Garland ECG User Manual

INSTALLATION AND OPERATING
INSTRUCTIONS
FOR
ECG SERIES ELECTRIC CHAIN
GRIDDLES
THIS MANUAL SHOULD BE HANDED TO THE EQUIPMENT OWNER AND RETAINED FOR FUTURE REFERENCE.
TABLE OF CONTENTS
GENERAL INFORMATION
TECHNICAL SPECIFICATIONS
GENERAL INSTALLATION
INSTALLATION PROCEDURE
COMMISIONING
OPERATING INSTRUCTIONS
MAINTENANCE & CLEANING
……………………………………
……………………………………
……………………………………
……………………………………
……………………………………
……………………………………
……………………………………
PAGE 1
PAGE 2
PAGE 3
PAGE 4
PAGE 4
PAGE 5
PAGE 6
MANUFACTURED BY: DISTRIBUTED BY: GARLAND COMMERCIAL RANGES LIMITED GARLAND COMMERCIAL INDUSTRIED, INC. 1177 KAMATO ROAD, MISSISSAUGA, 185 EAST SOUTH STREET, ONTARIO, CANADA L4W 1X4 FREELAND, PA 18224 Phone: 905/624-0260 Fax: 905/624-5669 Phone: 570/636-1000 Fax: 570/636-3903
ECGTRAINING06
GENERAL INFORMATION
1. Damage Check: Check carton or crate for possible damages incurred in shipping. After carefully examining, check for “Concealed” damage. Report any damage immediately to your carrier.
2. Any protective material covering stainless steel parts must be removed.
3. All units are shipped from the factory with legs or casters fitted, unless specifically ordered without
4. The type of voltage supply that the equipment was manufactured for at the factory is noted on the data plate and on the packaging. This type of supply must be used.
5. Do not remove permanently affixed labels, warnings or data plates from the appliance, for this may void approvals and create a safety hazard.
NOTE: The griddle top is raw steel and can react with moisture forming rust. This is normal and not considered a defect. Clean with a stainless steel fiber pad. A light coating of salt free oil may be applied to prevent further rusting.
INTRODUCTION
The Garland ECG series complies with the standards CSA C22.2 no. 109 – latest edition, the UL197 – latest edition and the ANSI/NSF 4 – latest edition. The installation & connection of this appliance must comply with current codes. In Canada – the Canadian Electrical Code Part 1 and in the USA – the National Electrical Code.
SAFETY
This manual pertains to Electric Chain Griddles. The reader/operator must interpret its contents to applicable needs. If there is any question of interpretation of any of the literature pertaining to Garland Electric Chain Griddles, please contact your Authorized Service Agency or our Customer Service Department at 1 800 427 6668.
A qualified person must perform the installation in accordance with local codes.
Always follow these safety instructions when operating the Electric Chain Griddle:
Qualified persons must only operate the unit. DO NOT operate without reading this manual.
DO NOT operate the product unless it has been properly installed and grounded.
SAFETY - CONTINUED
1
DO NOT operate the product unless all service and access panels are in place and fastened properly.
DO NOT attempt to repair or replace any part of this product unless all main power supplies have been disconnected.
WARNING - to avoid personal injury:
USE EXTREME CAUTION in setting up, operating and cleaning this product to avoid coming
into contact with hot grill surfaces or hot grease. Suitable protective clothing should be worn to prevent the risk of burns. NOTE all warning labels and markings on the product, which call attention to further dangers and necessary precautions.
WARNING – This appliance must not be cleaned with a water jet.
TECHNICAL SPECIFICATIONS
LOADING CHART
MODEL
ECG-24R
ECG-36R
ECG-48R
ECG-60R
ECG-72R
TOTAL
kW LOAD
8.60 208 2.60 3.00 3.00 23.3 23.3 25.0 41.3
8.60 240 2.60 3.00 3.00 20.2 20.2 21.7 35.8
12.90 208 4.30 4.30 4.30 35.8 35.8 35.8 62.0
12.90 240 4.30 4.30 4.30 31.0 31.0 31.0 53.8
17.20 208 5.60 6.00 5.60 48.3 46.6 48.3 82.7
17.20 240 5.60 6.00 5.60 41.9 40.4 41.9 71.7
21.50 208 6.90 7.30 7.30 59.1 59.1 60.8 103.4
21.50 240 6.90 7.30 7.30 51.2 51.2 52.7 89.6
25.80 208 8.60 8.60 8.60 71.6 71.6 71.6 124.0
25.80 240 8.60 8.60 8.60 62.1 62.1 62.1 107.5
Voltage
LOAD PER PHASE AMPS PER PHASE
X-Y X-Z Y-Z X Y Z
Amps
1 phase
EXTERIOR DIMENSIONS
MODEL HEIGHT WIDTH DEPTH WEIGHT
mm ins mm ins mm ins kg Lb.
ECG-24R 905 35 5/8 610 24 889 35 120 265 ECG-36R 905 35 5/8 914 36 889 35 181 400 ECG-48R 905 35 5/8 1219 48 889 35 227 500 ECG-60R 905 35 5/8 1524 60 889 35 272 600 ECG-72R 905 35 5/8 1829 72 889 35 318 700
ELECTRICAL SUPPLY
Before attempting the electrical connection, the rating plate should be checked to ensure that the equipment’s electrical characteristics agree. On Electric Chain Griddles, the supply entrance is located at the rear of the main bottom. The supply terminal block is accessible from the front.
ELECTRICAL SUPPLY
CONTINUED
The electrical supply must be adequate for the voltage, phase and current marked on the rating plate.
2
Note: A means of disconnection from the supply having a contact separation of at least 3 mm in all poles must be incorporated in the fixed wiring.
WARNING: THIS APPLIANCE MUST BE GROUNDED
GENERAL INSTALLATION
A qualified person as required by the local electrical authorities must install this equipment.
WARNING: The appliance must be grounded.
CAUTION: Prior to installation, check the electrical supply to ensure input voltage and phase
match the equipment voltage rating and phase. See data plate located on the bottom of the control section near the front.
The Electric Chain Griddle must be level front to back, side to side and diagonally. This leveling must be done with the unit under the hood and in its normal operational position.
SITING
The base on which the unit is to be sited, must be capable of adequately supporting the weight of the appliance and any ancillary equipment. (Refer to technical specifications in this manual). Once in position check the equipment is level, both front to back, side to side and diagonally. Adjust if necessary.
VENTILATION AIR
The Electric Chain Griddle (ECG) is intended to be installed under a ventilation hood.
Proper operation of exhaust fans (proper speed, rotation and adjustment) is essential. In addition, a make-up air system (HVAC) for the kitchen to supply fresh air is recommended.
Any ventilation system will break down if improperly maintained. The duct system, the hood, and filters must be cleaned on a regular basis and kept grease free.
CLEARANCES
The space in which the appliance is to be sited must include the minimum installation clearances shown below:
3
Loading...
+ 8 hidden pages