GARLO GAVAZZI DPB01, PPB01 Service Manual

Specifications are subject to change without notice (06.11.00) 1
Monitoring Relays
Product Description Ordering Key
Housing Function Type Item number Output Power supply
• 3-phase over and under voltage, phase sequence and phase loss monitoring relays
• Detect when all 3 phases are present and have the correct phase sequence
• Detect if all the 3-phase-phase or phase-neutral volt­ages are within the set limits
• Upper and lower limits separately adjustable
• Measure on own power supply
• Selection of measuring range by DIP-switches
• Adjustable voltage on relative scale
• Adjustable delay function (0.1 to 30 s)
• Output: 8 A SPDT relay N.E.
• For mounting on DIN-rail in accordance with DIN/EN 50 022 (DPB01) or plug-in module (PPB01)
• 22.5 mm Euronorm housing (DPB01) or 36 mm plug-in module (PPB01)
• LED indication for relay, alarm and power supply ON
Type Selection
Mounting Output Supply: 208 to 240 VAC Supply: 380 to 480 VAC
DIN-rail SPDT DPB 01 C M23 DPB 01 C M48 Plug-in SPDT PPB 01 C M23 PPB 01 C M48
Input
L1, L2, L3, N DPB01: Terminals L1, L2, L3, N
PPB01: Terminals 5, 6, 7, 11 Measure on own supply
Measuring ranges
208 to 240 VAC 177 to 275 VAC 380 to 480 VAC (DPB01CM48) 323 to 550 VAC 380 to 415 VAC (PPB01CM48) 323 to 475 VAC
Ranges
Upper level +2 to +22%
of the nominal voltage
Lower level -22 to -2%
of the nominal voltage
3-Phase, 3-Phase+N, Multi-function Types DPB01, PPB01
Input Specifications
Output SPDT relay
Rated insulation voltage 250 VAC
Contact ratings (AgSnO
2
Resistive loads AC 1 8 A @ 250 VAC
DC 12 5 A @ 24 VDC
Small inductive loads AC 15 2.5 A @ 250 VAC
DC 13 2.5 A @ 24 VDC
Mechanical life 30 x 106operations Electrical life 10
5
operations
(at 8 A, 250 V, cos ϕ = 1)
Operating frequency 7200 operations/h Dielectric strength
Dielectric voltage 2 kVAC (rms) Rated impulse withstand volt. 4 kV (1.2/50 µs)
Output Specifications
DPB 01 C M23
3-phase or 3-phase+neutral line voltage monitoring relay for phase sequence, phase loss, over and under voltage (separately adjustable set
points) with built-in time delay function. Supply ranges from 208 to 480 VAC covered by two multivoltage relays.
DPB01 PPB01
查询PPB01CM23供应商
2 Specifications are subject to change without notice (06.11.00)
Selection of function:
DIP-switch selector (1 to 2)
1
Power ON delay 6 ± 0.5 s Power ON delay 1 ± 0.5 s
2
Phase-neutral voltage Phase-phase voltage
Selection of measuring range:
DIP-switch selector (3 to 4)
34
3 x 208 VAC (M23) 3 x 380 VAC (M48)
3 x 220 VAC (M23) 3 x 400 VAC (M48)
3 x 230 VAC (M23) 3 x 415 VAC (M48)
3 x 240 VAC (M23) 3 x 480 VAC (DPB01CM48)
Selection of level and time delay:
Upper knob:
Setting of lower level on rela­tive scale.
Centre knob:
Setting of upper level on rela­tive scale.
Lower knob:
Setting of delay on alarm time on absolute scale (0.1 to 30 s).
Function/Range/Level and Time Delay Setting
DPB01, PPB01
Mode of Operation
Connected to the 3 phases (and neutral) DPB01 and PPB01 operate when all 3 phases are present at the same time, the phase sequence is correct and the phase-phase (or phase-neu­tral) voltage levels are within set limits. If one or more phase-phase or phase-neutral voltages exceeds the upper set level
or drops below the lower set level, the red LED starts flashing 2 Hz and the output relay releases after the set time period. In any case if phase-neutral measurement is selected both phase­phase and phase-neutral voltages are monitored. If the phase sequence is wrong or one phase is lost, the output relay releases immediately.
Only 200 ms delay occurs. The failure is indicated by the red LED flashing 5 Hz during the alarm condition.
Example 1
(mains network monitoring)
The relay monitors over and under voltage, phase loss and correct phase sequence.
Example 2
(load monitoring)
The relay releases in case of interruption of one or more phases, when one or more voltages drop below the low­er set level or exceed the upper set level.
Power supply Overvoltage cat. III
Rated operational voltage (IEC 60664, IEC 60038) through terminals:
L1, L2, L3, N (DPB01) 5, 6, 7, 11 (PPB01)
M23: 208 to 240 VAC ± 15%
45 to 65 Hz
M48: 380 to 480 VAC ± 15%
45 to 65 Hz
Rated operational power
DPB01CM23, PPB01CM23 13 VA @ 230 VAC, 50 Hz DPB01CM48, PPB01CM48 13 VA @ 400 VAC, 50 Hz
Supplied by L2 and L3
Supply Specifications
Indication for
Power supply ON LED, green Alarm ON LED, red (flashing 2 Hz
during delay time)
Output relay ON LED, yellow
Environment
Degree of protection IP 20 Pollution degree 3 (DPB01), 2 (PPB01) Operating temperature -20 to 60°C, R.H. < 95%
@ 475 VAC, 65 Hz
-20 to 50°C, R.H. < 95% @ 550 VAC, 65 Hz
Storage temperature -30 to 80°C, R.H. < 95%
Housing dimensions
DIN-rail version 22.5 x 80 x 99.5 mm Plug-in version 36 x 80 x 87 mm
Weight Approx. 120 g Screw terminals
Tightening torque Max. 0.5 Nm
acc. to IEC 60947
CE-marking Ye s
General Specifications (cont.)
ON
Power ON delay 1 s ± 0.5 s or 6 s ± 0.5 s Reaction time
Incorrect phase sequence or total phase loss < 200 ms Voltage level (input signal variation from
-20% to +20% or from
+20% to -20% of set value) Alarm ON delay < 200 ms (delay < 0.1 s) Alarm OFF delay < 200 ms (delay < 0.1 s)
Accuracy (15 min warm-up time)
Temperature drift ± 1000 ppm/°C Delay ON alarm ± 10% on set value ± 50 ms Repeatability ± 0.5% on full-scale
General Specifications
ON