Gamewell FCI MS-7AF, MS-7, MS-7S Operating Instructions Manual

MS-7AF, MS-7
and MS-7S
Description
The Gamewell-FCI MS-7 Style manual fire alarm stations are available in a wide variety of configurations. The Sta­tions comply with the Americans with Disabilities Act (ADA) 5-lb. maximum pull force requirement. Operating instruc­tions and Braille text are engraved in the handle. All sta­tions have a key lock/reset which is keyed alike with Gamewell-FCI fire alarm control panels and other manual fire alarm stations.
MS-7AF Velociti Addressable Station
The MS-7AF Velociti® Series addressable station is a dou­ble action station designed for installation in the signaling line circuit of Gamewell-FCI analog addressable control panels. Activation of the station causes its assigned address to register at the control panel. The door contains an LED which flashes green in normal condition and lights steady red when the station has been activated.* The sta­tion features screw terminals.
MS-7ASF Velociti Addressable Station
The MS-7ASF Velociti® Series addressable station is a single action station designed for installation in the signal­ing line circuit of Gamewell-FCI analog addressable con­trol panels. Activation of the station causes its assigned address to register at the control panel. The door contains an LED which flashes green in normal condition and lights steady red when the station has been activated.* The sta­tion features screw terminals.
The Velociti col that substantially increases the speed of communica­tion between the sensors and certain Gamewell-FCI analog addressable fire alarm controls. These devices operate in a grouped fashion. If one of the devices in the group has a status change, the panel’s microprocessor stops the group poll and focuses on the single device. The net effect is response speed up to five times greater than earlier designs.
MS-7 Double Action Station
The MS-7 double action station is used with conventional­fire alarm control panels. It features a set of single pole contacts and screw terminals for connection to an initiating circuit.
Velociti® is a registered trademark of Honeywell International Inc.
®
UL
is a registered trademark of Underwriter’s Laboratories Inc.
LEXAN Electric Company.
®
Series stations use a communication proto-
®
is a registered trademark of GE Plastics, a subsidiary of General
Non-Coded, Manual
MS-7
Features
• Addressable stations compatible with all Gamewell-FCI analog addressable fire alarm controls
• Conventional stations suitable for use with any UL® Listed control panel
• Both single and double action stations available
• Tumbler lock for test and reset keyed alike with Gamewell-FCI controls
• Surface or semi-flush mounting
• Shock and vibration resistant
• Stations (MS-7LOB) Listed for outdoor applications
• Complies with ADA pull force requirements
Only the red LED is operative in panels that do not operate in Velociti mode.
An ISO 9001-2000 Company
SIGNALING
FM
MEA
Approved
APPROVED
3023594
67-02-E Vol.VIII
07150-0694:261S2465
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2008 by Honeywell International Inc. All rights reserved.
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
GAMEWELL-FCI
www.gamewell-fci.com 9020-0616 Rev. B2 page 1 of 2
MS-7S Single Action Station
The MS-7S single action station is used with conventional fire alarm control panels. It features a set of single pole contacts and wire leads for connection to an initiating cir­cuit.
MS-7SP Double Action Station
The MS-7SP is a double action station similar to the MS-7 station, with the additional feature of both English and Spanish instructions molded into the unit.
MS-7LOB Double Action Station (Listed for Outdoor Applications)
The MS-7LOB station must be mounted on a Model SB-I/O backbox. In retrofit applications, the station is UL Listed for use with the WP-10 backbox. It is intended for use with conventional control panels and has a set of single pole contacts and screw terminals.
Mounting
The MS-7 interior stations may be surface mounted (use backbox SB-I/0) or semi-flush mounted on a standard dou­ble-gang, or 4-inch (10.2 cm) square electrical box. An optional trim ring (BG-TR) may also be used for semi-flush mounting.
NYC-Plate
The NYC-Plate provides the backplate for the manual pull station. (See Figure 1).
Specifications
Material:
Contact Ratings: 0.25 amps. @ 30 VAC/VDC
Dimensions: 5 5/8” H x 4 1/4” W x 1 1/4” D
Operating Temperature (MS-7AF): 32° to 120° F (0° to 49° C) Relative Humidity (MS-7AF): 10 to 93% (non-condensing) Alarm Current: .0030 amp. 0.007 for LED Supervisory Current (MS-7AF): .00030 amps.
®
Lexan
(resistive)
(14 x 10.1 x 3.2 cm)
Ordering Information
Model Description
MS-7 Double action station. MS-7AF** Velociti addressable double
action station.
MS-7ASF Velociti addressable single action
station
MS-7S Single action station, wire leads. MS-7SP Double action station, English
and Spanish instructions.
MS-7LOB Double action station, outdoor
use. (Must use SB-I/O - Indoor/ outdoor use backbox).
SB-I/O Indoor/outdoor use backback-
box.
SB-10 Surface backbox. BG-TR. Trim ring for semi-flush mount NYC-Plate NYC backplate for manual pull
station
**For use with Gamewell-FCI analog addressable control panels only.
Figure 1 NYC-Plate
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9020-0616 Rev. B2 page 2 of 2
GAMEWELL-FCI
www.gamewell-fci.com
Loading...