GARDASOFT RT Series, RT200, RT260F, RT220F, RT460 User Manual

...
Page 1
RTxxx LED
Lighting Controllers
Issue 013
User manual
www.gardasoft.com
WWW.STEMMER-IMAGING.COM
Page 2
RTxxx LEDcontrollers -User Manual
Except as prohibited by law:
All hardware, software and documentation is provided on an as is’ basis. This information is for guidance only. Installers must perform their own risk assessment specific to each installation.
It is essential that the user ensures that the operation of the product is suitable for
their application.
The user must ensure that incorrect functioning of this equipment cannot cause any dangerous situation or significant f inancial loss to occur.
Deliberate acts of endangerment and vandalism are not covered by this document and must be considered by the installer.
While care has been taken in the preparation of this document Gardasoft Vision Ltd will not accept any liability for consequential loss of any kind except those required by law.
All trademarks acknowledged. This document is Copyright 2019 Gardasoft Vision Ltd.
EC conformity declaration
The EC Certificate of Conformity is available from Gardasoft Vision Ltd on request
Issue status of this document: Issue v013 - July 2019
WWW.STEMMER-IMAGING.COM
Page 3
RTxxx LEDcontrollers -User Manual
Contents
1 Getting started 5
1.1 Summary of features
5
2 Safety 7
2.1 Heat
7
2.2 Electrical
7
2.3 General
8
2.4 Installation guidance (disclaimer)
9
3 Sicherheit 10
3.1 Wärme
10
3.2 Elektrik
10
3.3 Allgemein
12
3.4 Installationsanleitung (Haftungsausschluss)
12
4 Sécurité 13
4.1 Chaleur
13
4.2 Électricité
13
4.3 Généralités
15
4.4 Guide d'installation (clause de non-responsabilité)
15
5 Mounting the RTxxx 16
5.1 Environmental considerations
16
5.2 Electrostatic discharge
18
6 Connections 19
6.1 Power supply
19
6.2 Lighting output
19
6.3 Trigger inputs
22
6.4 12V Power output
23
6.5 Ethernet connection
23
6.6 Serial connection
23
6.7 Connectors
23
7 General description 25
7.1 Output modes
25
7.1.1 Continuous output, switched output, selected o utput 26
7.2 Pulsed output
26
7.3 Fault detection
27
7.4 Light auto-sensing
27
7.5 Cold start
28
8 Lighting setup 29 9 Front panel configuration (RT200) 30
9.1 Startup
30
9.2 Setting the light rating
31
9.3 Setting up continuous output
32
9.4 Setting up switched output
34
9.5 Setting up selected output
36
9.6 Setting up pulsed operation
38
9.7 Setting time periods
41
9.8 Setting the internal trigger timer
43
9.9 Using the key lock
44
WWW.STEMMER-IMAGING.COM
Page 4
RTxxx LEDcontrollers -User Manual
9.10 Viewing the trigger status
47
9.11 Viewing the output current
47
10 Ethernet communication(RT220, RT420, RT820F) 49
10.1 Connection
49
10.2 IP Address
49
10.2.1 DHCP 50
10.2.2 Fixed IP address 50
10.3 Automatic sensing
50
11 Webpage configuration (RT220, RT420, RT820F) 52
11.1 Main page
52
11.2 Configuration page
53
11.3 General setup page
54
12 Command configuration 55
12.1 Ethernet configuration(RT220, RT420, RT820F)
55
12.2 RS232 configuration(RT260, RT460, RT860F)
55
12.3 Command structure
55
12.3.1 General commands 56
12.3.2 Lighting channel commands 59
12.3.3 Command summary 61
13 Reference information 62
13.1 Specification
62
13.2 Restrictions
63
13.3 Error codes
64
13.4 Fatal error codes
65
13.5 Event codes
65
WWW.STEMMER-IMAGING.COM
WWW.STEMMER-IMAGING.COM
Page 5
RTxxx LEDlighting control l ers - U ser Manual
1 Getting started
This user manual describes the setting up and operation of the RTxxx range of LED lighting controllers.
Read Section Safety (or Section 3, Sicherheit, or Section4, Sécurité) and
Section 13.1, Specification, and check the RTxx controller fulfils your
requirements. Mount the RTxxx as described in Section 5, Mounting the RTxxx and
connect the RTxxx up toa power supply as described in Section6,
Connections. The RT200 shows a two alternatinglines on it's display to
indicate it is working properly. Read Section 8, Lighting setup. Enter the current or voltage rating of the
lights and then connect the lights. Set up the RTxxx for the desired operation as described in the configuration sections; Section 9, Front
panel configuration (RT200), Section 11, Webpage configuration (RT220, RT420, RT820F), and Section 12, Command configuration.
Visit www.gardasoft.com
for application notes on this product. There is
also a Support page which has information on troubleshooting problems.
1.1 Summary of features
Throughout this manual, references to the RTxxx refer to all variantsin the RTxxx range unless otherwise stated. The convention for the product number is:
RTcd0-vv RTcd0F-vv
where:
c
Number of channels: 2, 4, 8
d
Configuration option: 0 = Pushbutton, 2 = Ethernet, 6 = RS232
F
Option for fast pulsing. All RT8xx models are fast pulsing.
vv
Maximum pulse current in amps: 2, 20
5
WWW.STEMMER-IMAGING.COM
Page 6
RTxxx LEDlighting control l ers - U ser Manual
The table below lists the features on each model:
Number of
channels
Pushbutton
setup
Ethernet
setup
RS232
setup
Fast
pulsing
RT200 2 Yes No No No
RT220 2 No Yes No No
RT260 2 No No Yes No
RT200F 2 Yes No Yes Yes
RT220F 2 No Yes No Yes
RT260F 2 No No Yes Yes
RT420 4 No Yes No No
RT460 4 No No Yes No
RT420F 4 No Yes No Yes
RT460F 4 No No Yes Yes
RT820F 8 No Yes No Yes
RT860F 8 No No Yes Yes
6
WWW.STEMMER-IMAGING.COM
WWW.STEMMER-IMAGING.COM
Page 7
RTxxx LEDlighting control l ers - U ser Manual
2 Safety
Read this before using the RTxxx. Always observe the following safety precautions. If in doubt,contact Gardasoft Vision Ltd. The following symbols are used in this guide:
Warning: Read the instructions to understand the
possible hazards.
Warning: Surface may get hot.
Warning: Possible hazardous voltage.
Where these symbols appear in the manual, refer to the text for the precautions to be taken.
2.1 Heat
Ensure the RTxxx is mounted correctly (see Section 5, Mounting the
RTxxx), and that you do not exceed any of the ratings for the unit (see Section 1.1, Specifications and ratings)
At its maximum ratings, the RTxxx’s enclosure can exceed 65°C which is sufficient tocause a burn if touched. Place in a position where personnel cannot accidentally touch it and ensure there is a free flow of air around the unit.
2.2 Electrical
The RTxxx produces high energypulses. Take care to connect the outputs correctlyand protect the output wiring and load from any short-circuits. When switched off, energy remains stored in the RTxxx for about 15 seconds.
The RTxxx does not have complete electrical isolation of inputs (including triggering and communications ports) and outputs, therefore,please observe the following guidance:
Computer equipment that is connected to the communication or trigger ports must be internally powered or separated from mains electricity by double insulation/reinforced isolation or be approved to IEC 60950-1 standard. All other equipment connected to the triggers or other ports must also have double insulation/reinforced isolation protection from the mains supply.
The Power Supply Unit (PSU) used toenergise the RTxxx must provide double insulation/reinforced isolation from mains electricity and protected against short circuits and overloads. We recommend using a PSU that
7
WWW.STEMMER-IMAGING.COM
Page 8
RTxxx LEDlighting control l ers - U ser Manual
limits its output current to the appropriate rating of the controller by design, by settingthe current limit on the supply(if possible), or through over current protection. The PSU should be approved to either IEC 60950-1, IEC 60335-1, IEC 61010-1, IEC61558-1,-2,-16. The PSU may also be approved to equivalent or superior safety standards.
Any energised conductors derived from mains electricity must also have Safety Extra Low Voltage (SELV) output. Refer to Section 13, Reference
information for allowable voltage limits.
At maximum ratings the temperature of the enclosure can exceed 65°C. Therefore, either all cabling must be rated to at least 100°C, or all cabling must be additionally insulated by an appropriatelyrated heat resistant sleeve or prevented from touching the metal enclosure of the controller, or its heatsink where fitted.
Power supplycabling to the controller must be rated to at least 5A or 10A (RT8xxF).
The cabling from the channel output tothe load must be rated higher than the maximum channeloutput current.
If the controller is set up incorrectly, or in the event of failure, the energy provided by the power supplytothe controller may become directly connected to any or all output channels. You must consider this during installation, and if necessary, provide adequate protection.
The DC power supplyto controller must be externally fused to 5A or10A (RT8xxF) using a slow blow fuse (T5AH, 50V or T10A, 50V).
The installer must provide a clearly marked, nearby and easily accessible switch as part of the installation to allow the controller to be disconnected from its energy source on both power conductors.
Transients caused by inductive loads must be suppressed externallyto the RTxxx.
Warning: This is a Class A product. Its use in residential areas may cause
radio interference, and such use should be avoided unless special measures are taken by the user to restrict emissions to a levelthat allows the reception of broadcast transmissions.
2.3 General
The RTxxx must not be used in an application where its failure could be a danger to personal health or damage to other equipment.
If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
8
WWW.STEMMER-IMAGING.COM
WWW.STEMMER-IMAGING.COM
Page 9
RTxxx LEDlighting control l ers - U ser Manual
2.4 Installation guidance (disclaimer)
This information is for guidance only. Installers must perform their own risk assessment specific to each installation. While Gardasoft Vision Ltd has taken every care in the preparation of this advice, Gardasoft Vision Ltd accept no liability for damagesof any kind except those required by law.
Deliberate acts of endangerment and vandalism are not covered by this document and must be considered by the installer.
9
WWW.STEMMER-IMAGING.COM
Page 10
RTxxx LEDlighting control l ers - U ser Manual
3 Sicherheit
Bitte lesen Sie vor Verwendung des RTxxx diese Informationen. Beachten Sie immer die folgenden Sicherheitshinweise.Wenden Sie sich im Zweifelsfall an Ihren Händler oder Gardasoft Vision. Die folgenden Symbole haben die folgende Bedeutung:
Warnung: Lesen Sie die Hinweise, um eine mögliche
Gefahr zu verstehen.
Warnung: Oberfläche kann he werden.
Warnung:Mögliche gefährliche Spannung.
Wenn diese Symbole in der Anleitung auftauchen, enthält der Text Hinweise zu den zu ergreifenden Vorsichtsmaßnahmen.
3.1 Wärme
Stellen Sie sicher, dass der RTxxx korrekt montiert ist (siehe Section 5,
Mounting the RTxxx) und dass Sie die Grenzwerte r das Gerät nicht
überschreiten (siehe Section 13, Reference information). Bei den maximalen Grenzwerten kann das Geuse des RTxxx 65°C
überschreiten, was ausreichend ist um bei einer Berührung zu Verbrennungen zu führen. Positionieren Sie das Gerät so, dass eine versehentliche Berührung durch das Personalausgeschlossen ist und stellen Sie sicher, dass Luft frei um das Gerät zirkulieren kann.
3.2 Elektrik
Das RTxxx erzeugt Impulse mit hoher Energie. Achten Sie darauf,die Ausgänge korrekt anzuschließen und schützen Sie die Ausgangsverkabelung und Last gegen Kurzschlüsse. Beim Ausschalten bleibt Energie r etwa 15 Sekunden im RTxxx gespeichert.
Das RTxxx vergt über keine vollständige elektrische Trennung der Eingänge (einschließlich Trigger- und Kommunikationsports) und Ausgänge. Beachten Sie daher unbedingt die folgenden Hinweise:
Computergeräte, die an die Kommunikations- oder Trigger-Ports angeschlossensind, müssen über eine interne Stromversorgung vergen oder vom Stromnetz durch eine doppelte Isolierung/verstärkte Isolierung getrennt sein oder nach dem Standard IEC 60950-1 zugelassen sein. Alle anderen Geräte, die an die Trigger- oder andere Ports angeschlossen sind, müssen ebenfallsdurch eine doppelte Isolierung/verstärkte Isolierung vom Stromnetz getrennt sein.
10
WWW.STEMMER-IMAGING.COM
WWW.STEMMER-IMAGING.COM
Page 11
RTxxx LEDlighting control l ers - U ser Manual
Das Netzgerät, das zur Stromversorgung des RTxxx dient, muss durch eine doppelte Isolierung/verstärkte Isolierung von der Stromversorgung getrennt sein und gegen Kurzschlüsse und Überlastungen geschützt sein. Wir empfehlendie Verwendung eines Netzgeräts, das den Ausgangsstrom durch konstruktive Maßnahmen, durch Einstellen der Stromgrenze an der Versorgung (wenn möglich) oder durch einen Überstromschutz auf den geeigneten Nennstrom der Steuerung begrenzt. Das Netzgerät muss nach IEC 60950-1, IEC 60335-1, IEC 61010-1 oder IEC61558-1,-2,-16 zugelassensein. Das Netzgerät kann auch nach gleichwertigenoder höheren Standards zugelassen sein.
Alle stromführenden Leiter, die vom Stromnetz abgeleitet sind, müssen ebenfalls Sicherheitskleinspannung (SELV) am Ausgang erzeugen. Hinweise zu den zulässigen Spannungsgrenzwerten finden Sie im Section
13, Reference information.
Bei den maximalen Grenzwerten kann die Temperatur des Gehäuses 65°C überschreiten. Daher muss entweder die gesamte Verkabelungr mindestens 100°C bemessen sein oder die gesamte Verkabelungmuss zusätzlich mit einer angemessen dimensionierten wärmebeständigen Tülle isoliert sein oder gegen Kontakt mit dem Metallgehäuse der Steuerung oder deren Kühlkörper, sofern angebracht, geschützt sein.
Die Verkabelung der Stromversorgung zur Steuerung muss r mindestens 5A (oder 10A r RT8xxF) bemessensein.
Die Verkabelung vom Kanalausgang zur Last muss höher als der maximale Kanalausgangsstrom dimensioniert sein.
Wenn die Steuerung falsch eingerichtet ist oder im Fall einesFehlers,kann es vorkommen, dass die von der Stromversorgung an die Steuerung abgegebene Energie direkt mit einem oder allen Ausgangskanälen verbunden wird. Sie müssen dies bei der Installation berücksichtigen und gegebenenfalls r einen geeigneten Schutz sorgen.
Die Gleichstromversorgung der Steuerung muss extern durch eine träge Sicherung (T5AH, 50V, oder T10A, 50V r RT8xxF) bis 5A oder 10A gesichert sein.
Der Installationstechniker muss einen deutlich gekennzeichneten, leicht zugänglichen Schalter als Teil der Installation in der Nähe vorsehen, mit dem die Steuerung an beiden Stromleitern von ihrer Stromquelle getrennt werden kann.
Durch induktive Lasten verursachte Einschaltstöße zum RTxxx müssen extern unterdrückt werden.
Warnung: Es handelt sich hierbei um ein Produkt der Klasse A. Die
Verwendung in Wohngebieten kann zu Funkstörungen hren und eine solche Verwendung sollte vermieden werden, es sei denn besondere Maßnahmen werden vom Anwender ergriffen, um die Emissionen auf ein Niveau zu begrenzen, das den Empfang von Rundfunkübertragungen ermöglicht.
11
WWW.STEMMER-IMAGING.COM
Page 12
RTxxx LEDlighting control l ers - U ser Manual
3.3 Allgemein
Das RTxxx darf nicht in Anwendungen eingesetzt werden, bei denen es durch einen Ausfall des Geräts zu einer Gefahr r die Gesundheit von Personen oder zur Beschädigung anderer Geräte kommennnte.
Wenn das Gerät in einer anderen als der vom Hersteller vorgesehenen Weise verwendet wird, kann die Schutzvorrichtung des Geräts beeinträchtigt werden.
3.4 Installationsanleitung (Haftungsausschluss)
Diese Informationen dienen nur zur Orientierung. Installationstechniker müssen ihre eigene spezifische Risikobewertung r die jeweilige Installation durchführen. Auch wenn Gardasoft Vision Ltd diese Empfehlung mit größter Sorgfalt erstellt hat, übernimmt Gardasoft Vision Ltd keine Haftung r Schäden jeglicher Art, außer in dem gesetzlich erforderlichen Maße. Vorsätzliche Gehrdungs- oder Zerstörungshandlungen werden in diesem Dokument nicht behandelt und müssen vom Installationstechniker berücksichtigt werden.
12
WWW.STEMMER-IMAGING.COM
WWW.STEMMER-IMAGING.COM
Page 13
RTxxx LEDlighting control l ers - U ser Manual
4 Sécurité
Lisez ce document avant d'utiliser le RTxxx. Respectez les mesuresde sécurité suivantes en toutescirconstances. En cas de doute, contactez votre distributeur ou Gardasoft Vision. Les symboles ci-dessous auront la signification suivante:
Attention: Lisez les instructions pour comprendre quels
sont les risques éventuels.
Attention: La surface peut devenir chaude.
Attention:Risque d'électrocution.
Lorsque ces symboles apparaissent dans le manuel,reportez-vous aux consignes pour connaître les précautions à prendre.
4.1 Chaleur
Veillez à ce que le RTxxx soit monté correctement (voir Section 5,
Mounting the RTxxx) et à ne dépasser aucune valeur nominale pour l'unité
(voir Section 13, Reference information). Lorsqu'il atteint ses valeurs nominales maximales, le boitier RTxxx peut
dépasser les 65°C, ce qui est suffisant pour provoquer des bluresen cas de contact. Placez l'appareil à un endroit où le personnel ne risque pas de le toucher par accident et veillez à ce que l'air circule librement autour de l'unité.
4.2 Électricité
Le RTxxx produit des impulsions d'énergie élevées.Veillez à bien raccorder les sorties et à ce que les câbles de sortie et la charge soient à l'abri de tout court-circuit. Lorsque le RTxxx est éteint, de l'énergie résiduelle reste dans l'appareilpendant environ 15 secondes.
Le RTxxx ne possède pas d'isolation électrique complèt des entrées (notamment des ports de déclenchement et de communication) et des sorties. Par conséquent, respectez les consignes suivantes :
L'équipement informatique connecté aux ports de communication et de déclenchement doit être alimenté en interne ou séparé de l'alimentation secteur par une isolation double/renforcée, ou être approuvé selon la norme CEI 60950-1. Tous les autres équipements branchés aux déclencheurs ou à d'autres ports doivent aussi posséder une isolation double/renforcée pour être protégés de l'alimentation secteur.
13
WWW.STEMMER-IMAGING.COM
Page 14
RTxxx LEDlighting control l ers - U ser Manual
Le boîtier d'alimentation utilisé pour mettre sous tension le RTxxx doit fournir une isolation double/renforcée pour isoler le RTxxx de l'alimentation secteur, et le protéger des courts-circuits et des surcharges. Nous recommandons d'utiliser un boîtier d'alimentation qui limite le courant de sortie de l'appareilà la valeur nominale appropriée du contrôleur, en réglant la limite de courant sur l'alimentation (si possible) ou via la protection contre les surcharges. Le boîtier d'alimentation doit être approuvéselon la norme CEI 60950-1, CEI 60335-1, CEI 61010-1 ou CEI61558-1,-2,-16. Le boîtier d'alimentation peut aussi être approuvé selon des normes de sécurité équivalentes ou supérieures.
Tous les conducteurs sous tension dérivés depuisl'alimentation secteur doivent aussi posséder une sortie à tension de sécurité extra-basse. Se reporter à la Section 13, Reference information pour les limites de tension autorisées.
Lorsqu'il atteint ses valeurs nominales maximales, le boîtier du RTxxx peut dépasser les 65°C. Par conséquent, tout le câblage doit soit avoir une capacité minimale de 100°C, soit être en plus isolé par une gaine suffisamment résistante à la chaleur, soit ne pas toucher le boîtier en métal du contrôleur ou son dissipateur thermique s'il est installé.
Le câblage d'alimentation vers le contrôleur doit avoir une capacité minimale de 5A (ou 10A pour RT8xxF).
Le câblage reliant la sortie de la chaîne à la charge doit avoir une capacité supérieure au courant de sortie maximal de la chaîne.
Si le contrôleur est mal réglé ou en cas de panne, l'énergie fournie par l'alimentation au contrôleur peut devenir directement connectée à n'importe quelle chaîne de sortie ou à toutes les chaînesde sortie. Vous devez prendre en compte ce paramètre durant l'installation et si nécessaire, fournir une protection adéquate.
L'alimentation en courant continu vers le contrôleur doit être protégée par un fusible 5A (ou 10A pour RT8xxF)en externe, plus précisément un fusible à action retardée (T5AH, 50V ou T10A, 50V).
Dans le cadre de l'installation, l'installateur doit fournir un interrupteur clairement marqué, qui soit à proximité et facilement accessible, pour permettre au contrôleur dtre déconnecté de sa source d'énergie sur les conducteurs d'alimentation.
Les coupures causées par des charges inductives doivent être suppriméesde manière externe vers le RTxxx.
Attention: Il s'agit d'un produit de classe A. Son utilisation en zone
résidentielle peut causer des interférences radio. Ce type d'utilisation doit être évité, sauf si des mesures particulières sont prises par l'utilisateur pour restreindre les émissions à un niveau qui permet la réceptiondes transmissions diffues.
14
WWW.STEMMER-IMAGING.COM
WWW.STEMMER-IMAGING.COM
Page 15
RTxxx LEDlighting control l ers - U ser Manual
4.3 Généralités
Le RTxxx ne doit pas être utilisé dans une application où la santé des personnes et l'intégrité des équipements seraient mises en danger s'il venait à tomber en panne.
Si l'équipement est utilisé autrement qu'aux fins prévuespar le fabricant, la protection offerte par l'équipement pourrait en être altérée.
4.4 Guide d'installation (clause de non-responsabilité)
Ces informations sont seulement à titre indicatif. Les installateurs doivent effectuer leur propre évaluation des risques, pour chaque installation. Même si Gardasoft Vision Ltd a préparé minutieusement ces conseils, Gardasoft Vision Ltd décline toute responsabilité pour tout dommage, quel qu'il soit, à l'exception de ceux requis par la loi. La mise en péril volontaire ainsi que les actes de vandalisme ne sont pas couverts par le présent document et doivent être pris en compte par linstallateur.
15
WWW.STEMMER-IMAGING.COM
Page 16
RTxxx LEDlighting control l ers - U ser Manual
5 Mounting the RTxxx
In order to provide fixing points to mount the unit onto a flat surface or bracket, insert M3 nuts into one or more of the slots in the base, see the illustration below. The quantityand position of these nuts depends on the users requirements. One of the end coversfeatures cut-outs to allow the M3 nuts to be easily slid into place without dismantling the controller. Ensure that the fixing screws used do not extend past the lower base surface by more than 5.5mm.
The PP704 kit is available for mounting the RTxxx on a DIN rail.
5.1 Environmental considerations
The RTxxx enclosure is a fire enclosure as long as it is mounted so that none of the connectors are facingdownwards.
If a fire enclosure is used, the enclosure should be metal or plastic (with a flammability rating of UL94 V1 or better); with no holes below or to the sides of the RTxxx when mounted. Cable entries below the RTxxx should be through glands that also have a flammability rating of UL94 V1 or better. The RTxxx should be at least 10mm from any other part or side of the enclosure.
The RTxxx does not have an IP rating and must be mounted so that moisture and dirt cannot enter the unit.
The illustration below shows the dimensions of an RT2xx controller:
16
WWW.STEMMER-IMAGING.COM
WWW.STEMMER-IMAGING.COM
Page 17
RTxxx LEDlighting control l ers - U ser Manual
The illustration below shows the dimensions of an RT4xx controller:
17
WWW.STEMMER-IMAGING.COM
Page 18
RTxxx LEDlighting control l ers - U ser Manual
The illustration below shows the dimensions of a TR-RT8xxFcontroller:
5.2 Electrostatic discharge
Electrostatic discharge (ESD)can damage equipment and impair the electricalcircuitry inside your RTxxx. ESDdamage occurs when electronic components are improperly handled and can result in complete or intermittent failures. On the RTxxx, this is relevant only to the trigger connections and power input.
18
WWW.STEMMER-IMAGING.COM
WWW.STEMMER-IMAGING.COM
Page 19
RTxxx LEDlighting control l ers - U ser Manual
6 Connections
See Section 13, Reference information for information about connection ratings
6.1 Power supply
In the unlikely event of a fault in the RTxxx, the maximum power dissipation in the unit can be:
Power supply voltage x Max current delivered by power supply
Either limit the power supply output current so that the RTxxx cannot dissipate more than 30W, or mount the unit in a fire enclosure.
Choose a PSU that is designed to limit its output current, or by setting the current limit on the supply (if this feature exists), or use a fuse. The fuse should be de-rated if mounted in an enclosure, as the temperature can be higher than the ambient temperature.
The external power supplymust be capable of supplying at least the average output power for all active channels.
We recommend you use a regulated power supply with 100% short circuit protection. If however a non-regulated power supply is used, then the maximum ripple voltage of the power supply must not exceed 10% of the DC voltage.
Route the low voltage and mains wiring separately. If they must be loomed together, ensure that the insulation rating of the low voltage wiring is sufficient, or that you use supplementary insulation. The input connections are illustrated below:
6.2 Lighting output
The lighting connections can exceed 46.7V but should not exceed 70V DC. Pulse peak voltages above 72V are considered hazardous. The lighting connections must be shielded so they cannot be being touched both within the light and along the whole length of the cable.
19
WWW.STEMMER-IMAGING.COM
Page 20
RTxxx LEDlighting control l ers - U ser Manual
The lighting connections to an RTxxx are made through 4-way connectors as shown below:
Ensure you set the current or voltage rating of your light before you connect it, see Section 8, Lighting setup.
The connectorsfitted to anRT2xx, RT4xx, and an RT8xx seriescontroller are shown in the illustrations below. You should refer to Section 6.3,
Trigger inputs for the pin allocations of the trigger connectors.
RT2xx
20
WWW.STEMMER-IMAGING.COM
WWW.STEMMER-IMAGING.COM
Page 21
RTxxx LEDlighting control l ers - U ser Manual
RT4xx
21
WWW.STEMMER-IMAGING.COM
Page 22
RTxxx LEDlighting control l ers - U ser Manual
RT8xxF
6.3 Trigger inputs
The trigger inputs are opto-isolated 3V to 24V input, drawing a minimum of 3mA. The table overleafdescribes the pin allocations for the RTxxx controllers trigger connectors:
Note: All RTxxx controllers are fitted with Connector ET12. Connector
ET34 is present on the RT4xx and RT8xxFseries controllers. Connectors ET56 and ET78 are present only on RT8xxFcontrollers.
22
WWW.STEMMER-IMAGING.COM
WWW.STEMMER-IMAGING.COM
Page 23
RTxxx LEDlighting control l ers - U ser Manual
Pin
Connector ET12
Connector ET34
Connector ET56
Connector ET78
1 TRIG1 TRIG3 TRIG5 TRIG7 2 TRIG1 + TRIG3 + TRIG5 + TRIG7 + 3 TRIG2 TRIG4 TRIG6 TRIG8 4 TRIG2 + TRIG4 + TRIG6 + TRIG8 +
6.4 12V Power output
RT2xx and RT4xxx controllers have one 12Vpower supply output. The RT8xxF controller has two. These can supply up to 1A at 12V for powering cameras and other devices. Do not connect inductive loads or devicesthat take large peak currents. Do not exceed the current rating as these outputs are not fused.
The pin allocation for the power supply output connector is shown opposite:
6.5 Ethernet connection
Ethernet connectivity is standard on RT220, RT420, and RT820F controllers. The RJ45 Ethernet connector requires a straight through cable to connect into a network switch, hub or router. It operates at 10Mbits per second (10Base-T).
6.6 Serial connection
The RS232 connector fitted to RT260, RT460, and RT860F controllers is a standard 9-way female D-type. A standard straight through cable can be used to connect the controller to a PC serialport. The communications port settings are 115Kbaud, no parity, 8 data bits and 1 stop bit.
The pin allocation for the serial connector is shown opposite:
6.7 Connectors
The RTxxx packagingincludes mating connectors for the power supply input, digital outputs, 12V power output, and lighting output.
23
WWW.STEMMER-IMAGING.COM
Page 24
RTxxx LEDlighting control l ers - U ser Manual
Should spare parts be required these can be obtained from Würth (www.we-online.com), Farnell (www.farnell.com), or Newark (www.newark.com). See the table overleaf for further information.
Connector Description
Würth part number
Farnell/Newark part number
Power input
2W screw terminal free socket
691-351-500-002 164 1952
Trigger input
4W screw terminal free socket
691-361-100-004 184 1351
12V output
2W screw terminal free plug
691-348-500-002 N/A
24
WWW.STEMMER-IMAGING.COM
WWW.STEMMER-IMAGING.COM
Page 25
RTxxx LEDlighting control l ers - U ser Manual
7 General description
The RTxxx seriesof current controllers provide repeatable intensity control of LED lighting for machine vision applications. This includes the intensity control, timing and triggering functions required for machine vision systems.
LED lighting needs a constant current supply as small variations in voltage can cause large variations in light output. The RTxxx series of controllers can set currents in steps of 0.1% (with a lower limit of 2.5mA steps) to give very fine control of intensity.
Several modes of operation are separately available for each channel:
Continuous
In continuous mode the output is a continuous brightness.
Pulse (Strobe)
In pulse mode output is pulsed once per trigger. One trigger input is used as a trigger. The delay from trigger to pulse, the pulse duration and the brightness can be set.
Switched
In switched mode a trigger input is used to switch the output current on and off. The output is only enabled when the trigger input has a voltage on it.
Selected
In selected mode a trigger input is used to select between two different intensities.
Tandem
It is possible to connect, in parallel, between two and four channels to provide additional power for lighting. The operation of tandem mode is beyond the scope of this users’ manual and further information is available from your local distributor or Gardasoft Vision.
With the exception of the RT200, controllers in the RTxx series are set up using an Ethernet port or serial port. The set up is non-volatile, so the RTxxx resumes the same operation after a power cycle.
7.1 Output modes
The trigger inputs are used as described overleaf:
Note: The P flag inverts the sense of the trigger input, see Section 6.3,
Trigger inputs.
25
WWW.STEMMER-IMAGING.COM
Page 26
RTxxx LEDlighting control l ers - U ser Manual
7.1.1 Continuous output, switched output, selected output
Mode Trigger input Output
Continuous Unused Output is on
Switched Trigger = off
Trigger = on
Output is off Output is on
Selected Trigger = off
Trigger = on
Output is continuous brightness 2 Output is continuous brightness 1
Pulsed Trigger rising edge
Trigger falling edge
Pulse is triggered if P flag = 1 Pulse is triggered if P flag = 0
In continuous mode the output current is fixed and continuous. Switched mode uses a trigger input toswitch the output on or off.
Selected mode uses a trigger input to select between the two different brightness settings. Brightness 1 must be greater than brightness 2. The P flag can be used to invert the trigger input.
The output current can be varied from 0% to 100% of full brightness.
7.2 Pulsed output
The output is off by default. When the RTxx is triggered, it waits for a delay and then pulses the output. The delay,pulse width, retrigger delay and pulse intensity are all configurable.
Retrigger delay is the minimum allowed time from one trigger to the next. Any triggers that happen too soon after the previous trigger are ignored. The retrigger delay is set in multiples of 100μs.
When connected to a light, the brightness can be set up to 1000% of its rating, but only for short periods and at low duty cycles,so that the lighting does not overheat and get damaged. The table below shows the operating limits:
Output brightness
Maximum
pulse width
Maximum duty cycle
0 to 100% 999ms 100%
101% to 200% 30ms 30%
201% to 300% 10ms 20%
301% to 500% 2ms 10%
501% to 1000% 1ms 5%
The duty cycle is limited by ignoring triggers which are too soon after the previous trigger.
26
WWW.STEMMER-IMAGING.COM
WWW.STEMMER-IMAGING.COM
Page 27
RTxxx LEDlighting control l ers - U ser Manual
For example, if the brightness is set to 250%, then the RTxxx does not allow pulses greater than 10ms long. With 10ms pulses, if a trigger occurs within 50ms of a previous trigger (so that the duty cycle would be greater than 20%) the trigger is ignored.
7.3 Fault detection
The RTxxx controller detects the following errors. The error code is shown on the webpage of an Ethernet controller (see Section 11, Webpage
configuration (RT220, RT420, RT820F)),or the communicationswindow of
an RS232 controller (see Section 12, Command configuration). When the output current is less than 100mA, some fault detection is disabled.
You can issue a GR command to cancel the error (see Section 12,
Command configuration). The RTxxx controller re-senses the light.
Error Reason
34, 37 Internal power dissipation is too high. Output turned off.
35, 43
Output current to lighting is too low. The light is open cir- cuit or there is not enough supplyvoltage for the reques- ted output current.
36
If the output voltage is too low, the controller detects that the output is short circuited.
37
The voltage required for the lighting has increased too much. Check for ageing of the lighting or a failed LED.
38
The voltage required for the lighting has decreased too much. Check for ageing of the lighting or a failed LED.
7.4 Light auto-sensing
When a channel does not have a light connected, the RTxxx continually tries to supply a very small current.
When a light is connected, it flashes for a short time (the light is not damaged by this) until the RTxxx detects that it is conected.
For voltage rated lights, the light is briefly driven at an increasing amount until 100%output brightness is achieved in order to sense the current rating of the light. This can generate the following errors:
27
WWW.STEMMER-IMAGING.COM
Page 28
RTxxx LEDlighting control l ers - U ser Manual
Display error
Comms error number
Reason
E1 Err 21
Current output is too low. This may be because the light has become disconnected.
E2 Err 22
The lighting required more than the maximum available current for the voltage rating.
E3 Err 23
Current output is not what was expected. The controller might need calibrating.
E6 Err 23
The power rating of the light exceeds the maximum power rating.
7.5 Cold start
You can clear the RTxxx configuration to its default settings- this clears the lighting ratings and sets all channels to 50% brightness continuous operation. You can do this by sending the CL command using Ethernet or serialconnection.
28
WWW.STEMMER-IMAGING.COM
WWW.STEMMER-IMAGING.COM
Page 29
RTxxx LEDlighting control l ers - U ser Manual
8 Lighting setup
The rating of the light must be set by the user. This rating is the supply to the lighting that should be used to get 100% continuous brightness from the light. The RTxxx is compatible with both current and voltage rated lighting.
You must enter the rating for the light before connecting it to the controller, or if you replace it with a different type of light. If a light is replaced with the same type of light then the previous rating still applies.
Consult the specification or labelling for the light. For commercially available lighting modules, if a voltage and current rating is given, use the current rating. If a voltage and wattage rating is given, use the voltage rating. Otherwise use the current rating. For homemade lights using single LEDs or arrays of LEDs use the current rating from the LED datasheet.
You can set the current rating from 0.01A to 3A in steps of 0.01A, and you can set the voltage rating from 12V to 36V in steps of 1V.
When you connect a voltage rated light, the RTxxx automatically senses the current rating of the light.
Voltage and current rated lights are both driven with a constant current. This gives better brightness stability and allows the RTxxx to prevent the light being driven with too much power.
To set the rating of a light on RS232 or Ethernet versions of the RTxxx controller, use the VL command (see Section 12, Command
configuration), or use the internal webpages on Ethernet versions of the
RTxxx controller (see Section 11, Webpage configuration (RT220, RT420,
RT820F)).
29
WWW.STEMMER-IMAGING.COM
Page 30
RTxxx LEDlighting control l ers - U ser Manual
9 Front panel configuration (RT200)
Using the front panel keypad, you can set the configuration for each channel, set a keylock code so unauthorised users cannot change any settings, set the internal trigger time, view trigger status, and set the voltage or current rating.
9.1 Startup
On power up, the RT200 displays b for five secondsfollowed by 8.8.8. to show that the display is working, then
RT 2 and 0 0, followed by the
firmware version (for example
03 9). The controller is then ready for
operation. When the RT200 is not being configured the display indicates the statusof
both channels as shown below:
The RT200 displays an error if a light is connected but no rating has been specified. See Section 9.2, Setting the light rating.
To configure the RT200 from the front panel, press and hold SEL for 1 second.
CH 1 is displayed. You can then use the p and q keys to scroll
through the menu, pressing the SEL button to access the required set up as shown in the table below:
Display Select to:
CH 1
Set up output channel 1
CH 2
Set up output channel 2
LO C
Set up a key lock
Fr E
Set up the internal trigger
30
WWW.STEMMER-IMAGING.COM
WWW.STEMMER-IMAGING.COM
Page 31
RTxxx LEDlighting control l ers - U ser Manual
Display Select to:
tr g
View the trigger status
UA L
View the output current
rA t
Set the lighting rating
During the setup of a channel, the trigger can be set to active high or low according to the P flag setting. Error checking can be enabled or disabled using the E flag.
9.2 Setting the light rating
Press and hold SELfor one second , CH1 is displayed. Use the p and q buttons to scroll to
rA t and follow the keystrokes below:
rAt
is displayed.Press the
SEL
button.
Use the p and q buttonstoselect the channel you want toset the rating for, and press the
SEL
button.
Cur is displayed. Press the SELbutton if your light is current rated. Or...
31
WWW.STEMMER-IMAGING.COM
Page 32
RTxxx LEDlighting control l ers - U ser Manual
If your light is voltage rated, use the p and q buttonsto select
Uol
and press the
SEL
button.
For current rated lights, use the p and q but- tons to set the rating in Amps, and press the
SEL
button.
Or...
For voltage rated lights use the p and q but- tons to set the rating in volts, and press the SELbutton.
The light's rating is set up and the RT200 is ready to use.
9.3 Setting up continuous output
Press and hold SELfor one second , CH1 is displayed. Use the p and q buttons to select the channel you want toset up, and follow the keystrokes
below:
The channel you want toset up is displayed. Press the
SEL
button.
32
WWW.STEMMER-IMAGING.COM
WWW.STEMMER-IMAGING.COM
Page 33
RTxxx LEDlighting control l ers - U ser Manual
Use thepandqbuttonsto select
SCo
and
press the
SEL
button.
bri
is displayed.Press the
SEL
button to select
the light's intensity.
Use the p and q buttonstoset the intensity from 1% to 99.9%. The default setting is 50%.
Press the SELbutton.
To set the error detection,press the
SEL
button
with
F E
displayed.
Or...
If you wish to disable the error detection, use thepandqbuttonsto select
F-E
, and press
the
SEL
button.
Continuous output is set up on the RT200.
33
WWW.STEMMER-IMAGING.COM
Page 34
RTxxx LEDlighting control l ers - U ser Manual
9.4 Setting up switched output
Switched output is when the light remainson for as long as there is a signal on the trigger input. Press and hold SELfor one second ,
CH 1 is
displayed. Use the p and q buttons to select the channel you want to set up, and follow the keystrokesbelow:
The channel you want toset up is displayed. Press the
SEL
button.
Use thepandqbuttonsto select
SOn
and
press the
SEL
button.
bri
is displayed.Press the
SEL
button to select
the light's intensity.
Use the p and q buttonstoset the intensity from 1% to 99.9%. The default setting is 50%.
Press the SELbutton.
trg
is displayed.Press the
SEL
button.
34
WWW.STEMMER-IMAGING.COM
WWW.STEMMER-IMAGING.COM
Page 35
RTxxx LEDlighting control l ers - U ser Manual
Use the p and q buttonstoselect the trigger (
IP1orIP2
) you want toset up, and press the
SEL
button.
To set the trigger polarity so that it is active high, press the
SEL
button with
F P
displayed.
Or...
If you wish to set the trigger polarity so that it is active low, use the p and q buttons to select
F-P
and press the
SEL
button.
To set the error detection,press the
SEL
button
with
F E
displayed.
Or...
If you wish to disable the error detection, use thepandqbuttonsto select
F-E
, and press
the
SEL
button.
Switched output is set up on the RT200.
35
WWW.STEMMER-IMAGING.COM
Page 36
RTxxx LEDlighting control l ers - U ser Manual
9.5 Setting up selected output
Set up selected output if you want to switch between to lighting levels on a trigger input. Press and hold SELfor one second ,
CH 1 is displayed. Use
the p and q buttonstoselect the channelyou want to set up, and follow the keystrokes below:
The channel you want toset up is displayed. Press the
SEL
button.
Use thepandqbuttonsto select
SSE
and
press the
SEL
button.
b1
is displayed.Press the
SEL
button to set the
first intensity level.
Use the p and q buttonstoset the first intens- ity level from 1% to 99.9%. The default settingis 50%.
Press the SELbutton.
b2
is displayed.Press the
SEL
button to set the
second intensity level.
36
WWW.STEMMER-IMAGING.COM
Page 37
RTxxx LEDlighting control l ers - U ser Manual
Use the p and q buttonstoset the second intensity level from 1% to 99.9%. The default settingis 50%.
Press the SELbutton.
trg
is displayed.Press the
SEL
button.
Use the p and q buttonstoselect the trigger (
IP1orIP2
) you want toset up, and press the
SEL
button.
To set the trigger polarity so that it is active high, press the
SEL
button with
F P
displayed.
Or...
If you wish to set the trigger polarity so that it is active low, use the p and q buttons to select
F-P
and press the
SEL
button.
37
WWW.STEMMER-IMAGING.COM
Page 38
RTxxx LEDlighting control l ers - U ser Manual
To set the error detection,press the
SEL
button
with
F E
displayed.
Or...
If you wish to disable the error detection, use thepandqbuttonsto select
F-E
, and press
the
SEL
button.
Selected output is set up on the RT200.
9.6 Setting up pulsed operation
Pulsed operation allows you to set up the characteristicsof the lighting pulse irrespective of the trigger pulse duration. Press and hold SELfor one second ,
CH 1 is displayed. Use the p and q buttons to select the channel
you want to set up, and follow the keystrokes below:
The channel you want toset up is displayed. Press the
SEL
button.
Use thepandqbuttons to select
SPu
and
press the
SEL
button.
38
WWW.STEMMER-IMAGING.COM
Page 39
RTxxx LEDlighting control l ers - U ser Manual
bri
is displayed.Press the
SEL
button to set the
lighting intensity.
Use the p and qbuttons to set the lighting intensity from 1% to 999%. Press the
SEL
button.
dEL is displayed. Press the SEL buttonto set up the delay time as described in Section9.7,
Setting time periods.
Press the SELbutton.
PUL is displayed.Press the SEL buttonto set up the pulse width as described in Section 9.7,
Setting time periods.
Press the SEL button.
rEt is displayed. Press the SELbuttontoset up the retrigger time as described in Section 9.7,
Setting time periods.
Press the SELbutton.
39
WWW.STEMMER-IMAGING.COM
Page 40
RTxxx LEDlighting control l ers - U ser Manual
trg
is displayed.Press the
SEL
button.
Use the p and q buttonstoselect the trigger (
IP1orIP2
) you want toset up, and press the
SEL
button.
To set the trigger polarity so that it is active high, press the
SEL
button with
F P
displayed.
Or...
If you wish to set the trigger polarity so that it is active low, use the p and q buttons to select
F-P
and press the
SEL
button.
To set the error detection,press the
SEL
button
with
F E
displayed.
Or...
40
WWW.STEMMER-IMAGING.COM
Page 41
RTxxx LEDlighting control l ers - U ser Manual
If you wish to disable the error detection, use thepandqbuttonsto select
F-E
, and press
the
SEL
button.
Pulsed operation is set up on the RT200.
9.7 Setting time periods
When the RT200 requires you to enter a numeric value, the right hand digit flashes to indicate you can use the p and q buttons to change the value.
To set pulse delay,retrigger, and pulse width values a scheme is used where the exponent (power of 10) of the value is set. The exponent values are as follows:
Exponent value
Multiplier
Number format
Range of values
E-2 0.01 9.99
Valuesare displayed in seconds from 10ms to 5s in steps of 10ms.
E-3 0.001 999.
Valuesare displayed in milliseconds from 1ms to 999ms in steps of 1ms.
E-4 0.0001 99.9
Valuesare displayed in milliseconds from 0.1ms to
99.9ms in steps of 0.1ms.
E-5 0.00001 9.99
Valuesare displayed in milliseconds from 0.01ms to
9.99ms in steps of 0.01ms.
E-6 0.000001 999.
Valuesare displayed in microseconds from 1μs to 999μs in steps of 1μs.
Note: The permitted range of values for pulse delay, pulse width, and
retrigger time is given in Section 13, Reference information, or as limited by the operating conditions of the light.
41
WWW.STEMMER-IMAGING.COM
Page 42
RTxxx LEDlighting control l ers - U ser Manual
Follow the keystrokes below to enter numerical data into the RT200 using the above scheme:
E-2
is displayed.Press the
SEL
button to enter time valuesfrom
10ms to 5s.
Use the p and q buttonstoselect the required value in steps of 10ms. Press the
SEL
button.
E-3
is displayed.Press the
SEL
button to enter time valuesfrom 1ms to 999ms.
Use the p and q buttonstoselect the required value in steps of 1ms. Press the
SEL
button.
E-4
is displayed.Press the
SEL
button to enter time valuesfrom
0.1ms to 99.9ms.
42
WWW.STEMMER-IMAGING.COM
Page 43
RTxxx LEDlighting control l ers - U ser Manual
Use the p and q buttonstoselect the required value in steps of 0.1ms. Press the
SEL
button.
E-5
is displayed.Press the
SEL
button to enter time valuesfrom
0.01ms to 9.99ms.
Use the p and q buttonstoselect the required value in steps of 0.01ms. Press the
SEL
button.
E-6
is displayed.Press the
SEL
button to enter time valuesfrom 1μs to 999μs.
Use the p and q buttonstoselect the required value in steps of 1μs. Press the
SEL
button.
9.8 Setting the internal trigger timer
You can set an internal trigger timer when the RT200 is in pulse mode. When set, the RT200 triggers with the same delay and pulse width already set up, as described in Section 9.6, Setting up pulsed operation. External triggering remainsunchanged.
43
WWW.STEMMER-IMAGING.COM
Page 44
RTxxx LEDlighting control l ers - U ser Manual
Ensure the RT200 is set to pulsed operation. To set the period of the internal trigger, press and hold SELfor one second and follow the keystrokes below:
Use thepandqbuttonsto select
FrE
and
press the
SEL
button.
OFF
is displayed.Press the
SEL
button to end
the sequence.
Or...
Use thepandqbuttonsto selectOnand press the
SEL
button.
The internal trigger is running with the parameters set up in Section 9.6, Setting up
pulsed operation.
9.9 Using the key lock
You can lock the RT200 front panel keypad so that unauthorised users cannot change the configuration. To do this you can set a numeric code from 0 to 255, which providesmoderate protection.
To lock the keypad, press and hold SEL for one second.
CH 1 is displayed.
Follow the keystrokes below:
44
WWW.STEMMER-IMAGING.COM
Page 45
RTxxx LEDlighting control l ers - U ser Manual
Use thepandqbuttonsto select
LOC
, and
press the
SEL
button.
To set up the lock code, use the p and q buttonsto selectLc. Press the
SEL
button.
0
is displayed.Use thepandqbuttonsto set
a lock code value from 0 to 255, and press the
SEL
button.
The RT200 keypad is locked.
To unlock the keypad, press and hold SELfor one second and follow the keystrokes below:
LOC
is displayed. Keep pressing the
SEL
button.
45
WWW.STEMMER-IMAGING.COM
Page 46
RTxxx LEDlighting control l ers - U ser Manual
Un
is displayed.Press the
SEL
button.
Use the p and q buttonstoenter the lock code and press the
SEL
button.
CH1 is displayed and the RT200 keypad is unlocked.
If the code entered is incorrect, LOC is displayed.
46
WWW.STEMMER-IMAGING.COM
Page 47
RTxxx LEDlighting control l ers - U ser Manual
9.10 Viewing the trigger status
You can view the trigger input statusand whether the light is pulsing when the RT200 is set to pulse mode. To do this, press the SELbutton for one second and
CH 1 is displayed. Use the p and q buttons to select t r g
and press SEL. The display shown below appears:
9.11 Viewing the output current
You can view an approximate measure of the output current from the RT200 front panel. The current measurement is updated roughly once per second, but this can be slower when the RT200 is set to pulsed operation.
To view the output current, press the SEL button for one second and
CH 1
is displayed.Follow the keystrokesbelow:
Use thepandqbuttonsto select
UAL
and
press the
SEL
button.
47
WWW.STEMMER-IMAGING.COM
Page 48
RTxxx LEDlighting control l ers - U ser Manual
CH1
is displayed.Use thepandqbuttonsto
select
CH2
if you wish to view the output
current from channel 2. Press the
SEL
button.
The measured output current is displayed. Press the
SEL
button.
Continue touse the RT200 normally.
48
WWW.STEMMER-IMAGING.COM
Page 49
RTxxx LEDlighting control l ers - U ser Manual
10 Ethernet communication
(RT220, RT420, RT820F)
You may need to ask your network administrator for advice about setting up the Ethernet connection.
Ethernet set up is not affected by cold booting the RTxxx. See Application note APP923(available from www.gardasoft.com
) for
troubleshooting Ethernet problems.
10.1 Connection
The Ethernet link uses a 10Base-Tconnectionon an RJ45 connector.The RTxxx is usually connected to a network switch, hub or router, but you can connect it directly into the network port on a PC using a crossover cable.
10.2 IP Address
The RTxxx needs an IP address to communicate over Ethernet. There are two ways to get an IP address; either programmed into the unit or using DHCP.
For DHCP mode, the RTxxx acquiresits IP address, subnet mask and gatewayaddress from a DHCP server. Otherwise the RTxxx has a fixed IP address, subnet mask and gatewayaddress.
DHCP mode or the IP address can be set and read using the GardasoftMaint program available at www.gardasoft.com
.
The GardasoftMaint window is shown below:
49
WWW.STEMMER-IMAGING.COM
Page 50
RTxxx LEDlighting control l ers - U ser Manual
GardasoftMaint allows you to view the controllers on your network, change their IP addresses and upgradetheir firmware if it becomes necessary. In the messaging sectionof GardasoftMaint, you can communicate with your controller using the commands explained in Section 12, Command
configuration. You can also open the selected controller's web pagesat
the click of a button. For more information about the RTxxx's web pages, see Section 11, Webpage configuration (RT220, RT420, RT820F).
10.2.1 DHCP
Most networksuse a DHCP server. If there is a PC on the network, you may be able to find out whether a PC on the same network uses DCHP as follows:
i. Go to the Control Panel.
ii.
Select Network Connections.
iii.
Right click on Local Area Connection. Select Properties.
iv.
From the list, select Internet Protocol (TCP/IP), press Properties.
If Obtain an IP addressautomatically is set, then DHCP is probably used. However, there may be an alternative fixed IP address on the Alternative Configuration tab.
You can find out what IP addressis being used by a PC at any time by following the steps below:
i. Go to the Control Panel.
ii.
Select Network Connections.
iii.
Right click on Local Area Connection. Select Status.
iv.
Select the Support tab. The IP address is displayed.
10.2.2 Fixed IP address
When using a fixed IP address, you must ensure that you use an IP address that is not being used by any other device on the network. It is usual to keep the first three numbers of the IP address the same as other devicesand to change only the last number. For example, if you have a network consisting of a PC (IP address 192.168.1.35) and two RTxxs could be allocated addresses 192.168.1.201 and 192.168.1.202.
10.3 Automatic sensing
All the features below are implemented in sample C++ source code available for download from www.gardasoft.com.
The RTxxx sends a message on three events:
i. On power up
ii. When an IP address is received or renewed by DHCP
iii. When an enquiry message is received.
On the first two events, the message is broadcast. On the third it is a reply to a single IP address.
50
WWW.STEMMER-IMAGING.COM
Page 51
RTxxx LEDlighting control l ers - U ser Manual
An enquiry message is a UDP packet from source port 30310, destination port 30311 with the message body Gardasoft Search (8-bit ASCII, 13 characters).
The message output by the RTxxx is a UDP packet from source port 30311, destination port 30310. It is formatted as:
Gardasoft,RT220-20,000000,111111111111,22222222
(8-bit ASCII, 44 characters) where,
000000
The serial number of the unit
111111111111
The MAC address in 6 HEX bytes
22222222
The IP address in 4 HEX bytes
For example; for RT220-20, serial number 12345, IP address
192.168.1.103, MAC address 00.0B.75.01.80.99 the packet is formatted: Gardasoft,RT220-20,012345,000B75018099,C0A8016
51
WWW.STEMMER-IMAGING.COM
Page 52
RTxxx LEDlighting control l ers - U ser Manual
11.2 Configuration page
There is one configuration page for each output channel, as shown below:
You can set up all the parameters for each output channel. Pressing the Submit button updates the RTxxx configuration and saves the changes to non-volatile memory. On this page you can:
Change the current rating for the light. View some measured voltages and the actual output current. Set the output mode: continuous, pulsed, or switched. Set the pulse parameters.
53
WWW.STEMMER-IMAGING.COM
Page 53
RTxxx LEDlighting control l ers - U ser Manual
11.2 Configuration page
There is one configuration page for each output channel, as shown below:
You can set up all the parameters for each output channel. Pressing the Submit button updates the RTxxx configuration and saves the changes to non-volatile memory. On this page you can:
Change the current rating for the light. View some measured voltages and the actual output current. Set the output mode: continuous, pulsed, or switched. Set the pulse parameters.
53
WWW.STEMMER-IMAGING.COM
Page 54
RTxxx LEDlighting control l ers - U ser Manual
11.3 General setup page
The General Setup page allows you to set up or clear the webpage's password and set up the internal trigger. You can also enter any Ethernet command from Section 12, Command configuration.
54
WWW.STEMMER-IMAGING.COM
Page 55
RTxxx LEDlighting control l ers - U ser Manual
12 Command configuration
The RTxxx can be configured through the Ethernet connection using UDP or TCP/IP. You can download sample C++, C#, VB.NET code from
www.gardasoft.com
to allow configuration.
12.1 Ethernet configuration (RT220, RT420, RT820F)
For TCP, commands from a host should be sent to destination port 30313 with replies sent to destination port 30312. For UDP, commands from a host should be sent from source port 30312 to destination port 30313. Replies are sent from source port 30313 to destination port 30312.
A carriage return (ASCII 13) character should be sent to terminate the command line, in case multiple packets get joined together.
12.2 RS232 configuration (RT260, RT460, RT860F)
When using RS232 the COM port should be set to 115200 baud, 8 data bits, no parity, 1 stop bit, no handshaking.
A carriage return (ASCII 13) character should be sent to terminate the command line.
12.3 Command structure
Communication consists of commands sent by the host (controlling PC). All output generated by the command is returned in reply UDP or TCP/IP packets. The last character sent is > (greater than’ symbol). Once this is received, the host knows that the command has been completed.
We recommend that the host waits for the > symbol before sending the next command. UDP communicationsare not guaranteed to arrive, so the host software must be able to cope with lost messages.
Using the GT command, a host can request that a message is sent to it whenever an error occurs.
Several commands can be put into one command line by separating them by a semi-colon (; ).The RTxxx sends any replies to the commands followed by a > character to show that the command line has completed.
All commands comprise a code of two letters followed by any optional parameters. All spaces in the commands are ignored.
Numeric parameters are separated by a comma(, ). For a parameter which is a time period,the default units are milliseconds. ‘s’, ms’ or us’ can be added to the end of the number toindicate seconds, milliseconds or microseconds. For currents, ‘A or ‘ma can be added to indicate amps or milliamps. The default unit is amps.
55
WWW.STEMMER-IMAGING.COM
Page 56
RTxxx LEDlighting control l ers - U ser Manual
Note: parameters are in USA/UKformat so that a half is written ‘0.5 not
‘0,5’. For example:
Parameter Meaning
0.1 0.1 millisecond 200μs 200 microseconds
0.1s 0.1seconds 100ma 100mA
2.45A 2.45A
2.3 2300mA or 2.3A
The command codes and their meaningare described in Section 12.3.1,
Generalcommands. The upper case commands are shown, followed by
lower case letters denoting the numeric argument.
12.3.1 General commands
Any changesyou make using Ethernet commands are not saved permanently until you send the AW command.
Report the version of firmware running in the RTxxx
This command returns the firmware version. For example:
VR returns
RT420-20 (HW02) V031
Set Internal Trigger
Enable or disable the internal trigger. When enabled, all outputs are triggered simultaneously using an internaltrigger signal. This setting can be saved to non-volatile memory using the AW command.
TT0
Disable internal trigger
TT1
Enable internal trigger (uses previously set period)
TT1,p
Enable internal trigger and set the period
Where:
P = period of the triggers in milliseconds
For example:
TT1,200
Set the internaltrigger to 200ms (5Hz)
TT1,500US
Set the internaltrigger to 500μs (2KHz)
56
WWW.STEMMER-IMAGING.COM
Page 57
RTxxx LEDlighting control l ers - U ser Manual
Save the settings to memory
AW
Once the settings are saved to memorythey are retained when the unit is switched off. If this is not done, changesto the settings are volatile, and if the unit is switched off they revert to those in force when the last AW command was issued.
Clear Configuration
CL
Clears the channel configuration and lighting ratings and sets all channels to 50% continuous operation. The results of the VL, RS,
RW, RU, RT, RE, RP, TT, and AW commands are all cleared.
Show Configuration
ST
This command shows the operational parameters for all channels in the controller. A typicaloutput for an RT220 controller is:
CH1,MD0,S50.0,0.0,DL1.000ms,PU1.000ms,RT0.0us,IP1,FL0,CS0. 000A,RA0.000A
CH2,MD0,S50.0,0.0,DL1.000ms,PU1.000ms,RT0.0us,IP2,FL0,CS0. 000A,RA0.000
Where:
CH
Channel number
MD
Mode: 0 = continuous, 1 = pulse, 2 = switched, 3 = select
S
Brightness percentage settings: 1st setting used in all modes 2nd settingonly used for select mode
DL
Pulse delay
PU
Pulse width
RT
Retrigger delay
IP
Input trigger (set using the
RP
command)
FL
Flags (set using the
RE
command)
CS
Rating of the light (after SafeSense has successfully completed sensing the light)
RA
Rating of the light (set using theVLcommand).
57
WWW.STEMMER-IMAGING.COM
Page 58
RTxxx LEDlighting control l ers - U ser Manual
When using Ethernet, use the following forms of the ST command:
ST0
Reports the general settings. A typical output is:
TM 1, TP 20.00ms
STc
Where:
c = the input channel(1 to 2, 4, or 8 dependingon model).
This reports the settings for a single channel.
Simulate an Input Trigger
TRc
Where:
c = the input channel(1 to 2,4 or 8, dependingon model).
This simulates a trigger pulse. If the channelis in pulse mode it pulses the output once.
Enable Ethernet Messages
GTm
Where:
m = 0 to disable Ethernet messages, or m = 1 to enable Ethernet messages.
When Ethernet messages are enabled, any error reports are sent to the most recent UDP or TCP address from which a command has been received. Messages are of the form:
Evtc,e
Where:
c = the channel number (1 to 2,4 or 8), or 0 for no channel
e = event value (see Section 13.5, Event codes).
Clear any Errors
GR
If Ethernet messages are not enabled, the last event or error number can be read by this command. Any error displayed on the unit is cleared, so if there was a lighting error, the RTxxx resumesauto- sensing on that channel.
The reply is in the same form as the GT command above. If there are no outstanding events or errors, then only the prompt > is returned.
58
WWW.STEMMER-IMAGING.COM
Page 59
RTxxx LEDlighting control l ers - U ser Manual
Set/Clear the Webpage Password
EY EY asc1, asc2, asc3, asc4, asc5, asc6
This command sets the password required to access the webpages. If EY is entered on its own then the password is cleared. There are six optional parameters, which are decimal ASCII values for a password from one to six letters. A value of 65 is ‘A’, 66 is ‘B’, and so on, to 90 is ‘Z’.
You can set an unlock code. This can be used as a low-security way of allowing trusted users to unlock the keypad. Ethernet commands and the web pagesstill work. The settingof this command is restored after a power cycle.
12.3.2 Lighting channel commands
Set the rating of a light
This command sets the current or voltage rating for a light. If a current rating is being set, then the voltage rating value should be 0.
VLo,v,c
Where:
o = output channel (1 to 2, 4 or 8, depending on model) v = voltage rating (0 or 12 to 36) c = current rating (0 or 10mA to3A)
Set continuous mode
The output is set to continuous mode at a percentage of full brightness.
RSc,s
Where:
c = output channel (1 to 2, 4 or 8, dependingon model) s = settingin percent (s = 0 to 100)
Set switched mode
The output is set to switched mode at a percentage of full brightness.
RWc,s
Where:
c = output channel (1 to 2, 4 or 8 dependingon model) s = settingin percent (s = 0 to 100)
59
WWW.STEMMER-IMAGING.COM
Page 60
RTxxx LEDlighting control l ers - U ser Manual
Set selected mode
The output is set to selected mode with two brightness settings.
RUc,s,t
Where:
c = output channel (1 to 2, 4 or 8, dependingon model) s = brightness 1 settingin percent (s = 0 to 100) t = brightness 2 setting in percent (t = 0 to s)
Set pulse mode
The output can be set up to pulse on a trigger input. The delay from trigger to the start of the pulse, the length of the pulse and the brightness are configurable.
An error is generated if the brightness settingrequires a current greater than 20A or if the combination of pulse width and settingis not allowed.
RTc,p,d,s RTc,p,d,s,r
Where:
c = output channel (1 to 2, 4 or 8, dependingon model) p = pulse width in milliseconds (0.02 to 999) d = delay from trigger to pulse in milliseconds (0.02 to 999) s = settingin percent (s = 0 to 999) r = retrigger delay. This parameter is optional.
Set the Option Flags
REc,m
Where:
c = output channel (1 to 2, 4 or 8, dependingon model) m = flags:
bit 1 =
01E flag set (error detection enabled)
E flag cleared (error detection disabled)
bit 2 =
01P flag set (positive triggers)
P flag cleared (negative triggers)
Set the Trigger Input
This command sets which input is used for pulse and switch output modes.
RPc,p
60
WWW.STEMMER-IMAGING.COM
Page 61
RTxxx LEDlighting control l ers - U ser Manual
Where:
c = output channel (1 to 2, 4 or 8, dependingon model) p = trigger input (1 or 2)
This command can be used to override the state of an input. The override is cancelled as soon as an edge is detected on the input.
12.3.3 Command summary
Command Example Effect
AW
AW Save changes.
CL
CL Clear configuration.
GT
GT1 Enable Ethernet messages.
GR
GR Clear any error conditions
EY
EY65,66 Set webpage password to 'AB'.
VR
VR Read the firmware version.
VL
VL1,0,0.5 Set the rating of channel 1 to 0.5A.
RS
RS2,65 Set channel 2 to 65% brightness
continuous.
RW
RW1,50 Set channel1 to 50% switch mode.
RU
RU1,75,25 Set channel 1 to selected mode at
75% and 25%.
RT
RT2,3,4,50 Set channel2 to 3ms pulses, delayed
by 4ms at 50% brightness.
RP
RP1,2 Output channel 1 is triggered using
output 2
RE
RE1,3 Set channel 1 to ignore lighting errors
and not prompt for the current rating of a light when it is connected.
TT
TT1,1ms Set internal triggers every 1ms.
TR
TR2 Trigger channel 2.
ST
ST2 Show configuration for channel 2.
61
WWW.STEMMER-IMAGING.COM
Page 62
RTxxx LEDlighting control l ers - U ser Manual
13 Reference information
This sectioncontains the specification for the RTxxx and any restrictions on its use. Error and event codes are also listed.
13.1 Specification
The RTxxx range of controllers has a 2 amp option with a '-2' suffix, and a fast pulsing option with an 'F' suffix. The specification for these is shown below alongside standard versions.
RTxxx-20 RTxxx-2
Each output channel
3Amaximum continuous / 20A pulsed, 46V output and 30W average output power*
2Amaximum continuous /
2A pulsed, 46V output and
30W average output power*
Lighting rating
12V to 36V in steps of 1V
100mA to 3A in steps of 5mA
12V to 36V in steps of 1V
100mA to 2A in steps of 1mA
Operating modes Continuous, strobe, switch, and selected
Trigger input
Opto-isolated, standard or inverted operation
3V to 24V
Pulse width:
(RT2xx, RT4xx )
20 microsecondsto1 second. Repeatable to
0.1 microseconds.
Pulse width:
(RT2xxF, RT4xxF RT8xxF)
1 microsecond to 1 second. Repeatable to
0.1 microseconds.
Trigger delay:
(RT2xx, RT4xx )
20 microsecondsto1 second. Repeatable to
2 microseconds.
Trigger delay:
(RT2xxF, RT4xxF RT8xxF)
2 microsecondsto 1 second. Repeatable to
2 microseconds.
Internal trigger timer 0.2Hz to 1kHz
Supplyvoltage 24VDC to 48VDC regulated
Heat dissipation 10W maximum
*Refer to Section 13.2, Restrictions
62
WWW.STEMMER-IMAGING.COM
Page 63
RTxxx LEDlighting control l ers - U ser Manual
13.2 Restrictions
The maximum output power for an RT2xx is 30W per channel or 40W total. For an RT4xx, it's 30W per channel or 50W total. The maximum output power for an RT8xxF is 30W per channel or 100W total.
The following timings and restrictions are applied whenever settingsare saved (using the AW command).
B.1 Continuous Mode
The maximum output current is 3A (2A for an RTxxx-2).
B.2 Switched Mode
The maximum delay from a trigger input changing to the output current being turned on or off is 10us. The maximum output current is 20A (2A for an RTxxx-2).
B.3 Selected Mode
The maximum delay from a trigger input changing to the output current being turned on or off is 5ms. The maximum output current is 0.5A.
B.4 Pulse Mode
The maximum output current is 20A (2A for an RTxxx-2). For high current pulses the following limits apply:
Pulse current Pulse length limit
20A 100μs 12A 400μs 10A 1ms 5A 3ms
Pulses of 2A or more for pulse widths longer than 2ms may cause an error or have a lower current towards the end of the pulse.
For fast pulse controllers (RTxxxF) the minimum pulse delay is about 2μs. When overdriving or using the retrigger delay, the minimum delay is around 5μs.
For pulse widths less than approximately 150us, the output voltage and current cannot be measured. Because of this, fault detectionis disabled and the following restrictions apply:
For pulse currents greater than 0.5A, the duty cycle is restricted to 1%. For pulse currents less than or equal to 0.5A, the duty cycle restricted to
10%.
Special note for RT8xxF controllers: If you need to generate a variety of
output currents, the highest current loads should be connected to the low- numbered output channels. For example CH1, CH2... This minimises the spread of high currents on the internal PCB and helps to maintain a low temperature rise in the unit.
63
WWW.STEMMER-IMAGING.COM
Page 64
RTxxx LEDlighting control l ers - U ser Manual
13.3 Error codes
Error number Reason
Err 1 A parameter value is invalid.
Err 2 Command not recognised.
Err 3 Numeric value is the wrong format.
Err 4 Wrong number of parameters.
Err 5
This is a warning, not an error. One of the para- meters is out of range. The value of the parameter has been adjusted. For example, sending an RT command with a delay of 0 gets a reply of ‘Err 5. The command is accepted but the delay is set to the minimum allowed value.
Err 19
A light has been connected to a channel but no rat- ing has been set.
Err 8, 12
EEPROM corrupt. The configuration has been cleared.
Err 9, 20 Could not save settings to EEPROM.
Err 21, 22, 23 Sensing error. See Section 6.2, Light auto-sensing.
Err 27
Can’t read Ethernet settings from EEPROM, so these may be incorrect.
Err 34, 47
Internal power dissipation is too high. Output turned off.
Err 35 Output current to lighting is too low.
Err 43
The requested output current requirestoo high a voltage.
Err 36 The output is short circuit.
Err 42 The output current is too high.
Err 37
The voltage required for the lighting has increased too much. Check for ageing of the lighting or a failed LED.
Err 38
The voltage required for the lighting has decreased too much. Check for ageing of the lighting or a failed LED.
Err 39
Internal protection has prevented SafePower voltage going too high.
64
WWW.STEMMER-IMAGING.COM
Page 65
RTxxx LEDlighting control l ers - U ser Manual
13.4 Fatal error codes
Error number Reason
Err 44
The RTxxx is too hot. The RTxxx has a thermal cutout which operates around 65°C to 70°C, dependingon conditions.
Err 40, Err 41 Err 45
One channelis outputting more current than expected.
Err 46 One channelis dissipating more than 30W.
Err 47
Internal protection has prevented too much heat in the output driver.
13.5 Event codes
Event messages are sent when a light is connected or an error occurs. The format of these is:
Evt<channel>,<event code>;
These event messagesare only sent after the GT1 command has been sent.
Event number Reason
1 to 127
An error has occurred. The error code is given by the event number.
128 A light has been connected and is working.
129
A light has been connected but doesnt have a current or voltage rating.
130 An over temperature error occurred.
131 An over current error occurred.
132
An error has occurred while autosensing the rating of a light.
138 SafePower trainup has completed.
139 SafePower trainup has failed or been cancelled.
140
In switch output mode, the light has been turned off because the duty cycle is too high.
65
WWW.STEMMER-IMAGING.COM
Page 66
RTxxx LEDlighting control l ers - U ser Manual
Issue v013 - July 2019
© Copyright 2019 Gardasoft Vision Ltd
Gardasoft Vision Ltd
Trinity Court
Buckingway Business Park
Cambridge CB24 4UQ UK
tel: +44 1954 234970
fax: +44 1954 231567
Gardasoft LLC Oak Ridge Road Weare New Hampshire 03281 USA tel: +1 603-657-9026
www.gardasoft.com
ILL-GARD19-10/2019 ∙ Subject to technical change without notice. No liability is accepted for errors which may be contained in this document.
ILL-GARD31-10/2019 ∙ Subject to technical change without notice. No liability is accepted for errors which may be contained in this document.
WWW.STEMMER-IMAGING.COM
WWW.STEMMER-IMAGING.COM
Loading...