GD AQUALINE 1100, AQUALINE1600, AQUALINE 2700, AQUALINE2100 Installation & Operating Instructions Manual

AQUALINE 1100/1600/2100/2700
Installation Operating & Maintenance Instructions
4990671000 February 2008
Contents
4990671000 February 2008 2
Contents
Contents
1. Technical data . . . . . . . . . . . . . . . . . . . . . 5
1.1 Machine data . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . .6
1.2.1 Connection versions. . . . . . . . . . . . . . . . . . . . 7
1.3 Location of lubricating points . . . . . . . . . . . . . 8
1.4 Operating fluid . . . . . . . . . . . . . . . . . . . . . . . .8
1.5 Drive. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
2. Safety instructions and hazard alerts . . 9
2.1 Use for intended purpose. . . . . . . . . . . . . . . .9
2.2 Acceptance and monitoring . . . . . . . . . . . . . . 9
2.3 Hazard alerts and symbols. . . . . . . . . . . . . . . 9
2.4 Safe working . . . . . . . . . . . . . . . . . . . . . . . . .9
3. Transport, Storage and Scope of
delivery . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.1 Transport . . . . . . . . . . . . . . . . . . . . . . . . . . .11
3.2 Storage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.3 Scope of delivery . . . . . . . . . . . . . . . . . . . . . 11
4. Installation . . . . . . . . . . . . . . . . . . . . . . . 12
4.1 System setup with cooler in main flow . . . . .12
4.2 System setup with cooler in side flow . . . . .13
4.3 Point of installation and fastening . . . . . . . .15
4.4 Connections and piping . . . . . . . . . . . . . . . . 15
4.5 Protection against intake of dirt and
residue . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
4.5.1 Suction line. . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.5.2 Vacuum filter . . . . . . . . . . . . . . . . . . . . . . . .16
4.5.3 Safety dome . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.5.4 Safety bowl. . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.6 Safety and monitoring instruments. . . . . . . . 16
4.6.1 Vacuum gauge . . . . . . . . . . . . . . . . . . . . . . . 17
4.6.2 Vacuum filter . . . . . . . . . . . . . . . . . . . . . . . .17
4.6.3 Non-return valve. . . . . . . . . . . . . . . . . . . . . . 17
4.6.4 Thermometer . . . . . . . . . . . . . . . . . . . . . . . . 17
4.6.5 Safety valve . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.6.6 Pressure gauge . . . . . . . . . . . . . . . . . . . . . .17
4.6.7 Guard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
4.6.8 Bellows. . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
4.6.9 Speed monitor . . . . . . . . . . . . . . . . . . . . . . .18
4.7 Operating fluid . . . . . . . . . . . . . . . . . . . . . . .18
4.7.1 Operating water back-cooling and
storage tank . . . . . . . . . . . . . . . . . . . . . . . . .18
4.7.2 Cell Ventilation . . . . . . . . . . . . . . . . . . . . . . .19
4.8 Drive. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
4.8.1 Drive by hydraulic motor . . . . . . . . . . . . . . .19
4.8.2 Drive by flexible clutch . . . . . . . . . . . . . . . . .19
4.8.3 Drive by propeller shaft . . . . . . . . . . . . . . . .19
4.9 Drive by Vee belt . . . . . . . . . . . . . . . . . . . . .20
5. Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5.1 Testing the system . . . . . . . . . . . . . . . . . . . . 22
5.2 Operating liquid . . . . . . . . . . . . . . . . . . . . . . 22
5.3 Stop slide and shut-off valves . . . . . . . . . . .22
5.4 Direction of rotation . . . . . . . . . . . . . . . . . . . 22
5.5 Drive. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
5.6 Inspection of speed, vacuum and pressure .22
5.6.1 Speed. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
5.6.2 Vacuum and vacuum gauge . . . . . . . . . . . .22
5.6.3 Pressure at pressure gauge. . . . . . . . . . . . .22
6. Operation . . . . . . . . . . . . . . . . . . . . . . . . 23
6.1 Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
6.2 Regular inspections . . . . . . . . . . . . . . . . . . . 23
6.2.1 Safety valve . . . . . . . . . . . . . . . . . . . . . . . . . 23
6.2.2 Water stop valve . . . . . . . . . . . . . . . . . . . . .23
6.2.3 Inspection intervals . . . . . . . . . . . . . . . . . . .24
6.3 Operating the liquid ring pump . . . . . . . . . . . 24
6.3.1 Operating water consumption and control . .24
6.4 Possible faults by the operator . . . . . . . . . . .25
6.5 Extended period of non-use . . . . . . . . . . . .25
6.6 Troubleshooting . . . . . . . . . . . . . . . . . . . . . .26
7. Maintenance . . . . . . . . . . . . . . . . . . . . . 28
7.1 Warranty. . . . . . . . . . . . . . . . . . . . . . . . . . . .28
7.2 Maintenance, maintenance
schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
7.2.1 Water back-cooling with air . . . . . . . . . . . . .28
7.2.2 Liquid ring pump . . . . . . . . . . . . . . . . . . . . . .28
7.2.3 Vacuum filter (GDD types) . . . . . . . . . . . . . .28
7.2.4 Vee belts and Vee belt tension. . . . . . . . . . .29
7.2.5 Non-return valve . . . . . . . . . . . . . . . . . . . . . .29
7.3 Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . .29
7.3.1 Antifriction bearings . . . . . . . . . . . . . . . . . . .29
7.3.2 Shaft seal . . . . . . . . . . . . . . . . . . . . . . . . . . .30
8. Spare parts . . . . . . . . . . . . . . . . . . . . . . 31
8.1 Spare parts. . . . . . . . . . . . . . . . . . . . . . . . . .31
9.
Preface
4990671000 February 2008 3
Preface
Dear customer,
Your new Water Ring Pump is the outcome of inten­sive development based on decades of experience as a supplier of vacuum pumps and compressors to the suction vehicle market. Advanced manufacturing methods in combination with highest quality standards and extensive testing ensure reliability, a high degree of availability and long life of your machine.
This machine requires proper handling, especially un­der severe operating conditions. Startup, operation and maintenance must must therefore be performed only by trained and authorised personnel.
These Operating Instructions contain all required infor­mation and have been written for those in charge of the unit. The machine will give smooth service over a long period provided these Instructions are followed. The Operating Instructions are a component part of the product and must be kept available for the operating personnel. You will appreciate that we cannot be held responsible for any damage caused due to non-com­pliance with these Instructions.
Please note that repairs should only be undertaken by authorized repair centres using original parts. Other­wise our guarantee will be void.
We wish you success with your water ring pump from Gardner Denver Drum. If you have any questions which are not answered in this manual, please call us.
Sincerely yours,
Gardner Denver Drum Ltd.
Mode of operation, Design versions
4990671000 February 2008 4
Mode of operation, Design versions
Mode of operation
Liquid compressor vacuum pumps, like rotary com­pressor vacuum pumps, work on the displacement principle, providing uniform, low-pulsation flow.
Single-shaft liquid ring machines have a housing with cylindrical bore and an eccentrically mounted rotor. The housing is partly filled with liquid, which the rota­tion of the rotor forms into a rotating liquid ring in con­tact with the housing. Together with the hub of the eccentrically mounted rotor, it forms a sickle-shape working space divided by the vanes of the rotor.
The rotation of the rotor causes the cell volume to be­come large at the intake side. This creates a vacuum which sucks air into the cell, which is open towards the air intake. As the rotation continues, the cell closes and the cell volume becomes smaller. As a result of this, the enclosed air is compressed and pushed out of the pressure outlet.
The cells are charged and drained through openings in the housing covers located on either side of the rotor faces.
This functional principle causes the machine to work at nearly isothermal compression due to internal cooling.
The first digit of the references to illustrations in these Operating Instructions refers to the chapter in which you find the illustration. The illustrations within each chapter are numbered consecutively. The last number of an illustra­tion reference denotes the position number of the item in the references illustration. For example, the reference (7.2 / 3): second illustration in chapter 7, item number 3.
This symbol precedes information that refers to units used in a potentially explosive atmos­phere.
Design versions
The design versions differ in their direction of rotation.
Type code:
AQUALINE 2100 R
Liquid ring pump, operating
medium: water
1)
1)
Water is the working liquid commonly used by suction vehicles.
Machine size R = CW rotation
L = CCW rotation
Technical data
4990671000 February 2008 5
Technical data
1. Technical data
1.1 Machine data
Liquid ring pumps of the Aqualine series use water as operating fluid.
Conveyed medium
Air of maximum intake temperature of 60 °C.
Operating fluid
Water or water-glycol mixture
Maximum outlet temperature
The temperature at the outlet of the liquid compressor vacuum pump should be restricted to maximum 65 °C.
The machine number and other important machine data are given on the machine’s nameplate.
Liquid ring pump Aqualine
1100
Aqualine
1600
Aqualine
2100
Aqualine
2700
Rated operating vacuum (absolute) mbar 400 400 400 400
Maximum gauge pressure in
compressor operation
1)
barg 1.5 1.5 1.5 0.5
At 400 mbar (absolute) intake pressure
volume flow rate final gauge pressure power consumption on shaft
m
3
/h
barg
kW
900
0.0 32
1,300
0.0 46
1,700
0.0
60.5
2,075
0.0 74
At 1,000 mbar (absolute) intake pressure
volume flow rate final gauge pressure power consumption on shaft
m
3
/h
barg
kW
840
0.5 33
1,270
0.5 50
1,660
0.5 65
2,100
0.5 84
Possible max. intermitant vacuum (absolute)
approx.
2)
mbar 130 130 130 130
Rated speed
3)
1/min 1,500 1,500 1,500 1,500
Mass moment of inertia, incl. liquid ring kgm
2
0.7 1.0 1.3 1.6
Sound pressure at 7 m distance at 400 mbar (absolute)
dB(A)66687072
Weight of the basic machine kg 150 165 180 195
All data relate to water at 20°C inlet temperature as the operating fluid and intake temperature of 20°C. Operating fluids other than water or water-glycol mixture require prior consultation with the manufacturer. The data and illustrations reflect the current state. The right of modifications is reserved.
1)
Secure by providing a safety valve.
2)
Dependant on water temperature.
3)
The permitted speed range from 1,100 to 1,500 rpm must be observed.
Technical data
4990671000 February 2008 6
1.2 Dimensions
Fig. 1.1 Dimensions of Aqualine 1100 to 2700
E
F
G
H
Air
Water
b
590
448
Ø 48
k6
80
270
a
c
M16
26
AB
45°
479
370
157
210
18
200
274
50
122
190
500
52
147,5
C
D
a b c Machine serial no. Connection
for
additional
ventilation
Z
1) 2) 3)
1)
One-side cell venting Z only for connection to the machine numbers in this table.
2)
Second venting lines on opposite side required for machine serial nos. 910 390/.., 910 400/.. et 910 410/.. for housing pipe socket
Z = G 1
1
⁄4" and OD = 28 mm.
3)
If conditions at the installation site require a second cell venting line, the minimum diameter in the table above also applies.
Ø Cell
venting
line I/D
Connection
for liquid ring fluid
Ø
Operating
water line
Weight
[mm] [mm] [mm]
cw
rotation
ccw
rotation
[mm] [kg]
Aqualine
1100
170 355 630 910 389/.. 910 381/..
Optional
G 1"
or
G 1
1
⁄2"
28
G 1
1
⁄2"R 1
1
⁄2"
150
Aqualine
1600
260 400 720 910 399/.. 910 382/.. 165
Aqualine
2100
350 445 810 910 409/.. 910 383/.. 180
Aqualine
2700
450 495 910 910 439/.. 910 440/.. G 1
1
⁄2" 52 195
A
A-Side BB-Side C Connecting flanges with connecting variations (see figure 1.2) D Drain for the liquid ring fluid G 3/4" E Connection for an additional ventilation Z
F Drain for an additional ventilation G 3/4" G Connection for the liquid ring fluid G 11/2";
Operating water inflow duct – drain
H Covered on A-side and B-Side
Technical data
4990671000 February 2008 7
1.2.1 Connection versions
Fig. 1.2 Connection sizes for Aqualine 1100 to 2700 versions (in mm)
Version I Version II Version III Version IV Version V Version VI
DEDEDEDEDEDE
Aqualine 1100 335 670 263 526 373 746 263 526 297 594 297 594
Aqualine 1600 380 760 308 616 418 836 308 616 342 684 342 684
Aqualine 2100 425 850 353 706 463 926 353 706 387 774 387 774
Aqualine 2700 475 950 403 806 513 1026 403 806 437 874 437 874
Version I
E
D
506
Part number 910 423 00
Version II
E
D
E
D
E
D
E
D
E
D
577
504
616
504
540238
28
Part number 910 423 00
Version II
8 x Ø14
Flange in acc. with DIN 28 459 – DN125
Flange in acc. with DIN 28 459 – DN125
Version I
Version III
Version IV
Version IVVersion III
Version V
Version VI
Version VIVersion V
Ø204
Ø204
Ø176
Ø176
Ø125
Ø125
105
105
105
105
Part number
910 424 00
Part number 910 427 00
Part number 910 427 00
Part number
910 424 00
Technical data
4990671000 February 2008 8
1.3 Location of lubricating points
1.4 Operating fluid
The operating fluid is water or water-glycol mixture. Operating fluids other than water or water-glycol mix­ture require prior consultation with the manufacturer.
1.5 Drive
From the vehicle engine:
by auxiliary drive and propeller shaft
by Vee belt, whereby the Vee belt pulley is installed
on the free shaft end
by hydraulic drive
From other engine, electric or hydraulic motor:
by flexible coupling
by Vee belt, whereby the Vee belt pulley is installed
on the free shaft end
For more details, see Installation section.
Fig. 1.3 Lubrication fittings and venting valve
X
Air
Water
X 2:1
0
Cover the lubrication fit­tings and the venting valve when final painting!
Safety instructions and hazard alerts
4990671000 February 2008 9
Safety instructions and hazard alerts
2. Safety instructions and hazard alerts
2.1 Use for intended purpose
The intended purpose of the liquid ring pump is to con­vey and compress filtered air. The entrainment of small amounts of water in the air is possible. Any use other than or beyond that described above is contrary to the intended purpose.
Following the operating data and the specified mainte­nance are also part of the use for the intended pur­pose.
Liquid ring pumps of the aqualine series comply with the requirements of directive 94/ 9/EC (ATEX) and belong to equipment group II, catagory 2, temperature class T4 (135°C maximum surface temperature), zone 1,2 (gas atmosphere).
Changes and repairs must only be made with the manufacturer’s written permission. Units of the Aqualine series are designed for integration in a higher-level machine. The new risks created by the integration must be assessed by the manufacturer of the new machine.
2.2 Acceptance and monitoring
The liquid ring pump as a unit is not subject to any ac­ceptance or monitoring requirements.
Any special provisions in effect at the site of the liquid ring pump must be observed by the operator.
2.3 Hazard alerts and symbols
This hazard alert symbol indicates important safety messages in this booklet. Carefully read the message that follows and act as required. Make certain that the safety instructions are known to all who need to know them!
“CAUTION” indicates provisions and regula­tions preventing damage to the machine.
Symbol for potentially explosive atmosphere.
Here the symbol draws attention to provisions or information which must be observed if the machine is to be used in a potentially explosive atmosphere.
This symbol indicates information of particular importance to the operator of the machine.
This symbol indicates that no unauthorized persons must enter this area.
Risk of burning! This symbol indicates a hot surface.
This symbol indicates that you must wear ear protectors.
This alert symbol indicates that environmental protection requirements must be observed.
2.4 Safe working
The liquid ring pump has been designed and built to good engineering practice and the accepted rules of safety. However, hazardous situations may still arise in using the machine with the possibility of personal injury or death of the operator or other persons and damage of the machine or other objects.
Air is the only conveyed medium.
Use the liquid ring pump only in good working con­dition and for the intended purpose. Be alert to possible hazards. Defects impairing safety must be repaired without delay.
Modifications, additions and alterations of the liq­uid ring pump that are likely to impair its safety are forbidden unless agreed with the manufacturer.
The machine must only be used with delivery and intake lines connected.
All warnings on the liquid ring pump must be legi­ble and observed at all times.
Work on electrical equipment must be carried out by a trained electrician applying the rules of the trade.
All persons carrying out work on the liquid ring pump must have read these Operating Instruc­tions, especially the chapter on safety, before start­ing work. It may be too late to refer to these Instructions when work has already started!
Operation and maintenance of the machine must only be carried out when the machine is not run­ning.
Safety instructions and hazard alerts
4990671000 February 2008 10
Secure the drive against starting before beginning to work on the machine.
When work is carried out on the system, the latter must not be under pressure or vacuum. On the vehicle: Close the stop slide valve. Bleed or vent the pressure line between the system and the stop slide valve. Relieve elevated pressure manually at the safety valve. Observe the pressure gauge reading.
Remove the drive guard only when the machine is not running.
Remove the safety guard only when the machine and the pressure line have cooled down.
Before starting the machine, make certain that all guards are installed and in place.
Environmental protection requires that all emerging fluids, e.g., cooling water, cooling oil or lubricant residue, are collected and dis­posed of as prescribed.
Transport
4990671000 February 2008 11
Transpor t
3. Transport
Symbols on the packaging:
Top
Fragile
Keep dry
3.1 Transport
Avoid any use of force and load / unload the packages with care.
Attach lifting equipment only at the firmly installed eye bolts (see figure 3.1).
Remove transport safeguards, where provided.
3.2 Storage
Store the machine in a dry and heated room until in­stallation. Remove the covers on and pressure open­ings only at the time of actual installation.
3.3 Scope of delivery
The contents of the consignment are described in the delivery note. Check for short delivery and transit dam­age without delay. Claims for damage in transit and short delivery can only be accepted if made in writing without delay.
Fig. 3.1 Lifting eye bolt
Installation
4990671000 February 2008 12
Installation
4. Installation
Figures 4.1 and 4.2 show a typical Aqualine liquid ring pump system completely installed. Other arrangement versions are also possible.
4.1 System setup with cooler in main flow
Fig. 4.1 Components of a system with liquid ring pump – Cooler in main flow
6
min
max
7 1 8 3 4 9 1a 5 19 12 11
10141518182171314155
16
15
20
For details of shaded area see page 14
1 +1a Vent line 2 Vacuum filter 3 Liquid ring pump 4 Non-return valve 5Bellows 6 Safety valve
7 Pressure gauge 8 Thermometer 9 Operating water tank 10 Four-way directional control
valve
11 Safety dome and float valve
12 Vehicle tank 13 Operating water cooler 14 Water stop valve 15 Drain valves 16 Safety bowl with float valve 17 Flexible mounting
18 Vacuum gauge 19 Float switch 20 Water inlet for filling system
* For dimensions of the vent line, see table page 6
Installation
4990671000 February 2008 13
4.2 System setup with cooler in side flow
Notes
Installation and start-up must only be undertaken by trained persons. Damage due to improper han­dling is not included in the guarantee terms.
The machine is delivered in fully assembled condi­tion. It must not have suffered damage in transit.
Please make certain that the rotor shaft can be rotated by hand. If this is not the case, inform our service staff.
Lift the machine using only the securely installed eye bolts.
For use in a potentially explosive atmos­phere,all parts of the equipment must satisfy the requirements for the zone in which they are used.
Note that it may be necessary to provide equipotential bonding between the equip­ment and the truck. The safe operation of the vacuum pump in a potentially explosive at­mosphere requires that all safety instructions in our operating instructions and comple­mentary instructions are strictly observed.
Fig. 4.2 Components of a system with liquid ring pump – Cooler in side flow
54
Z
min
max
1 6 8 1a 7 5 3 14 19 9 12 11
101415171320
21
18182
16
15
15
For details of shaded area see page 14
1+1a V
ent line 2 Vacuum filter 3 Liquid ring pump 4 Non-return valve 5Bellows 6 Safety valve
7P
ressure gauge 8 Thermometer 9 Operating water tank 10 Four-way directional control
valve
11 Safety dome and float valve
12 Vehicl
e tan
k
13 Operating water cooler 14 Water stop valve 15 Drain valves 16 Safety bowl with float valve 17 Flexible mounting
18 V
acuum gauge 19 Float switch 20 Pump 21 Water inlet for filling system
* For dimensions of the vent line, see table page 6
Installation
4990671000 February 2008 14
Details of figure 4.1
Details of figure 4.2
15a Drain valve for the
liquid ring fluid
15b Drain valve in
cell venting line
15c Drain valve after
water stop valve
15d Drain valve for the
operating water cooler
Fig. 4.3 Components of a system with liquid ring pump – Cooler in main flow (detail)
Z
15b
15a
15c
15d
15a Drain valve for the
liquid ring fluid
15b Drain valve in
cell venting line
15c Drain valve after
water stop valve
15d Drain valve for the
operating water cooler
Fig. 4.4 Components of a system with liquid ring pump – Cooler in side flow (detail)
15b
15c
15a
15d
Installation
4990671000 February 2008 15
4.3 Point of installation and fastening
The point of installation on the vehicle must
be easy to access,
be protected from dirt, the impact of stones and water splash.
leave sufficient space for the connection of operat­ing water, the suction and pressure lines and the operating water drain.
be accessible for maintenance (for regreasing the grease barrier).
Fasten the machine at the 4 feet (M16 tapped holes). The machine can be fastened directly onto a suitable frame. The minimum depth of thread engagement is 23 mm.
Framework must be of sufficient strength to support machine in operation and while vehicle is driven.
The four fastening points (machine foot supports) must be in exact alignment.
For dimensions and weights, see chapter 1. "Technical data".
The machine must be adequately earthed. An equipotential earth bonding strap should be securely fastened between the machine body and a suitable point on the vehicle frame.
Ensure that the machine and all ancilliaries are earthed in accordance with BS5958 Pt1: 1991;
'Control of undesirable Static Electricity'.
4.4 Connections and piping
For regular service of the liquid ring pump the suction, pressure lines, operating water supply, and water drain line must be connected to the machine
The various possibilities of the suction and pressure line connections are illustrated in figure 4.5 for ma­chines of clockwise and counterclockwise rotation.
The suction and pressure line, respectively, can either be connected on the A side or B side. The same ap­plies to the operating water supply, the drain line and the venting line.
As regards piping, the minimum pipe diameters in the table below are recommended.
Fig. 4.5 Aqualine 1100 to 2700 connection versions
Aqualine 1100 1600 2100 2700
Suction line DN 125
(5")
DN 125
(5")
DN 125
(5")
DN 125
(5")
Pressure line DN 125
(5")
DN 125
(5")
DN 125
(5")
DN 125
(5")
Top view
clock wise Operation
Suction side
connection on one
flange optional
Pressure side
connection on one
flange optional
Top view
counter clock wise Operation
Suction side
connection on one
flange optional
Pressure side
connection on one
flange optional
Installation
4990671000 February 2008 16
4.5 Protection against intake of dirt
and residue
4.5.1 Suction line
The pipe must be corrosion-resistant inside. Clean the pipe inside before installing it. Remove all welding beads, scale and rust.
The suction line should be sufficiently large. The pipe diameter must at least meet the diam­eter specifications in chapter 4.4. Otherwise the machine will be overloaded!
Wrong design of the suction line causes forfei­ture of all guarantee claims on Gardner Denver
4.5.2 Vacuum filter
Install the vacuum filter directly upstream the machine. The filter protects the machine from the ingress of im­purities and attenuates the suction noise.
Observe the flow direction when installing the filter. The filter insert shall be removable from the filter for maintenance.
4.5.3 Safety dome
In addition to the float valve, a splash guard must be in­stalled in the safety dome of the vehicle tank. The splash guard prevents liquid splash into the system.
4.5.4 Safety bowl
The safety bowl (at the lowest point of the suction line) must be so designed that
entering air does not hit the liquid level directly,
sufficient calming space is available,
the filter element does not dip into the liquid (also filters with non-absorbing texture become satu­rated due to the capillary action of the liquid).
A filter element in the safety bowl is not required if a vacuum filter type SFA-F is used.
To inspect the function of the optimized gravity sepa­rator illustrated in figure 4.6 proceed as follows:
When the amount of water to be separated is sucked in, that amount must remain in the bowl.
We will be glad to assist you in designing and inspect­ing your safety bowl.
4.6 Safety and monitoring instruments
The safe operation of the machine (i.e., the operation of the machine without risk) requires the following safety and monitoring equipment (also see figure 4.1 and figure 4.2).
All items of safety equipment must be inspected for proper function at regular inter­vals (see manufacturer’s technical instruc­tions). It is forbidden to change, block or render safety guards ineffective in any way.
The operating safety of the system (i. e., the safe op­eration of the machine requires the following safety and monitoring instruments:
At the suction side:
Vacuum gauge
Vacuum filter
Non-return valve
Bellows
At the pressure side:
Safety valve
Fig. 4.6 Safety bowl
1
2
3
4
5
6
1 Intake bend 2 Baffle plate 3 Double perforated plate
4Drain cock 5 Two floating balls 6 Four guide rods
Installation
4990671000 February 2008 17
Thermometer
Pressure gauge
Bellows
Operating water supply line:
Solenoid valve for opening or closing the operating water supply
Guard:
Protection against rotating parts
Protection of the machine
Speed monitor
Install drain cocks for the operating fluid to ensure that the complete system can be drained of liquid.
Non-compliance causes forfeiture of all guar­antee claims on Gardner Denver.
4.6.1 Vacuum gauge
To monitor the permitted operating vacuum as speci­fied in chapter 1.1 "Machine data", a vacuum gauge is to be installed downstream the non-return valve at the suction side.
To measure the pressure loss in the filter, we also rec­ommend the installation of a vacuum gauge upstream of the filter.
4.6.2 Vacuum filter
The vacuum filter protects the machine from coarse mechanical impurities. The vacuum filter must be in­stalled in the suction line.
Note on installation the flow direction and required space for replacing the filter insert.
4.6.3 Non-return valve
The non-return valve prevents the entry of water from the pump to the intake line when the machine is not running.
Install the non-return valve in the suction line as near to the machine as possible. Observe the direction of flow through the valve.
4.6.4 Thermometer
To monitor the compression end temperature, install the thermometer in the pressure line directly down-
stream the pressure socket. For this, install a pipe cou­pling R
1
⁄2". The immersion depth of the thermometers
must be equivalent to one half the diameter of the pipe.
The indicating range of the thermometers must 0 to 100 °C.
4.6.5 Safety valve
A non-shutting off safety valve shall be installed down­stream every compressor. The valve must be dimen­sioned and set so that the highest permitted operating pressure cannot be exceeded by more than 10%. The valve must be capable of blowing off the entire volume conveyed by the liquid ring pump. This valve must also be suitable for manual venting.
If the safety valve is handled or located improp­erly or tampered with, there is RISK OF EXPLOSION due to pressure and temperature rise!
The following points must be observed when installing the safety valve:
Install the valve directly downstream the liquid ring pump, upstream of any other shutoff elements (especially shutoff valve),
the component marking and seal must be visible.
the setting must correspond to the maximum per­mitted operating pressure (see chapter 1.1 "Machine data"),
the setting must be protected against tampering,
the valve must not be blocked,
the safety valve must not be used for control of the air volume in compression service.
Make a weekly check of the function of the safety valve by actuating the manual vent while the machine is running.
4.6.6 Pressure gauge
Provides pressure readings during normal machine service. Measuring range in accordance with the oper­ating pressure. Install directly downstream the pres­sure connection.
Installation
4990671000 February 2008 18
4.6.7 Guard
The drive of the machine and the hot pressure lines must be protected by guards.
It must not be possible to touch rotating or reciprocat­ing machine parts accidentally.
4.6.8 Bellows
To limit the connection forces in the suction and pres­sure line of the liquid ring pump, vacuum-tight and pressure-tight bellows must be installed.
At the same time, the bellows isolate solid-borne noise of the suction and pressure lines.
4.6.9 Speed monitor
Speed control of the liquid ring pump and a speed in­dicator in the operating area of the machine are recom­mended. For permitted speed range, see chapter 4.8 “Drive”.
4.7 Operating fluid
For start-up, the liquid ring pump requires an amount of water sufficient to form the liquid ring.
Therefore, when installing the pump, make certain that the water tank is located so that when the operating water feed valve is open and the tank contains a mini­mum of water, the liquid ring pump fills with water up to the middle (also see Operating Instructions). If this is not ensured there may be problems in starting the pump (no conveyed medium flow).
If the water tank is located so that the liquid level is above the middle of the liquid ring pump, an automatic water stop valve must be installed in the operating wa­ter supply line. This valve must open when the pump starts and close when it is stopped to prevent inunda­tion of the pump.
If the liquid ring pump is installed above the water level in the tank, a pump is required to ensure the operating water supply. The design of that pump must be such that the liquid ring pump is supplied with sufficient op­erating fluid. We will be glad to assist you in selecting the right pump.
Because liquid is removed from the working space and also because heat must be dissipated, the liquid ring pump requires a constant supply of operating fluid. For this, the covers of the machine have a G 1
1
/4" connec­tion (only one operating water supply connection is needed, i.e. either on the A side or B side).
If the piping has sufficiently low resistance (feeding line diameter R1
1
/2" to R2", depending on pipeline length and layout) no recirculation pump may be needed for the operating water supply provided the arrangement of the liquid ring pump is such that the middle of the pump is at a lower level than the minimum liquid level in the storage tank.
A level control of the operating liquid must be­provided if the machine is operating in a poten­tially explosive atmosphere.
4.7.1 Operating water back-cooling and
storage tank
A circulation cooling system is required for back-cool­ing the operating water. The circulation cooling must be able to handle the following amounts of heat.
To reduce the loss of liquid by the exhaust air to a min­imum and to ensure sufficient operating hours of the system, a combined operating water storage and sep­arating tank is needed. For minimum sizes, refer to the table below.
The above minimum water storage figures relate to systems with water back-cooling.
Systems without water back-cooling require substan­tially larger storage tanks to ensure sufficient operating hours of the liquid ring pump without running the risk that the recommended limit temperature of 55 °C the operating water inflow is exceeded.
Suction dramatically reduces at higher temperatures.
Aqualine
1100 1600 2100 2700
Amount of heat to be dissipated
at 1.5 bar
(g)
at 0.5 bar
(g)
at 400 mbar at 200 mbar
kW 50
25 29 33
65 32 39 48
78 39 48 57
50 58 67
Recom­mended pipe diameter oper­ating water line
R1
1
/2"R11/2"R11/2"R11/2"
Recom­mended mini­mum tank size
ltr 250 350 450 600
Recom­mended water volume in the tank
ltr 150 225 300 400
Installation
4990671000 February 2008 19
4.7.2 Cell Ventilation
The cell ventilation is required to ensure the proper op­eration of the liquid ring pump at low intake pressure down to total residual pressure. The ventilation line is connected on the A-side and B-side housing covers (see figure 1.1 connection socket “Z”).
Aqualine models 1100/1600/2100 need a ventilation line with a pipe internal diameter Øi = 28 mm. Aqualine model 2700 required pipe internal diameter Øi = 52 mm. The specified cross sections refer to about
2.5 meters line length. The ventilation line must be in­stalled at an upward gradient and the connection is made on the “clean side” of the water separation ves­sel.
Make sure the entrained air line is the correct size. Ensure sufficient fresh air can enter the work space of the liquid pump via the ventila­tion line. This is done by running the liquid pump with a closed intake line. If a loud noise is heard, the entrained air flow rate is insuffi­cient. In this case a larger ventilation line must be installed.
If you want to drain all operating fluid from the liquid ring pump, open both water drains (see figure 1.1).
4.8 Drive
The direction of rotation must agree with the direction of the arrow on the liquid ring pump.
Permitted speed range: 1,100 to 1,500 rpm
Ensure the drive speed increasing or reducing ratios are observed (belt drive, auxiliary drive of vehicle, ...)
We recommend a speed monitor at the liquid ring pump with an indicator in the operating area.
Check the speed after installing the liquid ring pump and put up a note for the operator of the vehicle.
If the machine is powered by a combustion engine, the engine must have speed control which limits the speed to a permitted level if the power requirement drops.
The axial thrust of the drive must not be trans­ferred to the rotor shaft. Install the drive components on the rotor shaft using the available M16 thread. Do not use a hammer or other impact device to install the drive components on the rotor shafts
A coupling guard must be fitted as appropriate.
4.8.1 Drive by hydraulic motor
The selection and installation of the hydraulic motor is the responsibility of the installation firms.
We can supply a matching flange and coupling.
After mounting the flange, the motor side coupling hub must not transfer axial thrust onto the liquid ring pump.
4.8.2 Drive by flexible coupling
If the pump is coupled directly to the drive (e.g. diesel engine) a torsionally flexible coupling that compen­sates most of the drive irregularities must be selected according to the specifications of the engine maker.
Align the coupling exactly as prescribed by the manufacturer.
4.8.3 Drive by propeller shaft
The propeller shaft drive must
incorporate a splined shaft,
be balanced,
have smallest possible angles and be as short as
possible.
The centre axes of the propeller shaft flanges must be parallel with each other.
Installation
4990671000 February 2008 20
The mounting flange of the propeller shaft must be in­stalled on the drive shaft of the compressor.
Bolt the propeller shaft to the mounting flange of the liquid ring pump shaft.
The resulting angle of bend must not exceed 15° at 1,500 rpm speed.
Ensure propshaft spline is correctly engaged. Observe marking.
4.8.4 Drive by Vee belt
If the engine speed must be raised or reduced, Vee belt drive is recommended. Observe the rated speeds in chapter 1.1 "Machine data".
The belt pulleys in the table below can directly be in­stalled on the free shaft end.
Installation of the Vee belt drive
The axis of the driving and driven machines should
be parallel.
The grooves of the belt pulleys must be inline.
Vee belt lenghts should be the same to ensure uni-
form belt tension.
• The Vee belt tension is correct when the
installed and tensioned belt can be deflected by the pressure of the thumb by 16 to 20 mm for every 1000 mm axial distance.
Ensure the bending moment exerted by the belt drive on the shaft of the driving machine is within the limits recommended by the manufac­turer.
Installing the Vee belt pulley with taper lock bush
1. Clean and degrease all blank faces. Place the pul-
ley and the bush one in the other. Bring holes in alignment with each other and install screws loosely.
2. Push the pulley with the bush on the shaft, align and
uniformly tighten the screws.
Fig. 4.7 Mounting the propeller shaft
Aqualine 1100 1600 2100 2700
Belt profile XPB XPB XPB XPB
Belt pulley minimum
diameter D
W
1)
1)
Consult the manufacturer if smaller pulleys are to be used.
mm 280 280 280 280
Max. gauge pressure with Vee belt drive
bar
ü
1.5 1.5 0.5 0.5
Number of belts in pressure service
4555
Number of belts in vacuum service
4455
max. 15 at 1500 [1/min]
1
2
4
3
2
1 To liquid ring pump 2 Keyed shaft
3 Marking on splined joint 4From drive
Fig. 4.8 Correct Vee belt tensioning
1000 mm
16…20 mm
Dw
1
2
1 Vee belt deflection (16 to
20 mm for every 1.000 mm distance)
2 Axial distance
DWVee belt pulley diameter,
min. 280 mm
Installation
4990671000 February 2008 21
Removal
1. Take out the screws, install one as a forcing screw
in the half-thread hole in the bush and tighten. This slackens the taper lock bush.
Fig. 4.9 Installing the Vee belt pulleys
1
2
Fig. 4.10 Removing the Vee belt pulley
1
2
Installation
4990671000 February 2008 22
2. Remove the slack pulley assembly by hand; do not use a hammer as this may damage the machine.
Fig. 4.11 Removing the Vee belt pulley
Start-up
4990671000 February 2008 23
Start-up
5. Start-up
5.1 Testing the system
The correct initial commissioning and start-up after ex­tended standstill (more than 4 weeks) is essential for the optimum function of the liquid ring pump.
We recommend that you allow adequate time to com­mission the system. The liquid ring pump may be dam­aged if the correct procedure is not followed.
Damage as a result of incorrect commissioning is not covered by our warranty!
Before start-up
Inspect the liquid ring pump (for damage in transit, incorrect installation),
Inspect the drive guard and the safety guard on the pressure side for damage,
Instruct the operators,
Instruct others who need to know the operation and maintenance of the water ring pump,
Make certain that the rotor shaft can be rotated by hand.
5.2 Operating liquid
Make certain of the following points to ensure that the liquid ring pump is supplied with operating liquid:
Completely fill the operating water system, fill only up to the maximum mark in the combined operat­ing water and separating vessel.
Fill the liquid ring pump up to shaft centre, it may be necessary to observe a closed automatic water stop valve (also see chapter 6.2.4 "Operating the liquid ring pump").
Check the function of the automatic water stop valve.
Make sure that the pressure line is not blocked.
If sub-zero temperatures are likely, mix anti­freeze as specified by the manufacturer (usu­ally 33%). Alternatively drain the operating water system completely if the machine is not used.
5.3 Stop slide and shut-off valves
Inspect the installation direction of the non-return valve (see arrowed direction)
Open all manual stop slide and shut-off valves.
Switch over the four-way directional control valve to extreme position, an intermediate position is not allowed. (If the valve is set to an intermediate position, the temperature of the operating water rises and more water is lost.)
5.4 Direction of rotation
When starting the system for the first time, briefly switch on the drive to check the rotation. Observe the arrowed direction on the machine housing.
5.5 Drive
Switch on the drive and check if pressure or vacuum are produced.
5.6 Check speed, vacuum and pressure
5.6.1 Speed
Permitted speed range: 1,100 to 1,500 min-1
5.6.2 Vacuum and vacuum gauge
Permitted minimum suction pressure see nameplate
5.6.3 Pressure at pressure gauge
The maximum pressure indicated on the nameplate is permitted (also see chapter 1.1 "Machine data").
Make certain that the safety valve blows off.
Operation
4990671000 February 2008 24
Operation
6. Operation
6.1 Start-up
For normal setting the liquid ring pump (referred to as the “machine”), follow chapter 5. "Start-up".
6.2 Regular inspections
In pressure service
Check the operating gauge pressure at the pressure gauge (for permitted pressure, see machine name­plate)
In vacuum service
Check the operating vacuum at the vacuum gauge (for permitted vacuum, see machine nameplate)
Operating water inlet temperature
Recommended max. inlet temperature: 55 °C
pH
5 < pH < 8
Speed
Permitted speed range: 1,100 to 1,500 min
-1
Check the operating speed
6.2.1 Safety valve
Every compressor must be fitted with a safety valve in the pressure line that cannot be shut off. The valve should be set so that the highest permitted operating pressure cannot be exceeded by more than 10%.
The setting of the valve must be guarded against tampering.
The safety valve must not be blocked or manip­ulated.
Avoid blowing the full volume flow through the safety valve with the pressure line closed. This can produce harmful vibration.
On Initial installation and at weekly intervals check the function of the safety valve by actu­ating the manual vent while the machine is run­ning.
6.2.2 Water stop valve
Check for proper function.
Operation
4990671000 February 2008 25
6.2.3 Inspection intervals
6.2.4 Operating the liquid ring pump
The volumes of operating water required for proper op­eration of the liquid ring pump are given in the table be­low:
Note that the actual operating water requirement var­ies widely as a function of the operating vacuum / op­erating pressure.
6.2.5 Operating water consumption and control
While passing through the liquid ring pump, the con­veyed medium (air) comes into close contact with the operating medium (water). This causes the relative hu­midity of the conveyed medium to be, as a rule, 100% at the discharge side. Even if all water droplets were separated in the water storage tank or in a cyclone, the steam in the exhaust air will always cause a certain consumption of operating fluid.
The specific water discharge as a function of the oper­ating pressure and the operating water temperature can be seen in Fig. 6.1.
It follows that for Aqualine 2100 at 400 mbar operating pressure and operating water temperature of 40 °C the water loss due to steam is
1,700 [m
3
/h] x 0.016 [kg/m3] = 25.6 kg/h
That is roughly 26 [ltr/h]
In actual pump service, therefore, the following points should be noted:
The loss of water due to steam can cause a rise in the concentration of pollutants in the operating water tank, which depends on the conveyed medium; this again can change the pH of the oper­ating water.
To avoid operating water pH outside the permitted range of 5 < pH < 8, the pH should be checked regularly (daily or as dictated by experience) and the operating water changed in regular intervals. Litmus paper can be used for pH measurement.
Water can condense in long exhaust lines, espe­cially in cold weather. To prevent the outflow of condensed operating fluid from the exhaust sys­tem, the installation of an additional separator (cyclone) at the end of the exhaust line may be used.
See chapter Every 10 –
20 min while
running
Weekly If necessary
Operating speed 6.2
X
Operating pressure / operating vacuum
Nameplate
X
Operating water feed temperature 6.2 X
Actuate safety valve 6.2.1 X
Water stop valve 6.2.2 X
Replace contaminated operating water (e.g. pH, abrasive material)
X
Clean compressor and cooling unit X
Operating liquid level: Inspect the level of the operating liquid before every start and during operation of the pump. Bearings: Inspect the housing, housing covers and end covers for symptoms of overheating, abnor­mal
noise or colour daily/regularly.
Aqualine 1100 1600 2100 2700
Operating water volume at 400 mbar in [ltr/min]
50 – 70 60 – 80 70 – 90 80 – 90
Operation
4990671000 February 2008 26
If the water inlet temperature exceeds 55°C. Stop the machine immediately. Recirculate the water for half an hour or until the water temperature is below 55°C.
6.3 Possible faults by the operator
Faulty operation can cause failure of the machine.
The following must be avoided:
Underspeeding and overspeeding (see chapter 6.2 or nameplate)
Pressure above the permitted limit (see chapter
6.2 or nameplate)
Blowing off the full volume flow through the safety valve when the pressure line is closed
Vacuum below the permitted limit (see chapter 1.1 "Machine data" or nameplate)
Poor cooling (lack of water, contaminated cooling unit)
Poor water quality (e.g. pH, abrasive material, etc.)
Blocked vacuum filter
Water stop valve malfunction
Wrong lubricating grease
Damage due to wrong operation causes forfei­ture of all warranty claims on Gardner Denver.
6.4 Extended period of non-use
Check the operating water, replace if necessary.
Fig. 6.1 Specific loss of water as a function of the operat-
ing water temperature and the operating pressure (Calculated for air at atmospheric pressure and 60% RH)
0
0
10
20
30
40
50
60
70
80
100 200 300 400 500
Operating pressure [mbar]
Water loss [gr/m
3
]
(Grams per each cubic metre suction volume)
600 700 800 900 1000
Operating water temperature of 50 C
Operating water temperature of 45 C
Operating water temperature of 40 C
Operating water temperature of 30 C
Operating water temperature of 20 C
Operation
4990671000 February 2008 27
6.5 Troubleshooting
The following table can be used for fault diagnosis.
All failures should be repaired without delay. The machine should not be started until the fail­ure has been repaired. Repairs must only be carried out by qualified technical personnel.
Possible cause Remedy
Poor pump output
Vacuum filter soiled
Suction line leaking
Instrument leaking
Underspeed
Lack of operating water
High operating water feed temperature
Clean vacuum filter
Locate and repair leak
Replace leaking instrument
Run at prescribed speed
Top up operating water to maximum level
Inspect the operating water cooling system
Abnormal noise
1)
Poor machine alignment
Bearings worn
Operating water grossly contaminated
Incorrect speed
Pressure has changed
Vacuum has changed (higher vacuum needed)
Vent line blocked
Operating water temperature high
Foreign object in the machine
Re-align machine
Replace bearings or have them repaired
Change the operating water
Keep within speed limit
Keep within rated pressure
Keep within rated vacuum / inspect, clean exhaust air system
Inspect and/or clean vent line
Inspect the operating water cooling system
Remove foreign object immediately and flush the machine
Operating pressure or operating vacuum cannot be obtained
Incorrect pressure gauge or vacuum gauge reading
Vee belt slip
Directional control valve at wrong position
Operating water feed disturbed (not enough or no water)
Replace pressure gauge / vacuum gauge
Inspect Vee belt tension, re-tension if necessary
Set directional control valve to correct position
Ensure sufficient operating water supply
Operating water temperature high (above 55 °C)
Not enough water in the operating system
Cooling unit soiled
Top up operating water & recirculate water until water temperature is less than
55°C.
Clean cooling unit
Sludge or liquid has entered the machine
Vehicle oversucking Clean the machine; check the operating water, change if necessary
High power consumption
Overspeed
Exceedingly high output pressure
Pressure gauge reading wrong
Keep within speed limit
Keep within rated pressure, actuate/check safety valve
Replace pressure gauge
Operation
4990671000 February 2008 28
1)The cause of abnormal noise in the machine can be a foreign object; remove the foreign ob­ject without delay.
If the problem persists, please call our Service depart-
ment.
Safety valve blowing
Closed valves in pressure line
Pressure pipework blocked
Open valves
Remove blockage
Compressed air exits at shaft end and water leaks
Seal damaged Replace shaft seal in end cover or have it repaired
Rubber smell (with Vee belt drive)
Vee belt slip due to lack of belt tension
High output pressure
Check belt tension, re-tension if necessary
Keep within rated pressure
Vee belts buckling
Lack of belt tension
•Belt wear
Belt pulley out of alignment
Belt pulley wear
Check belt tension, retension if necessary
Install new Vee belts
Align pulley
Replace pulleys
Possible cause Remedy
Maintenance
4990671000 February 2008 29
Maintenance
7. Maintenance
7.1 Warranty
Damage due to non-compliance with the installation and operating instructions are not covered by the war­ranty.
Please note that repairs to the liquid ring pump must be made by an authorized repair centre using original parts. Otherwise the warranty will be invalid.
7.2 Maintenance, maintenance schedule
When carrying out maintenance or inspection, observe the safety instructions (chapter 2. "Safety instructions and hazard alerts").
Machine failure due to poor or improper maintenance can result in high repair costs and machine down time. Regular maintenance is therefore necessary.
The operating, safety and service life of the machine are largely determined by the level of maintenance un­dertaken.
The table below contains time, type and maintenance work information for normal service of the liquid ring pump.
The specified maintenance intervals assume approxi­mately 5 hours of pump service per day. If your service conditions are different, the maintenance intervals may be proportionally shorter or longer.
As operating conditions may vary, no forecast can be made as to how often the necessary wear inspections, maintenance and general inspections should be made. Decide on the most suitable arrangement in the light of your conditions.
Refit all guards properly after completion of any maintenance work.
Dispose of grease, cleaners and spent compo­nents, e.g., filter cartridges, as prescribed by the environment laws.
7.2.1 Water back-cooling with air
The flow of cooling air must not be obstructed.
Remove dust and dirt from the cooler every week.
Inspect the operating water level in the compensa­tion tank and top up water if necessary.
7.2.2 Liquid ring pump
Clean the machine every week.
7.2.3 Vacuum filter (GDD types)
Depending on the dust load, daily cleaning may be necessary; clean at least once every week.
The filter insert consists of either a stainless steel mesh or a fine filter cartridge.
Maintenance points Type of work See chapter Maintenance interval
1 week 1 month 3 months
Cooling unit/water cooler
clean 7.2.1
X
Liquid ring pump
clean 7.2.2
X
Vacuum filter
clean 7.2.3
X
Safety valve
check 6.2.1
X
Water stop valve
check 6.2.2
X
Vee belts, Vee belt tension inspect,
re-tension
7.2.4
X
Non-return valve
check 7.2.5
X
Shaft seal lubrication
regrease 7.3.2
X
Maintenance
4990671000 February 2008 30
Opening the filter:
Warning! Only open when the machine is stopped and de-pressurized.
Slacken or unscrew the tapered handle or star handles (7.1/2+3). With type SFA, turn the cover (7.1/1) about 15° counterclockwise out of straight pins. With type SFD, simply lift up the cover.
Cleaning the filter
Caution! Filter cover is under moderate spring tension.
Wash out the filter housing with a cold cleaner.
If the filter insert is stainless steel mesh it can be washed out with cold cleaner.
If the filter insert has a fine filter cartridge, it can be blown out with a steam jet directed from the inside to the outside. Inspect the fine filter cartridge for damage. Replace damaged filter insert.
Inspect the round seal ring or seal for damage. Replace damaged seal.
Make certain that dirt or cleaning residue does not en­ter the pump when the filter housing is cleaned.
Assembling the filter
Install the filter cartridge.
Place the round seal ring /seal in the cover and fil­ter cage (type SFD) (7.1/1). Install washers to the tapered handles or star handles (7.1/2+3).
Push the cover (7.1/1) in the housing (with type SFA; turn cover clockwise into the straight pins (7.1/6)).
Tighten the cover with tapered handles or star han­dles (7.1/2+3).
7.2.4 Vee belts and Vee belt tension
Remove the Vee belts and Vee belt/ drive guards only when the machine is stopped and the vehicle engine is stopped.
Inspect the Vee belts and the Vee belt tension every week and re-tension or replace the belts if necessary, see installation section 4.
Always replace damaged Vee belts as a complete set of length matched belts.
7.2.5 Non-return valve
The non-return valve needs maintenance every 3months.
We recommend a first inspection after 300 operating hours.
7.3 Lubrication
7.3.1 Antifriction bearings
The antifriction bearings of the liquid ring pump are pre-lubrication with enough grease for 5,000 operating hours.
The special lubricating grease ensures outstanding wear protection, excellent resistance to water and de­bris, good corrosion protection, good ageing resist­ance and an especially high resistance to tribocorrosion.
The grease is available from Gardner Denver in 400g cartridges (Part No. TW53105000).
Work on the antifriction bearings must only be
carried out by trained personnel with knowl­edge of the equipment and the potential risks.
The lubrication of the anti-friction bearings must be replaced, at the latest, after 5,000 operating hours, or three years. Remove all old lubricant and clean the bearings before filling with new lubricant. Use only lubricant certified by the manufacturer (GDD Part No. TW53105000).
Remove the bearings and install new bearings (GDD Part No. TW41123100) at the latest after 15,000 operating hours.
Fig. 7.1 Vacuum filters SFA and SFD
1
2
3
1
1Cover 2 Tapered handle (type SFA)
3 Star handle (type SFD)
Maintenance
4990671000 February 2008 31
7.3.2 Shaft seal
The Aqualine series is equipped with a combination of seals with grease barriers especially developed for this application.
The grease barrier of this seal needs regreasing with the above special lubricating grease in regular inter­vals of 200 – 300 operating hours. The lubricating nip­ples are located on the bearing caps on both faces of the liquid ring pump.
Regrease the machine when it is cold; apply grease until it emerges from the vent valve (see figure 1.3). The amount of grease is approx. 10 – 15 grams on each side. If access to the lubricating nipples is diffi­cult, an extension of the lubricating line by maximum
0.5 m and 6 – 8 mm diameter may provide easier ac-
cess.
If the operating water has a high pollutant content (es­pecially solvents) regreasing may be required more of­ten. The actual intervals are determined by experience.
Caution! Connecting the Aqualine lubrication to the cen­tral lubrication of the vehicle is not allowed!
A mixture of grease-water vapour can emerge from the grease nipple at fist start-up or after extended downtime, occasionally steam in nor­mal operation.
8. Spare parts
8.1 Spare parts
Keeping a sufficient stock of major spares (mainte­nance and wearing parts) at the site of the machine is an important to ensure the constant availability of the liquid ring pump.
Please order spare parts from the list below.
Our warranty is only for original parts supplied by us.
Any installation or attachment of spare parts or extra units not supplied by us is not included in the Gardner Denver warranty. Please note that that specific manu­facturing and delivery specifications may apply to parts made by us or OEM suppliers. All parts delivered by us are of latest engineering standard and satisfy latest mandatory regulations.
For ordering spare parts, please specify the data in the spare parts list...
Repairs and maintenance must only be carried out by qualified technical personnel.
Use only original parts from Gardner Denver.
Repairs and maintenance must only be carried
out by qualified technical personnel.
Repairs must be carried out or parts ex­changed only outside a potentially explosive atmosphere.
Use only original parts from Gardner Denver.
8.2 Wearing parts
We recommend to keep a stock of the following parts
Item
No.
Order No. for type Quantity Part name
Aqualine
1100
Aqualine
1600
Aqualine
2100
Aqualine
2700
9
⇒ ⇒ ⇒
TW46530900 TW46530700 TW46531000
TW46530900 TW46530700 TW46531000
⇐ ⇐ ⇐
2
Housing seal 481 / 471 x 0.5 mm 481 / 471 x 0.75 mm 481 / 471 x 1.0 mm
11
TW42438700 TW42438700
2 Sealing bush
14
TW91044400 TW91044400
2 Seal
TW53105000 TW53105000
400 g Bearing grease
For additional information, contact your local
representative or
Gardner Denver Drum Ltd
PO Box 178,
Springmill Street,
Bradford,
West Yorkshire, UK
BD5 7YH
Tel: +44 (0)1274 718100
Fax: +44 (0)1274 718101
Email: wittig.sales@gardnerdenver.com
Web: www.gardnerdenverproducts.com
© 2008 Gardner Denver Drum Ltd.
Specifications subject to change.
4990671000 February 2008
Loading...