Gamatronic POWER PLUS Technical Manual

Page 1
P
P
O
WEERR
O
W
+
+
MMoodduullaarr UUPPSS ssyysstteemm
1100 kkVVAA ttoo 110000 kkVVAA,, 33xx440000 VV
TTeecchhnniiccaall GGuuiiddee
Release 2.1, September 2009
Har Hotzvim Industrial Park,
14 Hartom St., PO Box 45029, Jerusalem 91450, Israel
Tel: +972-2-588-8222 Fax: +972-2-582-8875
Email: info@gamatronic.co.il Website: www.gamatronic.com
Page 2
Gamatronic Electronic Industries Ltd.
Har Hotzvim Industrial Park 14 Hartom St., PO Box 45029, Jerusalem 91450 Israel Tel: +972-2-588-8222 Fax: +972-2-582-8875 Email:
The equipment described in this document is not intended to be used in connection with any application requiring fail-safe performance, unless the application design includes appropriate redundancy. This exclusion includes, but is not limited to, the direct operation of any life support system or any other system whose failure could lead to serious injury, death, environmental damage or mass destruction.
© Copyright 2009 by Gamatronic Electronic Industries Ltd. All rights reserved worldwide.
The information contained in this document is proprietary and is subject to all relevant copyright, patent and other laws protecting intellectual property, as well as any specific agreement protecting Gamatronic Electronic Industries Ltd. rights in the aforesaid information. Neither this document nor the information contained herein may be published, reproduced or disclosed to third parties, in whole or in part, without the express, prior, written permission of Gamatronic Electronic Industries Ltd. In addition, any use of this document or the information contained herein for any purposes other than those for which it was disclosed is strictly forbidden.
Gamatronic Electronic Industries Ltd. reserves the right, without prior notice or liability, to make changes in equipment design or specifications.
Information supplied by Gamatronic Electronic Industries Ltd. is believed to be accurate and reliable. However, no responsibility is assumed by Gamatronic Electronic Industries Ltd. for the use thereof nor for the rights of third parties which may be affected in any way by the use thereof.
Any representation(s) in this document concerning performance of Gamatronic Electronic Industries Ltd. product(s) are for informational purposes only and are not warranties of future performance, either express or implied. Gamatronic Electronic Industries Ltd. standard limited warranty, stated in its sales contract or order confirmation form, is the only warranty offered by Gamatronic Electronic Industries Ltd. in relation thereto.
This document may contain flaws, omissions or typesetting errors; no warranty is granted nor liability assumed in relation thereto unless specifically undertaken in Gamatronic Electronic Industries Ltd. sales contract or order confirmation. Information contained herein is periodically updated and changes will be incorporated into subsequent editions. If you have encountered an error, please notify Gamatronic Electronic Industries Ltd. All specifications are subject to change without prior notice.
info@gamatronic.co.il Website: www.gamatronic.com
ii
Power+ Technical Guide
Page 3
Gamatronic Electronic Industries Ltd.
TABLE OF CONTENTS
1. SYSTEM STRUCTURE........................................................................................................ 1
2. FUNCTIONAL OVERVIEW.................................................................................................. 4
2.1 UPS Basic Module (10kVA / 8KW).......................................................................... 4
2.1.1 Single UPS Module Specifications ....................................................... 9
2.2 UPS System Controller ......................................................................................... 10
2.2.1 System Controller Specifications.......................................................12
2.3 Static Switch (ST/SW) Module.............................................................................. 12
3. SYSTEM INTERCONNECTION......................................................................................... 15
3.1 internal System wiring .......................................................................................... 16
3.1.1 The Power+ always requires a neutral line........................................ 20
3.1.2 UPS Module – Connectors Description.............................................. 24
3.1.3 UPS Module Pin Assignment Table.................................................... 25
3.2 DC Distribution Panel Cabling ............................................................................. 26
3.2.1 DC Fuses ............................................................................................... 28
3.3 AC Input Fuses ...................................................................................................... 29
3.4 AC Distribution Compartment..............................................................................30
3.5 AC Input/Output Main Terminals.......................................................................... 31
3.6 Static Switch Connections ................................................................................... 32
3.7 System Controller Connections........................................................................... 33
3.7.1 PC714 – the controller card.................................................................33
3.8 Setting the Shelf Address..................................................................................... 36
3.9 F.A.Q. (Frequently Asked Questions).................................................................. 39
3.9.1 Batteries ................................................................................................ 39
3.9.2 General................................................................................................... 40
3.9.3 Menus..................................................................................................... 41
3.9.4 Installation............................................................................................. 42
3.9.5 Mechanics ............................................................................................. 43
3.9.6 Common problems............................................................................... 43
4. SYSTEM INSTALLATION ................................................................................................. 45
4.1 Inspections to be Performed Prior to Installation.............................................. 47
4.2 Installation Procedure and System Start-up....................................................... 48
4.3 Initial Start-up Sequence ...................................................................................... 49
4.4 Checks to be Performed Following Initial Startup.............................................51
4.5 Special considerations for 1-phase output......................................................... 52
4.5.1 Dip-switch settings on the modules................................................... 52
4.5.2 Wiring of input and output terminals.................................................. 52
4.5.3 System start-up..................................................................................... 53
4.6 DIP switch settings of the UPS modules ............................................................ 54
5. USING THE SYSTEM CONTROLLER.............................................................................. 55
5.1 System information display.................................................................................. 56
5.2 Display UPS module data ..................................................................................... 59
5.3 Setting the Number of UPS Modules................................................................... 61
5.4 Retrieving History (LOG of Events).....................................................................62
5.5 System Controller Alarms.....................................................................................65
6. BATTERIES .......................................................................................................................66
6.1 Batteries and Configurations...............................................................................66
6.1.1 Internal Batteries .................................................................................. 66
6.1.2 External Batteries.................................................................................67
6.2 Installing and connecting the Batteries .............................................................. 67
Power+ Technical Guide
iii
Page 4
Gamatronic Electronic Industries Ltd.
6.2.1 Configuring the batteries to the system............................................. 69
7. DRY CONTACTS AND ALARM TERMINALS..................................................................70
7.1 DC Current measurement..................................................................................... 71
7.2 Temperature sensor..............................................................................................71
7.3 User-defined alarms..............................................................................................71
8. PERIODIC MAINTENANCE .............................................................................................. 72
8.1 Objectives of the Periodic Maintenance ............................................................. 72
8.2 Recommended Tools ............................................................................................ 72
8.3 Maintenance Procedures and Report.................................................................. 73
9. TROUBLESHOOTING....................................................................................................... 76
10. SYSTEM CONTROLLER & COMMUNICATIONS............................................................ 80
10.1 Introduction............................................................................................................ 80
10.2 SCC POWER+ characteristics.............................................................................. 80
10.3 Controller User Interface ...................................................................................... 81
10.4 Service Utilities...................................................................................................... 81
10.4.1 Start-up Screens................................................................................... 81
10.4.2 The Main Menu...................................................................................... 84
11. SETUP PROCEDURES.....................................................................................................85
11.1 Setting Alarm Thresholds..................................................................................... 85
11.1.1 Setting Alarm Vibration Parameters................................................... 86
11.1.2 Setting the Integration Factor for Alarms .......................................... 86
11.1.3 'Auto' Test Batteries............................................................................. 86
11.2 Setting Password Level 1 ..................................................................................... 86
11.3 Adding a POWER module..................................................................................... 87
11.4 System Controller setup verification................................................................... 88
11.4.1 ACCESS................................................................................................. 88
11.4.2 SCREEN 1.............................................................................................. 88
11.4.3 SCREEN 2.............................................................................................. 89
11.4.4 SCREEN 3.............................................................................................. 89
12. REPLACEMENT PROCEDURES...................................................................................... 90
12.1 UPS module............................................................................................................ 90
12.2 System Controller module.................................................................................... 91
12.3 Static Switch module ............................................................................................ 92
12.4 Replacing the controller's flash memory............................................................ 93
13. USING SERVICE PROGRAMS......................................................................................... 95
13.1 Access to Service Mode ....................................................................................... 95
13.2 Selecting the Controller’s Low Level Utilities .................................................... 96
13.3 Setting the Network Addresses ........................................................................... 96
13.3.1 Setting the SNMP Factor...................................................................... 96
13.4 Configuring Dry Contacts and Alarms................................................................97
13.4.1 Linking Alarms to Dry Contacts.......................................................... 97
13.4.2 Enabling and disabling specific alarms.............................................97
13.5 Calibrating Measurements.................................................................................... 98
13.6 Controller Self-Test ............................................................................................... 98
13.7 Battery Test............................................................................................................ 98
13.7.1 Periodic/Automatic Battery Test......................................................... 98
14. MONITORING THE SYSTEM............................................................................................ 99
14.1 Power Meter ........................................................................................................... 99
14.2 System Operating Times..................................................................................... 100
iv
Power+ Technical Guide
Page 5
Gamatronic Electronic Industries Ltd.
14.3 Main DIP Switch Status....................................................................................... 100
14.4 Panel and Slave DIP Switch Status ................................................................... 101
14.5 SC POWER+ Internal Power Supply..................................................................101
14.6 System Temperature...........................................................................................101
14.7 Internal Communication ..................................................................................... 102
14.8 Monitoring System Components.......................................................................103
14.8.1 Monitoring the Batteries .................................................................... 103
14.8.2 Monitoring Alarms.............................................................................. 104
14.9 After Using the Emergency Power Off .............................................................. 104
15. SYSTEM SPECIFICATIONS ........................................................................................... 105
16. SYSTEM MODULES ORDERING INFORMATION......................................................... 106
LIST OF FIGURES
Figure 1-1: Block diagram ...................................................................................................... 1
Figure 1-2: Sub-assemblies.................................................................................................... 2
Figure 1-3: 10kVA configuration............................................................................................2
Figure 1-4: 50kVA configuration............................................................................................3
Figure 1-5: 100kVA configuration..........................................................................................3
Figure 2-1: Single UPS Module- Front/Rear View ................................................................ 4
Figure 2-2: Block diagram of a single UPS Module ............................................................. 5
Figure 2-3: Power section of the PFC in a single UPS module .......................................... 6
Figure 2-4: Input currents of the PFC (without filters) ........................................................ 6
Figure 2-5: PFC control scheme ............................................................................................ 7
Figure 2-6: DC/AC inverter principal topology.....................................................................8
Figure 2-7: System controller - Front panel........................................................................ 10
Figure 2-8: System controller - Block diagram................................................................... 11
Figure 2-9: ST/SW front panel view ..................................................................................... 13
Figure 2-10: ST/SW block diagram ...................................................................................... 13
Figure 2-11: 3-Phase ST/SW block diagram ....................................................................... 14
Figure 3-1: Power+ system - Modular structure................................................................. 15
Figure 3-2: Schematic of a 3:1 Phase 30kVA POWER+ System....................................... 16
Figure 3-3: Schematic of a 3-Phase 30kVA POWER+ System.......................................... 17
Figure 3-4: POWER+ System - Rear View...........................................................................18
Figure 3-5: Control PCB and flat cable................................................................................ 19
Figure 3-6: Wrong way to connect UPS with grounded-neutral-generator..................... 21
Figure 3-7: Acceptable connection for grounded generator and 4-pole switch............. 22
Figure 3-8: Preferred generator (neutralized) and connection (3-pole)........................... 23
Figure 3-9: UPS module – Rear view...................................................................................24
Figure 3-10: UPS module connectors - Pin assignments ................................................. 24
Figure 3-11: DC distribution panel (50KVA model)............................................................ 27
Figure 3-12: DC distribution. panel (100kVA model) ......................................................... 27
Figure 3-13: DC fuses on front side of DC dist. panel (50KVA model) ............................ 28
Figure 3-14: DC fuses on front of DC dist. panel (100KVA model) .................................. 28
Figure 3-15: UPS modules - AC input fuses (100KVA model) ........................................... 29
Figure 3-16: AC input fuse assignments (50KVA model).................................................. 29
Figure 3-17: AC distribution.................................................................................................30
Figure 3-18: AC distribution panel (100KVA model).......................................................... 30
Figure 3-19: AC distribution panel (50KVA model)............................................................ 30
Figure 3-20: Input & output main terminals........................................................................ 31
Figure 3-21: Static switch terminals Rear view ............................................................... 32
Figure 3-22: System controller outside the shelf - Rear view...........................................33
Figure 3-23: Front side of PC714 card................................................................................. 34
Figure 3-24: Rear of PC714 – white rectangle indicates jumper area .............................. 34
Figure 3-25: The jumpers on PC714 .................................................................................... 34
Figure 3-26: The PC917 Control PCB on a shelf – general view....................................... 36
Power+ Technical Guide
v
Page 6
Gamatronic Electronic Industries Ltd.
Figure 3-27: DIP switches on PC719 card– close-up......................................................... 37
Figure 3-28: Recommended master/slave DIP switch settings........................................37
Figure 3-29: DIP switch settings...........................................................................................38
Figure 4-1: POWER+ system connections.......................................................................... 45
Figure 4-2: Switch and wire ratings for 10-100kVA installation.......................................46
Figure 4-3: Start-up screen 1................................................................................................49
Figure 4-4: Start-up screen 2................................................................................................49
Figure 4-5: Start-up screen 3................................................................................................49
Figure 4-6: Start-up screen 4................................................................................................49
Figure 4-7: Normal display of the controller LCD (default)............................................... 50
Figure 4-8: Example of dip switch setting for 3/3 phase, 50 Hz UPS...............................53
Figure 5-1: The controllers main menu.............................................................................. 55
Figure 5-2: Main menu option 1 ("System")........................................................................ 56
Figure 5-3: System DC voltages........................................................................................... 56
Figure 5-4: Output power factor 1........................................................................................ 57
Figure 5-5: Input power factor 1...........................................................................................57
Figure 5-6: Overall phase voltages/currents ...................................................................... 57
Figure 5-7. General timers and counters ............................................................................ 57
Figure 5-8. Jumper setting and general information ......................................................... 58
Figure 5-9. Internal controller voltages...............................................................................58
Figure 5-10: Main Menu option 2 (UPS Module”) .............................................................. 59
Figure 5-11: LCD Panel – Selection ..................................................................................... 60
Figure 5-12: Module phase voltages/currents.................................................................... 60
Figure 5-13: Battery voltages, I-active current...................................................................60
Figure 5-14: Controller menu #2 .......................................................................................... 61
Figure 5-15: Controller menu #3 .......................................................................................... 61
Figure 5-16: Controller menu #4 .......................................................................................... 61
Figure 5-17: Number of UPS modules................................................................................. 61
Figure 5-18: Log display ....................................................................................................... 62
Figure 6-1: 40kVA N+1 System with Internal Batteries...................................................... 66
Figure 6-2: Internal Battery Drawer – Exploded View........................................................67
Figure 6-3: Connection diagram for external battery ........................................................ 68
Figure 7-1: Location of dry contacts at rear of POWER+ controller module..................70
Figure 7-2: Dry Contacts “group A (as per Figure 7-1).................................................... 70
Figure 7-3: Dry Contacts group B (as per Figure 7-1).................................................... 71
Figure 9-1: UPS module front panel .................................................................................... 76
Figure 12-1: PC575 ................................................................................................................ 93
Figure 12-2: Extracting the EPROM..................................................................................... 93
Figure 13-1: Low level utility menu (SC2012 menu) .......................................................... 96
Figure 14-1: Key panel .......................................................................................................... 99
LIST OF TABLES
Table 2-1 Single UPS Module Specifications........................................................................ 9
Table 2-2: System controller specifications.......................................................................12
Table 3-1: UPS module pin assignment and function ....................................................... 25
Table 3-2: Jumpers on PC714 .............................................................................................. 35
Table 3-3: DIP switch setup in a 100kVA system (X = don't care).................................... 38
Table 4-1: Power Configuration DIP Switch Settings........................................................ 53
Table 5-1: Controller main menu options ............................................................................ 55
Table 5-2: Format of log messages ..................................................................................... 62
Table 5-3: Log Messages "description" field...................................................................... 63
Table 5-4: Static Switch transfer code (for LOADBP event) ............................................. 64
Table 5-5: System controller alarms..................................................................................... 65
Table 9-1: UPS Module Indicators........................................................................................ 77
Table 9-2: Troubleshooting table......................................................................................... 78
Table 10-1: General information screen.............................................................................. 83
vi
Power+ Technical Guide
Page 7
Gamatronic Electronic Industries Ltd.
Table 10-2: Main Menu functions......................................................................................... 84
Table 11-1: Setup Menu options .......................................................................................... 85
Table 11-2: Setting alarm thresholds .................................................................................. 85
Table 13-1: Calibrating battery current measurements..................................................... 98
Table 14-1: Time displays................................................................................................... 100
Table 14-2: Main dip switch statuses ................................................................................ 100
Table 14-3: Panel and slave dip switch statuses ............................................................. 101
Table 14-4: Controller external and internal power statuses..........................................101
Table 14-5: System temperature displays......................................................................... 101
Table 14-6: Battery test information.................................................................................. 103
Table 15-1: Technical specifications................................................................................. 105
Table 16-1: Ordering parts..................................................................................................106
Power+ Technical Guide
vii
Page 8
Gamatronic Electronic Industries Ltd.
WARNING: RISK OF SEVERE DAMAGE TO THE UPS!!!
THIS SYSTEM USES THE NEUTRAL LINE FOR
OPERATION
. THEREFORE, IT IS STRICTLY
FORBIDDEN TO CONNECT THIS SYSTEM TO
THE
AC POWER SOURCE WITHOUT A NEUTRAL
(NULL) CONDUCTOR!!
AILURE TO USE A NEUTRAL CONDUCTOR MAY
F
CAUSE PERMANENT DAMAGE TO THE SYSTEM
IN THE EVENT THAT SYSTEM OUTPUT CAPACITY IS INCREASED ABOVE THE ORIGINAL FACTORY CONFIGURATION, THE SYSTEM NAMEPLATE MUST BE UPDATED TO INDICATE THE NEW POWER AND CURRENT CAPACITY. This condition applies when new, non-redundant power modules are added to the system or when formerly redundant modules are designated as non-redundant.
.
viii
Power+ Technical Guide
Page 9
Gamatronic Electronic Industries Ltd.
r
t
T
r

1. SYSTEM STRUCTURE

The Power+ is a parallel redundant UPS. A block diagram is shown in Figure 1-1 below.
System Controller
RS232, TCP/IP, Cellular,
Bypass Powe
Mains Powe
UPS
10KVA
UPS
10KVA
UPS
10KVA
UPS
10KVA
Static Switch
Isolation
ransformer
(optional)
Outpu
Centralized
Figure
1-1: Block diagram
Power+ Technical Guide 1
Page 10
Gamatronic Electronic Industries Ltd.
The system comprises the following sub-assemblies.
1-10 UPS modules × 10kVA (4 in the example in Figure 1-2 below)
System Controller
Static Switch Module
Power Distribution Block
Figure 1-2: Sub-assemblies
Figure 1-3: 10kVA configuration
2 Power+ Technical Guide
Page 11
Gamatronic Electronic Industries Ltd.
Figure 1-4: 50kVA configuration
Figure 1-5: 100kVA configuration
Power+ Technical Guide 3
Page 12
Gamatronic Electronic Industries Ltd.

2. FUNCTIONAL OVERVIEW

2.1 UPS BASIC MODULE (10KVA / 8KW)

The UPS Basic Module is the core of the system, which comprises 1 to 10 identical parallel modules depending on capacity requirements.
A general module view is shown in type block diagram is illustrated in
Figure 2-1. The module classic on-line double-conversion
Figure 2-2.
This design has proved to be very stable. No transfer time is required for the UPS to switch from normal to backup mode; the load is supplied constantly by stable and clean power. A Power Factor Correction (PFC)
1
is responsible for the low Total Harmonic Distortion (THD) and
unity Power Factor (PF) at the input.
The input voltage(s) is converted to a stable ±425V at the DC link.
This stage can maintain current sharing between the three input phases as well as among other parallel units, because of the current sharing signal that it produces.
Figure 2-1: Single UPS Module- Front/Rear View
1
PFC is a feature included that reduces the amount of generated reactive power. Reactive power operates at right angles to true power and energizes the magnetic field. Reactive power has no real value for an electronic device, but electric companies charge for both true and reactive power resulting in unnecessary expense. In power factor correction, the power factor (represented as "k") is the ratio of true power (kwatts) divided by reactive power (kvar). The power factor value is between 0.0 and 1.00. If the power factor is above
0.8, the device is using power efficiently. A standard power supply has a power factor of 0.70–0.75, and a power supply with PFC has a power factor of 0.95–0.99.
4 Power+ Technical Guide
Page 13
Gamatronic Electronic Industries Ltd.
Figure 2-2: Block diagram of a single UPS Module
Power+ Technical Guide 5
Page 14
Gamatronic Electronic Industries Ltd.
The PFC power section block diagram is shown in Figure 2-3. Input currents of the PFC
(without filters) is shown in
Figure 2-4; the control scheme is illustrated in Figure 2-5.
+
Ir
R S
Control
Is
Control
It
T
Control
-+
-+
-+
N
Figure 2-3: Power section of the PFC in a single UPS module
+
Ipeak
Ir Is
(CCM)
t
-Ipeak
Figure 2-4: Input currents of the PFC (without filters)
As shown in Figure 2-3, the PFC section operates in Continuous Current Mode (CCM)
conduction, which has many advantages. Input currents are shaped in such a way that they follow the input voltages with precision. This makes the system appear to be nothing more than a resistive load with respect to the line voltage. In other words, the system corrects the input current waveform of the connected load, and acts as an active power filter. The PFC section also draws symmetrical currents from each phase, and maintains good current sharing among identical UPS modules in parallel.
Each phase input is sensed for voltage and current, required to force the input current drawn from the phase input to follow its voltage and emulate a resistor. Two feedback loops are
It
6 Power+ Technical Guide
Page 15
Gamatronic Electronic Industries Ltd.
required for the proper operation, an inner current loop for maintaining a correct wave shape and an outer voltage loop to ensure a correct DC output level.
The voltage sample (k*Vin) is multiplied by the error voltage from a common voltage feedback amplifier (Integrator). The result is than compared to the actual sampled phase current which forces the current amplifier current to follow the phase input voltage. The output of the integrator is connected to a current sharing bus causing all other modules to be connected to this bus via the same resistor. This ensures that all the multipliers of each UPS module receive the same input and all that modules are equally loaded.
PH1
NEUTRAL
PH2
NEUTRAL
K1*V1
K1*V2
MULT
MULT
Current Amplifier
+
-
Current Amplifier
+
-
Comparator
+
-
Triangle
Comparator
+
-
Triangle
PWM
PWM
POWER BLOCK
POWER BLOCK
Vout (DC)
Current Amplifier
+
-
Integarator
Comparator
+
-
Triangle
-
+
PWM
Vref
POWER BLOCK
K2*Vout
PH3
NEUTRAL
MULT
K1*V3
Verror
DC share bus
Figure 2-5: PFC control scheme
Power+ Technical Guide 7
Page 16
Gamatronic Electronic Industries Ltd.
The second stage of the UPS module is the DC/AC inverter.
This stage is fed by the DC symmetrical voltage produced by the PFC stage which then it inverts to create clean sinusoidal output(s).
POWER+ employs “3-L” (3-level) topology which achieves very high efficiency (over 96%) which in turn enhances the overall AC-AC efficiency of the entire system.
As shown in
Figure 2-6 the inverter voltage is produced using three levels of DC voltage (unlike
standard two-level system).
The POWER+ inverter uses Insulated Gate Bipolar Transistors (IGBT) as efficient high frequency switches.
Apart from the AC/DC PFC and DC/AC inverter each UPS module also contains a digital controller, responsible for all the control mechanism and all communications with other modules of the system.
Each UPS module also provides the system controller with a report related to its condition and operation status. All the data available from all modules is displayed on an LCD display.
The UPS module is cooled using forced convection. The fan varies with the load level, making for improved reliability, reduced noise, and less dust is introduced.
+
L L L
Vr Vs Vt
C
-+
-+-+
C
C
N
+
Control
Figure 2-6: DC/AC inverter principal topology
8 Power+ Technical Guide
Page 17
Gamatronic Electronic Industries Ltd.

2.1.1 SINGLE UPS MODULE SPECIFICATIONS

2-1 Single UPS Module Specifications
Table
TECHNICAL DATA – UPS MODULE
Output Rated Power 10 kVA / 8 kW Topology Online Battery, Double Conversion Construction Modular parallel hot-plugged modules Input Voltage (V) 3 × 400+N (3 × 230 V) Input Voltage range (%) -27 and +20 Input Current (A) 15 A Input Frequency (Hz) 47–63 Hz Frequency tracking range (Hz) ±1, ±2, ±3 (selectable) Output slew rate 1 Hz/sec Power walk-in (sec) > 60 Input Power Factor 0.99 Input THDI (%) 5 Output Voltage (V) 3 × 400+N (3 × 230V) Output Static Regulation (%) ±1 Output Regulation for unbalanced load (%) ±1 for 100% unbalanced load Dynamic response to 100% load step (%) 2
110 % for 10 minutes
Overload
Output Waveform Sinusoidal Output THD (%) Less than 2 for linear load Load CF (max) 6:1 Fuse clearance capability Input, Output, DC link AC-AC efficiency (nominal) Up to 96 at full load Maximum power dissipation (Po=8KW) 421 W (1437 BTU)
Ambient temperature (ºC)
Relative humidity (%) 95 max non-condensing Altitude (m) 1500 w/o de-rating DC-Link Voltage ±340 V to ±425 V Cooling system Forced air: multi-fan with speed control Dimensions: W x H x D 19" x 2U x 455 mm (Excluding shelf) Weight 9.5 Kg
125 % for 60 seconds 1000 % for 1 cycle
-10 to +40 (operating)
-20 to +60 (storage)
Power+ Technical Guide 9
Page 18
Gamatronic Electronic Industries Ltd.

2.2 UPS SYSTEM CONTROLLER

The POWER+ system controller is designed primarily for monitoring, diagnostics and communications.
Some other useful features include temperature compensation of the battery voltage.
The POWER+ can work without the system controller but with reduced functionality.
Figure 2-8 shows the system controller block diagram. The core of the controller is a powerful
embedded micro-controller, surrounded by many peripherals (analog, digital, communication).
The controller front panel is shown in
Figure 2-7: System controller - Front panel
Figure 2-7.
10 Power+ Technical Guide
Page 19
Gamatronic Electronic Industries Ltd.
Figure 2-8: System controller - Block diagram
Power+ Technical Guide 11
Page 20
Gamatronic Electronic Industries Ltd.

2.2.1 SYSTEM CONTROLLER SPECIFICATIONS

Table 2-2: System controller specifications
TECHNICAL DATA – SYSTEM CONTROLLER
Micro Controller core 16 bit Display 4 x 40 characters LCD with backlight Other indicators 8 LED’s, buzzer Analog input channels 4 Digital input channels 8 Real Time Clock (RTC) Yes, with backup Power meter kVA, kW, PF Voltage-free outputs (dry contacts) 6 RS232 user port Yes, isolated Optional communication TCP/IP, GPRS/SMS Wireless
communication (Optional) Communications with system modules Serial, isolated Events log 255 events System operation without controller Unchanged On-screen parameters Load bar-graph
3-phase voltages
3-phase currents
Battery voltage
Status of each UPS module
Static-switch parameters and status
Battery sensor temperature Alarms AC abnormal
DC abnormal
UPS module(s) failure
Load on bypass
Battery test failed
Over/under temperature
Overload RTC operation without power 2 weeks Power requirements 12V±10%, 1A via 2.1mm phono jack

2.3 STATIC SWITCH (ST/SW) MODULE

The static switch module is used for overriding the input to output in case of a system failure or heavy load start or if specifically requested by the user.
The module receives two AC inputs and supplies only one.
Generally the ST/SW connects the output of the paralleled UPS modules to the main output of the system. However, if the modules fail to provide an adequate voltage for a determined time, i.e. detection time, the ST/SW module instantly switches to the alternative power source, that is the AC input, as illustrated in purpose using a combination of fast semiconductors and an electromechanical relay. The module monitors all the inputs in real time to determine the method of operation. The ST/SW module’s front panel is shown in
12 Power+ Technical Guide
Figure 2-10. The unit employs an efficient AC switch for this
Figure 2-9.
Page 21
Gamatronic Electronic Industries Ltd.
Figure 2-9: ST/SW front panel view
Figure 2-10: ST/SW block diagram
Power+ Technical Guide 13
Page 22
Gamatronic Electronic Industries Ltd.
INV
INV
INV
B
Outputs
Monitoring & Control
BP
BP
BP
Figure 2-11: 3-Phase ST/SW block diagram
14 Power+ Technical Guide
Page 23
Gamatronic Electronic Industries Ltd.

3. SYSTEM INTERCONNECTION

The POWER+ system comprises UPS Modules, a System Controller, Static Switch and distribution elements such as AC, DC and fuses. These components are assembled as shown in
Figure 3-1.
A major advantage of the POWER+ is its upgradability simply by adding UPS modules and shelves as required.
The system controller occupies the same space as the UPS module and although not critical, is most often mounted at the top shelf for convenience. This permits easier viewing of the display. The static switch module however, is always mounted at the bottom of the system (see
3-1).
Figure
Figure 3-1: Power+ system - Modular structure
Power+ Technical Guide 15
Page 24
Gamatronic Electronic Industries Ltd.

3.1 INTERNAL SYSTEM WIRING

The cabling and wiring of a 30kVA Power+ system are illustrated in schematics in Figure 3-2
(single-phase output) and
Figure 3-3 (3-phase output) below.
Figure 3-2: Schematic of a 3:1 Phase 30kVA POWER+ System
Note: For use with single-phase input, all 3 phases of each AC input are connected together internally inside the cabinet. REFER TO SINGLE-PHASE OUTPUT INSTRUCTIONS.
16 Power+ Technical Guide
Page 25
Gamatronic Electronic Industries Ltd.
Figure 3-3: Schematic of a 3-Phase 30kVA POWER+ System
Cables for the POWER+ are all connected at the rear of the system.
Cables are routed between the UPS modules system controller and static switch – down to the AC and DC distribution sections that are mounted at the bottom of the rack.
Figure 3-1 shows
the rear view of the POWER+ system. (Note that 3 UPS modules are in use in this illustration). UPS modules are numbered from bottom to top; i.e. the lowest UPS module is "UPS #1"; the UPS above it is "UPS #2" and so on.
Power+ Technical Guide 17
Page 26
Gamatronic Electronic Industries Ltd.
Figure 3-4: POWER+ System - Rear View
18 Power+ Technical Guide
Page 27
Gamatronic Electronic Industries Ltd.
UPS modules are inter-connected by a flat cable which is used for the transmission of digital and analog data. This data is essential for maintaining synchronization and current sharing between modules. This flat cable is connected to a small PCB in the UPS shelf and is connected to the control DIN48 connector described on page
24.
NOTE:
PROPER CONNECTION OF THE FLAT CABLE
IS OF CRITICAL IMPORTANCE.
INCORRECT OR WEAK CONNECTION
WILL PREVENT THE SYSTEM FROM OPERATING.
Each shelf has a digital address that is preset at the factory and determined by the DIP switch mounted on the small control board as shown in
Figure 3-5.
Figure 3-5: Control PCB and flat cable
Power+ Technical Guide 19
Page 28
Gamatronic Electronic Industries Ltd.

3.1.1 THE POWER+ ALWAYS REQUIRES A NEUTRAL LINE

During both installation and operation of the Power +, a neutral line must always be connected to the UPS. This neutral line shall be connected during the entire period that the UPS is working, and shall not be disconnected at any time!
Caution: If at any time the neutral line becomes disconnected, there will be no input or output
reference voltage, because the input neutral line and the output neutral line are physically linked together. That may result in system defining its own reference voltage, which will be set
by the load distribution between the three phases. This can result in serious damage to the
UPS.
A 4-pole switch might disconnect the neutral line
WARNING! If you have a mains-to-generator four-pole switching system you are in danger of having the neutral line disconnected when the four-pole switch is operated. This can result in
the problems described above.
To avoid these problems, we strongly recommend that, if you use a four-pole mains-to­generator switching system, you install an isolation transformer that will constantly provide the UPS with a neutral line.
Figure 3-6 on page 21 illustrates the wrong way to connect the UPS with a grounded-neutral
generator.
Figure 3-7 on page 22 illustrates an acceptable connection solution if you already have a
grounded-neutral generator.
Figure 3-8 on page 23 shows the preferred generator (neutralized, not grounded) and the
preferred connection (three-pole).
20 Power+ Technical Guide
Page 29
Gamatronic Electronic Industries Ltd.
Figure
Power+ Technical Guide 21
3-6: Wrong way to connect UPS with grounded-neutral-generator
Page 30
Gamatronic Electronic Industries Ltd.
Figure
22 Power+ Technical Guide
3-7: Acceptable connection for grounded generator and 4-pole switch
Page 31
Gamatronic Electronic Industries Ltd.
Figure 3
Figure
Power+ Technical Guide 23
3-8: Preferred generator (neutralized) and connection (3-pole)
Page 32
Gamatronic Electronic Industries Ltd.

3.1.2 UPS MODULE – CONNECTORS DESCRIPTION

The UPS module includes three connectors (see Figure 3-9) on the rear panel. Two 15-pin DIN
connectors (“DIN15”) are for power connections and one 48-pin (“DIN48”) DIN connector for signaling and control.
WARNING
ALL THE CONNECTOR PINS CARRY HAZARDOUS VOLTAGES
ALWAYS AVOID ACCESS TO THESE PINS!
Input Connector
(15-Pin DIN)
Output Connector
(15-pin DIN)
Figure 3-9: UPS module – Rear view
The connectors pin assignments are illustrated in below.
30
32
26 22
28
18
14
24
"DIN 15" CONNECTOR
20
16
12
10
Control Connector
(48-Pin DIN)
Figure 3-10 and described in Table 3-1
bac
1 2 3 4 5
6
84
6 7 8
9 10 11 12 13 14 15 16
b 8
"DIN 48" CONNECTOR
Figure 3-10: UPS module connectors - Pin assignments
24 Power+ Technical Guide
Page 33
Gamatronic Electronic Industries Ltd.

3.1.3 UPS MODULE PIN ASSIGNMENT TABLE

WARNING
THE DATA PROVIDED BELOW IS FOR INFORMATION ONLY.
DO NOT ATTEMPT TO MAKE ANY CONNECTIONS.
Table 3-1: UPS module pin assignment and function
Input Connector
4 = (-425V) 6 = (-425V) 8 = (-425V) 10 = Neutral 12 = Neutral
14 = T phase 16 = T phase 18 = S phase 20 = S phase 22 = R phase
24 = R phase 26 = Neutral 28 = (+425V) 30 = (+425V) 32 = (+425V)
Output Connector
4 = OUT3 (T) 6 = OUT3 (T) 8 = OUT2 (S) 10 = OUT2 (S) 12 = OUT1 (R)
14 = OUT1 (R) 16 = N.C. 18 = N.C. 20 = N.C. 22 = Neutral
24 = Neutral 26 = Neutral 28 = N.C. 30 = N.C. 32 = N.C.
Control Connector
"a" Column "b" Column "c" Column
1 = System Controller Com 1 = Controller TX 1 = Controller RX
2 = Dry2_opto_E 2 = N.C. 2 = N.C.
3 = Dry2_opto_C 3 = N.C. 3 = N.C.
4 = N.C. 4 = N.C. 4 = N.C.
5 = N.C. 5 = N.C. 5 = N.C.
6 = DRY 0 6 = UPS OFF 6 = Vout_Sum
7 = DRY 1 7 = CAN BUS 7 = WANT
8 = +12V BUS 8 = Stand Alone 8 = Vcc (+5V)
9 = Force B/P Inv 9 = AC on INV 1 9 = Address Com.
10 = Common BUS 10 = Common BUS 10 = Common BUS
11 = Dry 2 11 = Device Address (#3) 11 = PLL DATA BUS
12 = Reference Frequency 12 = Device Address (#2) 12 = PLL SYNC BUS
13 = SPI Select 13 = Device Address (#1) 13 = Sharing BUS (S)
14 = MIS 0 14 = Device Address (#0) 14 = Sharing BUS (R)
15 = MIS 1 15 = +12V BUS 15 = Sharing BUS (T)
16 = SPI_SCK 16 = Address Common 16 = +12V BUS
Power+ Technical Guide 25
Page 34
Gamatronic Electronic Industries Ltd.
Legend
N.C. = Not Connected (Unused)
PLL = Phase Locked Loop (Synchronization system)
Sharing = Current Sharing circuit (Among modules)
Device Address = Identifies the location of a UPS module within the system
WANT / CAN = Signals related to the parallel mechanism

3.2 DC DISTRIBUTION PANEL CABLING

WARNING
BATTERY CABINETS MAY BE CONNECTED AND
MAINTAINED BY A QUALIFIED TECHNICIAN ONLY!!!
NOTE:
The Neutral line is common to the input and
output as well as to the battery "0V" point!
The DC distribution panel is located at the bottom of the system on the rear, below the first UPS module (”UPS #1”).
This panel receives the DC wires from the system’s UPS modules and from the controller, as well as from internal or external battery cabinets.
The DC voltages are very high and dangerous (± 425Vdc).
External battery connections are performed at the right side of this panel.
The DC distribution panel on your system will have one of two possible layouts, depending on whether your system has a maximum capacity of 50KV or 100KV. maximum capacity, as shown in
Figure 3-11.
The Anderson connector plugs on the DC distribution panel are color coded: RED=positive, BLACK=negative, BLUE=neutral.
Refer also to
26 Power+ Technical Guide
Figure 6-3 on page 68 for battery connection details.
Page 35
Gamatronic Electronic Industries Ltd.
Figure 3-11: DC distribution panel (50KVA model)
Figure
3-12: DC distribution. panel (100kVA model)
Power+ Technical Guide 27
Page 36
Gamatronic Electronic Industries Ltd.

3.2.1 DC FUSES

All DC fuses are located on the opposite side (the front side) of the DC distribution panel. There are two fuses for each power module and for the controller – one for the positive line and one for the negative line.
Figure 3-13 and Figure 3-14 show the assignments.
Figure 3-13: DC fuses on front side of DC dist. panel (50KVA model)
Figure 3-14: DC fuses on front of DC dist. panel (100KVA model)
28 Power+ Technical Guide
Page 37
Gamatronic Electronic Industries Ltd.

3.3 AC INPUT FUSES

The input of each UPS module is protected by a 15A fuse for each phase, so that each module, including the controller, has 3 fuses (for R, S, T phases). 10 modules plus the controller would require 33 fuses, as illustrated in i.e. the 3 fuses on the far right protect UPS #1.
Figure 3-15. Fuse receptacles are numbered from right to left,
Figure 3-15: UPS modules - AC input fuses (100KVA model)
WARNING
ALWAYS REPLACE FUSES WITH THE SAME TYPE AND RATINGS !!!
Figure 3-16: AC input fuse assignments (50KVA model)
Power+ Technical Guide 29
Page 38
Gamatronic Electronic Industries Ltd.

3.4 AC DISTRIBUTION COMPARTMENT

The AC distribution compartment (Figure 3-17) distributes AC voltages to and from the UPS
modules and is located on the rear of the UPS, below the DC distribution panel. Connections are as shown below.
The AC input to the modules are protected by the AC fuses as described above.
Figure 3-17: AC distribution
Figure
Figure
3-18: AC distribution panel (100KVA model)
3-19: AC distribution panel (50KVA model)
30 Power+ Technical Guide
Page 39
Gamatronic Electronic Industries Ltd.

3.5 AC INPUT/OUTPUT MAIN TERMINALS

The main terminals section is critical for system installation. The terminals are used to connect the AC inputs and AC output to the mains electricity cabinet. The terminals section is illustrated in
Figure 3-20. The installation procedure is detailed in Section 4.
NOTE:
The Neutral line is common to the input and
output as well as to the battery "0V" point!
Figure 3-20: Input & output main terminals
Power+ Technical Guide 31
Page 40
Gamatronic Electronic Industries Ltd.

3.6 STATIC SWITCH CONNECTIONS

The static switch’s internal connections include two AC inputs and one AC output. As shown in separate terminal is dedicated for the Neutral line (which does not carry current) and is used for measurements.
This module communicates with the rest of the system via the communication port located at the right side of the unit.
Additional terminals are provided as shown for Emergency Power-Off (EPO) and for Load On Bypass indication.
Figure 3-21, three groups of terminals are located accordingly on top of the unit. A
Figure 3-21: Static switch terminals – Rear view
32 Power+ Technical Guide
Page 41
Gamatronic Electronic Industries Ltd.

3.7 SYSTEM CONTROLLER CONNECTIONS

The controller is typically located in the top housing shelf of the UPS for easier access.
Although the UPS modules reads their digital address number from the Control PCB (discussed
later) the controller does not
Connections to the System Controller are from the rear, as shown in Figure 3-22.
!
NOTE:
Several Controller options are available
(e.g TCP/IP, cellular and more).
Refer to your dealer for further details.
Figure 3-22: System controller outside the shelf - Rear view

3.7.1 PC714 – THE CONTROLLER CARD

The PC714 card contains the logic chips that perform the UPS controller functions. PC714 also contains the LCD display screen, and several jumpers, the usage of which are explained below.
Figure 3-23 shows the front side of the PC714 card, Figure 3-24 shows the rear side. Figure 3-25 shows the location of the jumpers on the rear of the card, and
function of the jumpers. (See also section status on the controller screen.)
To reach the PC714 card it is necessary to remove card PC575.
The controller's flash memory resides on PC714. Instructions for replacing the flash memory are in section
Power+ Technical Guide 33
12.4 on page 93.
11.4.4 on page 89 for how to display the jumper
Table 3-2 explains the
Page 42
Gamatronic Electronic Industries Ltd.
3-23: Front side of PC714 card
Figure
Figure
3-24: Rear of PC714 – white rectangle indicates jumper area
Figure
34 Power+ Technical Guide
3-25: The jumpers on PC714
Page 43
Gamatronic Electronic Industries Ltd.
3-2: Jumpers on PC714
Table
JUMPER DESCRIPTION
This jumper should be in place only the first time the UPS is started up, before the UPS has
JP1
JP2
JP3
JP4,
JP5
been configured. When this jumper is in place, the UPS used fixed internal "factory default" configuration values. Once you have configured the UPS this jumper should be removed.
When in place, the UPS operational parameters can be updated. When not in place, the UPS parameters cannot be changed.
This jumper affects the entry of the battery capacity parameter in the "Setups > Battery" option. When the jumper is in place, a capacity from 10 to 890 amp/hrs can be specified. When the jumper is removed, a capacity from 10 to 89 amp/hrs can be specified.
These two jumpers should normally always be in place. When in place they enable the UPS to communicate with the network board PC575, which in turn interfaces with the "outside world" (the network) via the RS232 interface. JP4 enables signal transmission, JP5 enables signal reception.
JP6
JP9
When this jumper is removed, the remote control panel can be used.
When this jumper is in place, the UPS expects 220/230 Vac input. When this jumper is removed the UPS expects 110/120 Vac input. (Note that the jumper status screen [main menu, down arrow, down arrow] displays only 110 or 220 to indicate the status of JP9, but the acceptable voltages are as stated above, insofar as jumper JP9 is concerned.)
Power+ Technical Guide 35
Page 44
Gamatronic Electronic Industries Ltd.

3.8 SETTING THE SHELF ADDRESS

Each UPS module shelf – including the controller module shelf – has a digital address that can be accessed by the module once it has been initialized. The module addresses are used to identify each module during the normal operation and monitoring of the system.
No two shelves can have the same address. The address is related to the physical location of a
specific shelf, and is preset at the factory by the “Module Location” DIP switch mounted on
the control PCB. (See address of the newly added shelf must be set correctly.
The control PCB contains an additional DIP switch – the “Master/Slave” DIP switch – that is
used to indicate which of the UPS modules is the “Master”, and which UPS modules are the “Slaves”. Only one UPS module is designated as “Master”; all of the other UPS modules are “Slaves”.
Figure 3-26). When adding a new module to an existing system, the
Figure 3-26: The PC917 Control PCB on a shelf – general view
36 Power+ Technical Guide
Page 45
Gamatronic Electronic Industries Ltd.
Figure 3-27: DIP switches on PC719 card– close-up
Figure 3-27 shows the DIP switches on the PC719 card, which is located on the back of each
shelf housing a UPS or the controller module.
Master/Slave DIP Switch Settings
The two DIP switches on the left determine which UPS will be the “master” UPS. Best practice is to make UPS#1 (the first UPS) the master, and let the others be slaves.
Figure 3-28: Recommended master/slave DIP switch settings
Power+ Technical Guide 37
Page 46
Gamatronic Electronic Industries Ltd.
“Module Location” DIP switch Settings
In the example shown the “FIRST UPS” DIP switch is set as follows:
1= "on", 2= "on", 3= "on", 4="on”, indicating UPS #1. See
Table 3-3: DIP switch setup in a 100kVA system (X = don't care).
Table 3-3 below and FIGURE 3-29.
Figure 3-29: DIP switch settings
Lowest Module Select (LMS) jumper: The first module (UPS #1) must be assigned as such
by a jumper on the MOLEX-2 connector. Other versions of the Control PCB may have a 2 level DIP switch instead of this connector, in which case both switches must be ON.
38 Power+ Technical Guide
Page 47
Gamatronic Electronic Industries Ltd.

3.9 F.A.Q. (FREQUENTLY ASKED QUESTIONS)

3.9.1 BATTERIES

3.9.1.1 Q: WHAT IS THE DC VOLTAGE OF THE SYSTEM? HOW MANY BATTERIES ARE
NEEDED
A: The nominal DC voltage of the system is ±424v to ±432. Power Plus units operate with positive and negative voltage independently. There are 64 batteries in series in each battery bank, with a middle connection point which has additional wire connected, so there are two groups – positive and negative, 32 batteries in each. The DC voltage is measured between the center point and one of the poles. The middle point is interconnected with the input neutral. If the DC voltage is measured between the positive side and the negative side, it will be in range of 848v to 864v DC.
3.9.1.2 Q: WHY SHOULD THE BATTERY CAPACITY BE ENTERED IN THE SYSTEM
CONTROLLER
A. The battery capacity has to be entered for the calculation of the battery test duration. Power Plus units offer smart battery handling, and one of the features is a smart battery test. It uses the relevant information to provide the best information about the current battery status. This information includes global battery Ah rating, current load level, battery current (if available) and some calculations.
?
?
3.9.1.3 Q: WHAT WILL HAPPEN IF THE BATTERY CAPACITY WAS NOT SETUP
CORRECTLY
A. Accurate values of Ah battery capacity should be entered; otherwise the reliability of the smart battery test will be lower.
?
3.9.1.4 Q: WHY DOES MY BATTERY TEST LAST FOR MORE THEN 1 MINUTE?
A. Battery test can last for a number of minutes, it is not a problem. For a unit with large batteries and low load, checking the battery condition in the best way will take more then one minute. Power Plus units have smart battery test feature implemented, which discharges the batteries by 5% of the capacity during the test to check them in the best way.
3.9.1.5 Q: WHAT IS THE MAXIMUM CHARGING CURRENT FOR THE BATTERIES?
A. Under full load each module can provide 2 A to charge the batteries. In case that a module is not loaded, the entire rectifier current (12 A) can be passed to the batteries. Another example, if one module is loaded at 50% on the output it can provide around 7 A to the batteries. This means that in Gamatronic systems with on-line battery topology all current that doesnt go to inverter is available for battery charging.
3.9.1.6 Q: SHOULD THE BATTERY CURRENT LIMIT FEATURE BE ACTIVATED?
A. The battery current limit is an optional feature. Before enabling it please make sure that you have this option in the system. In order to check it, please see the rear side of the controller. There are three battery current sensors connections there, in a green plug. If nothing is connected there, then this option is not available in your system and must be disabled.
Power+ Technical Guide 39
Page 48
Gamatronic Electronic Industries Ltd.
3.9.1.7 Q: WHY SHOULD I USE THE BATTERY CURRENT LIMIT? IF I ACTIVATE IT, WHAT
PARAMETERS DO
A. Correct parameters for battery current limit are specified by a battery manufacturer, in a datasheet. It improves the battery lifetime and protects from overcharging. Caution: Incorrect setting might cause unexpected system operation.
I USE?
3.9.1.8 Q: SHOULD THE BATTERY TEMPERATURE COMPENSATION BE ACTIVATED?
A. The battery temperature compensation is an optional feature, which consists of a temperature sensor with wires for specified length for external or going into the unit for internal batteries. It connects to the rear side of the controller, to a green plug with its own specific connection. Before enabling this feature, make sure you have it in your system.
3.9.1.9 Q: WHY SHOULD I USE THE BATTERY TEMPERATURE COMPENSATION? WHAT IS
THE CORRECT VALUE
A. The battery temperature compensation should be corrected according to the battery manufacturer’s recommendations; it protects the batteries form overcharging in a high temperature environment.
?
3.9.1.10 Q: WHEN THE AH VALUE FOR THE BATTERIES IS ENTERED, AND THERE ARE TWO
OR THREE BATTERY CABINETS SELECTED VALUES OR DIVIDE THEM BETWEEN THE CABINETS
A. If the number of battery cabinets is set to more than one, then you will have to select the battery Ah rating for each battery cabinet independently, as it can be different. Eventually the unit will add these values and obtain the global Ah value.
, WILL THE UNIT ADD THE ENTERED
?

3.9.2 GENERAL

3.9.2.1 Q: DOES POWER PLUS UNIT HAVE EQUALIZING (BOOST CHARGE) MODE?
A. Gamatronic UPS systems do not use equalizing (boost) battery charging. If you have equalizing menu entry in your controller menu, please arrange software version upgrade for your controller.
3.9.2.2 Q: WHAT WILL HAPPEN TO THE UNIT IF THE SYSTEM CONTROLLER IS REMOVED?
A. When the controller is removed, the system will continue with normal operation, including battery charging and backup operation upon power failure. It will also start normally when mains power is turned on.
3.9.2.3 Q: CAN I USE THE SYSTEM WITHOUT SYSTEM CONTROLLER MODULE AT ALL?
A. Yes, the UPS system will provide the basic functionality; however, many important features will not be available. Major features include battery test, measurements, control etc. Without a system controller the system will function as a rectifier, batteries and an inverter (with ST/SW) only with no additional features. This kind of operation is not recommended.
3.9.2.4 Q: HOW CAN THIS SYSTEM WORK AS A SINGLE AND TRIPLE PHASE (SELECTABLE) ON THE INPUT?
40 Power+ Technical Guide
Page 49
Gamatronic Electronic Industries Ltd.
A. This unit features advanced rectifier technology which allows you to connect triple phase voltage to the inputs or just a single phase linked together on R (L1), S (L2) and T (L3) inputs. The unit will accept both connection types on the input, no additional settings are needed.
3.9.2.5 Q: HOW CAN THIS SYSTEM WORK AS A SINGLE AND TRIPLE PHASE (SELECTABLE) ON THE OUTPUT?
A. The special inverter function allows single phase output operation. To switch the system to single phase operation, each UPS module should be removed while the system is off and its dip switch number 3 (they are located in a small window on the left side of each module) should be moved to the OFF position (ON for 3 phase output operation). Then the output phases R (L1), S (L2) and T (L3) should be linked altogether to a single phase wire output (used with the output neutral), as the phase angle will be switched to 0
0
and each module will have its inverters operating in parallel.
3.9.2.6 Q: HOW CAN THIS SYSTEM BE SWITCHED TO 60HZ OUTPUT?
A. The unit will auto-detect input frequency and have same frequency on the output. To switch the system to 60Hz output operation manually, each UPS module should be removed while the system is off and its dip switch number 2 (they are located in a small window on the left side of each module) should be moved to the on position (off for 50 Hz or auto-detect output operation).
3.9.2.7 Q: HOW WILL THE ST/SW MODULE REACT TO A CHANGE FROM TRIPLE TO
SINGLE PHASE AND VICE VERSA ON THE OUTPUT
A. The bypass input of the unit should fit the output voltage. If the output voltage is triple phase, then the bypass input should be triple phase as well. If the output is single phase, and the output phases are linked altogether, then the same thing should be done with the bypass input of the unit – one phase connected and the R (L1), S (L2) and the T (L3) inputs of the bypass linked altogether. The ST/SW module will detect it and function as a triple or single phase unit automatically.
?
3.9.2.8 Q: DOES THIS UNIT HAVE DRY CONTACT OUTPUTS, AND FOR WHAT ALARMS?
A. These systems have 6 dry contacts on the controllers rear panel. Two of them are in a DB9 connector (pins 3, 4 alarm no. 1 and pins 5, 4 alarm no. 2). The other four are located in a marked wide green connector with screw wire attachments. There are N.O., N.C. and the COMMON connections for each dry contact. All dry contacts are programmable through the controller, selectable from the global list of 32 alarms. Any number of alarms can be set for any dry contact. All the contacts are rated at 24V 1A.
3.9.2.9 Q: DOES THIS UNIT HAVE INPUT DRY CONTACTS?
A. There are 4 input normally closed dry contacts, located in specific green plug on the rear side of the system controller. As a standard they are all linked to the common on the plug, and provide no alarms.

3.9.3 MENUS

3.9.3.1 Q: WHAT IS THE ALARM HYSTERESIS SETTING?
A. The voltage alarm hysteresis is the value of voltage difference for finalizing the alarm. For example, if the alarm value is 245v and the hysteresis is 5v, then when the voltage grows above 245v and the alarm will activate, it will end only when the voltage drops below 240v.
3.9.3.2 Q: WHAT IS THE “INTEGRAT.” MENU ENTRY?
A. The “Integrat.”, which is the integration factor, is a value for confirming the internal RS232 communications. This option should not be changed usually and is preset for optimal performance.
Power+ Technical Guide 41
Page 50
Gamatronic Electronic Industries Ltd.
3.9.3.3 Q: WHY SHOULD I USE THE INDIVIDUAL UPS MODULE TURN ON/OFF FEATURE?
A. The individual UPS turn on/off feature is disabled.
3.9.3.4 Q: WHY ARE THERE TWO SETTINGS FOR A NUMBER OF UPS MODULES IN THE
SYSTEM
A. A total number of modules represent the units with which the controller will communicate and monitor. The redundancy number of modules shows how many units are functioning as a backup, without being calculated in a global load level of the system. For example, if you have a 30KVA unit with a setting for 1 redundant module, when the output load will reach 20KVA the unit will show a full load condition. It will still not switch to bypass, but will alarm you with overload if the output load will rise above 20KVA. For the user this means that the unit does not have the redundancy anymore under this load. If the redundant modules value is set to 0, then a 40KVA unit will function as a standard unit of 40KVA output load maximum. It you set this parameter to 3, the same unit will have a load bar-graph of a 10k system and will alert the customer with overload when there is more then 10k of load on the output.
?
3.9.3.5 Q: WHAT IS THE DC-I OFFSET REMOVAL AND THE DC-I CALIBRATION MENU
ENTRIES
A. The DC-I offset removal and the DC-I calibration should be performed only if the battery current measurement is not correct. It is being used on new controllers only upon current sensors connection. You might have do use these features if adding current sensors on a later stage. To perform it the unit should work without a load and with batteries disconnected. Then the offset removal should be preformed (only if the measurement current is not zero) and then the unit should be connected to some load and batteries and operated in input power failure mode. Then the actual current is being measured and corrected live in the controller using the calibration menu entry.
?

3.9.4 INSTALLATION

3.9.4.1 Q: DOES THE UNIT HAVE EPO (EMERGENCY POWER OFF) CONNECTION?
A. Yes. The connection is on the ST/SW module. Unscrew two mounting screws on the front panel of the ST/SW module and slightly pull it out. The EPO connection is on its top.
3.9.4.2 Q: WHEN THE EPO IS DEACTIVATED, THE UNIT STILL WONT RETURN TO
NORMAL OPERATION
A. When the EPO function was activated, the unit stopped functioning and provided voltage to battery breaker trip coil (option of the battery cabinet) to switch the batteries off as well. To restore normal operation of the UPS system, it should be completely restarted.
3.9.4.3 Q: UPON THE INSTALLATION, THE UNIT WONT SWITCH TO INVERTER AND THE “SYNC LED ON ST/SW MODULE IS IN RED. EVERYTHING ELSE IS OK. WHY IS
THAT
?
A. Usually this means that the phase sequence on the ST/SW input (the bypass) is not correct. These units get synchronized on the bypass and therefore check the phase sequence there. Swapping phase S (L2) and T (L3) on the bypass input should correct the situation.
3.9.4.4 Q: WHEN I PRESS THE INV/BYP BUTTON ON THE ST/SW MODULE, IT DOESNT
SWITCH TO
A. The Inv/Byp button is a press and hold button for protection. It should be held for a number of seconds until the alarm LED lights in green, and then released. There is the same button on the controller; there it should be pressed twice to initiate a manual transfer.
/FROM BYPASS. HOW DO I DO THE MANUAL TRANSFER?
. WHY IS THAT?
42 Power+ Technical Guide
Page 51
Gamatronic Electronic Industries Ltd.
3.9.4.5 Q: DOES THIS UNIT HAVE DUAL INPUTS?
A. Power Plus systems, as any other standard Gamatronic systems above 10Kva, use dual inputs, meaning independent input for the rectifier and a bypass input for the ST/SW.
3.9.4.6 Q: WHAT SHOULD BE THE CONNECTION WIRE SIZE IN MM2?
A. The wires should fit he current they stand for. Each P+ module consumes 15A of current maximum on the input of each phase. This current has to be multiplied by the total number of modules. Each country can have different accepted standards for wire size assignment. The size of the neutral wire should stand for 1.5 times the maximum current of the phase wires, because the rectifier in each phase works with the neutral independently. When connecting a unit with two input cables, the neutral wire is double size anyway because the input and the bypass of Power Plus have single common neutral connection.
3.9.4.7 Q: IS THERE A NEUTRAL CONNECTION ON THE INPUT AND THE OUTPUT OF THE
UNIT
?
A. Power Plus units operate with neutral on input and on the output. To achieve three-phase operation without neutral delta to star (or the opposite for output) transformers can be used.
3.9.4.8 Q. WHAT IS THE TERMINALS TYPE OF THE UNIT FOR THE INSTALLATION?
A. The terminals are 70mm screw type on all models. To connect you will need to use cable ends with your cables with 8mm or 10mm hole.
3.9.4.9 Q. DOES THE UNIT HAVE DRY CONTACT FOR THE “LOAD ON BYPASS
SIGNAL
A. Yes, it is located on the ST/SW module. Unscrew two mounting screws on the front panel of the ST/SW module and slightly pull it out. The dry contact connection is on its top, 230v rated, usually for use with electricity switchboards with make-before-break load transfer function for protection.
?

3.9.5 MECHANICS

3.9.5.1 Q: THERE ARE 50/40KVA AND 100/80KVA ST/SW MODULES. WHY?
A. There are two types of ST/SW modules, for 50/40KVA and for 100/80KVA. For example, for a 30k unit you should think if after all additional upgrades (an additional module each time) more then 50KVA load will be reached. If so, then its better to order a unit with ST/SW module for 100Kva. Of course, there is a price difference. Don’t forget that the base module for these units can also be 50/40Kva or 100/80Kva. So, every customer might require different solution.
3.9.5.2 Q: HOW CAN THE UNIT BE UPGRADED IF THERE ARE NO FREE SHELVES?
A. In these systems the housing is modular. In order to upgrade the system with a new module an additional shelf should be installed. This is a simple process, which might take no mode then half an hour for single person.

3.9.6 COMMON PROBLEMS

3.9.6.1 Q: AN ALARM LED IS IN RED ON THE FRONT PANEL. HOW CAN I QUICKLY
UNDERSTAND WHAT IS WRONG
A. On the left side of the controller there is an alarm off button. When you press it, you will see the list of all the alarms for the system and their state. They can be browsed using the up and down arrows. The active alarms will have an asterisk (*) sign near them.
Power+ Technical Guide 43
?
Page 52
Gamatronic Electronic Industries Ltd.
3.9.6.2 Q: WHEN I LOOK AT THE LIST OF THE ALARMS, I CAN SEE SOME ALARMS WHICH
ARE ALWAYS ON
A. There is a number of alarms that might be on. One of them is the “STRTUP” alarm, which stands for the startup time stamp. This alarm only means that the unit is on, and it will not raise an alarm signal. Other alarms can be the user alarm 1-4”, which are the input dry contacts. If they are not in use, you can disable them through the controller menus.
. WHY IS THAT?
3.9.6.3 Q: WHAT WILL HAPPEN IF THE EQUALIZING MODE WAS ACTIVATED IN THE UNIT?
A. The equalizing mode should always be set to DISABLED, this feature is not available. If you had it on in your system, please note that it could simulate a failure condition and a shutdown to the computers. On all the units today this feature is absent. Please contact your Gamatronic representative to upgrade your controller software version.
3.9.6.4 Q: THE UNIT ALWAYS SHOWS BATTERY TEST FAULT ALARM. THE BATTERIES
ARE
OK. WHAT IS WRONG?
A. On some older systems the controller might show false battery alarms. This was corrected, so in case that you have this problem and positively sure that the batteries are alright, please contact your Gamatronic representative to upgrade your controller software version. After you perform this action, the unit will still show battery test fault. Please perform manual battery test to restore normal operation.
44 Power+ Technical Guide
Page 53
Gamatronic Electronic Industries Ltd.

4. SYSTEM INSTALLATION

RISK OF ELECTRICAL SHOCK OR INJURY! INSTALLATION MAY BE PERFORMED BY
WARNING
Figure 4-1 illustrates the cabling of the POWER+ system to the mains electricity cabinet.
QUALIFIED TECHNICIAN ONLY!
Figure 4-1: POWER+ system connections
Power+ Technical Guide 45
Page 54
Gamatronic Electronic Industries Ltd.
Figure 4-2 below shows required switch and wire ratings for 10-100kVA installation. For battery connections, see
Figure 4-2: Switch and wire ratings for 10-100kVA installation
Figure 6-3 on page 68.
POWER+ 400 V MODEL
UPS OUTPUT
CAPACITY (KVA)
10 16 2.5 32 20 32 6 63 30 50 10 100 40 63 16 120 50 80 25 140 60 100 35 175 70 100 35 200 80 125 50 225 90 140 50 250
100 160 50 300
S2 S6
AND RA101
(AMPS)
WIRES (mm2)
RA101
(OPTION)
(AMPS)
46 Power+ Technical Guide
Page 55
Gamatronic Electronic Industries Ltd.
4.1 INSPECTIONS TO BE PERFORMED PRIOR TO
INSTALLATION
Type of check Requirement
Ambient temperature in the immediate
1. location of the equipment
2. Humidity and condensation
3. Ventilation
4.
Foundation and route to installation site
When planning the location of the UPS
5.
units, room for access to battery cabinets and electrical boards is critical.
Circuit breakers on the electrical board
6.
supplying the system Diameter of input and output power
cable connections, PE (Gnd) and neutral
7. lines.
Recommended: between 15°C and 25°C Required: between 0°C and 40°C
Verify that there is no water condensation or dampness within the installation site
Verify that sufficient airflow or forced ventilation is provided for battery cabinets location
Verification of adequate structure, space and clearance for dimensions and weights of the UPS units and their battery cabinets
Verify 40 cm clearance at rear for cable connections and 100cm at front for user access and service
Must be in accordance with Gamatronic system specifications and connection schematic
Must comply with local and international codes, and be appropriate for the circuit breakers protecting them. Refer to connections schematic.
Value, Verification
Lightning / Voltage surge protection on
8.
electrical board supplying the system.
Voltage surge suppressors type B must be installed between each phase and the neutral line:
Ratings: 300VAC for 220-230VAC mains.
Phase-to-Phase: 380*VAC, +10%, -15%
9. AC input voltage
Phase-to-Neutral: 220*VAC, +10%, -15%
10. Voltage between neutral and ground 0 – 2 VAC
Must be performed only by authorized personnel in
11. System installation and start-up
accordance with connection schematic, Gamatronic system specifications and this User Guide
* Or other, according to nominal voltage rating of local power mains.
R-S S-T T-R
R S T
Power+ Technical Guide 47
Page 56
Gamatronic Electronic Industries Ltd.

4.2 INSTALLATION PROCEDURE AND SYSTEM START-UP

Operation
Remove rear covers and connect AC input and output power cables to terminals according to markings as shown in this User Guide and according to connection schematic.
1.
Verify correct phase sequence Connect ground lines to busses according to markings as shown in the connection schematics (Figure 3-2 on
2.
16, Figure 3-3 on page 17, Figure 4-1 on page 45). Verify secure connections.
page Connect the DC power cables of the battery cabinets to the UPS terminals according to markings as shown in
Figure 4-1 on page 45 and Figure 6-3 on page 68. Connect neutral and ground lines to busses as above. Verify correct polarity of the connections (+ / N / -)
3.
terminals. Auxiliary contacts of Battery C.B.s are connected to UPS Controller inputs “Bat CB” and “Com” as marked, and as shown in
An external dual-pole / N.C. EPO switch may be connected according to connection schematic.
4.
EPO wiring and switch rating must be rated for at least 5A / 230VAC. Before connecting power to each system verify again that all connections are secure and are according to
5.
instructions and schematics.
between board and UPS
Between the Battery Cabinets C.B.s / Terminals and the UPS
Figure 7-2 on page 70.
Follow the instructions in section 4.3, “Initial Start-up Sequence”, on page 49.
6.
48 Power+ Technical Guide
Page 57
Gamatronic Electronic Industries Ltd.

4.3 INITIAL START-UP SEQUENCE

Note: Before first setting up the UPS, make sure that the load is not connected.
1. Ensure that the maintenance bypass switch (if installed) is disconnected.
2. Turn the AC input and AC bypass switch ON and wait (for about 2 minutes) for the
POWER
+
to initialize.
When applying power to the POWER
+
, the system automatically runs the startup process
without a need to press the On/Off button.
The start-up sequence will begin and the control panel will show the following sequence. (The details will vary, depending on your application.)
During this step, the LEDs are also checked sequentially.
Power up
Start-up 1
Figure 4-3: Start-up screen 1
Power up
Start-up 2
Figure 4-4: Start-up screen 2
Power up
Start-up 3
Figure 4-5: Start-up screen 3
Power up
Start-up 4
Figure 4-6: Start-up screen 4
Power+ Technical Guide 49
Page 58
Gamatronic Electronic Industries Ltd.
3. Ensure that you have a normal reading on the System Controller display. The bar graph on the left side displays loads of all 3 phases as shown in
Figure 4-7.
Power up
Default window
Figure 4-7: Normal display of the controller LCD (default)
4. Switch all battery switches ON on all battery cabinets.
Checks to be performed following initial startup
Type of check Requirement
Phase to Phase:
AC input voltage during operation under load.
1.
Take measurements on the input terminals of the system
Not less than 2% below no-load values measured in item 5 below. Phase to Neutral:
Not less than 2% below no-load values measured in item 5 below.
With no load on the system, measure current
2.
circulation between the units. With no load on the system, measure the DC
3.
voltage of the system.
Irst should be <15 A
Total DC voltage between + and – terminals should be between 850 V and 880 V.
Voltage between neutral and ground during operation under load
4. On the input terminals of the system
5. System output voltage
6. Total system load / output current
7. Correct and orderly operation
0–2 VAC
220 V +/- 2 % or other according to system specifications
Verify that the system is not overloaded in relation to system specifications
Verify that the UPS is operating normally in accordance with this User Guide and that no alarms or fault indications are evident
NOTE: It is the responsibility of the customer to notify Gamatronic Electronic Industries Ltd. and receive approval for any deviations from these requirements.
50 Power+ Technical Guide
Page 59
Gamatronic Electronic Industries Ltd.
4.4 CHECKS TO BE PERFORMED FOLLOWING INITIAL
STARTUP
Type of check Requirement Result
Phase to Phase: Not less than 2% below no-load values measured in
AC input voltage during operation under load.
8.
Take measurements on the input terminals of the system
item 5 below.
R­S
S­T
T­R
With no load on the system, measure current
9.
circulation between the units. With no load on the system, measure the DC
10.
voltage of the system. Voltage between neutral and ground during
operation under load
11. On the input terminals of the system
12. System output voltage
13. Total system load / output current
Correct and orderly operation
14.
Phase to Neutral: Not less than 2% below no-load values measured in
item 5 below.
Irst should be <15A
Total DC voltage between + and – terminals should be between 850V and 880V.
0–2VAC
220V +/- 2% or other according to system specifications
Verify that the system is not overloaded in relation to system specifications
Verify that the UPS is operating normally in accordance with this User Guide and that no alarms or fault indications are evident
R S T
R S T
NOTE: It is the responsibility of the customer to notify Gamatronic Electronic Industries Ltd. and receive approval for any deviations from these requirements.
Power+ Technical Guide 51
Page 60
Gamatronic Electronic Industries Ltd.

4.5 SPECIAL CONSIDERATIONS FOR 1-PHASE OUTPUT

This section discusses some special considerations for Power+ UPS System single-phase output (3/1 and 1/1 configuration).

4.5.1 DIP-SWITCH SETTINGS ON THE MODULES

1. On the left side of each module, close to the front panel is a small window with access to
three dip-switches.
2. For standard three-phase input and output (3/3 configuration) dip-switch no. 3 is set to
ON(LEFT) position.
3. For single-phase output (3/1 or 1/1 configuration) set the dip-switch no. 3 to OFF(RIGHT)
position on all of the modules of the System.

4.5.2 WIRING OF INPUT AND OUTPUT TERMINALS

1. For 3/1 configuration (Three phase input and single-phase output) the Bypass AC input
terminals R,S&T must be shorted between them with 35mm² wiring and so must be the AC output terminals R,S&T.
2. For 1/1 configuration (Single-phase input & output) The UPS (Rectifier) AC input
terminals R, S & T must also be shorted between them.
3. Illustrations of 3/3 3/1 and 1/1 External wiring configurations are presented in attached
files.
52 Power+ Technical Guide
Page 61
Gamatronic Electronic Industries Ltd.

4.5.3 SYSTEM START-UP

After start-up of the system the POWER+ controller automatically displays the Phase readings according to the System configuration.
Table 4-1: Power Configuration DIP Switch Settings
Switch Purpose Set left (on) Set right (off)
SW1 Master module
preference
SW2 Output power
Preferred master select(not used)
60 Hz 50Hz
frequency selection
SW3 Output power phase
3-phase Single-phase
selection
Automatic via console
Figure
Power+ Technical Guide 53
4-8: Example of dip switch setting for 3/3 phase, 50 Hz UPS
Page 62
Gamatronic Electronic Industries Ltd.

4.6 DIP SWITCH SETTINGS OF THE UPS MODULES

y Dip switch #1(in bottom) should always be OFF(RIGHT), designed for manual master
operation in stand-alone mode.
y Dip switch #2(in middle) should be ON(LEFT) for 60Hz and OFF(RIGHT) for 50Hz
inverter operation.
y Dip switch #3(in top) should be ON(LEFT) for 3 phase and OFF(RIGHT) for 1 phase
inverter output.
NOTE: All settings must be identical on each of the modules in a single (non-parallel) system.
The location of the dip switches on a UPS module is shown in the picture below.
54 Power+ Technical Guide
Page 63
Gamatronic Electronic Industries Ltd.

5. USING THE SYSTEM CONTROLLER

From the default system screen (the “Main Screen”), pressing the "ENTER" button displays the main menu.
Figure 5-1: The controller’s main menu
Table
5-1: Controller main menu options
SYSTEM UPS SELFTEST HISTORY BATTERY ALARM SETUP STATIC SW COMM
General information such as voltages, currents etc.
Information for a specific UPS module
Self checking of the Controller's components (supply, RTC, memory)
History log events (last 255 events, dated and timed)
Charging / discharging voltages and currents, battery test etc.
Detailed alarm status
Configuring the system (number of modules, alarm, time etc.)
Static Switch data
Determining the type of communication (TCP/IP, RS232 or WING)
Power+ Technical Guide 55
Page 64
Gamatronic Electronic Industries Ltd.

5.1 SYSTEM INFORMATION DISPLAY

Figure
5-2: Main menu option 1 ("System")
The SYSTEM option on the Main Menu (option 1) shows the DC voltages and current (positive, negative and summary):
Figure 5-3: System DC voltages
56 Power+ Technical Guide
Page 65
Gamatronic Electronic Industries Ltd.
1.
From the DC voltages screen, press the key to view the current output power factors
2
.
Figure 5-4: Output power factor 1
Press again to view the current input power factor.
2.
Figure 5-5: Input power factor 1
From the DC voltages screen, scroll down to view the three-phase input and output
3.
total voltage and current:
Figure 5-6: Overall phase voltages/currents
Scroll down again to see accumulated operation time and duration of current
4.
session.
Figure 5-7. General timers and counters
2
1 kVA is 1000 VA. Apparent power is measured in VA which is a reactive (i.e. a mix of both capacitive and inductive) load’s RMS voltage multiplied by the RMS current. True power is VA multiplied by the power factor, and the power factor is the cosine of the phase angle between voltage and current. A reactive load that draws an apparent power of 1000 VA and has a 0.5 power factor is consuming 500 watts of power. If a device were purely inductive, it would have a power factor 0. See also footnote 1, on page 4.
Power+ Technical Guide 57
Page 66
Gamatronic Electronic Industries Ltd.
5.
Press the down arrow again to see the jumper settings on PC714.
Figure 5-8. Jumper setting and general information
See section 3.7.1 beginning on page 33 for more information about jumpers 1, 2, 3, 6, and 9 on
PC714. See Section
6. Pressing the down arrow once again displays measurements of various internal
6.2.1.2 on page 69 for instruction for setting the battery capacity.
voltages of the controller.
Figure 5-9. Internal controller voltages
7.
Press "ENTER" again to return to the menu (Figure 5-1).
58 Power+ Technical Guide
Page 67
Gamatronic Electronic Industries Ltd.

5.2 DISPLAY UPS MODULE DATA

1. From the Main Menu, select option 2 “UPS MODULE”. The message shown in
Figure 5-11) appears.
2. Use the and keys to scroll between UPS modules. The display shows the
voltage and current measurements for each module (see
3. Scroll and keys to view additional information for the specific module chosen
(see
Figure 5-13 on page 60).
Figure 5-12 on page 60).
Figure 5-10: Main Menu option 2 (“UPS Module”)
Power+ Technical Guide 59
Page 68
Gamatronic Electronic Industries Ltd.
Figure 5-11: LCD Panel – Selection
Figure 5-12 and Figure 5-13 show parameters for the first module of a UPS system with four
modules. (UPS: #01/04).
Figure 5-12: Module phase voltages/currents
Figure 5-13: Battery voltages, I-active current
60 Power+ Technical Guide
Page 69
Gamatronic Electronic Industries Ltd.

5.3 SETTING THE NUMBER OF UPS MODULES

(The default system password is 8 left arrows [8x<”]. To change the password, see 11.2,
Setting Password Level 1 on page 86.
From the Main Screen, press Ent to display the Main Menu
1.
2. Select "7>SETUP" (Figure 5-1).
3. Enter the password and press Ent (default password is 8 x “<”).
4. Select "8>Service" (Figure 5-14).
5. Select "5>Configure" (Figure 5-15).
6. Select "2> # of UPSs" (Figure 5-16).
7. Set the number of UPS modules by using the and keys (Figure 5-17).
8. Press Enter to complete the setup.
The controller applies and saves the new number of modules.
Figure 5-14: Controller menu #2
Figure 5-15: Controller menu #3
Figure 5-16: Controller menu #4
Figure 5-17: Number of UPS modules
Power+ Technical Guide 61
Page 70
Gamatronic Electronic Industries Ltd.

5.4 RETRIEVING HISTORY (LOG OF EVENTS)

1. Select "4> HISTORY" (Figure 5-1). The last 255 events reserved in the LOG are
displayed, as shown in
2. Navigate the LOG by scrolling using the "up" and "down" arrow keys( ).
Figure 5-18.
Figure 5-18: Log display
Log messages are formatted as described in Table 5-2 below.
Table 5-2: Format of log messages
FIELD DESCRIPTION Time Date
HH:MM:SS – time message logged.
YY:MM:DD – date message logged.
Dc voltage between "+" and "-" terminals for all events except LOADBP.
Data
For LOADBP, the field holds the STSW status. See
Table 5-4 below for
interpretation of STSW status codes.
IN or OUT Description Event number
"IN" = start of event or condition; "OUT" = end of event or condition.
See
Table 5-3 below.
0 through 255, 255 being the most recent.
Example of a log message:
11:23:56 09.01.28 865 IN -> E.P.O. 254
This message means that at 11:23:56 on January 28
th
2009, Emergency Power Off alarm was
registered as event 254; dc voltage at the time was 865 V being a sum of (V+ -N) and (V- -N).
Table 5-3 below lists the various "description" field values that can appear in a log message.
62 Power+ Technical Guide
Page 71
Gamatronic Electronic Industries Ltd.
Table 5-3
: Log Messages "description" field
Alarm
01 UPSMAJ More than 1 UPS Module is sending an alarm or fault warning.
02 UPSMIN Single UPS Module is sending an alarm or fault warning.
03 ------ N.A.
04 ------ N.A.
05 LOADBP
06 VIBRA_
07 OVTEMP Excess temperature.
08 OUTFLT No ac output to load.
09 BAT-HI Excessive battery voltage.
10 ------ N.A.
11 BATEND End of battery backup. Battery is discharged to shutdown limit.
12 BATLOW Low battery voltage.
13 STSWRN Static Switch Warning or alarm.
14 E.P.O. Emergency Power Off is active.
15 EQ-HST
16 BATFLT Batteries failed last test.
17 USER-1 User 1 input open.
18 USER-2 User 2 input open
19 USER-3 User 3 input open.
20 AC-BRN Input ac supply brown-out.
21 ACIN_H Ac input excessive.
22 ACFAIL Ac input failure.
23 STSWCM Static Switch does not respond.
24 SLFFLT Last controller self-test failed.
25 BAT-CB Battery circuit breaker open.
26 CURSHR
27 UPSOUT Fault (no current) in 1 or more output stage.
28 UPSHDN UPS shutdown by EPO, Battery Discharge, ON/OFF pressed.
29 OVLOAD Load current is high.
30 UPS-CM
31 STRTUP Startup time-stamp.
32 ------ N.A.
Message Explanation
#
Load is now running on bypass. "Data" field holds the STSW transfer code – see Table 5-4 for interpretation of the STSW transfer code.
Alarm(s) vibrating. Alarm is frequently raised and lowered. Ignore to avoid loading the log filling up.
Battery is currently charging in equalizing mode, dc voltage is temporarily increased.
Current Sharing fault, load current is not equally divided between modules.
One or more UPSs not responding.
Power+ Technical Guide 63
Page 72
Gamatronic Electronic Industries Ltd.
5-4: Static Switch transfer code (for LOADBP event)
Table
The STSW transfer code, given as a decimal, is the sum of the eight components listed in this table. Each component has its own weight if detected, and a weight of zero if not detected.
COMPONENT
WEIGHT
1 2 4
8 16 32 64
128
Example: If LOADBP data = 67 = (64+2+1), this means that three conditions were present:
y (64) Instruction to transfer the load was issued by the controller.
y (2) Low peak voltage detected.
CONDITION DESCRIPTION
Inverter voltage blackout for >3 ms.
Inverter peak voltage <185 V (brownout).
Inverter peak voltage high <185 V (brownout).
Frequency beyond limits (45-65 Hz).
Inverter average voltage low.
Inverter average voltage high.
Instruction for load transfer was received from the controller.
Instruction for load transfer was received from the Static Switch.
y (1) Voltage blackout encountered.
64 Power+ Technical Guide
Page 73
Gamatronic Electronic Industries Ltd.

5.5 SYSTEM CONTROLLER ALARMS

System Controller alarms are described in Table 5-5.
Table 5-5: System controller alarms
AC-BRN Input AC supply Brown Out
ACFAIL AC input failure
ACIN_H AC input excessive
BAT-CB Battery Circuit Breaker Open
BATEND End of battery backup. Battery is discharged to shutdown limit
BATFLT Batteries failed last test
BAT-HI Excessive battery voltage
BATLOW Low battery voltage
CURSHR Current Sharing fault, load current is not equally divided between modules
E.P.O. Emergency Power Off is active
EQ-HST
LOADBP Load is now running on bypass
OUTFLT No AC output to load
OVLOAD Load current is high
OVTEMP Excess temperature
SLFFLT Last controller self-test failed
STRTUP Startup time-stamp
STSWCM Static Switch does not respond
STSWRN Static Switch Warning or alarm
UPS-CM
UPSHDN UPS shutdown by EPO, Battery Discharge, ON/OFF pressed
UPSMAJ More than 1 UPS Module is sending an alarm or fault warning
UPSMIN Single UPS Module is sending an alarm or fault warning
UPSOUT Fault (no current) in 1 or more output stage
USER-1 User 1 input open
USER-2 User 2 input open
Battery is currently charging in equalizing mode, dc voltage is temporarily increased
One or more UPSs not responding
USER-3 User 3 input open
VIBRA_
Power+ Technical Guide 65
Alarm(s) vibrating. Alarm is frequently raised and lowered. Ignore to avoid loading the log filling up.
Page 74
Gamatronic Electronic Industries Ltd.

6. BATTERIES

6.1 BATTERIES AND CONFIGURATIONS

The POWER+ is flexible in structure, in that it may be extended by adding modules as required. The battery bank is common to all modules and may comprise one or more branches to include a redundant battery if desired.
For systems from 10kVA through 30kVA, the batteries may be internal; otherwise, the batteries are housed in external cabinets. See and connections.

6.1.1 INTERNAL BATTERIES

Up to 3 internal packs, each containing 64 × 12v/5Ah batteries, may be housed in the Power+ system cabinet. This would provide 4 minutes of backup time at full load, on a redundant system of 5 modules (total 40kVA). See
Each battery pack is 6U high and weighs about 135 kg on average, depending on the manufacturer and model. It comprises 4 drawers, each containing 16 batteries, to facilitate removal and replacement. See
Figure 6-3 on page 68 for details on battery cabinet wiring
Figure 6-1 below.
Figure 6-2 on page 67.
System controller
4 x 10kVA UPS modules (plus 1 x redundant)
DC distribution
Static switch
Battery drawers
Figure 6-1: 40kVA N+1 System with Internal Batteries
66 Power+ Technical Guide
Page 75
Gamatronic Electronic Industries Ltd.
Figure 6-2: Internal Battery Drawer – Exploded View

6.1.2 EXTERNAL BATTERIES

External batteries are housed in separate cabinets.
These batteries are connected to the system by heavy duty cables, care must be taken to ensure correct polarity. Overall voltage may be as high as 870vDC + to -, i.e. +435vDC and – 435vDC with respect to ground/earth. Precautionary measures must be taken whenever connecting the battery or servicing the battery cabinets.

6.2 INSTALLING AND CONNECTING THE BATTERIES

As shown in the diagram, the DC output cable from the batteries is connected directly to the small Anderson connectors on the UPS rear panel.
WARNING: When connecting the batteries to the UPS:
y The UPS’s AC INPUT circuit breaker must be in the OFF position, AND
y The battery circuit breaker must be in the OFF position.
WARNING: After connecting the batteries to the UPS, do not turn on the battery circuit breaker until the UPSs AC INPUT circuit breaker is turned on.
Cables from battery banks are connected to the Anderson connectors on the DC distribution shelf as indicated in
Power+ Technical Guide 67
Figure 3-11 on page 27 and Figure 3-12 on page 27.
Page 76
Gamatronic Electronic Industries Ltd.
Figure 6-3: Connection diagram for external battery
68 Power+ Technical Guide
Page 77
Gamatronic Electronic Industries Ltd.

6.2.1 CONFIGURING THE BATTERIES TO THE SYSTEM

When you are installing the battery for the first time, or if you have changed either
y the number of battery sets (1 battery set = 64 batteries)
OR
y the total Ampere/hour capacity of your batteries,
you must reconfigure the batteries to the system.
6.2.1.1 TO (RE)CONFIGURE THE NUMBER OF BATTERY SETS:
1. On the system control panel, press Ent.
2. Choose Setup, press Ent.
3. Enter the system password (the default password is eight left arrows), press Ent.
4. Select Service, press Ent.
5. Select Configure, press Ent.
6. Select # of Batteries, press Ent.
7. Use the up and down arrow keys to modify the number of batteries, then press Ent.
6.2.1.2 TO (RE)CONFIGURE THE BATTERIES' AMPERE/HOUR RATING:
1. On the system control panel, press Ent.
2. Choose Setup, press Ent.
3. Enter the system password (the default password is eight left arrows), press Ent.
4. Select Battery, press Ent.
5. Select Capacity, press Ent.
6. Choose the battery set that you want to configure and press Ent.
7. Use the arrow keys to set the desired number of Ampere/hours, then press Ent.
Power+ Technical Guide 69
Page 78
Gamatronic Electronic Industries Ltd.

7. DRY CONT ACTS AND ALARM TERMINALS

Dry Contact terminals are located on the right side of the rear of the POWER+ controller
module, as shown in
Figure 7-1: Location of dry contacts at rear of POWER+ controller module
Figure 7-1, labeled A and B.
Figure 7-2: Dry Contacts “group A (as per
“INPUTS” DRY CONTACT DESCRIPTION
Figure 7-1)
NAME IN
ALARM DISPLAY
COM Shared contact ---
BAT CB
Auxiliary contact (N.C.) for battery Circuit Breaker trip indication
BAT CB
N.C.1 USER1 – user assigned dry contact USER-1
N.C.2 USER2 – user assigned dry contact USER-2
70 Power+ Technical Guide
Page 79
Gamatronic Electronic Industries Ltd.

7.1 DC CURRENT MEASUREMENT

The dry contacts in Figure 7-2 labeled “DC CURRENT MEASUREMENT” are for monitoring
battery current. Each group may be connected to a different current sensor. Measurements can be taken from up to three battery sets, as per the three groups of Current Measurement contacts.

7.2 TEMPERATURE SENSOR

An optional temperature sensor (see Figure 7-3) may be attached to the contacts labeled
TEMP to monitor the temperature of the batteries.
Figure 7-3: Dry Contacts “group B” (as per Figure 7-1)
To install the temperature sensor, connect the sensor according to Figure 7-3 and Figure 7-1.
To see the temperature reading, a configuration change must be made to the controller. Enter the following commands on the system controller panel:
Ent, Setup, Password (default password is 8 left-arrows), Battery, Enable/Disable Options, Enable Batt Temp Sensor
To see the temperature reading, enter the following commands on the system controller panel:
Ent, System, 5 x down arrow. Press Esc to exit.

7.3 USER-DEFINED ALARMS

There are four groups of 3 contacts each (see Figure 7-3) that can be used for user-defined
alarms. In each group, either the N.C. or N.O. contact is used together with the COM contact.
Power+ Technical Guide 71
Page 80
Gamatronic Electronic Industries Ltd.

8. PERIODIC MAINTENANCE

The Power+ system should undergo periodic maintenance at least once a year.

8.1 OBJECTIVES OF THE PERIODIC MAINTENANCE

The periodic maintenance is performed to verify the following:
y Power+ UPS and batteries are in proper electrical and physical condition
y The operation of the UPS and its batteries conform to design specifications
y The UPS and batteries are in compliance with all relevant safety standards and
regulations

8.2 RECOMMENDED TOOLS

Before proceeding with the periodic maintenance make sure that the following tools are available to you:
Philips screw driver
Flat head screw driver
Thermometer
Oscilloscope
Air compressor (for cleaning)
Flashlight
72 Power+ Technical Guide
Page 81
Gamatronic Electronic Industries Ltd.

8.3 MAINTENANCE PROCEDURES AND REPORT

Record the values of all parameters checked and of measurements taken during the periodic maintenance in the form below. Fax the completed form to Gamatronic at +972-2-582-8875.
Power+ model and configuration Company ______________________ _______________________________ Site ___________________________ Phone ________________ E-mail _________________ Power+ Model __________________ [ ] Up to 50 kVA [ ] Up to 100 kVA
Type of maintenance: [ ] Annual [ ] Semi-annual [ ] Quarterly System S/N (found at the bottom left side of the base): ______________________________________ Static Switch S/N (found on top of Static Switch after opening):______________________________ Module S/Ns (found on the right side of each module after removing from housing – six last digits only):
1________________ 2________________ 3________________ 4_____________ 5_______________
6________________ 7________________ 8________________ 9_____________ 10______________
Technician Name _______________
_______________________________
Address _______________________________________ _______________________________________________
No. of modules _______ [ ] 2-phase [ ] 3-phase
Date ___________________
No. of redundant
modules _______
Signature ___________________________
Visual Inspection OK [ ] Not OK [ ] Environmental Inspection
Environmental temperature
Ventilation
Air conditioning
Comments _________________________________________________________________________________
Display Panels
LCD Display
LEDs
Voltages
Verify that displayed dc voltages, rectifier input voltages, and inverter output voltages are showing proper values. Verify the readings
for the UPS as a whole (menu option 1, System) and for each module (menu option 2, UPS Module).
Dc voltages
Rectifier input voltages
Inverter output voltages
Serial Number / Clock and Calendar
Done
Done
Comments ________________________________________________________
________°F
[ ] OK [ ] Not OK [ ] Yes [ ] No
[ ] OK [ ] Not OK Comments ____________________________ [ ] OK [ ] Not OK Comments ____________________________
(+)_______________ (-)_______________ (Total)_______________ Volts: __________ __________ __________ Amperes: __________ __________ __________ Hertz: __________ Volts: __________ __________ __________ Amperes: __________ __________ __________ Hertz: __________
Verify that the Power+ serial number is registered in the System Controller memory. If not, enter the serial number into the memory and save.
Verify that the Power+ clock and calendar show the right time and date. If either time or date are incorrect, enter the correct information and save.
Power+ Technical Guide 73
Page 82
Gamatronic Electronic Industries Ltd.
Alarms
Use menu option 6 to display the alarms. Active alarms are identified by an asterisk to the right of the alarm name. List the names of any active alarms: ___________________ ___________________ ___________________
Done
I-active / I-bus
Verify that the difference between I-active and I-bus for each module is no greater than 1 mA.
[ ] OK [ ] Not OK Comments ____________________________________________________ Bypass Test and Module Maintenance
Connect an oscilloscope to Power+ output terminals L1 and N. Press the INV/BYPASS button twice to transfer the UPS to bypass mode. Verify that the transfer takes place normally, with no interruption of power to the load.
[ ] OK [ ] Not OK Comments ____________________________________________________
Done
Done
Software Version
Check the software version in the System Controller. If it is not the latest, replace the EPROM with the latest version.
Done
Check Front and Rear Fans
Use a flashlight to visually verify that the 4 front fans and 2 rear fans in each module are operating.
Front fans
Rear fans
Voltage Measurements
Measured value: ____ Vac Measure the voltage between Neutral and Ground at the bypass input. The value should be no
Use a voltmeter to measure the bypass input voltages according to the table below. Compare your measurements with the console display of the bypass input voltage.
Location Phases
Calibration
Select option 7 from the Main Menu. When prompted for the password press the left arrow key 8 times and press Enter. When the submenu appears, select option 2, Module Configuration, then option 7, Dc calibration or option 8, Ac calibration. Enter here any calibration performed: __________________________________________________
Verify that the Power+ clock and calendar show the right time and date. If either time or date are incorrect, enter the correct information and save.
Remove each module and clean the exterior and rear contacts with compressed air. Check the rear of each module for corrosion. Blow compressed air into the module front to back and back to front.
Return the modules and transfer the UPS back to Inverter mode. Verify that the UPS functions normally.
Comments ____________________________________________________
[ ] OK [ ] Not OK Comments ____________________________ [ ] OK [ ] Not OK Comments ____________________________
greater than 5 Vac..
Voltmeter reading
L1 – N
L2 – N Inverter output
L3 – N
Console reading
YES NO
Readings match?
74 Power+ Technical Guide
Page 83
Gamatronic Electronic Industries Ltd.
Battery Checks
Turn the battery circuit breaker to Off and disconnect all Anderson connectors in the battery set. Record the battery serial number, type, and number of cells in the table below:
Battery
manufacturer
Battery model Rating (Ah) Number of strings (x 32)
Use a power resistor of 0.5
(300 W rating recommended) for the load to check the voltage drop across the
terminals of each battery. There should be no more than a 10 Vdc drop for any battery. Replace any batteries that seem to be inadequate.
BATTERY STRING #1 BATTERY STRING #2
Batt.
no.
1 17 33 49
2 18 34 50
3 19 35 51
4 20 36 52
5 21 37 53
6 22 38 54
7 23 39 55
8 24 40 56
9 25 41 57
10 26 42 58
11 27 43 59
12 28 44 60
13 29 45 61
14 30 46 62
15 31 47 63
16 32 48 64
Good Bad
Batt.
no.
Good Bad
Batt.
no.
Good Bad
Batt.
no.
Good Bad
END OF MAINTENANCE PROCEDURES REPORT
Power+ Technical Guide 75
Page 84
Gamatronic Electronic Industries Ltd.

9. TROUBLESHOOTING

The system log (option "4 – HISTORY" on the main menu) can be very useful in determining the cause of a UPS malfunction. See section
The indicator lights on the UPS module's front panel can also signal a malfunction.
5.4 "Retrieving History (LOG of Events)" on page 62.
Figure 9-1: UPS module front panel
As shown in Figure 9-1 there are three LEDs on the front panel of each UPS module: Alarm,
Output and Line. The internal buzzer in the UPS module sounds when there is no communication with the system controller.
These 3 LEDs and the buzzer indicate the status of the UPS module (see
The alarm LED is red, line and output LEDs are green. Normal condition is indicated by the green line LED and output LED on, with no beeps from the buzzer.
Table 9-1 below).
76 Power+ Technical Guide
Page 85
Gamatronic Electronic Industries Ltd.
9-1: UPS Module Indicators
Table
CONDITION LINE
Wake-up Start Normal
Operation Abnormal
Input voltage One phase
abnormal input
High Input Current
Vdc > 450V Vdc > 500V DC imbalance Low Vdc< 360V Vdc very low,
< 320V DC critical fail
< 200V Circulation
Current Output overload
Output is disconnected
Communication failed
Output short-circuit
(GREEN)
On On On
Off Off Off About 1 minute
On On Off
Off On On
Blinks On Off
Blinks On On
On Off Off High Vdc
On Off On Very high Vdc
On On Blinks
On* On Blinks
On* Off On
Blinks Off On
On Off On
On Blinks Off
On Blinks On Result of output
On On On Or absence of
Blinks Off On
OUTPUT (GREEN)
ALARM (RED)
BEEPS REMARKS
* Mostly will be caused by Vin fault that will turn
off LINE LED
overload
System Controller
Power+ Technical Guide 77
Page 86
Gamatronic Electronic Industries Ltd.
Table
9-2: Troubleshooting table
1
After the startup the unit won’t switch to inverter.
2 On a module OUTPUT and
ALARM LEDs are flickering.
3 The unit shows output load while
there is no load connected.
PROBLEM SOLUTION
1. Check the phase sequence of the bypass input. Swap phases S (L2) and T (L3) on this input for proper phase rotation.
2. Make sure that the bypass input voltage and frequency is within the tolerance.
1. Try resetting the module by pushing the RESET button on its front.
2. Check its output voltage through the controller. If no voltage – replace the module.
1. Check and compare each modules output voltage on each phase. One of the modules might be configured to a voltage different from others, thus causing circulation currents on the output.
2. Compare I-BUS and I-ACT for each module in the UPS module” menu on the controller. If these values are not similar for one of the modules, check it individually.
4 Contactor sounds can be heard
from the unit from time to time, but no transfers to bypass have been registered.
5 Red alarm LED is lit on the
controller.
6 LINE LED blinks in green on a
module, while output is green and alarm is not lit.
These units have internal synchronization contactor, which should protect from switching to bypass and feedbacks while the bypass input is not synchronized with inverter. It will switch off automatically each time bypass frequency gets out of tolerance, and when the problem is restored it will switch back on. Check the supply. Power+ units frequency window is adjustable from ±0.5Hz to ±4Hz.
1. To see the list of active alarms with short descriptions, press the ALARM OFF button (the middle one on the right hand side of the controller). Navigate with arrow keys.
2. To see the list of active alarms with full description, press and hold “ESC” key to get in to the menu and choose Alarms Status”. Navigate with arrow keys.
A phase is missing on the main input. If the problem exists on one module only, check the input fuses (located on the rear side of base unit, above the AC terminals). There is one fuse for each phase of each module.
78 Power+ Technical Guide
Page 87
Gamatronic Electronic Industries Ltd.
7 DC voltage gets low, sometimes
until the unit switches off and goes on bypass.
1. The unit might be in the middle of the battery test. Check it through the controller. If it is, either let it finish or stop it manually.
2. Check the current limit and battery temperature compensation settings in the controller. They can cause severe drop in DC voltage if not configured properly.
3. Try to remove the system controller and check if the DC voltage restores to normal. If it does, check controller settings. This will not stop P+ operation or cause interference with the load.
4. If battery temperature compensation and/or battery current limit are enabled, make sure that the unit has the required optional sensors installed. If not, disable the corresponding feature.
8 The modules are working
normally, but the system controller is off.
9 The system is running normally,
but shows UPS-CM alarm.
10 No values are received from the
unit through the communication port or through the WING.
1. Check AC fuses (located on the rear side of base unit, above the AC terminals) and DC fuses (located behind a blank cover above the ST/SW module).
2. Replace PC093 power supply PCB inside the system controller.
3. Replace the system controller.
Check the number of modules value in the controller. If the system is set up for more modules then actually exist, it will fail to communicate with non-existing modules.
In the COMM. menu there are three communication options. In units with PC375 communication boards (before 2006) the first option should be selected, TCP/IP Comm. Board. On units with PC575 boards, which appeared from the beginning of 2006, the second option should be selected – PC575. WING will work with both options, and the third option, WING communication, should not be used. It is designed for special units without communication cards only.
Power+ Technical Guide 79
Page 88
Gamatronic Electronic Industries Ltd.

10. SYSTEM CONTROLLER & COMMUNICATIONS

10.1 INTRODUCTION

The SCC POWER+ controller enables you to control and monitor all the individual components of the POWER+ system. Flexibility in setting the various configurations allows you to adjust the system to suit specific individual needs.
The system is equipped with clear, simple, user-friendly menus and submenus for easy monitoring, parameter definition and control of the system. The SCC provides communication with a wide range of management equipment, such as computers and mobile phones.

10.2 SCC POWER+ CHARACTERISTICS

The controller’s main functions include:
y Real-time 32 alarm display
y Manual and periodic battery testing
y An event log that records recent 254 events
y Service utility software
y Remote control of the system (via TCP/IP, SNMP, PPP, GSM, GPRS, SMS,CDMA).
y Three levels of access to the controller: factory, supervisor and service
y Easy restoration of factory defaults
y Easy setting and saving of user defaults
y Flexible output dry contacts
y Manual bypass command
y System turn off with or without bypass
80 Power+ Technical Guide
Page 89
Gamatronic Electronic Industries Ltd.

10.3 CONTROLLER USER INTERFACE

The controller’s user interface includes:
y 40 × 4 LCD panel
y 6 Navigation Keys
y 3 Quick Command Buttons
y 8 Indication LEDs
y 2 Communication LEDs

10.4 SERVICE UTILITIES

There are several service programs intended for higher-level users (i.e. technicians, maintenance staff, etc.).
These programs allow canceling and performance of low-level operations in the system at the same time. These operations are complex and can modify the system configuration, affecting its operation. The service utilities should only be used by authorized personnel.
These service utilities allow the operator to:
y Change configuration
y Manually turn off and on UPS
y Test dry contact outputs
y Switch to alternative version of the software
y Change communication settings
y Restart the controller
y Restart the network adapter

10.4.1 START-UP SCREENS

The welcome screen is displayed for a few seconds when the controller is switched on or restarted, and is immediately followed by a self-check test.
On completion of the self-check test the initializing screen appears and remains on display until the controller’s restarting process is completed. The software’s version is shown on the second row. The time remaining in the restart process appears on the fourth row of the screen. The main screen appears once the initializing screen closed.
The main screen provides the basic and essential information about the real-time status of the power system. The LED indicator lights located to the right of the screen, warn if there is a problem. The main menu remains displayed until one of the keys is pressed. The controller automatically returns to this main menu screen whenever a key is not pressed for five minutes.
Power+ Technical Guide 81
Page 90
Gamatronic Electronic Industries Ltd.
The following information is displayed on this screen:
y DATE - Current date y TIME - Current time y AC-VOLT - System input voltage from mains y AC-CURRENT - System input current from mains y AC-Output Voltage – System output voltage y FL - Number of the active flash y PD - Peripheral device status y UP – UPS general status
From the main screen you can navigate to:
y The Fast Information Menu through which you can access the 7 Fast Information screens y The Main Menu from which you can access:
y Monitor Screens that let you monitor the system and components
y Calibration Screens that let you calibrate the system and components
y Control Screens that let you control the system and components
Fast Information Screens
In addition to the many screens displaying detailed information about all aspects of the system,
there are seven Fast Information screens that contain further details about the real-time status of the system. These screens can be accessed from the Fast Information Menu.
Network Fast Information Screen
This screen provides information about network related parameters such as the IP address, the gateway address and the mask.
There is also a counter that shows the number of times the controller failed to connect with the server. The maximum value that the counter can display is 225. Under normal operating conditions the value should be 0.
There is also a count of the number of times there was no SNMP link. This value resets the Network card.
Dry Contact Fast Information Screen
This screen provides real-time data on the status of the input and output dry contacts.
For both input and output dry contacts:
y A filled circle appears when the dry contact is closed.
y An unfilled circle appears when the dry contact is open.
82 Power+ Technical Guide
Page 91
Gamatronic Electronic Industries Ltd.
System Alarm Status Fast Information Screen
This screen shows the status of the existing system faults, indicating whether or not they are active. This screen shows:
y A filled circle indicates an active fault.
y An empty circle indicates an inactive fault.
General Information Screen
The following table describes the information displayed on the Information screen:
Table 10-1: General information screen
FIELD DESCRIPTION REV
T.C. V-SET MAINT V-AUX SITE BATT
Software revision number
Temperature
Output voltage
Last maintenance date
Input Voltage
ID number of the site
General battery information
Power+ Technical Guide 83
Page 92
Gamatronic Electronic Industries Ltd.

10.4.2 THE MAIN MENU

The Main Menu enables you to access screens that monitor and control every aspect of the
system including setting parameter limits, activating the system checks and monitoring the status of individual components of the system.
The Main Menu functions are listed in
Table 10-2: Main Menu functions
Screen Description 0 SYSTEM
1 UPS 2 SELFTEST 3 HISTORY 4 BATTERY 5 ALARM 6 SETUP 7 COMMS
Monitoring the System
Monitoring UPS
Initiates a Self Test of the Controller
Event Log
Monitoring the Batteries
Monitoring the Alarms
Submenu for setting parameters and starting tests
Communication (not implemented)
Table 10-2 below.
84 Power+ Technical Guide
Page 93
Gamatronic Electronic Industries Ltd.

11. SETUP PROCEDURES

The options in the Setup Menu enable you to configure system parameters.
Table 11-1: Setup Menu options
Option Description 1 ALARM SET
2 UPS 3 BATTERY 4 CHARGE 5 TIME 6 SITE 7 PASSWORD 8 SERVICE 9 SILICON
Opens menu with options for setting the threshold levels that trigger alarms
Sets the UPS Parameters
Sets the Battery current parameters
Sets the Charge mode parameters
Sets the systems clock which sets a time stamp on log entries
Sets the power system's ID number
Sets Level 1 Password
Opens menu of service utility programs
Opens menu with options for restoring factory-defined default values to parameters

11.1 SETTING ALARM THRESHOLDS

It is possible to define the threshold values for setting off alarms for the parameters of system components. An alarm is set off each time a parameter value is outside the defined range of permitted values.
Press the number that appears beside a menu option to open a screen in which you can set the alarm thresholds for that option.
Table 11-2: Setting alarm thresholds
OPTION DESCRIPTION
0 AC VOLT
1 OUTPUT VOLT
6 BATTERY
7 TEMPERATURE
8 VIBRATION
9 INTEGRATION
Sets the permitted AC voltage range (minimum and maximum input voltage) and the AC voltage hysteresis
Sets the permitted DC voltage range (minimum and maximum output voltage)
Sets the permitted battery voltage range (minimum and maximum output voltage) (indicates possible battery fault)
Sets the permitted battery temperature range (minimum and maximum temperature)
Sets the number of times an alarm must occur within a specified period of time to be considered a vibrating alarm
Sets the number of times the controller must receive an alarm from the system before it logs the alarm
Power+ Technical Guide 85
Page 94
Gamatronic Electronic Industries Ltd.

11.1.1 SETTING ALARM VIBRATION PARAMETERS

A “vibrating” alarm is an alarm that is activated often. A vibrating alarm can fill a log with alarm messages for the same alarm. To avoid filling the alarm with this kind of messages, you can define a vibrating alarm (setting the number of times an alarm must occur as well as the period of time in which it must occur).

11.1.2 SETTING THE INTEGRATION FACTOR FOR ALARMS

The integration factor is the coefficient that determines the number of times an alarm must occur before the controller records it. The smaller the value of the coefficient is, the sooner the warning notification is received. However, with a small coefficient there is a chance that an alarm may be given for a glitch rather than a fault. The larger the value of the coefficient is, the more notification is delayed and the greater the reliability.

11.1.3 'AUTO' TEST BATTERIES

The 'Auto' test option checks the periodic/automatic testing of the batteries.

11.2 SETTING PASSWORD LEVEL 1

A level 1 (supervisor) password allows you to monitor and control the system.
86 Power+ Technical Guide
Page 95
Gamatronic Electronic Industries Ltd.

11.3 ADDING A POWER MODULE

If an additional shelf is attached at the top of the system, the DIP switch of the Control PCB must be changed to the next address code as shown in
Updating the number of modules in the Power Plus processor:
(‘Ent’ represents a press of the Ent key.)
Ent, Setup,
Ent, Password (default password is 8 “left arrows” [½] ),
Ent, Service ,
Ent, Configure
Ent, Total # of UPS,
Table 3-3 on page 38.
Ent, (enter number of UPSs),
Ent , Ent
The system reinititializes itself.

11.3.1.1 TURNING OFF THE OUTPUT CURRENT LIMIT:

Ent, Setup,
Ent, Password (default password is 8 “left arrows” [½] ),
Ent, Battery,
Ent, Current Limit,
Ent, Enable current limit (off)
Esc.
Power+ Technical Guide 87
Page 96
Gamatronic Electronic Industries Ltd.

11.4 SYSTEM CONTROLLER SETUP VERIFICATION

The system verification is available for software versions beginning from 050106.

11.4.1 ACCESS

Press ESCAPE key and hold it for 3S. Using ARROW UP/DOWN key, select GENERAL (8) and press ENTER. Screen 1 is presented.

11.4.2 SCREEN 1

a) ACV: nominal value of the input/output AC voltage (220 for 2x32 batteries ; 110 for 2x16
batteries)
b) ALM: input AC voltage alarm HIGH/LOW
c) TEMP.ALARM: high temperature limit for external thermosensor d) MODULES: QUANTITY/REDUNDANCY – 07/02 in the screen means that 7 modules are
presented in the system, 2 modules are reserve (full load is 10KVA*(7-2)=50KVA/40KW)
e) C.LIM.=off (VALUE)- battery current limit function is de-activated (off) or max. battery current
value in Amps. In C.LIM is activated, the system must be equipped with optional battery current sensor.
f) T.C.=2.0mV – negative temperature coefficient of the battery DC voltage in mV per ºC per
battery cell. Nominal temperature is 25ºC. For DC nominal voltage 432V , temperature 35ºC, 32 batteries of 6 cells, T.C.=2mV, the voltage is 432- 2*6*32*(35-25)~=428V. NOTE. For most applications T.C. must be 0 (off).
g) DCV: DC nominal voltage for both positive and negative battery sets. For 32 batteries in the set
DCV=432V, for 16 batteries 216V.
h) DCV …ALM: DC voltage alarms HIGH/LOW/SHUTDOWN. SHUTDOWN alarm is DC voltage
value when the unit is stopped due to battery discharge.
i) BATT.TEST: PERIOD IN WEEKS/MAX.DURATION IN HOURS/ALARM
VOLTAGE/CHARGER DERATED VOLTAGE. In the screen: the test is performed automatically once per 4 weeks, max. test duration is 5 Hours, if battery voltage drops below 360V alarm Battery Low is given, the chargers of the modules continue to supply voltage 352V to prevent shutdown if battery is faulty.
j) CAP: CAPACITY in Amp-Hours. Is used to calculate estimated back up time of the system and
battery test duration.
88 Power+ Technical Guide
Page 97
Gamatronic Electronic Industries Ltd.

11.4.3 SCREEN 2

To access SCREEN 2 press the key ARROW RIGHT when SCREEN 1 is selected.
a) #OF PHASE: FORCE 3 for 3 phase output, FORCE 1 for single phase output or AUTO when the
mode is defined by DIP SWITCH of the modules.
b) REV: revision of system controllers (SC) software
c) LVD BY AC FAIL: DIS (disabled) or EN (enabled). This function, if enabled, performs system
shutdown after 3 Hours of AC failure to prevent deep battery discharge by low current. In most application the function must be DIS.
d) MAINT: YEAR.MONTH.DAY: date of last maintenance
e) TEMP. SENSOR: DIS or EN . External thermosensor is disabled/ enabled. In most applications
must be DIS.
f) SITE: the site identification number. Is used in network applications.
g) CURR.SENSOR: DIS or EN. Optional battery current sensor is disabled/ enabled. In most
applications must be DIS.

11.4.4 SCREEN 3

To access SCREEN 3 press the key ARROW RIGHT when SCREEN 2 is selected.
The screen presents status of controller boards jumpers. See also section controller card" beginning on page
a) Not HARD Silicon. Must be HARD only initially, during first activation of non-configured
controller. After production should be Not HARD Silicon.
b) Silicon Mode. Regular mode allowing setups change. The setups are saved in EEPROM chip. c) CAPACITY HI (LO). High/low battery capacity mode when battery capacity is more/less than
100AH to achieve optimal resolution of battery current displayed value.
33 for more information regarding these jumpers.
3.7.1 "PC714 – the
d) No/Yes Rmt Pan. Outputs of SC are not configured/ configured for optional remote panel
connection.
e) AC: 220V. Nominal AC input voltage: 220V for 2x32 batteries, 110V for 2x16 batteries in series.
Power+ Technical Guide 89
Page 98
Gamatronic Electronic Industries Ltd.

12. REPLACEMENT PROCEDURES

12.1 UPS MODULE

To remove a UPS module from the system:
1. Unscrew the mounting screws on both sides on the front module panel.
2. Hold the front handle of the module and remove it by pulling out.
3. If the module is being permanently removed, update the total amount of modules in the system controller.
WARNING: Do not touch or short-circuit metal pins on rear plugs of the module, as they might still be
energized. Let the module discharge for at least 15 minutes prior to any operation or disassembly.
NOTE: Other UPS modules operation will not be affected by this removal, unless the load will become
too high for them with less power in total. For instance, if the load is 25Kva and one module out of three was removed, the system might switch to bypass due to overload of the remaining UPS modules.
To insert a UPS module in to the system:
1. Insert the module firmly in to the housing and slide it in until it stops.
2. Screw the module in with two mounting screws located on the sides of its front panel.
3. It might be required to reconfigure the system controller with the new amount of modules in the system
WARNING: Make sure that the module has the same configuration as other modules in the system. This
includes the dip switch settings (on the module itself) for frequency and number of output phases, as well as the internal output voltage configuration, like 240v or 230v, which can be changed through the system controller only. If the UPS module configuration will diverse from other modules configuration, this and/or other modules might be damaged.
NOTE: If the Power+ system was energized during modules connection, the module will switch on
automatically within one minute. This will not affect other modules or the load.
90 Power+ Technical Guide
Page 99
Gamatronic Electronic Industries Ltd.

12.2 SYSTEM CONTROLLER MODULE

To remove a system controller module from the system:
1. Ensure that there are no cables connected to the rear plugs of the controller. If there are any, disconnect them prior to controller removal. This includes LAN cable and the WING (optional) connections.
2. Unscrew the mounting screws on both sides of the system controller and pull it out of the housing.
NOTE: Controller removal will not affect modules operation and the load. Every module has its own
internal control and will keep up with proper operation, like current sharing and battery charging. Some functions will not be available while the system controller is removed: battery test, battery conditioning systems etc.
To insert a system controller module in to the system:
1. Confirm that the rear cables/plugs (if any) will not hinder the process; take them out of the housing.
2. Hold the controller firmly and slide it in to the housing.
3. Screw the controller in with two mounting screws located on both sides of its front panel.
4. Connect rear external cables (if any) including LAN and WING (optional) connections.
5. If the controller was replaced with a new one, make sure that its configuration matches the system with number of modules, battery settings, etc.
WARNING: If the controller is not properly configured for the given Power+ system, it might produce
false alarms and incorrect DC voltage handling.
NOTE: If the system was energized, the controller will start automatically within one minute.
Power+ Technical Guide 91
Page 100
Gamatronic Electronic Industries Ltd.

12.3 STATIC SWITCH MODULE

To remove a ST/SW from the system:
1. Switch the entire Power+ system off, including input power and the batteries.
2. Unscrew two mounting screws on both sides of the ST/SW front panel, and slightly pull it out, not more than 20cm.
3. Disconnect:
A.
Communication flat cable (mounted with 2 screws)
B. EPO/dry contact connections (if any) C. 9 phase wires from the terminals (marked according to their order) D. 1 neutral wire from its terminal E. 1 earth wire from a dedicated screw
4. Pull the ST/SW module out from the system.
WARNING: This operation is not possible to perform live, without load and Power+ system
disconnection. The system should be switched off completely. Ensure that there are no AC voltages on the terminals. If another ST/SW module will not be mounted immediately, all disconnected wires should be isolated to prevent accidental damage and protect from electrocution.
To connect a ST/SW in to the system:
1. Make sure that there are no AC voltages on the system’s terminals and that the system is switched off completely.
2. Slide the ST/SW module into its housing.
3. Connect in opposite order to it’s disconnection (above).
92 Power+ Technical Guide
Loading...