Galletti UTN 08, UTN 06A, UTN 12, UTN 12A, UTN 08A Technical Manual

...
high pressure fan coils technical manual
GB
UTN
INDEX
1 Main features ............................................................................... pag. 2
2 Versions and components ............................................................. pag. 2
3 POSSIBLE CONFIGURATIONS ....................................................... pag. 3
4 Available options .......................................................................... pag. 3
5 Rated technical data ..................................................................... pag. 4
6 Ventilation features ................................................................. pagg. 5 / 6
6.1 Accessories: air pressure drop ................................................. pagg. 7 / 8
6.2 Sound power levels for octave band ............................................... pag. 8
7 Performances ...................................................................................
7.1 Cooling capacity ..... .......... .......... ........................................... pagg. 9 / 10
7.2 Heating capacity ................................................................. pagg. 11 / 12
7.3 DF coil heating capacity ............................................................... pag. 13
8 Installation suggestions ............................................................... pag.14
9 Dimensional data ................................................................ pagg. 15 / 16
10 Wiring diagrams .................................................................. pagg. 17 / 23
10.1 Motors electrical data .................................................................. pag. 24
11 Accessories ........................................................................ pagg. 24 / 27
12 Maintenance ............................................................................... pag. 28
DECLARATION OF CONFORMITY
Galletti S.p.A. with head offices in Via Romagnoli 12/A, 40100 Bentivoglio (Bologna) - Italy, declares under its own exclusive responsibility that the UTN range of air conditioning and hot-air heating units, heating and conditioning equipment, for systems that distribute air through channels, comply with the requirements of the following EEC Directives: 73/23, 89/392, 91/368, 93/44, 93/68, 98/37 and 89/336. Bologna, 02/07/2001 Luigi Galletti Chairman
OPERATING LIMITS
Thermal carrier: water Water temperature: + 5°C to +95°C Air temperature: -20°C to + 43°C Power supply voltage: 230 V +/-10 % Max. pressure of primary fluid: 10 bar
The new range of UTN high pressure fan coils units has been designed for conditioning rooms that require the installation of ducted units. Proposed in 12 models with air flows from 600 to 3000 m3/h, the UTN units are characterized by a wide applicative flexibility thanks to the special constructive solutions. > possibility of installation both in horizontal and vertical position thanks
to the special conformation of the condensate discharge system; > the air intake direction may be modified during installation; > reduced height (280 mm up to model 16A); > pre-shared element for the recycle of external air, standard on all models
(Φ 100 mm); > wide range of accessories for effectively.
2 VERSIONS AND COMPONENTS
Versions UTN air handling unit setup for 2-pipe systems UTNDF air handli ng unit set up for 4-pipe systems (2 heat
exchangers)
N.B. both version may be manufactured, on request, with pre-painted
panels. Components > Load-bearing structure made of galvanized steel sheet of suitable
thickness, duly insulated with noise-proof/anticondensing material, self-estinguishing in Class 1; the insulating material is characterized by a thickness of 10 mm and a density of 90 Kg/m3. The unit is completed by the following:
- inspections panels;
- setup for external air intake;
- fast-coupling slots.
> Dual intake centrifugal fans made of alluminium, with statically and
dinamically balanced impellers, coupled directly to the electric motor.
> 3 speed electric motor, equipped with permanently fit condenser and
thermal safety device, installed on vibrator damping supports.
> Heat exchanger: high efficiency, made of copper tube and alluminium
fins secured to the tubes by mechanical expansion. It is fitted with brass manifolds and air valves. The heat exchanger, normally supplied with left hand attachments, may be turned by 180°.
> System for collecting and discharging condensate setup either for
horizontal or vertical installation.
> Terminal strip for fast - on electrical connections.
The technical and dimensional data indicated in this catalougue are subject to modifications in the view of the improvement of the product.
UT66000806 - 02
All copying, even partial, of this manual is strictly forbidden
2
UTN
3 POSSIBLE CONFIGURATIONS
VERTICAL INSTALLATION
AA
Heating and cooling operation
HORIZONTAL INSTALLATION
AA
AB
Heating and cooling operation
Example of installation UTN - Air distribution with circular flexible ducts
GA
GAT
PCOF TFA
MAF
MAFO
MAF
MAFO
UTN
UTN
CA
CAF TFM
Example of installation UTN - Air distribution with rectangular ducts
PCOC
G90
GR
AB
PCOF
GA
GAT
PCOC
4 AVAILABLE OPTIONS
The wide and complete range of accessories completes the UTN air handling units as far as operation is concerned, adapting these units to any plant­engineering requirements, from the solution with rectangular section channels to the one with round flexible ducts. The standard machines are supplied without control panel and without air
filter.
CONTROL PANELS AND THERMOSTATS
CD Flush wall-mounted speed selector CDE Wall-mounted speed selector TD Wall-mounted control with speed selector, electromechanical
thermostat and summer/winter selector
TDC Wall-mounted control with speed selector and
electromechanical thermostat
TD4T Wall-mounted control with speed selector,
electromechanical thermostat and summer winter selector for 2/4 pipe systems with valves
MICRONET Microprocessor control ERGO solution MICROD Microprocessor wall-mounted control for the automatic
control of the fan-coil
MICROPROD Microprocessor wall-mounted control for the automatic
control of the fan-coil, valves and electric heater
SW Water temperature electronic probe for MICROD and
MICROPROD
TC Fan stop thermostat: electromechanical thermostat for
minimum water temperature during heating mode
IPM Power interface for MICROD and MICROPROD TA Electromechanical room thermostat TA2 Electromechanical room thermostat with summer/winter
selection
CSD Wall-mounted control for proportional opening and
closing of the motor driven air intake louver
AIR SUCTION MODULES WITH FILTERS
MAF Air suction module with flat filter G2 MAFO Air suction module with waved filter G4
CONNECTION PANELS
PCOC Connecting panel to rectangular ducts PCOF Connecting panel to flexible ducts φ 200
3-WAY VALVES AND DRIP TRAYS
V 3 way valve (possibility of motor driven) M Electrothermal motor for motor driven valve R Hydraulic connection mounting kit VRCV Auxiliary drip tray for ver tical installation units VRCH Auxiliary drip tray for horizontal installation units KSC Condensate removal kit
HOT WATER POST HEATING COIL
BP Hot water post heating coil module
ELECTRIC HEATERS
RE Electric heater, with safety thermostat and power relay
MOTOR DRIVEN FRESH AIR INTAKE LOUVER
PA90 Motor driven fresh air intake louver
VIBRATION DAMPERS
CM
GM
GA PVC vibration damper GAT Silicone cloth heat proof vibration dampers
FLEXIBLE DUCTS - CAPS
TFA Not insulated flexible ducts, φ 200 TFM Insulated flexible ducts, φ 200 TP Plastic caps φ 200
AIR INLET AND OUTLET PLENUM BOX
CA Air inlet plenum box with double row grille CAF Air inlet plenum box with double row grille and filter G2 CM Insulated air outlet plenum box with 2 way grille
AIR INLET AND OUTLET GRILLES
GM Aluminium air outlet grille with counterframe GR Air suction aluminium grille with counter frame
All copying, even partial, of this manual is strictly forbidden
3
UT66000806 - 02
UTN
5 RATED TECHNICAL DATA
UTN
Air flow High
Availa ble stati c pressure Hi gh Pa 80 75 90 85 88 82 100 95 130 110 185 175
Tota l cooling capacity kW 2,80 3,20 3,90 4,80 6,20 7,00 7,80 8,82 11,90 13,70 16,40 18,30
Sensibl e cooling capaci ty kW 2,15 2,46 3,08 3,71 4,65 5,36 6,52 7,16 9,36 10,50 12,80 14,10
Water flow l/ h 484 553 674 829 1071 1209 1339 1514 2056 2367 2833 3140
Water pressure drop kPa10 8 17152420241626223445
He ating capacity Hi gh k W 7,20 8,30 10,10 12,10 16,10 18,50 19,60 22,40 30,00 33,70 40,90 45,00
Water flow l/ h 634 731 890 1066 1418 1630 1726 1974 2642 2970 3603 3695
Water pressure drop kPa121020172926281930243850
DF heating cap acity (4 pipe s) Hi gh k W 4,01 4,01 5,63 5,63 8,24 8,24 11,50 11,50 19,70 19,70 26,20 26,20
Water flow l/ h 353 353 496 496 726 726 1013 1013 1735 1735 2309 2309
Water pressure drop kPa101013132121191917172222
Standard heat exchanger - rows n°343434343445
Sta nda rd heat exchanger - hy drau li c co nnecti ons in 3/ 4" 3/ 4" 3/4" 3/ 4" 3/4" 3/4" 3/ 4" 3/4" 1" 1" 1" 1"
Sta nda rd heat exchanger - water conte nt l 1,06 1,41 1,06 1,41 1,42 1,90 1,79 2,38 2,50 3,34 4,02 5,03
DF heat exchanger - rows n°111111112222
DF heat exchanger - hydraulic connection in 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 1" 1" 1" 1"
DF heat exc hanger - wate r content l 0,35 0,35 0,47 0,47 0,59 0,59 1,42 1,42 1,42 1,42 1,72 1,72
Powe r supply V/ph/Hz
Ma ximum current abs orpti on A 0,718 0,718 0,954 0,954 1,575 1,575 1,971 1,971 3,210 3,210 5,370 5,370
Ma ximum power i nput W 175 175 234 234 349 349 443 443 714 714 1197 1197
Sound pow er dB(A) 63 63 66 66 69 69 72 72 74 74 78 78
Sound pow er - air outlet component dB( A) 59,3 59,3 62,5 62,5 65,2 65,2 68,9 68,9 70,7 70,7 74,5 74,5
Sound pow er - transm itted compon ent dB(A) 54,7 54,7 58,0 58,0 60,3 60,3 64,0 64,0 65,7 65,7 69,4 69,4
Sound pow er - air inlet component dB(A) 59,3 59,3 62,5 62,5 65,2 65,2 68,9 68,9 70,7 70,7 74,5 74,5
Weight 2 pi pe m odel s (UTN) Kg 31,5 32,5 32,5 33,3 40,6 41,7 47,3 48,7 65,3 67,2 77,0 79,5
Weight 4 pi pe m odel s (UTN DF) Kg 33,7 34,7 34,7 35,5 43,2 44,3 50,3 51,7 70,9 72,8 83,4 85,9
Fan speed 6 06A 8 08A 12 12A 16 16A 22 22A 30 30A
3
m
/h
600 600 800 800 1250 1250 1600 1600 2200 2200 3000 3000
230 / 1 / 50
The aforesaid performance is related to the following conditions.
Air flow:
- related to the rated usable static pressure, at max. speed
Cooling:
- rated air flow
- water inlet temperature 7°C
- water outlet temperature 12°C
- air temperature with dry bulb 27°C
- air temperature with moist bulb 19°C (47% relative humidity)
Heating:
- rated air flow
- water inlet temperature 80°C
- water outlet temperature 70°C
- air temperature 20°C Sound power read conforming to EN 23741 and EN 23742.
UT66000806 - 02
All copying, even partial, of this manual is strictly forbidden
4
UTN
6 VENTILATION FEATURES
Legend: Psu Available static pressure Qa Air flow
-------
-------
-------
282------
150 160 170 180 200 220 240
-------
261------
581------
-------
369 519 411 - - - -
-------
570500-----
338------
Vr Fan speed:
-------
-------
438------
332------
-------
413------
3= high 2= medium 1= low
-------
942698-----
515------
-------
921694-----
490------
527------
1918 854 1516 1152 - - -
1075------
1670 1475 1200 - - - -
1003 782 - - - - -
498------
3112 3081 3050 3018 2952 2883 2813
2428 2394 2358 2322 2246 2167 2081
1808 1774 1739 1702 1625 1541 1447
3079 3048 3016 2983 2917 2848 2777
2389 2355 2319 2283 2207 2127 2042
1784 1749 1713 1675 1596 1508 1411
Psu [Pa]
/h 782 762 742 721 699 676 652 627 600 571 540 506 467 422 367
3
3m
Vr Qa 0 102030405060708090100110120130140
/h 592 573 554 534 512 490 467 442 415 385 353 316 271 213 -
/h 426 405 382 359 335 309 282 253 222 189 152 110 - - -
3
/h 768 749 728 708 686 663 639 614 587 558 527 492 454 408 352
3
3
2m
1m
3m
UTN 06
/h 583 564 545 525 504 482 459 434 407 378 346 309 265 206 -
/h 422 401 378 355 331 305 279 250 219 186 150 109 - - -
3
/h 1002 982 963 942 921 899 876 851 826 799 771 740 707 671 629
3
3
2m
1m
3m
UTN 06A
/h 850 831 811 791 769 747 724 699 673 645 615 582 545 502 448
/h 597 583 569 553 537 520 502 483 462 439 413 383 345 - -
/h 981 963 944 924 904 883 861 838 813 787 760 730 698 661 620
3
3
3
2m
1m
3m
UTN 08
/h 836 818 798 779 758 736 714 689 664 637 607 574 537 493 437
/h 596 582 568 552 536 519 501 482 461 438 412 381 343 - -
/h 1840 1783 1725 1664 1601 1535 1466 1393 1316 1233 1144 1046 937 812 658
/h 1537 1491 1444 1395 1343 1290 1233 1174 1110 1043 969 888 797 690 555
/h 1284 1246 1207 1166 1124 1080 1033 983 931 874 812 744 666 573 450
/h 1787 1731 1673 1613 1551 1486 1417 1346 1269 1188 1100 1004 897 774 623
/h 1505 1459 1412 1362 1311 1257 1200 1141 1077 1009 935 853 761 653 515
/h 1259 1222 1183 1143 1101 1057 1011 962 910 854 793 725 647 555 431
/h 2359 2296 2231 2164 2094 2021 1946 1866 1782 1693 1599 1496 1385 1260 1116
/h 1834 1782 1728 1672 1614 1553 1489 1422 1351 1274 1191 1101 999 881 734
/h 1495 1451 1405 1358 1308 1256 1201 1143 1081 1015 942 862 770 661 515
3
3
3
2m
1m
3m
UTN 08A
3
3
3
2m
1m
3m
UTN 12
3
3
3
2m
1m
3m
UTN 12A
3
/h 2304 2242 2178 2112 2043 1972 1897 1819 1737 1650 1557 1457 1348 1227 1088
3
3
2m
1m
3m
UTN 16
3
5
All copying, even partial, of this manual is strictly forbidden
/h 1819 1767 1713 1657 1599 1538 1474 1407 1335 1259 1176 1085 982 863 715
/h 1487 1443 1397 1349 1299 1247 1192 1134 1072 1006 933 852 760 650 503
/h 3369 3299 3227 3153 3077 2998 2915 2830 2740 2646 2547 2441 2328 2206 2070
3
3
2m
1m
3m
UTN 16A
/h 2425 2365 2302 2237 2170 2101 2028 1952 1872 1787 1696 1599 1492 1374 1238
/h 1747 1696 1645 1591 1535 1476 1415 1350 1282 1209 1130 1044 949 840 708
/h 3114 3047 2977 2905 2831 2753 2673 2589 2501 2408 2310 2205 2092 1967 1829
3
3
3
2m
1m
3m
UTN 22
/h 2317 2258 2198 2135 2070 2002 1932 1858 1780 1698 1610 1515 1411 1296 1164
/h 1695 1646 1595 1542 1487 1430 1370 1307 1240 1168 1091 1007 913 806 676
3
/h 3532 3506 3480 3454 3427 3400 3373 3346 3318 3290 3261 3232 3203 3173 3143
3
3
2m
1m
3m
UTN 22A
/h 2876 2849 2822 2795 2767 2739 2710 2681 2651 2621 2591 2559 2528 2495 2462
/h 2232 2207 2182 2157 2131 2105 2078 2051 2023 1994 1965 1935 1905 1874 1841
3
/h 3500 3474 3448 3422 3395 3368 3341 3313 3285 3257 3228 3199 3170 3140 3110
3
3
2m
1m
3m
UTN 30
UT66000806 - 02
/h 2837 2810 2783 2756 2728 2700 2671 2642 2613 2582 2552 2521 2489 2456 2423
/h 2217 2192 2167 2141 2115 2088 2060 2033 2004 1975 1945 1915 1883 1851 1818
3
3
2m
1m
UTN 30A
UTN
6 VENTILATION FEATURES
Legend: Psu Available static pressure Qa Air flow
-------
-------
-------
276------
150 160 170 180 200 220 240
-------
255------
571 508 388 - - - -
-------
360------
-------
559487-----
323------
419------
Vr Fan speed:
-------
-------
-------
-------
397------
906665-----
3= high 2= medium 1= low
-------
496------
-------
888664-----
471------
1855 1676 1448 1055 - - -
518------
981759-----
1050 828 - - - - -
490------
1617 1421 1138 - - - -
3091 3060 3028 2996 2931 2862 2792
2413 2378 2343 2307 2231 2152 2066
1799 1765 1730 1694 1616 1532 1438
3058 3026 2995 2962 2896 2828 2756
2375 2340 2305 2268 2193 2113 2027
1775 1740 1704 1667 1587 1500 1402
3
Vr Qa 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140
Psu [Pa]
UT66000806 - 02
776 756 736 715 693 670 646 621 594 566 534 500 462 417 361
/h m
3
588 570 550 530 509 487 464 439 412 383 350 313 269 210 -
/h
3
3
m
2
UTN 06DF
424 403 380 357 333 307 280 252 221 188 151 110 - - -
762 743 723 702 680 657 633 608 581 553 521 487 449 403 347
579 561 542 522 501 479 456 431 404 375 343 306 262 204 -
420 399 376 353 329 304 277 249 218 185 149 108 - - -
992 973 953 932 911 889 866 842 817 790 761 731 698 661 620
843 824 804 784 762 740 717 692 666 638 608 575 538 495 441
595 581 566 551 535 518 500 480 459 436 410 380 342 - -
973 954 935 916 895 874 852 829 804 779 751 721 688 652 610
829 811 792 772 751 730 707 683 657 630 600 567 530 486 430
594 579 565 550 533 516 498 479 458 435 409 378 340 - -
1790 1734 1677 1618 1556 1491 1423 1352 1277 1196 1109 1013 907 784 633
1507 1462 1415 1367 1316 1263 1208 1149 1087 1020 947 867 777 672 538
1266 1229 1190 1150 1108 1064 1017 968 916 860 799 731 654 561 439
1740 1685 1629 1570 1509 1445 1378 1308 1233 1153 1068 974 869 748 602
1477 1431 1384 1336 1285 1232 1176 1117 1054 987 914 834 743 636 500
1242 1205 1167 1127 1086 1042 996 948 896 840 780 712 636 544 421
2301 2239 2175 2108 2040 1968 1894 1815 1733 1646 1553 1452 1342 1219 1078
1803 1751 1698 1643 1585 1525 1462 1395 1325 1249 1167 1078 977 860 714
1477 1433 1388 1340 1291 1239 1185 1127 1066 1000 928 849 758 649 504
2248 2187 2124 2059 1992 1922 1848 1772 1691 1605 1514 1416 1309 1189 1053
1789 1737 1684 1628 1571 1511 1447 1381 1310 1234 1152 1062 961 843 696
1469 1425 1379 1332 1282 1231 1176 1119 1057 991 919 839 748 639 492
3294 3225 3154 3081 3005 2927 2845 2760 2672 2578 2480 2375 2263 2141 2006
2389 2329 2267 2203 2137 2067 1995 1920 1840 1756 1666 1570 1464 1347 1212
1730 1680 1628 1575 1519 1461 1400 1336 1268 1196 1118 1032 937 829 698
3051 2984 2915 2844 2770 2694 2614 2531 2444 2352 2254 2150 2037 1914 1776
2284 2226 2166 2104 2040 1973 1903 1830 1753 1671 1584 1490 1387 1272 1140
1679 1631 1580 1528 1473 1416 1356 1294 1227 1156 1080 996 903 796 667
3509 3484 3458 3432 3405 3378 3351 3324 3296 3268 3239 3210 3181 3152 3121
2860 2833 2806 2779 2751 2723 2694 2665 2636 2606 2575 2544 2512 2480 2447
2222 2198 2173 2148 2122 2096 2069 2042 2014 1985 1956 1926 1896 1865 1833
3478 3452 3426 3400 3373 3346 3319 3292 3264 3236 3207 3178 3148 3119 3088
2821 2795 2768 2741 2713 2685 2656 2627 2597 2567 2537 2506 2474 2441 2408
2208 2183 2157 2132 2105 2079 2051 2023 1995 1966 1936 1906 1874 1842 1809
/h
/h
/h
/h
/h
/h
/h
/h
/h
/h
/h
/h
/h
/h
/h
/h
/h
/h
/h
/h
/h
/h
/h
/h
/h
/h
/h
/h
/h
/h
/h
/h
/h
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
1
3
2
1
3
2
1
3
2
1
3
2
1
3
2
1
3
2
1
3
2
1
3
2
1
3
2
1
UTN 06ADF
UTN 08DF
UTN 08ADF
UTN 12DF
UTN 12ADF
UTN 16DF
UTN 16ADF
UTN 22DF
UTN 22ADF
m
3
3
m
m
2
1
UTN 30DF
/h
3
3
3
m
m
m
3
2
1
UTN 30ADF
6
All copying, even partial, of this manual is strictly forbidden
UTN
6 VENTILATION FEATURES
6.1 ACCESSORIES: AIR PRESSURE DROP
Legend: Qa Air flow DPa Air pressure drop
Qa [m3/h] 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050
MAF Pa234568101214151720- - -----
MAFO Pa245679121416182023- - -----
PCOF A* Pa112345781012141619- -----
PCOF M** Pa- 11233456891012- -----
RE Pa- 111223556789------
UTN 06 - 06A
GR Pa- 122345689111214- -----
GM Pa-----11111222------
Qa [m
MAF Pa67910111315171922242628------
MAFO Pa781011131518202225283032------
PCOF A* Pa34578101214161921242730-----
PCOF M** Pa23345689101214151719-----
RE Pa233345678911121214-----
UTN 08 - 08AUTN 12 - 12A
GR Pa234568911121416182023-----
GM Pa- - 111112223344-----
Qa [m
MAF Pa5810131618212529323640-------
MAFO Pa6912151821252933374246-------
PCOF A* Pa245791215182125293338- -----
PCOF M** Pa12356810121416192124- -----
RE Pa1335679111315172022- -----
GR Pa245791214172124283237- -----
GM Pa- - 11122344567------
Qa [m
MAF Pa468911131618202326323844-----
MAFO Pa5791113151821232730374451-----
PCOF A* Pa123457810121416212733-----
PCOF M** Pa112334568910141721-----
RE Pa1233456781012151923-----
UTN 16 - 16AUTN 22 - 22AUTN 30 - 30A
GR Pa123567911131618243037-----
GM Pa---11112233467-----
Qa [m
MAF Pa45678101213151721252933384348- -
MAFO Pa467810121415182024293438445055- -
PCOF A* Pa12345781012141621273340485665-
PCOF M** Pa11233456891014172126313642-
RE Pa1222244567911131519222529-
GR Pa123345689101317212530364148­GM Pa----11111223456789-
Qa [m
MAF Pa--13141618182226293336404549----
MAFO Pa--151718202125303338424652-----
PCOF A* Pa8910121415172126313642485461----
PCOF M** Pa5678910111417202327313540----
RE Pa- - 55677911131517202326----
GR Pa5678911121518212529333843----
GM Pa111112223445678----
Pa
'
3
/h] 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150 1200
Pa
'
3
/h] 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 19 00 2000 2100 2200
Pa
'
3
/h] 400 500 600 700 800 900 1000 1100 1200 1300 1400 1600 1800 2000 2200 24 00 2600 2800 3000
Pa
'
3
/h] 500 600 700 800 900 1000 1100 1200 1300 1400 1600 1800 2000 2200 2400 2600 2800 3000 3200
Pa
'
3
/h] 1200 1300 1400 1500 1600 1700 1800 2000 2200 2400 2600 2800 3000 3200 3400 3600 3800 4000 4200
Pa
'
* Inlet connecting panel to rectangular ducts ** Outlet connecting panel to rectangular ducts
All copying, even partial, of this manual is strictly forbidden
7
UT66000806 - 02
UTN
6 VENTILATION FEATURES
6.1 ACCESSORIES: AIR PRESSURE DROP
The pressure drops shown below refer to accessories that are not affected by the various sizes of the thermal ventilating units. Pressure drops refer to the accessory itself and are not related to the size of the thermal ventilating units.
Qa[m3/h]
UTN
TFA - TFMPa112346791113151720232629323539
CAF2Pa48121722293644536272--------
CAF3 Pa2 4 5 8 101317202429333944505662697683
CM1Pa1324375373--------------
CM2 Pa11235679111316- - ------
CM3 Pa- -111122334556778910
'Pa300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100
CA2Pa135811152025313744--------
CA3 Pa- -1235791215192327313641475259
6.2 SOUND POWER LEVELS FOR OCTAVE BAND
Legend: Psu Available static pressure L
A-weighted sound power
WA
Vr Fan speed:
3= high 2= medium 1= low
Legend:
Qa Air flow Pa Air pressure drop
UTN 06 - 06A
UTN 08 - 08A
UTN 12 - 12A
UTN 16 - 16A
UTN 22 - 22A
UTN 30 - 30A
Lw
125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz LwA
Vr dB dB dB dB dB dB dB dB/A
max 40,6 53,6 56,0 58,9 56,7 50,9 42,1 63,0
med 36,5 49,2 51,2 52,0 48,2 44,9 36,5 57,0
min 29,5 42,9 40,9 43,3 39,3 33,9 24,9 48,0
max 43,6 47,0 60,0 62,0 60,7 54,8 46,2 66,0
med 40,7 53,8 53,8 57,0 53,6 50,6 43,3 61,0
min 33,8 47,7 47,0 49,8 47,0 41,9 33,5 54,0
max 45,0 56,9 60,8 64,7 63,5 57,7 49,7 69,0
med 41,5 52,6 56,9 59,0 54,7 50,9 40,5 63,0
min 37,0 48,8 53,0 54,4 50,0 48,6 33,5 59,0
max 50,7 62,1 64,8 68,1 66,5 62,5 56,2 72,0
med 45,0 57,5 60,1 62,5 58,9 56,4 49,2 67,0
min 40,5 53,4 55,9 57,5 54,3 50,3 42,4 62,0
max 52,0 62,5 65,2 70,0 69,2 64,5 58,2 74,0
med 46,2 57,7 59,9 62,8 60,5 57,1 50,0 67,0
min 39,3 50,6 54,2 55,9 53,1 47,8 41,5 60,0
max 61,0 70,5 70,0 72,5 71,1 69,6 63,8 78,0
med 58,3 65,1 67,1 67,9 65,8 64,2 56,7 73,0
min 52,1 61,3 62,3 63,8 62,6 60,7 49,1 69,0
UT66000806 - 02
All copying, even partial, of this manual is strictly forbidden
8
UTN
7 PERFORMANCES
7.1 COOLING CAPACITY
Legend: Tbs1Inlet air temperature D.B. Tbu1Inlet air temperature W.B. Tw1Inlet water temperature Tw2Outlet water temperature Qa Air flow
PFT Total cooling capacity
PFS Sensible cooling capacity
Qw Water flow rate
DPw Pressure drop on water side
Tbs1 / Tbu1 (UR1) °C
Tw
/ Tw2 °C
1
UTN 06
UTN 06A
UTN 08
UTN 08A
UTN 12
UTN12A
UTN 16
UTN 16A
UTN 22
UTN 22A
UTN 30
UTN 30A
25 /18 (5 1%)
6/11 7/12 8/13 9/14
Pw
PFT PFS Qw
Qa PFT PFS Qw
3
m
/h
W W l/s kPa W W l/s k Pa W W l/s kPa W W l/s kPa
300 1680 1260 0,080 4 1450 11 60 0,069 3 129 0 1100 0,061 2 1120 1040 0,053 2
450 2390 1790 0,114 7 2040 16 50 0,097 5 163 0 1500 0,078 4 1430 1430 0,068 3
600 3010 2270 0,143 11 2 590 2110 0,123 8 2 110 1930 0,101 6 1800 180 0 0 ,086 4
300 1970 1410 0,094 3 1780 13 40 0,085 3 158 0 1260 0,076 2 1380 1180 0,066 2
450 2820 2060 0,134 6 2410 18 90 0,115 4 194 0 1710 0,093 3 1730 1730 0,082 2
600 3630 2680 0,173 9 3130 24 70 0,149 7 256 0 2250 0,122 5 2140 2140 0,102 4
400 2170 1620 0,103 6 1840 14 90 0,088 5 146 0 1350 0,070 3 1330 1330 0,063 3
600 3010 2270 0,143 11 2 590 2110 0,123 8 2 110 1930 0,101 6 1800 180 0 0 ,086 4
800 3740 2860 0,178 16 3 220 2660 0,154 12 2660 2450 0,12 7 9 22 40 2240 0 ,107 6
400 2530 1840 0,120 5 2140 16 80 0,102 4 184 0 1560 0,088 3 1600 1470 0,076 2
600 3630 2680 0,173 9 3130 24 70 0,149 7 256 0 2250 0,122 5 2140 2140 0,102 4
800 4600 3460 0,219 14 3 990 3210 0,190 11 3300 2940 0,15 8 8 27 40 2740 0 ,131 5
800 4220 3070 0,201 12 3 630 2840 0,173 9 2 960 2580 0,141 6 2490 249 0 0 ,119 5
1000 5030 3660 0,2 69 17 4340 3390 0,207 13 3580 3 100 0,171 9 29 90 2990 0 ,142 7
1200 5770 4200 0,2 75 21 4990 3900 0,238 16 4140 3 580 0,197 12 3440 3440 0 ,164 8
800 4700 3430 0,224 10 4 050 3170 0,193 8 3 320 2880 0,158 6 2730 273 0 0 ,130 4
1000 5640 4150 0,2 69 14 4890 3850 0,233 11 4060 3 530 0,194 8 33 00 3300 0 ,158 5
1200 6510 4830 0,3 10 18 5660 4490 0,270 14 4730 4 140 0,226 10 3830 3830 0 ,183 7
1200 6020 4740 0,2 87 15 5180 4410 0,247 12 3870 3 870 0,185 7 35 50 3550 0 ,169 6
1400 6770 5400 0,3 23 19 5840 5040 0,279 14 4370 4 370 0,208 9 40 10 4010 0 ,191 7
1600 7470 6040 0,3 56 22 6470 5650 0,308 17 4830 4 830 0,230 10 4440 4440 0 ,212 9
1200 6650 5130 0,3 17 10 5640 4720 0,269 7 4260 4260 0,203 4 3870 3870 0,185 4
1400 7570 5900 0,3 61 12 6470 5460 0,308 9 4870 4870 0,232 6 4450 4450 0,212 5
1600 8440 6640 0,4 02 15 7240 6170 0,345 11 5450 5 450 0,260 7 49 90 4990 0 ,238 6
1600 8930 6680 0,4 25 16 7730 6200 0,369 12 6380 5 680 0,305 9 52 50 5250 0 ,251 6
1900 10220 7720 0 ,487 20 8860 71 80 0,422 16 7 370 6610 0,352 1 1 6030 603 0 0 ,288 8
2200 11420 8710 0 ,544 24 9920 81 20 0,473 19 8 280 7490 0,395 1 4 6760 676 0 0 ,322 10
1600 10070 7360 0 ,480 13 8740 68 10 0,417 10 7 230 6210 0,345 7 5840 5840 0,279 5
1900 11660 8600 0 ,555 17 10150 7980 0,484 13 8470 7320 0,404 9 6800 680 0 0 ,324 6
2200 13150 9800 0 ,627 21 11480 9110 0,547 16 9630 8390 0,459 12 7700 770 0 0 ,367 8
2000 11600 8520 0 ,552 18 10180 7950 0,485 15 8640 7340 0,412 11 6670 667 0 0 ,318 7
2500 1 3770 10270 0,656 25 12120 9610 0,577 20 10330 8910 0, 493 15 7970 797 0 0 ,380 9
3000 1 5780 11930 0,752 32 13890 11180 0,662 25 11 870 10410 0,56 6 19 9150 9150 0 ,437 12
2000 12920 9310 0 ,616 25 11510 8720 0,549 20 9990 8110 0,476 15 8300 745 0 0 ,396 11
2500 1 5380 11280 0,732 33 13700 10600 0,653 27 11 900 9880 0,56 8 21 9940 9120 0 ,474 15
3000 1 7650 13180 0,841 42 15720 12400 0,750 34 13670 11590 0,652 2 7 1144 0 10740 0,546 20
'
Pw
'
PFT PFS Qw
Pw
'
PFT PFS Qw
'
Pw
All copying, even partial, of this manual is strictly forbidden
9
UT66000806 - 02
UTN
7 PERFORMANCES
7.1 COOLING CAPACITY
Legend: Tbs1Inlet air temperature D.B. Tbu1Inlet air temperature W.B. Tw1Inlet water temperature Tw2Outlet water temperature Qa Air flow
PFT Total cooling capacity PFS Sensible cooling capacity Qw Water flow rate DPw Pressure drop on water side
Tbs1 / Tbu1 (UR1) °C
Tw
/ Tw2 °C
1
UTN 06
UTN 06A
UTN 08
UTN 08A
UTN 12
UTN 12A
UTN 16
UTN 16A
UTN 22
UTN 22A
UTN 30
UTN 30A
27 /19 (4 7%)
6/11 7/12 8/13 9/14
Pw
Qa PFT PFS Qw
3
m
/h
W W l/s kPa W W l/s k Pa W W l/s kPa W W l/s kPa
300 2030 1460 0,097 5 1780 13 60 0,085 4 150 0 1250 0,072 3 1320 1180 0,063 2
450 2840 2060 0,135 10 2 520 1930 0,120 8 2 160 1800 0,103 6 1760 165 0 0 ,084 4
600 3560 2600 0,169 14 3 150 2450 0,150 12 2720 2290 0,13 0 9 22 50 2110 0 ,107 6
300 2300 1620 0,110 4 2020 15 00 0,096 3 182 0 1420 0,087 3 1620 1340 0,077 2
450 3340 2370 0,159 8 2960 22 10 0,141 6 255 0 2050 0,122 5 2060 1860 0,098 3
600 4270 3070 0,203 12 3 800 2870 0,181 10 3290 2670 0,15 7 8 27 30 2460 0 ,130 5
400 2580 1870 0,123 8 2280 17 50 0,109 7 195 0 1620 0,093 5 1570 1480 0,075 3
600 3560 2600 0,169 14 3 150 2450 0,150 12 2720 2290 0,13 0 9 22 50 2110 0 ,107 6
800 4400 3270 0,210 21 3 910 3080 0,186 17 3390 2890 0,16 2 13 2660 2660 0 ,127 9
400 3010 2120 0,143 6 2660 19 80 0,127 5 228 0 1830 0,109 4 1880 1670 0,090 3
600 4270 3070 0,203 12 3 800 2870 0,181 10 3290 2670 0,15 7 8 27 30 2460 0 ,130 5
800 5400 3950 0,257 18 4 810 3710 0,230 15 4190 3460 0,20 0 11 3500 3210 0 ,167 8
800 4990 3520 0,238 16 4 430 3300 0,211 13 3830 3070 0,18 3 10 3160 2820 0 ,151 7
1000 5920 4180 0,2 82 22 5270 3930 0,251 18 4570 3 660 0,218 14 3800 3380 0 ,181 10
1200 6780 4800 0,3 23 28 6040 4510 0,288 23 5240 4 210 0,250 18 4380 3900 0 ,209 13
800 5520 3920 0,263 14 4 920 3680 0,235 11 4270 3430 0,20 4 9 35 40 3150 0 ,169 6
1000 6600 4740 0,3 15 19 5900 4450 0,281 15 5140 4 160 0,245 12 4300 3850 0 ,205 9
1200 7610 5500 0,3 63 24 6800 5180 0,324 19 5940 4 850 0,283 15 5000 4500 0 ,238 11
1200 7100 5420 0,3 38 20 6310 5110 0,301 17 5460 4 790 0,260 13 4230 4230 0 ,202 8
1400 7970 6160 0,3 80 25 7090 5820 0,338 20 6150 5 470 0,293 16 4760 4760 0 ,227 10
1600 8790 6890 0,4 19 30 7820 6520 0,373 24 6800 6 130 0,324 19 5260 5260 0 ,251 12
1200 7910 5890 0,3 77 13 6990 5530 0,333 11 5990 5 140 0,285 8 46 90 4690 0 ,224 5
1400 8960 6760 0,4 27 17 7950 6360 0,379 13 6840 5 930 0,326 10 5340 5340 0 ,255 7
1600 9970 7600 0,4 75 20 8850 7160 0,422 16 7640 6 700 0,364 12 5950 5950 0 ,284 8
1600 10490 7630 0 ,500 21 9350 71 70 0,446 17 8 130 6700 0,388 1 3 6780 619 0 0 ,324 10
1900 11970 8800 0 ,571 26 10690 8290 0,509 22 9310 7760 0,444 17 7800 720 0 0 ,372 12
2200 13370 9920 0 ,637 32 11940 9360 0,569 26 10410 8780 0, 496 20 8740 8170 0,417 15
1600 11780 8390 0 ,561 17 10540 7880 0,503 14 9200 7340 0,438 11 7690 676 0 0 ,367 8
1900 13600 9790 0 ,648 22 12180 9210 0,581 18 10650 8600 0, 508 14 8970 7960 0,428 10
2200 1 5330 11150 0,731 27 13740 10500 0,655 22 12 030 9830 0,57 4 17 10160 9120 0 ,485 13
2000 13450 9670 0 ,641 24 12100 9130 0,577 20 10660 8560 0, 508 16 9100 7970 0,434 12
2500 1 5950 11640 0,760 32 14360 11010 0,685 27 12 670 10360 0,60 5 21 10850 9670 0 ,518 16
3000 1 8260 13510 0,871 41 16450 12800 0,784 34 14520 12060 0,692 2 7 1245 0 11290 0,594 21
2000 1 4790 10490 0,705 31 13430 9930 0,640 26 11990 9350 0, 572 21 10440 8740 0,498 17
2500 1 7610 12710 0,839 42 15990 12050 0,762 35 14270 11370 0,680 2 9 1243 0 10660 0,593 23
3000 2 0150 14820 0,960 53 18350 14100 0,875 45 16370 13320 0,781 3 7 1427 0 12520 0,681 29
'
PFT PFS Qw
Pw
'
PFT PFS Qw
Pw
'
PFT PFS Qw
'
Pw
UT66000806 - 02
All copying, even partial, of this manual is strictly forbidden
10
UTN
7 PERFORMANCES
7.2 HEATING CAPACITY
Legend: Tbs1Inlet air temperature D.B. Tw1Inlet water temperature Tw2Outlet water temperature Qa Air flow
Tbs
/ Tbu1 (UR1) °C
1
Tw
/ Tw2 °C
1
Qa PT Qw
3
m
/h
300 2410 0,116 6 3060 0,074 3 3970 0,097 4 5330 0,065 2
UTN 06
UTN 06A
UTN 08
UTN 08A
UTN 12
UTN 12A
UTN 16
UTN 16A
UTN 22
UTN 22A
UTN 30
UTN 30A
450 3290 0,159 10 4180 0,101 5 5430 0,132 7 7260 0,089 3
600 4070 0,197 15 5160 0,125 7 6700 0,163 10 8940 0,110 5
300 2690 0,130 4 3450 0,084 2 4450 0,108 3 6020 0,074 1
450 3790 0,184 8 4850 0,118 4 6270 0,153 5 8460 0,104 3
600 4790 0,232 12 6110 0,148 5 7900 0,192 8 10620 0,130 4
400 3010 0,146 9 3830 0,093 4 4970 0,121 6 6660 0,082 3
600 4070 0,197 15 5160 0,125 7 6700 0,163 10 8940 0,110 5
800 4990 0,242 22 6300 0,153 9 8200 0,200 15 10910 0,134 7
400 3440 0,166 7 4400 0,107 3 5690 0,139 5 7680 0,094 2
600 4790 0,232 12 6110 0,148 5 7900 0,192 8 10620 0,130 4
800 5980 0,290 18 7610 0,185 8 9860 0,240 12 13210 0,162 6
800 5760 0,279 18 7320 0,178 8 9490 0,231 12 12690 0,156 6
1000 6790 0,328 23 8600 0,209 10 11170 0,272 16 14900 0,183 7
1200 7730 0,374 29 9770 0,237 13 12710 0,310 20 16920 0,207 9
800 6480 0,314 15 8290 0,201 7 10690 0,261 10 14400 0,177 5
1000 7720 0,374 20 9850 0,239 9 12730 0,310 14 17100 0,210 7
1200 8880 0,430 26 11300 0,274 11 14630 0,356 17 19590 0,240 8
1200 7920 0,383 21 10030 0,244 9 13030 0,318 14 17370 0,213 7
1400 8830 0,428 25 11170 0,271 11 14520 0,354 17 19320 0,237 8
1600 9690 0,469 29 12220 0,297 13 15920 0,388 20 21150 0,259 9
1200 8940 0,433 14 11380 0,276 6 14730 0,359 9 19730 0,242 4
1400 10040 0,486 17 12740 0,309 7 16530 0,403 11 22090 0,271 5
1600 11080 0,536 20 14040 0,341 9 18230 0,444 13 24330 0,298 6
1600 11760 0,569 21 14960 0,363 9 19380 0,472 14 25930 0,318 7
1900 13350 0,646 27 16930 0,411 12 21970 0,536 18 29340 0,360 9
2200 14830 0,718 32 18770 0,455 14 24400 0,595 21 32520 0,399 10
1600 12980 0,628 17 16620 0,403 7 21420 0,522 11 28840 0,354 5
1900 14880 0,720 21 19000 0,461 9 24540 0,598 14 32970 0,404 7
2200 16680 0,807 26 21260 0,516 11 27500 0,670 18 36870 0,452 8
2000 15010 0,727 24 19180 0,466 11 24740 0,603 16 33240 0,407 8
2500 17750 0,859 32 22600 0,549 14 29220 0,712 22 39140 0,480 10
3000 20270 0,980 41 25760 0,625 18 33350 0,813 27 44570 0,546 13
2000 16300 0,788 31 20970 0,509 14 26890 0,655 21 36350 0,446 10
2500 19430 0,940 42 24930 0,605 19 32040 0,781 28 43180 0,529 14
3000 22340 1,081 53 28590 0,694 24 36810 0,897 36 49510 0,607 17
PT Heating capacity
Qw Water flow rate
DPw Pressure drop on water side
20
50 / 45 60 / 50 70 / 60 90 / 70
Pw
'
W l/s kPa W l/s kPa W l/s kPa W l/s k Pa
PT Qw
Pw
'
PT Qw
Pw
'
PT Qw
'
Pw
All copying, even partial, of this manual is strictly forbidden
11
UT66000806 - 02
UTN
7 PERFORMANCES
7.2 HEATING CAPACITY
Legend: Tbs1Inlet air temperature D.B. Tw1Inlet water temperature Tw2Outlet water temperature Qa Air flow
Tbs
/ Tbu1 (UR1) °C 22
1
Tw
/ Tw2 °C 50 / 45 60 / 50 70 / 60 90 / 70
1
Qa PT Qw
3
m
/h
300
UTN 06
UTN 06A
UTN 08
UTN 08A
UTN 12
UTN 12A
UTN 16
UTN 16A
UTN 22
UTN 22A
UTN 30
UTN 30A
450 3040 0,147 9 4180 0,101 5 5430 0,132 7 7260 0,089 3
600 3760 0,182 13 5160 0,125 7 6700 0,163 10 8940 0,110 5
300 2480 0,120 4 3450 0,084 2 4450 0,108 3 6020 0,074 1
450 3500 0,170 7 4850 0,118 4 6270 0,153 5 8460 0,104 3
600 4420 0,214 11 6110 0,148 5 7900 0,192 8 10620 0,130 4
400 2780 0,135 8 3830 0,093 4 4970 0,121 6 6660 0,082 3
600 3760 0,182 13 5160 0,125 7 6700 0,163 10 8940 0,110 5
800 4610 0,223 19 6300 0,153 9 8200 0,200 15 10910 0,134 7
400 3170 0,154 6 4400 0,107 3 5690 0,139 5 7680 0,094 2
600 4420 0,214 11 6110 0,148 5 7900 0,192 8 10620 0,130 4
800 5520 0,267 16 7610 0,185 8 9860 0,240 12 13210 0,162 6
800 5320 0,258 15 7320 0,178 8 9490 0,231 12 12690 0,156 6
1000 6270 0,303 20 8600 0,209 10 11170 0,272 16 14900 0,183 7
1200 7130 0,345 25 9770 0,237 13 12710 0,310 20 16920 0,207 9
800 5980 0,290 13 8290 0,201 7 10690 0,261 10 14400 0,177 5
1000 7130 0,345 18 9850 0,239 9 12730 0,310 14 17100 0,210 7
1200 8200 0,397 22 11300 0,274 11 14630 0,356 17 19590 0,240 8
1200 7310 0,354 18 10030 0,244 9 13030 0,318 14 17370 0,213 7
1400 8830 0,428 25 11170 0,271 11 14520 0,354 17 19320 0,237 8
1600 9690 0,469 29 12220 0,297 13 15920 0,388 20 21150 0,259 9
1200 8250 0,399 12 11380 0,276 6 14730 0,359 9 19730 0,242 4
1400 10040 0,486 17 12740 0,309 7 16530 0,403 11 22090 0,271 5
1600 11080 0,536 20 14040 0,341 9 18230 0,444 13 24330 0,298 6
1600 11760 0,569 21 14960 0,363 9 19380 0,472 14 25930 0,318 7
1900 13350 0,646 27 16930 0,411 12 21970 0,536 18 29340 0,360 9
2200 14830 0,718 32 18770 0,455 14 24400 0,595 21 32520 0,399 10
1600 12980 0,628 17 16620 0,403 7 21420 0,522 11 28840 0,354 5
1900 14880 0,720 21 19000 0,461 9 24540 0,598 14 32970 0,404 7
2200 16680 0,807 26 21260 0,516 11 27500 0,670 18 36870 0,452 8
2000 15010 0,727 24 19180 0,466 11 24740 0,603 16 33240 0,407 8
2500 17750 0,859 32 22600 0,549 14 29220 0,712 22 39140 0,480 10
3000 20270 0,980 41 25760 0,625 18 33350 0,813 27 44570 0,546 13
2000 16300 0,788 31 20970 0,509 14 26890 0,655 21 36350 0,446 10
2500 19430 0,940 42 24930 0,605 19 32040 0,781 28 43180 0,529 14
3000 22340 1,081 53 28590 0,694 24 36810 0,897 36 49510 0,607 17
PT Heating capacity Qw Water flow rate DPw Pressure drop on water side
Pw
'
W l/skPaW l/skPaW l/skPaW l/skPa
2220 0,107 5 3060 0,074 3 3970 0,097 4 5330 0,065 2
PT Qw
Pw
'
PT Qw
Pw
'
PT Qw
Pw
'
UT66000806 - 02
All copying, even partial, of this manual is strictly forbidden
12
UTN
7 PERFORMANCES
7.2 DF COIL HEATING CAPACITY
Legend: Tbs1Inlet air temperature D.B. Tw1Inlet water temperature Tw2Outlet water temperature Qa Air flow PT Heating capacity Qw Water flow rate DPw Pressure drop on water side
Tbs1 °C
/ Tw2 °C
Tw
1
UTN 06DF
UTN 08DF
UTN12DF
UTN 16DF
UTN 22DF
UTN 30DF
Tbs1 °C
/ Tw2 °C
Tw
1
UTN 06DF
UTN 08DF
UTN12DF
UTN 16DF
UTN 22DF
UTN 30DF
20
50 / 45
Pw
Qa PT Qw
3
/h
m
300 1660 0,080 6 2010 0,049 2 2730 0,066 4 3540 0,043 2
450 2070 0,100 8 2530 0,061 3 3400 0,083 5 4420 0,054 2
600 2390 0,116 11 2930 0,071 4 3920 0,096 7 5090 0,062 3
400 1950 0,094 7 2370 0,058 3 3190 0,078 5 4150 0,051 2
600 2390 0,116 11 2930 0,071 4 3920 0,096 7 5090 0,062 3
800 2740 0,133 13 3360 0,081 6 4490 0,110 9 5820 0,071 4
800 3280 0,158 16 4060 0,099 7 5370 0,131 10 7030 0,086 5
1000 3650 0,176 19 4510 0,109 8 5970 0,146 13 7800 0,096 6
1200 3970 0,192 22 4900 0,119 9 6500 0,158 14 8470 0,104 7
1200 4900 0,237 15 6040 0,146 6 8030 0,196 10 10460 0,128 5
1400 5280 0,255 17 6490 0,158 7 8650 0,211 12 11250 0,138 5
1600 5620 0,272 19 6900 0,168 8 9210 0,224 13 11960 0,147 6
1600 7930 0,384 13 9880 0,240 5 13020 0,317 9 17110 0,210 4
1900 8840 0,428 15 10990 0,267 7 14500 0,353 10 19020 0,233 5
2200 9670 0,468 18 12010 0,292 8 15860 0,387 12 20790 0,255 6
2000 10020 0,485 15 12540 0,304 6 16450 0,401 10 21690 0,266 5
2500 11530 0,558 19 14400 0,350 8 18920 0,461 13 24900 0,305 6
3000 12900 0,624 23 16080 0,390 10 21150 0,515 16 27790 0,341 7
Qa PT Qw
m
300
450 1900 0,092 7 2350 0,057 3 3230 0,079 5 4240 0,052 2
600 2200 0,107 9 2730 0,066 4 3730 0,091 6 4900 0,060 3
400 1790 0,087 6 2210 0,054 3 3030 0,074 4 3990 0,049 2
600 2200 0,107 9 2730 0,066 4 3730 0,091 6 4900 0,060 3
800 2520 0,122 12 3130 0,076 5 4270 0,104 8 5590 0,069 4
800 3020 0,146 13 3800 0,092 6 5110 0,124 10 6760 0,083 4
1000 3360 0,163 16 4220 0,102 7 5680 0,139 11 7510 0,092 5
1200 3650 0,177 19 4580 0,111 8 6180 0,151 13 8150 0,100 6
1200 4510 0,218 13 5640 0,137 6 7630 0,186 9 10060 0,123 4
1400 4860 0,235 15 6070 0,147 6 8220 0,200 11 10820 0,133 5
1600 5170 0,250 17 6450 0,157 7 8750 0,213 12 11500 0,141 6
1600 7310 0,354 11 9250 0,225 5 12380 0,302 8 16460 0,202 4
1900 8140 0,394 13 6970 0,169 8 13790 0,336 9 18310 0,224 4
2200 8910 0,431 16 11250 0,273 7 15090 0,368 11 20010 0,245 5
2000 9240 0,447 13 11760 0,285 6 15650 0,381 9 20880 0,256 4
2500 10630 0,515 17 13490 0,327 7 18000 0,439 12 23970 0,294 6
3000 11890 0,575 20 15070 0,366 9 20130 0,490 14 26760 0,328 7
W l/s kPa W l/s kPa W l/s kPa W l/s kPa
50 / 45 60 / 50 70 / 60 90 / 70
3
/h
W l/s kPa W l/s kPa W l/s kPa W l/s kPa
1520 0,074 5 1870 0,045 2 2590 0,063 3 3390 0,042 2
'
Pw
'
All copying, even partial, of this manual is strictly forbidden
60 / 50 70 / 60 90 / 70
PT Qw
PT Qw
13
Pw
'
22
'
Pw
PT Qw
PT Qw
Pw
'
Pw
'
PT Qw
PT Qw
'
'
UT66000806 - 02
Pw
Pw
UTN
8 INSTALLATION SUGGESTIONS
UTN units can be installed both vertically and horizzontally. The UTN units are always supplied for the A-A placing. If a different placing is needed the installer can modify it before mounting the unit (see chapter 3 "POSSIBLE CONFIGURATIONS"). Choose the unit position to have the best ductwork path. The air sucted by the unit must be filtered: use the MAF or MAFO accessories. Fit any accessories on the standard unit before installing it. It is suggested to use anti-vibration joint (available as option) between the unit and the ducts. Ductworks, in particular the air outlet one, must be insulated to avoid moisture formation.
Glycol percentage in weight Freez ing temperature (°C) Capacity correct ion factor Pressure drop correction factor
0 0 1,00 1,00
10 -4 0,97 1,05
20 -10 0,92 1,10
30 -16 0,87 0,05
40 -24 0,82 1,20
Keep free space around the fan coil to allow proper operation of the unit and ordinary and extraordinary maintenance. Install the remote control panel, if any, in a position that can easily be reached by the user to set the functions and that is suitable for the proper detection of the temperature, if provided. Therefore avoid:
- positions directly exposed to sunlight;
- positions exposed to hot or cold draughts;
- obstacles preventing the proper temperature detection. If the system is shut down during the winter months, drain off the water from the system to prevent damage due to freezing; if antifreeze solutions are
used, check the freezing point using the table shown at the foot of the page.
UT66000806 - 02
All copying, even partial, of this manual is strictly forbidden
14
UTN
9 DIMENSIONAL DATA
1: 6 fast-coupling slots 2: condensate discharge - horizontal installation 3: condensate discharge - vertical installation 4: right-hand hydraulic attachments 5: AIR DELIVERY
15
6: AIR INTAKE
6-A supply terms 6-B changeable during installation
7: round pre-sheared element (φ 100 mm) for external air inlet
UTN 06 - UTN 08 - UTN 12 - UTN 16
558
444
319
3
227
177
Ø 100
7
312
400
409
208
280
52
197
2
Ø 17
28
4
69
23
4DF
230
164
49
45
15
C15D
6A
A
D
6B
5
C15D
1
23 B
32
40
280
208
280
166
52
101
28
559
263
481
409
112
363
125
312
49
7
4DF
4
Ø 17
3
2
558
319
Ø 100
227
177
15
All copying, even partial, of this manual is strictly forbidden
67
164
229
173
280
40
ABCD
UTN 06 754 707 676 646 UTN 08 754 707 676 646 UTN 12 964 917 886 856 UTN 16 1174 1127 1096 1066
UT66000806 - 02
UTN
9 DIMENSIONAL DATA
1: 6 fast-coupling slots 2: condensate discharge – horizontal installation 3: condensate discharge – vertical installation 4: right-hand hydraulic attachments 5: AIR DELIVERY
53
241
6: AIR INTAKE
6-A supply terms 6-B changeable during installation
7: round pre-sheared element (φ 100 mm) for external air inlet
UTN 22 - UTN 30
392
3
579
510
506
382
273
Ø 100
227
208
7
294
215
57
45
15
2
28
Ø 17
4
98
4DF
UT66000806 - 02
D15C
6A
B23A
D
6B
D
5
C
1
15
45
275
352
32
204
53
23
135
28
170
375
718
718
617
523
473
4DF
4
Ø 17
2
3
7
392
365
Ø 100
208
273
165
88
74
188
198
82
353
294
UTN 22 1174 1127 1096 1066
15
44
ABCD
UTN 30 1384 1337 1306 1276
16
All copying, even partial, of this manual is strictly forbidden
UTN
10 WIRING DIAGRAMS
Wiring diagram notes WARNING! Turn off the power supply before beginning any wiring connections.
The dashed lines connections must be carried out by the installer.
Each fan-coil thermal-ventilating unit requires a switch (IL) on the feeder line with a distance of at least 3 mm between the opening contacts, and a suitable safety fuse (F).
10.1 UTN without control panel:
BK = black, high speed BU = blue, medium speed CN = faston connector F = protection fuse, not supplied GNYE = green/yellow, ground GY = grey, medium speed IL = mains switch, not supplied M = fan motor RD = red, low speed WH = white, common
To the control panel
CN
456789
BK
WH
BU / GY
GNYE
M 1~
RD
10.2 UTN with CD remote three speed selector and TC fan stop thermostat:
BK = black, high speed BU = blue, medium speed CD = remote speed selection switch CN = faston connector F = protection fuse, not supplied GNYE = green/yellow, ground GY = grey, medium speed IL = mains switch, not supplied M = fan motor RD = red, low speed TC = fan stop thermostat WH = white, common
230/1/50
L
N
SRL
IL
CD
4123
F
CN
456789
IL
WH
BK
GY/BU
RD
TC
F
10.3 UTN with CD remote three speed selector and TA room thermostat:
BK = black, high speed BU = blue, medium speed CD = remote speed selection
switch
CN = faston connector F = protection fuse, not supplied GNYE = green/yellow, ground GY = grey, medium speed IL = mains switch, not supplied M = fan motor RD = red, low speed TA = room thermostat WH = white, common
987654
F
IL
LN
230 / 1 / 50
NL
230/1/50
BU/GYBKWH
RD
M
1
CN
GNYE
M
1~
GNYE
3
2 1 N N
T
RF
TA
4
S
1
2
3
RL
C
CD
All copying, even partial, of this manual is strictly forbidden
17
UT66000806 - 02
UTN
10 WIRING DIAGRAMS
Wiring diagram notes WARNING! Turn off the power supply before beginning any wiring connections.
The dashed lines connections must be carried out by the installer.
Each fan-coil thermal-ventilating unit requires a switch (IL) on the feeder line with a distance of at least 3 mm between the opening contacts, and a suitable safety fuse (F).
10.4 UTN with CD remote three speed selector and TA2 room thermostat:
BK = black, high speed BU = blue, medium speed CD = remote speed selection switch CN = faston connector F = protection fuse, not supplied GNYE = green/yellow, ground GY = grey, medium speed IL = mains switch, not supplied M = fan motor RD = red, low speed
987654
TA2 = room thermostat WH = white, common
IL
F
LN
230 / 1 / 50
RD
10.5 UTN unit connected in parallel with CD remote selection switch, TA room thermostat and KP power interface:
BK = black, high speed BU = blue, medium speed CD = Remote speed selection switch CN = faston connector F = protection fuse, not supplied GNYE = green/yellow, ground GY = grey, medium speed KP = master/sleeve interface, accessory IL = mains switch, not supplied M = fan motor RD = red, low speed WH = white, common
BU/GY
BK
M
1
WH
WH
CN
GNYE
M
BU/GY
BK
654
SF
2
1
N
N
4
1
2
3
M
WH
1
RD
BU/GY
BK
98765
4
221920
4
1
RD
987
CN
CN
M
1
RD
BU/GY
BK
WH
98765
4
262324
21
302728
25
3
M
1
RD
BU/GY
BK
WH
4
CN
34
313233
29
1
2
RF
T
TA2
S
RL
c
98765
CN
CD
UT66000806 - 02
C12
3
234
5
CD
S RL
C
TA
4 1 2 3
T
RF
N
1 N
3 2
18
All copying, even partial, of this manual is strictly forbidden
13L14 N
IL
KP
15 L
16 N
F
230 / 1 / 50
L
N
UTN
10 WIRING DIAGRAMS
Wiring diagram notes WARNING! Turn off the power supply before beginning any wiring connections.
The dashed lines connections must be carried out by the installer.
10.6 UTN units with TA room thermostat with centralised mode selector and CD, CDE speed selectors:
BK = black, high speed BU = blue, medium speed CD = flush remote speed selection switch CDE = remote speed selection switch CN = faston connector F = protection fuse, not supplied GNYE = green/yellow, ground GY = grey, medium speed IL = mains switch, not supplied M = fan motor RD = red, low speed SF = Centralised mode selector, not supplied TA = room thermostat TC = fan stop thermostat WH = white, common
Each fan-coil thermal-ventilating unit requires a switch (IL) on the feeder line with a distance of at least 3 mm between the opening contacts, and a suitable safety fuse (F).
TC
TA
RF
T
1
2
3
N
N
IL
F
C
S
TC
3
IL
CDE
23456
1
4
TA
RF
T
2
1
N
N
F
CD
S
C
RL
321
SF
F
IL
230 / 1 / 50
L
N
19
All copying, even partial, of this manual is strictly forbidden
CN
4
876 5 9
CN
54
76
98
WH BK
RD
WH BK
BU/GY
RD
BU/GY
M
1
M
1
UT66000806 - 02
UTN
10 WIRING DIAGRAMS
Wiring diagram notes WARNING! Turn off the power supply before beginning any wiring connections.
The dashed lines connections must be carried out by the installer.
10.7 UTN units with TD wall mounted control with speed selector, electromechanical thermostat and summer winter selector:
Each fan-coil thermal-ventilating unit requires a switch (IL) on the feeder line with a distance of at least 3 mm between the opening contacts, and a suitable safety fuse (F).
BK = black, high speed BU = blue, medium speed CN = faston connector F = protection fuse, not supplied GNYE = green/yellow, ground GY = grey, medium speed IL = mains switch, not supplied M = fan motor
87654
RD = red, low speed
9
SF = centralised mode selector, not
supplied
TD = wall mounted control with
F
speed selector, electromechanical thermostat
IL
and summer winter selector
WH = white, common
LN
230 / 1 / 50
10.8 UTN units with TDC wall mounted control with speed selector and electromechanical thermostat:
BK = black, high speed BU = blue, medium speed CN = faston connector F = protection fuse, not supplied GNYE = green/yellow, ground GY = grey, medium speed IL = mains switch, not supplied M = fan motor RD = red, low speed SF = centralised mode selector, not supplied TC = fan stop motor TDC = wall mounted control with speed selector and
electromechanical thermostat
WH = white, common
RD
BU/GYBKWH
M
1
CN
GNYE
TC
6 5
N
4 3 2 1
S
C
SF
T
ACC
TD
ACC
TDC
T
C
S
6
5
N
TC
2
9
3
4
1
10
UT66000806 - 02
SF
F
IL
L
20
All copying, even partial, of this manual is strictly forbidden
N
230 / 1 / 50
CN
WH
BK
M
BU/GY
RD
987654
GNYE
1
UTN
10 WIRING DIAGRAMS
Wiring diagram notes WARNING! Turn off the power supply before beginning any wiring connections.
The dashed lines connections must be carried out by the installer.
10.9 UTN units with TD4T wall mounted control with speed selector, electromechanical thermostat and summer winter selector (heating/ cooling) for 2/4 pipe systems with valves:
BK = black, high speed BU = blue, medium speed CN = faston connector F = protection fuse, not supplied GNYE = green/yellow, ground GY = grey, medium speed IL = mains switch, not supplied M = fan motor RD = red, low speed SF = centralised mode selector, not supplied TD4T = wall mounted control with speed selector,
electromechanical thermostat and summer winter selector for 2/4 pipe systems with valves.
VK-C = on/off valve for cooling circuit VK-H = on/off valve for heating circuit WH = white, common
Each fan-coil thermal-ventilating unit requires a switch (IL) on the feeder line with a distance of at least 3 mm between the opening contacts, and a suitable safety fuse (F).
987654
F
IL
LN
230 / 1 / 50
RD
BU/GYBKWH
1
VK-C
VK-H
N 4 6 8
S
SF
3 2 1
C
ACC
7
T
CN
TD4T
M
GNYE
All copying, even partial, of this manual is strictly forbidden
21
UT66000806 - 02
UTN
SA
MICROD
10WIRING DIAGRAMS
1
C
2
V1
3
V3
V2
V1
L
PE
N
N
SW
V2
4C
V3
L
14
L
15
N
16
N
17
V3 V2
V1
IPM
28 27 26 25
4
5
6
7
8
9
CN
WH
BK
BU/GY
RD
ILF
M
1
L N
Wiring diagram notes
WARNING! Turn off the power supply before beginning any wiring
connections.
The dashed lines connections must be carried out by the installer.
10.10UTN units with MICRO-D microprocessor remote control panel, for
the automatic control of the fan-coil:
BK =black, high speed
BU =blue, medium speed
CN =faston connector
F =protection fuse, not supplied
GNYE =green/yellow, ground
GY =grey, medium speed
IL =mains switch, not supplied
IPM =power interface
M =fan motor
MICRO-D =microprocesor remote control panel, for the automatic
control of the fan-coil
RD =red, low speed
SA =Room temperature probe for automatic fan speed selection
SW =Water temperature probe (option for the MICROPROD
control), for the automatic cooling/heating mode selection.
WH =white, common
Each fan-coil thermal-ventilating unit requires a s
line with a distance of at least 3 mm between the opening contacs anda
suitable safety fuse (F).
witch (IL) on the feede
230/1/50
UT66000806 - 02
All copying, even partial, of this manual is strictly forbidden
22
UTN
10WIRING DIAGRAMS
Wiring diagram notes
WARNING! Turn off the power supply before beginning any wiring
connections.
The dashed lines connections must be carried out by the installer.
10.11UTN units with microprocessor remote control panel MICROPRO-D
BK =Black, maximum speed
BU =Blue, medium speed
CN =Fast on connector
CRHC =Group of controls connected to the centralised switch
RCH
EXT =External reed contact for the automatic switch ON and
OFF af the unit (not supplied)
F =Protection fuse (not supplied)
IL =Mains switch (not supplied)
MICROPROD = Wall mounted microprocessor control panel
RCH =Remote switch for the centralized cooling / heating mode
selection (not supplied)
RD =Red, minimum speed
SA =Room temperature probe for automatic fan speed
selection
SW =Water temperature probe (option for the MICROPROD
control), for the automatic cooling/heating mode selection.
WH =White, common.
Each fan-coil thermal-ventilating unit requires a switch (IL) on the feeder
line with a distance of at least 3 mm between the opening contacts, and a
suitable safety fuse (F).
All copying, even partial, of this manual is strictly forbidden
23UT66000806 - 02
MICROPROD
SA
SW
L N
230/1/50
L N
230/1/50
CRHC
V3
V2
V1
L
PE
N
N
N
RE
V
RM
RM
EX
EX
IL
IL
F
F
RHC
MICROPRO
EXT
1
C
2
V1
3
V2
C
4
RM RM
RM RM
MICROPROD
V3
14 L
15 L
16 N 17 N
V3 V2 V1
IPM
28 27 26 25
CN
WH
4
BK
5
BU/GY
6
RD
7
8
9
M
1
Vr Iass (A) Pass (W
)
high 0,820 188
UTN06-06A
med 0,550 122 low 0,400 84
high 1,210 265 med 0,810 185
UTN08-08A
low 0,700 135 high 2,100 460
UTN12-12A
med 1,600 345 low 1,350 385 high 2,500 505
med 1,800 380
UTN16-16A
low 1,400 290
high 3,500 750 med 2,350 535
UTN22-22A
low 1,800 370 high 5,600 1300
UTN30-30A
med 4,600 1090 low 3,800 870
UTN
11MOTORS ELECTRICAL DATA
12ACCESSORIES
The following table describes the characteristics of the motors at available
CD - Flush wall-mounted speed selector
working conditions.
Flush wall-mounted control panel is provided
with a 4
positions (3speed + stop) rotation selector.
Legend:
The CD control panel allows the ON/OFF and fan speed
VrOperation speedXC
selection of the high pressure fan coil unit.
P
Power input
ASS
IASS Operation current
CDE - wall mounted speed selector
Wall mounted control panel is provided
with a 3
positions (3 speed ) and switch ON/OFF .
The CDE control panel allows the ON/OFF and fan
speed selection of the high press
ure fan col unit.
TD - Wall mounted control with speed
selector, thermostat and summer-winter
selector
Wall mounted control panel complete with
fan speed selector, electromechanical
thermostat and cooling / heating mode
selector.
Fan speed control, regulation of the room temper
ature and cooing heng
mode selection:
- manual setting of the fan speed;
- room temperature regulation both in cooling / heating mode, by means
of fan start / stop, at a manually set temperature.
TDC - Wall mounted control with speed
selector and thermostat
Wall mounted control panel complete with fan
speed selector, electromechanical ther
mostat
and cooling / heating mode selector.
Fan speed control, regulation of the room
temperature and cooling / heating mode selection:
- manual setting of the fan speed;
- room temperature regulation both in cooling / heating mode, by
mean
fan start/stop, at a manually set temperature.
TD4T - Wall mounted control with
speed selector, thermostat and
summer-winter selector, for 2/4 pipe
system with valves
Wall mounted control panel provided with
fan speed selector, electromechanical
thermostat, and cooling / heating mode
selector; if installed it controls regulating valves.
Fan speed control and regulation of the room tem
perature:
- manual setting of the operation fan speed;
- regulation of the room temperature for 2 and 4 pipe systembn
heating and cooling mode, by means of fan start/stop at a may
temperature and by means of openv
24UT66000806 - 02
All copying, even partial, of this manual is strictly forbidden
UTN
12 ACCESSORIES
MICRONET- Advanced microprocessor control panels for ergo solution
MICRONET is the control panel suitable for the connection to the ERGO SOLUTION. Microprocessor control panels for wall installation complete with fan speed selector, electronic thermostat and cooling / heating mode selector; for the automatic control of the fan working on the valves and electric heater, if installed. Fan speed control, room temperature regulation and cooling / heating mode selection:
- room temperature regulation both in the cooling and heating mode, by means of fan start/stop, at a manually set speed;
- room temperature regulation both in the cooling and heating mode, by means of the automatic regulation of the fan speed;
- timer function (not available for MICROPRO-D);
- cooling / heating mode selection in the following way:
- manual in built;
- automatic according to the water temperature;
- automatic according to the room temperature;
- control of the ON/OFF valves for 2 or 4 pipe system;
- control of the electric heater as integration or replacement of the hot water heat exchanger with delayed stop of the fan (2 min.). The MICRONET control panels are provided also with contacts for external signals in order to enable or disable the unit operation.
- terminals for the connections with external signals in order to enable or disable the unit operation;
- terminals for the connections with external signals in order to enable or disable the ECONOMY set point (only if combined with ERGO software)
- air temperature probe
- water temperature probe
- RS485
- built-in MODBUS communication protocol
- Built-in Polarity and termination resistance
- Protocollo di comunicazione MODBUS integrato
- Resistenze di polarizzazione e terminazione integrate attivabili tramite jumper
MICRO e MICRO-D - Microprocessor control panels
Microprocessor control panels for in built (MICRO) or wall (MICRO-D) installation, complete with fan speed selector, electronic thermostat and cooling / heating mode selector; for the automatic control of the fan coil unit. Fan speed control, room temperature regulation and cooling / heating mode selection:
- regulation of the room temperature both in the cooling and heating mode, by means of fan start/stop, at a manually set temperature;
- regulation of the room temperature, both in the cooling and heating mode, by means of the automatic regulation of the fan speed;
- timer function (not available for MICRO-D);
- cooling / heating mode selection in the following ways:
- manual in built;
- automatic according to the water temperature (with the SW water probe; option).
MICROPRO e MICROPRO-D - Microprocessor control panels
Microprocessor control panels for in built (MICROPRO) and wall (MICROPRO-D) installation complete with fan speed selector, electronic thermostat and cooling / heating mode selector; for the automatic control of the fan working on the valves and electric heater, if installed. Fan speed control, room temperature regulation and cooling / heating mode selection:
- room temperature regulation both in the cooling and heating mode, by means of fan start/stop, at a manually set speed;
- room temperature regulation both in the cooling and heating mode, by means of the automatic regulation of the fan speed;
- timer function (not available for MICROPRO-D);
- cooling / heating mode selection in the following way:
- manual in built;
- manual remote (centralized);
- automatic according to the water temperature (with the SW water probe, option for MICROPRO-D, included in MICROPRO kit);
- automatic according to the room temperature (with air temperature probe, option);
- control of the ON/OFF valves for 2 or 4 pipe system;
- control of the electric heater as integration or replacement of the hot water heat exchanger with delayed stop of the fan (2 min.). The MICROPRO / MICROPRO-D control panels are provided also with contacts for external signals in order to enable or disable the unit operation.
SW - Water temperature lectronic probe for microprocessor control panels
Water probe for the MICRO, MICRO-D and MICROPRO-D control panels: automatic selection of the cooling / heating operation mode. Connected directly to the microprocessor control panel, this probe measures the water temperature inside the heat exchanger. If the temperature is lower than 17°C the unit works in cooling mode and the temperature range of the control panel will be referred to the cooling mode (19/31°C); if the temperature registered is higher than 37°C the unit works in heating mode and the temperature range of the control panel will be referred to the heating mode (14/26°C). If the temperature registered is between 17°C and 37°C the control panel will disable the unit operation. The SW water probe is included in the MICROPRO and MICRONET kit.
TC - Fan stop thermostat: elecromechanical thermostat for minimum water temperature during heating
Fan stop thermostat with automatic resetting, it stops the fan motor assembly when the water temperature in the heat exchanger decreases under the set value (42°C). Usefull only in the heating mode for installation on the finned pack of the heat exchanger.
IPM - Power interface for the connections to the control panels MICRO-D and MICROPRO-D
The IPM power board permits to use MICRO-D and MICROPRO-D microprocessor-based control panels on the whole range of UTN air handling units, even for models with current consumation greayer than 1A. The capacity of the IPM contacts is 16A, IP30 rating. The use of the IPM power board matched with the microprocessor controls is:
- recommended for the UTN06, UTN08 air handling unit;
- compulsory for all the others models.
25
All copying, even partial, of this manual is strictly forbidden
UT66000806 - 02
UTN
12 ACCESSORIES
TA - Wall mounted room thermostat
Room thermostat for wall installation. Automatic regulation of the room temperature:
- only in the heating mode working on the fan motor assembly and on the regulating valve, if installed (ON/ OFF operation);
- only in the cooling mode working on the fan motor assembly and on the regulating valve, if installed (ON/OFF operation);
- both in cooling and heating mode, with remote mode selection working on the fan motor assembly and on the regulating valve, if installed (ON/OFF operation).
TA2 - Wall mounted room thermostat with summer/ winter selector
Wall mounted room thermostat with cooling / heating mode selector. Automatic regulation of the room temperarure both in heating and cooling mode, working on the fan motor assembly and on the regulating valve if installed (ON/OFF operating).
CSD - Wall mounted control for proportional opening and closing of the PA90 motorized louver
50%
Designed for wall installation it allows the proportional opening and closing from 0 to 100% of the PA90 outdoor air intake motorized louver
0% 100%
MAF / MAFO - Air intake modules with filter
Made of galvanized steel sheet, these modules permit to filter the air sucked up by the unit and also to connect the unit to the intake channeling. 2 version are proposed depending on the guaranteed filtering degree: MAF: air intake module with flat filter made of acrylic material, self-extinguishing in class 1, with filtering class G2. MAFO: air intake module with corrugated filter made of acrylic fiber, self­extinguishing in class 1, with filtering EU4.
PCOC - Connecting panel to rectangular ducts
Manufactured in galvanised sheet steel, the PCOC connection panels are used for the connection of rectangular ducts with flanges and with other flanged accessories. They can be installed on both the intake and delivery line. They are made up of a rectangular panel that is to be secured to the machine (or to another accessory with similar drilling, for example, MAF, MAFO, RE etc..) coupled to a flanged sleeve that represents the starting point for rectangular ducts of the type commonly used in distribution plants.
PCOF - Connecting panel to flexible ducts
Manufactured in galvanised sheet steel, the PCOF connection panels are used to connect to air distribution plants achieved by means of hoses or to other dedicated accessories. They can be installed on both the intake and delivery line (in this case the hose should be insulated). They are made up of a rectangular panel that is to be secured to the machine or to another accessory with similar drilling (i.e. MAF, MAFO, RE etc..) complete with circular collars (Ø 200 mm) that represent the starting point for the hoses of the type commonly used in distribution plants.
Model UTN 06-06A 08-08A 12-12A 16-16A 22-22A 30-30A
n° of holes 223445
V - M - R 3-way valve, on-off actuator and hydraulic connections kit
IThe system allows the regulation of the ambient temperature by stopping the water flow into the heat exchanger. Available for 2 pipe and 4 pipe systems, the kit is made of the components below indicated: Valve body (V): 3-way with in-built by-pass (4 connections):
- 3/4” for the models UTN 6, UTN 6A, UTN 8, UTN 8A
- 1” for the models UTN 12, UTN 12A, UTN 16, UTN 16A Actuator (M): normally closed, electrothermal type, 230V single phase, with ON-OFF operation, it works directly on the valve shutter. Hydraulic connections kit (R): made of copper tubes and brass connections, complete with balancing valve, is different according to the models (standard coil or additional coil in case of 4 pipe systems) and for the unit water connection side. The hydraulic connections kit is not available for the UTN22 - 22A and UTN30
- 30A units.
VRCV / VRCH - Auxiliary trays for collecting condensate
Auxiliary trays for collecting condensate, used for collecting any condensate that might form on the adjusting valves, the hydraulic unions and the holdfasts during the cooling operating mode. The trays are made of galvanized metal sheet, with condensate discharge pipe (φ17 mm) setup for being connected to a flexible rubber tube, like that which has been envisaged for the condensate discharge trays of the basic unit. They are available for: UTN units installed vertically, VRCV. UTN units installed horizontally, VRCH.
UT66000806 - 02
All copying, even partial, of this manual is strictly forbidden
26
UTN
12 ACCESSORIES
KSC - Condensate removal kit
This device allows to overcome displacements in the condensate drain. The pump can drain water up to 8 l/h and it is completed by a non return valve on the discharge side.
BP - Kit batterie di post riscaldamento
BP 1 or 2 row reheating exchangers are designed for installation on the air outlet of the UTN air conditioning and thermal ventilating units. NOTE: The BP module has holes like those on the machine air intake, on the extremity turned toward the air outflow ducts. This allows you to attach all the accessories that can be directly applied on the machine (PCOC, PCOF, GAT, etc…).
RE - Supplementary heating elements
Useful as heating integration to the hot water system, the RE kit is made of an electric heater with safety thermostat (automatic and manual resetting) and power relay. The RE electric heater kit has to be matched with the MICROPRO-D control panel and with the IPM power board.
PA90 - Outdoor air inlet motorized louver
The outdoor air inlet motorized louvre is intended for replacing the air in the room directly from the air­handling unit. The amount of outdoor air that will be let into the room, after having been filtered and treated thermally, may be regulated proportionally from 0 to 100% by means of a servomotor controlled by a rotary potentiometer that is inside the specific CSD control, which is designed for flush wall-mounting installations. Kit PA90, as shown in figure (1), essentially comprises the following components: A) Outdoor air inlet louvre made of galvanized steel sheet and setup for being connected to the machine, at one end, and to the other required accessories. B) Servomotor connected directly to the louvre’s baffle, with a protection rating of IP54 and power supply of ~ 24V. The louvre may be opened or closed automatically at the signal of the external auxiliary contacts (not supplied) such as antifreeze thermostats, timers, etc., with the possibility of connecting multi-servomotors in parallel to an individual opening-closing control. C) 230V - 24V voltage transformer, complete with support terminal strip housed inside the specific electrical box, which functions as a mechanical protection for preventing the access to the connecting terminal strip and to the transformer itself. D) Self-threading fixing screws.
All copying, even partial, of this manual is strictly forbidden
GA / GAT - Vibration dampers
Manufactured in galvanized sheet steel, the GA/GAT connection panels are used to connect to rectangular ducts equipped with flanges and other flanged accessories. They are made up of a rectangular panel that is to be secured to the machine or to another accessory with similar drilling (i.e. MAF, MAFO, RE etc...) coupled by means of a flexible bellow to a flanged sleeve that rapresents the starting point for rectangular ducts of the type commonly used in distribution plants. If the vibration damping joint is used together with the electrical heating elements module (accessory RE) a GAT joint made of heat-resistant silicone material is to be fitted on the delivery line.
TFA - Not insulated flexible ducts
Uninsulated flexible duct for the connections to the air distribution with φ 200 mm diameter, supplied in 6 m lenght undivisible.
TFM - Insulated flexible ducts
Insulated flexible duct for the connections to the air distribution with φ 200 mm diameter, supplied in 6 m lenght undivisible. The insulation of the duct is optained by means of fiberglass, thickness 25 mm with 16
3
density.
Kg/m
TP - Plastic cap
Plastic cap φ 200 mm for the closing on the PCOF, of the air outlet not used.
CA / CAF - Air inlet plenum box
Intake Plenum box in galvanised sheet metal complete with circular collars (Ø 200 mm) for the connection, by means of hoses and intake grids with fixed fins, to pocket type structures, to increase the free air flow cross section. Sized to be adaptable to the modular structure of the ceiling panels, they are equipped with 2 or 3 circular collars so that they can be connected, following their suitable combination, to all the heater fans of the UTN range. The CA version is equipped with just the grid alone whereas the CAF version is also equipped with a flat filter in acrylic material, with filtering rating G2, housed in the standard frame. The filter of this second type of intake box can be serviced (cleaned) on a periodic basis without having to access the unit fitted behind the ceiling panels or in a service room.
GM - Alluminium air outlet grille
Air delivery grids with double row of adjustable fins in anodised aluminium, equipped with galvanised sheet metal frame that is used to wall-mount the grids or to fit them directly on the delivery head of the machine. The galvanised sheet metal frame is drilled at one end so that it can be secured directly to the delivery head of the heater fan (or to accessories such as the additional RE electrical module).
GR - Alluminium air inlet grille
Air intake grids with single row of fins in anodised aluminium, equipped with galvanised sheet metal frame that is used to wall-mount the grids or to fit them directly on the intake head of the machine. The galvanised sheet metal frame is drilled at one end so that it can be secured directly to the intake head of the heater fan (or to accessories such as the MAF and MAFO filtering units).
27
UT66000806 - 02
UTN
13 MAINTENANCE
The maintenance operations for the UTN air conditioning and hot-air heating units are limited to the periodic cleaning of the air filter (provided on MA/F and MA/FO accessories) and the heat exchanger, and the checking of the working efficiency of the condensate discharge. Only skilled personnel may perform the aforesaid maintenance. Pay utmost attention during the maintenance operations: accidentally coming into touch with some of the metallic parts might cause injuries therefore wear safety work gloves. Every time the units are started after long dwell times, make sure that air is NOT present inside the heat exchanger. The motor is maintenance-free since it is equipped with self-lubricating bearings.
For safety reasons, before performing any maintenance or cleaning operations, turn off the equipment and cut voltage by turning the line switch.
UT66000806 - 02
40010 Bentivoglio (BO)
Via Romagnoli, 12/a
Tel. 051/8908111 Fax 051/8908122
www.galletti.it