OPERATING LIMITS
Thermal carrier: water
Water temperature: + 5°C to +95°C
Air temperature: -20°C to + 43°C
Power supply voltage: 230 V +/-10 %
Max. pressure of primary fluid: 10 bar
1MEAN FEATURES
The new range of UTN high pressure fan coils units has been designed for
conditioning rooms that require the installation of ducted units.
Proposed in 12 models with air flows from 600 to 3000 m3/h, the UTN units
are characterized by a wide applicative flexibility thanks to the special
constructive solutions.
> possibility of installation both in horizontal and vertical position thanks
to the special conformation of the condensate discharge system;
> the air intake direction may be modified during installation;
> reduced height (280 mm up to model 16A);
> pre-shared element for the recycle of external air, standard on all models
(Φ 100 mm);
> wide range of accessories for effectively.
2VERSIONS AND COMPONENTS
Versions
UTNair handling unit setup for 2-pipe systems
UTNDFair handli ng unit set up for 4-pipe systems (2 heat
exchangers)
N.B. both version may be manufactured, on request, with pre-painted
panels.
Components
>Load-bearing structure made of galvanized steel sheet of suitable
thickness, duly insulated with noise-proof/anticondensing material,
self-estinguishing in Class 1; the insulating material is characterized
by a thickness of 10 mm and a density of 90 Kg/m3.
The unit is completed by the following:
- inspections panels;
- setup for external air intake;
- fast-coupling slots.
>Dual intake centrifugal fans made of alluminium, with statically and
dinamically balanced impellers, coupled directly to the electric
motor.
>3 speed electric motor, equipped with permanently fit condenser and
thermal safety device, installed on vibrator damping supports.
>Heat exchanger: high efficiency, made of copper tube and alluminium
fins secured to the tubes by mechanical expansion. It is fitted with
brass manifolds and air valves. The heat exchanger, normally
supplied with left hand attachments, may be turned by 180°.
>System for collecting and discharging condensate setup either for
horizontal or vertical installation.
>Terminal strip for fast - on electrical connections.
The technical and dimensional data indicated in this catalougue are subject to modifications
in the view of the improvement of the product.
UT66000806 - 02
All copying, even partial, of this manual is strictly forbidden
2
UTN
3POSSIBLE CONFIGURATIONS
VERTICAL INSTALLATION
AA
Heating and cooling operation
HORIZONTAL INSTALLATION
AA
AB
Heating and cooling operation
Example of installation UTN - Air distribution with circular flexible ducts
GA
GAT
PCOF TFA
MAF
MAFO
MAF
MAFO
UTN
UTN
CA
CAFTFM
Example of installation UTN - Air distribution with rectangular ducts
PCOC
G90
GR
AB
PCOF
GA
GAT
PCOC
4AVAILABLE OPTIONS
The wide and complete range of accessories completes the UTN air handling
units as far as operation is concerned, adapting these units to any plantengineering requirements, from the solution with rectangular section channels
to the one with round flexible ducts.
The standard machines are supplied without control panel and without air
filter.
CONTROL PANELS AND THERMOSTATS
CDFlush wall-mounted speed selector
CDEWall-mounted speed selector
TDWall-mounted control with speed selector, electromechanical
thermostat and summer/winter selector
TDCWall-mounted control with speed selector and
electromechanical thermostat
TD4TWall-mounted control with speed selector,
electromechanical thermostat and summer winter
selector for 2/4 pipe systems with valves
MICRONETMicroprocessor control ERGO solution
MICRODMicroprocessor wall-mounted control for the automatic
control of the fan-coil
MICROPRODMicroprocessor wall-mounted control for the automatic
control of the fan-coil, valves and electric heater
SWWater temperature electronic probe for MICROD and
MICROPROD
TCFan stop thermostat: electromechanical thermostat for
minimum water temperature during heating mode
IPMPower interface for MICROD and MICROPROD
TAElectromechanical room thermostat
TA2Electromechanical room thermostat with summer/winter
selection
CSDWall-mounted control for proportional opening and
closing of the motor driven air intake louver
AIR SUCTION MODULES WITH FILTERS
MAFAir suction module with flat filter G2
MAFOAir suction module with waved filter G4
CONNECTION PANELS
PCOCConnecting panel to rectangular ducts
PCOFConnecting panel to flexible ducts φ 200
3-WAY VALVES AND DRIP TRAYS
V3 way valve (possibility of motor driven)
MElectrothermal motor for motor driven valve
RHydraulic connection mounting kit
VRCVAuxiliary drip tray for ver tical installation units
VRCHAuxiliary drip tray for horizontal installation units
KSCCondensate removal kit
HOT WATER POST HEATING COIL
BPHot water post heating coil module
ELECTRIC HEATERS
REElectric heater, with safety thermostat and power relay
CAAir inlet plenum box with double row grille
CAFAir inlet plenum box with double row grille and filter G2
CMInsulated air outlet plenum box with 2 way grille
AIR INLET AND OUTLET GRILLES
GMAluminium air outlet grille with counterframe
GRAir suction aluminium grille with counter frame
All copying, even partial, of this manual is strictly forbidden
3
UT66000806 - 02
UTN
5RATED TECHNICAL DATA
UTN
Air flowHigh
Availa ble stati c pressureHi ghPa80759085888210095130110185175
Tota l cooling capacitykW2,803,203,904,806,207,007,808,8211,9013,7016,4018,30
Sensibl e cooling capaci tykW2,152,463,083,714,655,366,527,169,3610,5012,8014,10
Water flowl/ h48455367482910711209133915142056236728333140
Water pressure dropkPa10 8 17152420241626223445
He ating capacityHi ghk W7,208,3010,1012,1016,1018,5019,6022,4030,0033,7040,9045,00
Water flowl/ h634731890106614181630172619742642297036033695
Water pressure dropkPa121020172926281930243850
DF heating cap acity (4 pipe s)Hi ghk W4,014,015,635,638,248,2411,5011,5019,7019,7026,2026,20
Water flowl/ h353353496496726726101310131735173523092309
Water pressure dropkPa101013132121191917172222
Standard heat exchanger - rowsn°343434343445
Sta nda rd heat exchanger - hy drau li c co nnecti onsin3/ 4"3/ 4"3/4"3/ 4"3/4"3/4"3/ 4"3/4"1"1"1"1"
Sta nda rd heat exchanger - water conte ntl1,061,411,061,411,421,901,792,382,503,344,025,03
*Inlet connecting panel to rectangular ducts
**Outlet connecting panel to rectangular ducts
All copying, even partial, of this manual is strictly forbidden
7
UT66000806 - 02
UTN
6VENTILATION FEATURES
6.1ACCESSORIES: AIR PRESSURE DROP
The pressure drops shown below refer to accessories that are not
affected by the various sizes of the thermal ventilating units.
Pressure drops refer to the accessory itself and are not related to the
size of the thermal ventilating units.
PTHeating capacity
QwWater flow rateDPw Pressure drop on water side
Pw
'
W l/skPaW l/skPaW l/skPaW l/skPa
22200,107530600,074339700,097453300,0652
PTQw
Pw
'
PTQw
Pw
'
PTQw
Pw
'
UT66000806 - 02
All copying, even partial, of this manual is strictly forbidden
12
UTN
7PERFORMANCES
7.2DF COIL HEATING CAPACITY
Legend:
Tbs1Inlet air temperature D.B.
Tw1Inlet water temperature
Tw2Outlet water temperature
QaAir flow
PTHeating capacity
QwWater flow rateDPw Pressure drop on water side
All copying, even partial, of this manual is strictly forbidden
60 / 5070 / 6090 / 70
PTQw
PTQw
13
Pw
'
22
'
Pw
PTQw
PTQw
Pw
'
Pw
'
PTQw
PTQw
'
'
UT66000806 - 02
Pw
Pw
UTN
8INSTALLATION SUGGESTIONS
UTN units can be installed both vertically and horizzontally.
The UTN units are always supplied for the A-A placing.
If a different placing is needed the installer can modify it before mounting the
unit (see chapter 3 "POSSIBLE CONFIGURATIONS").
Choose the unit position to have the best ductwork path.
The air sucted by the unit must be filtered: use the MAF or MAFO accessories.
Fit any accessories on the standard unit before installing it.
It is suggested to use anti-vibration joint (available as option) between the
unit and the ducts.
Ductworks, in particular the air outlet one, must be insulated to avoid
moisture formation.
Glycol percentage in weight Freez ing temperature (°C)Capacity correct ion factorPressure drop correction factor
001,001,00
10-40,971,05
20-100,921,10
30-160,870,05
40-240,821,20
Keep free space around the fan coil to allow proper operation of the unit and
ordinary and extraordinary maintenance.
Install the remote control panel, if any, in a position that can easily be reached
by the user to set the functions and that is suitable for the proper detection
of the temperature, if provided.
Therefore avoid:
- positions directly exposed to sunlight;
- positions exposed to hot or cold draughts;
- obstacles preventing the proper temperature detection.
If the system is shut down during the winter months, drain off the water from
the system to prevent damage due to freezing; if antifreeze solutions are
used, check the freezing point using the table shown at the foot of the page.
UT66000806 - 02
All copying, even partial, of this manual is strictly forbidden
6-A supply terms
6-B changeable during installation
7:round pre-sheared element (φ 100 mm) for external air inlet
UTN 22 - UTN 30
392
3
579
510
506
382
273
Ø 100
227
208
7
294
215
57
45
15
2
28
Ø 17
4
98
4DF
UT66000806 - 02
D15C
6A
B23A
D
6B
D
5
C
1
15
45
275
352
32
204
53
23
135
28
170
375
718
718
617
523
473
4DF
4
Ø 17
2
3
7
392
365
Ø 100
208
273
165
88
74
188
198
82
353
294
UTN 221174112710961066
15
44
ABCD
UTN 301384133713061276
16
All copying, even partial, of this manual is strictly forbidden
UTN
10WIRING DIAGRAMS
Wiring diagram notes
WARNING! Turn off the power supply before beginning any wiring
connections.
The dashed lines connections must be carried out by the installer.
Each fan-coil thermal-ventilating unit requires a switch (IL) on the feeder
line with a distance of at least 3 mm between the opening contacts, and a
suitable safety fuse (F).
10.1UTN without control panel:
BK =black, high speed
BU =blue, medium speed
CN =faston connector
F =protection fuse, not supplied
GNYE = green/yellow, ground
GY =grey, medium speed
IL =mains switch, not supplied
M =fan motor
RD =red, low speed
WH =white, common
To the control panel
CN
456789
BK
WH
BU / GY
GNYE
M
1~
RD
10.2UTN with CD remote three speed selector and TC
fan stop thermostat:
BK =black, high speed
BU = blue, medium speed
CD =remote speed selection switch
CN =faston connector
F =protection fuse, not supplied
GNYE = green/yellow, ground
GY =grey, medium speed
IL =mains switch, not supplied
M =fan motor
RD =red, low speed
TC =fan stop thermostat
WH = white, common
230/1/50
L
N
SRL
IL
CD
4123
F
CN
456789
IL
WH
BK
GY/BU
RD
TC
F
10.3 UTN with CD remote three speed
selector and TA room thermostat:
BK =black, high speed
BU =blue, medium speed
CD =remote speed selection
switch
CN =faston connector
F =protection fuse, not supplied
GNYE = green/yellow, ground
GY =grey, medium speed
IL =mains switch, not supplied
M =fan motor
RD =red, low speed
TA =room thermostat
WH =white, common
987654
F
IL
LN
230 / 1 / 50
NL
230/1/50
BU/GYBKWH
RD
M
1
CN
GNYE
M
1~
GNYE
3
2
1
N
N
T
RF
TA
4
S
1
2
3
RL
C
CD
All copying, even partial, of this manual is strictly forbidden
17
UT66000806 - 02
UTN
10WIRING DIAGRAMS
Wiring diagram notes
WARNING! Turn off the power supply before beginning any wiring
connections.
The dashed lines connections must be carried out by the installer.
Each fan-coil thermal-ventilating unit requires a switch (IL) on the feeder
line with a distance of at least 3 mm between the opening contacts, and a
suitable safety fuse (F).
10.4UTN with CD remote three speedselector and TA2 room thermostat:
BK =black, high speed
BU =blue, medium speed
CD =remote speed selection switch
CN =faston connector
F =protection fuse, not supplied
GNYE = green/yellow, ground
GY =grey, medium speed
IL =mains switch, not supplied
M =fan motor
RD =red, low speed
987654
TA2 =room thermostat
WH =white, common
IL
F
LN
230 / 1 / 50
RD
10.5UTN unit connected in parallel with CD remote selection
switch, TA room thermostat and KP power interface:
BK =black, high speed
BU =blue, medium speed
CD =Remote speed selection switch
CN =faston connector
F =protection fuse, not supplied
GNYE = green/yellow, ground
GY =grey, medium speed
KP =master/sleeve interface, accessory
IL =mains switch, not supplied
M =fan motor
RD =red, low speed
WH =white, common
BU/GY
BK
M
1
WH
WH
CN
GNYE
M
BU/GY
BK
654
SF
2
1
N
N
4
1
2
3
M
WH
1
RD
BU/GY
BK
98765
4
221920
4
1
RD
987
CN
CN
M
1
RD
BU/GY
BK
WH
98765
4
262324
21
302728
25
3
M
1
RD
BU/GY
BK
WH
4
CN
34
313233
29
1
2
RF
T
TA2
S
RL
c
98765
CN
CD
UT66000806 - 02
C12
3
234
5
CD
S RL
C
TA
4 1 2 3
T
RF
N
1 N
3 2
18
All copying, even partial, of this manual is strictly forbidden
13L14 N
IL
KP
15 L
16 N
F
230 / 1 / 50
L
N
UTN
10WIRING DIAGRAMS
Wiring diagram notes
WARNING! Turn off the power supply before beginning any wiring
connections.
The dashed lines connections must be carried out by the installer.
10.6 UTN units with TA room thermostat with centralised mode selector
and CD, CDE speed selectors:
BK =black, high speed
BU =blue, medium speed
CD =flush remote speed selection switch
CDE =remote speed selection switch
CN =faston connector
F =protection fuse, not supplied
GNYE =green/yellow, ground
GY =grey, medium speed
IL =mains switch, not supplied
M =fan motor
RD =red, low speed
SF =Centralised mode selector, not supplied
TA =room thermostat
TC =fan stop thermostat
WH =white, common
Each fan-coil thermal-ventilating unit requires a switch (IL) on the feeder
line with a distance of at least 3 mm between the opening contacts, and a
suitable safety fuse (F).
TC
TA
RF
T
1
2
3
N
N
IL
F
C
S
TC
3
IL
CDE
23456
1
4
TA
RF
T
2
1
N
N
F
CD
S
C
RL
321
SF
F
IL
230 / 1 / 50
L
N
19
All copying, even partial, of this manual is strictly forbidden
CN
4
876 5
9
CN
54
76
98
WH
BK
RD
WH
BK
BU/GY
RD
BU/GY
M
1
M
1
UT66000806 - 02
UTN
10WIRING DIAGRAMS
Wiring diagram notes
WARNING! Turn off the power supply before beginning any wiring
connections.
The dashed lines connections must be carried out by the installer.
10.7 UTN units with TD wall mounted control
with speed selector, electromechanical
thermostat and summer winter selector:
Each fan-coil thermal-ventilating unit requires a switch (IL) on the feeder
line with a distance of at least 3 mm between the opening contacts, and a
suitable safety fuse (F).
BK =black, high speed
BU =blue, medium speed
CN =faston connector
F =protection fuse, not supplied
GNYE =green/yellow, ground
GY =grey, medium speed
IL =mains switch, not supplied
M =fan motor
87654
RD =red, low speed
9
SF =centralised mode selector, not
supplied
TD =wall mounted control with
F
speed selector,
electromechanical thermostat
IL
and summer winter selector
WH =white, common
LN
230 / 1 / 50
10.8 UTN units with TDC wall mounted control with speed
selector and electromechanical thermostat:
BK =black, high speed
BU =blue, medium speed
CN =faston connector
F =protection fuse, not supplied
GNYE =green/yellow, ground
GY =grey, medium speed
IL =mains switch, not supplied
M =fan motor
RD =red, low speed
SF =centralised mode selector, not supplied
TC =fan stop motor
TDC =wall mounted control with speed selector and
electromechanical thermostat
WH =white, common
RD
BU/GYBKWH
M
1
CN
GNYE
TC
6
5
N
4
3
2
1
S
C
SF
T
ACC
TD
ACC
TDC
T
C
S
6
5
N
TC
2
9
3
4
1
10
UT66000806 - 02
SF
F
IL
L
20
All copying, even partial, of this manual is strictly forbidden
N
230 / 1 / 50
CN
WH
BK
M
BU/GY
RD
987654
GNYE
1
UTN
10WIRING DIAGRAMS
Wiring diagram notes
WARNING! Turn off the power supply before beginning any wiring
connections.
The dashed lines connections must be carried out by the installer.
10.9 UTN units with TD4T wall mounted control with speed selector,
electromechanical thermostat and summer winter selector (heating/
cooling) for 2/4 pipe systems with valves:
BK =black, high speed
BU =blue, medium speed
CN =faston connector
F =protection fuse, not supplied
GNYE = green/yellow, ground
GY =grey, medium speed
IL =mains switch, not supplied
M =fan motor
RD =red, low speed
SF =centralised mode selector, not supplied
TD4T =wall mounted control with speed selector,
electromechanical thermostat and summer winter selector
for 2/4 pipe systems with valves.
VK-C =on/off valve for cooling circuit
VK-H =on/off valve for heating circuit
WH =white, common
Each fan-coil thermal-ventilating unit requires a switch (IL) on the feeder
line with a distance of at least 3 mm between the opening contacts, and a
suitable safety fuse (F).
987654
F
IL
LN
230 / 1 / 50
RD
BU/GYBKWH
1
VK-C
VK-H
N
4
6
8
S
SF
3
2
1
C
ACC
7
T
CN
TD4T
M
GNYE
All copying, even partial, of this manual is strictly forbidden
21
UT66000806 - 02
UTN
SA
MICROD
10WIRING DIAGRAMS
1
C
2
V1
3
V3
V2
V1
L
PE
N
N
SW
V2
4C
V3
L
14
L
15
N
16
N
17
V3
V2
V1
IPM
28
27
26
25
4
5
6
7
8
9
CN
WH
BK
BU/GY
RD
ILF
M
1
L
N
Wiring diagram notes
WARNING! Turn off the power supply before beginning any wiring
connections.
The dashed lines connections must be carried out by the installer.
10.10UTN units with MICRO-D microprocessor remote control panel, for
the automatic control of the fan-coil:
BK =black, high speed
BU =blue, medium speed
CN =faston connector
F =protection fuse, not supplied
GNYE =green/yellow, ground
GY =grey, medium speed
IL =mains switch, not supplied
IPM =power interface
M =fan motor
MICRO-D =microprocesor remote control panel, for the automatic
control of the fan-coil
RD =red, low speed
SA =Room temperature probe for automatic fan speed selection
SW =Water temperature probe (option for the MICROPROD
control), for the automatic cooling/heating mode selection.
WH =white, common
Each fan-coil thermal-ventilating unit requires a s
line with a distance of at least 3 mm between the opening contacs anda
suitable safety fuse (F).
witch (IL) on the feede
230/1/50
UT66000806 - 02
All copying, even partial, of this manual is strictly forbidden
22
UTN
10WIRING DIAGRAMS
Wiring diagram notes
WARNING! Turn off the power supply before beginning any wiring
connections.
The dashed lines connections must be carried out by the installer.
10.11UTN units with microprocessor remote control panel MICROPRO-D
BK =Black, maximum speed
BU =Blue, medium speed
CN =Fast on connector
CRHC =Group of controls connected to the centralised switch
RCH
EXT =External reed contact for the automatic switch ON and
OFF af the unit (not supplied)
F =Protection fuse (not supplied)
IL =Mains switch (not supplied)
MICROPROD = Wall mounted microprocessor control panel
RCH =Remote switch for the centralized cooling / heating mode
selection (not supplied)
RD =Red, minimum speed
SA =Room temperature probe for automatic fan speed
selection
SW =Water temperature probe (option for the MICROPROD
control), for the automatic cooling/heating mode selection.
WH =White, common.
Each fan-coil thermal-ventilating unit requires a switch (IL) on the feeder
line with a distance of at least 3 mm between the opening contacts, and a
suitable safety fuse (F).
All copying, even partial, of this manual is strictly forbidden
23UT66000806 - 02
MICROPROD
SA
SW
L
N
230/1/50
L
N
230/1/50
CRHC
V3
V2
V1
L
PE
N
N
N
RE
V
RM
RM
EX
EX
IL
IL
F
F
RHC
MICROPRO
EXT
1
C
2
V1
3
V2
C
4
RM
RM
RM
RM
MICROPROD
V3
14 L
15 L
16 N
17 N
V3
V2
V1
IPM
28
27
26
25
CN
WH
4
BK
5
BU/GY
6
RD
7
8
9
M
1
Vr Iass (A) Pass(W
)
high 0,820 188
UTN06-06A
med 0,550 122
low 0,400 84
high 1,210 265
med 0,810 185
UTN08-08A
low 0,700 135
high 2,100 460
UTN12-12A
med 1,600 345
low 1,350 385
high 2,500 505
med 1,800 380
UTN16-16A
low 1,400 290
high 3,500 750
med 2,350 535
UTN22-22A
low 1,800 370
high 5,600 1300
UTN30-30A
med 4,600 1090
low 3,800 870
UTN
11MOTORS ELECTRICAL DATA
12ACCESSORIES
The following table describes the characteristics of the motors at available
CD - Flush wall-mounted speed selector
working conditions.
Flush wall-mounted control panel is provided
with a 4
positions (3speed + stop) rotation selector.
Legend:
The CD control panel allows the ON/OFF and fan speed
VrOperation speedXC
selection of the high pressure fan coil unit.
P
Power input
ASS
IASS Operation current
CDE - wall mounted speed selector
Wall mounted control panel is provided
with a 3
positions (3 speed ) and switch ON/OFF .
The CDE control panel allows the ON/OFF and fan
speed selection of the high press
ure fan col unit.
TD - Wall mounted control with speed
selector, thermostat and summer-winter
selector
Wall mounted control panel complete with
fan speed selector, electromechanical
thermostat and cooling / heating mode
selector.
Fan speed control, regulation of the room temper
ature and cooing heng
mode selection:
- manual setting of the fan speed;
- room temperature regulation both in cooling / heating mode, by means
of fan start / stop, at a manually set temperature.
TDC - Wall mounted control with speed
selector and thermostat
Wall mounted control panel complete with fan
speed selector, electromechanical ther
mostat
and cooling / heating mode selector.
Fan speed control, regulation of the room
temperature and cooling / heating mode selection:
- manual setting of the fan speed;
- room temperature regulation both in cooling / heating mode, by
mean
fan start/stop, at a manually set temperature.
TD4T - Wall mounted control with
speed selector, thermostat and
summer-winter selector, for 2/4 pipe
system with valves
Wall mounted control panel provided with
fan speed selector, electromechanical
thermostat, and cooling / heating mode
selector; if installed it controls regulating valves.
Fan speed control and regulation of the room tem
perature:
- manual setting of the operation fan speed;
- regulation of the room temperature for 2 and 4 pipe systembn
heating and cooling mode, by means of fan start/stop at a may
temperature and by meansof openv
24UT66000806 - 02
All copying, even partial, of this manual is strictly forbidden
UTN
12ACCESSORIES
MICRONET- Advanced microprocessor control
panels for ergo solution
MICRONET is the control panel suitable for the
connection to the ERGO SOLUTION. Microprocessor
control panels for wall installation complete with fan
speed selector, electronic thermostat and cooling /
heating mode selector; for the automatic control of
the fan working on the valves and electric heater, if
installed.
Fan speed control, room temperature regulation and
cooling / heating mode selection:
- room temperature regulation both in the cooling and heating mode, by
means of fan start/stop, at a manually set speed;
- room temperature regulation both in the cooling and heating mode, by
means of the automatic regulation of the fan speed;
- timer function (not available for MICROPRO-D);
- cooling / heating mode selection in the following way:
- manual in built;
- automatic according to the water temperature;
- automatic according to the room temperature;
- control of the ON/OFF valves for 2 or 4 pipe system;
- control of the electric heater as integration or replacement of the hot
water heat exchanger with delayed stop of the fan (2 min.).
The MICRONET control panels are provided also with contacts for external
signals in order to enable or disable the unit operation.
- terminals for the connections with external signals in order to enable or
disable the unit operation;
- terminals for the connections with external signals in order to enable or
disable the ECONOMY set point (only if combined with ERGO software)
- air temperature probe
- water temperature probe
- RS485
- built-in MODBUS communication protocol
- Built-in Polarity and termination resistance
- Protocollo di comunicazione MODBUS integrato
- Resistenze di polarizzazione e terminazione integrate attivabili tramite jumper
MICRO e MICRO-D - Microprocessor control panels
Microprocessor control panels for in built (MICRO) or
wall (MICRO-D) installation, complete with fan speed
selector, electronic thermostat and cooling / heating
mode selector; for the automatic control of the fan
coil unit.
Fan speed control, room temperature regulation and
cooling / heating mode selection:
- regulation of the room temperature both in the cooling
and heating mode, by means of fan start/stop, at a manually set temperature;
- regulation of the room temperature, both in the cooling and heating mode,
by means of the automatic regulation of the fan speed;
- timer function (not available for MICRO-D);
- cooling / heating mode selection in the following ways:
- manual in built;
- automatic according to the water temperature (with the SW water
probe; option).
MICROPRO e MICROPRO-D - Microprocessor control
panels
Microprocessor control panels for in built (MICROPRO)
and wall (MICROPRO-D) installation complete with
fan speed selector, electronic thermostat and cooling
/ heating mode selector; for the automatic control of
the fan working on the valves and electric heater, if
installed.
Fan speed control, room temperature regulation and
cooling / heating mode selection:
- room temperature regulation both in the cooling and heating mode,
by means of fan start/stop, at a manually set speed;
- room temperature regulation both in the cooling and heating mode, by
means of the automatic regulation of the fan speed;
- timer function (not available for MICROPRO-D);
- cooling / heating mode selection in the following way:
- manual in built;
- manual remote (centralized);
- automatic according to the water temperature (with the SW water
probe, option for MICROPRO-D, included in MICROPRO kit);
- automatic according to the room temperature (with air temperature probe,
option);
- control of the ON/OFF valves for 2 or 4 pipe system;
- control of the electric heater as integration or replacement of the hot
water heat exchanger with delayed stop of the fan (2 min.).
The MICROPRO / MICROPRO-D control panels are provided also with contacts
for external signals in order to enable or disable the unit operation.
SW - Water temperature lectronic probe for
microprocessor control panels
Water probe for the MICRO, MICRO-D and
MICROPRO-D control panels:
automatic selection of the cooling / heating
operation mode.
Connected directly to the microprocessor control
panel, this probe measures the water temperature inside the heat exchanger.
If the temperature is lower than 17°C the unit works in cooling mode and the
temperature range of the control panel will be referred to the cooling mode
(19/31°C); if the temperature registered is higher than 37°C the unit works
in heating mode and the temperature range of the control panel will be
referred to the heating mode (14/26°C).
If the temperature registered is between 17°C and 37°C the control panel
will disable the unit operation.
The SW water probe is included in the MICROPRO and MICRONET kit.
TC - Fan stop thermostat: elecromechanical
thermostat for minimum water temperature
during heating
Fan stop thermostat with automatic resetting, it stops
the fan motor assembly when the water temperature
in the heat exchanger decreases under the set value
(42°C).
Usefull only in the heating mode for installation on the finned pack of the
heat exchanger.
IPM - Power interface for the connections to the
control panels MICRO-D and MICROPRO-D
The IPM power board permits to use MICRO-D and
MICROPRO-D microprocessor-based control panels on
the whole range of UTN air handling units, even for
models with current consumation greayer than 1A.
The capacity of the IPM contacts is 16A, IP30 rating.
The use of the IPM power board matched with the
microprocessor controls is:
- recommended for the UTN06, UTN08 air handling unit;
- compulsory for all the others models.
25
All copying, even partial, of this manual is strictly forbidden
UT66000806 - 02
UTN
12ACCESSORIES
TA - Wall mounted room thermostat
Room thermostat for wall installation.
Automatic regulation of the room temperature:
- only in the heating mode working on the fan motor
assembly and on the regulating valve, if installed (ON/
OFF operation);
- only in the cooling mode working on the fan motor assembly and on the
regulating valve, if installed (ON/OFF operation);
- both in cooling and heating mode, with remote mode selection working on
the fan motor assembly and on the regulating valve, if installed (ON/OFF
operation).
TA2 - Wall mounted room thermostat with summer/
winter selector
Wall mounted room thermostat with cooling / heating
mode selector.
Automatic regulation of the room temperarure both in
heating and cooling mode, working on the fan motor
assembly and on the regulating valve if installed (ON/OFF operating).
CSD - Wall mounted control for proportional opening
and closing of the PA90 motorized louver
50%
Designed for wall installation it allows the proportional
opening and closing from 0 to 100% of the PA90 outdoor
air intake motorized louver
0%100%
MAF / MAFO - Air intake
modules with filter
Made of galvanized steel sheet,
these modules permit to filter the
air sucked up by the unit and also
to connect the unit to the intake
channeling.
2 version are proposed depending
on the guaranteed filtering degree:
MAF: air intake module with flat
filter made of acrylic material,
self-extinguishing in class 1, with filtering class G2.
MAFO: air intake module with corrugated filter made of acrylic fiber, selfextinguishing in class 1, with filtering EU4.
PCOC - Connecting panel to
rectangular ducts
Manufactured in galvanised sheet
steel, the PCOC connection panels
are used for the connection of
rectangular ducts with flanges
and with other flanged
accessories. They can be
installed on both the intake and
delivery line.
They are made up of a rectangular
panel that is to be secured to the machine (or to another accessory with
similar drilling, for example, MAF, MAFO, RE etc..) coupled to a flanged
sleeve that represents the starting point for rectangular ducts of the type
commonly used in distribution plants.
PCOF - Connecting panel to
flexible ducts
Manufactured in galvanised sheet
steel, the PCOF connection panels
are used to connect to air
distribution plants achieved by
means of hoses or to other
dedicated accessories. They can
be installed on both the intake
and delivery line (in this case the
hose should be insulated).
They are made up of a rectangular panel that is to be secured to the machine
or to another accessory with similar drilling (i.e. MAF, MAFO, RE etc..)
complete with circular collars (Ø 200 mm) that represent the starting point
for the hoses of the type commonly used in distribution plants.
Model UTN 06-06A 08-08A 12-12A 16-16A 22-22A 30-30A
n° of holes223445
V - M - R 3-way valve, on-off actuator
and hydraulic connections kit
IThe system allows the regulation of the
ambient temperature by stopping the water
flow into the heat exchanger.
Available for 2 pipe and 4 pipe systems, the
kit is made of the components below indicated:
Valve body (V): 3-way with in-built by-pass
(4 connections):
- 3/4” for the models UTN 6, UTN 6A, UTN 8,
UTN 8A
- 1” for the models UTN 12, UTN 12A, UTN
16, UTN 16A
Actuator (M): normally closed, electrothermal
type, 230V single phase, with ON-OFF
operation, it works directly on the valve shutter.
Hydraulic connections kit (R): made of copper tubes and brass connections,
complete with balancing valve, is different according to the models (standard
coil or additional coil in case of 4 pipe systems) and for the unit water
connection side.
The hydraulic connections kit is not available for the UTN22 - 22A and UTN30
- 30A units.
VRCV / VRCH - Auxiliary trays for collecting condensate
Auxiliary trays for collecting condensate, used for collecting any condensate
that might form on the adjusting valves, the hydraulic unions and the
holdfasts during the cooling operating mode.
The trays are made of galvanized metal sheet, with condensate discharge
pipe (φ17 mm) setup for being connected to a flexible rubber tube, like that
which has been envisaged for the condensate discharge trays of the basic
unit.
They are available for:
UTN units installed vertically, VRCV.
UTN units installed horizontally, VRCH.
UT66000806 - 02
All copying, even partial, of this manual is strictly forbidden
26
UTN
12ACCESSORIES
KSC - Condensate removal kit
This device allows to overcome displacements
in the condensate drain.
The pump can drain water up to 8 l/h and it is
completed by a non return valve on the
discharge side.
BP - Kit batterie di post
riscaldamento
BP 1 or 2 row reheating exchangers
are designed for installation on the air
outlet of the UTN air conditioning and
thermal ventilating units.
NOTE:
The BP module has holes like those
on the machine air intake, on the extremity
turned toward the air outflow ducts. This allows you to attach all the
accessories that can be directly applied on the machine (PCOC, PCOF,
GAT, etc…).
RE - Supplementary heating elements
Useful as heating integration to the hot
water system, the RE kit is made of an
electric heater with safety thermostat
(automatic and manual resetting) and
power relay.
The RE electric heater kit has to be matched
with the MICROPRO-D control panel and
with the IPM power board.
PA90 - Outdoor air inlet motorized
louver
The outdoor air inlet motorized louvre
is intended for replacing the air in
the room directly from the airhandling unit. The amount of outdoor
air that will be let into the room, after
having been filtered and treated
thermally, may be regulated
proportionally from 0 to 100% by
means of a servomotor controlled
by a rotary potentiometer that is inside the specific CSD control, which is
designed for flush wall-mounting installations.
Kit PA90, as shown in figure (1), essentially comprises the following
components:
A) Outdoor air inlet louvre made of galvanized steel sheet and setup for being
connected to the machine, at one end, and to the other required accessories.
B) Servomotor connected directly to the louvre’s baffle, with a protection
rating of IP54 and power supply of ~ 24V. The louvre may be opened or
closed automatically at the signal of the external auxiliary contacts (not
supplied) such as antifreeze thermostats, timers, etc., with the possibility
of connecting multi-servomotors in parallel to an individual opening-closing
control.
C) 230V - 24V voltage transformer, complete with support terminal strip
housed inside the specific electrical box, which functions as a mechanical
protection for preventing the access to the connecting terminal strip and to
the transformer itself.
D) Self-threading fixing screws.
All copying, even partial, of this manual is strictly forbidden
GA / GAT - Vibration dampers
Manufactured in galvanized sheet
steel, the GA/GAT connection
panels are used to connect to
rectangular ducts equipped with
flanges and other flanged
accessories.
They are made up of a rectangular
panel that is to be secured to the
machine or to another accessory
with similar drilling (i.e. MAF,
MAFO, RE etc...) coupled by means of a flexible bellow to a flanged sleeve
that rapresents the starting point for rectangular ducts of the type commonly
used in distribution plants.
If the vibration damping joint is used together with the electrical heating
elements module (accessory RE) a GAT joint made of heat-resistant silicone
material is to be fitted on the delivery line.
TFA - Not insulated flexible ducts
Uninsulated flexible duct for the connections to the air distribution with φ
200 mm diameter, supplied in 6 m lenght undivisible.
TFM - Insulated flexible ducts
Insulated flexible duct for the connections to the air distribution with φ
200 mm diameter, supplied in 6 m lenght undivisible. The insulation of
the duct is optained by means of fiberglass, thickness 25 mm with 16
3
density.
Kg/m
TP - Plastic cap
Plastic cap φ 200 mm for the closing on the PCOF, of the air outlet not used.
CA / CAF - Air inlet plenum box
Intake Plenum box in galvanised sheet metal
complete with circular collars (Ø 200 mm)
for the connection, by means of hoses and
intake grids with fixed fins, to pocket type
structures, to increase the free air flow cross
section.
Sized to be adaptable to the modular structure
of the ceiling panels, they are equipped with
2 or 3 circular collars so that they can be connected, following their suitable
combination, to all the heater fans of the UTN range. The CA version is
equipped with just the grid alone whereas the CAF version is also equipped
with a flat filter in acrylic material, with filtering rating G2, housed in the
standard frame. The filter of this second type of intake box can be serviced
(cleaned) on a periodic basis without having to access the unit fitted behind
the ceiling panels or in a service room.
GM - Alluminium air outlet grille
Air delivery grids with double row of adjustable
fins in anodised aluminium, equipped with
galvanised sheet metal frame that is used to
wall-mount the grids or to fit them directly on
the delivery head of the machine.
The galvanised sheet metal frame is drilled at
one end so that it can be secured directly to
the delivery head of the heater fan (or to accessories such as the additional
RE electrical module).
GR - Alluminium air inlet grille
Air intake grids with single row of fins in anodised
aluminium, equipped with galvanised sheet metal
frame that is used to wall-mount the grids or to fit
them directly on the intake head of the machine.
The galvanised sheet metal frame is drilled at one
end so that it can be secured directly to the intake
head of the heater fan (or to accessories such as the
MAF and MAFO filtering units).
27
UT66000806 - 02
UTN
13MAINTENANCE
The maintenance operations for the UTN air conditioning and hot-air heating
units are limited to the periodic cleaning of the air filter (provided on MA/F and
MA/FO accessories) and the heat exchanger, and the checking of the working
efficiency of the condensate discharge.
Only skilled personnel may perform the aforesaid maintenance.
Pay utmost attention during the maintenance operations: accidentally
coming into touch with some of the metallic parts might cause injuries
therefore wear safety work gloves.
Every time the units are started after long dwell times, make sure that air is
NOT present inside the heat exchanger.
The motor is maintenance-free since it is equipped with self-lubricating
bearings.
For safety reasons, before performing any maintenance or cleaning
operations, turn off the equipment and cut voltage by turning the line
switch.
UT66000806 - 02
40010 Bentivoglio (BO)
Via Romagnoli, 12/a
Tel. 051/8908111
Fax 051/8908122
www.galletti.it
28
All copying, even partial, of this manual is strictly forbidden