Total heat recovery reversible multi-purpose heat pumps - DC INVERTER
HWMC
1 THE SERIES HWMC ......................................................................................................................................................................................................................5
1.1 Field of application
1.2 Models and versions
1.3 Description of components
1.4 Plumbing diagrams
2 INSPECTION, HANDLING, DIMENSIONS AND SITING
2.1 Inspection
2.2 Handling
2.3 Dimensions
2.4 Siting
2.4.1 Installation clearance requirements
2.5 Position of vibration dampers
3 WATER AND ELECTRICAL CONNECTIONS
3.1 Water connections
3.1.1 Water connections
3.1.2 Recommended water circuit
3.1.3 Filling the system
3.1.4 BASE Multi-purpose system DIAGRAM
3.2 Electrical connection
3.3 Electrical specifications
4 STARTING UP
4.1 Preliminary checks
5 OPERATING LIMITS
5.1 Operating limits in chiller mode
5.2 Operating limits in heat pump mode
5.3 Operating limits in DHW total recovery
5.4 Operating limits only in DHW production
5.5 Thermal carrier fluid
6 CONTROL AND SAFETY DEVICES
6.1 Control devices
6.1.1 Service thermostat
6.1.2 Control device settings
6.2 Safety devices
6.2.1 High pressure switch
6.2.2 Low pressure switch
6.2.3 Anti-recycle timer
6.2.4 Antifreeze thermostat
6.2.5 Water differential pressure switch
6.2.6 Water safety valve
6.2.7 Safety device settings
7 ROUTINE MAINTENANCE AND CHECKS
7.1 Checks to be performed by the user
7.2 Checks and maintenance to be performed by specialised personnel
8 RETIRING THE UNIT
9 TECHNICAL CHARACTERISTICS
9.1 Rated technical data of heat pumps
10 COOLING CIRCUIT DIAGRAMS
11 TROUBLESHOOTING
I REFRIGERATORI D'ACQUA E LE POMPE DI CALORE SONO CONFORMI
ALLA DIRETTIVA 97/23/CE (PED) ATTRAVERSO MODULO D1,
APPROVATO DALL'ENTE TERZO NOTIFICATO ICIM N°0425.
The technical and dimensional data provided herein may undergo changes in
connection with product improvements.
2
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
HWMC
The unit data are reported on the rating label in this page.
THE LABEL SHOWS THE FOLLOWING DATA:
- Series and size of the unit
- Date of manufacture
- Main technical data
- Manufacturer
- The label is applied on the unit, usually on the enclosing panels beside
the condenser coil
IMPORTANT: NEVER REMOVE THE LABEL
- Serial number of the unit
- The serial number permits to identify the technical characteristics and
the components installed
- Without this datum it will be impossible to identify the unit correctly
Galletti S.p.A. via L.Romagnoli 12/a
40010 Bentivoglio (BO) Italia
Made in Italy
CATEGORIA 2
Serial number
Code
Date of production
Cooling capacity (W)
Heating capacity (W)
Power supply
Power input (kW)
Weight (kg)
Max power input (kW)
Max running amperage (A)
HP Power input (kW)
Refrigerant
Max refrigerant pressure (bar)
Max refrigerant temperature (°C)
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
3
HWMC
GENERAL CAUTIONARY NOTES
- Please keep this manual complete and in good condition for the entire life of the machine.
- Carefully read all the information contained in this manual, paying special attention to sections marked “Important” and “WARNING”; failure to comply
with the instructions provided could result in injury to persons or damage to the equipment.
- Should a fault occur, consult this manual and if necessary contact the nearest Galletti S.p.A. service centre.
- All installation and maintenance operations must be carried out by qualified personnel, unless otherwise indicated in this manual.
- FIRST START-UP MAY BE CARRIED OUT SOLELY BY QUALIFIED TECHNICIANS DULY AUTHORIZED BY GALLETTI S.P.A. (SEE ENCLOSURE)
- Before performing any work on the unit, disconnect it from the power supply.
- Failure to comply with the rules provided in this manual will result in the immediate invalidation of the warranty.
- Galletti S.p.A. shall not accept any liability for injury or damage resulting from improper use of the equipment or failure to comply with the directions
provided in this manual and on the unit itself.
- It is mandatory to install filters to protect the heat exchangers. Failure to do so will invalidate the warranty.
- For any further information, contact the manufacturer: info@galletti.it
- To get the weight of the unit, refer to the User Manual, Rated technical data table.
IMPORTANT:
1) (a) Do not use heat transfer fluids other than those specified.
(b) This unit is not suitable for use in Atex environment or with inflammable heat transfer fluids.
(c) Use original factory parts only.
(2) Use appropriate PPE (refrigerant protection gloves, protective goggles).
(3) If protection grilles (accessory) are not provided or if the unit can be reached by unauthorized persons, special protection barriers should be provided
in order to prevent access to the finned coil.
(4) Upstream from the power supply it is necessary to install a differential switch for protection against earth connection failure.
SAFETY SYMBOLS
Carefully read this manual
USE APPROPRIATE PPE (REFRIGERANT PROTECTION GLOVES, PROTECTIVE GOGGLES).
WARNING
Use individual protective
devices
4
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
HWMC
1 THE SERIES HWMC
1.1 FIELD OF APPLICATION
The DC INVERTER multi-purpose HWMC units have been designed to cool
and heat water for air conditioning and heating systems and for the production
of DHW for residential or commercial use. The units are “real” multipurpose
units, with 4 water collections, whose operating modes are described below:
1. Cold water production in summertime mode, for the air conditioning
system (air condensing system on the finned exchanger)
2. Cold water production in the summertime mode, for the air conditioning
system, with TOTAL CONDENSATION HEAT RECOVERY (for the production
of DHW by means of a dedicated plate exchanger)
3. Production of hot water in wintertime mode, for the heating system,
functioning as a traditional heat pump (air evaporation on the heat
exchanger side and water condensation on the dedicated plate heat
exchanger on the system side)
4. Domestic hot water production in winter time mode, temporarily stopping
hot water production for air heating purpose (DHW priority);
5. DHW production only (in particular in mid seasons and in summertime
and wintertime)
Warning
When reference is made to the production of domestic
hot water, what is meant is the storage of thermal energy in a tank of
“technical” water. Water for domestic use must be heated by means
of a stainless steel coil contained inside the storage tank, in this way
it is possible to avoid storing domestic water and it is not necessary
to provide for an anti-Legionella cycle (see recommended plumbing
layouts for further details).
Warning
HWMCunits are NOT suitable for use as “rapid” heaters."
The HWMC units are designed for outdoor installation (protection rating
IP24), in a position not accessible to the public.
If protection grilles (accessory) are not provided or if the unit can be reached
by unauthorized persons, special protection barriers should be provided in
order to prevent access to the finned coil.
Do not install the unit in places where inflammable gases or powders
are present.
Winter configuration
V1V2
V5
V4
V3
HEAT
PUMP
DHW / Springtime (operating 365 days a year)
V1V2
V5
V4
V3
DHW
S2S1
S2S1
DHW
S3
Summer configuration (total heat recovery)
V4
V4
V1V2
V5
V3
HEAT
PUMP
Summer configuration
V1V2
V5
V3
S2S1
DHW
DHW
S2S1
S3
HEAT
PUMP
S3
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
HEAT
PUMP
S3
5
HWMC
1 THE SERIES HWMC
1.2 MODELS AND VERSIONS
The HWMC series features 5 models of varying capacity, indicatively from
10 to 29 kW in cooling versions (9-32 kW in heating versions) in nominal
conditions (ref. EN14511).
All models are charged with R410A refrigerant and equipped with compressors
optimised for heat pump applications and domestic hot water production in
all seasons.
N.B. The choice of some options may preclude the choice of others or make
some other fields become mandatory. Contact Galletti S.p.A. for verification
Complete unit code HWMC010H0AAA100CE0000000
Version 0
Single compressor
400 - 3N - 50 + circuit breakers 2
Single-phase + circuit breakers 4
0
Tan d em T
Model (size) 10
Operation
Supply voltage 0
Standard 400 - 3N - 50
Single-phase M
R410A high efficiency
2 Modulating pumps (system+DHW side) 5
H
H
0
Refrigerant A
(Field 1) Expansion valve A
(Field 2) Pump and accessories
2 EC pumps (system+DHW side) 6
External electric heating element control 2
MYCHILLER BASE remote control (option 1 - 3 field 13 disabling) B
MYCHILLER PLUS remote control (option 1 - 3 field 13 disabling) P
A
Revision A
Initial
A
Electronic valve
(Field 3) Inertial buffer tank 0
Present, system side S
(Field 4) Auxiliary contacts 0
Standard with condensation control
Additional protection for 1 pump and tank 2
Additional protection for 2 pumps and tank 4
A
1
Absent
0
Absent
User tank sensor 1
Opt 1 + Opt 2 3
(Field 5) Fans C
BLDC with electronic control E
(Field 6) Antifreeze kit E
Base (plate exchangers only)
Additional protection for 1 pump 1
Additional protection for 2 pumps 3
(Field 7) Sound insulation 0
Compressor compartment soundproofing 1
Compressor silencing housings 2
0
Opt 1 + Opt 2 3
(Field 8) Cooling accessories 0
Refrigerant pressure gauges M
(Field 9) Remote control 0
ADVANCED pGD1 remote control C
(Field 10) Special exchangers 0
C
Absent
(Field 11) Protective grille 0
E
0
None
0
Absent
0
Standard
Copper - copper R
Cataphoresis C
Corrosion-proof B
Hydrophilic GB
(Field 12) Additional options 0
Exchanger heating cable 1
(Field 13) Additional cards 0
O
Absent
Present G
Absent
RS485 (Carel / Modbus) 1
Clock card 2
0
0
Absent
LON car d 3
0
6
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
HWMC
1 THE SERIES HWMC
1.3 DESCRIPTION OF COMPONENTS
HWMC 10 EC PUMPS
HWMC 10 EC PUMPS
Description
12 Circulation pump
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
7
HWMC
1 THE SERIES HWMC
1.3 DESCRIPTION OF COMPONENTS
HWMC 10
Description
1 R410A - air exchanger
2 R410A - water exchanger
3 Fan
4 Water differential pressure switch (no. 1 fan compartment)
5 Automatic air vent valve
6 Expansion tank (fan compartment)
7 Buffer tank
8 Refrigerant solenoid valve
9 Electronic thermostatic valve
10 Water safety valve
11 Liquid receiver (fan compartment)
12 Circulation pump
13 Compressor
14 Refrigerant filter
15 Low pressure switch
16 High pressure switch
17 Water pressure gauge
18 Water filling point
8
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
HWMC
1 THE SERIES HWMC
1.3 DESCRIPTION OF COMPONENTS
HWMC 13 - 18 EC PUMPS
Description
12 Circulation pump
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
9
HWMC
1 THE SERIES HWMC
1.3 DESCRIPTION OF COMPONENTS
HWMC 13 - 18
Description
1 R410A - air exchanger
2 R410A - water exchanger
3 Fan
4 Water differential pressure switch (no. 1 fan compartment)
5 Automatic air vent valve
6 Expansion tank (fan compartment)
7 Buffer tank
8 Refrigerant solenoid valve
9 Electronic thermostatic valve
10 Water safety valve
11 Liquid receiver (fan compartment)
12 Circulation pump
13 Compressor
14 Refrigerant filter
15 Low pressure switch
16 High pressure switch
17 Water pressure gauge
18 Water filling point
10
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
HWMC
1 THE SERIES HWMC
1.3 DESCRIPTION OF COMPONENTS
HWMC 23 - 29 FANSHWMC 23 - 29 EC PUMPS
HWMC 23 - 29 EC PUMPS
Description
12 Circulation pump
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
11
HWMC
1 THE SERIES HWMC
1.3 DESCRIPTION OF COMPONENTS
HWMC 23 - 29
Description
1 R410A - air exchanger
2 R410A - water exchanger
3 Fan
4 Water differential pressure switch
5 Automatic air vent valve
6 Expansion tank (fan compartment)
7 Buffer tank
8 Refrigerant solenoid valve
9 Electronic thermostatic valve
10 Water safety valve
11 Liquid receiver (fan compartment)
12 Circulation pump
13 Compressor
14 Refrigerant filter
15 Low pressure switch
16 High pressure switch
17 Water pressure gauge
18 Water filling point
12
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
HWMC
1 THE SERIES HWMC
1.4 PLUMBING DIAGRAMS
HWMC (EVAPORATOR AND PUMP)HWMC (EVAPORATOR)
OPTIONAL
SYSTEM SIDE
DHW SIDE
OPTIONAL
SYSTEM SIDE
Legend VR Filling valve
VS Safety valve
EV Evaporator
PD Differential pressure switch
MA Water pressure gauge
VAS Air vent valve
VE Expansion tank
P Pump
RS Drainage valve
RC Water filling cock
VU Check valve
DHW SIDE
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
13
HWMC
1 THE SERIES HWMC
1.4 PLUMBING DIAGRAMS
HWMC (EVAPORATOR AND TANK)HWMC (EVAPORATOR, PUMP AND TANK)
FRAME 2 ONLY
OPTIONAL
SYSTEM SIDE
OPTIONAL
DHW SIDE
FRAME 2 ONLY
SYSTEM SIDE
DHW SIDE
Legend VR Filling valve
VS Safety valve
EV Evaporator
PD Differential pressure switch
MA Water pressure gauge
VAS Air vent valve
VE Expansion tank
P Pump
RS Drainage valve
RC Water filling cock
VU Check valveSA Buffer tank
14
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
HWMC
1 THE SERIES HWMC
1.4 PLUMBING DIAGRAMS
OPTIONAL
SYSTEM SIDE
HWMC (EVAPORATOR AND DUAL PUMP)HWMC (EVAPORATOR, DUAL PUMP AND TANK)
DHW SIDE
FRAME 2 ONLY
SYSTEM SIDE
OPTIONAL
DHW SIDE
Legend VR Filling valve
VS Safety valve
EV Evaporator
PD Differential pressure switch
MA Water pressure gauge
VAS Air vent valve
VE Expansion tank
P Pump
RS Drainage valve
RC Water filling cock
VU Check valveSA Buffer tank
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
15
HWMC
2 INSPECTION, HANDLING, DIMENSIONS AND
SITING
2.1 INSPECTION
On receiving the unit, check that the packing is intact: the machine left the
factory in perfect conditions and after thorough inspection.
Should you detect any signs of damage, immediately report them to the
carrier and note them on the delivery slip.
Galletti S.p.A. must be notified of the entity of the damage within 8 days of
the delivery date.
Check that the following items are present:
- putting into service report,
- wiring diagram,
- warranty certificate and list of authorised service centres,
- make sure that this manual is intact (40 pages).
2.2 HANDLING
During handling it is compulsory to check dimensions, weights, centre of
gravity and anchorages. Check as well that lifting and positioning devices
conform to the current safety regulations.
The unit leaves the factory screwed onto a wooden pallet, which allows
it to be easily conveyed with a forklift truck. After removing the unit from
the pallet, handle it gently, without applying excessive pressure on the side
panels, finned coil and fan grille.
You should collect and separate the packing materials (wood, cardboard,
nylon etc.) and make them available for recycling in order to minimise their
environmental impact.
Before lifting, remove the screws fastening the base of the unit to the wood
platform.
The unit should be lifted using Ø1½” GAS steel pipes at least 3mm thick,
to be inserted in the round holes provided on the base side members (see
figure) and identified by means of stickers. The pipes, which should protrude
by at least 250-300mm on every side, must be slung with ropes of equal
length secured to the lifting hook (provide stops at the ends of the pipes to
prevent the ropes from slipping off due to the weight).
Use ropes or belts whose length exceeds the machine height and place
spacer boards and bars on the top of the unit to avoid damaging the sides
and upper part of the unit itself.
At this point, before final positioning, it is possible to install the vibrationdamping supports (optional).
WARNING: In all lifting operations make sure that the unit is securely anchored
in order to prevent accidental falls or overturning.
16
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
HWMC
2 INSPECTION, HANDLING, DIMENSIONS AND
SITING
2.3 DIMENSIONS
HWMC 10 ÷ 13 ÷ 18
Legend:
1 Water inlet 1" ¼ female
2 Sanitary hot water inlet 1" ¼ female
3 Water outlet 1" ¼ female
2 Sanitary hot water outlet 1" ¼ female
5 Safety valve discharge outlet with rubber ring holder
6 Water supply ½" male (optional tap)
7 Water drainage ½" female
8 Sanitary hot water drainage ½" female
9 Power supply Ø 28 mm
10 Electric control board
11 Fastening points for vibration dampers
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
17
HWMC
2 INSPECTION, HANDLING, DIMENSIONS AND
SITING
2.3 DIMENSIONS
HWMC 23 ÷ 29
Legend:
1 Water inlet 1" ¼ female
2 Sanitary hot water inlet 1" ¼ female
3 Water outlet 1" ¼ female
2 Sanitary hot water outlet 1" ¼ female
5 Safety valve discharge outlet with rubber ring holder
6 Water supply ½" male (optional tap)
7 Water drainage ½" female
8 Sanitary hot water drainage ½" female
9 Power supply Ø 28 mm
10 Electric control board
11 Fastening points for vibration dampers
18
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
HWMC
2 INSPECTION, HANDLING, DIMENSIONS AND
SITING
2.4 SITING
It is important to bear in mind the following aspects when choosing the best
site for installing the unit:
-size and origin of water pipes;
-location of the power supply;
-solidity of the supporting surface;
-avoid obstacles to the outflow of air from the fan which could cause back
suction (see section on “installation clearance requirements”);
-direction of prevalent winds: (position the unit so that prevalent winds
do not alter the fan air flow). A prevalent wind blowing from a direction
opposite to the fan air flow will reduce the maximum air temperature
to a lower value than specified in the operating limits, a wind blowing
in the same direction as the fan air flow will increase the minimum air
temperature to a higher value than specified in the operating limits. Also
in the heat pump mode, wind may have the effect of reducing the unit's
operating range.
-avoid the possible reverberation of sound waves; do not install the unit
in narrow or cramped spaces;
-ensure adequate accessibility for maintenance or repairs (see section
on “installation clearance requirements”).
This device is not intended to be used by children or by people with
physical, sensory or mental impairments, except under supervision. Make
sure that children do not have access to the device.
2.4.1 INSTALLATION CLEARANCE REQUIREMENTS
To guarantee the proper functioning of the unit and access for maintenance
purposes, it is necessary to comply with the minimum installation clearance
requirements shown in figures 1, 2 and 3.
There must be no obstacles blocking the path of the air flow from the fans.
Avoid any and all situations of backflow of hot air between air outlet and
inlet of the unit.
If even only one of the above conditions is not fulfilled, please contact the
manufacturer to check for feasibility.
In the design of the HWMC series, special care has been taken to minimise
noise and vibrations transmitted to the ground.
Even greater insulation may be obtained, however, by using vibration damping
base supports (available as optional accessories).
If vibration damping base supports are adopted, it is strongly recommended
also to use vibration damping couplings on the water pipes.
Whenever the unit is to be sited on unstable ground (various types of soil,
gardens, etc.) it is a good idea to provide a supporting base of adequate
dimensions.
Warning
produce condensation..
while operating in heating or DHW mode, the units
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
19
HWMC
2 INSPECTION, HANDLING, DIMENSIONS AND
SITING
2.4 SITING
2.4.1 INSTALLATION CLEARANCE REQUIREMENTS
1
HWMC 10 ÷ 18
COIL PLUMBING CONNECTION SIDE
COIL SIDE
ELECTRIC CONTROL BOARD
2
ELECTRIC CONTROL BOARD
HWMC 23 ÷ 29
COIL PLUMBING CONNECTION SIDE
COIL SIDE
20
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
HWMC
2 INSPECTION, HANDLING, DIMENSIONS AND
SITING
2.5 POSITIONING OF VIBRATION DAMPERS (ACCESSORY)
HWMC NO. OF VIBRATION DAMPERS
10 - 18 4
23 - 29 4
Vibration dampers
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
21
HWMC
3 WATER AND ELECTRICAL CONNECTIONS
3.1 WATER CONNECTION
All units belonging to the HWMC series are equipped with water differential
pressure switch, safety valve, water differential pressure switch, safety valve,
water pressure gauge, automatic vent valve and drainage valve.
According to the specific configuration they can be equipped with pump,
expansion tank and buffer tank.
3.1.1 WATER CONNECTIONS
Warning
connections tightly in place using a hexagonal wrench or make sure
that they do not rotate to prevent the pipes inside the unit from being
damaged (see figure).
3.1.2 RECOMMENDED WATER CIRCUIT
Warning!
are no open flames in proximity to or inside the unit.
When setting up the water circuit, it is advisable to equip it with:
- valves for regulating (VI) the unit on the water pipes, immediately upstream
and downstream from the unit itself, to be used in the event maintenance
work is required;
- a mechanical filter supplied as standard (FM) (MANDATORY!) on the
pipes feeding the unit, in proximity to the latter;
- a mechanical filter supplied as standard (FM) (MANDATORY!) and a
check valve (VNR), on the supply line upstream from the filling tap (RC);
- an air vent valve at the highest point of the circuit;
- escape pipe for the safety valve (VS), which, in the event the safety valve
opens, diverts the jet of water to an area where it cannot harm persons
or damage property (Important!);
- vibration-damping couplings (GA) on the pipes to prevent vibrations from
being transmitted toward the system.
Important!It is advisable to ensure that the pipes connected upstream
and downstream from the unit are not smaller in diameter than the
plumbing connections of the unit itself.
While connecting the taps, hold the unit's plumbing
when making the plumbing connections, make sure there
Important! During winter time periods of quiescence the water circuit must
be emptied to prevent damages caused by freezing; in alternatively, the
circuit may be filled with a mixture of water and glycol; the percentage
of glycol necessary will depend on the lowest forecast temperature
(see table):
Percentage by weight of
ethylene glycol (%)
00
10-4
15-8
20-14
30-18
Important! If different antifreeze product is to be used, please contact
the manufacturer.
Failure to install filters and vibration dampers may cause problems of clogging,
breakages and noise, for which the manufacturer may not be held liable.
Mixture freezing temperature
(°C)
22
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
HWMC
3 WATER AND ELECTRICAL CONNECTIONS
3.1 WATER CONNECTION
3.1.2 RECOMMENDED WATER CIRCUIT
FRAME 2 ONLY
SYSTEM SIDE
OPTIONAL
Legend
VS Safety valve
EV Evaporator
PD Differential pressure switch
MA Water pressure gauge
VAS Air vent valve
SA Buffer tank
VE Expansion tank
RS Drainage valve
RC Water filling cock
VI Regulating valve (not supplied)
GA Vibration-damping coupling (not supplied)
FM Mechanical filter (MANDATORY)
VNR Check valve (not supplied)
P Pump
3.1.3 FILLING THE SYSTEM
- Before you start filling, make sure that the system drainage cock is
closed.
- Open all the air vent valves of the system and of the indoor units and
chiller.
- Open the system regulating devices.
- Start filling the system by slowly opening the water fill valve (optional).
- When water starts coming out of the air vent valves of the indoor
units, close them and continue filling until the pressure gauge reading
is 1.5 bars.
DHW SIDE
Warning
Heating/cooling system circuit and domestic hot water
system circuit are separated. To fill the DHW system use a heat storage
tank (boiler).
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
23
HWMC
3 WATER AND ELECTRICAL CONNECTIONS
3.1 WATER CONNECTION
3.1.4 BASE MULTI-PURPOSE SYSTEM DIAGRAM
SOLAR HEAT
DOMESTIC HOT WATER BUFFER
TAN K
SANITARY HOT WATER STORAGE
DHW
HIGH T
HEATERS
Water supply system
Floor 1
Fan coil 2Fan coil 1
Floor 1Floor 1
Warning
the circuit for the production of DHW must be connected
directly to the buffer tank (without interposed coil), in this way the water
content of the buffer tank will be sufficient to ensure the proper operation
of the unit (heat transfer to DHW line), thus avoiding repeated start-ups
and stops of the compressor
24
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
HWMC
3 WATER AND ELECTRICAL CONNECTIONS
3.2 ELECTRICAL CONNECTIONS
Warning
emissions and at the same time to ensure that the unit complies with the
EMC Directives) produce earth leakage. This may cause the differential safety
switch to trip It is recommended to install an additional calibratable differential
switch, dedicated to the unit supply line only.
All operations must be performed by qualified ser vice personnel in accordance
with current laws and regulations. For any electrical work on the unit, refer
to the electric diagrams supplied with the unit.
It is recommended to make sure that:
- The characteristics of the mains power supply are adequate for the electrical
inputs specified in the table of electrical data.
Warning
the power supply is disconnected. Check also that the mains electricity
supply is compatible with the specifications (voltage, number of phases,
frequency) shown on the unit rating plate. The supply voltage may not
undergo fluctuations exceeding ±5% of the rated voltage. The electrical
connections must be made in accordance with the wiring diagram
provided with the unit and the regulations in force.
Warning
any undue modifications will immediately invalidate the warranty.
Important!Upstream from the electrical control panel it is mandatory to
use an omnipolar thermomagnetic circuit breaker complying with IEC-EN
standards (contact gap of at least 3 mm), with an adequate breaking
capacity and differential protection based on the electrical data table
shown below, installed as close as possible to the unit.
For the unit power supply line use H07RN-F- type flexible cables having
the cross sectional area shown in the table.
the filters associated with the inverter (in order to minimize
Before carrying out any job on electrical par ts, make sure
Never attempt to modify internal electrical connections:
To route the cables use sheaths and conduits suitable for outdoor
installation.
You must provide a switch with a delayed fuse meeting the specifications
indicated in the table.
Important!Upstream from the electric control board, you must provide a
switch with a delayed fuse meeting the specifications indicated in the table.
To access the electric control board it is necessary to remove the inspection
panel (figure 4) by taking out the screws; introduce the power cable into the
unit through the bushing on the side panel; then bring it to the electric control
board through the cable holder provided.
Important!Tighten the wires securely to the terminals and clamp the
cable in place with the cable holder (figure 5).
Important!To maintain the IP protection rating a cable gland compatible
with the diameter of the sheath or power cable must be fit in the hole
on the side panel of the unit.
Important!Make sure that the length of cable inside the unit enters
the bushing from below: this is necessary to prevent rainwater from
dripping inside the unit.
Important! An earth connection is mandatory: connect the earthing
wire to the terminal provided on the electric control board (see the
electric control board layout supplied with the unit ), marked
Important!If you wish to include:
- a remote on/off switch
- a remote switch for changing over
- a remote control
it is a good idea to do so at this stage of the installation procedure, by
connecting the switches or the remote control (accessory) to the electric
control board terminals as directed in section 3.3 and using the unit wiring
diagram as your reference.
HWMC 010M 013 018 023 029
Cross-section area of power cables mm
Safety fuse F A 20 25 25 32 32
Main switch IL A 20 25 25 40 40
45
2
4 6 6 10 10
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
25
HWMC
3 WATER AND ELECTRICAL CONNECTIONS
3.3 ELECTRICAL SPECIFICATIONS
HWMC010 M013018023029
Maximum power inputkW5,67,110,710,821,9
Maximum current absorptionA26,6202228,543
Starting absorbed currentA1010101010
Fan motor rated powerkW0,140,140,140,140,14
Fan motor rated currentA0,640,640,640,640,64
Pump motor rated powerkW0,480,650,650,650,65
Pump motor rated current A2,73333
Power supplyV/f/Hz230/1/50400/3N/50
Auxiliary power supplyV/f/Hz
Power cables mm
PCD connecting cablesmm
PCDS connecting cablesmm
Safety fuse FA2025253232
Circuit breaker ILA2025254040
- The maximum power input is the mains electricity that must be available in order for the unit to work.
- The maximum current absorption refers to the current that will trigger the internal safety devices of the unit.
It is the maximum current allowed in the unit. This value may never be exceeded; it must be used as a reference for determining the size of the power supply line and the related safety devices
(refer to the wiring diagram supplied with the units).
2
4661010
2
AWG22AWG22AWG22AWG22AWG22
2
11111
DIAGRAM SHOWING HWMC ELECTRICAL CONNECTIONS
BETWEEN REMOTE PCD CONTROL PANEL AND pCO3 REMOTE
CONTROL
Use a shielded 3 twisted
pairs
Note: Should the unit go into an alarm status, a voltage of 24V will be present
on the terminals of the electric control panel at the terminals 50/24V; where an
interface with a voltage-free contact is desired, a relay must be fitted by the
installer.
26
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
HWMC
4 STARTING UP
FIRST START-UP MAY BE CARRIED OUT SOLELY BY QUALIFIED
TECHNICIANS DULY AUTHORIZED BY GALLETTI S.P.A.
(SEE ENCLOSURE)
When starting up the system for the first time, abide by the provisions of the
national laws currently in force.
4.1 PRELIMINARY CHECKS
When starting up the unit for the first time (or after a seasonal shutdown) it is
a good idea to have the following checks carried out by specialised personnel:
- Check that the electrical connections have been made properly and that
all the terminals are securely tightened.
- Check that the mains voltage corresponds to the voltage rating of the
machine, within a tolerance range of ± 5%.
If the power supply is subject to frequent voltage fluctuations, contact
Galletti S.p.A. for advice on choosing suitable protections.
- Check for refrigerant leaks, with the aid of a leak detector if necessary.
- Check that the plumbing connections have been properly made according
to the indications given on the plates to be found on the unit itself (water
inlet, water outlet etc.).
- Make sure that the pump is not blocked.
- Make sure that the water circuit is duly bled to completely eliminate the
presence of air: load the circuit gradually and open the air vent valves,
which the installer should have set in place.
Warning
are in place and secured with the fastening screws provided. To start
the unit, move the main switch to on.
To start the unit turn on the main switch. Then use the keypad of the
electronic control as directed in section 3.3 to select the cooling or
heating mode.
Warning
during periods when it is inoperative but only when it is to be taken out
of service for a prolonged period (e.g. at the end of the season). To turn
off the unit temporarily follow the directions provided in section 3.3.
Warning
device is used to disconnect the unit from the electricity supply when
there is no passage of current. i.e. when the unit is already turned OFF.
Before starting the unit, make sure all the covering panels
You should not disconnect the unit from the power supply
Do not cut off power using the main switch: the latter
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
27
HWMC
5 OPERATING LIMITS
The graphs below illustrate the operating limits of HWMC units (in the case of continuous operation) in relation to the outlet water temperature and outdoor
air temperature.
Operating limits
Inlet water temperature (°C)820
Outlet water temperature (°C)5192858
ChillerHeat pump
minmaxminmax
1
2542
2
Water temperature differential (°C)3838
Outdoor air temperature (°C)-10
3
48-1035
1 For transitory periods (e.g. equipment start up) values up to 25 °C are allowed
2 Value that may be reached only for outdoor air temperatures exceeding 0°C.
3 With condensation control: Outdoor air T min -15 °C
Warning The units are designed to work with water and air temperatures falling within the range defined by the operating limits.
Attempting to operate the units beyond these limits could cause irreparable damage to the units themselves.
5.1 OPERATING LIMITS IN CHILLER MODE
60
50
40
30
20
air tem p (°C)
10
CHILLER e nvelope
0
-10
-20
-15-10-50510152025
5.2 OPERATING LIMITS IN HEAT PUMP MODE
65
55
45
35
25
out water te mp (°C)
15
5
out w ate r tem p (°C)
Heat Pump envelope
-5
-20-10010203040
Air te mp (°C)
28
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
HWMC
5 OPERATING LIMITS
5.3 OPERATING LIMITS IN DHW TOTAL HEAT RECOVERY
65
55
45
35
25
TW OUT ACS (°C)
15
5
-5
-15-10-505101520
5.4 OPERATING LIMITS ONLY IN DHW PRODUCTION
65
TOAL HEAT RECOV ERY enve lop e
TW OUT chiller (°C)
DHW e nve lope
55
45
35
25
DHW out water te mp (°C)
15
5
-5
-20-100 10203040
Air te mp (°C)
5.5 THERMAL CARRIER FLUID
The units belonging to the HWMC series can work with mixtures of water and up to 30% ethylene glycol.
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
29
HWMC
6 CONTROL AND SAFETY DEVICES
All the control and safety devices are set and tested in the factory before
the unit is dispatched.
6.1 CONTROL DEVICES
6.1.1 Service thermostat
The service thermostat activates and deactivates the compressor according
to the demand for chilled water (cooling mode) or heated water (heat pump
mode), as determined by a sensor installed on the water exchanger outlet.
This device is governed by the microprocessor control (see also the manual
regarding the microprocessor).
6.1.2 CONTROL DEVICE SETTINGS
Control devices Set point min max differential
Service thermostat °C 7 5 15 2
(outlet water temp. cooling mode)
Service thermostat °C 45 25 53 2
(outlet water temp. heat pump mode)
6.2 SAFETY DEVICES
6.2.1 HIGH PRESSURE SWITCH
The high pressure switch stops the compressor when the outlet pressure
exceeds the set value.
6.2.2 LOW PRESSURE SWITCH
The low pressure switch stops the compressor when the intake pressure
falls below the set value.
6.2.4 ANTIFREEZE THERMOSTAT
The antifreeze thermostat situated at the evaporator outlet performs a dual
function: it prevents ice from forming in the evaporator in the event of an
excessive decrease in the water flow; it stops the unit in the event of a failure
of the service thermostat.
This device is governed by the microprocessor control (see also the chapter
regarding the microprocessor).
6.2.5 WATER DIFFERENTIAL PRESSURE SWITCH
The water differential pressure switch stops the unit in the event of an
excessive reduction in the water flow, thus protecting it from the formation
of ice (chiller operation) and excessively high condensation temperatures
(heat pump operation).
6.2.6 WATER SAFETY VALVE
The water safety valve opens when the pressure within the water circuit
reaches a level that may cause damage to the unit.
The function of the timer is to prevent excessively frequent compressor
starts and stops. This device is a function included in the microprocessor
control; it prevents the compressor from starting up again after a stop until
a set period of time has elapsed (approximately 5 minutes).
30
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
HWMC
7 ROUTINE MAINTENANCE AND CHECKS
It is necessary to periodically check the correct functioning of safety devices
(pressure switches and safety valves) and that there are no leaks of refrigerant.
After the initial start-up, periodic checks must be conducted at the intervals
and in the manner prescribed by current national laws and regulations.
To keep the unit in good working order and guarantee the expected levels of
performance and safety, it is necessary to carry out some periodic routine
checks: some may be performed directly by the user while others must be
carried out solely by specialised personnel.
7.1 CHECKS TO BE PERFORMED BY THE USER
The checks and operations described in this section may be easily performed
by the user, provided that the latter shows a minimum of attention.
- Remove any dirt that has built up around the coil or objects trapped in
the mesh protecting the coil itself (leaves, paper etc., to be carried out
monthly).
Warning
coils since the aluminium fins are extremely sharp and can cause cuts.
- Check the level of water in the circuit using the water pressure gauge,
which should indicate a pressure of about 1.5 bars (monthly).
- Check that the escape pipe of the water safety valve is tightly secured.
- Check the water circuit for leaks (monthly).
- If the unit is to remain out of service for a long time, drain the water (or
other fluid present in the circuit) from the pipes and the unit itself.
This is indispensable if during the period of quiescence the ambient
temperature is expected to fall below the freezing point of the fluid used
(seasonal operation).
Drain the unit and parts of the circuit subject to the risk of freezing by
opening the RS emptying tap (optional).
Before placing the unit back in service at the start of the season, refill
the water circuit as directed in section 1.4.
- Check that the noise emissions of the unit are regular (monthly).
- If necessary, release the pump rotor P and S models)
Be especially careful when working in proximity to finned
Come into contact with the dissipator can cause burns.
Warning
component.
Important! After completing maintenance jobs, always replace the panels
enclosing the unit and secure them with the fastening screws provided.
The checks and operations described in this section must be carried out on
a yearly basis by specialised personnel.
- Check the electric control board terminals to ensure that they are securely
tightened: the movable and fixed contacts of the circuit breakers must
be periodically cleaned and replaced whenever they show signs of
deterioration.
- Check the compressor and pipes for oil leaks.
- Check the efficiency of the water differential pressure switch.
- Clean the metal filters mounted in the water pipes.
- Clean the finned coil by aiming a jet of compressed air in a direction
opposite to the outflow of air, taking care not to bend the fins.
Do not perform any voltage insulation test on any
8 RETIRING THE UNIT
When the unit has reached the end of its working life and needs to be removed
and replaced, a series of operations should be carried out:
- the refrigerant gas it contains should be recovered by specialised personnel
and sent to a waste collection facility;
- the lubricating oil in the compressor should also be recovered by specialised
personnel and sent to a waste collection facility;
- if they cannot be reused, the framework and components should be
scrapped and separated according to the type of material: this applies
especially for the considerable quantities of copper, aluminium and steel
present in the unit.
This will make the job of waste collection, disposal and recycling facilities
easier and minimise the environmental impact of the dismantling.
7.2 CHECKS AND MAINTENANCE TO BE PERFORMED BY
SPECIALISED PERSONNEL
WARNINGS
Important! All the operations described in this section MUST ALWAYS BE
PERFORMED BY QUALIFIED PERSONNEL.
Warning
parts, make sure you have disconnected it from the mains electricity supply.
Warning
reach high temperatures. Be especially careful when working in their vicinity.
Warning
coils since the aluminium fins are extremely sharp and can cause cuts.
Warning
without having first disconnected it from the power supply. Wait
another 5 minutes before accessing the internal parts of the unit
Warning
live when it is connected to the mains voltage.
Coming into contact with this voltage is extremely dangerous and
can cause death or serious harm.
Warning
dedicated power line, with calibratable differential switch, separate
from the other power lines of home appliances.
Warning
Before carrying out any work on the unit or accessing inter nal
The upper par t of the compressor casing and the outlet pipe
Be especially careful when working in proximity to finned
Never attempt to access internal parts of the unit
The electrical components of the inverter power unit are
The inverter unit has capacitive leakage current . Set a
The dissipator may be hot when the inverter is running.
Installation and maintenance may be carried out solely by qualified
technicians specifically trained for this type of equipment, in conformity
with current regulations.
On receiving the equipment, check that it has not undergone any damage
during transport.
For installation and use of accessories, please refer to the relative technical
sheets.
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
31
HWMC
9 TECHNICAL FEATURES
9.1 RATED TECHNICAL DATA OF HEAT PUMPS
HWMC 010M013 018023 029
Power supplyV-ph-Hz230-1-50400-3-50400-3-50400-3-50400-3-50
Cooling mode
Cooling capacity
1
Power input 1kW3,344,377,527,4011,50
EER3,183,142,462,932,45
Cooling mode +ACS
Cooling capacity
Power input
1
1
Heating capacity DHWkW13,0017,2025,0029,7040,00
Total COP6,997,296,297,026,43
Heating mode (system / DHW)
Heating capacity
Power input
2
2
COP3,303,212,863,182,82
Water flow - chiller model/h1.8202.3623.1744.0135.080
Water flow - pdc model/h1.9732.5823.7344.4475.856
DHW water flow (total recovery)l/h2.2632.9844.3515.1706.952
Pump head, system side (chiller)kPa127157116146120
Diameter of water connectionsinches1”1/4 1”1/4 1”1/41”1/41”1/4
Buffer tankdm
Heightmm12501250125013001300
Lengthmm15301530153018451845
Depthmm560560560600600
Sound power leveldB(A)7071717474
R410A refrigeration charge(kg)6,48,38,311,511,5
Transport weight*(kg)220220220300300
Operating weight*(kg)240240240347347
kW10,6013,8018,5023,4029,60
kW10,1013,5018,9023,1030,40
kW3,314,216,987,5311,00
kW11,4014,9021,5025,6033,70
kW3,444,347,518,0512,00
3
3
3
55555
11111
3030305050
1 Water temperature 12°C - 7°C; outdoor air temperature 35°C
2 Water temperature 40°C - 45°C, outdoor air temperature 7°C dry bulb, outdoor air temperature 6°C wet bulb
Performances reported in accordance with standard UNI EN 14511
* Weights refer to model with pump and tank
32
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
HWMC
10 COOLING CIRCUIT DIAGRAMS
Legend
NO. COMPONENT SYMBOL
1 Compressor
2 Evaporator
3 Condenser
4 Thermostatic valve
5 Electric fan
6 Filter
7 Sight glass
8 Solenoid valve
9 High pressure switch
10 Low pressure switch
11 High pressure gauge
12 Low pressure gauge
13 Service connection
14 Differential pressure switch
15 Check valve
16 4-way valve
17 Liquid separator
18 Liquid receiver
19 Pressure transducer
20 Liquid distributor
21 Oil pressure gauge
22 Desuperheater
23 Tap
24 Trap
25 Safety valve
26 Fuse cap
27 Flow switch
28 Throttle valve
29 Electronic expansion valve
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
33
HWMC
10 COOLING CIRCUIT DIAGRAMS
10.1 BASIC COOLING CIRCUIT LAYOUT OF HWMC CHILLING UNITS WITH ELECTRONIC VALVE
V4
HEAT
PUMP
V1V2
V5
S2S1
DHW SIDESYSTEM SIDE
V3
S3
34
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
HWMC
10 COOLING CIRCUIT DIAGRAMS
10.2 COOLING CIRCUIT LAYOUT OF HWMC 10 - 29 CHILLING UNITS WITH ELECTRONIC VALVE
SYSTEM SIDE
DHW SIDE
HWMC ONLY
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
35
HWMC
11 TROUBLESHOOTING
In this section you will find a list of the most common problems that may cause the chiller unit to stop or malfunction. Possible remedies are shown alongside a description of easily identifiable remedies.
Warning
Extreme care should be taken when performing work or repairs on the unit: overconfidence can result in injuries, even serious ones, to inexpert individuals. Operations marked with the letter "U" can be per formed directly by the user, who must carefully follow the instructions provided in this
manual.
Operations marked with the letter "S" may be performed exclusively by specialised personnel.
Once the cause has been identified, you are advised to contact a Galletti service centre or a qualified technician for help.
Who can take
SYMPTOMCoolingHeating
XXS Alarm from Digital Input
XXSNot enabled by remote controls
X
X
A The unit does
not start
XXUAntifreeze Alarm - circuit 1
XXS
X
X
corrective action
U = User
S = specialised
personnel
S
U
Possible control panel
indication
Evaporator Inlet Temp.
Sensor Alarm
Evaporator Inlet Temp.
Sensor Alarm
Probable causePossible remedy
Faulty connection or contacts open
Wrong voltage
Service thermostat sensor defective
Not enabled by service thermostat
Not enabled by antifreeze
thermostat
Antifreeze sensor defective Check whether it is functioning properly
Check the voltage and close the contacts
Check the efficiency of the water circulation
pump, pressure switch, bleed air from the
circuit; check whether contacts 16 and 30 on
the terminal board are closed
Check and replace if necessary
System at the set temperature, no demand;
check the setting
Check the water temperature
Checking the antifreeze setting
B The compressor
does not start
XXSTripping of main circuit breaker
X
X
XXSCompressor burnout or seizure Replace the compressor
XXSCompressor contactor deenergized
XXSPower circuit open
XXSInverter Alarm Motor thermal protection open
X XU S
X
X
S
S
LOW pressure alarm
circuit 1
HIGH Pressure Alarm
circuit 1
User flow alarm
DHW flow alarm
Not enabled by high or low pressure
switch
Compressor defective
Water circulation pump blocked
Defective water circulation pump
Lack of water flow
Check for the presence of short circuits in
the wiring or windings of the pump, fan and
compressor motors or in the transformer.
See items D-E
See item B
Check the voltage at either end of the
compressor contactor coil and verify the
continuity of the coil itself
Locate the cause that tripped the protection;
check for the presence of short circuits in
the wiring or windings of the pump, fan and
compressor motors or in the transformer
The compressor has operated in critical
conditions or there is insufficient refrigerant
within the circuit: check the working conditions
and make sure they fall within the operating
limits.
Refrigerant leak: refer to item G
Release the pump
Check the pump and replace it if necessary
Let water flow
C The compressor
starts up and
stops repeatedly
36
XXS
XXSCompressor contactor defective Check and replace if necessary
XXSLack of refrigerant See item G
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
LOW Pressure Alarm
triggered by sensor
-circuit 1
Minimum pressure switch has
tripped
See item E
HWMC
11 TROUBLESHOOTING
SYMPTOM Cooling Heating
Who can take
corrective action
U = User
S = specialised
personnel
Possible control panel
indication
Probable cause Possible remedy
D The compressor
does not start
because the maximum pressure
switch has tripped
E The compressor
does not start
because the minimum pressure
switch has tripped
X X S
X X S
X U
X S
X X S
X X S
X X S
X X S
X S
X S
X U
HIGH Pressure Alarm triggered by sensor - circuit 1
HIGH Pressure Alarm triggered by sensor - circuit 1
HIGH Pressure Alarm triggered by sensor - circuit 1
HIGH Pressure Alarm triggered by sensor - circuit 1
HIGH Pressure Alarm triggered by sensor - circuit 1
HIGH Pressure Alarm triggered by sensor - circuit 1
LOW Pressure Alarm triggered by sensor - circuit 1
LOW Pressure Alarm triggered by sensor - circuit 1
LOW Pressure Alarm triggered by sensor - circuit 1
LOW Pressure Alarm triggered by sensor - circuit 1
LOW Pressure Alarm triggered by sensor - circuit 1
Pressure switch failure Check and replace
Excessive refrigerant charge Discharge the excess gas
Finned coil obstructed, insufficient
air flow
Fan not working See item F
Presence of incondensable gas in
the cooling circuit
Refrigerant filter clogged Check and replace
Pressure switch failure Check and replace
Unit completely empty See item G
Finned coil obstructed, insufficient
air flow
Presence of frost on the evaporating coil
Evaporator fan not working See item F
Remove dirt from the coil and any obstacles
to air flow.
Recharge the circuit after having drained and
evacuated it
Remove dirt from the coil
See item O
F The fans do not
start
X X S
X X S
X X S
X X S
X X S
X
X
X X S
X X S
X
X
S S
LOW Pressure Alarm triggered by sensor - circuit 1
LOW Pressure Alarm triggered by sensor - circuit 1
LOW Pressure Alarm triggered by sensor - circuit 1
HIGH Pressure Alarm triggered by sensor - circuit 1
LOW Pressure Alarm triggered by sensor - circuit 1
HIGH Pressure Alarm triggered by sensor - circuit 1
LOW Pressure Alarm triggered by sensor - circuit 1
HIGH Pressure Alarm triggered by sensor - circuit 1
LOW Pressure Alarm triggered by sensor - circuit 1
HIGH Pressure Alarm triggered by sensor - circuit 1
LOW Pressure Alarm triggered by sensor - circuit 1
HIGH Pressure Alarm triggered by sensor - circuit 1
LOW Pressure Alarm triggered by sensor - circuit 1
Refrigerant filter clogged Check and replace
Expansion valve is not working
properly
Presence of humidity in the cooling
circuit
Fan contactor deenergized
No power output by the fan speed
control card
The fan's internal thermal protection
has tripped
Fan motor defective Check and replace if necessary
Loose electrical connections Check and fasten securely
Check and replace if necessary
Replace the filter and, if necessary, dry out the
circuit and recharge
Check the voltage at either end of the contactor
coil and verify the continuity of the coil itself
Check the contacts and replace if necessary
Check the fan conditions and the air temperature while the unit is running.
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
37
HWMC
11 TROUBLESHOOTING
SYMPTOM Cooling Heating
Who can take
corrective action
U = User
S = specialised
personnel
Possible control panel
indication
Probable cause Possible remedy
G Lack of gas X X S
I Frost in liquid
pipe downstream
from a filter
L The unit works
continuously
without ever
stopping
M The unit works
regularly but with
an insufficient
capacity
X X S
X X S Lack of refrigerant gas See item G
X X U
X X S Thermal overload Reduce the thermal load
X X S
X X Liquid filter clogged Replace
X X S Low level of refrigerant See item G
X X S
LOW Pressure Alarm
triggered by sensor -
circuit 1
HIGH Pressure Alarm
triggered by sensor -
circuit 1
LOW Pressure Alarm
triggered by sensor -
circuit 1
Cooling circuit leak
Liquid filter clogged Replace the filter
Wrong setting of operating
thermostat
Compressor does not provide the
rated heating capacity
4-way cycle reversing valve
defective
Check the cooling circuit using a leak detector
after pressurising the circuit to approximately
4 bars. Repair, evacuate and refill.
Check the setting
Check and replace or overhaul
Check the valve power supply and coils and
replace the valve if necessary
N Frost in the
compressor intake
pipe
O The defrosting
cycle is never
activated
P Abnormal
noises detected in
the system
X X S
X S Water circulation pump blocked Release the pump
X X S Water circulation pump defective Check the pump and replace it if necessary
X X S Low level of refrigerant See item G
X X SLiquid filter clogged Replace
X S
X S
X X S The compressor is noisy Check and replace if necessary
X X S The panels vibrate Fasten properly
Expansion valve is not working
properly
4-way cycle reversing valve
defective
The defrost thermostat has broken
down or has been set incorrectly
Check replace
Check the valve power supply and coils and
replace the valve if necessary
Check and replace if defective or change the
setting
38
All copying, even partial, of this manual is strictly forbiddenRG66008809 - Rev 00
ISTRUZIONI PER AVVIAMENTO
VS. INSTALLAZIONE
1
Nel manuale d’installazione troverete tutti i suggerimenti per una
perfetta posa delle apparecchiature. Ricordate d’installare il filtro a “Y”
a protezione della scambiatore (obbligatorio).
2
VS. COLLEGAMENTO
Effettuate correttamente tutti gli allacciamnti. Nel Modulo Richiesta
Primo Avviamento troverete una lista di tutte le verifiche prima di
richiederci lo start-up della macchina.
3
VS. RICHIESTA
Con almeno una settimana di anticipo inviate via fax il modulo di
richiesta persente nei documenti della macchina in mancanza di tale
documento fare richiesta alla sede Galletti:
L’assistenza Galletti organizzerà l’intervento facendovi contattare dal
Centro Assistenza Tecnica Autorizzato di zona.
NS. COLLAUDO
5
Assieme a Vs. personale verranno effettuati tutti i controlli preliminari ed
il collaudo della macchina.
Al Vs. personale verranno date istruzioni per la corretta gestione della
macchina.
6
NS. GARANZIA
A collaudo effettuato il Centro Assistenza Tecnica Autorizzato rilascerà
il certificato di collaudo valido per la garanzia della macchina.
Z
N
I
A
A
R
A
G
I
T
T
G
E
A
L
L
Galletti S.p.A. mette a Vs. disposizione un programma di manutenzione personalizzato.