Gantner Electronic GEA1150002A User Manual

Installation, Operation, Configuration Document version 1.2
GAT Access 6100
GAT Access 6100
F BIO
(GAT Access 6100 F + GAT FR 055
)
GAT Access 6100
F
Enrollment Station
GAT
TimeAxx
6150
GAT Access 6100 GAT Access 6100 F BIO GAT Access 6100 F Enrollment Station GAT TimeAxx 6150
Entry Control and Shower Control Terminals
GAT Access 6100, GAT Access 6100 F BIO, GAT Access 6100 F Enrollment Station, GAT TimeAxx 6150
General Warning and Safety Instructions
Dear customer, We congratulate you on having selected a product (appliance or software) from GANTNER Electronic GmbH. Our aim is to ensure that our product operates with safety and to your complete satisfaction. To achieve this aim we take this opportunity to familiarize you with the following guidelines:
1. Installation, commissioning, operation and maintenance of the purchased product must be carried out in accordance with the instructions, i.e., in accordance with the technical conditions of operation as described in the corresponding product documentation.
2. Before installation, commissioning, operation or maintenance it is therefore essential that you read the corresponding chapter of this manual and observe its instructions.
3. If there are still some points on which you are not entirely clear, please do not take a chance. All queries can be clarified by your Gantner company representative, or by ringing the GANTNER Electronic GmbH hotline.
4. Where not otherwise specifically documented, the appropriate installation, commissioning, operation and maintenance of the product is the customer’s responsibility.
5. Directly on receipt of the goods, inspect both the packaging and the product itself for any signs of damage. Additionally, check that the delivery is complete and includes all accessories, documentation, auxiliary devices, etc.
6. If the packaging or product has been damaged in transport, or should you suspect that it may have a fault, the product must not be put into service. In this case, contact your Gantner company representative. They will make every effort to resolve the problem as quickly as possible.
7. Installation, commissioning and servicing of our appliances must only be carried out by suitably trained personnel. In particular, electrical connections must only be made by correspondingly qualified specialists. Here, the appropriate installation provisions in accordance with the relevant national Electrical Engineers construction regulations (e.g., ÖVE, [Austrian] VDE, [German]...) must be observed.
8. Where not otherwise stated, installation and maintenance work on our appliances must be carried out when disconnected from the power supply. This applies in particular to appliances that are normally supplied by low-voltage current.
9. It is prohibited to alter the device or to remove protective shields and covers.
10. Do not attempt yourself to repair an appliance after a defect, failure or damage, or to put it back into operation again. In such cases, it is essential you contact either your Gantner company representative or the GANTNER Electronic GmbH hotline.
11. GANTNER Electronic GmbH accepts no responsibility for any injuries or damage caused as a result of improper use.
12. Although every care is taken and we are continuously aiming for improvement, we cannot completely exclude the possibility of errors appearing in our documentation. GANTNER Electronic GmbH therefore accepts no responsibility for the completeness or the accuracy of this manual. The right is reserved to make alterations, and we may carry out alterations at any time without giving prior notice.
13. Should you discover any fault with the product or in its accompanying documentation, or have any suggestions for improvement, you may confidently approach either your Gantner company representative or GANTNER Electronic GmbH directly.
14. We especially look forward to hearing from you if you just want to tell us that everything is functioning perfectly.
We wish you a successful experience with our product and look forward to welcoming you again as a customer soon.
Contact address / manufacturer:
GANTNER Electronic GmbH Montafonerstrasse 8 A - 6780 Schruns/Austria Tel.: +43 5556 73784 - 0 Fax: +43 5556 73784 - 8000 Email: info@gantner.com Website: www.gantner.com
www.gantner.com
HB_GAT-ACCESS6100--EN_12
3
GAT Access 6100, GAT Access 6100 F BIO, GAT Access 6100 F Enrollment Station, GAT TimeAxx 6150
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device must not cause harmful interference, and (2) this device must accept any interference received, including
interference that may cause undesired operation.
FCC Label
Applicable for the following devices:
- GAT Access 6100 F
- GAT Access 6100 F BIO
- GAT Access 6100 F Enrollment Station
This WEEE symbol on GANTNER products and their packaging indicates that the corresponding material must not be disposed of with normal household waste. Instead, such marked waste equipment must be disposed of by handing it over to a designated electronic waste recycling facility. Separating and recycling this waste equipment at the time of disposal will help to conserve natural resources and ensure that it is recycled in a manner that protects human health and the environment. Please contact your local authority for details on your nearest electronic waste recycling facility.
Copyright 2015 by GANTNER Electronic GmbH, Schruns (Austria).
Copyrights: Operating instructions, manuals and software are protected by copyright ©. All rights are reserved. Copying,
duplication, translation, installation in any electronic medium or machine-readable form in whole or in part is prohibited. The sole exception is represented by creation of a back-up copy of software for own use as a safeguard, so far as this is technically possible and recommended by us. Any infringement will render the party committing such infringement liable to compensation payment.
Liability: Any claims against the manufacturer based on the hardware or software products described in this manual shall
depend exclusively on the conditions of the guarantee. Any further-reaching claims are excluded, and in particular, the manufacturer accepts no liability for the completeness or accuracy of the contents of this manual. The right is reserved to make alterations, and alterations may be made at any time without prior notice being given.
Trademarks: Attention is drawn at this point to the logos and registered trademarks used in this manual.
4
HB_GAT-ACCESS6100--EN_12
www.gantner.com
GAT Access 6100, GAT Access 6100 F BIO, GAT Access 6100 F Enrollment Station, GAT TimeAxx 6150 Table of Contents
TABLE OF CONTENTS
1. GENERAL ...................................................................................................................................................... 7
1.1 Intended Use ........................................................................................................................................... 7
1.2 Device Types .......................................................................................................................................... 8
1.3 Standard Operation ............................................................................................................................... 10
1.4 Operating Modes ................................................................................................................................... 10
1.5 Other Devices in the GAT Access 6xxx Series ..................................................................................... 11
1.6 Function Matrix for the GAT Access Devices ....................................................................................... 12
1.7 Special Functions and Options ............................................................................................................. 13
1.7.1 GAT Device Finder Support ........................................................................................................... 13
2. MOUNTING THE GAT ACCESS 6100 TERMINALS .................................................................................. 15
2.1 GAT Access 6100 ................................................................................................................................. 15
2.1.1 Wall Mounting ................................................................................................................................ 15
2.2 GAT Access 6100 F BIO ....................................................................................................................... 17
2.2.1 Wall Mounting ................................................................................................................................ 17
2.3 GAT Access 6100 F Enrollment Station ............................................................................................... 20
2.4 GAT TimeAxx 6150 ............................................................................................................................... 21
2.4.1 Surface Mounting ........................................................................................................................... 21
2.4.2 Flush Mounting .............................................................................................................................. 23
3. ELECTRICAL CONNECTIONS ................................................................................................................... 27
3.1 Power Supply ........................................................................................................................................ 27
3.2 Network ................................................................................................................................................. 28
3.2.1 Ethernet Network ........................................................................................................................... 28
3.3 Connection to Turnstile or Door ............................................................................................................ 29
3.4 Checklist for Final Installation ............................................................................................................... 30
4. START-UP AND CONFIGURATION ........................................................................................................... 31
4.1 Starting the GAT Access 6100 .............................................................................................................. 31
4.2 System Settings .................................................................................................................................... 32
4.2.1 Service Menu of GAT Access 6100 ............................................................................................... 32
4.2.2 Communication Parameters .......................................................................................................... 33
4.2.3 Reader Settings ............................................................................................................................. 34
4.2.4 Date and Time Settings ................................................................................................................. 35
4.2.5 Display Contrast ............................................................................................................................. 35
4.2.6 Restore Factory Settings ............................................................................................................... 35
4.3 Configuration Settings ........................................................................................................................... 36
4.3.1 Direct Configuration ....................................................................................................................... 36
4.3.2 Project Configuration ..................................................................................................................... 39
4.3.3 List of Configuration Settings ......................................................................................................... 41
4.3.4 Display Texts ................................................................................................................................. 45
4.4 Configuration of Offline Emergency Mode for a GAT Access 6100 ..................................................... 46
5. OPERATION ................................................................................................................................................ 49
5.1 Control and Display Elements ............................................................................................................... 49
5.2 General .................................................................................................................................................. 50
5.3 User Operation at a GAT Access 6100 ................................................................................................. 51
5.3.1 Additional Acknowledgment or Selection by the User ................................................................... 52
5.3.2 Problem when Writing to the Data Carrier ..................................................................................... 52
5.4 User Operation at a GAT Access 6100 F BIO ...................................................................................... 53
5.5 User Operation at a GAT Access 6100 F Enrollment Station ............................................................... 53
5.5.1 Enrol Fingerprints at the Enrollment Station .................................................................................. 53
5.5.2 Deactivation of the Fingerprint Verification .................................................................................... 57
5.5.3 Verifying the Functionality of a Data Carrier .................................................................................. 58
5.5.4 Cleaning the Fingerprint Sensor .................................................................................................... 59
www.gantner.com
HB_GAT-ACCESS6100--EN_12
5
GAT Access 6100, GAT Access 6100 F BIO, GAT Access 6100 F Enrollment Station, GAT TimeAxx 6150 Table of Contents
5.6 Standard Operation for the GAT TimeAxx 6150 with Countdown Functionality .................................. 59
5.7 Online Mode and Emergency Mode ..................................................................................................... 61
5.8 Out of Order Screen ............................................................................................................................. 62
5.9 Locker Check-In ................................................................................................................................... 63
5.10 General Open Function (Group Entry) ............................................................................................. 64
5.11 External Release Function................................................................................................................ 64
6. COMMUNICATION ..................................................................................................................................... 65
6.1 Online Mode ......................................................................................................................................... 65
6.2 Emergency Mode ................................................................................................................................. 65
6.3 Out of Operation Mode ......................................................................................................................... 65
7. UPDATING THE GAT ACCESS 6100 ........................................................................................................ 67
7.1 Updating with GAT Config Manager .................................................................................................... 67
8. TROUBLESHOOTING AND FAQ .............................................................................................................. 71
8.1 How can I update the firmware of a GAT Access 6100? ..................................................................... 71
8.2 How do I configure a GAT Access 6100? ............................................................................................ 71
8.2.1 How do I activate service mode? .................................................................................................. 71
8.3 Which TCP/IP ports can be used by a GAT Access 6100? ................................................................. 72
8.4 Which bit rates are used by a GAT Access 6100 for Ethernet and is this configurable? .................... 72
8.5 How can I set the date and time of a GAT Access 6100? ................................................................... 72
8.6 How can I find the IP address of a GAT Access 6100 and change it? ................................................ 72
8.7 How can I find the MAC address of a GAT Access 6100? .................................................................. 73
8.8 Setting IP address when MAC address is not known and IP address of the terminal is 0.0.0.0 ......... 73
8.9 Difference between "Time" and "Delay" in the "Mode" field for Locker Check-In configuration? ........ 73
8.10 Meaning of optocoupler settings "Rising_Edge", "Falling_Edge", "Rising- and Falling Edge"? ....... 74
8.11 How can the reader of a GAT Access 6100 B be authorised for LEGIC®? ...................................... 74
8.12 How can I read or delete the authorisation data of a GAT Access 6100? ....................................... 74
8.13 How can I configure the display texts of a GAT Access 6100? ........................................................ 74
8.14 The relay of the GAT Access 6100 is activated even if the host has denied access. ...................... 75
8.15 Which FUNLINE protocol commands are supported by a GAT Access 6100? ............................... 75
8.16 Why does the GAT Access 6100 deny access with my data carrier in Emergency mode? ............. 75
8.17 What is the maximum start-up current consumption of a GAT Access 6100? ................................. 75
8.18 What are the factory settings of a GAT Access 6100? ..................................................................... 75
8.19 How do I configure a GAT Access 6100 for offline emergency mode? ............................................ 77
8.20 What is the data carrier certificate? .................................................................................................. 77
9. TECHNICAL DATA ..................................................................................................................................... 79
9.1 Dimensions ........................................................................................................................................... 81
9.1.1 GAT Access 6100 ......................................................................................................................... 81
9.1.2 GAT Access 6100 F BIO ............................................................................................................... 81
9.1.3 GAT Access 6100 F Enrollment Station ....................................................................................... 82
9.1.4 GAT TimeAxx 6150 ....................................................................................................................... 82
9.1.5 FCC and ICES Information ........................................................................................................... 83
6
HB_GAT-ACCESS6100--EN_12
www.gantner.com
GAT Access 6100, GAT Access 6100 F BIO, GAT Access 6100 F Enrollment Station, GAT TimeAxx 6150 General

1. GENERAL

This manual describes the installation, configuration and operation of the terminals GAT Access 6100, GAT Access 6100 F BIO, GAT Access 6100 F Enrollment Station and GAT TimeAxx 6150. More information about these device types see next chapter. GANTNER Electronic GmbH also offers other types of access terminals, which are described in separate manuals.
Note: The GAT Access 6100 F BIO is a combination of the GAT Access 6100 F with a GAT FR 055 fingerprint
reader, which is used at the GAT Access 6100 F Enrollment Station. In this manual the combination of these two parts will be referenced as "GAT Access 6100 F BIO".
For identification of visitors, contactless RFID (Radio Frequency Identification) data carriers are used. Data carriers are available in a variety of different forms such as plastic wristbands and chip cards. Data transmission between the data carrier and the GAT Access 6100 is encoded for optimal security.
For technological flexibility, the access terminal is available with different types of RFID readers (all 13.56 MHz). The following codes are used for the terminals to indicate the used RFID technology:
- GAT Access 6100 B: LEGIC® Prime
- GAT Access 6100 F: MIFARE®
- GAT Access 6100 ISO: ISO 15693
- GAT Access 6100 F BIO: MIFARE®
- GAT Access 6100 F Enrollment Station: MIFARE®
- GAT TimeAxx 6150 B: LEGIC® Prime
- GAT TimeAxx 6150 F: MIFARE®
- GAT TimeAxx 6150 ISO: ISO 15693
Supported Segments on Data Carriers
The memory on a RFID data carrier is segmented. Different types of segments are possible. For LEGIC® data carriers, the following segments are supported:
- Cash1
- Cash2
- Locker
- UserData
For MIFARE® data carriers, the segments for locker and fingerprint data are supported.
For ISO 15693 data carriers, the segments for locker data are supported.

1.1 Intended Use

The GAT Access 6100 B/F/ISO and GAT Access 6100 F BIO terminals are intended to be used for identifying persons in leisure facilities like public baths, fitness clubs and spas by reading their RFID data carriers and granting acces to controlled areas according to the access rights of the persons. The GAT Access 6100 F Enrollment Station is used to capture fingerprints of persons, which are then stored on the data carriers of the persons for later verification of the persons. The fingerprints are not stored anywhere else except the data carriers of the persons. The GAT TimeAxx 6150 B/F/ISO is intended to control the usage time of showers in leisure facilities like public baths or fitness clubs.
www.gantner.com
HB_GAT-ACCESS6100--EN_12
7
GAT Access 6100, GAT Access 6100 F BIO, GAT Access 6100 F Enrollment Station, GAT TimeAxx 6150 General

1.2 Device Types

This manual provides information on the following access terminals:
- GAT Access 6100 B, F and ISO
- GAT Access 6100 F BIO
- GAT Access 6100 F Enrollment Station
- GAT TimeAxx 6150 B, F and ISO These terminals share the same electronic hardware and have similar operating modes and functions. The difference is the type of RFID technology supported, the functionality, the housing type of the GAT TimeAxx 6150 and the fingerprint-reading functionality.
Note: In this manual, the term "GAT Access 6100" refers to all of the terminals described above in general. If a
section of the manual is only applicable for a certain type of access terminal, the type will be indicated explicitly.
The GAT Access 6100 terminal is used for access control in leisure facilities such as swimming pools, spas and gyms. It can be installed at turnstiles or gates, which control the entry or exit to certain areas. The access terminal checks the authorisation of visitors and allows entry through an access point such as a turnstile or gate. The terminal is designed to be wall-mounted or integrated with a turnstile (using the GAT Holder system). It has a graphical LC-display, 4 function keys for configuration or user input on the front side, an LED bar with red/green/yellow lights for status indication and a blue/red/green LED on the RFID scan field.
1 ... Four-segment LED display 2 ... Monochrome display (LCD) 3 ... Function keys 4 ... Illuminated, round scan field 5 ... Device back part 6 ... Device upper part
Figure 1.1 - GAT Access 6100
The GAT Access 6100 F BIO is similar to the GAT Access 6100 F and is equipped with a fingerprint reader for additional verification of the guest’s identity. If the visitor is authorised to enter the facility AND the fingerprint read by the terminal’s fingerprint sensor is the same as the fingerprint stored on the user’s data carrier, access is granted.
1 ... Four-segment LED display 2 ... Monochrome display (LCD) 3 ... Function keys 4 ... Illuminated, round scan field 5 ... Device back part 6 ... Device upper part 7 ... Fingerprint reader GAT FR 055 8 ... Fingerprint sensor of GAT FR 055 9 ... Weather protection cover (optional)
Figure 1.2 - GAT Access 6100 F BIO
8
HB_GAT-ACCESS6100--EN_12
www.gantner.com
GAT Access 6100, GAT Access 6100 F BIO, GAT Access 6100 F Enrollment Station, GAT TimeAxx 6150 General
The GAT Access 6100 F Enrollment Station is located at a central location such as the reception desk of a leisure facility. When visitors first register at the facility the device is used to scan the visitor’s fingerprint(s) and to transmit the fingerprint data directly onto the visitor’s personal data carrier. The fingerprint data is only ever stored on the visitor’s data carrier and never in the terminal or any other location in the facility.
1 ... Four-segment LED display 2 ... Monochrome display (LCD) 3 ... Function keys 4 ... Illuminated, round scan field 5 ... Device back part 6 ... Device upper part 7 ... Fingerprint reader 8 ... Fingerprint sensor 9 ... Stand
Figure 1.3 - GAT Access 6100 F Enrollment Station
The GAT TimeAxx 6150 is an elegant terminal for public baths, fitness studios and other leisure facilities where the duration of use of services must be regulated. When used as a shower terminal, the terminal is installed directly in the shower cubicle (see mounting instructions) and, via a digital output, controls an electrovalve that activates or deactivates the shower. The remaining time is continuously shown to the user on a large graphical display, which helps to reduce overall water consumption. This device has the same electrical hardware as the other GAT Access 6100 terminals but uses a waterproof housing for flush or surface mounting in shower areas. The terminal also has a display and LED signals, but no mechanical buttons for user input.
1 ... Four-segment LED display 2 ... Monochrome display (LCD) 3 ... Illuminated, round scan field 4 ... Front frame 5 ... Device upper part (below the front frame) 6 ... Device back part
Figure 1.4 - GAT TimeAxx 6150
www.gantner.com
HB_GAT-ACCESS6100--EN_12
9
GAT Access 6100, GAT Access 6100 F BIO, GAT Access 6100 F Enrollment Station, GAT TimeAxx 6150 General

1.3 Standard Operation

When a visitor of the leisure facility holds their data carrier next to the illuminated round RFID scan field, the GAT Access 6100 reads the information on the data carrier and sends the data over the network (Ethernet) to a server for evaluation. The visitor’s authorisation is checked and a response returned to the GAT Access 6100. When access is granted, the GAT Access 6100 activates a corresponding relay output that opens the connected turnstile or gate for a certain time period.
Visitors using the GAT Access 6100 F BIO must also scan their fingerprints (if this is activated) for additional verification. The terminal compares the scanned fingerprint of a visitor with the data stored on the visitor’s data carrier and grants access only when the visitor is authorised and the fingerprint data matches.
Different settings for the GAT Access 6xxx, e.g., the access time of a turnstile/gate or the text displayed on the terminal, can be defined via the configuration settings in GAT Config Manager. See "4.3. Configuration Settings" for more information on configuring the terminals.
Note: The GAT TimeAxx 6150 operates differently to the description above. After user identification the terminal
activates the external application (e.g., opens the shower valve) and starts a countdown timer. The user can pause the countdown and restart as required. After a configurable time the terminal deactivates the application.

1.4 Operating Modes

The GAT Access 6100 access terminals operate in online mode. They must always be connected to a server/host computer. In Online mode the GAT Access 6100 automatically sends the information of a data carrier over the interface to the host computer and waits for an appropriate reaction from the host. An exception is the GAT Access 6100 F Enrollment Station, which usually operates in Offline Mode.
For instances where an error occurs or the communication is interrupted, the GAT Access 6100 can switch into Emergency mode or Out of Order mode (depending on the configuration). For more information about the operating modes see chapter "6. Communication".
10
HB_GAT-ACCESS6100--EN_12
www.gantner.com
GAT Access 6100, GAT Access 6100 F BIO, GAT Access 6100 F Enrollment Station, GAT TimeAxx 6150 General

1.5 Other Devices in the GAT Access 6xxx Series

In addition to the previously mentioned access devices in the GAT Access 6100 family, GANTNER Electronic GmbH also offers the following access terminals in the 6xxx series.
GAT Access 6200 This is an access terminal for hidden installation and with a connected external antenna for reading the data carriers of the visitors. The terminal itself has no display or keys for operation. More information on the GAT Access 6200 is available in a separate manual.
1 ... Cable inlet 2 ... Screws for locking the housing 3 ... Mechanical lock
Figure 1.5 - GAT Access 6200
GAT Access 6350
This access terminal has a monochrome display, signal lights and an internal reader to read the visitor’s data carriers. The terminal is designed to integrate with access hardware such as turnstiles. More information on the GAT Access 6350 is available in a separate manual.
1 ... Monochrome display (LCD) 2 ... Traffic light display (red/green) 3 ... Acknowledge key 4 ... Illuminated, round scan field 5 ... Screw terminals for cable connection 6 ... Housing
Figure 1.6 - GAT Access 6350
www.gantner.com
HB_GAT-ACCESS6100--EN_12
11
GAT Access 6100, GAT Access 6100 F BIO, GAT Access 6100 F Enrollment Station, GAT TimeAxx 6150
GAT Access 6100 B GAT Access 6100 F GAT Access 6100 ISO GAT Access
6100 F BIO
GAT Access 6100 F
Enrollment Station
GAT TimeAxx 6150 B GAT TimeAxx 6150 F GAT TimeAxx 6150 ISO GAT Access 6200 B GAT Access 6200 F GAT Access 6200 ISO GAT Access 63
50 B
GAT Access 6350 F GAT Access 6350 ISO GAT Access 6500 B GAT Access 6500 F GAT Access 6500 ISO GAT Access 6600
B
GAT Access 6600 F GAT Access 6600 ISO
Online Functions
UID (card number)
X X X X X X X X X X X X X X X X X X X X Read locker data
X X X X X X X X X X X X X X X X X X X X Read cash 1 data
X - - - - X - - X - - X - - X - - X - - Read cash 2 data
X - - - - X - - X - - X - - X - - X - - Write locker check-in
X X X X X X X X X X X X X X X X X X X X Emergency operation
X X X X X X X X X X X X X X X X X X X X Offline Emergency mode2)
- X - - - - X - - - - - - - - - - - - - Bookings
X X X X X X X X X X X X X X X X X X X X Check FID and Sub-FID 1)
X X X X X X X X X X X X X X X X X X X
X
Device parts
Display
X X X X X X X X - - - X X X X X X X X X Number of function keys
4 4 4 4 4 0 0 0 4*
4*
4*
4*
4*
4* 4 4 4 4*
4*
4*
Internal antenna
X X X X X X X X - - - X X X X X X X X X External antenna
- - - - - - - - X X X X X X X X X X X X Serial Interface RS 485
- - - - - - - - X X X X X X X X X X X
X
Ethernet TCP/IP
X X X X X X X X X X X X X X X X X X X X Relay outputs
1 1 1 1 1 1 1 1 4 4 4 4 4 4 4 4 4 4 4 4 Optocoupler inputs
1 1 1 1 1 1 1 1 4 4 4 4 4 4 3 3 3 4 4 4 Barcode
- - - - - - - - X X X X X X X X X X X
X
General
GAT Access 6500 This access terminal has a monochrome display, traffic light status display and internal reader, just like the GAT Access 6350. The difference to the GAT Access 6350 is that the housing of the GAT Access 6500 is designed for installation onto a wall or holder. The description of the GAT Access 6500 is available in a separate manual.
1 ... Monochrome display (LCD) 2 ... Traffic light display (red/green) 3 ... Function keys 4 ... Illuminated, round scan field 5 ... Mounting frame 6 ... Display unit
Figure 1.7 - GAT Access 6500

1.6 Function Matrix for the GAT Access Devices

Table 1.1 gives an overview of the functionalities of the different GAT Access devices and the connectible hardware.
X ... Available * .... On the rear/inside of device
- .... Not available
Table 1.1 - Function matrix of the GAT Access 6xxx devices
12
HB_GAT-ACCESS6100--EN_12
1)
The FID and Sub-FID check depends on the configuration
2)
Requires "GAT Access 6100 F Upgrade” licence, see "4.4. Configuration of Offline
Emergency Mode for a GAT Access 6100 "
www.gantner.com
GAT Access 6100, GAT Access 6100 F BIO, GAT Access 6100 F Enrollment Station, GAT TimeAxx 6150 General

1.7 Special Functions and Options

1.7.1 GAT Device Finder Support

The GAT Access 6100 terminals implement the Device Finding technology from GANTNER Electronic GmbH, which allows devices on a TCP/IP network to be found without knowing their exact IP addresses or network name. The GAT Device Finder software scans a TCP/IP network and lists all found devices.
Figure 1.8 - GAT Device Finder Support
The Device Finding technology uses the UDP protocol and port 8216. All GAT Access 6100 are set to use this port 8216 by default.
www.gantner.com
HB_GAT-ACCESS6100--EN_12
13
GAT Access 6100, GAT Access 6100 F BIO, GAT Access 6100 F Enrollment Station, GAT TimeAxx 6150 General
14
HB_GAT-ACCESS6100--EN_12
www.gantner.com
GAT Access 6100, GAT Access 6100 F BIO, GAT Access 6100 F Enrollment Station, GAT TimeAxx 6150 Mounting the GAT Access 6100 Terminals

2. MOUNTING THE GAT ACCESS 6100 TERMINALS

The GAT Access 6100 devices can be mounted directly onto a flat surface such as a wall.
Attention: The GAT Access 6100 must not be mounted directly onto a metallic surface as this can
negatively affect the reading field so that the data carriers may not be read anymore.
In the following sections the mounting of the GAT Access 6100 and GAT Access 6100 F BIO are described. The GAT Access 6100 F Enrollment Station has a stand and can just be placed, for example, onto a table without mounting.
For the mounting of the GAT TimeAxx 6150 terminal see "2.4 GAT TimeAxx 6150".

2.1 GAT Access 6100

2.1.1 Wall Mounting

First, the device back part of the GAT Access 6100 is secured by screws to a flat background (e.g. concrete wall). When fixing to an uneven background the device back part must not be distorted, as this will prevent correct connection of the upper part. The recommended mounting height from the top edge of the device to the floor is 1.3 meters.
1. Flush-mounted cable
2. Surface-mounted cable
3. Back box
4. Device back part
5. Cable conduit for surface cable connection
Figure 2.1 - Mounting measures
Cable Inlets
The housing of the GAT Access 6100 has cable inlets both, for flush (1) or surface (2) installed cables. When the cables are surface mounted please check whether the cables can still be inserted once the device back part has been mounted, otherwise run the cables through the cable lead-ins prior to securing.
Attention: See chapter "3. Electrical Connections" for information about the electrical connection. The
connection of the cables must always be performed in powerless state!
www.gantner.com
HB_GAT-ACCESS6100--EN_12
15
GAT Access 6100, GAT Access 6100 F BIO, GAT Access 6100 F Enrollment Station, GAT TimeAxx 6150 Mounting the GAT Access 6100 Terminals
Mounting the Device Upper Part
Once the connection cables are terminated, the device back part and upper part are connected together via a connection cable (already connected in the upper part) and the two parts are fixed together.
Figure 2.2 - Connection and mounting of the device upper part
Notes:
1. Check the socket in the device back part (circled in figure 1). Dirt, dust and humidity must be removed so that a good contact of the connection cable is guaranteed. No aggressive detergent may be used. Please do not damage socket contacts. Attention: Cleaning only in powerless state.
2. Plug in the connection cable into the socket in the device back part (consider alignment) and clip the top of the device upper part into the device back part.
3. Swing down the device upper part until it clicks.
4. The device can only be opened with the supplied special tool! With this, the two catches on the bottom of the device can be unlocked in succession.
Figure 2.3 - Opening the housing
16
HB_GAT-ACCESS6100--EN_12
www.gantner.com
GAT Access 6100, GAT Access 6100 F BIO, GAT Access 6100 F Enrollment Station, GAT TimeAxx 6150 Mounting the GAT Access 6100 Terminals

2.2 GAT Access 6100 F BIO

2.2.1 Wall Mounting

First, the back part of the GAT FR 055 reader is secured by 3 screws (a) to a flat background (e.g. concrete wall) according to the following dimensional drawing. When fixing to an uneven background the device back part must not be distorted, as this will prevent correct connection of the upper part. The recommended mounting height from the top edge of the device to the floor is 1.3 meters.
.
Figure 2.4 - Dimensions of GAT FR 055 back part and mounting holes (a)
Connection Cables
The connection cables (power supply, network etc.) are run through the cable lead-ins of the GAT FR 055. With concealed/flush wiring (1) the connection cables are fed from behind via the back box. With surface wiring (2) the connection cables must lie in the cable duct on the back part of the GAT FR 055.
www.gantner.com
HB_GAT-ACCESS6100--EN_12
17
GAT Access 6100, GAT Access 6100 F BIO, GAT Access 6100 F Enrollment Station, GAT TimeAxx 6150 Mounting the GAT Access 6100 Terminals
Figure 2.5 - Dimensions of GAT FR 055 back part and mounting holes (a)
Mounting the GAT Access 6100 F Back Part
Pay attention when fixing to an uneven background that the GAT FR 055 housing and the device back part of the GAT Access 6100 F must not be distorted. Recommended mounting height from the top edge of the device to the floor is 1.3 m.
1. GAT FR 055
2. Device back part of GAT Access 6100 F
3. Fastening screws
4. Connection cable
5. Connection cable GAT FR 055 to GAT Access 6100 F
6. Weather protection cover (optional)
7. Fastening screws for weather protection cover
Figure 2.6 - Mounting the GAT Access 6100 F back part
18
HB_GAT-ACCESS6100--EN_12
www.gantner.com
GAT Access 6100, GAT Access 6100 F BIO, GAT Access 6100 F Enrollment Station, GAT TimeAxx 6150 Mounting the GAT Access 6100 Terminals
Electrical Connection
The connection cables (see (4) in Figure 2.6) are connected at the device back part of the GAT Access 6100 F.
Attention: See chapter "3. Electrical Connections" for information about the electrical connection. The
connection of the cables must always be performed in powerless state!
Mounting of the GAT Access 6100 F Upper Part
The connection cable of the GAT FR 055 (1) is plugged into the housing upper part of the GAT Access 6100 F and the connection cable of the upper part (2) is plugged into the back part of the GAT Access 6100 F. Next, the device upper part can be swung down into the back part (3).
Figure 2.7 - Mounting the GAT Access 6100 F back part
Check the sockets (1) and (2)! Dirt, dust and humidity must be removed so that a good contact of the connection cable is guaranteed. No aggressive detergent may be used. Please do not damage socket contacts.
Attention: Cleaning must always be performed in powerless state!
www.gantner.com
HB_GAT-ACCESS6100--EN_12
19
GAT Access 6100, GAT Access 6100 F BIO, GAT Access 6100 F Enrollment Station, GAT TimeAxx 6150 Mounting the GAT Access 6100 Terminals
Opening the GAT Access 6100 F Upper Part
The device can only be opened with the supplied special tool! With this, the two catches on the bottom of the device can be unlocked in succession.
Figure 2.8 - Opening the housing
Maintenance
The sensor field of the GAT FR 055 should be cleaned from time to time so that fingerprints can be clearly scanned.
Attention: To clean the sensor field always use a damp (not wet!), smooth cloth. Acrid detergents and no
sharp materials must not be used.

2.3 GAT Access 6100 F Enrollment Station

The GAT Access 6100 F Enrollment Station is mounted onto a stainless-steel stand and placed directly on a table or similar.
Figure 2.9 - Dimensions of the GAT Access 6100 F Enrollment Station
20
HB_GAT-ACCESS6100--EN_12
www.gantner.com
GAT Access 6100, GAT Access 6100 F BIO, GAT Access 6100 F Enrollment Station, GAT TimeAxx 6150 Mounting the GAT Access 6100 Terminals

2.4 GAT TimeAxx 6150

Though the GAT TimeAxx 6150 housing is specially designed for flush mounting that only the front is visible, it can also be mounted onto a surface such as a wall without any back box.

2.4.1 Surface Mounting

1. Apply silicone around the cable entrance on the device back part. This is necessary to seal the housing after it is mounted on the wall.
Apply the silicone on the slightly recessed area (1) around the cable entrance. The amount of silicone must be
dosed so that after pressing the device to the wall the cable entrance is completely sealed.
2. Mount the device back part to the wall by using the three screws (2). Recommended mounting height is 1.3 m.
www.gantner.com
HB_GAT-ACCESS6100--EN_12
21
GAT Access 6100, GAT Access 6100 F BIO, GAT Access 6100 F Enrollment Station, GAT TimeAxx 6150 Mounting the GAT Access 6100 Terminals
3. Connect the connection cables at the screw terminal strips (4) in the device back part. For a description of the pin assignment and electrical specifications see "3. Electrical Connections".
4. Insert the rubber seal (5) in the device back part.
5. Attach the device upper part with the front print (7) by using the four screws included in the package of the GAT TimeAxx 6150 (6). Pay attention that the rubber seal is total closed around the housing.
22
HB_GAT-ACCESS6100--EN_12
www.gantner.com
GAT Access 6100, GAT Access 6100 F BIO, GAT Access 6100 F Enrollment Station, GAT TimeAxx 6150 Mounting the GAT Access 6100 Terminals
6. Push on the front frame (8). It holds in place with latches, without the need for screws.

2.4.2 Flush Mounting

For flush mounting of the GAT TimeAxx 6150 a back box is shipped together with the terminal. This back box can also be ordered as a separate article (GAT TimeAxx 6150 UP, Part No: 532325). Using the back box the GAT TimeAxx 6150 can be installed in brickwork, concrete and cavity walls.
a) Installation in Brickwork Walls
www.gantner.com
HB_GAT-ACCESS6100--EN_12
23
GAT Access 6100, GAT Access 6100 F BIO, GAT Access 6100 F Enrollment Station, GAT TimeAxx 6150 Mounting the GAT Access 6100 Terminals
1. Insert the FX tube (12) with the connection cable (3) into the opening of the back box. The opening is designed
for an FX tube with 25 mm outer diameter. In this case, the lugs (13) at the opening are holding the FX tube in place.
2. Insert the back box (10) into the wall recess (11) and make sure, that it is flush with the wall surface (see 15).
Fix the back box e.g. with plaster or PU foam (14).
3. Feed the connection cable (3) through the opening of the GAT TimeAxx 6150 back part.
4. Caulk the edge of the cable opening in the GAT TimeAxx 6150 back part with silicone (1) -> see also step 1 at
the description of the surface mounting.
5. Mount the GAT TimeAxx 6150 into the back box by using three screws (2). This is done the same way as
described in Step 2 of the surface mounting. Pay attention, that the cable opening is completely sealed with the previously applied silicone.
6. The remaining mounting procedure is the same as described at the surface mounting, beginning with step 3
onward.
Attention: To finish the installation the GAT TimeAxx 6150 must be hermetically sealed. Humidity/water
must never be able to penetrate into the housing. Pay special attention that the silicone applied in step 4 seals the housing completely and that the rubber seal (see step 4 of surface mounting) is inserted correctly and seals the housing in its entire length.
b) Installation in Concrete Walls
1. Unscrew the four screws of the back box (16) and remove them, together with the metal lugs.
24
HB_GAT-ACCESS6100--EN_12
www.gantner.com
GAT Access 6100, GAT Access 6100 F BIO, GAT Access 6100 F Enrollment Station, GAT TimeAxx 6150 Mounting the GAT Access 6100 Terminals
2. Insert the FX tube (12) with the connection cable (3) into the opening of the back box. The opening is designed for an FX tube with 25 mm outer diameter. In this case, the lugs (13) at the opening are holding the FX tube in place.
3. Place the back box (10) inside first onto the concrete formwork and nail it onto the formwork by using four nails (17) at the holes where the screws (16) had been removed in step 1. Pay attention that the back box lies flat, without any gap, on the formwork. If the connection cable (3) is already drawn-in, the cable must be placed inside the back box.
4. After the wall is concreted and hardened and the formwork is removed, cut the nails on the front side (18).
5. The remaining mounting procedure is the same as described for installation in masonry walls (see previous section a) ).
Attention: To finish the installation the GAT TimeAxx 6150 must be hermetically sealed. Humidity/water
must never be able to penetrate into the housing. Pay special attention that the silicone applied in step 4 seals the housing completely and that the rubber seal (see step 4 of surface mounting) is inserted correctly and seals the housing in its entire length.
c) Installation in Cavity Walls (e.g. Plasterboard Walls)
1. Cut-out a rectangle hole of 105.4 x 160.4 mm in the wall. The cut-out must not be larger than 107 x 162 mm, because the lugs of the back box must lie on the wall (see 19).
2. Insert the FX tube (12) with the connection cable (3) into the opening of the back box. The opening is designed for an FX tube with 25 mm outer diameter. In this case, the lugs (13) at the opening are holding the FX tube in place.
www.gantner.com
HB_GAT-ACCESS6100--EN_12
25
GAT Access 6100, GAT Access 6100 F BIO, GAT Access 6100 F Enrollment Station, GAT TimeAxx 6150 Mounting the GAT Access 6100 Terminals
3. Insert the back box (10) into the cut-out in the wall. The four corner lugs of the back box must lie on the wall (19).
4. Turn the four mounting screws (16) to the right. This will first also turn the lugs at the screws (20) by 90° to the right and then pull them forward. Turn the screws until the lugs hit the inside of the wall, which will fix the back box in place.
5. The remaining mounting procedure is the same as described at the installation in brickwork walls (see page 4).
Attention: To finish the installation the GAT TimeAxx 6150 must be hermetically sealed. Humidity/water
must never be able to penetrate into the housing. Pay special attention that the silicone applied in step 4 seals the housing completely and that the rubber seal (see step 4 of surface mounting) is inserted correctly and seals the housing in its entire length.
26
HB_GAT-ACCESS6100--EN_12
www.gantner.com
Loading...
+ 60 hidden pages