GDH GDH70-Air, GDH120-Air, GDH240-Air Installation And Operating Manual

INSTALLATION AND OPERATING INSTRUCTIONS
GDH70-Air Cooling & Heating GDH120-Air
Cooling & Heating
GDH240-Air Cooling & Heating
SAFETY INSTRUCTIONS
Do not use this unit if it has been dropped or damaged in any way.
This unit should not be installed in any area where flammable liquids or
vapors may be present. Do not store or use gasoline or other combustible materials or liquids near or adjacent to this heat pump.
Check the rating plate on the unit before installation to make certain the
voltage shown is the same as the electricity supply to the heat pump.
The unit must be connected only to a properly grounded electrical supply.
Do not fail to properly ground the unit.
This unit should only be serviced by qualified service personal.
Always shut off electric power before making unit connections or
removing any panels and be extremely careful to avoid injury.
Components may have sharp edges which can cut you.
Tubing and compressor contain high pressure refrigerant and they should
not be exposed to high temperature or be punctured.
Water temperature over 52 °C (125 °f) can cause severe burns or death
from scalding. Feel the water before bathing or showering. Children, disabled, and elderly are at highest risk of being scalded.
Tampering with the thermostat, heater, elements or electrical connections
is dangerous and may result in serious injury. Only properly trained, qualified service personnel should service these components. Do not attempt to modify or change this heat pump in any way.
 
FEATURES
l SUMMARY GDH family is environment friendly, high efficiency air source heat pump, provides both domestic hot water and house heating. Intelligent self-adjusting
control on managing house heating and domestic hot water production. The GDH family heat pump can be combined to radiator or underfloor heating systems. Offering different options for house heating installations to satisfy all different favorites.
l EASY OPERATION Most of settings are finished by the manufacturer. System senses the leaving
water temperature, and regulate the leaving hot water temperature according to inner setting automatically. The end user just need to press ON/OFF button, then the system shall be managed by the controller properly.
l EXCELLENT PERFORMANCE High efficiency scroll compressor, high quality plate heat exchanger, control fan
speed, precise refrigerant flow control by expansion valve with unique inner programme. All these assure the GDH famility the most excellent performance at variable climate.
l EASY INSTALLATION All connections of refrigeration circle parts have been put in place by the
manufacturer, the connection requested on site is just to connect the heat pump to hydraulic circle.
l EXCELLENT SAFETY CONTROL Over-pressure, low pressure protection, over-load protection. Switch on or off system automatically according to the feedback of return water
temperature. Available with anti-freezing function in winter. The controller surveil the status of each component, each occurred malfuntion
shall be sent to the indoor display.
l WIDE RANGE WORKING CONDITION The GDH heat pump can work at -25 °C ~ 35 °C.
l EASY MAINTENANCE The system has self-diagnose programme. Any malfunction occurred shall be
indicated through special code on the screen of the indoor display, so the cause of malfunction can be shoot out easily.
CONTROLLER FEATURES
The GDH200 controller is a specialized heat pumps controller including the complete cooling circle. This controller can easily be adjusted to the most various heat pump conditions. Furthermore an additional electric heating can be controlled depending on time and temperature. Of course it has a defrost function for air-water machines and a cooling function for all types. All actuators and sensors are operated from the GDH200 or scanned and processed.
The controller consists of a built-in part and a remote operating unit, either a built­in device or a wall mounting.
Integrated functions
Control of the heat pump
brine-to-water
Automatic defrosting
2 heating circuits
(outdoor temperature
compensated)
Switching to cooling mode
DHW preparation
Circulation pump control
Storage tank management
Cascade management
Energy management
Measurement of heat yield
(optional feature)
Variations and equipment
16 outputs for the control
of valves or pumps
12 sensor inputs
1 input or output for set
points
6 optocouplers
2 inputs for pressure
sensors
eBus interface
GDH200 Heat pump controller
GDH200 Display Air- Unit
GDH200 Display Air-Split Unit
DIMENSIONS GDH70-Air & GDH120-Air GDH240-AIR
PRE-INSTALLATION
The heat pump should never be stored or installed on its side. Upright transportation is recommended. If it becomes necessary to transport the heat pump on its side, the manufacturer recommends that the unit be in the upright position for a minimum of two hours prior to operation. Failure to follow these instructions may result in damage to the heat pump.
After removing the unit from the crate/carton, immediately remove the panels and inspect for any damage that might have occurred during shipment.
Report concealed damage immediately to the transportation company and request inspection.
The electric power source must be the same voltage and phase as shown on the rating plate. Line and low voltage wiring must be done in accordance with local codes or the national electric code.
The heat pump must be installed by authorised installation engineers and the installation must follow the applicable local rules and regulations as well, as these installation instructions described in this manual.
We reserve the right to change the specifications within this publication in whole or in part without prior notice. This brochure is to be used as a general guide and does not form any part of a contract or is binding in any way. We reserve the right when necessary, or at our discretion to use alternative suppliers or components manufactured by other suppliers.
INSTALLATION
The heat pump should be mounted level on a vibration absorbing pad
slightly larger than the base to provide isolation between the unit and floor
Connect the heat pump with your water pipes (DN25) – inlet and outlet water
Install a circulation water pump direct after the outlet water
Connect the circulation pump with the heat pump
Connect the controller panel with the two wire
Put the water tank sensor into your water tank
If the heat pump installed into south side, please use the second outdoor
temperature sensor. Change the existent outdoor temperature sensor. The new one is to install and to put it into the north side. The outdoor temperature sensor is not to install into the sun.
Compressor Time Delay: Be aware there is a 3 minutes time delay.
ELECTRIC INSTALLATION
GDH70-AIR
GDH120-Air & GDH240-Air
GDH200 CONTROLLER INSTALLATION
APPENDIX: ELECTRICAL WIRING DIAGRAM
GDH70-AIR
GDH120-AIR
GDH240-AIR
DIMENSIONS GDH70-AIR / GDH120-AIR
TECHNICAL DATA
Type GDH70-Air GDH120-Air
Certificate and protection CE / IP24 CE / IP24
Installation location Indoor / Outdoor Indoor / Outdoor
Operation temperature limits
Air ºC -25 to +35 -25 to +35
Heat water flow ºC Up to 60 Up to 60
Heating capacity / COP
Outlet water temp. A10/35 9.20 kW / COP 4.3 15.90 kW / COP 4.1
Outlet water temp. A7/35 8.50 kW / COP 3.9 14.80 kW / COP 3.8
Outlet water temp. A2/35 7.10 kW / COP 3.3 12.10 kW / COP 3.4
Outlet water temp. A-7/35 6.30 kW / COP 2.8 9.70 kW / COP 2.7
Cooling capacity / COP
Outlet water temp. A30/18 4.5 kW / COP 3.0 9.2 kW / COP 2.9
Sound pressure level at distance dB(A) 34 34
Heat carrier flow nominal m3/h 1.5 2.4
Internal pressure drop heat carrier kPa 10 15
Air flow m3/h 2900 5800
Compressor type Scroll Scroll Refrigerant R404A kg 1.9 2.6
Control Voltage V 230 230 Supply Voltage 230V 1-N, 50 HZ 400V 3-N, 50 HZ Nominal power consumption at A2/W35 KW 2.4 3.9 Starting current A 90 or 20 with soft starter 60 or 25 with soft starter Nominal current A 24.0 12.5 Nominal current at A2/W35 A 10.4 7.7 Device connection to heating system Inch G1 1” external G1 1” external Type of defrosting Reverse cycle Reverse cycle
Dimensions
Size (H X W X D) mm 1.500 x 790 x 650 1.500 x 790 x 650 Weight kg 150 180
TECHNICAL DATA
Type GDH240-Air
Certificate and protection CE / IP24
Installation location Indoor / Outdoor
Operation temperature limits
Air ºC -25 to +35
Heat water flow ºC Up to 60
Heating capacity / COP
Outlet water temp. A10/35 31.80 kW / COP 4.1
Outlet water temp. A7/35 29.60 kW / COP 3.8
Outlet water temp. A2/35 24.20 kW / COP 3.4
Outlet water temp. A-7/35 19.4 kW / COP 2.7
Cooling capacity / COP
 Outlet water temp. A30/18 21.3 kW / COP 2.8
Sound pressure level at distance dB(A) 42
Heat carrier flow nominal m3/h 4.8
Internal pressure drop heat carrier kPa 30
Air flow m3/h 11600
Compressor type 2x Scroll Refrigerant R404A kg 5.2
Control Voltage V 230 Supply Voltage 400V 3-N, 50 HZ Nominal power consumption at A2/W35 KW 7.8 Starting current A 2x 60 or 2x 25 with soft starter Nominal current A 25 Nominal current at A2/W35 A 15.4 Device connection to heating system Inch G1 1” external Type of defrosting Reverse cycle
Dimensions
Size (H X W X D) mm 1.500 x 1.380 x 650 Weight kg 360
EC Declaration of Conformity
The undersigned GDH Energy Guangzhou Co., Ltd.
No. 340 Dongjiang Road, Zhongye Building, Free Trade Zone, GETDD, 510730 Guangzhou, China
hereby confirm that the design and construction of the product(s) listes below, in the version(s) placed on the market by us, conform to the relevant requirements of the applicable EC directives.
This declaration becomes invalidated if any modifications are made to product(s) without our prior authorization.
Designation
EC Directives
Air-to-water heat pumps EC Low Voltage Directive for outdoor installation, containing R404A/R407C EC EMC Directive Pressure Equipment Directive
Typ(e):
Harmonized EB Standards:
GDH70-Air EN 255:1997 GDH120-Air EN 378:2000 DIN 8901
DIN EN 60335-1 (VDE 0700 T1):2005-07 EN603351:2002+A1:2004+A1:2004 DIN EN 60335-2 (VDE 0700 T40):2004-03 EN 60335-2-40:2003 DIN EN 55014-1 (VDE 0875 T14-1):2003-09 EN 55014-1:2000+A1:2001+A2:2002 DIN EN 55014-2 (VDE 0875 T14-2):2002-08 EN 55014-2:1997+A1:2001 DIN EN 61000-3-2 (VDE 0838 T2):2001-12 EN 61000-3-2:2000 DIN EN 61000-3-3 (VDE 0838 T3):2002-05 EN 61000-3-3:1995+Corr.: 1997+A1:2001
National Directives
VBG20 DruckbehV DIN 8901 DIN 8975 SVTI
GDH Energy Guangzhou Co., Ltd. Guangzhou, China, 2009-07-01
Subject to modification. Images are for demonstrations.