed ValueTIME:± 2% of trip time or ± 1 sec
whichever is greater
START PROTECTION
THERMAL:separate start & run protectionACTIVATION:inrush 3 phase current increases
from <5% to >101% FLC in 1 s
DEACTIVATION: current dropsto <100% FLC
motor running if current >5%
FLCLOCKEDROTOR:0.5 to 11.0 ×FLCSAFESTALL TIME:1.0 to 600.0 sec
THERMAL MODELING
THERMAL CAPACITY:separate start/run,
exponential cool down
COOL RATE:
STOP:1 to 5000 minutes programmableRUN:50% of stopped cool timeHOT/COLD:50 to 100%, hot after 15 min runningLOCKOUT:1 to 5000 min programmable ±20%
power on / off
UNBALANCE
RANGE:5 to 100% / OFFACCURACY:± 2%DELAY:0 - 60 secCALCULATION:
IMI
–
AV
If
I
AVIFLC
, UB%≥
-----------------------
I
AV
100×=
1
SHORT CIRCUIT& GROUND TRIP
GROUND TRIP LEVEL: 0.05 to 15A (50:0.025 CT)
3 to 100% (5A CT)S/C TRIP LEVEL:1 to 11× CT PRI / OFFINTENTIONAL DELAY:INST. or 10 to 60000 ms
programmableINST:20 to 45ms* TOTAL DELAY:INST + INTENTIONAL*trip timeaccuracy guaranteedif
current > 1.4 × trip level setting
BREAKER FAILURETIMING
DELAY:INST. or 10 to 60000 ms
programmableINST:20 to 45ms* TOTAL DELAY:INST + INTENTIONAL *trip timeaccuracy guaranteedif
current > 1.4 × trip level setting
IMI
–
AV
-----------------------
I
FLC
100×=
where:
If
I
AVIFLC
I
= average phase current
AV
I
= current in phase with maxdev. from
M
I
= full load current setting
FLC
, UB%<
THERMISTOR
TYPE:PTC or NTC programmableHOT RESISTANCE:100 to 30000 ΩCOLD RESISTANCE: 100 to 30000 ΩDELAY:2 secACCURACY:±5% or 100 Ω, whichever is
greatest
UNDERCURRENT
RANGE:5 to 100% FLC / OFFDELAY:0 to 250 sec
I
AV
GE Multilin239 Motor Protection Relay1-7
Page 14
1 OVERVIEW1 OVERVIEW
RTDs (OPTIONAL)
INPUTS:3 RTDs, stator/bearing prog.
1
TYPE:100 Pt (DIN 43760), 100 Ni, 120
Ni,10 Cu programmable
RANGE:–40 to 200 °C/ –40 to 400 °F
TRIP/ALM RANGE:0 to 200 °C / 0 to 400 °FDEAD BAND:2 °C / 4 °FACCURACY:±2 °C / ±4 °FLEAD RESISTANCE:
Pt or Ni RTD:25 Ω max Cu RTD:3 Ω max
3 wire lead resistance compensation
COMMUNICATIONS
TYPE:RS485 2 wire, half duplex, isolatedBAUD RATE:1200 to 19.2k bpsPROTOCOL:Modbus
®
RTU
FUNCTIONS:Read/write setpoints, read actual
values, execute commands
ANALOG OUTPUT (OPTIONAL)
PROGRAMMABLE
OUTPUT0-1 mA0-20 mA4-20 mA
MAX LOAD2400 Ω600 Ω600 ΩMAX OUTPUT1.1 mA21 mA21 mA
ACCURACY:±2% of full scale reading
ISOLATION:36 V DC isolated, active source
OUTPUT RELAYS
92/7$*(0$.(&$55<
RESISTIVE30 VDC103010
125 VDC10300.5250 VDC10300.3
INDUCTIVE(L/R=7 ms)
RESISTIVE120 VAC103010
INDUCTIVEPF=0.4
30 VDC10305125 VDC10300.25250 VDC10300.15
250 VAC103010120 VAC103010250 VAC103010
CONFIGURATION:FORM C NO/NCCONTACT MATERIAL: SILVER ALLOY
&217,18286
0$.(&$55<
V
%5($.
CT INPUTS
CT INPUT
(A)
10.0090.01PHASE CT(1A)
PHASE CT(5A)
GROUNDCT (5A)
GROUNDCT(50:0.025)
PHASE CT(1A)
PHASE CT(5A)
GROUNDCT (5A)
50.20.01
203.50.01
50.040.002
250.90.002
100160.002
50.040.002
251.10.002
100170.002
0.0250.07116
0.11.19119
0.530.5122
1s xCT5s xCTcontinuous
100403
100403
100403
50:0.025 GROUND INPUT WITHSTAND:
CONTINUOUS:150 mAMAXIMUM:12 A for 3 cycles50:0.025 input canbe driven by a 50:0.025 CT.
BURDEN
VAΩ
BURDEN
xCT
SWITCH INPUTS
TYPE:dry contactsOUTPUT:29 V DC, 10 mA (pulsed)DURATION:100 ms minimum
CONTROL POWER
INPUT:90 to 300 VDC or
70 to 265 VAC, 50/60 HzPOWER:10 VA (nominal) 20 VA (max)HOLDUP:non-failsafe trip: 200 ms
failsafe trip: 100 ms
both times at 120VAC / 125VDC
It is recommended that all 239 relays bepoweredup atleastonce per year to avoid
NOTE
deterioration of electrolytic capacitors in the power supply.
1-8239 Motor Protection RelayGE Multilin
Page 15
1 OVERVIEW1 OVERVIEW
FUSE TYPE/RATING
5 × 20mm, 2.5 A, 250VSlow blow, High breaking capacity
ENVIRONMENT/GENERAL INFO
POLLUTION DEGREE: 2OVERVOLTAGECATEGORY: 2INSULATIONVOLTAGE: 300 V
OPERATING TEMPERATURE RANGE: 0°C to 60°CSTORAGE TEMPERATURE RANGE: –40°C to 70°CIP CLASS:40
ISO9001 recognized programUL:Recognized under E83849CSA:Approved underLR41286
NOTE: Specifications subject tochange without notice.
GE Multilin239 Motor Protection Relay1-9
Page 16
1
1 OVERVIEW1 OVERVIEW
1-10239 Motor Protection RelayGE Multilin
Page 17
2 INSTALLATION2 INSTALLATION
239INSTRUCTION MANUAL 2 INSTALLATION2.1 MOUNTING
Physical dimensions for the 239 and the required cutout dimensions are shown below. Once the cut-out and mounting holes are made inthe panel, use the eight #6 self tappingscrews suppliedtosecure the relay. Mount the relay ona panel or switchgear doorto allow operatoraccess to the frontpanel keys and indicators.
2
GE Multilin239 Motor Protection Relay2-1
Figure 2–1:PHYSICAL DIMENSIONS
Page 18
2 INSTALLATION2 INSTALLATION
2.2 PRODUCT IDENTIFICATION
Product attributes will vary according to the configuration and options installed based on the cus-tomer order. Before applying power to the relay, examine the label on the back of the 239 and checkthat the correct options are installed.
The information included onthe product label isexplained below:
2
1
2
3
654
7
8
9
10
11
12
GE Power Management
MAXIMUMCONTACTRATING
MAXIMUM CONTACT RATING
250VAC10ARESISTIVE
250VAC10ARESISTIVE
1/4HP125VAC1/2HP250VAC
1/4HP125VAC1/2HP250VAC
®
MADEINCANADA
NRTL
MODEL
SUPPLYVOLTAGESERIALNO.:
SUPPLYVOLTAGE
TAG#1234-567-89
TAG#
239-RTD-AN
90-300VDC20VA70-265VAC50/60HZ20VA
MOD#sNONE
MOD#
FIRMWARE
64D240C4.000
110.000
D6401234
819790AH-X4.CDR
Figure 2–2: 239 PRODUCT LABEL (EXAMPLE)
1.MODEL NO: The model number shows the configuration of the relay.The model number for abasicunit is 239. RTD and AN willappear in the model number only if the RTD option or AnalogOutput optionis installed.
2.SUPPLY VOLTAGE:Indicates the 239 power supplyinput configuration. The 239 shown abovecan accept any AC 50/60Hz voltage from 70 to 265 V AC or DC voltage from 90 to300 V DC.
3.TAG#: This is an optional identification numberspecified by the customer.
4.MOD#s: These are used ifunique features have been installed for specialcustomerorders.These numbers should be available when contacting GE Multilin for technical support. Up to fiveMOD#s can be installed into the 239.
5.SERIAL NO:Indicates the serial number for the 239 in numeric and barcode format.
The following table shows the revision history of the 239. Each revision of the instruction manual cor-responds to a particular firmware revision in the 239. The instruction manual revision islocated onthe first page of the manual as part of the manual P/N (1601-00XX-Revision). The 239 firmware revi-sion is loaded inthe relay andcan be found byscrollingto the displaymessage
,1)2?),50:$5(9(56,216?0$,1352*5$09(5
.
$352'8&7
When using the manual to determine relay features and settings, ensure that the revision corre-
sponds to the 239 firmware revision using the table below. For a large instruction manual (8.5” × 11”)the part number is1601-0067; fora small instruction manual (5.5” × 7.25”)it is1601-0060.
Table 2–1:FIRMWARE/MANUAL REVISIONS TABLE
MANUAL PARTNO.FIRMWARE VERSIONMANUAL PART NO.FIRMWARE VERSION
Signal wiring is to box terminals that can accommodate wire as large as 12 gauge. CT connections
are made using #8 screw ring terminals thatcan acceptwire as large as8 gauge (see Figure 2–3:TYPICAL WIRING DIAGRAM on page 2–4).A minimal configuration will includeconnections forcontrol power,phase CTs and the trip relay. Other features can be wired as required. Considerationsfor wiring each feature are given inthe sectionsthatfollow.
Table 2–2:EXTERNAL CONNECTIONS
CT ROWSIGNAL LOWER ROWSIGNAL UPPER ROW
1Phase ACT5A13Safety ground36Control live(+)2Phase A CT 1A14Filter ground37Control neutral (–)
3Phase A CT COM15RS485 A+38Sw com4Phase B CT 5A16RS485 B–39Sw com5Phase B CT 1A17RS485 ground40Sw com6Phase B CT COM18Analogout +41Sw com7PhaseC CT 5A19Analog out –42Sw com8Phase C CT1A20Analogout shield43Access sw +
SHIELD TERMINALS ARE INTERNALLYCONNECTED TO SAFETY GROUNDTERMINAL 13
4)
RTD TEMPERATURE SENSINGAND ANALOG OUTPUT OPTIONAL
50:0.025
GROUND CT
TWISTLEADS
9
10
5A
GROUND
RS485 +
RS485 -
0-1mA
4-20mA
SHIELD
COM
SHIELD
HOT
COMP
HOT
COMP
HOT
COMP
11
12
COM
50:0.025
15
16
17
18
19
20
IN+
21
22
48
49
50
51
RET
52
53
RET
54
55
56
57
RET
L1L1
L2L2
L3L3
Figure 2–3:TYPICAL WIRING DIAGRAM
MOTOR
USE SHIELDED TWISTED
PAIR WIRE
RS485
THERMALCAPACITY
STATOR
THERMISTOR
STATOR
RTD
STATOR/
BEARING RTD
STATOR/
BEARING RTD
USE SHIELDED WIRE
819751B5.DWG
819829B6.CDR
2-4239 Motor Protection RelayGE Multilin
Page 21
2 INSTALLATION2 INSTALLATION
a) CONTROL POWER (36/37)
A universal AC/DCpower supply is standard. It covers the range 90 to 300 V DC and 70 to 265 V ACat 50/60 Hz. It is not necessary to make any adjustment to the relay as long as the control voltagefalls within this range.A low voltage power supply is available upona request of MOD# 501. It coversthe range 20 to 60 V DC and 20 to 48 V AC at 50/60 Hz. Verify from the product identification labelon the back of the relay thatthe control voltage matches the intended application. Connectthe con-trol voltage input to a stable source of supply for reliable operation. A 2.5 A fuse is accessible fromthe back of the unitwithout opening the relay by sliding back the fuse accessdoor.
b) PHASE CT INPUTS (1-9)
Current transformer secondaries of 5 or 1 A can be used for current sensing. Each phase currentinput has 3 terminals: 5 A input, 1 A input, and common. Select the 1 or 5 Aterminal and common tomatch thephase CT secondary. Observethe polarity indicated in theTYPICAL WIRING DIAGRAM,otherwise current measuresincorrectly forthe 2-phase or residuallyconnected CTconfigurations.
CTsshouldbe selected tobe capable of supplying the required current tothe total secondary loadwhich includes the 239 relay burden mentioned inSection 1.4: SPECIFICATIONS at rated second-ary current and the connection wiring burden. The CTmust not saturate under maximum currentconditions which can be up to 8 times motor full load during starting or greater than 12 times during ashort circuit. Only CTs rated for protective relaying should be used since metering CTs are usuallynot rated to provide enough current during faults.Examples oftypicalCT ratings are:
2
Table 2–3:TYPICAL CT RATINGS
25*$1,=$7,21&/$667<3(&7,1387'(),1,7,216
CSA(Canada)
ANSI (USA)10T4 B0.2 or
IEC (Europe)5P15 0.2VA1 AmpP= Protection class
NOTE:
The sizes shown above may not be standard CTratings. The numbers are merely used to indicatewhat size CTs can be used with the 239.
10L4 B0.21 AmpL = Protection class
10 =10% ratio error4 =Voltage the CT can deliver to load burden at 20 × rated
secondary current without exceeding the 10% ratio error
B0.2 =Maximum burden (0.2Ω)that can be put on the
transformer without exceeding the 10% ratio error
10L20 B0.25 Ampsame as1 Amp input
1 AmpT = Ratings determined by Tests
10C4 B0.2
10T20 B0.2 or10C20 B0.2
5P15 2.5VA5 Ampsame as 1 Amp input
5 Ampsame as 1 Amp input
C = Ratings determined by Calculations10 = 10% ratio error4 =Voltage the CT can deliver to load burden at 20 × rated
secondary current without exceeding the 10% ratio error
B0.2 =Maximum burden (0.2Ω)that can be put on the
transformer without exceeding the 10% ratio error
5 = Maximum %voltage error at limiting factor15 =
Limit factor,determinesmax. voltage CT can deliver toload burden without exceeding the %voltage error
0.2 = Maximum amount of continuous burden allowed forrated CT secondary
GE Multilin239 Motor Protection Relay2-5
Page 22
2 INSTALLATION2 INSTALLATION
c) GROUND CT INPUT (10/11/12)
Ground sensing terminalsare labeled 5A, 50:0.025, and COM. Connectiondepend on the groundingsystem and sensitivity required. For high resistance grounded systems that limit the ground currentor in mines where low levels of ground leakage must be detected, use a separate CT to senseground current.In this configuration,referred to as zero sequence or core balance detection, allthree phase conductors must pass through the CT window. Ifthe phase conductors are bundled in acable with a ground, the ground wiremust eitherpass outside the ground CT window or be routed
2
back through the windowifitpasses through as part of the cable. Shielded and unshielded cableinstallations are illustrated in theTYPICAL WIRING DIAGRAM.A ground CT witha ratio of50:0.025for sensing primary ground currents from0.05 to 15 A isavailable from GE. Connect this CT to termi-nals 50:0.025 and COM. If a conventional 5 A secondary CT is used for zero sequence ground sens-ing, connect itto the 5A and COM terminals. A 1 A secondary CT can also be used; however, toprevent readings from being off by a factor of 5, the ground CT primary setpoint must be adjusted.
See Section 4.3a) CTINPUTS on page 4–10 under
*5281'&735,0$5<forsuitable settings in this
situation. Due to the low secondary currents, it is recommended that the ground CT secondary leadsbe twisted togetherand routed to the 239 away from high currentcarrying conductors.NOTE: The
50:0.025 input is only recommended for resistance grounded systems. Where the system issolidly grounded orhigh levels of current are to be detected use the 5A ground input.
For low resistance or solidly grounded systems where higher ground fault currents will flow, thephase CTs can be residually connected to provide ground sensing levels as low as 20% of the phaseCT primary rating. For example, 100:5 CTs connected inthe residualconfiguration cansense groundcurrents as low as 20 A (primary) without requiring a separate ground CT. This saves the expense ofan extra CThowever 3 phase CTs are required. If this connection is used on a high resistancegrounded system verify thatthe ground fault alarm and trip current setpoints are below the maximumground current that can flow due to limiting by the systemground resistance. Sensing levels below20% of thephase CT primaryrating are notrecommended forreliable operation.
UNSHIELDEDCABLE
SHIELDEDCABLE
Figure 2–4: CORE BALANCE GROUND CT INSTALLATION
2-6239 Motor Protection RelayGE Multilin
Page 23
2 INSTALLATION2 INSTALLATION
d) OUTPUT RELAYS
There are 4 output relays each with form C contacts(normally open (NO), normally closed (NC), andcommon (COM)). Contact ratings for each relayare identical and are listed in Section 1.4: SPECIFI-
CATIONS. Figure 2–3: TYPICAL WIRING DIAGRAM on page 2–4 shows the state of the relay con-tacts withnocontrol power applied; thatis,the relays are not energized. Relay contact wiring willdepend onhow the relay operation isprogrammedin
62873875(/$<6 (seeSection 4.4: S3: OUT-
PUT RELAYS on page 4–13).
Relay contacts must be considered unsafe to touch when the system is energized. Ifthe relay contacts are required for lowvoltage accessible applications, itis the cus-
WARNING
tomer’s responsibility to ensure proper insulation levels.
•TRIP RELAY (23/24/25): Wiring ofthe trip relay contacts willdepend on whether a breakerorcontactor is themotor tripping device and if failsafe or non-failsafe operation is desired. See pro-gramming considerationsfor thetriprelay in Section4.4a) TRIP RELAYon page 4–14.
2
Contactor:
For maximum motor protection, program the trip relay to be failsafe and wire thecontactor to the NO/COMtrip relay terminals. When control power is lost to the 239, the con-tactor will trip to ensure maximum protection. If process considerations are more importantthan protection, programnon-failsafe and wire the contactor to the NC/COM trip relay termi-nals. When control power to the 239 is lost, no protection isavailable and the motor will con-tinue to run. This has the advantage that the process will not shut down, however the motormay be damaged ifa faultdevelops underthese conditions.
Breaker:
Wire the breaker tripcoil to the NO/COM triprelay terminals. The breaker auxiliary52a contact (closed when the breaker is closed) should be wired in series with the trip relaytobreak the current to the trip coil as soonas the breaker opens. Program the trip relay as non-failsafe. Breaker close coil control is not provided by the 239 as itis a protection device. Con-trolfor closing the breaker mustbe provided externally.
•ALARM RELAY (26/27/28): A selected alarm condition willcause the alarmrelay to activate.Alarms can be disabled for each featureso that only desired conditions cause analarm. Alarmconditions thatcan beprogrammed to activate the alarm relayare: ground fault, undercurrent,phase unbalance, overload,RTD 1-3, thermistor, option switch 1, option switch 2, testandloss ofcontrol power(failsafe mode).If an alarm isrequiredwhen control poweris notpresent, indicat-ing that protection is not available, select
5(/$<6?$/$505(/$<?$/$5023(5$7,21
)$,/6$)( operation for thealarm relay using 6287387
. Contacts NC/COM will be normally open going to a closedstate on an alarm. Since the service relay gives a fault indication for loss of control power, it maybe preferable to have no alarm on loss of control power and use the service relay for this indica-tion to distinguish it from a process problem. In this case, wire the external alarm to the NO/COMterminals which willbe normally open going to a closed state on an alarm condition. If
81/$7&+('
mode isselected using setpoint 62873875(/$<6?$/$505(/$<?$/$50$&7,9$7,21 the alarm relayautomatically resets when the alarm condition disappears. For
/$7&+(' mode, the key
RESET
must be pressed (or serial port reset command received) to reset the alarm relay.
•AUXILIARY RELAY (29/30/31): An additionaloutputrelay isprovided which can be configuredfor:
short circuit/groundtrip:
output to trip the main feeder breaker in the event of a short circuit at the motor. See setpoint
Contactorsare not ratedto open undera shortcircuit. Use this
Page 24
2 INSTALLATION2 INSTALLATION
undercurrent:
Use as a process control output such as in a conveyor where an undercurrentcondition controls flow of product onto the conveyor or in a pump situation to control a valve.Also can be used asan independent alarm.Seesetpoint
63527(&7,21?3+$6(&85
5(17?81'(5&855(17?81'(5&855(17)81&7,21
serial port command:
For remote control via the RS485 communications link, a command
can be issued to directlycontrol this relay. This may be useful for control applications. See
2
Chapter 7: COMMUNICATIONS.For further process control the auxiliary relay can beassigned to
switch 2
, or
thermistor function
.
option switch 1, option
•SERVICE RELAY (32/33/34): If the 239 detects an internal failure during its self monitoring or ifcontrol power is not present, the NO/COM terminals of the servicerelay will be opento indicatethat service is required. This relay is internally programmed to be failsafe so that in the normalcondition, withcontrol power applied, the relay isenergized and the NO/COM terminals shown inFigure 2–3: TYPICAL WIRING DIAGRAM on page 2–4 are closed. Connect these relay contactstoasuitable signaling input of a DCS system.
e) SWITCH INPUTS
Eachswitchcommon terminal 38/39/40/41/42 is internally connected inside the 239. A single com-mon wire can be connected between anyof these terminals and a remote switchcommon terminaltoreduce wiring if preferred.
239
RELAY
ISOLATEDPOWERSUPPLY
+29VDC
FILTERIN
TOLOGIC
OPTO
ISOLATION
Figure 2–5:SWITCH INPUT CIRCUIT
•SETPOINT ACCESS (38/43):The access terminals 38 and 43 must be shorted together in orderfor the faceplate keypad to have the ability to store new setpoints. Typically theaccessterminalswould be connected to a security keyswitch to allow authorized access only. Serial port com-mands to store a new setpoint will operate even if the access terminals are not shorted. When a
TYPICAL
SWITCH
TERMINALS
COM
10mAPULSED
819780A3.CDR
EXTERNALSWITCH
2-8239 Motor Protection RelayGE Multilin
Page 25
2 INSTALLATION2 INSTALLATION
jumper wire is connected between the accessterminals all setpoints and configurations can beprogrammed using the keypad. Once programming is complete the jumper willnormally beremoved fromthese terminals or the connected keyswitch left open. When this isdone all actualandsetpoint values can still be accessedfor viewing; however, ifan attempt is made to store anew setpoint value themessage point will remain intact. In this way all of the programmed setpoints will remain secure andtamperproof.
•EMERGENCY RESTART (39/44): When production or safety considerations become more
important thanmotor protection requirements, itmay be necessary to restart a tripped motor. If itis desired to override relay trips or lock-outs and restart the motor, a normally open keyswitchshould beinstalled between the emergency restart terminals 39and 44. Momentarily shortingthese terminals together will cause the thermal memory of the 239 todischarge to 0% used. Theemergency restartterminals can be used to override a triplockout causedbya runningoverloador locked rotor start.This option should be used only when animmediate restart after a lock-outtrip is required for process continuity or personnel safety. Discharging the thermal memory of the239gives the relay an unrealistic value forthe thermal capacityremaining inthe motor and itispossible to thermally damagethe motor by restarting it.Shorting the Emergency Restart termi-nals together will have no effect unlessthe motor is stopped (no phaseor ground currentpresent). Having these terminals permanently shorted togetherwill cause the memoryto becleared wheneverthe motor stops.This willallow for an immediate restartafter an overload trip.Caution is recommended in the use of Emergency Restartinputsince the thermal protectivefunctions ofthe 239 will be over-ridden and itis possible to damage the motor.
•EXTERNAL RESET (40/45): An external reset switch which has the same effect as the front
panelRESET key or a serial port reset command can be connected to terminals40 and 45 forremote reset operation. The switch should have normally open contacts. Upon the momentaryclosure ofthese contacts the 239 will reset anylatched alarm, latched auxiliary relay output,ortrip providing itis notlocked out. Installing a jumper wire permanently acrossthe external resetterminals will cause the 239 to reset any latchedalarm or trip whenever motor conditions allowfor automatic reset.
•OPTION SWITCH1 (41/46) & 2 (42/47): Two option inputs are provided. These switch inputs are
considered active when closed. The state of these input switches can be monitored by the serialport forprocess signaling. Theycan also be programmed to provide an alarm, trip, alternatemotor control setpoints or processcontrolafter a programmable time delay. Programming forthese switch inputs,if used,is found in
illegal access
63527(&7,21?6:,7&+,13876setpoints.
willappear on the display and the previous set-
2
f) THERMISTOR INPUT (21/22)
A motor can be equipped with a single thermistor inthe end turns or three in the stator windings forovertemperature detection.Either positive thermal coefficient (PTC)or negative thermal coefficient(NTC) type thermistors may be directlyconnected to the 239. PTC thermistors are preferred because3 thermistors can be connected in series to monitor each of the stator phases. This is not possiblewith NTC thermistors because all three thermistors must be hotto obtain an indication. Selectther-mistors that have a resistance between 100 to 30000 Ω at the intended alarm/trip temperature.Either linear thermistors or those with a sharp change in resistance at the required temperature canbe used. If no thermistor sensing is required, these terminals can be left disconnected and the ther-mistor featureprogrammed OFF.
GE Multilin239 Motor Protection Relay2-9
Page 26
2 INSTALLATION2 INSTALLATION
g) RTDS (OPTION) (48-57)
Up to3 resistance temperature detectors(RTDs) must be supplied with the motor touse this option.Verifythat the RTD option is installed by noting that the product identification label on back of therelay includes -RTD in the order code. When ordering a motor with RTDs, the 100 Ω platinum DIN43730 type is the preferred choice for optimum sensitivity and linearity.Other RTDs that can beselected and used with the 239 are 100 Ω nickel, 120Ω nickel and 10 Ω copper. RTDs do not haveto be the same type, however the 239 must be programmed correctly so that each RTD input
2
matches the installed type. The factory default is 100 Ωplatinum. RTDs are placed inthe stator slotsand/ormotor bearingstoprovide the required sensing signals to the 239 relay.
Up to 3 resistance temperature detectors (RTDs) may be used for motor statorand bearing tempera-ture monitoring. Since an RTD indicates temperature by the value of its resistance, it is necessary tocompensateforthe resistance ofthe connecting wires, which isdependent on leadlength and ambi-ent temperature. The 239 uses a lead compensation circuit to cancel thislead resistance and readonly the actual RTD resistance.Correct operation willoccurproviding all three wires are of the same
length and the resistance of each lead is not greater than 25% of theRTD 0°C resistance (see Sec-tion 1.4: SPECIFICATIONS on page 1–7). This can be accomplished by using identical lengths of thesame type of wire. Each RTD COM terminal is internally connected to the safety ground, terminal 13.Consequently, where code permits, the 3 RTD terminals should not be grounded at the motor end forthe leadresistance compensation to workcorrectly.If 10 Ω copper RTDs are used, special careshould be taken to keep the lead resistance as low as possible. Ifno RTD sensor is installed,the cor-responding terminals may be left unconnectedand the RTD programmed as OFF.
Shielded,three wire cable must be used in industrial environments to prevent noise pickup. Wher-ever possible, the RTD leadsshould bekept closeto grounded metal casingsand avoid areasofhigh electromagnetic or radiofrequency fields. RTD leads shouldnot run adjacent to, or inthe sameconduit as high current carrying wires. Use either multiconductor shielded cable for all 3 RTDsorseparate three wire shielded cable of #18 AWG copper conductors for each RTD. The 239 shield ter-minal(48) and each RTD COM (51,54,57) are internallyconnected to safety ground,terminal13.The shield connection of the RTD cable should not be grounded at both ends. This arrangement pre-vents noise pickup that could otherwise occur from circulating currents due to differences in groundpotentials on a doublygrounded shield.
Terminals18-20 of the 239 are available fora single analog currentoutputof one parameter. Verifythatthe Analog Output option is installed by noting that the product identification labelonback of therelay includes-ANin the order code. The choice of output and current rangeis selected in
6(783?$1$/2*287387?$1$/2*2873877<3(5$1*(
. Use the TYPE message to select one of the fol-
6
lowing for output: phase CT (secondary) amps,%motor full load current (FLC),thermal capacityused (100% = motor tripped), RTD1 temperature, RTD2 temperature, or RTD3 temperature. TheRANGE message selects the output current as: 0-1 mA, 0-20 mA or4-20 mA. Rangeassignment is
shown below in Table 2–4: ANALOG OUTPUTRANGE ASSIGNMENT.
Table 2–4:ANALOG OUTPUT RANGE ASSIGNMENT
PROGRAMMED RANGE
2
SELECTED OUTPUT
Average PhaseCurrent0 A1A/5A*0 A1A/5A*0A1A/5A*Motor FullLoad%0%200%0%200%0%200%Thermal Capacity0%100%0%100%0%100%RTD 1-3 Temperature0°C180°C0°C180°C0°C180°CForced Output0%100%0%100%0%100%
* 1 Amp CT secondary = 1A,5 AmpCTsecondary= 5 A
0-1 mA0-20 mA4-20 mA
0 mA1 mA0 mA20 mA4 mA20 mA
This output is a current source suitable for connection to a remote meter, chart recorder, programma-ble controller, or computer load. Use the 4-20 mA with a programmable controller that has a currentinput. If only a voltage input isavailable use a scaling resistor at the PLC terminals to scalethe cur-rent to theequivalent voltage and select the 0to 20 mA output.For example,install a 500 Ω resistoracross the terminals of a 0 to 10 V input to make the 0 to 20 mAoutput correspond to 0 to 10V (R =V/I = 10 V / 0.02 A = 500 Ω). When the GE Multilin TCS2 thermal capacity meter is connected to theterminals, select the 0 to 1 mA range. Current levels are not affected by the total lead and load resis-tance which must not exceed 600 Ω for 0-20 mAand 4-20mA range and 2400 Ω for 0-1mA range.For readings greater than full scale the output willsaturate at 21 mA (0-20/4-20 range) or 1.1 mA (0-1 range). This analog output is isolated. Since both output terminals 18 and 19 are floating, the con-nection of the analog output to a process inputwill not introduce a groundloop.Part of thesystemshould be grounded for safety, typically at the programmable controller. For floating loads, such as ameter, ground terminal 19 externally. Terminal20 isinternallygrounded and may be used as a shieldground if required. Ground the shield at one end onlytoprevent groundloop noise.
i) SERIAL PORT (15/16/17)
A serial port provides communication capabilities between the 239anda remote computer, PLC ordistributed control system (DCS). Up to thirty-two 239 relays can be daisy chained together with 24AWG stranded, shielded, twisted pair wire on a single communication channel. Suitable wire shouldhave a characteristic impedance of 120 Ω suchasBelden #9841. These wires should be routedaway from high power AC lines and other sources of electrical noise. The total length of the commu-nications wiring should not exceed 4000 feet for reliable operation. Correct polarity is essential forthe communicationsport to operate. Terminal 15(485 A+) of every 239 in a serial communication linkmustbeconnected together. Similarly, terminal 16 (485B-) of every 239 must also be connectedtogether. These polarities are specified for a 0 logic and should match the polarity of the master
GE Multilin239 Motor Protection Relay2-11
Page 28
2 INSTALLATION2 INSTALLATION
device. Whenthe communications link is active, the frontpanel&20081,&$7( light willbe solid ifvalid data and relay address are being received. If the front panelindicate invalid data, try reversing the wires to terminals 15 and 16. Each relay must be daisy
chained to the next one as shown in Figure 2–7: RS485 COMMUNICATION WIRING on page 2–12.Avoid staror stub connected configurations. If a large difference in ground potentials exists, commu-nication on the serial communication link will not be possible. Therefore, it isimperative that theserial master and 239 are both at the same ground potential. This is accomplished by joining 485
2
ground terminal17 ofevery unit together and grounding itat the master only.The last 239 in the chain and the master computer need a terminating resistor and terminating
capacitor to preventcommunicationerrors by ensuring properelectrical matching ofthe loads. Usingterminating resistors on all the 239s would load down the communication network while omittingthem at the ends could cause reflections resulting ingarbled data. Install the 120 Ω / ¼ watt terminat-ing resistorsand 1 nF capacitor externally. Although any standard resistoror capacitor ofthese val-uesare suitable, these components can also be ordered from GE Multilin as a combined terminatingnetwork.
Each communication link must have only one computer (PLC or DCS) issuing commands called themaster. The master should be centrally located and canbe used toview actual values and setpointsfrom each 239 relay called the slave device.Other GE Multilin relays or devices that use the ModbusRTU protocol can be connected to the communicationlink.Setpoints ineach slave can also bechanged from themaster.Each 239 in thecommunication link mustbe programmed with a differentslave address prior to running communications using 239PC, a communications software package developed by GEMultilin, may be used on a PC toview motor status, actualvalues, and view and alter setpoints.
66(783?566(5,$/3257?6/$9($''5(66.
&20081,&$7( light flashes to
Figure 2–7: RS485 COMMUNICATION WIRING
2-12239 Motor Protection RelayGE Multilin
Page 29
2 INSTALLATION2 INSTALLATION
j) GROUNDING
•SAFETY GROUND (13):Connect the safety ground terminal 13 to a reliable system ground
within the starterusing heavy gauge wire. For safety, all metal parts within the 239 are connectedto this ground terminal. Shield terminals 20/48 and RTD COM terminals 51/54/57 are internallyconnected tothe safety ground, terminal 13.
•FILTER GROUND (14): Using #12 gauge wire or ground braid, connect this terminal to a solid
system ground, typicallya copper bus inthe starter. Extensive filtering and transient protectionisbuilt into the 239 to ensure reliable operation under harsh industrialoperating environments.Transient energy must be conducted back to the source through filter ground terminal 14. The fil-ter ground terminalis separated from the safetyground terminal to allow dielectrictesting of astarter witha 239 wired up.
When properly installed, the 239 will meet the interference immunityrequirements of IEC 801 andANSI C37.90.
2.4 DIELECTRIC STRENGTH TESTING
It may be required to test a complete motor starter for dielectric strength with the 239 installed. Thisisalso known as "flash" or "hipot" testing. The 239 is rated for 1530 V ACisolation for 1 minute (or1836 V AC for 1 second) between relay contacts, CT inputs, control power inputs and safety groundterminal 13. Someprecautions are necessaryto prevent damage to the 239 during these tests.
2
Filter networks and transient protection clamps areused betweenthe control power, serial port,switch inputs, analog output, thermistor, RTDs inputs and the filter ground terminal 14 tofilterouthigh voltage transients,radio frequency interference (RFI) and electromagnetic interference (EMI).The filter capacitors and transient absorbers could be damaged by the continuous high voltages rel-ative to ground that are applied during dielectric strength testing. Disconnect the filter ground termi-nal 14 during testing of the control power inputs. Relay contact and CT terminals do not require anyspecial precautions.Do not dielectric strengthtest the serial port, thermistor, RTD or analog
output terminals else the239 internal circuitrywill be damaged.
GE Multilin239 Motor Protection Relay2-13
Page 30
2
2 INSTALLATION2 INSTALLATION
Figure 2–8: DIELECTRIC STRENGTH TESTING
2-14239 Motor Protection RelayGE Multilin
Page 31
3 OPERATION3OPERATION
239INSTRUCTION MANUAL 3 OPERATION3.1 FRONT PANEL
The local operator interface for setpoint entry and monitoring of measured values is from the frontpanel, as shown in the figure below. Control keys are used to select the appropriate message forentering setpoints or displaying measured values.Alarm and status messages are automatically dis-played when required. Indicator LEDs provide important status information at all times.
All messages are displayed in English on the 40-character LCD display, which is visible under varied
3
lighting conditions. While the keypadand displayare notactively being used, the screen will displaythe default statusmessage. This message will appearifnokey has been pressed for the time pro-grammed in
66(783?35()(5(1&(6?'()$8/70(66$*(7,0(. Trip and alarm condition messages
will automatically override default messages.Tomaximizethe lifetime of the display, itsbrightness can be varied using the setpoint
6(783?35()(5(1&(6?'()$8/70(66$*(%5,*+71(66
.Thedisplay will adjust to set brightness levelwhen
6
the default messages are being displayed. If any one of keyson the 239 keypad is pressed or analarm/trip is present the display brightness will automatically become 100%. Ifthe default messagestime isset to OFF, the 239 display will dim to the set brightness level after 5 minutes have elapsedsince one of the keys on the keypad was last pressed.
NOTE: Message brightness control is available only on units withthe VFD display.
3.3 STATUS INDICATORS
TRIP
AUXILIARY
SERVICEALARM
PICKUP
COMMUNICATE
819762A7.CDR
Figure 3–3: 239 STATUS INDICATORS
•TRIP: The
75,3indicator flashes when the 239 has tripped. This willbe caused by any trip condi-
tion(overload, short circuit etc.)or a serial trip command issued via thecommunicationport. Theindicator and the trip relayare reset manually by pressingthe key,remotely using a
RESET
computer reset command, or by closing the external reset input.
•ALARM: The will be on while the
$/$50 relay isintended for general purpose alarm outputs. The $/$50 indicator
$/$50 relay is operating. If the $/$50 is programmed as unlatched, this
indicator will flash as long as the alarm condition persists. Whenthe condition clears,the
$/$50indicator will turn off. If the alarm relay has been programmed as latched, the alarm con-
dition can only be cleared by pressingthe key, by issuing a computer resetcommand,
RESET
or by closing the external reset input.
•AUXILIARY: The
,$5<
indicator willturn on while the $8;,/,$5<relay is operating.
$8;,/,$5<relay is intended forcustomer specific requirements.The$8;,/
3-2239 Motor Protection RelayGE Multilin
Page 33
3 OPERATION3OPERATION
SETPOINT
•SERVICE: Anyabnormal condition detected during 239 self-monitoring, suchasahardware fail-
ure, willcause the operated state is "Energized," operated state is "De-energized"). The on while the also causesthe
6(59,&(relay to operate.This relay isprogrammed tobe failsafe(i.e.non-
6(59,&( indicator will turn
6(59,&( relay is operating (i.e. de-energized). Loss of control power to the 239
6(59,&( relay to be de-energized, indicating thatno protection is present.
•PICKUP: During testing, for calibration verification, it is useful to have an indication of when the
motor full load or ground trip pickup setting has been exceeded. Eventually an alarm or a trip willoccur if these conditions persist.The indicatorwill remain flashing as long as themotor fullloadsetting remains exceeded while the motor is running or ground current is above the ground trippickup level. The indicator will automatically turn off when the phase current drops below the fullload threshold and the ground current isbelow thetrippickup setting.
•COMMUNICATE:Status ofthe RS485 communicationport ismonitored with this indicator. If
there is no serialdata being received via the rear serial port terminals the
&20081,&$7( indi-
cator will be off.This situation will occur if there is no connection, the serial wires have becomedisconnected or the master computer isinactive. If there is activity on the serial port but the 239is not receiving valid messages for its internally programmed address the indicator will flash. Thiscould be caused by incorrect message format such as baud rate or framing, reversed polarity ofthe two RS485 twisted pair connectionsor the master not sending the currently programmed 239address. If the 239 is being periodically addressed with a valid message, the
&20081,&$7(
indicator willbe on continuously. If no valid message has been received for 10 seconds, the indi-cator willeither flash (serial data present) or go off (no serial data).
3
3.4 KEYS
ACTUAL
MESSAGE
SETPOINT
STORE
VALUE
RESET
819764A4.CDR
Figure 3–4: FRONT PANEL KEYS
•SETPOINT: Setpointsare arranged into groups of related messages called setpoint pages. Each
time the key is pressed, the display advances to the first message of the next page ofsetpoints. Pressing thedisplay to the beginning of the next page. The and keys are used to move
SETPOINT
key while in the middle of a page of setpoints advancesthe
MESSAGE
▼
MESSAGE
▲
between messages within a page.
•ACTUAL: Measured values and collected data messages are arranged into groups of related
messages called actual values pages. Each time the key is pressed, the display
ACTUAL
GE Multilin239 Motor Protection Relay3-3
Page 34
3 OPERATION3OPERATION
STORE
MESSAGE
▼
advances tothe first messageofthe next page ofactual values.Pressing the key whilein themiddle of a page of actual values advances the display to the beginning of the next page.
MESSAGE
The and
▲
MESSAGE
▼
keys are used to movebetween messages within a page.
•STORE: When programming setpoints, enter the new value using the followed by the key.Setpointprogramming must be enabled forthe key to
STORESTORE
store the edited value. An acknowledgment message will flash if the new setpoint is successfullysaved innon-volatile memory. The keyis also usedto add and remove userdefined
•RESET:. After a trip the indicator.The key willclear the tripindicator and the active trip message if thecause of
RESET
75,3 indicator will be flashing. Press the key to clear the trip
the trip is no longer present. If the tripcondition isstill present, one of following two messages will
3
flash to indicate thatresetis notpossible.
RESET NOT POSSIBLE
OVERLOAD LOCKOUT
RESET NOT POSSIBLE
FAULT STILL PRESENT
The key, along with the key, is also used to remove user defined default mes-
RESET
Displayed when overload trip lockout condition is present.
Displayed when a trip condition otherthan an overload trip lockout ispresent.
sages.Refer to Section3.6: DEFAULT MESSAGES on page 3–6 forfurtherdetails.
RESET
VALUE
▼
ACTUAL
/
VALUE
▲
keys,
•MESSAGE UP/DOWN/LEFT/RIGHT:Tomove between message groups within a page use the
MESSAGE
MESSAGE
▲
▲
MESSAGE
/ keys. The key moves toward the end of the page and the
▼
keymovestowardthe beginning of the page. A page header message will appearatthe beginning of each page and a page footer message will appear at the end of each page. Toselect messages within a subgroup press . To backout of thesubgroup or access theprevious message,press.
MESSAGE
3
MESSAGE
4
3-4239 Motor Protection RelayGE Multilin
Page 35
3 OPERATION3OPERATION
VALUE
▲
MOVES TOPREVIOUS
SUBGROUP
MESSAGE
MOVES
TO NEXT
SUBGROUP
SETPOINT
]] SETPOINTS]] S1 239 SETUP
MESSAGE
MESSAGE
▲
▼
] PREFERENCES]
MESSAGE
MESSAGE
▲
▼
] ANALOG OUTPUT]
MESSAGE
MESSAGE
MESSAGE
SETPOINT
]] SETPOINTS]] S2 SYSTEM SETUP
MOVES BACK
WITHIN SUBGROUP
4
TEMPERATURE DISPLAYIN: CELSIUS
DEFAULT MESSAGE TIME
3
1.0 MINUTESDEFAULT MESSAGE
BRIGHTNESS: 60%
BLOCK KEYPAD TRIPRESET: NO
4
ANALOG OUTPUT TYPE:MOTOR LOAD
MESSAGE
MOVES FORWARD
WITHIN SUBGROUP
3
ANALOG OUTPUT RANGE:
3
0–1 mA
4
SERIAL COMMS FAILUREALARM: OFF
SLAVE ADDRESS:
3
1
BAUD RATE:
MESSAGE
MESSAGE
▲
▼
] RS485 SERIAL PORT]
MESSAGE
▲
MESSAGE
MESSAGE
MESSAGE
9600 BAUD
MESSAGE
▼
MSGKEYOP.VSD
Figure 3–5: MESSAGE KEY OPERATION
VALUE
▼
VALUE
•VALUE UP/DOWN:Setpoint valuesare entered using the point is displayed calling for a yes/no response, each time or is pressed, the
VALUE
/
▼
▲
keys. When a set-
VALUE
▲
"Yes" becomes a "No," or the "No" becomes a "Yes." Similarly, for multiple choice selections,
VALUE
each time or is pressed the next choice is displayed. When numeric values
▼
GE Multilin239 Motor Protection Relay3-5
Page 36
3 OPERATION3OPERATION
SETPOINT
MESSAGE
▲
VALUE
are displayed, each time is pressed, the value increases by the step increment, up to
▲
the maximum. Hold the key down to rapidly change the value.
•KEYPAD ENTRY: Pressthe
SETPOINT
the keyseveral times to move to the top of successive pages. A header message with
key once and the first page of setpoints is displayed. Press
two barsin the first two character positionsis the start of a new page. The page number andpage title appear on the second line. All setpoint page headers are numbered with an ‘S’ prefix.Actual value page headers are numbered with an ‘A’ prefix.
]]]]
]]
||
3
PAGE HEADERMESSAGE
The messages are organized into logical subgroups within each Setpoints and Actual Valuespage as shown above.
Press the
MESSAGE
3
subgroup. Otherwiseselectthe /keys todisplay the next subgroup.
•COMPUTER ENTRY: When using a computer running 239PC software, setpoint values aregrouped together on a screen. The data is organized ina system of menus. See Chapter 6:239PC SOFTWARE for further details.
•SCADA ENTRY: Detailsof the complete communication protocol for readingand writing set-points are given in Chapter 7: COMMUNICATIONS. A SCADA system connected to the RS485terminals can be customer programmed to make use ofany of the communication commands forremote setpoint programming, monitoring and control.
Hardware security is designed into the relay to provide protection against unauthorized setpointchanges. To program newsetpoints using the front panel keys a hardware jumper must be installedacrossthe setpoint access terminals on the back of the relay. These terminals can be permanentlywired to a panel mounted keyswitch if this is more convenient. Attempts to enter a new setpoint with-out the electrical connection across the setpoint access terminals will result in an ‘ILLEGALACCESS’ error message. When setpoint programming is via a computer connected to the rearRS485 communication port, no setpoint access jumper is required. If a SCADA system is used forrelay programming, itis up to the programmer to design in appropriate passcode security.
SUBGROUP HEADERMESSAGE
MESSAGE
/
4
key when displaying a subgroup to access messages within that
MESSAGE
SUB-SUBGROUPHEADER MESSAGE
▼
MESSAGE WITHIN SUB-SUBGROUP OR SUBGROUP
3.5 SETPOINT ACCESS
Up to5 default messagescan beselected toautomatically scan sequentiallywhenthe 239 isleftunattended.If no keys are pressed for the default messagetime setwith
(1&(6?'()$8/70(66$*(7,0(
then the currently displayed message will automatically be overwrittenby the first default message. After 5 seconds, the next default message in the sequence will displayif more than one is selected. Trip,Alarm and flash messageswill override the defaultmessage dis-play. Any setpoint or measured value can be selected as a default message.
Messages are displayed in the orderthey are selected.
3-6239 Motor Protection RelayGE Multilin
3.6 DEFAULT MESSAGES
66(783?35()(5
Page 37
3 OPERATION3OPERATION
•ADDING NEW DEFAULT MESSAGE:usethe /keys to displayany setpoint
MESSAGE
▲
MESSAGE
▼
or actual value message to be added to the default message queue and follow thesteps shownbelow. When selecting a setpointmessage for display as a default,do not modify the value using
VALUE
▼
VALUE
the
/
▲
keys or the 239 will recognize thekey as storing a setpoint
STORE
instead of selecting a defaultmessage
STORE
MOTOR LOAD =70% FULL LOAD
ACTUAL VALUE OR SETPOINT TOBE STORED AS DEFAULT MESSAGE
STORE
TO ADD THIS DEFAULT
MESSAGE PRESS STORE
DISPLAYED FOR 3 SECONDS WHENSTORE KEY PRESSED TWICE
STORE
NEW DEFAULT MESSAGE
SELECTED
DISPLAYED FOR 3 SECONDS WHENSTORE KEY PRESSED
ADEFMSG.VSD
If5 default messages are already selected the first message iserased and the new message isadded tothe end of the queue.
MESSAGE
▲
MESSAGE
•DELETING A DEFAULT MESSAGE: Use the / keys to display the default
▼
message to be erased. If default messages are not known, wait until the 239 starts to displaythem and then write them down. If no default messages havebeen programmed, the 239 willremain on the current message and the display willdimto the level assigned in setpoint
point or actual value message to be deleted from the default message queue and follow thesteps shown below.
3
MOTOR LOAD =70% FULL LOAD
ACTUAL VALUE OR SETPOINT TOBE REMOVED FROM THE DEFAULTMESSAGE QUEUE
STORE
RESET
VALID DEFAULT
MESSAGE
NOT A DEFAULT
MESSAGE
TO DELETE THIS
MESSAGE PRESS STORE
DISPLAYED FOR 3 SECONDS WHENSTORE KEY AND RESET KEY AREPRESSED IN SEQENCE
NOT A SELECTED
DEFAULT MESSAGE
DISPLAYED FOR 3 SECONDS WHENSTORE KEY AND RESET KEY AREPRESSED IN SEQENCE
STORE
DEFAULT MESSAGE
REMOVED
DISPLAYED FOR 3 SECONDSWHEN STORE KEY PRESSED
REDEFMSG.VSD
Each239 is pre-programmed withfive default messages asshown below. Note, each time the fac-torysetpoints are reloaded the user programmed default messagesare overwritten with these mes-sages.
GE Multilin239 Motor Protection Relay3-7
Page 38
3 OPERATION3OPERATION
The 239 willscrollthrough the defaultmessages in the sequence shown.
Prior to operating the 239 relay,setpoints defining system characteristics and protection settingsmust be entered, via one of the following methods:
1.Frontpanel, using the keys and display.
2.Rear terminal RS485 port and a computer running the 239PC communication program availablefrom GE Multilin.
3.Rear terminal RS485 port and a SCADA systemrunning user-written software.
Any ofthese methodscan be used toenter the same information.However,a computer makes entryeasier and files can be stored and downloaded for fast, error free entry. To facilitate this process, the239PC programming software is available from GE Multilin. With this programinstalled on a portablecomputer, all setpointscanbe downloaded to the 239.
Setpoint messages areorganized intological groups or pagesforeasy reference. Setpoint mes-sages are described individually and a reference of all messages is also provided at the end of thechapter. Messages may vary somewhat from those illustrated because of installed options. Also,some messages associated with disabled features are hidden. This context sensitive operation elim-inates confusing detail. Before attempting to start the protected motor,setpoints on each pageshouldbe worked through, entering values eitherby localkeypad orcomputer.
4
The 239 relay leavesthe factory with setpoints programmed to default values.These values are shownin all the setpoint message illustrations. Many of these factory default values can be leftunchanged. At
a minimum however, setpoints that are shown shaded on Figure 4–3: SETPOINTSPAGE 2 – SYS-TEM SETUP on page 4–9 must be enteredfor the system tofunction correctly. Inorder to safeguardagainst the installation of a relay whose setpoints have not been entered, the 239 will trip and lock outuntil the values havebeen entered for these setpoints. A warning message “CAUSE OF LAST TRIP:PARAMETERS NOT SET”along with a tripcondition is present until the 239 isprogrammed withthesecritical setpoints.
GE Multilin239 Motor Protection Relay4-1
Page 40
4 PROGRAMMING4 PROGRAMMING
4
SETPOINTSETPOINT
]] SETPOINTS]] S1 239 SETUP
MESSAGE
] PREFERENCES]
] ANALOG OUTPUT]
] RS485 SERIAL PORT]
] DEFAULTS]
] PROGRAMMABLE] MESSAGE
] PRODUCT OPTIONS]
]] SETPOINTS]] S2 SYSTEM SETUP
▼
] CT INPUTS]
] MOTOR DATA]
MESSAGE
SETPOINT
]] SETPOINTS]] S3 OUTPUT RELAYS
▼
] TRIP RELAY]
] ALARM RELAY]
] AUXILIARY RELAY]
MESSAGE
SETPOINT
]] SETPOINTS]] S4 PROTECTION
▼
] PHASE CURRENT]
] GROUND CURRENT]
] TEMPERATURE]
] SWITCH INPUTS]
MESSAGE
SETPOINT
]] SETPOINTS]] S5 TESTING
▼
] TEST CONFIGURATION]
] TEST RELAY & LEDS]
] CURRENT SIMULATION]
] ANALOG OUTPUT] SIMULATION
] SWITCH INPUTS] SIMULATION
] THERMISTOR] SIMULATION
] RTD SIMULATION]
]GE POWER MANAGEMENT]USE ONLY
MESSAGE
▼
Figure 4–1: SETPOINT MESSAGEORGANIZATION
4-2239 Motor Protection RelayGE Multilin
Page 41
4 PROGRAMMING4 PROGRAMMING
4.2 S1: 239 SETUP
Settings to configure the 239 are entered here. This includes user preferences, RS485 communica-tionport, loading offactory defaults, and user programmable messages.
•TEMPERATURE DISPLAY:Select whether temperatures should be displayed in degrees Cel-sius orFahrenheit. Temperature units can be changed at any time.
•DEFAULT MESSAGE TIME:Up to 5 default messages can be selected to automatically scansequentially when the 239 is left unattended. If no keys are pressed for the default message timeset with thissetpoint, then the currentlydisplayed message will automatically be overwritten bythe first default message. After 5 seconds, the next default message in the sequence will displayif morethan one is selected.Alarm and tripmessages willover-ride default message display. Anysetpointor measuredvalue canbe selected as a defaultmessage.Refer toSection 3.6:DEFAULT MESSAGES on page 3–6 for information on removing and adding new default mes-sages.
Default messages can be disabledby setting this setpoint to
2)). When this setpoint isturned off,
the currently displayed messagewill remaindisplayed until a condition such as a trip alarm,orkey press forces the 239 todisplay a different message.
4-4239 Motor Protection RelayGE Multilin
Page 43
4 PROGRAMMING4 PROGRAMMING
•DEFAULT MESSAGE BRIGHTNESS: The brightness of thedisplayed messages canbevaried
with thissetpoint. The brightnessset by this setpoint will be used when the default messagesarebeing displayed.The brightnessdefaultsback to 100% when:
•trip is present
•alarm ispresent
•anyone ofthe keys on the 239 keypad is pressed
•the 239 isturned off and on
When
66(783?35()(5(1&(6?'()$8/70(66$*(7,0( is set to2)), the brightness will adjust to
set level after 5 minutes have elapsed since the 239 keys were last pressed. The 239 statusmust also be NORMAL to display the set brightness. If no default message is programmed, thedisplay brightness willadjust to the set level after the programmed timein message
6(783?35()(5(1&(6?'()$8/70(66$*(7,0(
has elapsed.
6
NOTE: Message brightness control is available only withthe VFD display option.
•BLOCK KEYPAD TRIP RESETS:This feature blocks any attempts made to reset the present
trip using the pressing the
RESET
RESET
This feature is applicable to trips only. The function of the key in other areas (i.e. reset
key on the 239 keypad.When this feature is enabled and a tripis present,
key willdisplay the following flash message for 3 seconds.
•OVERLOAD PICKUP DISPLAY ENABLE:When an overload pickup has occurred, this setpoint
determines whether the 239 front display panelis automaticallyupdated withthe timetooverloadtrip. When this setpoint is programmed to
12, an overload pickup willhave no effect on the dis-
play.The pickup LED indicator and overloadprotection are notaffected by this setpoint.
b) ANALOG OUTPUT
4
•ANALOG OUTPUT TYPE: If the relay is to be used in conjunction with programmable control-
lers, automated equipment,ora chart recorder the analog output can beusedfor continuousmonitoring. Choosefrom one of the following parameters for output:
3+$6($036
, 02725/2$' (phase current as a percentage of full load), or57'7(03(5$785(.
7+(50$/&$3$&,7<, $9(5$*(
Although a single parameter can be selected for continuous analog output, all values are avail-able digitally through the communications interface. See Section 2.3h)ANALOG OUTPUT(OPTION) (18/19/20) on page 2–11 for a description of current output scaling. Applicationsinclude using a computer to automatically shed loads as the motor current increases by monitor-ing current as a percentage of full load current or a chart recorder to plotthe loading of a motor ina particularprocess.
•ANALOG OUTPUT RANGE:In processeswhere themotor loads are varied and operatedat
near the motor full load such asin grinding or in conveyor systems it is useful to know how closethe relay is to tripping so the load may be adjusted accordingly.The analog output can be con-nected to a remote meter, which is available and calibrated from 0 to 100% of motor capacityused. Select thermal capacity
0$
(0 mA = 0%, 1 mA = 100% i.e. motor tripped) for use withthe 0-1 mA range meter model TCS2 scaled in units of thermal capacity used and available fromGE Multilin. This meter would be situated near the operator and connected to the relay. Themeter indicates how much the memoryhas charged correspondingto heat buildup in the motor.When the relay is aboutto trip, the meter willapproach 100% capacity used. After a trip, the
GE Multilin239 Motor Protection Relay4-5
Page 44
4 PROGRAMMING4 PROGRAMMING
meter will indicate how much charge is leftin the memory to give a rough idea of the lockout timeremaining. Alternately,this output can be programmed as
thermal capacity
0$ (4 mA = 0%,
20 mA = 100% i.e. motor tripped) and connected to a programmable controller or DCS as a sig-nalfor process control. Itmight typically be used to reduce the feed on to a conveyor as the con-veyor motorthermal capacity approached 100%.
c)RS485 SERIAL PORT
•SERIALCOMMS FAILURE ALARM: If loss of communications to the external master is requiredto activate the alarm relay,select ON. In this case an absence of communication polling on theRS485 communication port for 60 seconds will generate the alarm condition. Disable this alarmoutputif communicationsis not used oris not considered critical.
•SLAVE ADDRESS: Enter a unique address from1 to 255 for this particular relay on the RS485communicationlink. This setpoint cannot be changed via the RS485 port.A messagesent withaddress 0 is a broadcast message to which all relays will listen but not respond. Althoughaddresses do not have tobe sequential, no two relays can have the same address or there willbe conflicts resulting in errors. Generally, each relay added to the link will use the next higher
4
address, starting from address 1.
•BAUD RATE: Enter the baud rate for the terminal RS485 communication port, which may beselected to one of
, , , , or baud.All relays on the RS485 communication
linkand the computer connecting them must run at the same baud rate. The fastest response willbe obtained at19200 baud. Slower baud rates should be used if noise becomesa problem. Thedata frame consists of 1 start bit, 8 data bits, 1 stop bit and a programmable parity bit, see
6(783?566(5,$/3257?3$5,7<
.The baud rate default setting is9600 baud.
•PARITY:Enter the parityfor the terminal RS485 communication port, which may be selected toone of
(9(1, 2'', or121(. All relays on the RS485 communication link and the computer con-
necting them must have thesame parity.
6
d) DEFAULTS
•LOAD FACTORY DEFAULTS:When the 239 is shipped from the factory all setpoints will be setto factory default values. These settings are shown inthe setpoint message reference figures. Toreturn a relay to these known setpoints select
<(6 and press the key while thismessage
STORE
is displayed and then momentarily remove power to the 239. It is a good idea to first load factorydefaultswhenreplacing a 239 to ensure all the settings are defaulted toreasonable values.
•CLEAR PRE-TRIP DATA:Whenall of the pre-trip data in
$67$786?/$6775,3'$7$ will be clearedand the following flash message
<(6 is selected in this setpoint and the key is pressed,
STORE
will be displayed for 3 seconds.
PRE-TRIP DATA
CLEARED
Ifthe pre-data is cleared while a trip isstill present, all pre-data except for “CAUSE OF LASTTRIP” willbe cleared.
•CLEAR STATISTICS DATA: Select
<(6 and press the key to clear all motor statistics,
STORE
motor maximum starting current, and running time.
4-6239 Motor Protection RelayGE Multilin
Page 45
4 PROGRAMMING4 PROGRAMMING
e) PROGRAMMABLE MESSAGE
•PROGRAMMABLE MESSAGE:A 40-character message can be programmed using the key-
pad, or via the serial port using the 239PC software. Usingthe 239 keypad, a new message canbe written overthe existing message as shown below.
VALUE
MESSAGE
STORE
]PROGRAMMABLE]MESSAGE
Phone:905-294-6222GEindustrial.com/pm
VALUE
TIPS:
•The setpoint access jumper must be installed in order toalter the characters.
•Toskip overa character press the key.
•If a character is entered incorrectly, press the key repeatedly until the cursorreturns to the position of the error, and re-enter the character.
•Toselect this message as a defaultmessage, see Section 3.6: DEFAULT MESSAGES onpage 3–6.
•A copy of this message is also displayed in Actual Values page A1 under
0(66$*(
Phone:905-294-6222GEindustrial.com/pm
STORE
NEWSETPOINT
STORED
DISPLAYEDFOR3SECONDS
WHENSTOREKEYISPRESSED
STORE
STORE
NEWSETPOINT
STORED
DISPLAYEDFOR3SECONDS
WHENSTOREKEYISPRESSED
4
CONTINUETOENTERTHEREMAININGCHARACTERS
352*5$00$%/(
.
f) PRODUCT OPTIONS
•SELECT OPTIONS TO ENABLE: The 239 factory options can be updated in the field. Enterthenew desiredoptions forthe 239.
•SELECT MOD 1 TOENABLE: Enterthe desired mod.If no MOD is to be enabled enter zero (0).
•SELECT MOD 2 TO ENABLE: Enter the desired mod. If no MOD is to be enabled enter zero (0).
•SELECT MOD 3 TO ENABLE: Enter the desired mod. If no MOD is to be enabled enter zero (0).
•SELECT MOD 4 TO ENABLE: Enter the desired mod. If no MOD is to be enabled enter zero (0).
•SELECT MOD 5 TO ENABLE: Enter the desired mod. If no MOD is to be enabled enter zero (0).
•ENTER PASSCODE:Toenter a passcode through the keypad use the value up and/or valuedown keys. When the appropriate character isreached press the message right keyto movetothe next character to be entered. If a character was entered incorrectly use the message left or
GE Multilin239 Motor Protection Relay4-7
Page 46
4 PROGRAMMING4 PROGRAMMING
right keysto the position the cursor atthe errorlocation. Use the value upor down keys toselectthe correctcharacter.
When the entire passcode has been entered correctly press the store key.The 239 will then wait2 seconds beforeresetting.Seeflow diagram below.
4
NOTE: Passcodes are obtained by contacting the factory.There will be a charge
which isdependanton the options/Mods tobeinstalled. Desired Modsare limited to firmwareMods,no hardware Mods are supported with this feature. The firmware version of the 239 defineswhatfirmware Mods can be enabled.
EXAMPLE: The original 239was ordered with the AN option. After receiving the unit,require-ments have changedfor the239,and the RTD option isnow required.
Step 1:To add the RTD option to the 239 while keeping the AN option enter
6(/(&7237,21672(1$%/(setpoint.
Step 2:If no Modsare to be enabled, leave zerosin the
6(/(&702';72(1$%/(setpoints.
57'$1 in the
Step 3:With theunitserialnumber and theunitoptions required callthe factory to obtain
the passcode. Enter the passcode and press . After a 2 second delay the
STORE
239 will reset and the desired optionswill now bepresent.
Step 4:Verify correct options were installed:
ORDER CODE:239-RTD-AN
Located in ACTUAL VALUES page A3 underthe sub-heading MODEL INFORMATION
Step 5:Verify correct MODs were installed:
MOD NUMBER(S): 0
Located in ACTUAL VALUES page A3 underthe sub-heading MODEL INFORMATION
Step 6:Proceed with 239 setup.
4-8239 Motor Protection RelayGE Multilin
Page 47
4 PROGRAMMING4 PROGRAMMING
4.3 S2: SYSTEM SETUP
SETPOINT
]] SETPOINTS]] S2 SYSTEM SETUP
MESSAGE
MESSAGE
▲
▼
] CT INPUTS]
MESSAGE
MESSAGE
▲
▼
] MOTOR DATA]
MESSAGE
MESSAGE
▲
▼
SETPOINT
MESSAGE
MESSAGE
MESSAGE
MESSAGE
]] SETPOINTS]] S3 OUTPUT RELAYS
4
PHASE CT PRIMARY: OFF A
GROUND SENSING:
3
OFF
GROUND CT PRIMARY: 100 A
NOMINAL FREQUENCY: 60 Hz
4
MOTOR FULL LOADCURRENT: OFF
OVERLOAD PICKUP
3
INHIBIT
USE OVERLOAD PICKUPINHIBIT ON: RUN
LOCKED ROTORCURRENT: 6.0 x FLC
SAFE STALL TIMECOLD: 10.0 s
≤
1.00 x FLC
HOT/COLD CURVERATIO: 85%
DISABLE STARTS:NO
Range: 5 to 1500, OFFStep: 5 A
Range: RESIDUAL, CORE BAL 50:0.025,COR BAL X:5, OFF
Range: 5 to 1500Step: 5 A
Range: 50, 60
Range: 1 to 1500, OFF; Step 1 (CT PRI SET > 50 A)Range: 0.1 to 150.0, OFF; Step 0.1 (CT PRI SET
Range: 1.00 to 5.00; Step 0.05
Range: RUN, START, START & RUN
Range: 0.5 to 11.0; Step 0.1 x FLC
Range: 1.0 to 600.0; Step 0.1 s
Range: 5 to 100%; Step 1%
Range: NO, YES
≤
4
50A)
] END OF PAGE S2]
Figure 4–3: SETPOINTSPAGE2 – SYSTEM SETUP
GE Multilin239 Motor Protection Relay4-9
DESIGNATES SETPOINTS THATMUST BE PROGRAMMED BEFORETHE "TRIP" OUTPUT WILL RESET
Page 48
4 PROGRAMMING4 PROGRAMMING
a) CT INPUTS
3+$6(&735,0$5<!$, the 239 shifts the 02725)8///2$'&855(17 settings by a
At
factor of10 to remove the extra decimal place (see Figure 4–3:SETPOINTS PAGE2– SYSTEM SETUP above). If changing the
NOTE
•PHASE CT PRIMARY: Enter the primary current rating of the phase current transformers. Allthree phase CTs must be of the same rating. For example if500:5 CTs are used, the phase CTprimary value entered should be 500. When the relayis shipped with factory defaults loaded,thephase CT ratiois set off. When off is the CT value, the239 isforced to a trip state as a safety pre-caution untilavalid CT value is entered.Ensure that the CT is connected to the correct1 A or 5A terminals tomatch the CT secondary.
•GROUND SENSING: Ground sensing on solid or low resistance grounded systems is possiblewith residually connected phase CTs as shown in Figure 2–3: TYPICAL WIRING DIAGRAM on
4
page 2–4. Ifthis connection is used enter residual. The ground CT primary will automatically bethe same as the phase CTs. For moresensitive ground current detection a separate core bal-ance (zero sequence) CT whichencircles all three phase conductors can be used. In this caseselect corebalance50:0.025. A GE Multilin 50:0.025 CT is available. Ifaconventional 5 A sec-ondary CT is usedto encircle the 3 phase conductors,entercore balance x:5. It isthen neces-sary to specify the CT primary using the nextmessage
•GROUND CT PRIMARY:This message will only be visible ifthe ground sensing in the previousmessage is selected as core balance x:5. Enter the CT primary current. For example, if a 50:5CT is installed for ground sensing enter 50. One amp CTs can also be used for ground sensing.In this case enter the CT primary value multiplied by 5. For example, if a 100:1 ground CT isinstalled and the ground sensing is selected as core balance x:5 enter500 for the primary value.
•NOMINAL FREQUENCY: Enter the nominalsystem frequency as either 50 or 60 Hz. The 239uses thisinformation in the detection of Phase Short Circuit and Ground Fault Trips.
cross the 50 A value, the tor to restore the correct value. In previous firmware versions, crossing the 50 Avalue by changing the setting by a factorof10 automatically, often without the operator’s knowledge.
02725)8///2$'&855(17 is reset to 0 A, forcing the opera-
3+$6(&735,0$5< setting changed the 02725)8///2$'&855(17
3+$6(&735,0$5< setting causes itto
*5281'&735,0$5<.
b) MOTORDATA
•MOTOR FULL LOAD CURRENT (FLC):Enter the full load amps from the motor nameplate.This is the maximum rated current at which the motor can operate without overheating. It is the
1.0× pickup point on the timed overcurrent characteristic. When the current exceeds this value,the timed overcurrent feature begins to time, eventually leading to a trip. Immediate overloadwarning and undercurrent setpoints are multiples of this value. Timed overcurrent is not activeduring motor starting.
•OVERLOAD PICKUP INHIBIT:Enter the overloadpickup(servicefactor)specified on the motornameplate if shown. Otherwise enter an overload pickup of 1.00. The pickup inhibit will operateduring start and/or run depending upon the value programmed inthe setpoint
3,&.83,1+,%,721
which the overload curves begin timing. If the overload pickup is1.15 for example, the overloadcurveswill not begin to operate untilthe phase currentreaches 1.15 × FLC. Duringastart,
67$//7,0(
overload pickup inhibit setting.This setpoint acts as a lower cutoff for the overload pickup. The trip times are not shifted, but just
cut-off below the value specified by the overload pickup inhibitsetting.
and /2&.('52725&855(17 setpoints willnot be used until the current reaches the
described below. During a running condition this value adjusts the pickup at
86(29(5/2$'
6$)(
4-10239 Motor Protection RelayGE Multilin
Page 49
4 PROGRAMMING4 PROGRAMMING
•USE OVERLOAD PICKUPINHIBIT ON: This setpoint allows the overload pickup inhibit to be
applied during a START, RUN, or START & RUN condition.
•LOCKED ROTOR CURRENT AND SAFE STALL TIME COLD: During starting the locked rotor
current and safestalltime are used todetermine how fastthe thermal memoryfills up.Timedoverload curves are disabled. The starttimeallowed depends on the actual start current.
6$)(67$//7,0( and /2&.('52725&855(17 settings cannot be determined from the motor
If the
⁄()×
2
5()
2
2
nameplate, then use the above formula to determine the allowed start time. A good ruleof thumbis to set the
/2&.('52725&855(17 to 6× FLC and 6$)(67$//7,0( to the trip time for the speci-
fied timed overload curve at 6 × FLC.
•HOT/COLD CURVE RATIO: This feature determinesthermal capacity used when the motor is
running at or below the full load current setpoint. The
+27&2/'&859(5$7,2setpoint is deter-
mined from the motor data using the Locked Rotor Time Hot and Locked Rotor Time Cold speci-fications as shown below.
4
LRT Hot
-------------------------
HOT/COLD CURVE RATIO
=
LRT Cold
100×
where:
LRT Hot
= Locked RotorTime Hot,
is defined as the locked rotor time when the motor hasbeen running at FLC fora timesufficient for the motor temperature toreach a steady statevalue.
LRT Cold
= Locked Rotor Time Cold,
is defined as the locked rotor time when the motor has
been stopped for a time sufficient for the motor temperature to reach ambient.
LRT Hot and LRT Coldare usuallydetermined from the motor specifications. If this information isnot known, enter a typical value of 85% for the
+27&2/'&859(5$7,2 setpoint is used by the 239 to thermally model the motor when the
The
+27&2/'&859(5$7,2.
average phase current is at or belowthe FLC setpoint. When the motor is cold (motor tempera-ture at ambient) the thermal capacity used willbe 0%. When the motor ishot (motor running atFLC for a time sufficient to reach a steady state temperature) the thermal capacity used will becalculated as 100% –
+27&2/'&859(5$7,2, or 100 – 85=15% using the example value given
GE Multilin239 Motor Protection Relay4-11
Page 50
4 PROGRAMMING4 PROGRAMMING
above. Inbetween these two extremesthere is a linear relationship; the 239 thermal model cov-
ers the entire rangeofmotor temperatures: cold—cool—warm—hot.The steadystate value ofthermal capacity used foranyphase current levelcan be calculated as:
Actual Current
--------------------------------------
Thermal Capacity Used
For example, ifLRT Hot = 7.0 s, LRT Cold = 10.0 s, FLC = 100 A, and the actual motor current is80 A, then the steady state thermalcapacityvalue willbe:
Thermal Capacity Used
=
FLC Setpoint
Actual Current
--------------------------------------
=
FLC Setpoint
100%HOT/COLD CURVE RATIO
()×
100%HOT/COLD CURVE RATIO
()×
–
–
80
----------
=
100
=
20%
•DISABLE STARTS: In someapplications start protection may not be required. Therefore, by set-
4
ting this setpoint to
<(6, the 239 will go directly into run condition and overload curves will be employed toprotect the
connected load.This setpoint can also be used in conjunction with a switch input. If the
programmed toto
',6$%/(67$576, the 239 start protection will be defeated if the respective switch input is closed.
The
',6$%/(67$576 setpoint must be programmed to <(6 for the feature to work via the switch
inputs.
<(6, the start protection on the 239 can be defeated. If the setpoint is set to
<(6 and 237,216:,7&+)81&7,21 setpoint described on page 4–33 is assigned
100%
×
7.0
-----------
–
10.0
100%×
',6$%/(67$576 setpoint is
4-12239 Motor Protection RelayGE Multilin
Page 51
4 PROGRAMMING4 PROGRAMMING
4.4 S3: OUTPUT RELAYS
SETPOINT
]] SETPOINTS]] S3 OUTPUT RELAYS
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
▲
▼
] TRIP RELAY]
▲
▼
] ALARM RELAY]
▲
▼
SETPOINT
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
]] SETPOINTS]] S4 PROTECTION
4
TRIP OPERATION:NON-FAILSAFE
3
4
ALARM OPERATION:NON-FAILSAFE
3
ALARM ACTIVATION:UNLATCHED
4
Range: NON-FAILSAFE, FAILSAFE
Range: NON-FAILSAFE, FAILSAFE
Range: LATCHED, UNLATCHED
4
] AUXILIARY RELAY]
MESSAGE
MESSAGE
▲
▼
] END OF PAGE S3]
NON-FAILSAFE:
FAILSAFE:
The relaycoil isenergized inits non-active state. Lossof controlpower willcausethe relay to go into its active state; i.e. a failsafe alarm or trip relay will cause analarm or trip on loss of controlpower.Contact configuration is opposite tothat shownin Figure 2–3: TYPICAL WIRING DIAGRAM on page 2–4 for relays programmed asfailsafe when control power isapplied
Range: NON-FAILSAFE, FAILSAFE
Range: UNLATCHED, LATCHED
Range: NORMAL, TRIPS, ALARMS
MESSAGE
AUXILIARY OPERATION:NON-FAILSAFE
AUXILIARY ACTIVATION:
3
UNLATCHED
AUXILIARY FUNCTION:NORMAL
Figure 4–4:SETPOINTS PAGE 3 – OUTPUTRELAYS
The relaycoilis not energized in its non-activestate. Lossofcontrol powerwillcause the relayto remainin thenon-active state; i.e. a non-failsafealarm ortriprelay will not cause an alarm or trip on loss of control power. Contact configura-
tionis shown in Figure 2–3: TYPICAL WIRING DIAGRAM on page 2–4 withrelays programmed non-failsafe, control power notapplied
GE Multilin239 Motor Protection Relay4-13
Page 52
4 PROGRAMMING4 PROGRAMMING
RESET
a) TRIP RELAY
•TRIP OPERATION: Any trip condition will activate the trip relay. This relay can be programmed
121)$,/6$)( or)$,/6$)(. After a trip, the relay trip state willremainlatched untilreset by
to be pressing the key, momentarily closing the external reset switch input, or issuing a serial
RESET
port reset command.Where process continuity is more important than motor protection, the mode of operation can be
chosen as
121)$,/6$)( so the trip relay isnormally de-energized for a non-trip condition and
energized for a trip. No trip occurs if control power to the 239 is lost but there willbe no motorprotection while this condition is present. Set the mode to
)$,/6$)((the relay coil isnormally
energized for a non-trip condition going non-energized for a trip) to cause a trip when controlpowerto the 239 isnotpresent to ensure continuous motor protection.
When the motor interrupting device isa breaker, the trip relay is usuallyprogrammed
and the trip contactwired in serieswiththe breaker trip coil. Even though the tripcontact is
6$)(
latched, the breaker 52 contact will normally be wired in series with the 239 trip contact so thatthe breaker 52 contact breaks the trip coilcurrent as soon as the breaker opens. The 239 tripmessages and records operate in the same way for contactors or breakers so the trip condition
4
must still be cleared using the key, momentarily closing the external reset terminals, orby sending the reset command via the computer.
b) ALARM RELAY
•ALARM OPERATION: Any alarm condition will activatethe alarm relay. If an alarm is requiredwhen the 239 is not operational due to a loss of control power, selectwise, choose
121)$,/6$)(.
)$,/6$)( operation. Other-
•ALARM ACTIVATION: If an alarm indicationis only required while an alarm ispresent, select
81/$7&+('. Once analarm condition disappears,the alarm and associated message automati-
cally clear. To ensure all alarms are acknowledged, select
/$7&+('. Evenif an alarm condition is
no longer present, the alarm relay andmessage can only becleared bypressing the key,momentarily closing the external reset terminals, or by sending the reset command via thecomputer.
c) AUXILIARY RELAY
•AUXILIARY OPERATION:Any alarm, trip or auxiliary function can be programmed to activatethe auxiliary relay.If an output is required when the 239 is not operational due to a loss of controlpower, select
•AUXILIARY ACTIVATION: If an auxiliary relay output is only requiredwhilethe alarm or auxiliaryfunctionis present, select
81/$7&+('. Once an alarm orauxiliaryfunction condition disappears,
the auxiliary relay returns to the non-active state and the associated messageautomaticallyclears. To ensure all alarms or auxiliary function conditions are acknowledged, selectEvenif an alarm orauxiliary function condition isno longer present, the auxiliary relay and mes-sage can only be cleared by pressing the key,momentarily closing the external reset
RESET
terminals, orby sending the resetcommand via the computer.
•AUXILIARY FUNCTION:If the auxiliary relayis required to be controlledby the function it’sassigned tothen configure this setpoint to
1250$/.If the auxiliaryrelayis required to activate on
an occurrence ofan alarm or trip condition and remain energized while the alarm or tripconditionis present then configure the setpointto
$/$50 or75,3 depending on the requirement.
121)$,/
RESET
/$7&+('.
4-14239 Motor Protection RelayGE Multilin
Page 53
4 PROGRAMMING4 PROGRAMMING
]] SETPOINTS]] S4 PROTECTION
SETPOINT
] PHASE CURRENT]
| OVERLOAD|
OVERLOADCURVE NO:4
AT 2.00 x FLC,TRIPTIME = 116.6 s
OVERLOADLOCKOUTTIME:30 MIN
| PHASE S/C|
]] SETPOINTS]] S5TESTING
SETPOINT
Range:1 to 15;Step 1
Range:1.01 to 20.00Step 0.01 x FLC
Range:1 to 5000;Step:1 min.
MESSAGE >
MESSAGE <
PHASE S/CTRIP:OFF
| IMMEDIATE OVERLOAD|
AUTO RESET O/LTRIPSONCETC≤15%:NO
Range:OFF,TRIP, AUXILIARY,TRIP & AUXILIARY
Range:1.0 to 11;Step:0.1 x CT
Range:10 to 60000, INST;Step:10 ms
PHASE S/CPICKUP≥10 x CT
PHASE S/CDELAY:INST ms
Range:YES, NO
IMMEDIATE OVERLOADALARM:OFF
IMMEDIATE OVERLOADPICKUP≥1.1 x FLC
INHIBIT ON STARTFOR:UNLIMITED s
Range:ON, OFF
Range:0.5 to 11.0;Step 0.1 x FLC
Range:0 to 6000, UNLIMITEDStep:1 s
SEE NEXT PAGESEE NEXT PAGE
MESSAGEs
MESSAGEt
MESSAGEs
MESSAGEt
MESSAGEs
MESSAGEt
MESSAGEs
MESSAGEt
MESSAGEs
MESSAGEt
4.5 S4: PROTECTION
4
GE Multilin239 Motor Protection Relay4-15
Page 54
4 PROGRAMMING4 PROGRAMMING
SEE PREVIOUS PAGESEE PREVIOUS PAGE
| MECHANICAL JAM|
Range: OFF, TRIP, ALARM,AUXILIARY, TRIP&AUX
Range: 0.1 to 10.0Step 0.1 x FLC
Range: 0 to 250; Step: 1 s.
Range: 0 to 6000, UNLIMITEDStep: 1 s
MESSAGE
MESSAGE
MECHANICAL JAMFUNCTION: OFF
MECHANICAL JAMPICKUP
▲
≥
2.0 x FLC
MECHANICAL JAMDELAY: 2 s
▼
INHIBIT ON STARTFOR: UNLIMITED s
4
MESSAGE
MESSAGE
MESSAGE
MESSAGE
| UNDERCURRENT|
UNDERCURRENTFUNCTION: OFF
UNDERCURRENT
▲
▼
PICKUP
UNDERCURRENTDELAY: 2 s
| UNBALANCE|
PHASE UNBALANCETRIP: ON
PHASE UNBALANCETRIP PICKUP
PHASE UNBALANCE
▲
▼
TRIP DELAY: 2 s
PHASE UNBALANCEALARM: ON
≤
50% FLC
≥
20 %
PHASE UNBALANCEALARM PICKUP
≤
5 %
Range: OFF, ALARM, AUXILIARY,TRIP, ALARM & AUX, TRIP & AUX
Range: 5 to 100; Step: 1%
Range: 0 to 250; Step: 1 s.
Range: ON, OFF
Range: 5 to 100; Step: 1%
Range: 0 to 60; Step: 1 s
Range: ON, OFF
Range: 5 to 100Step: 1%
MESSAGE
MESSAGE
4-16239 Motor Protection RelayGE Multilin
| HOT MOTOR|
▲▼
SEE NEXT PAGESEE NEXT PAGE
THERMAL CAPACITYUSED ALARM
≥
OFF %
Range: 0 to 100; Step: 1%
Page 55
4 PROGRAMMING4 PROGRAMMING
SEE PREVIOUS PAGESEE PREVIOUS PAGE
| BREAKER FAILURE|
Range: OFF, ALARM, AUXILIARY,ALARM & AUX
Range: 0.1 to 11.0Step 0.1 x CT
Range: 10 to 60000, INSTStep: 10 ms
Range: 10 to 60000, INSTStep: 10 ms
MESSAGE
MESSAGE
BREAKER FAILUREFUNCTION: OFF
BREAKER FAILUREPICKUP
▲
≥
5.0 x FLC
BREAKER FAIL PICKUPDELAY: 100 ms
▼
BREAKER FAIL DROPOUTDELAY: 100 ms
] GROUND CURRENT]
MESSAGE
MESSAGE
▲▼
] TEMPERATURE]
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
4
GROUND TRIP:TRIP
3
▲▼
4
| THERMISTOR|
3
▲
▼
Range: OFF, TRIP AUXILIARY,TRIP & AUXILIARY
GROUND PRIMARY TRIPPICKUP
≥
10.00 A
GROUND TRIP DELAYON RUN: 500 ms
GROUND TRIP DELAYON START: 500 ms
GROUNDALARM: MOMENTARY
GROUND PRIMARYALARM PICKUP
GROUND ALARM DELAYON RUN: 5.0 s
GROUND ALARM DELAYON START: 5.0 s
THERMISTOR FUNCTION:OFF
THERMISTOR HOTRESISTANCE: 5.0 k
Ω
THERMISTOR COLDRESISTANCE: 0.3 k
Ω
THERMISTOR NOTCONNECTED ALARM: OFF
Range: 0.05 to 15 step 0.01A (GND PRI = 50:0.025);3 to 100 step 1% (GND PRI = X:5; RESIDUAL)
Range:1 to 1500 step 1 (4th CT PRIMset > 50 A); 0.1 to 150.0 step 0.1 (4th CTPRIM set
≤
50 A)
Range: 1 to 15 step 1
Range: OFF, TRIP, AUXILIARY,TRIP & AUXILIARY
Range: 1.0 to 11Step 0.1 x CT
Range: 10 to 60000, INSTStep: 10 ms
≤
50 A)
MESSAGE
MESSAGE
OPTION SW. 2 NAME:OPTION SWITCH 2
SWITCH 2 FUNCTION: OFF
TIME DELAY:
0.0 s3rd PHASE CT
PRIMARY: 100 A
3rd MOTOR FULL LOADCURRENT: 100 A
3rd OVERLOADCURVE NO: 4
3rd PHASE S/CTRIP: OFF
▲
▼
3rd PHASE S/CPICKUP
≥
3rd PHASE S/CDELAY: INST ms
4th PHASE CTPRIMARY: OFF A
4th MOTOR FULL LOADCURRENT: OFF A
4th OVERLOADCURVE NO: 4
] END OF PAGE 4]
Figure 4–5: SETPOINTS PAGE 4 – PROTECTION
4-20239 Motor Protection RelayGE Multilin
Page 59
4 PROGRAMMING4 PROGRAMMING
a) OVERLOAD
•OVERLOAD CURVE: One of 15 different time/overload curves can be selected with the PhaseOverload Curve number setpoint to closely match the thermal characteristics of the motor. Overlay motor curve data, if available, on the time overcurrent curves of Figure 4–6: PHASE TIMEDOVERLOAD CURVES on page 4–22 and choose the curve that falls just below the motor dam-age curve.
I2t
Each of the curves represents an
characteristic ofa motor. If no motor curve data is available,thissetpoint can be set using the locked rotor time from the motor nameplate. Plotthe pointcor-responding tothe rated locked rotor or stall time (vertical axis)atthe rated locked rotor current(horizontal axis). For example, choose the point at 9 seconds and 6 × FLC for a motor with alocked rotor time of 9 seconds and a locked rotor current of 6 × FLC. Ifthe stall timeis specifiedat some other inrush current, the pointcan be plotted on the time/overloadcurvesof Figure 4–6:PHASE TIMED OVERLOAD CURVES on page 4–22 and the next lowest curve selected. Curvepoints are also shown in tabular form in Table 4–2: 239 PHASE OVERLOAD TRIP TIMES (SEC-ONDS) on page 4–23. Points for a selected curve can be plotted directly on curves for associ-ated equipmentto facilitate acoordination study. These points can also be entered into acomputer co-ordination program to assist in curve selection.
The phase timed overload curve will come intoeffectwhen the motorcurrent in any phase goesover the overload pickup× FLC level. During overload motor thermal capacitywill increaseaccordingly until the trip relay is activated when 100% of the available thermal capacity has beenreached. After a trip, the thermal memory locks out a reset until the motor has cooled sufficiently(TC < 15%) to allow restarting.
4
•OVERLOAD TRIP TIME CALCULATION: This feature actsas a built-in calculator for a quick
VALUE
check of the expected trip time at all the selectable overload values. Using the
VALUE
▲
keys, scrollthrough the trip levels. As the trip level is being changed the trip time will
automatically be updated to correspond with the currentlydisplayed value. When the
▼
STORE
key is pressed the currently displayed trip level iskept in the memory for future reference. Theresolution of the displayed triptime isas shown inthe table below.
Table 4–1: OVERLOAD TRIPTIME CALCULATION
TRIP TIME RANGEDISPLAY RESOLUTION
trip time<100seconds0.01 x secondstrip time≥ 100 secondsand< 600 seconds0.1 x secondstrip time≥ 600 seconds and< 6000 seconds1.0x secondstrip time≥ 6000seconds1.0 x minutes
•OVERLOAD LOCKOUT TIME: The motor cooling rate is controlled by this setpoint. Enter a typi-cal timeof 30 minutes to allow sufficient cooling. If process criteria requires shorter cooling peri-ods, particularlyfor small motors, a different time can be entered. Care should be exercised inselecting short lockout times since operators may restart a hot motor resulting in damage if tooshort a lockout time is chosen. Timed overload is not active during motor start. The locked rotorcurrent and safe stall time are used to modelthermal capacity effect during starting.
•AUTORESET O/L TRIPS: When enabled, this feature will automatically reset overload tripsonce the thermal capacity (TC) decreases to 15% or less. All other types of trips are not affectedby this feature.
Inanyapplication where the available short circuitcurrentis above the inter-
rupting capability of the contactor, short circuit currents must cause a fuse or circuit breaker tooperate. This prevents damageto the contactor which is not designed to interrupt normal levelsof short circuit current. In an application with fuses, program the setpoint
&855(17?3+$6(6&?3+$6(6?&75,32))
to prevent the contactor from attempting to trip during a
63527(&7,21?3+$6(
short circuit.If a circuit breaker which can be tripped by an external contact closure is available upstream from
the contactor, itis possible to program the setpoint
&?3+$6(6?&75,3$8;,/,$5<
to cause a short circuit to activate the auxiliary relay instead of the trip
63527(&7,21?3+$6(&855(17?3+$6(6
relay. Though,itis also possible to activate both the trip & auxiliary relays simultaneously. Theauxiliary relay could then be connected to theupstream breaker to cause it toopen for a short cir-cuit. Ensure that the auxiliary relay is only programmed to activate under short circuit when usedin this manner.
SPECIAL NOTE:
TheAUXILIARY and TRIP status indicators will bothoperate for these tripseven if the TRIP relay is not selected for use (i.e. AUXILIARY). If the breaker cannot be externallytripped, program the setpoint
63527(&7,21?3+$6(&855(17?3+$6(6&?3+$6(6?&75,32)) to pre-
vent the contactor from attempting to trip during a short circuit. If a breaker is used as the motorstarter interrupting device, short circuitprotection would generallybe enabled as itwill normallybe capable of handling the faultcurrent. Short circuitprotection causes the breakerto openquickly to prevent excessive mechanical damage or fire due to any large phase current. Com-plete protection from phase-to-phase and phase-to-ground faults is provided with thisfeature.
GE Multilin239 Motor Protection Relay4-23
Page 62
4 PROGRAMMING4 PROGRAMMING
When enabled,by programming setpoint 63527(&7,21?3+$6(&855(17?3+$6(6&?3+$6(6?&75,3
,
short circuitprotection is active atall times, including during motorstarts.It can be disabled
75,3
by setting the setpoint
•PHASE S/C PICKUP: The phase current short circuit trip level can be set from1 to 11 times thephase CT primary. When any phase current meets or exceeds this setpoint value during start orrun conditions and is maintained forthe vate.
•PHASE S/C DELAY: The trip can be instantaneous (no intentional delay) or can be delayed byup to 60000 ms to prevent nuisance tripping or allow co-ordination with associated systemswitchgear. The intentionaldelay added to thedetection and outputrelay activationdelays of the 239.When thissetpoint is set to circuit trip level and timedelay should be set to co-ordinate with other system protective relays tominimize equipment shutdown during a high current fault.
c) IMMEDIATEOVERLOAD
4
•IMMEDIATE OVERLOAD ALARM: When the average phase current exceeds the fullload cur-rent (FLC) setpoint the phase timed overload protection begins timing. This will eventually lead toa trip unless the overload disappears. Immediate overload warning can be used to alert an oper-ator or to produce an alarm output using this setpoint. This feature should beset to off for sys-tems that experience overloads as partof normal operation such as crushers.
•IMMEDIATE OVERLOAD PICKUP:The immediate overload pickup setpoint is adjustable from
0.5 ×FLC to 11.0 × FLC. The alarm relay willactivate immediately when the average three phasecurrent exceeds this setpoint value when the motor is running. This feature can also operate dur-ing startcondition using the
•INHIBIT ON START FOR: If all other conditionsare met for an immediate overload alarm tooccur and the motor is starting, the alarm will occur when the delay set in this setpoint haselapsed. If this setpoint is set toa start.
3+$6(6&'(/$< setpoint, the selected relay(s) willacti-
63527(&7,21?3+$6(&855(17?3+$6(6&?3+$6(6?&'(/$< setpoint represents the
,167 the 239 will tripwithin 45 ms of the onsetofthe shortcircuit.Boththe short
,1+,%,72167$57)25 setpoint described below.
81/,0,7(', the immediate overload alarm will never occur during
d) MECHANICAL JAM
•MECHANICAL JAM FUNCTION:In protecting driven equipment such as pumps, gearboxes,compressors and saws, itis often desirable to have an immediate trip in the event of a lockedrotor during running. During startup the mechanical jam can be disabled using the
67$57)25
with loads that experience overloadsaspartof normaloperation such as crushers is not recom-mended.
•MECHANICAL JAM PICKUP: If a fast trip for mechanical jam isrequired, enable the feature andenterthe average currentpickup valueabove the normal maximum expected operating averagephase current.
•MECHANICAL JAM DELAY:If the average phase current exceeds thesetpoint value when the motor isrunning, and remains this way for the time delay programmed,oneof the assignedrelay(s) willactivate. Since themechanical jam function canbe assigned toany relay,iftrip and the “CAUSE OF LAST TRIP: MECHANICAL JAM” message will be displayed. Con-versely,if the function isassignedtoALARM, and the above conditions are met,the fault iscon-sidered to be anALARM, and the 239 willdisplay “MECHANICAL JAM ALARM”.
setpointdescribedbelow, since a typical inrush of 600% is normal. Use of this feature
0(&+$1,&$/-$03,&.83
75,3, $8;,/,$5<, or 75,3$8;5(/$<6are assigned, the function is considered to be a
,1+,%,721
4-24239 Motor Protection RelayGE Multilin
Page 63
4 PROGRAMMING4 PROGRAMMING
•INHIBIT ON START FOR: If all other conditionsare metfor a mechanical jam feature to activate
andthe motor is starting, the function will operate whenthe delay set in this setpoint has elapsed.If this setpoint isset to
e) UNDERCURRENT
•UNDERCURRENT FUNCTION: Typical uses for undercurrent include protection of pumps from
loss of suction, fans fromloss of airflow due to a closed damper or conveyor systems froma bro-ken belt. Undercurrent can either be disabled, used as an alarm, a trip or as a process control.Set this setpoint to off if the feature isnot required. Selecting alarm relay will cause the alarmrelay to activate and display an alarm message whenever an undercurrent condition exists.Selecting trip relay will cause the trip relay to activate and display a cause of trip message when-ever an undercurrent condition occurs. Selecting auxiliary relay will cause the auxiliary relay toactivate for an undercurrent condition but no message will be displayed. This is intended for pro-cess control.
For example, ifthe motor full load current (FLC) isset to 100 A for a pump motor,setting theundercurrent pickup to60% and selecting the alarm relay will cause the relayto activate and cre-ate an alarm message when the average phase currentdrops below 60A while running whichmight represent loss ofsuction.
•UNDERCURRENT PICKUP: A further use of this feature is as a pre-overload warning. This is
accomplished by setting the the motorbut below the rated full load current. Suppose a fannormally draws 90A and the fullload current (FLC) was set to 100 A, which was the maximum rating for the fan motor. If theundercurrent pickup was set at 95% and the auxiliary relay was selected with the
)81&7,21
energized. Bearing wear could cause the current to increase above 95 A causing the undercur-rent condition to disappear. If an external alarmwas wired across the normally closed auxiliaryrelay contacts,the alarm would sound above the normal current but before an overloadoccurredsignaling an abnormal condition prior to actualshut down. Alternatively, the output could be wiredto a process controller input to take automatic corrective action. The undercurrent feature worksas long as the average phase current is≥5% of fullload current.
•UNDERCURRENT DELAY:Ifthe average phase current drops below the
setpointvalue and remains this way forthe time delayprogrammed in thissetpoint, the alarmrelay will activate and the “UNDERCURRENT ALARM” message will be displayed if the setpoint
63527(&7,21?3+$6(&855(17?81'(5&855(17?81'(5&855(17)81&7,21 isset to$/$50. If the set-
pointthe auxiliaryrelay will activate and no message willbe displayed after the delay expires.
setpoint, the 239 would always sense an undercurrent condition with the auxiliary relay
63527(&7,21?3+$6(&855(17?81'(5&855(17?81'(5&855(17)81&7,21 is set to$8;,/,$5<,
81/,0,7(', the mechanical jam function will never operate during a start.
81'(5&855(173,&.83to be above the normal operating currentof
81'(5&855(17
81'(5&855(173,&.83
4
f) UNBALANCE
•UNBALANCE TRIP: Unbalanced three phase supply voltages are a major cause of induction
motor thermal damage. Unbalance can be caused by a variety of factors and is common inindustrial environments. Causes can include increasedresistance inone phase due to a pitted orfaulty contactor, loose connections, unequal tap settings in a transformer or non-uniformly distrib-uted three phase loads. The incoming supply to a plant may be balanced but varying singlephase loads within the plant can cause a voltage unbalance at the motor terminals. The mostserious caseof unbalance is single phasing which is the complete loss ofone phase oftheincoming supply. This can be caused by a utility supply problem or by a blown fuse in one phaseandcan seriouslydamagea three phase motor.
GE Multilin239 Motor Protection Relay4-25
Page 64
4 PROGRAMMING4 PROGRAMMING
Under normal balanced conditions the stator current in each of the three motor phases is equaland the rotor currentis just sufficient to provide the turning torque. When the stator currents areunbalanced, a much higher current is induced in the rotor because it has a lower impedance tothe negative sequence current component present under unbalanced conditions. This current isnormally at about twice the power supply frequency and produces a torque in the opposite direc-tion to the desired motor output.Usually the increase in stator current is small (125 to 200%) sothat timed overcurrent protection takes a long time to trip. However the much higher inducedrotor current can cause extensive rotor damage in a short period of time. Motors can tolerate dif-ferent levels of current unbalance depending on the rotor design and heat dissipation character-istics.
•UNBALANCE TRIP PICKUP:Unbalance protection is recommended at all times. Motor data israrely provided and direct measurementofrotortemperature is impractical sosetting the unbal-ance level is empirical. For a known balanced situation, a pickup level of 10% and time delay of 5seconds is recommended as a starting point.The pickup level can be decreased until nuisancetripping occurs. Similarly the time delay may be increased ifnecessary.
Toprevent nuisance trips/alarmsonlightly loaded motors when a much larger unbalance level
4
will not damage the rotor,the single phase detection willautomaticallybedefeatedif the averagemotor currentis less than 30% ofthe fullload current(
ImI
–
av
I
≥:
avIFLC
I
<:
avIFLC
---------------------
I
av
ImI
–
---------------------
I
FLC
av
100%×
100%×
I
)setting. Unbalance is calculated as:
FLC
where:
I
= average phase current
av
I
=current ina phasewith maximum deviation from
m
I
= motor fullload currentsetting
FLC
I
av
•UNBALANCE ALARM:The operation of thisfeature isidentical to the operation ofthe unbal-ance trip feature.
•UNBALANCE ALARM PICKUP: Theoperation of this feature is identical to the operation of theunbalance trip pickup feature.
•UNBALANCE DELAY:If phase current unbalance increases above
81%$/$1&(75,33,&.83 setpoint value and remains thisway for the timedelay programmed inthis
81%$/$1&($/$503,&.83 or
setpoint, the respectiverelay will activate and therespective warning message will be displayed.
g) HOT MOTOR
•THERMAL CAPACITY USED: This feature is used to signal a warning when the thermalcapac-ity has exceeded a level set in this setpoint. Once the set level is exceed the alarm relay will acti-vate immediately and the “THERMAL CAPACITY USED ALARM” message will be displayed.
h) BREAKER FAILURE
•BREAKER FAILURE FUNCTION: This feature is used toactivate the selected relay, if the cur-rent continues to flow after a trip has occurred. If the feature is assigned to
$/$50 or$/$50$8;,
the “BREAKER FAILURE ALARM” message will be displayed and the assigned output relay willbe active. If the function is assigned to
$8;,/,$5<, the auxiliary output relay willbe active but, no
message will be displayed.
4-26239 Motor Protection RelayGE Multilin
Page 65
4 PROGRAMMING4 PROGRAMMING
•BREAKER FAILURE PICKUP: If a trip ispresent and the current is still flowing (breaker failed to
open) and the level of the average three phase current is equal to or greater than the setting inthe
•BREAKER FAIL PICKUP DELAY: If all other conditions are met, the breaker failure feature will
operate after the delay programmed in this setpointhas elapsed. See Section 1.4: SPECIFICA-TIONS on page 1–7 forBREAKER FAILURE timing specifications.
•BREAKER FAIL DROPOUT DELAY:If the breaker opens or if the average three phase current
falls below the delay programmed in this setpoint has elapsed. See Section 1.4: SPECIFICATIONS on page 1–7 for BREAKER FAILURE timing specifications.
i) GROUND CURRENT
•GROUND TRIP: Aging and thermal cycling can eventually cause a lowering of the dielectric
strength of the winding insulation inthe statorwinding. This can produce a low impedance pathfrom the supply toground resulting in ground currents which canbequite high insolidlygrounded systems. These could quickly cause severe structuraldamageto the motor statorslots. In resistance grounded systems there is a resistance inseries with the supply ground con-nection to limit ground current and allow the system to continue operating for a short time underfault conditions. The fault should be located and corrected as soon as possible, however, since asecond fault on another phase wouldresult in a very high current flow betweenthe phasesthrough the two ground fault paths. In addition to damaging the motor, a ground fault can placethe motor casing aboveground potentialthus presenting a safety hazard topersonnel.
%5($.(5)$,/85(3,&.83setpoint, the breaker failure feature will notclear untilthe
4
On theoccurrence ofa ground faultcaused by insulation breakdown,a motor willusuallyhave tobe taken out of service and rewound. However an unprotected motor could suffer mechanicaldamage to the statorslotsmaking repair impossible. The fault could also cause the power supplybus to which the faulty motor is connected to trip in order to clear the fault resulting in unneces-sary process shutdowns. Ground faults can occur in otherwise good motors because of environ-mental conditions. Moisture or conductive dust,which are often present in mines, can provide anelectrical path to ground thus allowing ground current to flow. In this case, ground fault protectionshould shut down the motor immediately so that it can be dried or cleaned before being restarted.
On low resistance or solidly grounded systems, sensing of the ground current is done using thephase CTs wired in a residual connection. For more sensitive ground current detection, a sepa-rate CT, referred to as a core balance or zero sequence CT, encircles the three motor conduc-tors. Ground fault detection is only suitable for systems that have a path from the supply toground either through a resistance or by direct connection. Ungrounded systems require an arti-ficial ground to be created through use of a device likea zig-zag transformerifground fault pro-tection isto be used.
In systems with several levels of ground fault detection, time co-ordination is required for satis-factory operation.If ground fault protection is used on a bus, each motormusthave a shorterground fault trip time delay than the bus ground fault detector or a fault inany motor will shutdown the whole bus. Ina solidlygrounded system, time delays as short as possible should beused to prevent system damage unless the contactor is not capable of breaking the fault currentin which case a backup detectionsystem of sufficient interrupting capacity should be allowedtooperatefirst. When contactorsare used insolidly grounded systems, theground fault trip timeshould be longer than the fuseinterrupt time.
GE Multilin239 Motor Protection Relay4-27
Page 66
4 PROGRAMMING4 PROGRAMMING
On resistance grounded systems,where the ground currentis limited to safelevels longer timedelayscan beused subject toco-ordination constraints. Too short time delays maycause nui-sance tripping due to transients or capacitive charging currents and should be avoided if possi-ble. Timedelays of several hundred milliseconds are suitable for applications where the relay hasto be coordinated with other protective devices or a long delay is desired because of transients.Time delays of several seconds are suitable for use on high resistance grounded systems wherenuisance tripping may be a problem from capacitive or induced currentsduring the startinginrush. Ground currents limited by the supply ground resistance can flow for longer periods with-out causing any damage.
The relay(s) selectedin this setpoint along with the respectivestatus indicator(s) on the frontpanelofthe 239 will be active upon a groundfault trip.
•GROUNDPRIMARY TRIP PICKUP: Ground fault trip when enabled in
&855(17?*5281'75,3
exceeds the value set in this setpoint. The amount ofcurrentthatwill flow due toaground faultdepends on where thefault occurs inthe motorwinding. High current flows if a short to groundoccursnearthe end of the stator winding nearest to the terminalvoltage.Low ground fault cur-
4
rents flow if a fault occursat the neutral end ofthe winding since thisend should beavirtualground. Thus a low level of ground fault pickup is desirable to protect as much of the stator wind-ing as possibleand to preventthe motor casing from becoming a shock hazard. Inresistancegrounded systems the ground fault trip level must be set below the maximumcurrent limited bythe ground resistor or else the relay will not see a large enough ground fault current to cause atrip.
•GROUND TRIP DELAY ON RUN:This delay isused when the motor isin a RUNNING condition.If the ground current is equalto or abovethe remains this way for the time delay programmedin this setpoint while the motor is running, theassigned relay(s) will activate and the “CAUSE OF TRIP: GROUND FAULT” message will be dis-played.
NOTE:When the phase current increases from 0, the
described below is used untilthe 239 determines whetherthe motor isRUNNING orSTARTING.
Refer toSection 5.2: A1: STATUS on page 5–2 fordetails on how the 239 detects a startcondi-tion.
, will signal a trip condition when the ground current becomes equal to or
*5281'35,0$5<75,33,&.83 setpoint value and
*5281'75,3'(/$<2167$57 setpoint
63527(&7,21?*5281'
•GROUND TRIP DELAY ON START: This delay is used when the motor is in a STARTING condi-tion. If the ground current is equal to or above the remainsthiswayfor the time delay programmed in this setpoint while the motor isstarting,theassigned relay(s) will activate and the “CAUSE OF TRIP: GROUND FAULT” message will be dis-played.
NOTE:When the phase current increases from 0, this delay is useduntil the239 deter-
mines whether the motorisRUNNING or STARTING.
Refer toSection 5.2: A1: STATUS on page 5–2 fordetails on how the 239 detects a startcondi-tion.
•GROUND ALARM: For detecting momentary ground faultsdue to initial insulation breakdownandarcing, this setpoint can be set to latched. Thisis especiallyusefulin mines where moisturebuildup in the windings may start to cause excessive leakage. Any shortduration ground faultwillthen cause a latched alarm condition.Setto momentary ifa ground faultalarm isrequired onlywhile the ground current is actually present. Ground fault alarm when enabled, willsignal an
4-28239 Motor Protection RelayGE Multilin
*5281'35,0$5<75,33,&.83 setpointvalue and
Page 67
4 PROGRAMMING4 PROGRAMMING
alarmcondition when the ground current isgreater than or equal to the value set by the *5281'
35,0$5<$/$503,&.83
•GROUND PRIMARY ALARM PICKUP: Thisfeature functions in a similar manner to theground
primary trip pickup feature.
•GROUND ALARM DELAY ON RUN: This delay is used when the motor isin a RUNNING condi-
tion. If the groundcurrentis equal to or above the andremainsthisway for the time delay programmed inthis setpointwhile the motoris running,the alarm relay will activate and the “GROUND ALARM” message willbedisplayed.
setpoint.
*5281'35,0$5<$/$503,&.83 setpoint value
NOTE:When the phase current increases from 0,
below is used until the 239 determines whetherthe motor isRUNNING or START-ING.
Refer toSection 5.2: A1: STATUS on page 5–2 fordetails on how the 239 detects a startcondi-tion.
•GROUND ALARM DELAY ON START:This delay is used when the motor is ina STARTING
condition. If the ground current is equal to or above the value and remains this way for the time delayprogrammed inthissetpointwhilethe motorisstarting, the alarm relay willactivate and the “GROUND ALARM” message will be displayed.
NOTE:When the phase current increases from 0, this delay is useduntil the239 deter-
mines whether the motorisRUNNING or STARTING.
Refer toSection 5.2: A1: STATUS on page 5–2 fordetails on how the 239 detects a startcondi-tion.
a) THERMISTOR
Insulation breakdown of the stator windings due to overheating is the main cause of motor failureunder overload conditions. Heat buildup inthe rotor can be veryrapidbutthe large thermal massofthe motorpreventsdirect detectionbytemperature sensors embedded inthe stator slots soonenough to prevent damage.It may take several minutes for thetemperaturesensor toreach itstriptemperature. Consequently, a predictive model is required to accurately determineheat buildupwithin the motor. The 239 relay uses an accurate electronic memory method based on motor cur-rents and time based integration algorithms. Thermaloverloads relyonusingmotor current to heatan element with a much smaller timeconstant thanthe motoritself to predict overheating withinthemotor but these devices,although inexpensive,are subjecttomany limitations.
*5281'$/$50'(/$<2167$57 described
*5281'35,0$5<$/$503,&.83 setpoint
4.6 TEMPERATURE
4
Overheating from causes other than resistive heating due to current cannot be detected by modelingmethods that only sense current. To detectthe effects of motoroverheating due to blocked ventila-tion, high ambient temperature or other unforeseen causes, direct temperature sensing is necessary.Since temperature riseunder these conditionsis much slower, the temperaturedetectorwill accu-rately sense the actual temperature within the motor which would not be trueunder a rapid heatbuildup situation such as locked rotor for example.
•THERMISTOR FUNCTION: Linear sensing elements such as RTDs can give an output of actual
temperature but these are expensive and unnecessaryfor basic protection of smallmotors. Ther-mistors are available which give a rapid change of resistance at a specific temperature. The 239accepts a thermistor input and will provide a trip/alarm/auxiliary control within 2 seconds of thethermistor threshold temperature beingmatched or exceeded. Either negativetemperature coef-ficient (NTC) or positive temperature coefficient (PTC) thermistors can be used. The 239
GE Multilin239 Motor Protection Relay4-29
Page 68
4 PROGRAMMING4 PROGRAMMING
assumes a PTC thermistor connection when the +275(6,67$1&( is programmed > &2/'5(6,6
. The 239 assumes a NTC thermistorconnectionwhen the&2/'5(6,67$1&( is programmed
7$1&(
≥
+275(6,67$1&(. PTC thermistors are preferred becausethree PTC thermistors can becon-
nected inseries to monitor each of the statorphases. This is notpossible withNTC thermistorsbecause all three thermistors mustbe hot to obtain afault indication.Select OFFif no thermistoris installed. If the motor is still overheated after a trip, the thermistor signal will prevent restartingof the motor by tripping the239 immediately after reset.Thermistor temperature will be displayedas either hot or cold because the thermistor is nonlinear. If the thermistor function is to be usedfor processcontrol, assign it to the auxiliary relay in which casethe auxiliary relaywill activatebutno messagewill be displayed.
•THERMISTOR HOT RESISTANCE: Consult manufacturer’s data for the thermistor(s) installed inthe motorandenterthe hot resistance value here. If three PTC thermistors are connected inseries, enter the hot resistance of 1 thermistor.
•THERMISTOR COLD RESISTANCE:Consultmanufacturer’s data forthe thermistor(s) installedin the motor and enter the cold resistance value here. If three PTC thermistors are connected inseries,enter 3 times the coldresistance value of a single thermistor.
•THERMISTOR NOT CONNECTED ALARM: If the thermistor becomes open circuited duringuse, the ACTUAL VALUES display for the thermistorwill be "NOT CONNECTED". The 239 relaywill generate an alarm towarn of thefault ifthissetpointis enabled.
setting of
setting of
NΩ
.
NΩ
.
b) RTD 1-3
Protection against excessive motor temperature due to loss of ventilation or high ambient tempera-turesis provided by the RTD option which must be ordered with therelay ifrequired. Up to 3 resis-tancetemperature detectors (RTDs)must be supplied with themotor to use this option. Whenordering a motor with RTDs, the 100 Ωplatinum DIN 43730 type is the preferred choice for optimumsensitivity and linearity.Other RTDsthatcanbe selected are 100 Ω nickel, 120 Ωnickel and 10 Ωcopper.
(OPTION)
4-30239 Motor Protection RelayGE Multilin
Page 69
4 PROGRAMMING4 PROGRAMMING
•RTD 1-3APPLICATION: RTDscan belocated in the stator windings or the bearings. Specifythe
location of each RTD inthissetpoint. The application name selected here will be displayed aspart of the alarmand trip message. If a particular RTD input is not used, this setpoint should beset to off.
•RTD 1-3 TYPE: This setpoint must be programmed to thetype of RTD for each ofthe RTDscon-
nected. The factory default is 100 Ωplatinum but 100 Ω nickel, 120 Ω nickel, or10 Ω copper canalso be connected to each input.
•RTD 1-3 TRIP and RTD1-3 ALARM: Alarm and trip settings for stator RTDs depend on the
motor stator insulationtype. Class B insulation rating is the factorydefaultwith alarm and trip lev-els of110°C and 130°C respectively. Higher temperaturescan beselected for other insulationclasses.Consult the motor manufacturer for suitable settings if higher temperature insulation isinstalled inthe motor.Bearing temperature settings are empirically set.Default settings are 75°Calarmand 90°C trip. The alarm/trip will occur immediately after the input becomes equal to orexceeds the temperature setting. Once a motor is running for several hours the actual tempera-ture can be monitoredand the settingsreduced. Overtime a bearing problem such asalossoflubricant will show up as an increased temperature. Consequently, a setting close to theactualoperating temperature isdesirable providing itdoes not generate nuisance alarms fromambienttemperature changes or load variations.
Temperature display units are set as either Celsius or Fahrenheit depending on the selection ofthe setpointof the RTDs maybedisplayed. If RTD application is settoRTD". When the setpoint sius to Fahrenheit or
63527(&7,21?7(03(5$785(?57'?57'$/$50 willautomatically be scaled to the proper set-
ting.
66(783?35()(5(1&(6?7(03(5$785(',63/$<. RTD temperature readings from all
2)), the display forthat RTD willbe"no
66(783?35()(5(1&(6?7(03(5$785(',63/$<is changed from Cel-
vice versa
, setpoints 63527(&7,21?7(03(5$785(?57'?57'75,3 and
4
c)RTD SENSOR FAILURE
•RTD SENSOR FAILURE ALARM: If an RTD becomes open circuited during use, the ACTUAL
VALUES display for that RTD will be "no RTD". Readings from the disconnected RTD willthen beignored for overtemperature protection. The 239 relaywill generate analarm to warn ofthe faultyRTD if this setpoint is enabled. Setpoints
63527(&7,21?7(03(5$785(?57'?57'$/$50 should be set to off for any unused RTD ter-
minals.
63527(&7,21?7(03(5$785(?57'?57'75,3 and
•OPTION SWITCH 1-2 NAME:A 20 character name can beassigned to the option switch inputs.See Section 4.2e)PROGRAMMABLE MESSAGE on page 4–7 to learn how to enterthe switchnames. Thisname willappear in the following messages.
•OPTION SWITCH 1-2 FUNCTION: The two option switch inputs are identical in operation.Thesecan be programmed to alarm, trip, energize the auxiliary relay for process control, select alter-nate setpoints upon detection ofclosure,ordisable starts upon detection of closure inconjunc-tion with thesomeapplications start protection may not be required. Therefore, by setting this setpoint tothe start protection on the 239 can be defeated.If the setpoint is set to directly into run condition and overload curveswill be employedtoprotect the connected load.
•OPTION SWITCH 1-2 DELAY: A delay of 0.0 to 60.0 seconds is programmed here. The switchmust remainclosed for the programmed length oftimein order for the 239 to detect the condi-tion. If the switches are not used then they should be set to off in
',6$%/(67$576 setpoint described in Section 4.3b) MOTOR DATA on page 4–10. In
<(6,
<(6, the 239 willgo
63527(&7,21?6:,7&+
.
4
4.8 MULTI-SPEED MOTOR
The 239 has a multi-speed motor feature. This feature is intended to provide proper protection for atwo, three, or four-speed motor where there willbe different full motor characteristics (based uponspeed settings). The algorithm integrates the heating at each speed into one thermal model using acommon,thermal capacity used register for all speeds.
Ifthe two-speed motor feature is used, OPTION SWITCH 1 and/or OPTION SWITCH 2 will be dedi-cated as thetwo-speed motor. Terminals 41 and 46(and/or 42 and 47) willbe monitored foracon-tact closure – closure of the contact will signify that the motor is in Speed 2. If the input is open, itsignifiesthatthe motoris in Speed 1. This allows the 239 to determine whichsetpoints should beactive at any given point in time.
•OPTION SWITCH 1-2 ALTERNATE SETPOINTS: The alternate setpoints only appear if the
237,216:,7&+)81&7,21isset to $/7(51$7(6(732,176.As shown in the table below,there aresix
alternate setpointsthatare divided into 3 sets.Thefollowing table shows theconditions requiredto selectthe appropriateset of alternate setpoints.
The message shown below is available on the 239, to indicate which is the currently selectedgroup.The 239 willalso indicate the setpoints groupthat was in use atthe timeofthe last trip.
xxxx SETPOINTS GROUPCURRENTLY IN USE
Located in ACTUAL VALUES pages A1 underthe sub-heading SWITCH STATUS
xxxx= MAIN, 2nd, 3rd, 4th
4-34239 Motor Protection RelayGE Multilin
Page 73
4 PROGRAMMING4 PROGRAMMING
4
Figure 4–7: TWO SPEED MOTOR WIRING DIAGRAM
GE Multilin239 Motor Protection Relay4-35
Page 74
4 PROGRAMMING4 PROGRAMMING
4.9 S5: TESTING
4
SETPOINT
]] SETPOINTS]] S5 TESTING
MESSAGE MESSAGE
▲▼
] TEST CONFIGURATION]
MESSAGE
MESSAGE
▲
▼
] TEST RELAYS & LEDS]
MESSAGE
MESSAGE
▲
▼
] CURRENT SIMULATION]
MESSAGE
MESSAGE
▲▼
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
SETPOINT
4
3
4
3
4
3
]] SETPOINTS]] S1 239 SETUP
DISABLE STARTPROTECTION: NO
PROTECTION DISABLEDFOR: 15 min
DISABLE STATISTICSLOGGING: NO
OPERATION TEST: NORMAL MODE
SIMULATION: OFF
SIMULATION ENABLEDFOR: 15 min
PHASE A CURRENT:0 A
PHASE B CURRENT:0 A
PHASE C CURRENT:0 A
GROUND CURRENT:
0.0 A
Range: NO, YES
Range: 5 to 300, UNLIMITEDStep: 5 min.
Range: NO, YES.
Range: NORMAL MODE, TRIP RELAY & LEDON, ALARM RELAY & LED ON, AUXILIARYRELAY & LED ON, SERVICE RELAY & LEDON, ALL RELAYS ON, PICKUP LED ON,COMMUNICATE LED ON, ALL LEDS ON
Range: ON, OFF
Range: 5 to 300, UNLIMITEDStep: 5 min.
Range:0 to 10000, step 1 A (CT PRI SET > 50 A)
0 to 1000 step 0.1 A (CT PRI SET
Range: Same as PHASE A CURRENT
Range: Same as PHASE A CURRENT
Range:0 to 10000, step 1 A
(CT PRI SET > 50 A)
0 to 1000 step 0.1 A
(CT PRI SET
≤
50 A)
≤
50 A)
] ANALOG OUTPUT] SIMULATION
MESSAGE
MESSAGE
▲
▼
SEE NEXT PAGE
4-36239 Motor Protection RelayGE Multilin
MESSAGE
MESSAGE
4
SIMULATION: OFF
3
SIMULATION ENABLEDFOR: 15 min
ANALOG OUTPUT FORCEDTO: OFF %
Range: OFF, ON
Range: 5 to 300, UNLIMITEDStep: 5 min.
Range: 0.0 to 120.0, OFFStep: 0.1 %
DESIGNATES SETPOINTS THATARE ONLY VISIBLE IF ANALOGOUTPUT OPTION IS INSTALLED
Page 75
4 PROGRAMMING4 PROGRAMMING
SEE PREVIOUS PAGE
] SWITCH INPUTS] SIMULATION
MESSAGE
MESSAGE
▲
▼
] THERMISTOR] SIMULATION
MESSAGE
MESSAGE
▲
▼
MESSAGE
MESSAGE
MESSAGE
MESSAGE
4
SIMULATION: OFF
3
SIMULATION ENABLEDFOR: 15 min
EMERGENCY RESTARTINPUT: OPEN
4
SIMULATION:OFF
3
SIMULATION ENABLEDFOR: 15 min
THERMISTORRESISTANCE: 0
EXTERNAL RESETINPUT: OPEN
OPTION SWITCH 1INPUT: OPEN
OPTION SWITCH 2INPUT: OPEN
Ω
Range: OFF, ON
Range: 5 to 300, UNLIMITEDStep: 5 min.
Range: OPEN, CLOSED
Range: OPEN, CLOSED
Range: OPEN, CLOSED
Range: OPEN, CLOSED
Range: ON, OFF
Range: 5 to 300, UNLIMITEDStep: 5 min.
Range: 0 to 30000
Ω
Step: 1
4
] RTD SIMULATION]
MESSAGE
MESSAGE
▲
▼
] GE POWER MANAGEMENT] USE ONLY
MESSAGE
MESSAGE
4
SIMULATION:OFF
3
SIMULATION ENABLEDFOR: 15 min
RTD 1 TEMPERATURE:
0 °C
RTD 2 TEMPERATURE: 0 °C
RTD 3 TEMPERATURE: 0 °C
SERVICE PASSCODE: 0
Range: OFF, ON
Range: 5 to 300, UNLIMITEDStep: 5 min.
Range:–40 to +200 step 1°C (if °C)
–40 to +400 step 1°F (if °F)
Range:–40 to +200 step 1°C (if °C)
–40 to +400 step 1°F (if °F)
Range:–40 to +200 step 1°C (if °C)
–40 to +400 step 1°F (if °F)
Range: 0 to 9999 step 1
DESIGNATES SETPOINTS THATARE ONLY VISIBLE IF RTDOPTION IS INSTALLED
Figure 4–8:SETPOINTS PAGE 5 – TESTING
GE Multilin239 Motor Protection Relay4-37
Page 76
4 PROGRAMMING4 PROGRAMMING
a) TEST CONFIGURATION
•DISABLE START PROTECTION: To verify correct operation ofoverload curves it may be neces-sary to disablethe start protection.When thisfeature is turned onand currentis injectedabovethe fullload setting,the overload curves will be used to build up the thermal capacity instead of
/2&.('52725&855(17 and 6$)(67$//7,0( setpoints.When this featureis enabled the 239
the assumes the motorisin RUN condition any time current ispresentevenon initial startup inrushcurrent.
has elapsed since the start protection was firstdisabled
When startprotection isdisabled the following flash message willbedisplayed for 3 seconds.
START PROTECTION
HAS BEEN DISABLED
When start protection is re-enabled the following flash message willbe displayed for 3 seconds.
START PROTECTION
HAS BEEN ENABLED
•DISABLE PROTECTION FOR: Select the desired length oftime thatstartprotection will be dis-abled.When the programmed time haselapsed, start protectionwill be re-enabled. If
81/,0,7('
is selected, start protection will be disabled until the feature is turned off via the ',6$%/(67$57
3527(&7,21
•DISABLE STATISTICS LOGGING: Setting this setpoint to NO disables the logging of the
0$;67$57,1*&855(17
setpoint or via the serialportoruntil control power isremoved from the 239.
02725
and 027255811,1*7,0( actual values. See Section 5.2c) MOTOR STA-
TISTICS on page 5–5 forfurtherdetails.
b)TEST OUTPUT RELAYS & LEDS
•OPERATION TEST: To verify correct operation of outputrelay wiring, each output relayand sta-tus indicatorcanbe manually forcedon or offvia thekeypad or serial port. Testing is only allowedifthere is no phase and ground current present and current simulation isturned off.
4-38239 Motor Protection RelayGE Multilin
Page 77
4 PROGRAMMING4 PROGRAMMING
If the test isattempted whilecurrent ispresent, thesetpoint willbe forced toNORMAL MODEandthe following flash message willbedisplayed for 3 seconds.
RELAY TEST BLOCKED
CURRENT PRESENT
If
67(67,1*?&855(176,08/$7,21?6,08/$7,21 is21, the setpoint will be forced to NORMAL
MODE and the following flash message willbedisplayed for 3 seconds.
RELAY TEST BLOCKED
AMPS SIMULATION ON
If testing is attempted via the serial port while phase or ground current is present or simulationmode ison, an error code will be returned.
While the
23(5$7,217(67 setpoint is displayed, use the or key to scroll to the
▲
VALUE
▼
VALUE
desired output relay and/or status indicator to be tested. As long as the test message remainsdisplayed the respective output relay and/or status indicator will be forced to remain energized.As soon as a new message is selected, the respective output relay and/or status indicator returnto normal operation.
As a safeguard, relay and LED test willturnoff automatically if:
4
•powerto the 239 isturnedoff and on
•phase orground current is detected by the 239
•current simulation is turned on
•new message isdisplayed
c) CURRENT SIMULATION
Simulated currents can be forced instead of the actual currents sensed by the external CTs con-nected to the 239. This allows verification of all current related relay functions such as timed over-load trip. Italso allowsverificationthat external tripandalarm wiringis responding correctly.
•SIMULATION: Enter the required simulation phase and ground currents in the following mes-
sages. Enter ON to switch from actual currents to the programmed simulated values. This com-mand will be ignored if real phase or ground current is present. Set this setpoint
2)) after
simulation is complete. As a safeguard, simulation willautomatically turn off if:
•real phase or ground currentis detected while insimulation mode
When current simulationis turned on the followingflash message will be displayed for 3 seconds.
When currentsimulation is turned offthe following flash message will be displayed for 3 seconds.
GE Multilin239 Motor Protection Relay4-39
SIMULATION
HAS BEEN ENABLED
CURRENT SIMULATION
HAS BEEN DISABLED
Page 78
4 PROGRAMMING4 PROGRAMMING
•PHASE A/B/C CURRENT: Enter the desired phase current for simulation. For example, to verifyoperation of the unbalance function, turn the unbalance function trip on, set
•GROUND CURRENT: Enter the ground current for simulation of a ground fault. Then set
7(67,1*?&855(176,08/$7,21?6,08/$7,2121
•SIMULATION ENABLED FOR:Selectthe desired length of time thatsimulation will be enabled.
4
When the programmed time has elapsed, current simulation will turn off. If
to see the effect of this current.
81/,0,7(' is selected,
simulated current willbe used until one of the above mentioned conditions is met.
d) ANALOG OUTPUT SIMULATION
•SIMULATION: Enter ON to switch from actual analog output to the programmed simulationvalue. Set this setpoint to OFF after simulation is complete. As a safeguard, simulation willauto-matically turn off if:
•powerto the 239 isturnedoff and on
•time programmed inthe setpointhas elapsed sincesimulation was firstenabled
When analog output simulation is turned on the following flash message will be displayed for 3 sec-onds.
SIMULATION
HAS BEEN ENABLED
When analog output simulation is turned off the following flash message willbe displayed for 3seconds.
6
ANALOG OUT SIMULATION
•ANALOG OUTPUT FORCED TO: Enter in percent the analog output value to be simulated.Whether the output is 0-1mA, 0-20mAor 4-20mA is dependent upon the selection in
•SIMULATION ENABLED FOR:Selectthe desired length of time thatsimulation will be enabled.
When the programmed time has elapsed, analog output simulation will turn off.Ifselected, simulated analog output willbeused untilsimulation is turned off viathe
setpoint or via the serial portor untilcontrol poweris removed from the 239.
2))
81/,0,7(' is
6,08/$7,2121
e)SWITCH INPUTS SIMULATION
•SIMULATION: Enter
21 to switch from actual switch inputs to the programmed simulation status
of each switch input. While simulation is on the actual switch input status will be overridden bythe simulated status of each input. Set this setpoint to
point has elapsed since simulation was firstenabled
When switch inputssimulation isturned on the following flash message will be displayed for 3seconds.
SIMULATION
HAS BEEN ENABLED
When switch inputs simulation is turned off the following flash message will be displayed for 3seconds.
SIMULATION
HAS BEEN DISABLED
•EMERGENCY RESTART INPUT: Enter the status of this switch input as
23(1 or &/26('. The
functionality of this input remains as is with actual input connected.
•EXTERNAL RESET INPUT: Enter the status of this switch input as
23(1 or&/26('. The function-
ality of this input remains as iswith actualinput connected.
•OPTION 1 INPUT: Enterthe status of this switch input as
23(1 or&/26('. The functionality ofthis
input remains as iswith actualinput connected.
•OPTION 2 INPUT: Enterthe status of this switch input as
23(1 or&/26('. The functionality ofthis
input remains as iswith actualinput connected.
•SIMULATION ENABLED FOR:Selectthe desired length of time thatsimulation will be enabled.
When the programmed time has elapsed, switch inputs simulation willturn off. Ifselected,simulated switch input statuswillbe used untilsimulation is turned off via the
7,21212))
setpoint orvia the serial port or untilcontrolpower is removed from the 239.
81/,0,7(' is
6,08/$
4
f) THERMISTOR SIMULATION
•SIMULATION: Enter
21to switch from actualthermistor input to the programmed simulation
thermistor resistance value. While simulation is on the actualthermistor input will be overriddenby the simulated resistance value. Set this setpoint toguard, simulation will automatically turn off if:
•powerto the 239 isturnedoff and on
•the time programmed in has elapsed since simulation was first enabled
When thermistor simulation is turned on the following flash message will be displayed for 3 sec-onds.
SIMULATION
HAS BEEN ENABLED
When thermistor simulation isturned off the following flashmessage will be displayed for 3 sec-onds.
THERMISTOR SIMULATION
HAS BEEN DISABLED
•THERMISTOR RESISTANCE:Enterthe value ofthe thermistor resistance to be simulated. Thefunctionality ofthe thermistor remains as iswith an actual inputconnected to the 239.
•SIMULATION ENABLED FOR:Selectthe desired length of time thatsimulation will be enabled.When the programmed time has elapsed, thermistor simulation willturn off. Ifselected, simulated thermistor input willbe used until simulation is turned off via the
212))
setpoint orvia the serial port or untilcontrolpower is removed from the 239.
4
g) RTD SIMULATION
•SIMULATION: Enter ON to switch fromactual input to the programmed simulation temperaturevalue of each RTD input value. While simulation is on all three RTD r inputs will be overridden bythe simulated temperature values. Set thissetpointto guard, simulation will automatically turn off if:
•powerto the 239 isturnedoff and on
•time programmed in
67(67,1*?57'6,08/$7,21?6,08/$7,21(1$%/(')25 setpoint has
elapsed since simulation was firstenabled
2)) after simulation iscomplete. As a safe-
81/,0,7(' is
6,08/$7,21
When RTD simulationis turned on the following flash message will be displayed for 3 seconds.
SIMULATION
HAS BEEN ENABLED
When RTD simulationis turned off the following flash message willbedisplayed for 3 seconds.
RTD SIMULATION
HAS BEEN DISABLED
•RTD 1/2/3 TEMPERATURE: Enter the value of the each RTD temperature to be simulated. Thefunctionality ofthe RTDs remains as is with actual inputs connected to the 239.
•SIMULATION ENABLED FOR:Selectthe desired length of time thatsimulation will be enabled.When the programmed time has elapsed, RTD simulation will turn off. Ifsimulated RTD input will be used until simulation is turned off via the
81/,0,7(' is selected,
6,08/$7,21212)) setpoint
orvia the serial port or until controlpower isremoved from the 239.
h)GE MULTILIN USE ONLY
•SERVICE PASSCODE CODE: These messages are accessed by GE Multilin personnelonly fortesting and service.
4-42239 Motor Protection RelayGE Multilin
Page 81
5 MONITORING5 MONITORING
239INSTRUCTION MANUAL 5 MONITORING5.1 ACTUAL VALUES VIEWING
Any measured value can be displayed on demand using the key. Each time the
ACTUALACTUAL
key is pressed,the beginning of a new pageof monitored values is displayed. Theseare groupedas:A1: STATUS, A2: METERING, A3: PRODUCT INFO. Use the /keys in the same
MESSAGE
▲
MESSAGE
▼
fashion as for setpoints to move between actual value messages. A detailed description of each dis-played message in these groups is given in the sections that follow.
ACTUALACTUAL
]] ACTUAL VALUES]] A1 STATUS
MESSAGE
] GENERAL]
] LAST TRIP DATA]
]] ACTUAL VALUES]] A2 METERING
▼
] CURRENT]
] MOTOR CAPACITY]
MESSAGE
ACTUAL
]] ACTUAL VALUES]] A3 PRODUCT INFO
▼
] FIRWARE VERSIONS]
] MODEL INFORMATION]
MESSAGE
▼
5
] MOTOR STATISTICS]
] SWITCH STATUS]
] PROGRAMMABLE] MESSAGE
Figure 5–1: ACTUALVALUES MESSAGE ORGANIZATION
] TEMPERATURE]
GE Multilin239 Motor Protection Relay5-1
Page 82
5 MONITORING5 MONITORING
5.2 A1: STATUS
5
ACTUAL
]]ACTUALVALUES]]A1STATUS
MESSAGE
MESSAGEs
MESSAGEt
MESSAGE
]GENERAL]
MESSAGEs
MESSAGEt
MESSAGE4
MESSAGE3
ACTUAL
]]ACTUALVALUES]]A2METERING
SYSTEMSTATUSNORMAL
MOTORSTATUSSTOPPED
MOTORSTARTING1zz2zz3zz4zz5zz6zz7zz8
TIMETOOVERLOADRESET:10.0MINUTES
OVERLOADTRIPIN:11.5SECONDS
IMMEDIATEOVERLOADIavg=110%FLC
UNDERCURRENTALARMIavg=30%FLC
UNBALANCEALARMUB=10%
Range:TRIP,ALARM,TRIPANDALARM,NORMAL
Range:STOPPED,STARTING,RUNNING
GROUNDALARMIgnd=5A
STATORRTDALARMRTD=135°C
BEARINGRTDALARMRTD=135°C
RTDSENSORFAILURERTD1
INTERNALFAULTALARM
Seenonlywhenconditionispresent
SEENEXTPAGE
5-2239 Motor Protection RelayGE Multilin
THERMISTORALARM
THERMISTORNOTCONNECTED
THERMALCAPACITYUSEDALARM
COMMUNICATIONFAILUREALARM
OPTIONSWITCH1
ALARM
OPTIONSWITCH2
ALARM
MECHANICALJAM
ALARM
BREAKERFAILURE
ALARM
NOACTIVEALARM
Page 83
5 MONITORING5 MONITORING
SEE PREVIOUS PAGE
] LAST TRIP DATA]
MESSAGE
MESSAGE
▲
▼
] MOTOR STATISTICS]
MESSAGE
MESSAGE
MESSAGE
MESSAGE
4
CAUSE OF LAST TRIP:NO TRIP
3
A= 0 B= 0C= 0 AMPS
GROUND CURRENT=
0.0 ACURRENT UNBALANCE
U/B= 0%
STATOR RTD 1 TEMP:
130°C
BEARING RTD 2NO RTD
4
MOTOR MAX STARTINGCURRENT = 0 A
3
RUNNING TIME:
0.0 h
BEARING RTD 3NO RTD
SETPOINTS GROUPIN USE: MAIN
2nd LAST TRIP:NO TRIP
3rd LAST TRIP:NO TRIP
4th LAST TRIP:NO TRIP
5th LAST TRIP:NO TRIP
Range: NO TRIP, OVERLOAD, SHORT CIRCUIT, MECHANICALJAM, UNBALANCE, GROUND FAULT, STATOR RTD, BEARINGRTD, UNDERCURRENT, THERMISTOR, COMPUTER TRIP,PARAMETERS NOT SET, OPTION SWITCH 1, OPTION SWITCH 2
Range: 0 to 10000
Range: 0 to 1000
Range: 0 to 100
Range:–40 to +200 °C
–40 to +400 °F
Range:–40 to +200 °C
–40 to +400 °F
Range:–40 to +200 °C
–40 to +400 °F
Range: MAIN, 2nd, 3rd, 4th
Range: Same as CAUSE OFLAST TRIP above
Range: 0 to 10000 A
Range: 0 to 429496729.6 hrs
5
MESSAGE
] SWITCH STATUS]
MESSAGE
MESSAGE
MESSAGE
▲
▼
SEE NEXT PAGE
GE Multilin239 Motor Protection Relay5-3
4
SW. 1 ACCESSSWITCH STATE: OPEN
3
SW.2 EMERG RESTARTSWITCH STATE: OPEN
SW.3 EXTERNAL RESETSWITCH STATE: OPEN
OPTION SWITCH 1SWITCH STATE: OPEN
OPTION SWITCH 2SWITCH STATE: OPEN
Range: OPEN, CLOSED
Range: OPEN, CLOSED
MAIN SETPOINTS GROUPCURRENTLY IN USE
Range: OPEN, CLOSED
Range: OPEN, CLOSED
Range: OPEN, CLOSED
Range: OPEN, CLOSED
Page 84
5 MONITORING5 MONITORING
SEEPREVIOUSPAGE
MESSAGE4
]PROGRAMMABLE]MESSAGE
MESSAGE3
]ENDOFPAGEA1]
]Phone:905-294-6222]GEindustrial.com/pm
Figure 5–2: ACTUAL VALUES PAGE 1 – STATUS
a) GENERAL
•SYSTEM STATUS: This message gives an indication ifoperation is normal or whether a trip and/or alarm has occurred. Onlyone condition can cause a trip at a time and this will be displayedafter a trip. When alarms are present the system status will be alarm. Press to view all
MESSAGE
active alarm conditions and the corresponding actual value thatis causing the alarm. Select thecorresponding setpoint to determine byhow much the actual value exceeds the alarm setting.
•MOTOR STATUS: This message displays the currentstatus ofthe motor.
•MOTOR STARTING: This message is displayed when the motor is in a START mode. The
5
START condition occurs ifthe average of the three phase currents rises above the fullload cur-rent setting in
66<67(06(783?02725'$7$?02725)8///2$'&855(17within 300 ms (worst case)
of initial detection ofcurrent by the 239.
•TIME TOTRIP: This message is displayed when a trip condition is in progress. The messagedisplaytime isscaledasfollows:
▼
if thetrip timeis> 10.0 minutes, the display willbe ‘xxx.x MINUTES’
≤
10.0 minutes,the display will be ‘xxx.xSECONDS’
•TIME TO OVERLOAD RESET: This message displays theamount of time remaining before anOVERLOADTRIP is allowed to be reset. The time willbecome 0 when the thermal capacitydecreases to 15%.
•CAUSE OF ALARM: The appropriatealarm message isdisplayed when the respective alarmcondition is present. More than one alarm message can bepresentat once.
b) LAST TRIP DATA
After a trip, all conditions present at the timeof trip and the cause of trip are saved in non-volatilememory. Inaddition, a trip record of the last5 causes of trip isalso retained for diagnosing persistentproblems.
•CAUSE OF LAST TRIP: Only one condition at a time will cause a trip. The most recent cause oftrip is displayed.
•A: B: C: CURRENT: Actual current flowing in each of the three phases at the moment of trip isdisplayed. By comparingthese values tothe motor fullload current afteran overload trip, itshould be easy to determine in which phase the fault has occurred. A high current in one phaseandground indicates a phase to ground fault. A high current in2phases suggests a phasetophase fault.High current in all three phases indicates a running overload or possible short circuit.
5-4239 Motor Protection RelayGE Multilin
Page 85
5 MONITORING5 MONITORING
The currentresolution is 0.1A if the &735,0$5< setting is≤50 A. The resolution is 1A if the &7
35,0$5<
•GROUND CURRENT: Ifexcessive ground current was present atthe time oftrip,an insulation
failure is likely.With the motor off-line, checkthe insulation resistance inallthree phases andcable wiring.
•CURRENT UNBALANCE: Excessive unbalance can be caused by loose terminal connections,
faulty utility supply, a blown fuse, or faulty contactor.Check for these before restarting the motor.
•STATOR (BEARING)RTD 1-3 (OPTION): If any stator RTDs shows a hightemperature, check
that the ventilation to the motor isclear. Repeated starting using the Emergency Restart featurewill cause the motor to overheat and should be avoided. After an overload trip, the RTD tempera-ture may be elevated.Verify that the motor has cooled before restarting by checking each RTDtemperature using the messages an excessive bearing temperature usuallyindicates a need for lubricationor a faultwiththe bear-ing itself. Lubricate the bearing then monitor itstemperature closely afterstarting themotor.
•SETPOINTS GROUP IN USE: Alternate setpoints (i.e.
etc.) can be selected using the Option Switch 1 and OptionSwitch 2 inputs as explained in Sec-tion 4.7: SWITCH INPUTS on page 4–33. One of four possible groups of setpoints can beselected at once. Thismessage displaysthe selected group at the time of the lasttrip.
•2nd (3-5) LAST TRIP: A trip record ofthe last 5 causes of trip isretained for diagnosing persis-
tentproblems. Each new trip is added to the trip record and the oldest (fifth) cause of trip iserased.No trip data is saved in this trip record.However,by observing repeated trips of thesametype,an indication of an inherent fault isobtainedfor maintenance purposes.
settingis > 50A.
$0(7(5,1*?7(03(5$785(. If the RTDis installed on a bearing,
3+$6(&735,0$5<, )8///2$'&855(17,
5
c)MOTOR STATISTICS
The total motor running time (including start conditions) and the maximumaverage current presentduring the last successful start are monitored here.
d) SWITCH STATUS
To assist introubleshooting, the state of each switch can be verified using these messages. A sepa-rate message displays the status of each input identified by the corresponding name as shown inFigure 2–3: TYPICAL WIRING DIAGRAM on page2–4. For a dry contact closure across the corre-sponding switch terminals the message willread closed.
NOTE: If the switch simulation is turned on inshown in these messages willbe of the simulated inputs.
•SETPOINTS GROUP CURRENTLY IN USE: Alternate setpoints (i.e.
/2$'&855(17
explained in Section 4.7: SWITCH INPUTS on page4–33. One of four possible groups of set-points can be selected at once. This message displays the currently selected group.
e) PROGRAMMABLE MESSAGE
A 40 character message can be programmedusing the keypad orvia theserial port using the 239PCsoftware.See 4.2: S1: 239 SETUP on page 4–3 foran example of programming this message usingthe keypad.
, etc.) can be selected using the Option Switch 1 and Option Switch 2 inputs as
67(67,1*?6:,7&+6,08/$7,21?6,08/$7,21, the status
3+$6(&735,0$5<, )8//
This message can be used for identification purposes such as company name, site name, stationname, relay identification number, etc.It can be chosen as the default message so it isdisplayedwhen the unit isleft alone.
GE Multilin239 Motor Protection Relay5-5
Page 86
5 MONITORING5 MONITORING
5.3 A2: METERING
5
ACTUAL
]] ACTUAL VALUES]] A2 METERING
MESSAGE
MESSAGE
▲▼
] CURRENT]
MESSAGE
MESSAGE
▲
▼
] MOTOR CAPACITY]
MESSAGE
MESSAGE
▲
▼
] TEMPERATURE]
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
ACTUAL
4
3
4
3
4
3
]] ACTUAL VALUES]] A3 PRODUCT INFO
A= 0 B= 0C= 0 AMPS
GROUND CURRENT =
0.0 AMPSCURRENT UNBALANCE
U/B = 0%
MOTOR LOAD =0 % FULL LOAD
THERMAL CAPACITYUSED = 0%
STATOR RTD 1
TEMPERATURE: 80°C
BEARING RTD 2TEMPERATURE: 50°C
BEARING RTD 3TEMPERATURE: 50°C
THERMISTOR =COLD
Range:0 to 10000 (if CT SET PRI > 50 A)
0 to 1000 (if CT SET PRI
Range:0 to 1500 (if X:5 or RESIDUAL)
0 to 1000 (if 50:0.025 setting)
Range: 0 to 100%
Range: 0 to 100%
Range: 0 to 100%
Range:–40 to +200 °C
–40 to +400 °F
Range:–40 to +200 °C
–40 to +400 °F
Range:–40 to +200 °C
–40 to +400 °F
Range: HOT, COLD, CONNECTED
≤
50 A)
] END OF PAGE A2]
Figure 5–3: ACTUAL VALUES PAGE 2 – METERING
a) CURRENT
•A: B: C: CURRENT: Current in each phase corresponding to the A, B and C phase inputs isdis-played. Current will only be measured correctly ifprimary and the CTsecondary is wired to match the 1 or 5 A input. If the displayed current doesnot match the actual current, check this setpoint and wiring. During starting, the displaywill auto-
5-6239 Motor Protection RelayGE Multilin
DESIGNATES ACTUAL VALUES THATWILL ONLY BE DISPLAYED IF RTDOPTION IS INSTALLED AND THECORRESPONDING RTD FEATURE ISTURNED ON.
&735,0$5< is entered to match the installed CT
Page 87
5 MONITORING5 MONITORING
matically switch to a bar graph showing multiples of full load current. Once the current dropsbelow the motorfull load setting, thedisplaywill revert to the threephase currents. The currentresolution is 0.1 A if
&735,0$5<≤ 50A. The resolution is 1 A if&735,0$5< >50A.
•GROUND CURRENT: Presence of ground current indicates some undesirable current to ground
leakage. The ground currentreading willonly be correct if theCT is wired correctlyandthe cor-rect
&735,0$5<value is entered. Verify ground current by connecting a clamp-on ammeter
around all 3 phases. If the ground current appears incorrect, checkthe ground CT settings in
6<67(06(783?&7,13876
and verify the CT wiring.
6
•CURRENT UNBALANCE: Current unbalance causes rotor heating. Itis calculated as:
ImI
–
av
where:
I
≥:
avIFLC
I
<:
avIFLC
I
= average phase current
av
I
=current ina phasewith maximum deviation from
m
I
= motor fullload currentsetting
FLC
---------------------
I
av
ImI
–
---------------------
I
FLC
av
100%×
100%×
I
av
These formulasallow larger levelsof unbalance to be tolerated bylightly loaded motors. Exces-sive unbalance can be caused by loose terminal connections, faulty utility supply, a blown fuse ora faulty contactor.
5
b) MOTORCAPACITY
•MOTOR LOAD: In order to gauge how closely the motor is running to its maximum capacity, the
I
/
I
.
I
motor load iscalculated and displayed as: Motor Load = rent.
I
isthe rated motorfull load current entered insetpoint66<67(06(783?02725'$7$. A
FLC
av
FLC
isthe average 3 phase cur-
av
value greater than 100% indicates an overloaded motor that will eventually trip on timed over-load. Values less than 100% indicate that the motor is operating normally.
•THERMAL CAPACITY USED:The heating effect of starts and overloads is integrated and
stored in a thermal memory that models the heat buildup within the motor. When the thermalcapacity used equals 100%,the 239 trips the motor since the motoris considered to be runningat its maximum temperature. With no overloads present,the thermal capacity used will gradu-ally decrease to a steady state value, determined as described in
'$7$?+27&2/'&859(5$7,2
, to simulate motorcooling. When thermal capacity used isclose to
66<67(06(783?02725
100%, attempting to restart a stopped motor may result in a trip due to the rapid increase in thethermal memoryused under a startcondition.
GE Multilin239 Motor Protection Relay5-7
Page 88
5 MONITORING5 MONITORING
c) TEMPERATURE
•STATOR (BEARING) RTD1 (2-3) TEMPERATURE (OPTION): When enabled by
785(?57'?57'$33/,&$7,21
played. For RTDs installed in the stator, interpretation of the temperature is more meaningful ifthe insulation class of the stator windings is known. This value indicates how close the stator isoperatingtoits maximum allowable temperature.Consult the motormanufacturer’s data forsta-tor insulation class and maximum operating temperature. Insulation life typically is reduced byhalf for every 10°C rise in temperature. Bearing temperatures vary with ambient conditions,greasing, wear and loading. A significant increase in bearing temperature may indicate a prob-lem that needs investigation. Temperatures can be viewed in°Cor °F by selecting theappropri-ate setpoint in
•THERMISTOR: Thermistors typically installedin motors for temperature detection are nonlineardevices. When enabled, the thermistor readout will indicate hot or colddepending on whether thethermistor resistance exceeds itsalarm/trip threshold setpoint. If the terminals are left uncon-nected while the thermistor functionis set to trip or alarm or the thermistor resistance increasesabove 31.5 kΩ, the thermistoris not being used, the functionmustbeset to off.
66(783?35()(5(1&(6?7(03(5$785(',63/$<,1.
THERMISTOR NOT CONNECTED alarm message willbedisplayed. Therefore, if
, the actual temperaturemeasured by each RTD will be dis-
5
67(03(5$
5-8239 Motor Protection RelayGE Multilin
Page 89
5 MONITORING5 MONITORING
5.4 A3: PRODUCT INFO
ACTUAL
]] ACTUAL VALUES]] A3 PRODUCT INFO
MESSAGE
MESSAGE
▲▼
] FIRMWARE REVISIONS]
MESSAGE
MESSAGE
▲
▼
] MODEL INFORMATION]
ACTUAL
MESSAGE
MESSAGE
MESSAGE
MESSAGE
]] ACTUAL VALUES]] A1 STATUS
4
MAIN PROGRAM VER:
2.4 Nov 24, 1999
3
BOOT PROGRAM VER:
2.00 Mar 27, 1997SUPERVISOR PROG VER:
1.02 Jul 17, 1996
4
ORDER CODE:239-RTD-AN
3
MOD NUMBER(S): 000
SERIAL NUMBER: D6491234
5
HARDWARE
MESSAGE
MESSAGE
▲
▼
REVISION: D
DATE OF MANUFACTURE:February 29, 1999
DATE OF CALIBRATION:February 29, 1999
] END OF PAGE A3]
Figure 5–4: ACTUAL VALUES PAGE 3 – PRODUCT INFO
a) SOFTWARE VERSIONS
Productsoftware revision information iscontained inthese messages.
•MAIN PROGRAM VERSION: When referring to documentationor requestingtechnical assis-tance from the factory, record the
0$,1352*5$09(56,21 and 02',),&$7,21),/(180%(5. The
0$,1352*5$09(56,21 identifies the firmware installed internally in the flash memory.The title
page of this instruction manual states the main programrevision code for which the manual iswritten. Theremay be differences inthe product and manual if the revision codesdo notmatch.
•BOOT PROGRAM VERSION:This identifies the firmware installed internallyin the PROM mem-ory of the239.This doesnotaffect the functionality ofthe 239.
GE Multilin239 Motor Protection Relay5-9
Page 90
5 MONITORING5 MONITORING
•SUPERVISOR PROGRAM VERSION: This identifies the firmware installed internally in theSupervisor (power fail) processor of the 239. This does not affectthe functionality of the 239.
b) IDENTIFICATION
Productidentification information iscontained inthese messages.
•ORDER CODE: The order codeshows the configurationof the relay and will appear as shownbelow depending upon the optionsinstalled.
‘239’Íno optionshave been installed, basic unit
‘239-RTD’ÍRTDs option has been installed
‘239-AN’ÍAnalog Outputoption has been installed
‘239-RTD-AN’ÍRTDs and Analog Output options have been installed
•MOD NUMBER: Ifuniquefeatures havebeeninstalled for special customer orders, the
180%(5
replacement modelis required,the found on the label located on the back of the 239 should be specified withthe order.
Itis possible for the 239 to have more than one
5
case the message willdisplay all the
•SERIAL NUMBER: Each 239 shipped from the factory has a unique serial number for identifica-tion purposes. The serial number displayed in thismessage willmatch the serial number foundon the productlabel located on the backofthe 239.
•HARDWARE REVISION: This message identifies the internal hardware revision of the 239. Thefirst letter of the 239 serial numbermustmatch the hardware revision identified inthismessage.
•DATE OF CALIBRATION: Each 239 is calibrated to exceed the specifications listed in Section
1.4:SPECIFICATIONS on page 1–7 using custom made test equipment. When all parametershave been calibrated and tested for proper operation the unit is stamped with the calibration datedisplayed in this message.
•DATE OF MANUFACTURE:This isthe date the 239 was final tested at GE Multilin.
will be used by factory personnelto identifythe matching productrecords.If an exact
0$,1352*5$09(56,21, 02'180%(5, and productordercode
02'180%(5 installed (maximum of 5). In this
02'180%(5sseparated by a comma (i.e. 501, 502,503).
Although setpoints can be entered manuallyusing the front panel keys, it ismuch easier to use acomputerto download values through the communications port.A freeprogram called 239PC isavailable from Multilin to make this as convenientaspossible. With 239PC running on yourpersonalcomputerunder Windows it is possible to:
•Program/modify setpoints
•Load/save setpoint files from/to disk
•Read actualvalues
•Monitor status
•Plot/print trends
•Read pre-trip data and triprecord
•Get help on any topic
•Print the instructionmanualfrom diskThe 239PC software allows immediate accessto all the features ofthe 239 with easy touse pull
down menus inthe familiar Windowsenvironment.The 239PC software can run without a 239 connected to a computer and save settings to a file. If a
239 is connected to a serial port on a computer and communications is enabled, the 239 can be pro-grammed from the displayed with the
Setpoint
Actual
screens. In addition, measured values, status and trip messages can be
screens.
The 239 communications issetup as shown inthe figure below.
239RELAY
POWERSUPPLYMODULETOWALLPLUG
MULTILIN
RS232/RS485
COMPUTER
CONVERTOR
-+
R
S
2
P
O
W
E
R
R
S
4
8
5
32
RS232CONNECTORTO
COMPUTERCOMPORT
TYPICALLYCOM1ORCOM2
Figure 6–1: TYPICAL COMMUNICATIONS SETUP
6.2 HARDWARE CONFIGURATION
239RELAYSETUPPROGRAM
Setpoints
File
Actual
Diagnosis
Comms
MODE:
TRIPRECORD
2ndLastTrip
3rdLastTrip
4thLastTrip
5thLastTrip
ORMAL
N
Help
COMMUNICAL:
OK
Cancel
CLEAR
Overload
None
None
None
N
O
819807A4.CDR
LAST
T
RIP
Cause
PhaseA
PhaseB
PhaseC
Ground
Unbalance
TEMPERATURE
Degrees
RTD1Type
RTD1Temperature
RTD2Type
RTD2Temperature
RTD
3Type
RTD3Temperature
MOTOR:RUNNING
TRIPINFORMATION
D
ATA
CLEAR
Overload
100A
30A
50A
10.5A
30%
Celsius
Stator
95C
Bearing
75C
Bearing
73C
STATUS:OK
6
GE Multilin239 Motor Protection Relay6-1
Page 92
6 239PC SOFTWARE6 239PC SOFTWARE
6.3 239PC VERSION
If the 239PC software is already installed, check if it needs to be upgraded as shown below. If the239PC software isinstalled and isup-to-date thenskipto 6.4: INSTALLING/UPGRADING 239PC on
page 6–3.
1.Select the Help > About 239PC menuitem.
2.No upgrade is required ifthetwo versions are identical.
The following minimum requirements must be met for the239PC software to operateon the com-puter.
•Windows
•10MB free hard disk spaceIf the 239PC software already exists and is being upgraded, thenplease notedown exact path and
the directory name of the current installation because itwill be required during the new installationprocess.
1.Start Windows.
2.Insert the GE Multilin ProductsCD into the appropriate drive (alternately, you can go to the GEMultilin website atwww.GEindustrial.com/multilin tocontinue theinstallation—the steps are roughlythe same).
3.The following window will be displayed by yourdefault web browser once the CDdrawer, with theProduct CD, isclosed:
®
3.1 / Windows 95 or higher isinstalled and running
4.Use the mouse to click onSoftware. If3.5” floppy disksare required, they may becreated from the installationprogram on this CD, cre-ated from the GEMultilinwebsite atwww.GEindus-trial.com/multilin, or ordereddirectly fromthe factory.
6
5.The browser will display the GE Multilin product list in alphabetical order. Choose the 239 MotorProtection Relayfrom this list.
GE Multilin239 Motor Protection Relay6-3
Page 94
6 239PC SOFTWARE6 239PC SOFTWARE
6.Selectthe 239PC program from the listof softwareand firmware items.
239 Software
PC Program:
239PC Version 2.51 (.exe) [4M]
•
Relay Firmware:
2.51 Firmware serial# beginningwith B or C (.zip) [58k]
•
2.51 Firmware for serial# beginning with D (.zip) [59k]
•
7.The browser will launch the File Download window. Select the Run this program from its current loca-tion option and click OK. The following window will appear.
8.Verify that you wish toinstall 239PC by clicking Yes.
9.Click on CONTINUE WITH 239 PC VERSION 2.50 INSTALLATION to continue installingthe PC softwaredirectly to your hard drive. If you wish to make a 1.44MB floppy disk containing the 239PC soft-ware, click onStart Copying.
6
6-4239 Motor Protection RelayGE Multilin
Page 95
6 239PC SOFTWARE6 239PC SOFTWARE
10.The install program will prompt fora destination folder.
11.If the program isnot to be installed inthe defaultdirectory,or 239PC is alreadyinstalledin a dif-
ferent location, click on Browse and enter the complete path for 239PC. If 239PC is alreadyinstalled, the old files willbe replaced with new ones.ClickNextto continue with the installationprocessonce the destination directory iscorrect.
12.The 239PC install program will askyou tochoose between Typical, Compact, and Custom setup
(Typical is fine for almost all cases). Choose the desired type of setup preferred and click Next tocontinue the installation process.
13.You will bepromptedto choose a folder name to place the 239PC icon. Select a folder and click
Next tocontinue.
14.Click on Finish to complete the installation of 239PC. It is recommended that you restart Windows
before using the program.
The 239PC program may also be installed from the GE Multilin website atwww.GEindustrial.com/multilin.Follow the instructions above forinstallation.
NOTE
6
GE Multilin239 Motor Protection Relay6-5
Page 96
6 239PC SOFTWARE6 239PC SOFTWARE
6.5 239PC MENU STRUCTURE
6
6-6239 Motor Protection RelayGE Multilin
Page 97
6 239PC SOFTWARE6 239PC SOFTWARE
6.6 CONFIGURING239PC
1.Start239PC by double-clicking the 239PC icon in the GEMultilinfolder (or alternate folder con-
taining the 239PC icon) orfromthe Start menu.
2.Once 239PC starts to execute, it will attempt to communicate with the relay.If communication is
established successfully, the screen and LEDs on the relay graphic shown inthe 239PC windowwill display the same information as the actualrelay.
6
GE Multilin239 Motor Protection Relay6-7
Page 98
6 239PC SOFTWARE6 239PC SOFTWARE
3.If 239PC cannot establish communication with therelay,the following message willbe displayed.
4.Click on Yes to edit the 239PC communication settings. This will display the COMMUNICATION/COMPUTER window shown below.
6
5.SetSlave Addressto match therelay addresssetpoint.
6.SetCommunication Port #to the COM port where the relay is connected.
7.SetBaud Rateto match the relay baud rate setpoint.
8.SetParity to match the relay parity setpoint.
9.If using the GE Multilin F485 converter,leave the Control Type setting as is.
10.SetStartup Modeto“Communicate with relay”.
11.Click the ON button tocommunicatewiththe relay and 239PC will notify when communicationshave been established with the relay.Ifit fails to communicate, check the following:
•Ensure that the settings above match the relay settings.
•Ensure the COMport setting matches the COM port being used.
•Ensure thehardwareis connected correctly as shown in Figure 6–1: TYPICAL COMMU-NICATIONS SETUP on page 6–1.
•Ensure the RS485 cable polarity iscorrect and connected tothe correctrelay terminals.
6-8239 Motor Protection RelayGE Multilin
Page 99
6 239PC SOFTWARE6 239PC SOFTWARE
6.7 239 FIRMWARE UPGRADE
a)STEP 1—SAVING AND PRINTING SETPOINTS
1.Savethe 239 setpoints to a file by selecting Save As from the File menu.
2.239PC will prompt for a file name andlocation.Choose an appropriate file name and directorythen clickOKtocontinue saving the setpoints.
3.SelectPrint Setup fromthe File menu.
4.The Print Setup dialog box (shown below) will appear. Select the desired information to be printed,in this caseSetpoints (All), and thenclick OK.
5.SelectPrintfrom the File menu.
6.Ensure the printerselected issetup and on-line and click OK to printsetpoints.
b)STEP 2—LOADING NEW FIRMWARE INTOTHE 239
1.SelectUpgrade Firmwarefrom the Communication menu.
2.The following window will appear. SelectYesto proceed orNo toabort the process.
3.The fileto be loaded into the 239 mustmatch the hardware inside the 239.
•If the 239 serial number begins with B or C, select the file beginning with the characters 64C.
•If the239 serial number begins withD,select the file beginning with the characters64D.
6
GE Multilin239 Motor Protection Relay6-9
Page 100
6 239PC SOFTWARE6 239PC SOFTWARE
This isindicated in the following dialog box.Click OK tocontinue.
4.The Load Firmware dialog box appears.The firmware filename has the following format:
64 D 250 C4 000
Modification number (000 = none)
For GE Power Management use onlyProduct firmware revision (e.g. 2.50). On the 239, this number is
found in Actual Values page A3 under
PROGRAM VER
6
Required product hardware revision. This letter must matchthe first character of the serial number located on the productlabel on the back of the relay
Product Name (64 = 239 Relay)
5.Locate the firmware fileto be loaded into the relay and click OK toproceed.
6.The following dialog box willappear;select
•Yes to proceed
•No to load a differentfirmware file
•Cancel to abort the process
FIRMWARE VERSION/MAIN
6-10239 Motor Protection RelayGE Multilin
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.