Thank you for purchasing this quality-built GE home generator. We’re pleased that you’ve placed your confidence in
the GE brand. When operated and maintained according to the instructions in this manual, your home generator will
provide many years of dependable service.
This manual contains safety information to make you aware of the hazards and risks associated with home standby
generators and how to avoid them. Because we do not necessarily know all the applications this equipment could
be used for, it is important that you read and understand these instructions thoroughly before attempting to start or
operate this equipment.
Save these instructions for future reference.
This home standby generator requires professional installation before use. Refer to the separate installation manual
for full information. Your installer should follow the instructions completely.
Where to Find Us
You never have to look far to find GE support and service for your generator. For quick service when you need it, keep
your original receipt with this manual. You may contact Customer Service at (888) 575-8226 between 8:00 AM and 5:00
PM CT., or click on SERVICE & SUPPORT at http://www.gegenerators.com, which provides a list of authorized dealers.
Generator and engine model and serial numbers should be recorded in the installation manual.
important instructions that should be followed during
installation and maintenance of the generator and batteries.
Safety Symbols and Meanings
Explosion
Toxic Fumes
Lift Hazard
Fire
Rotating Parts
Read Manual
Electrical Shock
Hot Surface
Chemical BurnExplosive PressureAuto Start
The manufacturer cannot possibly anticipate every possible
circumstance that might involve a hazard. The warnings
in this manual, and the tags and decals affixed to the unit
are, therefore, not all-inclusive. If you use a procedure, work
method or operating technique that the manufacturer does
not specifically recommend, you must satisfy yourself that it
is safe for you and others. You must also make sure that the
procedure, work method or operating technique that you
choose does not render the generator system unsafe.
WARNING Running engine gives off carbon monoxide, an
odorless, colorless, poison gas.
Breathing carbon monoxide could result in death, serious
injury, headache, fatigue, dizziness, vomiting, confusion,
seizures, nausea or fainting.
• Operate this product ONLY outdoors in an area that will not
accumulate deadly exhaust gas.
• Keep exhaust gas away from any windows, doors, ventilation
intakes, soffit vents, crawl spaces, open garage doors or other
openings that can allow exhaust gas to enter inside or be drawn
into a potentially occupied building or structure.
• Carbon monoxide detector(s) MUST be installed and maintained
indoors according to the manufacturer’s instructions/
recommendations. Smoke alarms cannot detect carbon
monoxide gas.
The safety alert symbol indicates a potential personal
injury hazard. A signal word (DANGER, WARNING, or
CAUTION) is used with the alert symbol to designate a degree
or level of hazard seriousness. A safety symbol may be used
to represent the type of hazard. The signal word NOTICE is
used to address practices not related to personal injury.
DANGER indicates a hazard which, if not avoided, will
result in death or serious injury.
WARNING indicates a hazard which, if not avoided, could
result in death or serious injury.
CAUTION indicates a hazard which, if not avoided, could
result in minor or moderate injury.
NOTICE addresses practices not related to personal injury.
4
WARNING The engine exhaust from this product contains
chemicals known to the State of California to cause cancer, birth
defects, or other reproductive harm.
WARNING Certain components in this product and related
accessories contain chemicals known to the State of California
to cause cancer, birth defects, or other reproductive harm. Wash
hands after handling.
Not for
Reproduction
WARNING Storage batteries give off explosive hydrogen gas
during recharging.
Slightest spark will ignite hydrogen and
cause explosion, resulting in death or
serious injury.
Battery electrolyte fluid contains acid and is extremely caustic.
Contact with battery contents could cause severe chemical burns.
A battery presents a risk of electrical shock and high short circuit
current.
• DO NOT dispose of battery in a fire. Recycle battery.
• DO NOT allow any open flame, spark, heat, or lit cigarette during
and for several minutes after charging a battery.
WARNING Propane and Natural Gas are extremely flammable
and explosive, which could cause burns, fire or
explosion resulting in death or serious injury.
• Install the fuel supply system according to NFPA 37 and other
applicable fuel-gas codes.
• Before placing the generator into service, the fuel system lines
must be properly purged and leak tested.
• After the generator is installed, you should inspect the fuel
system periodically.
• NO leakage is permitted.
• DO NOT operate engine if smell of fuel is present or other
explosive conditions exist.
• DO NOT smoke around the generator. Wipe up any oil spills
immediately. Ensure that no combustible materials are left in the
generator compartment. Keep the area near the generator clean
and free of debris.
WARNING Generator produces hazardous voltage.
Failure to properly ground generator could result
in electrocution.
Failure to isolate generator from utility power could result
in death or serious injury to electric utility workers due to
backfeed of electrical energy.
• When using generator for backup power, notify utility company.
• DO NOT touch bare wires or bare receptacles.
• DO NOT use generator with electrical cords which are worn,
frayed, bare or otherwise damaged.
• DO NOT handle generator or electrical cords while standing in
water, while barefoot, or while hands or feet are wet.
• If you must work around a unit while it is operating, stand on an
insulated dry surface to reduce the risk of a shock hazard.
• DO NOT allow unqualified persons or children to operate or
service generator.
• In case of an accident caused by electrical shock, immediately
shut down the source of electrical power and contact the local
authorities. Avoid direct contact with the victim.
• Despite the safe design of the residential generator, operating
this equipment imprudently, neglecting its maintenance or being
careless could cause possible injury or death.
• Remain alert at all times while working on this equipment.
Never work on the equipment when you are physically or
mentally fatigued.
• Before performing any maintenance on the generator, disconnect
the battery cable indicated by a NEGATIVE, NEG or (-) first. When
finished, reconnect that cable last.
• After your system is installed, the generator may crank and start
without warning any time there is a power failure. To prevent
possible injury, always set the generator’s system switch to OFF,
remove the service disconnect from the disconnect box AND
remove the 15 Amp fuse BEFORE working on the equipment.
WARNING Unintentional sparking could cause fire or electric
shock resulting in death or serious injury.
WHEN ADJUSTING OR MAKING REPAIRS TO YOUR GENERATOR
• Disconnect the spark plug wire from the spark plug and place the
wire where it cannot contact spark plug.
WHEN TESTING FOR ENGINE SPARK
• Use approved spark plug tester.
• DO NOT check for spark with spark plug removed.
5
Not for
Reproduction
WARNING Exhaust heat/gases could ignite combustibles or
structures resulting in death or serious injury.
Contact with muffler area could cause burns
resulting in serious injury.
• DO NOT touch hot parts and AVOID hot exhaust gases.
• Allow equipment to cool before touching.
• Exhaust outlet side of weatherproof enclosure must have at least
5 ft (1.5 m) minimum clearance from any structure, shrubs, trees or
any kind of vegetation.
• Standby generator weatherproof enclosure must be at least 5 ft
from windows, doors, any wall opening, shrubs or vegetation over
12 inches (30.48 cm) in height.
• Standby generator weatherproof enclosure must have a minimum
of 5 ft (1.5 m) overhead clearance from any structure, overhang or
trees.
• DO NOT place weatherproof enclosure under a deck or other type
of structure that may confine airflow.
• USE ONLY flexible steel fuel line provided. Connect provided fuel
line to generator, DO NOT use with or substitute any other flexible
fuel line.
• Smoke detector(s) MUST be installed and maintained indoors
according to the manufacturer’s instructions/ recommendations.
Carbon monoxide alarms cannot detect smoke.
• Keep at least minimum distances shown in Generator Placement
to insure for proper generator cooling and maintenance
clearances.
• It is a violation of California Public Resource Code, Section 4442,
to use or operate the engine on any forest-covered, brushcovered, or grass-covered land unless the exhaust system is
equipped with a spark arrester, as defined in Section 4442,
maintained in effective working order. Other states or federal
jurisdictions may have similar laws.
Contact the original equipment manufacturer, retailer, or dealer to
obtain a spark arrester designed for the exhaust system installed
on this engine.
• Replacement parts must be the same and installed in the same
position as the original parts.
WARNING Starter and other rotating parts could entangle
hands, hair, clothing, or accessories resulting in
serious injury.
CAUTION Installing the 15 Amp fuse could cause the engine
to start at any time without warning resulting in minor or
moderate injury.
• Observe that the 15 Amp fuse has been removed from the control
panel for shipping.
• DO NOT install this fuse until all plumbing and wiring has been
completed and inspected.
CAUTION Excessively high operating speeds could result in
minor injury.
Excessively low speeds impose a heavy load on generator.
• DO NOT tamper with governed speed. Generator supplies correct
rated frequency and voltage when running at governed speed.
• DO NOT modify generator in any way.
NOTICE Improper treatment of generator could damage it and
shorten its life.
• Use generator only for intended uses.
• If you have questions about intended use, contact your
authorized dealer.
• Operate generator only on level surfaces.
• Adequate, unobstructed flow of cooling and ventilating air is
critical for correct generator operation.
• The access panels/door must be installed whenever the unit
is running.
• DO NOT expose generator to excessive moisture, dust, dirt, or
corrosive vapors.
• Remain alert at all times while working on this equipment.
Never work on the equipment when you are physically or
mentally fatigued.
• DO NOT start engine with air cleaner or air cleaner cover removed.
• DO NOT insert any objects through cooling slots.
• DO NOT use the generator or any of its parts as a step. Stepping
on the unit could cause stress and break parts. This may result in
dangerous operating conditions from leaking exhaust gases, fuel
leakage, oil leakage, etc.
• If connected devices overheat, turn them off and disconnect them
from generator.
• Shut off generator if:
-electrical output is lost;
-equipment sparks, smokes, or emits flames;
-unit vibrates excessively.
-unit makes unusual noises.
• NEVER operate generator without protective housings, covers, or
guards in place.
• DO NOT wear loose clothing, jewelry or anything that could be
caught in the starter or other rotating parts.
• Tie up long hair and remove jewelry.
• Before servicing, remove 15 Amp fuse from control panel and
disconnect Negative (NEG or -) battery cable.
6
Not for
Reproduction
Installation
We sincerely appreciate your patronage. For this reason, we
have made every effort to provide for a safe, streamlined
and cost-effective installation. Because each installation is
unique, it is impossible to know of and advise the trade of all
conceivable procedures and methods by which installation
might be achieved. Neither could we know of possible
hazards and/or the results of each method or procedure. For
these reasons,
Only current licensed electrical and plumbing
professionals should attempt home generator system
installations. Installations must strictly comply with all
applicable codes, industry standards and regulations.
Your home generator is supplied with this “Operator’s
Manual” and a separate “Installation Manual”. These are
important documents and should be retained by the owner
after the installation has been completed.
This product is only for use as an optional generator system
which provides an alternate source of electric power and
to serve loads such as heating, refrigeration systems, and
communication systems that, when stopped during any
power outage, could cause discomfort or inconvenience.
NOTICE This product does NOT qualify for either an
emergency standby or legally required standby system as
defined by NFPA 70 (NEC).
• Emergency generator systems are intended to
automatically supply illumination, power, or both,
to designated areas and equipment in the event of
failure of the normal supply. Emergency systems may
also provide power for such functions as ventilation
where essential to maintain life, where current
interruption of the normal supply would produce
serious life safety or health hazards.
• Legally Required standby generator systems are
intended to automatically supply power to selected
loads in the event of failure of the normal source
which could create hazards or hamper rescue or firefighting operations.
Every effort has been made to ensure that information in this
manual is accurate and current. However, we reserve the
right to change, alter, or otherwise improve the product and
this document at any time without prior notice.
Only current licensed electrical and plumbing professionals
should attempt home generator system installations.
Installations must strictly comply with all applicable codes,
industry standards, laws and regulations.
For the Home Owner
To help you make informed choices and communicate
effectively with your installation contractor(s),
Read and understand Owner Orientation in this manual
before contracting or starting your generator installation.
To arrange for proper installation, contact the store at
which you purchased your generator, your dealer, a licensed
electrician or your utility power provider.
For the Installing Dealer/Contractor
For most applications, the installation manual contains
all the information required to properly install and start
the generator. This operator’s manual describes routine
operation and owner maintenance procedures.
The generator warranty is VOID unless the system is
installed by licensed electrical and plumbing professionals.
Every effort has been made to ensure that information in this
manual is accurate and current. However, we reserve the
right to change, alter, or otherwise improve the product and
this document at any time without prior notice.
The Emission Control System for this generator is warranted
to standards set by the U.S. Environmental Protection Agency
and by the California Air Resources Board (CARB).
If you need more information in this matter, please call
888 575‑8226 between 8:00 AM and 5:00 PM CT.
7
Not for
Reproduction
Owner Orientation
This section provides generator owners with the information
necessary to achieve the most satisfactory and cost effective
installation possible.
Federal and local codes, appearance, noise levels, fuel types,
and distances are the factors that must be considered when
negotiating with an installation professional.
Remember that as the distance from the existing electrical
service and gaseous fuel supply increases, and the
number of 90 degree bends in the fuel supply increases;
compensations in piping and wiring materials must be made.
This is necessary to comply with local codes and overcome
electrical voltage drops and gaseous fuel pressure drops.
The factors mentioned above will have a direct affect on
the overall price of your generator installation.
In some areas you may need to acquire electrical permits for
installing the home generator, building permits for installing
gas lines, and permits for noise allowances. Your installer
should check your local codes AND obtain the permits before
installing the system.
Power Decrease at High Altitude or
High Temperature
Air density is less at high altitudes, resulting in less available
engine power. Specifically, engine power will decrease 3.5%
for each 1,000 feet (300 meters) above sea level and 1%
for each 10° F (5.6°C) above 77°F (25°C). Make sure you and
your installer consider these factors when determining total
generator load.
8
Not for
Reproduction
Generator Location
The actual physical location of your home generator has a
direct affect on:
1. The amount of plumbing required to fuel
your generator.
2. The amount of wiring required to control and connect
your generator.
Specific location guidelines are discussed in the installation
manual. Acquaint yourself with that information and confer
with your installer. Be sure to ask how your site might
affect installation costs and compliance with local codes
and standards.
• Install generator outdoors in an area that will not
accumulate deadly exhaust gas.
• DO NOT install generator where exhaust gas could
accumulate and enter inside or be drawn into a
potentially occupied building or structure.
• By law it is required in many states to have a Carbon
Monoxide (CO) detector in operating condition in
your home. Carbon monoxide detector(s)
be installed and maintained indoors according to
the manufacturer’s instructions/ recommendations.
A CO monitor is an electronic device that detects
hazardous levels of CO. When there is a buildup of
CO, the monitor will alert the occupants by flashing
visual indicator light and alarm. Smoke alarms cannot
detect CO gas.
A
MUST
WARNING Running engine gives off carbon monoxide, an
odorless, colorless, poison gas.
Breathing carbon monoxide could result in death, serious
injury, headache, fatigue, dizziness, vomiting, confusion,
seizures, nausea or fainting.
• Operate this product ONLY outdoors in an area that will not
accumulate deadly exhaust gas.
• Keep exhaust gas away from any windows, doors, ventilation
intakes, soffit vents, crawl spaces, open garage doors or other
openings that can allow exhaust gas to enter inside or be drawn
into a potentially occupied building or structure.
• Carbon monoxide detector(s) MUST be installed and maintained
indoors according to the manufacturer’s instructions/
recommendations. Smoke alarms cannot detect carbon
monoxide gas.
• Ensure exhaust gas is kept away from any windows,
doors, ventilation intakes, soffit vents, crawl spaces,
open garage doors or other openings that can
allow exhaust gas to enter inside or be drawn into
a potentially occupied building or structure. Your
neighbor(s) home may be exposed to the engine
exhaust from your standby generator and must be
considered when installing your standby generator.
• Wind and air currents should be taken into
consideration when positioning generator.
See the installation manual for full details on safe generator
location.
A
WARNING Exhaust heat/gases could ignite combustibles or
structures resulting in death or serious injury.
• Exhaust outlet side of weatherproof enclosure must have at least
5 ft (1.5 m) minimum clearance from any structure, shrubs, trees or
any kind of vegetation.
• Standby generator weatherproof enclosure must be at least
5 ft (1.5 m) from windows, doors, any wall opening, shrubs or
vegetation over 12 inches (30.5 cm) in height.
• Standby generator weatherproof enclosure must have a minimum
of 5 ft (1.5 m) overhead clearance from any structure, overhang or
trees.
• DO NOT place weatherproof enclosure under a deck or other type
of structure that may confine airflow.
• USE ONLY flexible steel fuel line provided. Connect provided fuel
line to generator, DO NOT use with or substitute any other flexible
fuel line.
• Smoke detector(s) MUST be installed and maintained indoors
according to the manufacturer’s instructions/ recommendations.
Carbon monoxide alarms cannot detect smoke.
• DO NOT place weatherproof enclosure in manner other than shown
in illustrations.
9
Not for
Reproduction
Delivery Inspection
Carefully inspect the home generator for any damage that
may have occurred during shipment.
If loss or damage is noted at time of delivery, have the
person(s) making delivery note all damage on the freight bill
and affix his signature under the consignor’s memo of loss or
damage. If loss or damage is noted after delivery, separate
the damaged materials and contact the carrier and your
installer for claim procedures. Parts damaged in shipping are
not warranted.
The home generator system is supplied with:
• Oil (5W30 Synthetic)
• Flexible steel fuel line
• Installation and start-up manual
• Operator’s manual
• Spare access roof keys
• Spare 15 Amp ATO-type fuse
• Remote wireless monitor
• Antenna
Not included:
• Carbon monoxide detector(s)
• Smoke detector(s)
• Starting battery
• Connecting wire and conduit
• Fuel supply valves/plumbing
• Crane, lifting straps, chains or cables
• Two 60” lengths of 3/4” nominal minimum scheduled
40 steel pipe (NOT conduit)
• Torque screwdriver, 5 to 50 inch-pound range
• Voltage/frequency meter
• Two (2) AA batteries for remote wireless monitor
10
Not for
Reproduction
Controls
8kW Generator
Read this operator’s manual and Important Safety Instructionsbefore operating your generator.
Compare the illustration with your generator to familiarize yourself with the locations of various
controls and adjustments. Save this manual for future reference.
E
D
F
C
B
A
Generator is shown with roof and access covers removed
for clarity.
A
- Lifting Holes — Provided at each corner for
lifting generator.
- Exhaust Port — High-performance muffler lowers engine
B
noise to comply with most residential codes.
- Alternator — An electrical machine that generates an
C
alternating current.
- Spark Plug — A device in the cylinder head of the engine
D
that ignites the fuel mixture by means of an electric spark.
G
H
J
E
- Air Cleaner — Uses a dry type filter element and foam
precleaner to protect engine by filtering dust and debris out
of intake air.
- Control Panel — Used for various test, operation and
F
maintenance functions. See System Control Panel.
G
- Circuit Breaker — Protects the system from shorts and
- Fuel Inlet Port — Attach appropriate fuel supply to
J
generator here.
Not for
Reproduction
Access Panels
The generator is equipped with an enclosure that has several
access panels, as shown.
Front Panel that is used to access:
A
• Battery Compartment
• Engine Oil Drain Hose
• Engine Oil Filter
• Engine Valve Cover
• Spark Plugs
Each generator is shipped with a set of identical keys.
A
13
Not for
Reproduction
To remove roof:
1. Remove the five screws that secure the roof to
the unit.
2. Carefully lift and remove roof from unit.
A
To remove front panel:
1. Remove the two screws that secure the panel to the
unit.
2. Lift and flex panel outward and off base. Use caution
not to damage the battery box (C.
To secure front panel:
1. Place panel in unit.
2. Secure the panel with two screws.
B
C
A
A
BB
A
14
C
B
Not for
Reproduction
System Control Panel
The generator control board, located inside the generator,
under the roof, is shown below. Brief descriptions of the
controls used during installation are:
A
- Menu/Programming Navigation Buttons — See
Menu section for details
B
- Mini USB Port — Authorized Dealer Service Use Only.
C
- Generator Operation Control Buttons —
• “AUTO” Normal operating position. Press and hold
button to put unit into Automatic mode. In Automatic
mode, if a utility power outage is sensed, the system
will start the generator. When utility power is restored,
auto lets the engine stabilize internal temperatures,
shuts o the generator, and waits for the next utility
outage.
• “OFF” Turns o running generator, prevents unit from
starting, and resets any detected service codes.
OFF must be pressed and held for more than 5 seconds in
order to reset service code memory.
•“MANUAL” Used to manually start the generator.
D
– 15 Amp Fuse — Protects the home generator DC
control circuits. If the fuse has ‘blown’ (melted open)
or was removed, the engine cannot crank or start.
Replace the fuse using only an identical ATO 15A fuse.
One spare fuse is supplied with the unit.
E
- Cover — This protective cover must be removed to
access the fuse and the USB port.
F
- Digital Display — Displays generator mode, menu
options, service codes, and service engine indicators
More information may be found in Controls in the
operator’s manual.
F
menu
A
B
auto
C
ok
esc
E
D
offmanual
15
Not for
Reproduction
Menu
ok
ok
ok
ok
ok
ok
ok
ok
ok
The following chart shows the icons for the buttons that control the system control panel.
ok
MENU
ESCAPE (EXIT)
RIGHT ARROW
LEFT ARROW
MANUAL MODE
OFF
AUTOMATIC MODE
ENTER THE MENU (VIEW SETTINGS)
PRESS TO CONFIRM SELECTION WHEN PROGRAMMING.
RETURN TO LAST MENU ITEM
TOGGLE THROUGH MENU OPTIONS
SETTING SYSTEM PARAMETERS
TOGGLE THROUGH MENU OPTIONS
SETTING SYSTEM PARAMETERS
USED TO MANUALLY START THE GENERATOR. PRESS AND HOLD BUTTON TO START
THE GENERATOR.
TURNS OFF RUNNING GENERATOR, PREVENTS UNIT FROM STARTING, AND RESETS
ANY DETECTED SERVICE CODES.
NORMAL OPERATING POSITION. PRESS AND HOLD BUTTON TO PUT UNIT INTO
AUTOMATIC MODE. IF A UTILITY POWER OUTAGE IS SENSED, THE
SYSTEM WILL START THE GENERATOR. WHEN UTILITY POWER IS RESTORED, AUTO
LETS THE ENGINE STABILIZE INTERNAL TEMPERATURES, SHUTS OFF THE GENERATOR, AND WAITS FOR THE NEXT UTILITY POWER OUTAGE.
The following chart describes key sequences for accessing different programming modes;
ok
16
GENERAL
SET-UP
WIRELESS
LINK MODE
PRESS AND HOLD [ARROW LEFT AND ARROW RIGHT] FOR
THREE SECONDS TO ENTER THE PROGRAM MODE.
PRESS AND HOLD [MENU AND ESC] FOR THREE SECONDS TO
ENTER THE WIRELESS LINKING MODE. (ONLY APPLICABLE ON
CERTAIN MODELS).
Not for
Reproduction
General Set Up Screen
ok
ok
For general set up, press and hold the left arrow and right arrow for 3 seconds. Follow the prompts as outlined below.
NOTE: Date and Time were set at the factory and stored in the control panel memory. The Exercise Cycle was also set at
the factory. The default exercise cycle occurs on Tuesdays, at 2:00 P.M. Central Standard Time. To update or change these
settings, follow the steps below.
SET DATE
or
SET TIME
or
YEAR
FLASHING
ororor
HOURS
FLASHING
ororor
or
MONTH
FLASHING
MINUTES
FLASHING
DAY##
FLASHING
AM/PM
FLASHING
If set to OFF, display will read:
EXERCISE CYCLE OFF
or
SET EXERCISE
CYCLE
EVENT LOG
DAY OF WEEK
FLASHING
orororor
HOURS
FLASHING
MINUTES
FLASHING
Display will scroll last service code event, date, time,
and ambient temperature of when the event occurred.
IF DURING PROGRAMMING NO BUTTONS ARE PRESSED FOR 30 SECONDS,
THE CONTROL PANEL WILL AUTOMATICALLY EXIT THE PROGRAM MODE.
AM/PM
FLASHING
or
17
Not for
Reproduction
Control Panel Prompts
Automatic Mode
In Automatic Mode, the display screen will display via
scrolling text:
• GENERATOR READY - if the unit is in standby and utility
power is present.
• GENERATOR ON - if the unit is running and utility
power is not on.
• SERVICE CODE - if a system service code has been
detected.
General System Parameters
To view general system parameters, press the MENU button.
The following will scroll across the digital display and then
move to the next item:
• Run time (total hours the unit has run since installation)
• Date
• Time
• Exercise Cycle date and start time
The user can press the LEFT ARROW or RIGHT ARROW at any
time to move to the next item.
The user can press ESCAPE to go back to GENERATOR READY.
If no user inputs are made for 10 seconds after all the items
have been displayed, the control board will reset to
GENERATOR READY.
AUTOMATIC MODE
GENERATOR READY OR SERVICE CODE DESCRIPTION
(When Generator NOT Running - Auto Mode)
GENERATOR ON
(When Generator Running - Auto Mode)
ok
(MENU)
RUN TIME
or
DATE
or
18
TIME
or
EXERCISE CYCLE
Not for
Reproduction
Operation
Important Owner’s Considerations
Engine Oil
The engine is shipped from the factory pre-run and filled
with synthetic oil (API SJ/CF 5W-30). This allows for system
operation in a wide range of temperature and climate
conditions. Before starting the engine, check oil level as
described in Maintenance.
NOTICE Any attempt to crank or start the engine before it has
been properly serviced with the recommended oil will result in
equipment failure.
• Damage to equipment resulting from failure to follow this
instruction will void engine and generator warranty.
Battery
WARNING Battery posts, terminals and related accessories
contain lead and lead compounds, chemicals known to the State
of California to cause cancer and reproductive harm. Wash hands
after handling.
The installer must supply a rechargeable 12 volt DC starting
battery. See Battery in Final Installation Considerations in the
installation manual.
With the battery installed, all wiring to transfer switch and
home generator completed, utility power supplied to the
automatic transfer switch, and the unit in AUTO mode, the
battery receives a trickle charge while the engine is not
running. The trickle charge cannot be used to recharge a
battery that is completely discharged.
NOTICE A battery booster should never be used to quick
charge a low battery.
15 Amp Fuse
The generator’s 15 Amp fuse is critical to correct system
operation. The 15 Amp fuse was removed at the factory.
Your installer will ensure the fuse is properly installed upon
completion of the installation.
19
Not for
Reproduction
Automatic Operation
The generator’s control board constantly monitors utility
voltage. Should utility voltage drop below a preset level, the
control board will signal the engine to crank and start.
When utility voltage is restored above a preset voltage level,
the engine is signaled to shut down.
The actual system operation is not adjustable and is
sequenced by sensors and timers on the control board,
as follows:
Utility Voltage Dropout Sensor
• This sensor monitors utility source voltage.
• If utility source voltage drops below about 70 percent
of the nominal supply voltage, the sensor energizes
a 3 second timer. The timer is used to ‘sense’
brown-outs.
• Once the timer has expired, the engine will crank
and start.
Utility Voltage Pickup Sensor
This sensor monitors utility voltage. When utility voltage is
restored above 80 percent of the nominal source voltage,
a time delay starts timing and the engine will go to engine
cool-down.
Engine Cool-down Timer
When utility power is sensed and the load transfers back to
the utility source, the engine will go into a cool down period
as described below:
• If the generator has run for MORE than 5 minutes,
once the utility transfer occurs, the engine will
continue to run for about 1 minute before shutting
down.
• If the generator has run for LESS than 5 minutes, once
the utility transfer occurs, the engine will continue to
run until 5 minutes has elapsed before shutting down.
Setting Exercise Timer
The generator is equipped with an exercise timer. During the
exercise period, the unit runs for approximately 20 minutes
and then shuts down. Electrical load transfer DOES NOT
occur during the exercise cycle (unless an utility power
outage occurs).
The generator will only enter the exercise cycle if the unit
is in the AUTO mode and this exact procedure is followed.
To set the exercise timer:
NOTICE The generator is set with a deservice code exercise
cycle setting of Tuesday at 2:00 P.M, Central Time. To change
the cycle setting, proceed to the following steps:
1. Choose the day and time you want your generator to
exercise.
2. Press and hold the left arrow and right arrow
simultaneously for three seconds to enter the General
Set-Up program mode. See General Set-Up flow chart
in Menu Section.
3. Verify and/or set the time and date on the unit.
4. Go to the SET EXERCISE prompt and hit the “OK”
button.
NOTICE Items will flash until they are selected.
SELECT DAY: Use the left or right arrow to toggle
through the days of the week, Once the day is
selected, hit the “OK” button.
SELECT HOUR: Use the left or right arrow to toggle
through between 1 and 12. Choose the hour of day
you want the generator to exercise then hit the “OK”
button.
SELECT MINUTE: Use the left of right arrow to toggle
between :00 and :59. Choose the minute of the day
you want the generator to exercise then hit the “OK”
button.
SELECT AM/PM: Use the left of right arrow to toggle
between AM and PM. Once chosen, hit the “OK”
button.
NOTICE During the weekly exercise cycle, the generator will
run for 20 minutes, but it will not supply power to the home.
During the exercise cycle, the in-home monitor will continue
blinking the GENERATOR READY green LED.
If you want to change the day and time the unit exercises,
simply perform the procedure again.
To turn off the generator exercise cycle, go to the OFF
selection within the day of the week menu and press OK. The
display will then scroll: EXERCISE CYCLE OFF.
20
Not for
Reproduction
Wireless Monitor
DEALER NAME
DEALER
PHONE
generator power
service needed
generator ready
system update
1 low battery voltage
2 low uid level
3 under/over voltage
4 engine does not start
part #: 316196 fcc id: MCQ-XBS2C IC id: 1846A-XBS2C
5 low frequency
6 engine overspeed
7 high temperature
8 transfer switch
# of flashes service needed
The generator is supplied with a battery-powered, wireless
monitor.
The monitor communicates wirelessly with the generator
control panel. The monitor may be placed in a suitable
location in the home. The system has a line-of-sight range of
about 200 feet, but this distance will decrease if the signal
has to pass through walls or other objects.
The wireless monitor communicates with the generator,
every 10 minutes and will display the status via a green or
red LED light on the front of the monitor.
Compare the illustration below with your monitor to
familiarize yourself with these important components.
• Generator Ready (A) - Green LED
• Generator Power (B) - Green LED
• Service Needed (C) - Red LED
• System Update (D) - Press for current system update
with generator.
• Service code descriptions (E) - Name and number
of flashes are listed on the backside of the wireless
monitor.
• Battery Access Cover (F) - Record the dealer name
and phone number on the label provided. Once
removed, two non-rechargeable AA batteries are
installed in the compartment (). .
A
B
C
D
E
F
G
A
B
C
D
E
G
F
21
Not for
Reproduction
Wireless Monitor Operation
1 low battery voltage2 low uid level
3 under/over voltage
5 low frequency6 engine overspeed
7 high temperature
# of flashes service needed
1 low battery voltage2 low uid level3 under/over voltage4 engine does not start
part#: 316196 fcc id: MCQ-XBS2C IC id: 1846A-XBS2C
5 low frequency6 engine overspeed7 high temperature8 transfer switch
# of flashes service needed
1. Remove battery access cover (A) on back of monitor
A
and install 2 AA batteries. (Observe correct battery
polarity which is embossed in the bottom of the
battery compartment). Replace battery access cover.
vice needed
4 engine does not start
part #: 316196 fcc id: MCQ-XBS2C IC id: 1846A-XBS2C
e
8 transfer switch
4. “LINKING MODE” will scroll across the generator
control panel.
5. Locate and hold the SYSTEM UPDATE button (C) on
C
the wireless monitor for 5 seconds. All 3 LEDs will flash
until the monitor links to the generator. Once it links,
the monitor will display the current state. The monitor
will try to link for 1 minute. (This step can only be
completed when the generator is in Linking Mode).
DEALERNAME
DEALER
PHONE
A
NOTICE The wireless monitor was linked to the generator at
the factory. Communication will begin upon the installation
of the batteries and the generator being placed in AUTO
mode. You may need to press System Update one time.
2. The wireless monitor does not have an on/off
switch. When batteries are installed correctly,
the GENERATOR READY green LED light will flash
once every 10 seconds indicating the status of the
generator.
NOTICE If communication does not begin upon placing the
generator in AUTO, installing batteries, and pressing System
Update, the monitor may need to be re-linked. To link, follow
Steps 3 through 6.
3. Locate the MENU AND ESCAPE buttons on the control
panel (B) . Press and hold for 3 seconds to enter the
B
linking mode.
generator ready
generator power
service needed
C
system update
6. Once the link has been confirmed, press the OK
button on the generator control panel to exit or the
control board will turn off linking after 5 minutes. The
generator will now communicate with the wireless
monitor.
NOTICE It may take up to 1 minute for the monitor to begin
displaying the generator status correctly.
menu
ok
esc
offmanual
B
B
auto
22
Not for
Reproduction
Standard Operation:
Wireless Monitor Status LED’s
• The wireless monitor receives data from the generator
every 10 minutes and displays the generator status
through 3 LED’s.
• Pressing the SYSTEM UPDATE button will provide
current generator status by flashing the status LED’s.
When pressed, all 3 LEDs will flash until the generator
status is received.
NOTICE Generator control panel must be in AUTO mode or
no communication with monitor will occur.
• In order to conserve power and to extend battery life,
the LED’s are not lit continuously; instead they are
briefly flashed as indicated below.
NOTICE During the weekly exercise cycle, the generator will
run for 20 minutes, but it will not supply power to the home.
During the exercise cycle, the monitor will continue blinking
the GENERATOR READY green LED.
• GENERATOR READY - When active, the green LED will
flash once every 7 seconds. The green LED indicates
that the generator is in AUTO mode and that it is
ready to run in the event of a loss of utility power.
• GENERATOR POWER - When active, the green LED will
flash every 7 seconds. The green LED indicates that
the generator is supplying power.
• SERVICE NEEDED - When active, the red LED will flash
in a sequence that corresponds to the service code.
For example, when Low Frequency scrolls across the
control board, the red LED will flash 5 times with a 3
second pause between series of blinks until it is reset
or the condition is corrected. When the red LED is lit,
contact your nearest authorized service dealer.
NOTICE None of the conditions on the display unit can be
cleared at the wireless monitor. All alerts must be cleared at
the generator control panel.
NOTICE Service conditions will only be displayed on the
basic monitor when the control board is placed in AUTO
mode.
Other:
LED Lighting Codes
• Batteries Inserted - GENERATOR READY LED will light
for 5 seconds.
• Wireless Communication Lost - SERVICE NEEDED LED
will flash 20 fast pulses, then pause for 5 seconds,
and repeat the sequence until the communication
has been restored.
• Linking Error or Not Linked - SERVICE NEEDED LED will
light for 4 seconds, pause for 4 seconds, and repeat
the sequence until a successful link is completed.
23
Not for
Reproduction
Maintenance
Servicing the System
Before performing any generator maintenance, always
perform the following steps:
1. Set generator’s circuit breaker to its OFF position.
2. Press and hold the control board OFF button.
3. Remove 15 Amp fuse from control board.
Service Code Detection System
The generator may have to run for long periods of time
with no operator present. For that reason, the system is
equipped with sensors that automatically shut down the
generator in the event of potentially damaging conditions,
such as low oil pressure, high temperature, over speed, and
other conditions.
The generator’s control board shows service code
descriptions scrolling across the digital display. The service
code descriptions are listed below:
• Low Battery Voltage
• Low Oil Pressure
• Under Voltage
• Over Voltage
• Engine Does Not Start
• Low Frequency
• Engine Overspeed
• High Oil Temperature
• Transfer Switch Service code
• No Wireless Communication
• Battery Charge Circuit
4. Utility voltage is present at generator control board.
Disconnect power before servicing control board by
removing the fuses from the transfer switch.
5. After all servicing has been completed, replace fuses
in transfer switch, replace 15 Amp fuse in control
board, set circuit breaker ON and press and hold
control board AUTO button.
Reset Service code Detection System
The operator must reset the service code detection system
each time it activates. To do so, press the control board OFF
button for 5 seconds. Once the display turns off, leave it off
for at least 30 seconds. Remedy the service code condition,
then return the home generator to service by pressing and
holding the control board AUTO button and installing the 15
Amp fuse (if removed).
Low Battery Voltage
This service code is indicated by Low Battery Voltage scrolling
across the digital display and a single flash on the wireless
monitor. This condition occurs if the battery voltage drops
below the preset value. Causes for this problem may be a
service code battery or battery charge circuit. See Battery Charge Circuit,
Remove the 15 Amp fuse and disconnect the battery from
the generator. Test the battery voltage. If voltage meets
specifications, take the battery to a local battery store for
analysis. Or contact your local service center for assistance.
Reinstall the battery (replace if necessary - see Battery in
Final Installation Considerations in the installation manual).
Then reset the service code detection system, as described
earlier.
24
Not for
Reproduction
Low Oil Pressure
This service code is indicated by Low Oil Pressure scrolling
across the digital display and two flashes on the wireless
monitor. The unit is equipped with an oil pressure switch
that uses normally closed contacts held open by engine oil
pressure during operation. Should oil pressure drop below
the 8 psi range, switch contacts close and the engine will
shut down.
To remedy the low oil pressure condition, add the
recommended oil to the FULL mark on the dipstick.
If the low oil pressure condition still exists, the engine will
start, then shut down again. The service code will appear. In
this case, contact an authorized dealer.
Under Voltage
This service code is indicated by Under Voltage scrolling
across the digital display and three flashes on the wireless
monitor. This condition is caused by a restriction in the
fuel flow, the electronic governing system not functioning
properly, a broken or disconnected signal lead, a failed
alternator winding, the control board circuit breaker is open,
or the generator is overloaded.
To remedy the problem, contact your installer or an
authorized dealer.
Over Voltage
This service code is indicated by Over Voltage scrolling across
the digital display and three flashes on the wireless monitor.
This feature protects devices connected to the transfer
switch by shutting the generator down if the generator
output voltage happens to increase above the preset limit.
This condition is most likely caused by a failed voltage
regulator, alternator excitation circuit or a load imbalance. To
remedy the problem, contact your installer or an
authorized dealer.
Engine Does Not Start
This service code is indicated by Engine Does Not Start
scrolling across the digital display and four flashes on the
wireless monitor. This feature prevents the generator from
damaging itself if it continually attempts to start in spite
of another problem, such as no fuel supply. Each time the
system is directed to start, the unit will crank for 10 seconds,
pause for 10 seconds, and repeat. If the system does not
begin producing electricity after approximately 2 minutes,
the unit will stop cranking.
The most likely cause of this problem is no fuel supply or
incorrect fuel selector setting. See Fuel Selection Switch in
the installation manual. Check the internal and external fuel
shut off valves to ensure they are fully open. Other causes
could be failed spark plug(s), a loose electronic governor
connection, a failed engine ignition, or the engine air filter
is clogged. You may need to contact your installer for
assistance if you can’t remedy these problems.
Low Frequency
This service code is indicated by Low Frequency scrolling
across the digital display and five flashes on the wireless
monitor. This feature protects devices connected to the
transfer switch by shutting the generator down if the engine
runs slower than 55 Hz for three seconds. This condition is
caused by a failed engine component, electronic governor
system, or by excessive loads on the generator. To resolve
the problem, contact your installer or an authorized dealer.
Engine Overspeed
This service code is indicated by Engine Overspeed scrolling
across the digital display and six flashes on the wireless
monitor. This condition can be caused by a problem within
the electronic governor system.
To resolve the problem, contact your installer or an
authorized dealer.
High Oil Temperature
This service code is indicated by High Oil Temperature
scrolling across the digital display and seven flashes on the
wireless monitor. The contacts of the temperature switch
are normally open. If the engine temperature exceeds a
predetermined temperature, the service code is detected and
the engine shuts down.
Common causes for this condition include running the
unit with an access doors removed, obstructed air inlet
or exhaust port, or debris in the engine compartment or
running unit with roof open.
To resolve the problem, let the engine cool down and remove
any accumulated debris and obstructions. Ensure that the
access doors are installed and the roof is closed whenever
the unit is running. If problem persists, contact your installer
or an authorized dealer.
Transfer Switch Service code
This service code is indicated by Transfer Switch Service
code scrolling across the digital display (if transfer switch is
equipped with service code detection) and eight flashes on
the wireless monitor.
The most likely cause of this service code is a blown fuse in
the transfer switch. To remedy the problem, contact your
installer or an authorized dealer.
No Wireless Communication
This service code is indicated by No Monitor Communication
scrolling across the digital display. The SERVICE NEEDED red
LED on the wireless monitor will flash 20 fast pulses, pause
5 seconds, and repeat if there is a loss in communication
between the wireless monitor and the generator.
To resolve the problem, move the wireless monitor closer to
generator. Re-link if necessary.
Battery Charge Circuit
This service code is indicated by Battery Charge Circuit
scrolling across the digital display. The most likely cause is
an electrical problem with the control panel. To remedy the
problem, contact your installer or an authorized dealer.
25
Not for
Reproduction
Maintenance Schedule
Follow the hourly or calendar intervals of operation,
whichever occurs first.
First 5 Hours
Change Engine Oil
Every 8 Hours or Daily
Clean Debris
Check Engine Oil Level
Every 100 Hours or Annually
Change Air Filter
Change Engine Oil and Filter
Replace Spark Plugs
Check Valve Clearance
Check Circuit Breaker Torques
Annually
Clean Oil Cooler Fins
Regular maintenance will improve the performance and
extend the life of the generator. See any authorized dealer
for service.
Emissions Control
Maintenance, replacement, or repair of the emissions
control devices and systems may be performed by any
non-road engine repair establishment or individual.
However, to obtain ”no charge” emissions control service, the
work must be performed by a factory authorized dealer. See
the Emissions Warranty.
Generator Maintenance
The generator’s warranty does not cover items that have
been subjected to operator abuse or negligence. To receive
full value from the warranty, the operator must maintain the
generator as instructed in this manual.
Some adjustments will need to be made periodically to
properly maintain your generator.
All service and adjustments should be made at least once
each season. Follow the requirements in the Maintenance Schedule chart.
Generator maintenance consists of keeping the unit
clean. Operate the unit in an environment where it will
not be exposed to excessive dust, dirt, moisture or any
corrosive vapors. Cooling air louvers on the enclosure
must not become clogged with snow, leaves, or any other
foreign material. To prevent generator damage caused by
overheating, keep the enclosure cooling inlets and outlets
clean and unobstructed at all times.
Check the cleanliness of the unit frequently and clean when
dust, dirt, oil, moisture or other foreign substances are visible
on its exterior/interior surface. Inspect the air inlet and outlet
openings inside and outside the enclosure to ensure air flow
is not blocked.
DO NOT use direct spray from a garden hose to clean
generator. Water can enter the engine and generator and
cause problems.
26
NOTICE Improper treatment of generator could damage it and
shorten its life.
• DO NOT expose generator to excessive moisture, dust, dirt, or
corrosive vapors.
• DO NOT insert any objects through cooling slots.
Clean the generator as follows:
1. Press and hold the control board OFF button.
2. Remove 15 Amp fuse from control board.
3. Clean generator as desired.
• Use a damp cloth to wipe exterior surfaces clean.
• Use a soft, bristle brush to loosen caked on dirt, etc.
• Use a vacuum cleaner to pick up loose dirt and debris.
• Use low pressure air (not to exceed 25 psi) to blow
away dirt. Inspect cooling air slots and openings on
the generator. These openings must be kept clean
and unobstructed.
4. Reinstall 15 Amp fuse in control board.
5. Press and hold the control board AUTO button.
Not for
Reproduction
Battery
Servicing of batteries is to be performed or supervised
by personnel knowledgeable of batteries and the
required precautions. Keep unauthorized personnel away
from batteries.
Servicing the Battery
If it is necessary to service the battery, proceed as follows:
1. Press and hold the control board OFF button.
2. Remove 15 Amp fuse from control panel.
3. Service or replace battery as required. See Battery
in Final Installation Considerations in the installation
manual for specific battery needed.
4. Connect red battery cable to battery positive terminal
(indicated by POSITIVE, POS, or (+)).
Charging the Battery
If it is necessary to charge the battery, proceed as follows:
1. Press and hold the control board OFF button.
2. Remove 15 Amp fuse from control board.
3. Disconnect negative battery cable from negative
battery terminal (indicated by NEGATIVE, NEG, or (-)).
NOTICE Failure to disconnect negative battery cable could result in
equipment failure.
• DO NOT attempt to jump start the generator.
• Damage to equipment resulting from failure to follow this
instruction will void engine and generator warranty.
WARNING Battery posts, terminals and related accessories
contain lead and lead compounds, chemicals known to the State
of California to cause cancer and reproductive harm. Wash hands
after handling.
6. Connect black negative battery cable to negative
battery terminal (indicated by NEGATIVE, NEG, or (-).
7. Ensure hardware on both positive and negative
battery terminals is secure.
8. Reinstall 15 Amp fuse in control panel.
9. Press and hold the control board AUTO button.
DON’T POLLUTE. CONSERVE RESOURCES, RETURN
USED BATTERY TO RECYCLING COLLECTION CENTER.
4. Charge battery with battery charger at 2 Amps until
battery holds 12 Volts. DO NOT exceed 13.7 volts
when charging.
NOTICE DO NOT use a battery booster to quick charge a low
battery.
5. Connect negative battery cable to negative battery
terminal (indicated by NEGATIVE, NEG, or (-)).
6. Ensure hardware on both positive and negative
battery terminals is secure.
7. Reinstall 15 Amp fuse in control board.
8. Press and hold the control board AUTO button.
WARNING Storage batteries give off explosive hydrogen gas
during recharging.
Slightest spark will ignite hydrogen and
cause explosion, resulting in death or
serious injury.
Battery electrolyte fluid contains acid and is extremely caustic.
Contact with battery contents could cause severe chemical burns.
A battery presents a risk of electrical shock and high short
circuit current.
• DO NOT dispose of battery in a fire. Recycle battery.
• DO NOT allow any open flame, spark, heat, or lit cigarette during
and for several minutes after charging a battery.
CAUTION With the system switch set to AUTO, the engine could
crank and start at any time without warning, resulting in
minor or moderate injury.
• To prevent possible injury that could be caused by such sudden
starts, always set the system switch to OFF if performing
maintenance on the system.
• Remove the 15 Amp fuse before working on or around the
generator or transfer switch.
27
Not for
Reproduction
Engine Maintenance
WARNING Unintentional sparking could cause fire or electric
shock resulting in death or serious injury.
WHEN ADJUSTING OR MAKING REPAIRS TO YOUR GENERATOR
• Disconnect the spark plug wire from the spark plug and place the
wire where it cannot contact spark plug.
WHEN TESTING FOR ENGINE SPARK
• Use approved spark plug tester.
• DO NOT check for spark with spark plug removed.
Adjust Valve Lash
The valve lash must be checked every 100 hours of
operation. Measure valve clearance with the engine cold.
To adjust the valve lash, proceed as follows:
1. Remove spark plug(s) to ease manual rotation of
engine crankshaft.
2. Turn crankshaft counterclockwise until the piston is at
Top Dead Center on the compression stroke.
3. Insert a narrow screwdriver or rod into spark
plug hole as a gauge, then slowly turn crankshaft
counterclockwise until the piston has moved down
the bore by 1/4”.
4. For the Model 31 Engine:
• Use a feeler gauge (A) , measure the valve
clearance.
• Adjust the rocker nut to obtain the correct
clearance as follows: 0.005 (0.013 mm) intake
and 0.007 (0.018 mm) exhaust.
• Hold rocker nut and tighten the rocker ball set
screw (B) to 45 in/lb (5 Nm).
5. For the Model 35 Engine:
• Use a feeler gauge (A) to measure the valve
clearance.
• Adjust the clearance by loosening the lock nut
(B) then turn the adjusting screw (C) to obtain
BC
the following measurement: 0.005 in. (0.013 mm)
intake and exhaust.
• Once the clearance is properly set, hold the
adjusting screw while torquing the lock nut to 70
in/lbs. (8 Nm).
6. Repeat for the other valve, if applicable.
B
A
A
When all engine servicing is complete, replace 15 Amp fuse
in control board and reset exercise timer.
A
B
Model 31 Engine
B
C
28
Model 35 Engine
Not for
Reproduction
Engine Oil
The engine is filled with synthetic oil (API SJ/CF 5W-30).
This allows for system operation in the widest range of
temperature and climate conditions.
We recommend the use of Briggs & Stratton Warranty
Certified oils for best performance. Other high-quality
detergent oils are acceptable if classified for service SJ or
higher. DO NOT use special additives.
Outdoor temperatures determine the proper oil viscosity for
the engine. Use the chart to select the best viscosity for the
outdoor temperature range expected.
NOTICE Synthetic oil meeting ILSAC GF-2, API
certification mark and API service symbol with “SJ/
CF ENERGY CONSERVING” or higher, is an acceptable
oil at all temperatures. Use of synthetic oil does not
alter required oil change intervals.
Changing Engine Oil and Oil Filter
Open roof and remove front panel to access the oil filter and
to add engine oil.
* Below 40°F (4°C) the use of SAE 30 will result in hard
starting.
** Above 80°F (27°C) the use of 10W30 may cause increased
oil consumption. Check oil level more frequently.
Checking/Adding Engine Oil
1. Open roof to access dipstick and oil fill area.
2. Clean the oil fill area of any debris.
3. Remove the dipstick and wipe with a clean cloth.
4. Fully insert dipstick into oil fill.
5. Remove dipstick and check oil level. Verify oil is at Full
mark on dipstick.
6. If needed, slowly pour recommended oil into oil fill
opening. DO NOT overfill. After adding oil, wait one
minute and recheck oil level.
NOTICE Overfilling with oil could cause the engine to not start, or
hard starting.
• DO NOT overfill.
• If over the FULL mark on dipstick, drain oil to reduce oil level to
FULL mark on dipstick.
7. Replace oil dipstick.
8. Close roof and secure.
29
Not for
Reproduction
Changing Engine Oil and Oil Filter
CAUTION Avoid prolonged or repeated skin contact with used
motor oil.
• Used motor oil has been shown to cause skin cancer in certain
laboratory animals.
• Thoroughly wash exposed areas with soap and water.
KEEP OUT OF REACH OF CHILDREN. DON’T POLLUTE.
CONSERVE RESOURCES. RETURN USED OIL TO
COLLECTION CENTERS.
NOTICE Any attempt to crank or start the engine before it has
been properly serviced with the recommended oil will result in
equipment failure.
• DO NOT attempt to crank or start the engine before it has been
properly serviced with the recommended oil. This may result in
an engine failure.
• Damage to equipment resulting from failure to follow this
instruction will void engine and generator warranty.
Change the oil while the engine is still warm from running, as
follows:
1. Press and hold the control board OFF button.
2. Remove 15 Amp fuse from control board.
3. Place oil drain hose into an approved container.
4. Remove brass fitting from end of drain hose and drain
oil into an approved container.
5. When oil has drained, replace brass fitting on hose.
6. Place oil absorbing towels under oil filter.
7. Remove oil filter and dispose of properly.
8. Before installing a new oil filter, lightly lubricate the oil
filter gasket with fresh, clean oil.
9. Install the oil filter by hand until the gasket contacts
the oil filter adapter, then tighten the oil filter 1/2 to
3/4 turn.
10. Add oil.
11. Remove container from under oil filter and clean up
any spilled oil.
12. Start and run engine. As engine warms up, check for
oil leaks.
13. Stop engine, wait for oil to settle, check oil level and
add if necessary.
Service Air Cleaner
Your engine will not run properly and may be damaged if you
run it with a dirty air cleaner. Clean or replace more often if
operating under dusty or dirty conditions.
To service the air cleaner, follow these steps:
1. Remove the knobs and the cover.
2. Remove air filter.
3. To loosen debris, gently tap air cleaner on a hard
surface. If air cleaner is excessively dirty, replace with
a new air cleaner.
4. Install the air filter.
5. Install the cover and secure with knobs.
NOTICE
same position as the original parts.
Replacement parts must be the same and installed in the
30
Loading...
+ 86 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.