Table 3-7 Preset Factory Relay Configurations and Functions .................................................................................75
Table 4-1 RTD Resistance vs. Temperature.............................................................................................................. 79
g
GE Power Management
1 INTRODUCTION
g
GE Power Management
1.1 Motor Protection Requirements
Three phase AC motors have become standard in modern industry. These motors are generally rugged and very
reliable when used within their rated limits. Newer motors, however, tend to be designed to run much closer to these
operational limits and thus, there is less margin available for any type of abnormal supply, load, or operating
conditions.
To fully protect these motors, a modern protective device is required. Accurate stator and rotor thermal modeling is
necessary to allow the motor to operate within its thermal limits and still give the maximum desired output. As well,
other features can be incorporated into a modern relay to fully protect the motor, the associated mechanical system,
and the motor operator from all types of faults or overloads.
Motor thermal limits can be exceeded due to increased current from mechanical overloads or supply unbalance.
Unbalance can greatly increase heating in the rotor because of the large negative sequence current components
present during even small voltage unbalances. A locked or stalled rotor can cause severe heating because of the
associated large currents drawn from the supply. Many motor starts over a short period of time can cause
overheating as well. Phase-to-phase and phase-to-ground faults can also cause damage to motors and hazards to
personnel. Bearing overheating, loss of load, and phase reversal can cause damage to the mechanical load being
driven by the motor.
The ideal motor protection relay should monitor the rotor and stator winding temperatures exactly and shut off the
motor when thermal limits are reached. This relay should have an exact knowledge of the temperature and proper
operating characteristics of the motor and should shut down the motor on the occurrence of any potentially
damaging or hazardous condition.
The Multilin Model 169 Motor Management Relay uses motor phase current readings combined with stator RTD
temperature readings to thermally model the motor being protected. In addition, the 169 takes into account the
heating effects of negative sequence currents in the rotor, and calculates the cooling times of the motor. The relay
also monitors the motor and mechanical load for faults and problems.
1.2 169 Relay Features
The Multilin Model 169 Motor Management Relay is a modern microcomputer-based product designed to provide
complete, accurate protection for industrial motors and their associated mechanical systems. The 169 offers a wide
range of protection, monitoring, and diagnostic features in a single, integrated package. All of the relay setpoints
may be programmed in the field using a simple 12 position keypad and 48 character alphanumeric display. A built-in
"HELP" function can instruct the user on the proper function of each of the programming keys and on the meaning of
each displayed message.
One 169 relay is required per motor. Phase and ground fault currents are monitored through current transformers so
that motors of any line voltage can be protected. The relay is used as a pilot device to cause a contactor or breaker
to open under fault conditions; that is, it does not carry the primary motor current.
The relay comes in two different models, thus allowing for choice of the most cost effective relay for each application.
The 169 Plus has the following features which the model 169 does not: custom curve selectability, motor statistical
records, speed switch input, differential relay input, two auxiliary output relays, two additional RTD inputs, single shot
emergency restart feature, an RS 422 communications port, unbalance input to thermal memory, start inhibit feature,
and spare input terminals.
The custom curve feature of the model 169 Plus gives the user additional flexibility. If one of the eight standard
overload curves is not suitable for the application under consideration, the user can enter his own breakpoints to
form a custom curve. This means that the 169 Plus can offer optimum motor protection in situations where other
relays cannot. Such applications include induced fan drives where the motor stator and rotor thermal capacities can
differ significantly.
An important feature of the Multilin 169 Plus relay, is its ability to "learn" individual motor parameters. The relay
actually adapts itself to each application by "learning" values of motor inrush current, negative sequence current K
factor, cooldown rates, and acceleration time. These values may be used to improve the 169's protective
capabilities (when enabled) and are continually updated. The model 169 learns inrush current only.
The 169 Plus calculates both positive and negative sequence currents. The equivalent motor heating current is
calculated based on the "learned" K factor. This, combined with RTD temperature readings by a motor thermal
modeling algorithm, gives the 169 Plus a complete thermal model of the motor being protected. Thus, the 169 Plus
will allow maximum motor power output while providing complete thermal protection.
1
1 INTRODUCTION
The 169 Plus relay provides a complete statistical record of the motor being protected. The total motor running
hours, the number of motor starts, and the total number of relay trips since the last commissioning are stored and
can be viewed on the display. As well, the number of short circuit, RTD, ground fault, unbalance, overload, start, and
rapid trips can be recalled by simple keypad commands. These values are stored along with all of the relay
setpoints in a non-volatile memory within the relay. Thus, even when control power is removed from the 169 Plus,
the statistical record and all relay setpoints will remain intact.
The 169 can provide one of various output signals for remote metering or programmable controller attachment.
Analog signals of motor current as a percentage of full load, hottest stator RTD temperature, percentage of phase
CT secondary current, or motor thermal capacity are available by simple field programming. A total of four output
relays are provided on the 169 Plus, including a latched trip relay, an alarm relay, and two auxiliary relays. The
model 169 provides a latched trip relay and an alarm relay. All output relays may be programmed via the keypad to
trip on specific types of faults or overloads.
When an output relay becomes active, the 169 will display the cause of the trip, and if applicable, the lock-out time
remaining. Pre-trip values of motor current, unbalance, ground fault current, and maximum stator RTD temperature
are stored by the 169 and may be recalled using the keypad.
The correct operation of the Multilin 169 relay is continually checked by a built-in firmware self-test routine. If any
part of the relay malfunctions under this self-test, an alarm indication will tell the operator that service is required.
Table 1-1 Model 169 and 169 Plus Relay Features
Protection Features
Overloads
•
Stator Winding Overtemperature (Alarm and Trip)
•
Multiple Starts
•
Short Circuit
•
Locked Rotor
•
Rapid Trip/Mechanical Jam
•
Unbalance/Single Phasing
•
Ground Fault (Alarm and Trip)
•
Phase Reversal
•
Bearing Overtemperature (Alarm and Trip)
•
Undercurrent
•
Variable Lock-Out Time
•
g
GE Power Management
Operational Features
Microcomputer controlled
•
Keypad programmable
•
48 character alphanumeric display
•
Built-in "HELP" function
•
Eight selectable standard overload curves
•
User defined custom overload curve capability (169 Plus)
•
Continual relay circuitry self-check
•
Monitoring and Display Features
Negative sequence phase current unbalance measurement
•
Ground fault (earth leakage) current measurement
•
Up to six stator RTD inputs
•
Two additional RTD inputs on the model 169, four on the 169 Plus
•
Monitoring of motor ambient air temperature
•
Display of all SETPOINTS or ACTUAL VALUES upon request
•
Display of relay TRIP/ALARM and HELP messages
•
2
1 INTRODUCTION
Communications and Control Features
One latched, main trip relay
•
One alarm relay
•
Emergency restart capability
•
Pre-trip alarm warnings
•
4-20mA output of motor current as a percentage of full load, motor thermal capacity, hottest stator RTD
•
temperature, or percentage of phase CT secondary current
Two auxiliary relays (169 Plus)
•
Optional single-shot restart on running overload trip (169 Plus)
•
Speed switch, differential relay, and spare input (169 Plus)
•
RS 422 port for connection to programmable controllers and computers (169 Plus)
•
Statistical and Memory Features
Recall of all pre-trip motor values
•
Tamperproof setpoints stored in non-volatile memory
•
Microcomputer "learns" motor inrush current, acceleration time
•
current heating K factor* (* 169 Plus only)
Complete record of motor statistical data: motor running hours, number of starts, number and type of relay trips
•
(169 Plus)
*
, cooldown rates*, and negative sequence
g
GE Power Management
1.3 Typical Applications
The many features of the 169 make it an ideal choice for a wide range of motor protection applications. Versatile
features and controls allow the relay to protect associated mechanical equipment as well as the motor. The 169
should be considered for the following and other typical uses:
1. Protection of motors and equipment from operator abuse.
2. Protection of personnel from shock hazards due to winding shorts or earth leakage current from moisture.
3. Protection of gears, pumps, fans, saw mills, cutters, and compressors from mechanical jam.
4. Indication of loss of suction for pumps or loss of air flow for fans using the undercurrent feature.
5. Protection of motor and load bearings from excessive heat buildup due to mechanical wear.
6. Protection of motors operated in environments with varying ambient temperatures.
7. Communication with programmable controllers and computers for integrated plant control.
8. Protection of high inertia, long acceleration drive systems using a custom overload curve.
9. Statistical record-keeping for effective maintenance programs.
10. Complete protection, allowing maximum motor utilization with minimum downtime, for all AC motors.
3
1 INTRODUCTION
g
1.4 Technical Specifications
Phase Current Inputs
conversion:calibrated RMS
range:0.05 to 12 × phase CT primary amps setpoint
full scale:12 × phase CT primary amps setpoint
accuracy:±0.5% of full scale (0.05 to 2 X phase CT primary amps setpoint)
±1.0% of full scale (over 2 X phase CT primary amps setpoint)
Ground Fault Current Input
conversion:calibrated RMS
range:0.1 to 1.0 X G/F CT primary amps setpoint (5 Amp secondary CT)
relay response time:within 3.5 sec. of motor start attempt
Differential Relay Input
relay response time:100 msec. maximum (contact closure to output relay activation)
4
1 INTRODUCTION
RTD Inputs
sensor types:10 Ω copper
100 Ω nickel
120 Ω nickel
100 Ω platinum (specified with order)
display accuracy:±2 C
trip/alarm setpoint range: 0 to 200°C
dead band:3°C
maximum lead resistance:25% of RTD 0°C resistance
Relay Contacts
type:form C
rated load:10 A @ 250 VAC / 10 A @ 30 VDC (resistive load)
7.5 A @ 250 VAC / 5 A @ 30 VDC (inductive load)
0.5 A @ 125 VDC (resistive load)
0.3 A @ 125 VDC (inductive load)
maximum operating voltage:380 VAC, 125 VDC
maximum operating current:10 Amps
minimum permissible load:5 VDC, 100 mA
NOTE: AC inductive load PF = 0.4
DC inductive load L/R = 7 msec.
g
GE Power Management
Analog Current Output (4-20 mA standard)
output:4-20 mA /0-20 mA /0-1 mA
maximum load resistance:300
maximum output (saturation):20.2 mA20.2 mA1.01 mA
accuracy:±1% of full scale reading
polarity:terminal 58 ("-") must be at ground potential (ie. output is not isolated)
Control Power
AC nominal:120 VAC, range: 90-150 VAC
240 VAC, range: 180-270 VAC
frequency:50/60 Hz
maximum power consumption:40 VA
DC nominal:24 VDC, range: 20-30 VDC
48 VDC, range: 30-55 VDC
125 VDC, range: 80-150 VDC
250 VDC, range: 160-300 VDC
maximum power consumption:30 W
Environment
operating temperature range:–10°C to +60°C
display operational range:0°C to +55°C
Ω
300
Ω
2000
Ω
5
1 INTRODUCTION
CT Burden Due to Connection of 169 Relay
phase CT: 1 amp or 5 amp input:less than 0.50 VA at rated load
ground fault CT: 5 amp input:less than 0.50 VA at rated load
2000:1 input:can be driven by GE Power Management 2000:1 CT
Running Hours Counter
accuracy:±1%
Note: It is recommended that all 169 relays be powered up at least once per year to avoid deterioration of
electrolytic capacitors in the power supply.
Due to updating technology, specifications may be improved without notice.
g
GE Power Management
6
2 INSTALLATION
g
GE Power Management
2.1 Physical Dimensions
The 169 relay is contained in a compact plastic and metal housing with the keypad, display, and all indicators located
on the front panel. The physical dimensions of the 169 unit are given in Figure 2-1.
Multilin also provides phase and ground fault CTs if required. Dimensions for these are shown in Figure 2-2. Note:
Dimensions of Figure 2-2 are for 100:5 to 1000:5 phase CT's, for the dimensions of 50:5 and 75:5 CT's, consult
factory.
Figure 2-1 Physical Dimensions
7
2 INSTALLATION
g
GE Power Management
Figure 2-2 CT Dimensions
8
2 INSTALLATION
g
GE Power Management
2.2 Mounting
The 169 should be positioned so that the display is visible and the front panel keypad is accessible. A cut-out is
made in the mounting panel and the unit is mounted as shown in Figure 2-3. Four washers and 10-32 X 3/8"
mounting screws are provided.
Although the 169 circuitry is internally shielded, to minimize noise pickup and interference the relay should be placed
away from high current conductors or sources of strong magnetic fields.
Connections to the relay are made through terminal blocks and CTs located on the rear of the unit.
Figure 2-3 Relay Mounting
9
2 INSTALLATION
g
GE Power Management
2.3 External Connections
The connections made to the 169 relay will vary depending on the programming of the unit. It is not necessary to
use all of the connections provided; a minimal configuration would include supply power, three phase current CT
inputs and the Trip relay contacts wired in series with the contactor control relay or circuit breaker shunt trip coil.
Connections to these and the other terminals outlined below will be explained in the following sections. Figures 2-4,
2-6, 2-7 show typical connections to the 169 relay.
NOTE: The rear of the 169 relay shows output relay contacts in their power down state. Figures 2-4, 2-6, 2-7 show
output relay contacts with power applied, no trips or alarms, Factory Configurations, i.e. TRIP - fail-safe, ALARM non-fail-safe, AUX.1 - non-fail-safe, AUX.2 - fail-safe). See Figure 2-5 for a complete list of all possible output relay
contact states. See page 62 for a description of the RELAY FAILSAFE CODE.
Table 2-1 169 External Connections
Inputs
Supply Power L, G, N
•
Phase CTs
•
Ground Fault CTs
•
6 Stator RTDs
•
2 additional RTDs on the 169, 4 on the 169 Plus
•
Emergency Restart keyswitch
•
External Reset pushbutton
•
Programming Access jumper or keyswitch
•
Speed Switch input on the 169 Plus
•
Differential Relay input on the 169 Plus
•
Spare Input on the 169 Plus
•
Outputs
2 Sets of Relay Contacts (NO/NC) on the 169, 4 on the 169 Plus
•
Programmable Analog Current Output Terminals
•
RS 422 Serial Communication Port on the 169 Plus
•
10
2 INSTALLATION
g
GE Power Management
Figure 2-4 Relay Wiring Diagram (AC control power)
11
2 INSTALLATION
g
GE Power Management
WARNING: In locations where system voltage disturbances cause voltage levels to dip below the range
specified in specifications (1.5), any relay contact programmed failsafe may change state. To avoid tripping
the motor in this case, trip relay contacts should be programmed non-failsafe.
Figure 2-5 Output Relay Contact States
12
2 INSTALLATION
g
GE Power Management
Figure 2-6 Relay Wiring Diagram (Two Phase CTs)
13
2 INSTALLATION
g
GE Power Management
Figure 2-7 Relay Wiring Diagram (DC Control Power)
14
2 INSTALLATION
g
GE Power Management
2.4 Control Power
Control power for the relay is nominally either 120/240 VAC at 50 Hz/60 Hz or either 24, 48, 125, or 250 VDC. The
AC voltage is selected by means of a slide switch on the power supply circuit board as shown in Figure 2-8. If an
alternative voltage is selected, ensure that the control power label on the back of the 169 Relay reflects the change.
This board is accessed by removing the perforated cover on the rear of the unit. The switch must be correctly set
before control power is applied to the 169. Maximum power consumption for the unit is 40 VA (AC version) or 30 W
(DC version).
The 169 will operate properly over a wide range of supply voltages typically found in industrial environments (see
control power specifications in section 1.5). When the supply voltage drops below the minimum, the output relays
will return to their power down states but all setpoints and statistical data will remain stored in the relay memory.
Motor lock-out time will be adhered to with or without control power applied.
Control power must be applied to the 169 relay, and the relay programmed, before the motor is energized. Power is
applied at terminals 41, 42, and 43 which is a terminal block having #6 screws.
NOTE: Chassis ground terminal 42 must be connected directly to the dedicated cubicle ground conductor to
prevent transients from damaging the 169/169 Plus resulting from changes in ground potential within the
cubicle.
Figure 2-8 AC Voltage Selection (120/240 VAC models only)
2.5 Phase CTs
One CT for each of the three motor phases is required to input a current into the relay proportional to the motor
phase current. The phase sequence must be as shown in Figures 2-4 and 2-7 in order for the phase reversal
function to operate properly. If two phase CTs are used as shown in Figure 2-6 the phase reversal function cannot
be used (see section 3.19). The CTs used can have either a 1 amp or 5 amp secondary and should be chosen so
that the motor full load current is between 50 and 95 percent of the rated CT primary amps. The CT ratio should
thus be of the form n:1 or n:5 where n is between 20 and 1500. The ratio of the CT used must be programmed into
the 169 (see section 3.7).
The CT connections to the relay are made between the ":1" and "COM" terminals for 1 amp CTs or between the ":5"
and "COM" terminals for CTs with a 5 amp secondary. The connections to the 169 internal phase CTs are made
directly via #10 screws.
AC VOLTAGE SELECTION SWITCH
A100 PC BOARD
15
2 INSTALLATION
g
GE Power Management
2.6 Ground Fault CT
All current carrying conductors must pass through a separate ground fault CT in order for the ground fault function to
operate correctly. If a safety ground is used it should pass outside the CT window.
The ground fault CT is connected to terminals 73 and 72 for 5 amp secondary CTs or to terminals 73 and 74 for
Multilin 2000:1 CTs. as shown in Figures 2-4, 2-6, 2-7. The polarity of the ground fault CT connection is not
important. It is recommended that the two CT leads be twisted together to minimize noise pickup. If a 2000:1 ground
fault CT is used, the secondary output will be a low level signal which allows for sensitive ground fault detection.
The zero sequence ground fault connection is recommended. If the residual ground fault method is used the 169
relay will not display ground fault current in direct primary amps.
The connections to the 169 internal ground fault CT are made directly via #10 screws.
2.7 Trip Relay Contacts
The main control relay or shunt trip coil of the motor starter or circuit breaker should be connected to the Trip relay
contacts of the 169. These contacts are available as normally open (NO), normally closed (NC), and can switch up
to 10 amps at either 250 VAC or 30 VDC with a resistive load. Silver cadmium oxide contacts are used because of
their ability to handle high inrush currents on inductive loads. Contact Multilin if these contacts are to be used for
carrying low currents since they are not recommended for use below 0.1 amps. Connection to the motor contactor
or breaker is shown in Figures 2-4, 2-6, 2-7.
The Trip output relay will remain latched after a trip. This means that once this relay has been activated it will remain
in the active state until the 169 is manually reset. The Trip relay contacts may be reset by pressing the RESET key
(see section 3.1) if motor conditions allow, or by using the Emergency Restart feature (see section 2.12). An
optional single shot restart can be selected on the 169 Plus to automatically reset the relay after a running
OVERLOAD TRIP. This feature is selected or defeated in page 5 of SETPOINTS mode.
The Trip relay may be programmed to be fail-safe or non-fail-safe. W hen in the fail-safe mode, relay activation or a
loss of power condition will cause the relay contacts to go to their power down state. Thus, in order to cause a trip
on loss of power to the 169, output relays should be programmed as fail-safe.
The Trip relay cannot be reset if a lock-out is in effect. Lock-out time will be adhered to regardless of whether control
power is present or not.
The Trip relay can be programmed to activate on any combination of the following trip conditions: overload, stator
RTD overtemperature, rapid trip, unbalance, ground fault, short circuit, RTD overtemperature, phase reversal,
acceleration time, number of starts per hour, single phase, speed switch closure on start, differential relay closure,
spare input closure, and start inhibit (see section 3.4 for factory preset configurations). Connections to the Trip relay
contacts are made via a terminal block which uses #6 screws.
NOTE: The rear of the 169 relay shows output relay contacts in their power down state. Figures 2-4, 2-6, 2-7
show output relay contacts with power applied, no trips or alarms, and Factory Configurations in effect (i.e.
TRIP - fail-safe, ALARM - non-fail-safe, AUX.1 - non-fail-safe, AUX.2 - fail-safe). See Figure 2-5 for a list of all
possible contact states.
2.8 Alarm Relay Contacts
These contacts are available as normally open (NO), normally closed (NC), with the same ratings as the Trip relay
but can only be programmed to activate when alarm setpoint levels are reached. (On a Draw-out version of 169,
only one set of alarm contacts is available and the user must specify normally open or normally closed when
ordering). Thus these contacts may be used to signal a low level fault condition prior to motor shut-down.
Conditions which can be programmed to activate the relay are alarm levels for the following functions: immediate
overload, unbalance, undercurrent, ground fault, stator RTD overtemperature, RTD overtemperature, broken RTD
sensor, spare input alarm, self-test alarm, and start inhibit (see section 3.4 for factory preset configurations). The
relay can be configured as latched or unlatched and fail-safe or non-fail-safe. Connections to the Alarm relay
contacts are made via a terminal block which uses #6 screws.
NOTE: The rear of the 169 relay shows output relay contacts in their power down state. Figures 2-4, 2-6, 2-7 show
output relay contacts with power applied, no trips or alarms, and Factory Configurations in effect (i.e. TRIP - fail-safe,
ALARM - non-fail-safe, AUX.1 - non-fail-safe, AUX.2 - fail-safe). See Figure 2-5 for a list of all possible contact
states.
16
2 INSTALLATION
g
GE Power Management
2.9 Auxiliary Relay #1 Contacts (169 Plus)
Auxiliary relay #1 is provided to give an extra set of NO/NC contacts which operate independently of the other relay
contacts. (On a Draw-out version of 169, only one set of Aux.1 contacts is available and the user must specify
normally open or normally closed when ordering). This auxiliary relay has the same ratings as the Trip relay.
Auxiliary relay #1 can be configured as latched or unlatched and fail-safe or non-fail-safe. The conditions that will
activate this relay can be any trip or alarm indications (see section 3.4 for factory preset configurations).
These contacts may be used for alarm purposes or to trip devices other than the motor contactor. For example, the
ground fault and short circuit functions may be directed to Auxiliary relay #1 to trip the main circuit breaker rather
than the motor starter.
Connections to the relay contacts are made via a terminal block which uses #6 screws.
NOTE: The rear of the 169 relay shows output relay contacts in their power down state. Figures 2-4, 2-6, 2-7
show output relay contacts with power applied, no trips or alarms, and Factory Configurations in effect (i.e.
TRIP - fail-safe, ALARM - non-fail-safe, AUX.1 - non-fail-safe, AUX.2 - fail-safe). See Figure 2-5 for a list of all
possible contact states.
2.10 Auxiliary Relay #2 Contacts (169 Plus)
This relay provides another set of NO/NC contacts with the same ratings as the other relays. (On a Draw-out version
of 169, only one set of Aux.2 contacts is available and the user must specify normally open or normally closed when
ordering). This relay is different from the others in the fact that it is permanently programmed as latched and failsafe.
This relay may be programmed to activate on any combination of alarm conditions (see section 3.4 for factory preset
configurations). The feature assignment programming is thus the same as for the Alarm relay.
Connections to the relay contacts are made via a terminal block which uses #6 screws.
NOTE: The rear of the 169 relay shows output relay contacts in their power down state. Figures 2-4, 2-6, 2-7
show output relay contacts with power applied, no trips or alarms, and Factory Configurations in effect (i.e.
TRIP - fail-safe, ALARM - non-fail-safe, AUX.1 - non-fail-safe, AUX.2 - fail-safe). See Figure 2-5 for a list of all
possible contact states.
2.11 RTD Sensor Connections
Up to six resistance temperature detectors (RTDs) may be used for motor stator temperature monitoring. The
remaining RTD inputs may be used for motor and load bearing, or other temperature monitoring functions. All RTDs
must be of the same type. RTD #8 (RTD #10 on the 169 Plus) may be used to monitor ambient air temperature.
This is done to enhance protection in environments where the ambient temperature varies considerably. Use of
stator RTDs will allow the 169 to "learn" the actual cooling times of the motor. W hen no stator RTDs are used the
169 will not learn the actual motor cooling times, but will rely on the user defined preset values. The number of
stator RTDs used together with RTD trip and alarm temperatures must be programmed into the 169 (see sections
3.16, 3.17). The RTD type to be used must be specified when ordering the 169 relay. If the type of RTD in use is to
be changed, the 169 must be returned to the factory.
Each RTD has four connections to the 169 relay as shown in Figures 2-4, 2-6, 2-7. Since the RTD indicates
temperature by the value of its resistance, it is necessary to compensate for the resistance of the connecting wires,
which is dependent on lead length and ambient temperature. The 169 uses a circuit to cancel this resistance and
read only the actual RTD resistance. Correct operation will occur providing all three wires are of the same length and
the lead resistance is not greater than 25% of the RTD 0 C resistance. This can be accomplished by using identical
lengths of the same type of wire. If 10 copper RTDs are to be used special care should be taken to keep the lead
resistance as low as possible.
If RTD #8 (RTD #10 on the 169 Plus) is to be used for ambient air temperature measurement the RTD should be
placed and mounted somewhere in the motor cooling air intake flow. The sensor should be in direct contact with the
cooling air but not with any surface that is at a temperature other than the cooling air. This RTD is selected for
ambient temperature use in page 5 of SETPOINTS mode.
If no RTD sensor is to be connected to any of the RTD terminals on the 169, the terminals may be left open.
If fewer than 6 stator RTDs are to be employed, they should be connected to the lowest numbered relay RTD
connections. For example, if 3 stator RTDs are to be used they should be connected to the terminals for RTD1,
17
2 INSTALLATION
RTD2, and RTD3 (terminals #1-12). Other RTDs should be connected to the terminals for RTD7-RTD10 (terminals
#13-28) as shown in Figure 2-4.
The connections are made via terminal blocks which can accommodate up to #12 AWG multi-strand wire.
Note: Shielded, three wire cable must be used in industrial environments to prevent noise pickup. Wherever
possible, the RTD leads should be kept close to grounded metal casings and avoid areas of high
electromagnetic or radio frequency fields. RTD leads should not run adjacent to, or in the same conduit as
high current carrying wires. It is recommended to use a three wire shielded cable of #18 AWG copper
conductors. The shield connection of the RTD should not be grounded at the sensor end as there is an
internal ground on the 169. This arrangement prevents noise pickup that would otherwise occur from
circulating currents due to differences in ground potentials on a doubly grounded shield.
g
GE Power Management
2.12 Emergency Restart Terminals
If it is desired to occasionally override relay trips or lock-outs and restart the motor, a normally open keyswitch
should be installed between terminals 54 and 55. Momentarily shorting these terminals together will cause the
thermal memory of the 169 to discharge to 0% (if RTD input to thermal memory is enabled, thermal memory can be
reduced to 0% by keeping terminals 54 and 55 shorted together for more than 11 seconds; see section 3.20). The
Emergency Restart terminals can thus be used to override an OVERLOAD TRIP. Shorting the Emergency Restart
terminals together will also decrement the relay's internal starts/hour counter by 1 and therefore allow the operator to
override a STARTS/HOUR TRIP.
Note: This option should be used only when an immediate restart after a lock-out trip is required for process
integrity or personnel safety. Discharging the thermal memory of the 169 gives the relay an unrealistic value
for the thermal capacity remaining in the motor and it is possible to thermally damage the motor by
restarting it. Thus, complete protection may be compromised in order to restart the motor using this feature.
A twisted pair of wires should be used. Connection to the 169 is made via a terminal block which can accommodate
up to #12 AWG multi-strand wire.
2.13 External Reset Terminals
An external reset switch, which operates similarly to the keypad RESET key (see section 3.1), can be connected to
terminals 56 and 57 for remote reset operation. The switch should have normally open contacts. Upon closure of
these contacts the relay will be reset. This external reset is normally equivalent to pressing the keypad RESET key
but a special reset feature can be selected on page 5 of setpoints mode, so that the keypad RESET key will not
cause Auxiliary relay #1 to be reset (see section 3.22). Keeping the External Reset terminals shorted together will
cause the 169 to be reset whenever motor conditions allow.
A twisted pair of wires should be used. Connection to the 169 is made via a terminal block which can accommodate
up to #12 AWG multi-strand wire.
2.14 Analog Output Terminals (Non-Isolated)
Terminals 58 and 59 of the 169 are available for an analog current output representing one of percentage of motor
thermal capacity used, motor current as a percentage of full load (i.e. 0-1 XFLC), hottest stator RTD temperature as
a percentage of 200 C or CT secondary current as a percentage of CT secondary amps rating. The choice of output
is selected in page 5 of SETPOINTS mode. This selection can be made or changed at any time without affecting the
protective features of the relay.
The output current range is standard at 4-20 mA. Contact Multilin if a different current range is required. 4 mA
output corresponds to a low scale reading (i.e. 0% thermal capacity used, 0 XFLC phase current, 0 C hottest stator
RTD temperature, or 0 A phase CT secondary current). 20 mA output current corresponds to a high scale reading
(i.e. 100% thermal capacity used, 1 XFLC or greater phase current, 200 C or greater hottest stator RTD temperature,
or either 1 A (or greater) or 5 A (or greater) phase CT secondary depending on the CT used).
This output is a current source suitable for connection to a remote meter, chart recorder, programmable controller, or
computer load. Current levels are not affected by the total lead and load resistance as long as it does not exceed
300 for the 4-20 mA range. For readings greater than 100% of full scale the output will saturate at 20.2 mA.
This analog output is not isolated. Terminal 58 is internally connected to system ground. Consequently the negative
terminal of the connected load device must be at ground potential.
18
2 INSTALLATION
A twisted pair of wires should be used. Connection to the 169 is made via a terminal block which can accommodate
up to #12 AWG multi-strand wire.
g
GE Power Management
2.15 Differential Relay Terminals (169 Plus)
Terminals 48 and 49 are provided for connection to a differential relay. This allows an external differential relay to be
connected to a 169 Plus relay. A contact closure between these terminals will cause an immediate activation of the
output relay assigned to the differential relay input function. After a DIFFERENTIAL INPUT TRIP terminals 48 and
49 must be open circuited in order to reset the relay.
If no differential relay is to be used terminals 48 and 49 should be left open.
A twisted pair of wires should be used. Connection to the 169 is made via a terminal block which can accommodate
up to #12 AWG multi-strand wire.
2.16 Speed Switch Terminals (169 Plus)
Terminals 50 and 51 are provided for connection to an external speed switch. This allows the 169 Plus relay to
utilize a speed device for locked rotor protection.
terminals 50 and 51 occurs within the "SPEED SWITCH TIME DELAY" (SETPOINTS, page 5) the output relay
assigned to the speed switch function will activate. This function must be enabled in order for operation to occur
(SETPOINTS, page 5). After a SPEED SWITCH TRIP terminals 50 and 51 must be open circuited in order to reset
the relay.
If no speed switch is to be used terminals 50 and 51 should be left open.
A twisted pair of wires should be used. Connection to the 169 is made via a terminal block which can accommodate
up to #12 AWG multi-strand wire.
During a motor start attempt
if no contact closure between
2.17 Programming Access Terminals
When a jumper wire is connected between ACCESS terminals 52 and 53 all setpoints and configurations can be
programmed using the keypad. Once programming is complete the jumper will normally be removed from these
terminals. When this is done all actual and setpoint values can still be accessed for viewing; however, if an attempt
is made to store a new setpoint value the message "ILLEGAL ACCESS" will appear on the display and the previous
setpoint will remain intact. In this way all of the programmed setpoints will remain secure and tamperproof.
Alternatively, these terminals can be wired to an external keyswitch to permit setpoint programming upon closure of
the switch.
A twisted pair of wires should be used for connection to an external switch. Connection to the 169 is made via a
terminal block which can accommodate up to #12 AWG multi-strand wire.
2.18 RS-422 Serial Communications Terminals (169 Plus)
Terminals 46 and 47 are provided for a digital serial communication link with other 169 Plus relays, computers, or
programmable controllers. Up to 20 169 Plus "SLAVES" can be connected to one "MASTER" (169 Plus or other
device) as shown in Figure 2-9. If devices other than 169 Plus relays are to be connected in the serial link a copy of
the "Multilin 169 Plus Relay Communication Protocol" will be required. This can be obtained by contacting Multilin.
Note that when using a device other than a 169 Plus to program a 169 Plus SLAVE, setpoints sent to the SLAVE
must be within the ranges listed in Table 3-3.
Each communication link must have only one MASTER. If the MASTER is a 169 Plus this relay cannot be used for
motor protection. Only relays programmed as SLAVEs can be used for motor protection. The MASTER should be
centrally located and can be used to view ACTUAL VALUES and SETPOINTS from each relay SLAVE. SETPOINTS
in each SLAVE can also be changed from the MASTER. In order to do this the MASTER relay must have its Access
terminals (52,53) shorted together.
Relays are programmed as MASTER or SLAVE using the last 2 setpoints of page 5 of SETPOINTS mode (see
section 3.4). Each SLAVE in the communication link must be programmed with a different SLAVE ADDRESS.
When a relay is programmed as a MASTER it will display all of the ACTUAL VALUES and SETPOINTS of the SLAVE
relay it is addressing. To view data from a different SLAVE the ADDRESSED SLAVE setpoint must be changed.
To avoid contention and improper reading of data ensure that the following conditions are met:
1. Each communication link has only one MASTER.
2. Each 169 Plus SLAVE in the link has a different SLAVE ADDRESS.
19
2 INSTALLATION
The wires joining relays in the communication link should be a twisted pair. These wires should be routed away from
high power AC lines and other sources of electrical noise. The total length of the communications link should not
exceed 4000 feet. When connecting units in a communication link each 169 Plus relay must have terminal 47
connected to terminal 47 of the next unit in the link, and terminal 46 connected to terminal 46.
As shown in Figure 2-9 the first and last devices in the link should have a terminating resistor placed across
terminals 46 and 47. The value of these resistors should match the characteristic impedance of the line wire being
used. A typical value is 50 , 1/4 watt.
Connection to the 169 is made via a terminal block which can accommodate up to #12 AWG multi-strand wire.
Note: The difference in potentials between serial master ground and the 169 Plus slave (terminal 42) must
not exceed 10 volts. If a large difference in ground potentials does exist, communication on the serial
communication link will not be possible. In addition damage to the 169 Plus may result.
g
GE Power Management
Figure 2-9 Serial Communication Link Wiring
2.19 Display Adjustment
Once the 169 relay has been installed and input power applied, the contrast of the LCD display may have to be
adjusted. This adjustment has been made at the factory for average lighting conditions and a standard viewing
angle but can be changed to optimize the display readability in different environments. To alter the display contrast
the trimpot on the rear of the unit marked "CONTRAST" must be adjusted with a small slotted screwdriver.
2.20 Front Panel Faceplate
The front panel faceplate is composed of a polycarbonate material that can be cleaned with isopropyl or denatured
alcohol, freon, naphtha, or mild soap and water.
2.21 Spare Input Terminals (169 Plus)
Terminals 44 and 45 are provided for an additional relay contact input. A contact closure between these terminals
will cause a "SPARE INPUT TRIP" and/or a "SPARE INPUT ALARM" after the appropriate time delay (page 5 of
SETPOINTS). These terminals must be open circuited in order to reset the relay after a SPARE INPUT TRIP or
ALARM.
A twisted pair of wires should be used. Connection to the 169 is made via a terminal block which can accommodate
up to #12 AWG multi-strand wire.
20
2 INSTALLATION
g
GE Power Management
2.22 169 Drawout Relay
The model 169 and 169 Plus relays are available in a drawout case option. The operation of the relay is the same
as described elsewhere in this manual except for the differences noted in this section. The physical dimensions of
the drawout relay are as shown in Figure 2-10. The relay should be mounted as shown in Figure 2-11.
The drawout 169 relay can be removed from service without causing motor shut-down. This can be useful for
replacing, calibrating, or testing units.
RELAY MOUNTING - Make cutout as shown and drill six 7/32" holes on mounting panel. Approximately 2-1/2"
should be clear at the top and bottom of the cutout in the panel for the hinged door. Ensure that the five #6-32 nuts
are removed from the threaded studs in the mounting flange and that the drawout chassis has been removed from
the drawout case. Install the case from the rear of the mounting panel by aligning the five #6-32 threaded case
studs to the previously drilled holes. With the studs protruding through the holes secure the case on the right hand
side with two #6-32 nuts provided. Install the hinged door on the front of the mounting panel using three #6-32 nuts
provided. There must be at least 1/2" clearance on the hinged side of the drawout relay to allow the door to open.
RELAY REMOVAL - Open the hinged door. Next remove the two ten finger connecting plugs making sure the top
one is removed first. Swivel the cradle-to-case hinged levers at each end of the 169 cradle assembly and slide the
assembly out of the case.
RELAY INSTALLATION - Slide the 169 cradle assembly completely into the case. Swivel the hinged levers in to lock
the 169 cradle assembly into the drawout case. Install the two ten finger connecting plugs making sure the bottom
plug is installed first. Close the hinged door and secure with the captive screw.
IMPORTANT NOTE:
withdrawn first. This isolates the 169 output relay contacts before power is removed from the relay. When installing
the drawout relay cradle assembly the bottom ten finger connecting plug must be installed first. This causes power
to be applied to the 169 relay before the output relay contacts are placed in the circuit.
After a 169 relay cradle assembly has been removed from the drawout case it is recommended that the hinged door
be closed in order to reduce the risk of electric shock.
Due to the hardware configuration of the drawout relay shorting bars, the RELAY FAILSAFE CODE (SETPOINTS,
page 5) should not be changed without consulting the factory. Wiring for the 169 Plus drawout is shown in Figure 2-
12. If it is required that any of the output relay configurations in Figure 2-12 be different than shown, this information
must be stated when the relay is ordered.
When removing the drawout relay cradle assembly the top ten finger connecting plug must be
21
2 INSTALLATION
g
GE Power Management
Figure 2-10 169 Drawout Relay Physical Dimensions
22
2 INSTALLATION
g
GE Power Management
Figure 2-11 169 Drawout Relay Mounting
23
Loading...
+ 65 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.