Thank you for purchasing this quality-built GE home generator. We’re pleased that you’ve placed your confidence in the GE
NOT
for
REPRODUCTION
brand. When operated and maintained according to the instructions in the operator’s manual, your home generator will provide
many years of dependable service.
This manual contains safety information to make you aware of the hazards and risks associated with standby generators and
how to avoid them. This product is only for use as an optional generator system which provides an alternate source of electric
power and to serve loads such as heating, refrigeration systems, and communication systems that, when stopped during any
power outage, could cause discomfort or inconvenience.
Save these original instructions for future reference.
This generator requires professional installation before use. The installer should follow the instructions completely.
Where to Find Us
You never have to look far to find support and service for your generator. For quick service when you need it most fill out the
information below and keep your original receipt with this manual. You may contact Customer Service at (888) 575-8226, or
click on SERVICE & SUPPORT at www.homestandbygeneratorsystems.com, which provides a list of authorized dealers.
For Future Reference
Please fill out the information below and keep with your receipt to assist in unit identification for future purchase issues.
important instructions that should be followed during
installation and maintenance of the generator and batteries.
Safety Symbols and Meanings
Explosion
Toxic Fumes
Lift Hazard
Fire
Rotating Parts
Read Manual
Electrical Shock
Hot Surface
Chemical BurnExplosive PressureAuto Start
The manufacturer cannot possibly anticipate every possible
circumstance that might involve a hazard. The warnings
in this manual, and the tags and decals affixed to the unit
are, therefore, not all-inclusive. If you use a procedure, work
method or operating technique that the manufacturer does
not specifically recommend, you must satisfy yourself that it
is safe for you and others. You must also make sure that the
procedure, work method or operating technique that you
choose does not render the generator system unsafe.
WARNING Running engine gives off carbon monoxide, an
odorless, colorless, poison gas.
Breathing carbon monoxide could result in death, serious
injury, headache, fatigue, dizziness, vomiting, confusion,
seizures, nausea or fainting.
• Operate this product ONLY outdoors in an area that will not
accumulate deadly exhaust gas.
• Keep exhaust gas away from any windows, doors, ventilation
intakes, soffit vents, crawl spaces, open garage doors or other
openings that can allow exhaust gas to enter inside or be drawn
into a potentially occupied building or structure.
• Carbon monoxide detector(s) MUST be installed and maintained
indoors according to the manufacturer’s instructions/
recommendations. Smoke alarms cannot detect carbon
monoxide gas.
The safety alert symbol indicates a potential personal
injury hazard. A signal word (DANGER, WARNING, or
CAUTION) is used with the alert symbol to designate a degree
or level of hazard seriousness. A safety symbol may be used
to represent the type of hazard. The signal word NOTICE is
used to address practices not related to personal injury.
DANGER indicates a hazard which, if not avoided, will
result in death or serious injury.
WARNING indicates a hazard which, if not avoided, could
result in death or serious injury.
CAUTION indicates a hazard which, if not avoided, could
result in minor or moderate injury.
NOTICE addresses practices not related to personal injury.
4
WARNING The engine exhaust from this product contains
chemicals known to the State of California to cause cancer, birth
defects, or other reproductive harm.
WARNING Certain components in this product and related
accessories contain chemicals known to the State of California
to cause cancer, birth defects, or other reproductive harm. Wash
hands after handling.
Page 5
WARNING Storage batteries give off explosive hydrogen gas
NOT
for
REPRODUCTION
during recharging.
Slightest spark will ignite hydrogen and
cause explosion, resulting in death, serious
injury and/or property damage.
Battery electrolyte fluid contains acid and is extremely caustic.
Contact with battery contents could cause severe chemical burns.
A battery presents a risk of electrical shock and high short
circuit current.
• DO NOT dispose of battery in a fire. Recycle battery.
• DO NOT allow any open flame, spark, heat, or lit cigarette during
and for several minutes after charging a battery.
WARNING Propane and Natural Gas are extremely flammable
and explosive, which could cause burns, fire or
explosion resulting in death, serious injury and/or
property damage.
• Install the fuel supply system according to NFPA 37 and other
applicable fuel-gas codes.
• Before placing the generator into service, the fuel system lines
must be properly purged and leak tested.
• After the generator is installed, you should inspect the fuel
system periodically.
• NO leakage is permitted.
• DO NOT operate engine if smell of fuel is present or other
explosive conditions exist.
• DO NOT smoke around the generator. Wipe up any oil spills
immediately. Ensure that no combustible materials are left in the
generator compartment. Keep the area near the generator clean
and free of debris.
WARNING Hazardous Voltage - Contact with power lines could
cause electric shock or burn, resulting in death or
serious injury.
Lifting Hazard / Heavy Object - Could result in
serious injury.
• If lifting or hoisting equipment is used, DO NOT contact any
power lines.
• DO NOT lift or move generator without assistance.
• Use lifting pipes as described in Lifting the Generator.
• DO NOT lift unit by roof as damage to generator will occur.
WARNING Generator produces hazardous voltage.
Failure to properly ground generator could result
in electrocution.
Failure to isolate generator from utility power could result
in death or serious injury to electric utility workers due to
backfeed of electrical energy.
• DO NOT touch bare wires or bare receptacles.
• DO NOT use generator with electrical cords which are worn,
frayed, bare or otherwise damaged.
• DO NOT handle generator or electrical cords while standing in
water, while barefoot, or while hands or feet are wet.
• If you must work around a unit while it is operating, stand on an
insulated dry surface to reduce the risk of a shock hazard.
• DO NOT allow unqualified persons or children to operate or
service generator.
• In case of an accident caused by electrical shock, immediately
shut down the source of electrical power and contact the local
authorities. Avoid direct contact with the victim.
• Despite the safe design of the residential generator, operating
this equipment imprudently, neglecting its maintenance or being
careless could cause possible injury or death.
• Remain alert at all times while working on this equipment.
Never work on the equipment when you are physically or
mentally fatigued.
• Before performing any maintenance on the generator, disconnect
the battery cable indicated by a NEGATIVE, NEG or (-) first. When
finished, reconnect that cable last.
• After your system is installed, the generator may crank and start
without warning any time there is a power failure. To prevent
possible injury, always set the generator’s system switch to OFF,
remove the service disconnect from the disconnect box AND
remove the 15 Amp fuse BEFORE working on the equipment.
5
Page 6
WARNING
NOT
for
REPRODUCTION
• DO NOT touch hot parts and AVOID hot exhaust gases.
• Allow equipment to cool before touching.
• Exhaust outlet side of weatherproof enclosure must have
at least 5 ft. (1.5 m) minimum clearance from any structure,
shurbs, trees or any kind of vegetation.
• Standby generator weatherproof enclosure must be at least
5 ft. (1.5 m) from windows, doors, any wall opening, shrubs
or vegetation over 12 inches (30.5 cm) in height.
• Standby generator weatherproof enclosure must have
a minimum of 5 ft. (1.5 m) overhead clearance from any
structure, overhang or trees.
• DO NOT place weatherproof enclosure under a deck or
other type of structure that may confine airflow.
• Use only flexible steel fuel line provided. Connect provided
fuel line to generator, DO NOT use with or substitute any
other flexible fuel line.
• Smoke detector(s) MUST be installed and maintained
indoors according to the manufacturer’s instructions/
recommendations. Carbon monoxide alarms cannot detect
smoke.
• Keep at least minimum distances shown in General
Location Guidelines to insure for proper generator cooling
and maintenance clearances.
• It is a violation of California Public Resource Code, Section
4442, to use or operate the engine on any forest-covered,
brush-covered, or grass-covered land unless the exhaust
system is equipped with a spark arrester, as defined in
Section 4442, maintained in effective working order. Other
states or federal jurisdictions may have similar laws.
Contact Briggs and Stratton, retailer, or dealer to obtain a
spark arrester designed for the exhaust system installed on
this engine.
• Replacement parts must be the same and installed in the
same position as the original parts.
WARNING Starter and other rotating parts could entangle
hands, hair, clothing, or accessories resulting in
serious injury.
Exhaust heat/gases could ignite combustibles
or structures resulting in death, serious injury
and/or property damage. Contact with muffler
area could cause burns resulting in serious
injury.
CAUTION Installing the 15A fuse could cause the engine
to start at any time without warning resulting in minor or
moderate injury.
• Observe that the 15 Amp fuse has been removed from the control
panel for shipping.
• DO NOT install this fuse until all plumbing and wiring has been
completed and inspected.
CAUTION Excessively high operating speeds could result in
minor injury and/or equipment damage.
Excessively low speeds impose a heavy load on generator.
• DO NOT tamper with governed speed. Generator supplies correct
rated frequency and voltage when running at governed speed.
• DO NOT modify generator in any way.
NOTICE Improper treatment of generator could damage it and
shorten its life.
• Use generator only for intended uses.
• If you have questions about intended use, contact your
authorized dealer.
• Operate generator only on level surfaces.
• Adequate, unobstructed flow of cooling and ventilating air is
critical for correct generator operation.
• The access panels/door must be installed whenever the unit
is running.
• DO NOT expose generator to excessive moisture, dust, dirt, or
corrosive vapors.
• Remain alert at all times while working on this equipment.
Never work on the equipment when you are physically or
mentally fatigued.
• DO NOT start engine with air cleaner or air cleaner cover removed.
• DO NOT insert any objects through cooling slots.
• DO NOT use the generator or any of its parts as a step. Stepping
on the unit could cause stress and break parts. This may result in
dangerous operating conditions from leaking exhaust gases, fuel
leakage, oil leakage, etc.
• If connected devices overheat , turn them off and disconnect them
from generator.
• Shut off generator and contanct an authorized deaker if:
-electrical output is lost;
-equipment sparks, smokes, or emits flames;
-unit vibrates excessively;
-unit makes unusual noises.
• NEVER operate generator without protective housings, covers, or
guards in place.
• DO NOT wear loose clothing, jewelry or anything that could be
caught in the starter or other rotating parts.
• Tie up long hair and remove jewelry.
• Before servicing, remove 15 Amp fuse from control panel and
disconnect Negative (NEG or -) battery cable.
6
Page 7
Installation
NOT
for
REPRODUCTION
This product is only for use as an optional generator system
which provides an alternate source of electric power and
to serve loads such as heating, refrigeration systems, and
communication systems that, when stopped during any
power outage, could cause discomfort or inconvenience.
NOTICE This product does NOT qualify for either an
emergency standby or legally required standby system as
defined by NFPA 70 (NEC).
• Emergency generator systems are intended to
automatically supply illumination, power, or both,
to designated areas and equipment in the event of
failure of the normal supply. Emergency systems may
also provide power for such functions as ventilation
where essential to maintain life, where current
interruption of the normal supply would produce
serious life safety or health hazards.
• Legally Required standby generator systems are
intended to automatically supply power to selected
loads in the event of failure of the normal source
which could create hazards or hamper rescue or firefighting operations.
Every effort has been made to ensure that information in this
manual is accurate and current. However, we reserve the
right to change, alter, or otherwise improve the product and
this document at any time without prior notice.
Only current licensed electrical and plumbing professionals
should attempt home generator system installations.
Installations must strictly comply with all applicable codes,
industry standards, laws and regulations.
Home Owner Responsibilities
• Read and follow the instructions given in the
operator’s manual.
• Follow a regular schedule in maintaining, caring for
and using your home generator, as specified in the
operator’s manual.
Installing Dealer/Contractor Responsibilities
• Read and observe the safety rules.
• Install only an UL approved transfer switch that is
compatible with the generator.
• Read and follow the instructions given in this
installation and start-up manual.
• Carbon monoxide detector(s) MUST be installed and
maintained indoors according to the manufacturer’s
instructions/ recommendations. Smoke alarms
cannot detect carbon monoxide gas.
• Smoke detector(s) MUST be installed and maintained
indoors according to the manufacturer’s instructions/
recommendations. Carbon monoxide alarms cannot
detect smoke.
• Installation must strictly comply with all applicable
codes, industry standards, laws, and regulations.
• Allow sufficient room on all sides of the generator for
maintenance and servicing.
7
Page 8
Cold Weather Kit
NOT
for
REPRODUCTION
If operating the generator below 30°F (-1°C), it is HIGHLY
RECOMMENDED that a Model 6231 Cold Weather Kit
(includes oil warmers and battery warmer) be installed.
These items are available at your local servicing dealer.
For cold weather areas (below 0°F (-18°C)) it is also
recommended that a BCI, Size 75, wet lead-acid battery be
used of 630 CCA minimum.
If you need more information on this matter, please call
(888) 575-8226, between 8:00 AM and 5:00 PM CT.
Unpacking Precautions
Avoid damage from dropping, bumping, collision, etc. Store
and unpack carton with the proper side up, as noted on the
shipping carton.
Delivery Inspection
30°F (-1°C)
After removing the carton, carefully inspect the generator for
any damage that may have occurred during shipment.
If loss or damage is noted at time of delivery, have the
person(s) making delivery note all damage on the freight bill
and affix his signature under the consignor’s memo of loss or
damage. If loss or damage is noted after delivery, separate
the damaged materials and contact the carrier for claim
procedures. Parts damaged in shipping are not warranted.
Shipment Contents
The home generator system is supplied with:
• Oil (5W30 Synthetic)
• Flexible steel fuel line
• Installation and start-up manual
• Operator’s manual
• Spare access roof keys
• Spare 15 Amp ATO-type fuse
• Remote wireless monitor
• Antenna
Not included:
• Carbon monoxide detector(s)
• Smoke detector(s)
• Starting battery
• Connecting wire and conduit
• Fuel supply valves/plumbing
• Crane, lifting straps, chains or cables
• Two 60” lengths of 3/4” nominal minimum scheduled
40 steel pipe (NOT conduit)
• Torque screwdriver, 5 to 50 inch-pound range
• Voltage/frequency meter
• Two (2) AA batteries for remote wireless monitor
8
Page 9
Installation Checklist - GE Home Generator Systems
NOT
for
REPRODUCTION
Proper installation of the home generator requires the completion of the following tasks:
Carbon Monoxide (CO) Detector/ Smoke Detector
Carbon Monoxide (CO) detector(s) installed and in working
order.
Smoke detector(s) installed and in working order.
Placement
Required permits have been obtained.
Generator placed in an area free from Carbon Monoxide
(CO) buildup. See Placement of Standby Generator to
Reduce the Risk of Carbon Monoxide Poisoning.
Generator placed in an area compliant to NFPA 37. See
Placement of Standby Generator to Reduce the Risk of
Fire.
Generator placed in an area free from water damage. See
Other General Location Guidelines.
Generator placed in an area free from utility and other
home systems. See Other General Location Guidelines.
Generator placed in a debris free zone. See Other General
Location Guidelines.
Generator placed on flat ground with provisions for water
drainage.See Other General Location Guidelines.
Fuel
Generator is connected to fuel source with steel flexible
fuel line, has no fuel leaks and conforms to local codes. See
The Gaseous Fuel System.
Proper fuel pressure has been measured with all gas
appliances operating. See The Gaseous Fuel System.
Fuel system has been configured for the proper fuel
supply: Natural gas (NG) or liquefied petroleum ( LP). See
Fuel pressure at fuel inlet port with generator on and at
full load and all gas appliances turned on and operating
____________________.
Electrical
Generator neutral is connected to Automatic Transfer
Switch. See Generator AC Connection System.
Generator is grounded. See Grounding the Generator and
NFPA 70,NEC.
Generator is connected to the transfer switch with the
specified wiring. See Utility Circuit Connection and
Transfer Switch Communication.
Generator is connected to the transfer switch with the
specified wiring. #18AWG twisted pair wiring from the
generator control panel to the transfer switch is installed
in a separate conduit from high voltage wires unless
the insulation rating on all wiring is rated for 600V See
Transfer Switch Communication.
Dipswitches in most transfer switches must be set to
correspond to the wattage of the generator. See Transfer
Switch Operator/Installation Manual.
Operation
Cold weather kit is installed in temperatures below 40°F
(5°C). See Cold Weather Kit.
Correct battery type is installed and fully charged. See
Final Installation Considerations.
Generator engine oil level is at full mark. See Final
Installation Considerations.
Circuit breaker is in the ON position.
Utility was shut off to test the operation of generator and
transfer switch. Note any fault codes and make corrections
as required.
Before installing the generator, consult with the homeowner
and convey the following requirements, which must be
satisfied before the installation is complete.
There are two equally important safety concerns in regards
to carbon monoxide poisoning and fire. There are also
several general location guidelines that must all be met
before the installation is considered complete.
Exhaust Side of the Generator
WARNING Running engine gives off carbon monoxide, an
odorless, colorless, poison gas.
Breathing carbon monoxide could result in death, serious
injury, headache, fatigue, dizziness, vomiting, confusion,
seizures, nausea or fainting.
• Operate this product ONLY outdoors in an area that will not
accumulate deadly exhaust gas.
• Keep exhaust gas away from any windows, doors, ventilation
intakes, soffit vents, crawl spaces, open garage doors or other
openings that can allow exhaust gas to enter inside or be drawn
into a potentially occupied building or structure.
• Carbon monoxide detector(s) MUST be installed and maintained
indoors according to the manufacturer’s instructions/
recommendations. Smoke alarms cannot detect carbon
monoxide gas.
ABB
Exhaust outlet side of weatherproof enclosure.
A
Air inlet side of weatherproof enclosure.
B
11
Page 12
Placement of Standby Generator to
NOT
for
REPRODUCTION
REDUCE THE RISK OF CARBON MONOXIDE POISONING
The arrows in the figure below point to POTENTIAL points of entry for Carbon Monoxide Gas.
All fossil fuel burning equipment, such as standby
generators, contains carbon monoxide (CO) gas in the engine
exhaust. CO gas is odorless, colorless and tasteless and is
unlikely to be noticed until a person is overcome. CO gas can
kill you so it is required that the following is included as part
of the installation:
• Install generator outdoors in an area that will not
accumulate deadly exhaust gas.
• DO NOT install generator where exhaust gas could
accumulate and enter inside or be drawn into a
potentially occupied building or structure.
• By law it is required in many states to have a Carbon
Monoxide (CO) detector in operating condition in
your home. Carbon monoxide detector(s)
be installed and maintained indoors according to
the manufacturer’s instructions/ recommendations.
A CO monitor is an electronic device that detects
hazardous levels of CO. When there is a buildup of
CO, the monitor will alert the occupants by flashing
visual indicator light and alarm. Smoke alarms cannot
detect CO gas.
• Your neighbor(s) home may be exposed to the engine
exhaust from your standby generator and must be
considered when installing your standby generator.
A
MUST
• Ensure exhaust gas is kept away from:
windows
B
doors
C
ventilation intakes
D
E
soffit vents
F
garage doors
G
crawl spaces or other openings that can allow
exhaust gas to enter inside or be drawn into a
potentially occupied building or structure.
A
12
Page 13
• Direct the standby generator exhaust away from or
NOT
for
REPRODUCTION
parallel to the building or structure. DO NOT direct the
generator exhaust towards a potentially occupied
building, structure, windows, doors, ventilation intakes,
soffit vents, crawl spaces, open garage doors or other
openings where exhaust gas could accumulate and
enter inside or be drawn into a potentially occupied
building or structure.
• DO NOT place standby generator in any area where
leaves or debris normally accumulates. Position
standby generator in an area where winds will carry
the exhaust gas away from any potentially occupied
building or structure.
STANDBY
GENERATOR
ENGINE
EXHAUST
13
Page 14
Placement of Standby Generator to REDUCE THE RISK OF FIRE
NOT
for
REPRODUCTION
The National Fire Protection Association (NFPA) standard
NFPA 37 establishes criteria for minimizing the hazard
of fire during the installation and operation of stationary
combustion engines. NFPA 37 limits the spacing of an
enclosed generator from openings in walls, structures and
combustible materials outside the enclosure.
The placement requirements provided are based on
compliance to NFPA 37 2010 section 4.1.4 and a full-scale
demonstration fire test. Details of compliance testing can be
found in section National Fire Protection Association (NFPA)
standard NFPA 37 requirements and testing.
WARNING
• Exhaust outlet side of weatherproof enclosure must have at least
5 ft. (1.5 m) minimum clearance from any structure, shrubs, trees
or any kind of vegetation.
• Standby generator weatherproof enclosure must be at least
5 ft. (1.5 m) from windows, doors, any wall opening, shrubs or
vegetation over 12 inches (30.5 cm) in height.
• Standby generator weatherproof enclosure must have a minimum
of 5 ft. (1.5 m) overhead clearance from any structure, overhang
or trees.
• DO NOT place weatherproof enclosure under a deck or other type
of structure that may confine airflow.
• Use only flexible steel fuel line provided. Connect provided fuel line
to generator, DO NOT use with or substitute any other flexible fuel
line.
• Smoke detector(s) MUST be installed and maintained indoors
according to the manufacturer’s instructions/recommendations.
Carbon monoxide alarms cannot detect smoke.
• DO NOT place weatherproof enclosure in manner other than
shown in illustrations.
Exhaust heat/gases could ignite combustibles
or structures resulting in death, serious injury and/or
property damage.
Examples of standby generator locations to reduce the
risk of fire:
Legend for Generator Locations to reduce the risk of fire.
Standby weatherproof enclosure must be at least 5 ft
A
(1.5 m) from windows, doors, any wall opening, shrubs
or vegetation over 12 inches (30.5 cm) in height.
Exhaust outlet side of weatherproof enclosure must
B
have at least 5 ft (1.5 m) minimum clearance from any
structure, shrubs, trees or any kind of vegetation.
Standby weatherproof enclosure must have a
C
minimum of 5 feet (1.5 m) overhead clearance from
any structure, overhang or trees.
Standby Weatherproof enclosure must have a
D
minimum of 18 inches (45.7 cm) clearance from any
structures with or without a fire rating.
NOTICE DO NOT place weatherproof enclosure under a deck
or other type of covered structure that may confine airflow.
Vertical Clearances
B
Exhaust
Direction
Structure
C
5 ft (1.5 m)
5 ft (1.5 m)
Standby
14
Center of Exhaust Panel
Page 15
NOTICE The gures below show the minimum installation distances allowed to structures and items in the legend.
NOT
for
REPRODUCTION
Generator Installations
AA
DD
A
5 ft (1.5 m) min
Exhaust
Direction
B
5 ft (1.5 m)
18 in (45.7 cm) min
Standby
DD
A
18 in (45.7 cm) min
5 ft
(1.5 m)
18 in (45.7 cm) min
Standby
Exhaust
Direction
B
5 ft (1.5 m) min
A
5 ft (1.5 m) min
D
Standby
Exhaust
Direction
5 ft
(1.5 m)
A
Standby weatherproof enclosure must be at least 5 ft
A
(1.5 m) from windows, doors, any wall opening, shrubs
or vegetation over 12 inches (30.5 cm) in height.
Exhaust outlet side of weatherproof enclosure must
B
have at least 5 ft (1.5 m) minimum clearance from any
structure, shrubs, trees or any kind of vegetation.
Standby weatherproof enclosure must have a
C
minimum of 5 feet (1.5 m) overhead clearance from
any structure, overhang or trees.
NOTICE DO NOT place weatherproof enclosure under a deck
or other type of covered structure that may confine airflow.
B
D
5 ft (1.5 m)
A
Standby Weatherproof enclosure must have a
D
minimum of 18 inches (45.7 cm) clearance from any
structures with or without a fire rating.
Standby
Exhaust
Direction
B
15
Page 16
Other General Location Guidelines
NOT
for
REPRODUCTION
• Place the standby generator in a prepared location
that is flat and has provisions for water drainage.
• Install the standby generator in a location where
sump pump discharge, rain gutter down spouts, roof
run-off, landscape irrigation, or water sprinklers will
not flood the unit or spray the enclosure and enter
any air inlet or outlet openings.
• Install the standby generator where it will not affect or
obstruct any services (including covered, concealed
and underground), such as telephone, electric, fuel
(natural gas / LPG vapor), irrigation, air conditioning,
cable, septic, sewer, well and so forth.
• Install the standby generator where leaves, grass,
snow, etc will not obstruct air inlet and outlet
openings. If prevailing winds will cause blowing or
drifting, you may need to construct a windbreak to
protect the unit.
National Fire Protection Association (NFPA) Standard NFPA 37 Requirements and Testing
Requirements:
NFPA 37 2010, section 4. 1. 4, Engines Located Outdoors.
Engines, and their weatherproof housings if provided, that
are installed outdoors shall be located at least 1.5m (5 ft)
from openings in walls and at least 1.5 m (5 ft) from structures
having combustible walls. A minimum separation shall not be
required where either of the following conditions exist:
1. The adjacent wall of the structure has a fire resistance
rating of at least 1 hour.
2. The weatherproof enclosure is constructed
of noncombustible materials and it has been
demonstrated that a fire within the enclosure will not
ignite combustible materials outside the enclosure. *
To comply with condition 2, the weatherproof enclosure has
been constructed completely of non-combustible materials
and full-scale fire tests have been conducted to demonstrate
that a fire within the enclosure will not ignite combustible
materials outside the enclosure.
Annex A Explanatory Material
A.4.1.4 (2) Means of demonstrating compliance are by means
of full-scale fire tests or by calculation procedures, such as
those given in NFPA 555, Guide on Methods for Evaluating
Potential for Room Flashover.
16
Page 17
Electrical and Fuel Inlet Locations
NOT
for
REPRODUCTION
The 3/4 inch N.P.T. fuel inlet connector
location B is shown below.
A ½ inch knock-out is provided for the electrical inlet. This
inlet may be enlarged or supplemented to accommodate
a maximum conduit size of 1 ½ inches. Ensure that the
installed conduit(s) enter the unit in the zone shown in the
drawing such that they properly enter the electrical box and
do not interfere with the fully opened roof.
A
and electrical inlet
The home generator is supplied with a base that, unless
mandated by local code, does not require a concrete slab.
B
A
17
Page 18
Lifting the Generator
NOT
for
REPRODUCTION
The generator weighs more than 500 pounds (227 kg). Proper
tools, equipment and qualified personnel should be used in
all phases of handling and moving the generator.
WARNING Hazardous Voltage - Contact with power lines could
cause electric shock or burn, resulting in death or
serious injury.
Lifting Hazard / Heavy Object - Could result in
serious injury.
• If lifting or hoisting equipment is used, DO NOT contact any
power lines.
• DO NOT lift or move generator without assistance.
• Use lifting pipes as described in Lifting the Generator.
• DO NOT lift unit by roof as damage to generator will occur.
Two 60” lengths of 3/4” nominal minimum scheduled 40
steel pipe
generator manually. Insert pipes through the lifting holes B
located near the unit’s base.
You may also lift the unit using a “hook and hoist” method
attached to the lifting pipes, provided that you use a
spreader bar to ensure that the chains or cables DO NOT
touch the generator’s roof.
A
, supplied by the installer, are required to lift the
A
B
Concrete Anchoring of Unit
In areas determined to be hurricane prone, it is
recommended to anchor the standby generator to concrete.
The concrete anchors must be rated to hold 800 lbs ( kg).
There are four 7/16 inch hole locations around the base
of generator in which to anchor the unit.
NOTICE Unless mandated by local or state code, a concrete
slab is not required.
C
18
C
C
C
C
Page 19
Access Panels
NOT
for
REPRODUCTION
The generator is equipped with an enclosure that has several
access panels, as shown.
The access panels and the components located behind them
are listed below:
A - Roof (Control Panel, air filter, oil dipstick, and circuit
A
breaker)
B - Front Access Panel (oil drain and oil filter)
B
D - Battery Panel (battery and generator data label)
C
E - Rear Access Panel (fuel regulator, fuel selector, and
D
engine starter)
E
F - Control Panel Cover (field wiring and control wires)
Each generator is shipped with a set of identical keys. These
keys fit in the lock on the front removable panel. The roof
must be unlocked in order for it to open.
A
B
D
E
C
B
19
Page 20
To open roof:
NOT
for
REPRODUCTION
1. Insert key into lock of front panel. Gently push
down on roof above the lock to aid in turning the key.
Turn key one quarter turn clockwise.
2. Lift roof to the open position.
To remove front panel:
1. Remove the two bolts that secure the panel to the
unit.
2. Lift panel to remove from unit.
To secure front panel:
1. Place panel in unit.
2. Secure the panel with two bolts.
A
A
B
B
To remove rear panel:
1. Ensure the roof is in the open position.
2. Remove the two bolts that secure the panel to the
unit.
3. Lift panel to remove from unit.
To secure rear panel:
1. Slide panel into place on unit.
2. Secure the panel with two bolts.
C
C
To remove battery panel:
1. Ensure the roof is in the open position.
2. Remove the two bolts that secure the panel to the
unit.
3. Lift up on panel and remove.
To secure battery panel:
1. Place panel in unit.
2. Secure the panel with two bolts.
D
D
20
Page 21
The Gaseous Fuel System
NOT
for
REPRODUCTION
The information below is provided to assist gaseous
fuel system technicians in planning installations. In no
way should this information be interpreted to override
applicable fuel gas codes. Consult with your local fuel
supplier or Fire Marshall if questions or problems arise.
WARNING Propane and Natural Gas are extremely flammable
and explosive, which could cause burns, fire or
explosion resulting in death, serious injury and/or
property damage.
• LP gas is heavier than air and will settle in low areas.
• Natural gas is lighter than air and will collect in high areas.
• The slightest spark could ignite these fuels and cause an explosion.
• DO NOT light a cigarette or smoke.
TO THE INSTALLER: Consult with the generator owner(s) and
convey any technical considerations that might affect their
installation plans before applying these general guidelines.
The following general rules apply to gaseous fuel
system piping:
WARNING Propane and Natural Gas are extremely flammable
and explosive, which could cause burns, fire or
explosion resulting in death, serious injury and/or
property damage.
• Before placing the generator into service, the fuel system lines
must be properly purged and leak tested.
• No leakage is permitted.
NOTICE The supplied flexible
underground or in contact with the ground.
• The entire
periodic inspection and must not be concealed within
nor contact nor run through any wall, floor, or partition.
• The piping should be of a material that conforms
to federal and local codes, rigidly mounted and
protected against vibration.
• Piping should be protected from physical damage
where it passes through flower beds, shrub beds, and
other cultivated areas where damage could occur.
NOTICE The illustration is representative of a typical
installation. Your installation may differ.
• Install the
the generator fuel inlet port A and rigid piping
to prevent thermal expansion, contraction, or any
standby movement from causing excessive stress on
the piping material.
flexible
flexible
steel fuel line
steel fuel line must be visible for
steel fuel line B (supplied) between
is not to be installed
D
C
E
F
• A union
downstream to permit removal of standby.
• A manometer port should be provided
manometer, P/N 19495, is available at your Briggs &
Stratton service center. When the initial test runs are
completed, the manometer is removed and the port
is plugged. The manometer port permits temporary
installation of a manometer to ensure that the
engine receives the correct fuel pressure to operate
efficiently throughout its operating range.
• Where the formation of hydrates or ice is known to
occur, piping should be protected against freezing. The
termination of hard piping should include a sediment
trap
• A minimum of one accessible, approved manual
shutoff valve shall be installed in the fuel supply
line within 6 ft. (180 cm) of the home generator.
• A manual fuel shut-off valve should be installed in the
interior of the building.
• Where local conditions include earthquake,
tornado, unstable ground, or flood hazards, special
consideration shall be given to increase strength and
flexibility of piping supports and connections.
• Piping must be of the correct size to maintain the
required supply pressures and volume flow under
varying generator load conditions with all gas
appliances connected to the fuel system turned on
and operating.
• Use a pipe sealant or joint compound approved for
use with NG/LPG on all threaded fittings to reduce the
possibility of leakage.
• Installed piping must be properly purged and
leak tested, in accordance with applicable codes
and standards.
C
or flanged connection shall be provided
where condensate is not likely to freeze.
F
E
A
D
. A digital
B
21
Page 22
Fuel Factors
NOT
for
REPRODUCTION
An important consideration affecting the entire installation
is the type of fuel used by your generator. The system was
factory tested and adjusted using natural gas, but can
be converted to use LP vapor. For proper engine function,
factors that are inherent to each of these fuels, your
location and the duration of possible utility interruptions are
important considerations in the following fuel guidelines:
• Use clean, dry fuel, free of moisture or any
particulate material. Using fuels outside the
following recommended values may cause
performance problems.
• In engines set up to run on propane (LP), commercial
grade HD5 propane with a minimum fuel energy of
2500 BTUs/ft3 with maximum propylene content of
5% and butane and heavier gas content of 2.5% and
minimum propane content of 90% is required.
Natural gas rating will depend on specific fuel but typical
derates are between 10 to 20% off the LP gas rating.
Natural gas or LP engines are certified to operate on natural
or liquid propane gas. The emissions control system for this
engine is EM (Engine Modifications).
WARNING Propane and Natural Gas are extremely flammable
and explosive, which could cause burns, fire or
explosion resulting in death, serious injury and/or
property damage.
• The residential generator is equipped with an automatic safety
gas “fuel shut-off” valve.
• DO NOT operate the equipment if the “fuel shut-off” valve is
missing or inoperative.
Fuel Pressure
Both LP vapor and natural gas fuel supply pressure at the
generator’s fuel inlet port should be between the following levels
at full load with all gas appliances turned on and operating.
• NG is 5-7” W.C.
• LP is 11-14” W.C.
Ensure that all gas line shutoff valves are OPEN and that
adequate fuel pressure is available whenever automatic
operation is desired.
Power Loss
Air density is less at high altitudes, resulting in less available
engine power. Specifically, engine power will decrease 3.5%
for each 1,000 feet (300 m) above sea level and 1% for
each 10° F (5.6°C) above 77°F (25°C). Generators located in
these conditions must have their transfer switch adjusted
appropriately for this power decrease. See Automatic
Transfer Switch manual on how to adjust for the power
decrease.
Fuel Pipe Sizing
There are numerous on-line or otherwise-published
references for fuel pipe sizing. For example, NFPA 54 National Fuel Gas Code, 2006 (Item #: 320-6031-06) is a
common resource.
The installer should consider the specific gravity of gas
and compensate for a nominal amount of restriction from
bends, fittings, etc. If an unusual number of fittings, bends, or
other restrictions are used, refer to federal and local codes
for guidance.
22
Page 23
Fuel Conversion
NOT
for
REPRODUCTION
The engine of your generator system is factory calibrated to
run on natural gas (NG) or on liquefied petroleum (LP) vapor.
To convert to either fuel, follow these steps:
NOTICE Units are set to NG at the factory.
1. Insert key into lock of front panel. Gently push down
on roof above the lock to aid in turning the key. Turn
key one quarter turn clockwise.
2. Lift roof to the open position.
3. Press the control board OFF button.
4. Remove 15 Amp fuse from control panel.
5. Remove the rear panel.
6. Locate the fuel selector switch (A). located on top of
the fuel regulator (B.Using a 5 mm Allen wrench,
turn the selector switch to either LP or NG.
7. Reinstall the rear panel.
8. Reinstall 15 Amp fuse in control panel.
9. Press the control board AUTO button.
B
A
A
B
23
Page 24
Fuel Consumption
NOT
for
REPRODUCTION
Estimated fuel supply requirements at half and full load for
natural gas and LP vapor fuels are shown here.
LP Vapor (Propane)
Full Load
3/4 Load
1/2 Load
1/4 Load
Exercise
Gal/Hr (liquid)3.753.283.03
Gal/Hr (liquid)3.032.752.5
Gal/Hr (liquid)2.312.061.89
Gal/Hr (liquid)1.561.51.42
Gal/Hr (liquid)1.111.111.11
Natural Gas
20kW17kW15kW
Cu Ft/Hr135118109
BTU/Hr337500295000272500
Cu Ft/Hr1099990
BTU/Hr272500247500225000
Cu Ft/Hr837468
BTU/Hr207500185000170000
Cu Ft/Hr565451
BTU/Hr140000135000127500
Cu Ft/Hr404040
BTU/Hr100000100000100000
Recommended Energy
Content of Fuel:
Heating Value:
BTU per gallon liquid
(gross*)
BTU per Cubic feet
(vapor)
Natural GasPropane
(LP Vapor)
N/A
1,000
91,547
2,500
Full Load
3/4 Load
1/2 Load
1/4 Load
Exercise
Cu Ft/ Hr260248240
BTU / Hr260000248000240000
Cu Ft/ Hr240218210
BTU / Hr240000218000210000
Cu Ft/ Hr187170156
BTU / Hr187000170000156000
Cu Ft/ Hr135128119
BTU / Hr135000128000119000
Cu Ft/ Hr999999
BTU / Hr990009900099000
20 kW
(18 kW)
17 kW
(14.4 kW)
15kW
(13.5 kW)
24
Page 25
System Connectors
NOT
for
REPRODUCTION
Low Voltage connections to signal fault contacts, transfer switch communication and auxiliary 12VDC power are made via a
field connection terminal block in control board area. Compare this illustration with your generator to familiarize yourself with
the location of these connections.
A
UTILITY A
NEUTRAL
GROUND
LINE 1
LINE 2
]
]
]
]
G
F
E
UTILITY B
NO
COMM
]
]
NC
TxRx
TxRx GND
+LED
]
]
GND
N/C
]
]
B
C
D
A
- Two Pin Terminal Block — Used to connect utility
240 VAC from fuse block in ATS to the control board.
Connect only one wire per terminal.
B
- Fault Contacts — Use NO, COM and NC to hook up a
siren, light, etc. to alert you in case of a fault. Contacts
reverse state (NO goes to NC and vice versa) upon a
fault condition.
C
– Transfer Switch Communication (TxRx and TxRx
GND) — Connect to transfer switch control board for
communication interface using 18AWG twisted pair
wire.
• For power output connection (Line 1, Line 2, Neutral, and Ground), refer to the following table:
15 kW17 kW20 kW
Power output connections
minimum 300V, 75°C
• Reference NEC 2011 table 310.15 (B) (16) • Use National Electric Code for correction factors and wire size calculations.
• For utility circuit connection (Utility A and Utility B) use #14 AWG minimum 300 volt wire.
• For transfer switch communication use #18 AWG twisted pair conductors, no greater than 200 ft in length, 300 volt wire.
• When connecting to the terminal block, fasten only one wire to each connector screw.
• Torque terminal block screws to 4.4 in-lb (0.49 Newton meter).
• Torque circuit breaker connections to 45 in-lb (5 Newton meter).
– +LED and GND Connection — Not required for wireless
monitor included with unit. Available for optional
hardwired remote system status panel accessory,
#6154.
E
- Eight Pin Terminal Block — Used to connect signal
wires to the control board. Connect only one wire per
terminal.
F
- Power Connection (Line 1 and Line 2) — Power
connection to transfer switch.
G
- Neutral and Ground Connection — Connect to transfer
switch neutral and ground
25
Page 26
Generator AC Connection System
33
NOT
for
REPRODUCTION
A single-phase, three-wire AC connection system is used in
the home generator. The stator assembly consists of a pair
of stationary windings with two leads brought out of each
winding. The junction of leads 22 and 33 forms the neutral
lead, as shown schematically and as a wiring diagram. A
complete schematic and wiring diagram can be found later
in this manual.
NOTICE
Neutral is not bonded to ground at generator.
NOTICE Generator must be used with only an UL approved
transfer switch that is compatible with the generator.
Neutral
22
120V
Power Winding
120V
Circuit
Breaker
11
240V
44
From Alternator Power Windings
1122440
Grounding the Generator
The home generator must be installed as part of a system
that includes a listed transfer switch, with neutral to
ground bonding at the transfer switch in accordance
with installation instructions. Unless mandated by local
code, additional grounding to earth at the generator is
not required. Any grounding at generator must use metal
piercing lock washers (or equal), UL listed terminals installed
per terminal supplier’s instructions, and comply with national
electrical codes and local requirements.
ound
Neutral
Line 2Gr
To Transfer Switch
Circuit
Breaker
Line 1
26
Page 27
Power Connections from Generator to Transfer Switch
NOT
for
REPRODUCTION
Utility Circuit Connection
“240V Utility” leads must be routed in conduit. The “240V
Utility” leads deliver power to the generator’s circuit board,
optional battery warmer and optional oil warmer. This power
also charges the battery. When power on these leads is lost,
the generator will start.
Generator Power Connection
Using installer supplied minimum 300V wires and the table
located on page 25, connect generator power output Line 1,
Line 2, neutral and ground to the corresponding Line 1, Line
2, neutral and ground in the transfer switch.
*Use National Electric Code for correction factors and wire
size calculations.
Transfer Switch Communication
Using installer supplied #18 AWG twisted pair conductors, no
greater than 200 ft in length, connect Tx Rx and Tx Rx GND
from the generator terminal block
transfer switch control board B.
A
to T/R and GND on the
Using installer-supplied minimum 300V, 14 AWG wire,
connect each control circuit terminal in the generator
(Utility A and Utility B) to the fuse block in the automatic
transfer switch.
Reference illustration on page 26 for further information.
When making connections, obey wire type and torque
specifications printed on the circuit breaker and neutral/
ground connectors.
A
B
27
Page 28
System Control Board
NOT
for
REPRODUCTION
The generator control board, located inside the generator,
under the roof, is shown below. Brief descriptions of the
controls used during installation are:
A
- Menu/Programming Navigation Buttons — See Menu
section for details
B
- Mini USB Port — Authorized Dealer Service Use Only
C
- Generator Operation Control Buttons —
•“AUTO” Normal operating position. Press and hold
button to put unit into Automatic mode. If an utility
power outage is sensed, the system will start the
generator. When utility power is restored, auto lets the
engine stabilize internal temperatures, shuts o the
generator, and waits for the next utility outage.
•“OFF” Turns o running generator, prevents unit from
starting, and resets any detected faults.
OFF must be pressed and held for more than 5 seconds in
order to reset service codes.
•“MANUAL” Used to manually start the generator.
- “AUTO” LED — LED will light when unit is placed into
*
Auto mode. LED will blink if exercise cycle is not set or
set to OFF.
D
– 15 Amp Fuse — Protects the home generator DC
control circuits. If the fuse has ‘blown’ (melted open)
or was removed, the engine cannot crank or start.
Replace the fuse using only an identical ATO 15A fuse.
One spare fuse is supplied with the unit.
E
- Cover — This protective cover must be opened to
access the fuse and the USB port.
F
- Digital Display — Displays generator mode, menu
options, service codes, and service engine indicators
More information may be found in Controls in the
operator’s manual.
A
B
C
auto
F
menu
ok
esc
E
D
offmanual
28
*
Page 29
Menu
ok
ok
ok
ok
ok
ok
ok
ok
ok
ok
ok
ok
NOT
for
REPRODUCTION
The following chart shows the icons for the buttons that control the system control panel.
ok
MENU
ESCAPE (EXIT)
RIGHT ARROW
LEFT ARROW
MANUAL MODE
OFF
AUTOMATIC MODE
ENTER THE MENU (VIEW SETTINGS)
PRESS TO CONFIRM SELECTION WHEN PROGRAMMING.
RETURN TO LAST MENU ITEM
TOGGLE THROUGH MENU OPTIONS
SETTING SYSTEM PARAMETERS
TOGGLE THROUGH MENU OPTIONS
SETTING SYSTEM PARAMETERS
USED TO MANUALLY START THE GENERATOR. PRESS AND HOLD BUTTON TO START
THE GENERATOR.
TURNS OFF RUNNING GENERATOR, PREVENTS UNIT FROM STARTING, AND RESETS
ANY DETECTED FAULTS.
NORMAL OPERATING POSITION. PRESS AND HOLD BUTTON TO PUT UNIT INTO
AUTOMATIC MODE. IF A UTILITY POWER OUTAGE IS SENSED, THE
SYSTEM WILL START THE GENERATOR. WHEN UTILITY POWER IS RESTORED, AUTO
LETS THE ENGINE STABILIZE INTERNAL TEMPERATURES, SHUTS OFF THE GENERATOR, AND WAITS FOR THE NEXT UTILITY POWER OUTAGE.
The following chart describes key sequences for accessing different programming modes;
ok
GENERAL
SET-UP
ADVANCED
SETTINGS
WIRELESS
LINK MODE
PRESS AND HOLD [ARROW LEFT AND ARROW RIGHT] FOR
THREE SECONDS TO ENTER THE PROGRAM MODE.
PRESS AND HOLD [ARROW LEFT, ARROW RIGHT AND ESC] FOR
THREE SECONDS TO ENTER THE ADVANCED SETTINGS MODE.
PRESS AND HOLD [MENU AND ESC] FOR THREE SECONDS TO
ENTER THE WIRELESS LINKING MODE.
29
Page 30
General Set Up Screen
ok
ok
ok
NOT
for
REPRODUCTION
For general set up, press and hold the left arrow and right arrow for 3 seconds. Follow the prompts as outlined below.
NOTE: Date and Time were set at the factory and stored in the control panel memory. The Exercise Cycle was
also set at the factory. The default exercise cycle occurs on Tuesdays, at 2:00 P.M. Central Standard Time.
To updated or change these settings, follow the steps below.
SET DATE
or
SET TIME
or
ok
ok
or
YEAR
FLASHING
oror
HOURS
FLASHING
oror
OFF
ok
ok
If set to OFF, display will read: EXERCISE CYCLE OFF
MONTH
FLASHING
MIN
FLASHING
okok
okok
DAY##
FLASHING
or
AM/PM
FLASHING
or
ok
or
SET EXERCISE
CYCLE
EVENT
LOG
30
ok
ok
DAY OF WEEK
FLASHING
or
ok
HOURS
FLASHING
or
ok
Display will scroll last service code event, date, time, and
temperature of when the event occured.
MIN
FLASHING
or
ok
AM/PM
FLASHING
or
ok
or
ok
Page 31
Control Panel Prompts
AUTOMATIC MODE
GENERATOR ON
(When Generator Running - Auto Mode)
GENERATOR READY or SERVICE CODE DESCRIPTION
(When Generator NOT Running - Auto Mode)
NOT
for
REPRODUCTION
Automatic Mode
In Automatic Mode, the display screen will display via
scrolling text:
• GENERATOR READY - if the unit is in standby and utility
power is present.
• GENERATOR ON - if the unit is running and utility
power is not present.
• SERVICE CODE - if a system fault has been detected.
General System Parameters
To view general system parameters, press the MENU button.
The following will scroll across the digital display and then
move to the next item:
• Run time
• Date
• Time
• Exercise Cycle date and start time
The user can press the LEFT ARROW or RIGHT ARROW at any
time to move to the next item.
The user can press ESCAPE to go back to GENERATOR READY.
If no user inputs are made for 10 seconds after all the items
have been displayed, the control board will reset to
GENERATOR READY.
AUTOMATIC MODE
GENERATOR READY or SERVICE CODE DESCRIPTION
(When Generator NOT Running - Auto Mode)
GENERATOR ON
(When Generator Running - Auto Mode)
ok
(MENU)
RUN TIME
or
DATE
or
TIME
or
EXERCISE CYCLE
31
Page 32
Advanced Settings Screen
ok
ok
ok
ok
ok
ok
ok
ok
NOT
for
REPRODUCTION
Advanced setting parameters are preset at the factory for a typical installation. To view Advanced Settings items and/or to
change items, follow the instructions listed below.
NOTICE Advanced settings are critical to the operation of the unit. Careful consideration should be taken when working
in the Advanced Settings menu. Exercise caution when selecting and verifying parameters for the generator and region
where the generator is being operated. Confirm all settings before operating the generator for the first time.
For advanced menu items, press and hold the left arrow, right arrow, and escape key for 3 seconds. Follow the
prompts as outlined below.
NOTICE In the Advanced Setting menu, a three button access code (left arrow, right arrow, and escape key must
be pressed once to enter the menu and again to change any setting. After each confirmation of a setting, the selection will
display solid for 2 seconds before moving to the next program item.
kW
or
Hz
or
PHASE
or
kW
FLASHING
or
50/60 Hz
FLASHING
or
SINGLE
or
THREE
FLASHING
or
ok
ok
ok
VOLTS
or
E-Governor
Check
32
or
SOFTWARE
Version Displayed
VOLTS
FLASHING
or
Stepper Motor
will sweep through throttle
range for dealer
visual verification
ok
or
ok
Page 33
Service Code Detection System
NOT
for
REPRODUCTION
The generator may have to run for long periods of time with
no operator present. For that reason, the system is equipped
with sensors that automatically shut down the generator
Final Installation Considerations
Engine Oil
NOTICE Any attempt to crank or start the engine before it has
been properly serviced with the recommended oil will result in
possible equipment failure and service codes.
• Refer to Maintenance in the operator’s manual for oil fill
information.
• Damage to equipment resulting from failure to follow this
instruction will void engine and generator warranty.
This engine is shipped from the factory pre-run and filled
with synthetic oil (API SJ/CF 5W-30). This allows for system
operation in a wide range of temperature and climate
conditions. Before starting the engine, check oil level as
described in Maintenance of the Operator’s Manual.
The use of synthetic oil does not alter the required oil change
intervals described in the Operator’s Manual.
For operation of temperatures below 30°F (-1°C), the use
of fully synthetic oil (minimum API SJ) of viscosity 5W30 is
required.
in the event of potentially damaging conditions, such as
low oil pressure, high temperature, over speed, and other
conditions. Refer to Service Code Detection System in the
operator’s manual for more detailed information.
Battery
The installer must supply and install a rechargeable 12 volt
starting battery. The starting battery MUST conform to the
specifications shown in this chart.
Battery Specifications
SpecificationsStandardCold Start
(less than 30°)
Volts
Amps (MIN)
Construction
Terminal Type
Dimensions (MAX):
Install the battery as described in Servicing the Battery in the
Maintenance section of the operator’s manual. Always make
sure the NEGATIVE cable is connected last and that the red
POSITIVE terminal insulator is fully in place.
12 Volt DC12 Volt DC
540 CCA (cold
cranking amps)
Wet lead acidWet lead acid
Top post type battery Top post type battery
BCI size 26BCI size 75
630 CCA (cold
cranking amps)
WARNING Battery posts, terminals and related accessories
contain lead and lead compounds, chemicals known to the State
of California to cause cancer and reproductive harm. Wash hands
after handling.
WARNING Storage batteries give off explosive hydrogen gas
during recharging.
Slightest spark will ignite hydrogen and
cause explosion, resulting in death, serious
injury and/or property damage.
Battery electrolyte fluid contains acid and is extremely caustic.
Contact with battery contents could cause severe chemical burns.
A battery presents a risk of electrical shock and high short
circuit current.
• DO NOT dispose of battery in a fire. Recycle battery.
• DO NOT allow any open flame, spark, heat, or lit cigarette during
and for several minutes after charging a battery.
The unit has been set-up for NG operation at the factory.
Fuel conversion, if needed, must be completed prior to
performing these steps. See Fuel Conversion.
Before operating the home generator or placing it into
service, inspect the entire installation carefully. Then begin
testing the system without any electrical loads connected,
as follows:
1. Remove three screws
cover to enclosure to expose unit’s circuit breaker.
A
2. Connect an accurate frequency meter to line side of
generator’s main circuit breaker.
3. Set generator’s main circuit breaker to ON
(closed) position.
4. Install 15 Amp fuse in control board.
A
that secure control box
A
A
5. Press and hold MANUAL button on control board for 3
seconds. Engine will start.
When the generator is started for the very first time, it will
require that air in the gaseous fuel lines be purged. This may
cause the engine to run roughly for a few minutes.
6. Listen for unusual noises, vibration or other
indications of abnormal operation. Check for oil leaks
while engine runs.
7. Let engine warm up for about 5 minutes to allow
internal temperatures to stabilize.
8. Check generator output at load side of circuit breaker.
Voltage should be 225 - 250 Volts, frequency should
be 59.0 - 61.0 Hz.
9. Check generator output between one generator
connection lug and neutral lug, then between
other generator connection lug and neutral lug.
In both cases, voltage reading should be between
112 and 125 Volts.
10. Push and hold OFF BUTTON on control board until
engine stops.
11. Reinstall control box cover.
CAUTION Installing the 15A fuse could cause the engine
to start at any time without warning resulting in minor or
moderate injury.
• Observe that the 15 Amp fuse has been removed from the control
panel for shipping.
• DO NOT install this fuse until all plumbing and wiring has been
completed and inspected.
34
Page 35
Electronic Governor System
NOT
for
REPRODUCTION
The engine electronic governor system allows for improved
control and increased generator performance compared
to mechanically governed systems. The result is smooth
steady-state operation without the "hunting" common to
many mechanical governors. The system also reduces
speed variations under engine loading and unloading and
signicantly reduces frequency uctuation experienced
when the engine is under higher loads.
The electronic governor system is composed of a stepper
motor (B) , stepper motor throttle control linkages (C) ,
and throttle side linkage (A) . The control board contains a
digital controller that processes engine speed information
and sends appropriate commands to the stepper motor to
control the position of the engine throttle.
Since the electronic governing system controls the engine
throttle demand based upon generator load, the following
service codes and/or conditions may be related to an
electronic governing system issue:
• Engine Does Not Start
• Over Speed
• Under Frequency
• Unstable No Load Engine Control
BC
A
A
While trouble shooting any of these conditions, a verication
of the electronic governor system can be initiated through
the control panel – advanced menu options – Electronic
Governor Check.
Electronic Governing Check:
The generator has an electronic governing check feature
that will turn on the stepper motor and move the throttle
linkage clockwise and counterclockwise within the throttle
limits. The test will rotate the stepper motor and move the
throttle arm between the wide open throttle and dead idle
limits 4 times with a 2 second delay between each throttle
sweep. This will allow visual verication that the stepper
motor is functioning properly and the control linkages are
connected. The engine will not attempt to start during this
test. If the stepper motor does not move, or if a linkage binds,
then service may be required.
NOTICE If stepper motor does not move, please make sure
the stepper motor connector is attached.
BC
35
Page 36
Operation
NOT
for
REPRODUCTION
Automatic Operation Sequence
The generator’s control board constantly monitors utility
voltage. Should utility voltage drop below a preset level, the
control board will signal the engine to crank and start.
When utility voltage is restored above a preset voltage level,
the engine is signaled to shut down.
The actual system operation is not adjustable and is
sequenced by sensors and timers on the control board,
as follows:
Utility Voltage Dropout Sensor
• This sensor monitors utility source voltage.
• If utility source voltage drops below about 70 percent
of the nominal supply voltage, the sensor energizes
a 3 second timer. The timer is used to ‘sense’
brown-outs.
• Once the timer has expired, the engine will crank
and start.
Setting Exercise Timer
Utility Voltage Pickup Sensor
This sensor monitors utility power voltage. When utility
voltage is restored above 80 percent of the nominal source
voltage, a time delay starts timing and the engine will go to
engine cool-down.
Engine Cool-down Timer
When utility power is sensed and the load transfers to the
utility source, the engine will go into a cool down period as
described below:
• If the generator has run for MORE than 5 minutes,
once the utility transfer occurs, the engine will
continue to run for about 1 minute before shutting
down.
• If the generator has run for LESS than 5 minutes, once
the utility transfer occurs, the engine will continue to
run until 5 minutes has elapsed before shutting down.
The generator is equipped with an exercise timer. During the
exercise period, the unit runs for approximately 20 minutes
and then shuts down. Electrical load transfer DOES NOT
occur during the exercise cycle (unless an utility power
outage occurs).
The generator will only enter the exercise cycle if the unit
is in the AUTO mode and this exact procedure is followed.
To set the exercise timer:
NOTICE The generator is set with a default exercise cycle
setting of Tuesday at 2:00 P.M, Central Time. To change the
cycle setting, proceed to the following steps:
1. Choose the day and time you want your generator to
exercise.
2. Press and hold the left arrow and right arrow
simultaneously for 3 seconds to enter the General
Set-Up program mode. See General Set-Up flow chart
in Menu Section.
3. Verify and/or set the time and date on the unit.
4. Go to the SET EXERCISE prompt and hit the “OK”
button.
NOTICE Items will flash until they are selected.
SELECT DAY: Use the left or right arrow to toggle
through the days of the week, Once the day is
selected, hit the “OK” button.
SELECT HOUR: Use the left or right arrow to toggle
through between 1 and 12. Choose the hour of day
you want the generator to exercise then hit the “OK”
button.
SELECT MINUTE: Use the left of right arrow to toggle
between :00 and :59. Choose the minute of the day
you want the generator to exercise then hit the “OK”
button.
SELECT AM/PM: Use the left of right arrow to toggle
between AM and PM. Once chosen, hit the “OK”
button.
NOTICE During the weekly exercise cycle, the generator will
run for 20 minutes, but it will not supply power to the home.
During the exercise cycle, the in-home monitor will continue
blinking the GENERATOR READY green LED.
If you want to change the day and time the unit exercises,
simply perform the procedure again.
To turn off the generator exercise cycle, go to the OFF
selection within the day of the week menu and press OK. The
display will then scroll: EXERCISE CYCLE OFF.
36
Page 37
Antenna Installation
NOT
for
REPRODUCTION
The supplied antenna must be installed before the wireless
monitor will operate.
1. Insert key into lock of front panel. Gently push down
on roof above the lock to aid in turning the key. Turn
key one quarter turn clockwise.
2. Lift roof to the open position.
3. Carefully push out the plug (A) located on the inside of
the roof.
A
A
5. Route antenna wire (D) from the top side of the roof,
through the hole in the roof where the plug was
removed.
6. Replace flange nut on wire. Ensure the wire is routed
through the washer end.
D
D
4. Unscrew flange nut (B) from antenna post and
remove from antenna wire.
B
B
7. Secure antenna to roof with the flange nut.
8. Locate wire connector (C) coming from control panel
and connect to the wire coming from antenna.
9. Route wire and secure with supplied cable ties (E) .
10. Close and open the roof to ensure the antenna wire
experiences no chaffing or pulling.
C
E
E
E
C
37
Page 38
Wireless Monitor
DEALER NAME
DEALER
PHONE
generator power
service needed
generator ready
system update
1 low battery voltage
2 low uid level
3 under/over voltage
4 engine does not start
part #: 316196 fcc id: MCQ-XBS2C IC id: 1846A-XBS2C
5 low frequency
6 engine overspeed
7 high temperature
8 transfer switch
# of flashes service needed
NOT
for
REPRODUCTION
The generator is supplied with a battery-powered, wireless
monitor.
The monitor communicates wirelessly with the generator
control panel. The monitor may be placed in a suitable
location in the home. The system has a line-of-sight range of
about 200 feet, but this distance will decrease if the signal
has to pass through walls or other objects.
The wireless monitor communicates with the generator,
every 10 minutes and will display the status via LED lights on
the front of the monitor.
Compare the illustration below with your monitor to
familiarize yourself with these important components.
• Generator Ready (A) - Green LED
• Generator Power (B) - Green LED
• Service Needed (C) - Red LED
• System Update (D) - Press for current system update
with generator.
• Service code descriptions (E) - Name and number
of flashes are listed on the backside of the wireless
monitor.
• Battery Access Cover ( F) - Record the dealer
name and phone number on the label provided.
Once opened, two AA batteries are installed in the
compartment (G)..
A
B
C
D
E
F
G
A
B
C
D
E
G
F
38
Page 39
Wireless Monitor Operation
1 low battery voltage2 low uid level
3 under/over voltage
5 low frequency6 engine overspeed
7 high temperature
# of flashes service needed
1 low battery voltage2 low uid level3 under/over voltage4 engine does not start
part#: 316196 fcc id: MCQ-XBS2C IC id: 1846A-XBS2C
5 low frequency6 engine overspeed7 high temperature8 transfer switch
# of flashes service needed
NOT
for
REPRODUCTION
1. Remove battery access cover (A) on back of monitor
A
and install 2 AA batteries. (Observe correct battery
polarity which is embossed in the bottom of the
battery compartment). Replace battery access cover.
vice needed
4 engine does not start
part #: 316196 fcc id: MCQ-XBS2C IC id: 1846A-XBS2C
e
8 transfer switch
4. “LINKING MODE” will scroll across the generator
control panel.
5. Locate and hold the SYSTEM UPDATE button (C) on
C
the wireless monitor for 5 seconds. All 3 LEDs will flash
until the monitor links to the generator. Once it links,
the monitor will display the current state. The monitor
will try to link for 1 minute. (This step can only be
completed when the generator is in Linking Mode).
DEALERNAME
DEALER
PHONE
A
NOTICE The wireless monitor was linked to the generator at
the factory. Communication will begin upon the installation
of the batteries and the generator being placed in AUTO
mode. You may need to press System Update one time.
2. The wireless monitor does not have an on/off
switch. When batteries are installed correctly,
the GENERATOR READY green LED light will flash
once every 7 seconds indicating the status of the
generator.
NOTICE If communication does not begin upon placing the
generator in AUTO, installing batteries, and pressing System
Update, the monitor may need to be re-linked. To link, follow
Steps 3 through 6.
3. Locate the MENU AND ESCAPE buttons on the control
panel (B) . Press and hold for 3 seconds to enter the
B
linking mode.
generator ready
generator power
service needed
C
system update
6. Once the link has been confirmed, press the OK
button on the generator control panel to exit or the
control board will turn off linking after 5 minutes. The
generator will now communicate with the wireless
monitor.
NOTICE It may take up to 1 minute for the monitor to begin
displaying the generator status correctly.
B
B
auto
menu
ok
esc
offmanual
39
Page 40
Standard Operation:
NOT
for
REPRODUCTION
Wireless Monitor Status LED’s
• The wireless monitor receives data from the generator
every 10 minutes and displays the generator status
through 3 LED’s.
• Pressing the SYSTEM UPDATE button will provide
current generator status by flashing the status LED’s.
When pressed, all 3 LEDs will flash until the generator
status is received.
NOTICE Generator control panel must be in AUTO mode or
no communication with monitor will occur.
• In order to conserve power and to extend battery life,
the LED’s are not lit continuously; instead they are
briefly flashed as indicated below.
NOTICE During the weekly exercise cycle, the generator will
run for 20 minutes, but it will not supply power to the home.
During the exercise cycle, the monitor will continue blinking
the GENERATOR READY green LED.
• GENERATOR READY - When active, the green LED will
flash once every 7 seconds. The green LED indicates
that the generator is in AUTO mode and that it is
ready to run in the event of a loss of utility power.
• GENERATOR POWER - When active, the green LED will
flash every 7 seconds. The green LED indicates that
the generator is supplying power.
• SERVICE NEEDED - When active, the red LED will flash
in a sequence that corresponds to the service code.
For example, when Low Frequency scrolls across the
control board, the red LED will flash 5 times with a 3
second pause between series of blinks until it is reset
or the condition is corrected. When the red LED is lit,
contact your nearest authorized service dealer.
NOTICE None of the conditions on the display unit can be
cleared at the wireless monitor. All alerts must be cleared at
the generator control panel.
NOTICE Service conditions will only be displayed on the
basic monitor when the control board is placed in AUTO
mode.
Other:
LED Lighting Codes
• Batteries Inserted - GENERATOR READY LED will light
for 5 seconds.
• Wireless Communication Lost - SERVICE NEEDED LED
will flash 20 fast pulses, then pause for 5 seconds,
and repeat the sequence until the communication
has been restored.
NOTICE Communication lost issues can typically be resolved
by moving the wireless monitor closer, within the home, to
the standby generator.
• Linking Error or Not Linked - SERVICE NEEDED LED will
light for 4 seconds, pause for 4 seconds, and repeat
the sequence until a successful link is completed.
Installation Inspection
Before placing the generator system into service, inspect the
entire installation carefully, utilizing the Installation Checklist
on page 9.
This completes the installation and start-up instructions.
The operator’s manual provides full details on Operation,
Maintenance and Troubleshooting for this generator system.
40
Page 41
NOTES
NOT
for
REPRODUCTION
41
Page 42
NOTES
NOT
for
REPRODUCTION
42
Page 43
Schematic / Wiring Diagrams
NOT
for
REPRODUCTION
Schematic Diagram
43
Page 44
Wiring Diagram
NOT
for
REPRODUCTION
is a trademark of General Electric Company