Galletti AREO 24, AREO 14, AREO 13, AREO 22, AREO 23, AREO 33, AREO 32, AREO 34, AREO 42, AREO 43, AREO 44, AREO 53, AREO 52, AREO 54, AREO 62, AREO 63, AREO 64 Technical Manual
In line with recent HVAC trends, Galletti offers a versatile unit for mediumsized and large industrial and commercial buildings which combines yearround heating and air-conditioning functions.
Distinguishable by its original rounded shape, AREO stands out above all for
its technical features (all models are equipped with three-speed motors and
configured for operation with chilled water) and one of the lowest noise levels
you will find in the market.
The AREO series comprises 18 models, all designed to be wall mounted
(horizontal air flow) and to operate with hot water and chilled water, thanks
to an innovative condensate collection and drainage system.
If used for heating only, AREO can also be ceiling mounted (vertical air flow).
The units are available in 6 sizes with 2-, 3- or 4-row heat exchangers
ensuring an efficient performance with hot water supplied by a boiler or heat
pump (4-row models).
OPERATING LIMITS
-Thermal carrier fluid: water
-Water temperature: min + 7°C, max +95°C
-Air temperature: min -10°C, max + 40°C
-Supply voltage: rated voltage 230 vac
-Max water pressure during operation: 10 bars
To prevent phenomena of condensate dripping, it is
advisable to select indoor units capable of maintaining,
when operating at full capacity, an air temperature below
35 °C and relative humidity of less than 60%.
Boiler
éstro Fan coil units
LCA water chiller
LCE water chilles
The technical and dimensional data reported in this manual may be modified in view of
any product improvement.
AP66000265 - 03
All copying, even partial, of this manual is strictly forbidden
(9) Top cover of heat exchanger
(10) Conveyor duct
(11) Wall/ceiling mounting brackets
(12) Plastic corner trim on cabinet (left and right)
8
3CONSTRUCTIVE FEATURES
The AREO are mainly made of the components listed below.
9
7
Prepainted sheet steel cabinet complete with ABS corner trim, internally
insulated to prevent condensate from forming on the cabinet during operation
with chilled water.
The cabinet is complete with adjustable aluminium louvers (spring operated)
placed on the air outlet which allow an optimal distribution of the air within
the air conditioned room.
AREO is supplied with brackets for suspending the fan heater to the ceiling
4
or joining it to the mounting board for installation on the wall (accessory).
High conductivity heat exchanger made with copper tubes and aluminium
fins assuring higher heat exchange than standard iron tubes exchangers.
The heat exchanger is set back in relation to the air outlet; an auxiliary drip
tray is fitted into the front to guarantee complete collection of condensate.
Galvanised sheet steel drip tray insulated with closed cells polyurethane,
connected to the auxiliary tray.
All motors are standard equipped with:
6
- internal thermal protection (klixon)
- windings in class F
- protection degree IP55
Two Speeds, 4/6 poles or 6/8 poles, in the three - phase 400V version.
3 speeds in the single - phase 230V (1400, 900 e 700 rpm), available for
the complete range
Upon request, the following equipment is available
- Polarity different from standard ones (example 4/8 poles)
Axial fan with statically balanced sickle blades housed in a specially
designed compartment that enhances ventilation and reduces noise emissions.
Safety grille made of electrogalvanised steel wire: it supports the motor and
is fixed to the cabinet by means of vibration damping supports.
:
4AVAILABLE OPTIONS
AREO is complete with a wide range of accessories as control panels usually associaded with fan coils, thanks to the use of 230V single-phase three speed
motors, a standard arrangement for all models and the operation system with chilled water.
230V SINGLE-PHASE CONTROL PANEL
CDFlush mounted speed control panel
CDEWall mounted speed control panel
TDWall mounted speed control panel, electromechanical thermostat
and summer winter selector
TDCWall mounted speed control panel and electromechanical
thermostat
MCBEWall-mounted microprocessor control - GALLETTI model
MYCOMFORT BASE
MCMEWall-mounted microprocessor control - GALLETTI model
MYCOMFORT MEDIUM
MCLEWall-mounted microprocessor control - GALLETTI model
MYCOMFORT LARGE
LED503Recess wall-mounted microprocessor control
MCSWEWater temperature electronic sensor for MYCOMFORT controls
DISTMYCOMFORT controller spacer for wall mounting
KPpower interface for connecting up to 4 units to a single control
panels
All copying, even partial, of this manual is strictly forbidden
CSTdelta/star selector for installation in electric panels
CSTPdelta/star selector with box for wall installation
TAelectromechanical room thermostat
TA2electromechanical room thermostat with summer winter selector
Rated capacity determined at the following conditions:
Cooling mode:water temperature 7/12°C, air temperature 28°C dry bulb, 55%
relative humidity
Heating mode: water temperature 85 / 75°C, inlet air temperature 20°C
Sound pressure: distance of 5 meters, directional factor equal to 2
AP66000265 - 03
All copying, even partial, of this manual is strictly forbidden
Fan speed:
4 p = 4 poles, 1400 rpm
6 p = 6 poles, 900 rpm
8 p = 8 poles, 700 rpm
4
To prevent phenomena of
condensate dripping, it is
advisable to select indoor units
capable of maintaining, when
operating at full capacity, an air
temperature below 35 °C and relative
humidity of less than 60%.
4 p = 4 poles, 1400 rpm
6 p = 6 poles, 900 rpm
8 p = 8 poles, 700 rpm
90 / 70
0 101520
pw
Tbs
PTQw
2
All copying, even partial, of this manual is strictly forbidden
pw
Tbs
2
PTQw
pw
Tbs
2
PTQw
pw
Tbs
2
10
AREO
7COOLING CAPACITY
To prevent phenomena of condensate dripping, it is
advisable to select indoor units capable of
maintaining, when operating at full capacity, an air
temperature below 35 °C and relative humidity of
less than 60%.
ATTENTION!
TO PREVENT PHENOMENA OF CONDENSATE DRIPPING, IT IS
RECOMMENDED TO USE AREO FAN HEATERS DURING THE COOLING
PHASE ONLY AT THE SPEEDS SHOWN ON THE TABLE (6-8 POLES FOR
SIZES FROM AREO 12 TO AREO 34; 8 POLES FOR SIZES FROM AREO
42 TO AREO 64)
PFSSensible cooling capacity
PFTTotal cooling capacity
QwWater flow rate
Tbs1Inlet air temperature dry bulb
Tbu
Inlet air temperature wet bulb
1
Tw1Inlet water temperature
Tw2Outlet water temperature
VrFan speed:
6 p = 6 poles, 900 rpm
8 p = 8 poles, 700 rpm
27 / 50% (19)
pwPFTPFSQw
pwPFTPFSQw
pw
All copying, even partial, of this manual is strictly forbidden
11
AP66000265 - 03
AREO
7COOLING CAPACITY
To prevent phenomena of condensate dripping, it is
advisable to select indoor units capable of
maintaining, when operating at full capacity, an air
temperature below 35 °C and relative humidity of
less than 60%.
ATTENTION!
TO PREVENT PHENOMENA OF CONDENSATE DRIPPING, IT IS
RECOMMENDED TO USE AREO FAN HEATERS DURING THE COOLING
PHASE ONLY AT THE SPEEDS SHOWN ON THE TABLE (6-8 POLES FOR
SIZES FROM AREO 12 TO AREO 34; 8 POLES FOR SIZES FROM AREO
42 TO AREO 64)
LwOctave band sound power level
LwAA - weighted sound power level
VrFan speed:
4 p = 4 poles, 1400 rpm
6 p = 6 poles, 900 rpm
8 p = 8 poles, 700 rpm
AREO
12 - 13 - 14
22 - 23 - 24
32 - 33 - 34
42 - 43 - 44
52 - 53 - 54
62 - 63 - 64
VrdBdBdBdBdBdBdBdB/AdB/A
4p61,963,161,861,359,156,249,66644
6p62,058,559,356,555,251,143,66240
8p56,052,553,350,549,245,137,65634
4p64,966,164,864,362,159,252,66947
6p63,059,560,357,556,252,144,66341
8p57,053,554,351,550,246,138,65735
4p69,971,169,869,367,164,257,67452
6p65,061,562,359,558,254,146,66543
8p59,055,556,353,552,248,140,65937
4p72,974,172,872,370,167,260,67755
6p69,065,566,363,562,258,150,66947
8p62,058,559,356,555,251,143,66240
4p80,783,278,278,777,874,166,68462
6p69,772,267,267,766,863,155,67351
8p63,762,961,561,761,357,848,56745
6p73,776,271,271,770,867,159,67755
8p67,766,965,565,765,361,852,57149
125 Hz250 Hz500 Hz1 kHz2 kHz4 kHz8 kHzLwALpA
Lw
9VENTILATION FEATURES
The correction factors refer to models without adjustable fins on the air
outlet. Multiply the air flow rate by factor F1 and the capacity by factor F2.
Legend:
PsuAvailable static pressure
VrFan speed:
4 p = 4 poles, 1400 rpm
6 p = 6 poles, 900 rpm
F
Air flow correction factor
1
F
Capacity correction factor
2
ModelPsu
VrF
AREO 12-13-14
AREO 22-23-24
AREO 32-33-34
AREO 42-43-44
AREO 52-53-54
AREO 62-63-64
4P0,810,870,720,87------
6P0,590,79--------
4P0,920, 950,860,910, 780,860, 670,78--
6P0,840,910,560,76------
4P0,980, 980,930,950, 890,930, 850,900, 7785,00
6P0,890,940,780,88------
4P0,970, 980,950,970, 910,940, 880,920, 840,90
6P0,870, 930,820,900, 670,81----
4P0,990, 990,970,980, 960,970, 920,950, 890,93
6P0,950, 970,890,940, 840,91----
6P0,940, 960,890,920, 830,880, 690,79--
10 Pa20 Pa50 Pa30 Pa
1
F
2
F
1
F
40 Pa
2
F
1
F
2
F
1
F
2
F
1
F
2
All copying, even partial, of this manual is strictly forbidden
AREO 123,07,05,53,05,03,03,04,04,0
AREO 133,06,55,53,04,53,03,03,54,0
AREO 143,06,55,53,04,53,02,53,04,0
AREO 223,511,07,03,57,55,03,55,54,0
AREO 233,510,07,03,57,05,03,55,04,0
AREO 243,59,57,03,56,55,03,54,54,0
AREO 324,515,58,04,09,56,03,58,05,0
AREO 334,515,08,04,09,06,03,57,55,0
AREO 344,014,58,03,58,56,03,07,04,5
AREO 424,519,08,04,011,56,53,59,55,5
AREO 434,518,08,03,510,56,53,59,05,5
AREO 444,018,08,03,510,06,53,09,05,0
AREO 525,019,010,04,512,08,04,09,56,0
AREO 535,018,010,04,011,08,04,09,06,0
AREO 544,518,010,04,010,08,03,59,06,0
AREO 62---5,512,58,05,010,07,0
AREO 63---5,511,58,05,09,57,0
AREO 64---5,010,58,04,59,07,0
AREO 123,57,54,02,54,02,5--AREO 133,57,54,02,54,02,5--AREO 143,57,04,02,54,02,5--AREO 224,08,55,03,56,03,53,05,02,5
AREO 234,08,55,03,56,03,53,05,02,5
AREO 244,08,55,03,56,03,53,05,02,5
AREO 325,010,56,04,07,55,03,56,53,5
AREO 335,010,56,04,07,55,03,56,53,5
AREO 345,010,06,04,07,55,03,56,53,5
AREO 425,512,07,04,08,55,53,57,04,5
AREO 435,512,07,04,08,55,53,57,04,5
AREO 445,512,07,04,08,55,53,57,04,0
AREO 526,014,09,05,510,06,55,08,55,0
AREO 536,014,09,05,510,06,55,08,55,0
AREO 546,014,09,05,510,06,55,08,55,0
AREO 62---6,011,07,05,09,56,0
AREO 63---6,011,07,05,09,56,0
AREO 64---6,011,07,05,09,56,0
Ho
Ao
Bo
AP66000265 - 03
All copying, even partial, of this manual is strictly forbidden
14
AREO
12OVERALL DIMENSIONS
Legend:
(1)Water inlet connection (male gas coupling)
(2)Water outlet connection (male gas co upling)
(3)Condensate drainage connection
All copying, even partial, of this manual is strictly forbidden
15
AP66000265 - 03
AREO
12OVERALL DIMENSIONS
50
PAE Fresh air intake
300
PAEModelair inlethole in the wall
AYPAE1AREO 12 - 13 - 14392 X 392400 x 400
AYPAE2AREO 22 - 23 - 24492 x 492500 x 500
AYPAE3AREO 32 - 33 - 34592 x 592600 x 600
AYPAE4AREO 42 - 43 - 44692 x 692700 x 700
AYPAE5AREO 52 - 53 - 54792 x 792800 x 800
AYPAE6AREO 62 - 63 - 64892 x 892900 x 900
PAE M - PAE MM Manual external air intake mixing louvers
A
97
C
B
AP66000265 - 03
H x L
only PAEMM
PAE MPAEMMModelABCair inlet hole in the wall
AYPAEM1 AYPAEMM1AREO 12 - 13 - 14 700 460 920 392 X 392400 x 400
AYPAEM2 AYPAEMM2AREO 22 - 23 - 24 700 560 1120 492 x 492500 x 500
AYPAEM3 AYPAEMM3AREO 32 - 33 - 34 800 660 1320 592 x 592600 x 600
AYPAEM4 AYPAEMM4AREO 42 - 43 - 44 800 760 1520 692 x 692700 x 700
AYPAEM5 AYPAEMM5AREO 52 - 53 - 54 900 860 1720 792 x 792800 x 800
AYPAEM6 AYPAEMM6AREO 62 - 63 - 64 900 960 1920 892 x 892900 x 900
All copying, even partial, of this manual is strictly forbidden
94,5
16
AREO
W2U2V2
U1V1W1
RS T
1112
KLIXON
13ELECTRICAL DATA
Features of the standard motor:
- tropicalised
- equipped internally with a thermal cutout
- IP 55 protection degree
- class F winding
- closed type: asynchronous three-phase 2-speed motors (400/400 V stardelta connection) or single-phase 3-speed motors.
400/400 V - Y motors are equipped internally with a thermal cutout and
speeds are selected by means of a normal star-delta switch (accessory
CST).
The terminals of the cutouts are connected to the terminal block so that they
can be used as protection in series with the coil of a contactor.
If the internal cutout is not used to protect the motor, it will be necessary to
provide a motor overload cutout set at a current that is 10-15% higher than
the current indicated on the unit rating plate.
Special 4/8 pole motors are available on request (single-voltage, dual
polarity).
ModelNumber of polesFan revolutionVoltagePower inputCurrent absorbed
The single-phase motor has an internal thermal cutout that acts directly on
the windings: therefore, NO EXTERNAL THERMAL OVERLOAD PROTECTION
IS NECESSARY.
Make the electrical connections with the power supply disconnected, in
accordance with current safety regulations. All the wiring must be done by
qualified personnel.
Check that the mains electricity supply is compatible with the voltage shown
on the unit rating plate.
Scrupulously follow the wiring diagram provided, according to the type of
installation.
Each unit requires a switch (IL) on the feeder line with a distance of at least
3 mm between the opening contacts, and a suitable safety fuse (F).
If, in case of single-phase motors with microprocessor control, power
input is higher than the values specified in the following figures (for
controls), use the IPM power interface.
14WIRING DIAGRAMS
Delta connection to terminal block of 400/400 V - Y
KLIXON
1112
W2U2V2
U1V1W1
RS T
motors, high speed
All copying, even partial, of this manual is strictly forbidden
Star connection to terminal block of 400/400 V - Y
17
motors, low speed
AP66000265 - 03
AREO
14WIRING DIAGRAMS
Wiring diagram showing connection of single-phase 3-speed motors, with CD wall-mounted control.
BKBlack, maximum speed of 230V 50 Hz motors
BUBlue, medium speed of 230V 50 Hz motors
CDRecess wall-mounted speed switch
CNConnecting terminal block
FProtective fuse (NOT SUPPLIED)
ILSwitch (NOT SUPPLIED)
MMotor
RDRed, minimum speed of 230V 50 Hz motors
WHWhite, shared by 230V 50 Hz motors
CN
3A
4
1
2
3
S
RL
C
CD
F
N
230V 50Hz
L
IL
WH
BK
BU
RD
M
GNYE
Wiring diagram showing connection of single-phase 3-speed motors, with CDE wall-mounted control.
BKBlack, maximum speed of 230V 50 Hz motors
BUBlue, medium speed of 230V 50 Hz motors
CDEwall-mounted speed switch
CNConnecting terminal block
FProtective fuse (NOT SUPPLIED)
ILSwitch (NOT SUPPLIED)
MMotor
RDRed, minimum speed of 230V 50 Hz motors
WHWhite, shared by 230V 50 Hz motors
3A
6
5
4
3
2
1
S
c
AP66000265 - 03
RD
BU
M
BK
F
CN
IL
WH
L
N
230V 50Hz
GNYE
All copying, even partial, of this manual is strictly forbidden
18
CDE
AREO
14WIRING DIAGRAMS
Wiring diagram showing connection of single-phase 3-speed motors, with TD wall-mounted control.
BKBlack, maximum speed of 230V 50 Hz motors
BUBlue, medium speed of 230V 50 Hz motors
CNConnecting terminal block
FProtective fuse (NOT SUPPLIED)
ILSwitch (NOT SUPPLIED)
MMotor
RDRed, minimum speed of 230V 50 Hz motors
TDremote control panel (accessory)
TCWinter fan stop thermostat for electromechanical control
WHWhite, shared by 230V 50 Hz motors
TC
F
IL
6
5
N
4
3
2
1
S
C
T
ACC
3A
L
N
230V 50Hz
RD
BU
M
BK
WH
CN
GNYE
SF
TD
All copying, even partial, of this manual is strictly forbidden
19
AP66000265 - 03
AREO
14WIRING DIAGRAMS
Wiring diagram showing connection of 400/400 V motor, with star-delta selector (YD).
CSTStar-triangle switch
MMotor
L1
L2
L3
N
ILF
N1
TA-TA2
2
A1
K
A2
135
246
CST - CSTP
Wiring diagram showing parallel connection of 2 single-phase 3-speed motors, with wall-mounted control (CD + KP).
BKBlack, maximum speed of 230V 50 Hz motors
BUBlue, medium speed of 230V 50 Hz motors
CDRecess wall-mounted speed switch
CNConnecting terminal block
FProtective fuse (NOT SUPPLIED)
KPPower interface
ILSwitch (NOT SUPPLIED)
MMotor
RDRed, minimum speed of 230V 50 Hz motors
WHWhite, shared by 230V 50 Hz motors
C
4 1 2 3
IL
F
L
N
230V 50 HZ
1
6
14
8
16
5
S RL
14
13
10
15
1
9
4
2
6
CD
13
15
2
W1
W2
U1
U2
V1
V2
KLIXON
12
11
W2 U2 V2
U1 V1 W1
M
CN
HW
GNYE
BK
BU
M
RD
CN
HW
GNYE
BK
HW
HW
M
GNYE
M
GNYE
M
2
3
4
5
13
14 N
15 L
16 N
KP
C
1
2
3
L
3A
22
19
4
20
21
26
23
3
24
25
30
27
2
28
29
34
31
1
32
33
BU
RD
CN
BK
BU
RD
CN
BK
BU
RD
AP66000265 - 03
All copying, even partial, of this manual is strictly forbidden
20
AREO
15ACCESSORIES
CD - Flush wall-mounted speed selector
Flush wall mounted control panel is provided with a 4
positions (3 speed + stop) rotation selector.
This control panel, that can be matched with all the AREO
230V single phase models, allows the ON/OFF and fan
2
1
3
0
speed selection of the fan coil unit.
CDE - Wall-mounted speed selector
Wall mounted control panel is provided with a 3
positions (3 speed ) and switch ON/OFF .
This control panel, that can be matched with all the
AREO 230V single phase models, allows the ON/OFF
and fan speed selection of the fan coil unit.
TD - Wall mounted control with speed
selector,thermostat and summer-winter
selector
Wall mounted control panel complete with
fan speed selector, electromechanical
thermostat and cooling / heating mode
selector.
This control panel, that can be matched with all the AREO 230V single phase
models, allows the fan speed control, regulation of the room temperature and
cooling / heating mode selection:
- manual setting of the fan speed;
- room temperature regulation both in cooling / heating mode, by means
of fan start/stop, at a manually set temperature.
TDC - Wall mounted control with speed
selector and thermostat
Wall mounted control panel complete with fan
speed selector, and electromechanical
thermostat .
This control panel, that can be matched with
all the AREO 230V single phase models, allows the fanan speed control,
regulation of the room temperature:
- manual setting of the fan speed;
- room temperature regulation in heating mode, by means of fan start/
stop, at a manually set temperature.
- regulation of the room temperature both in heating and cooling mode
when connected to a remote centralised summer-winter selector
MYCOMFORT BASE - Wall-mounted microprocessor control, GALLETTI model
MYCOMFORT BASE having the following main features:
- room air temperature reading and adjustment
- water temperature reading (water sensor as an
optional)
- manual and automatic adjustment of fan speed
- manual and automatic switching of heating and
cooling mode depending on the water temperature
within the heat exchanger or on the room temperature,
with a neutral zone that can be selected in the range from 2° to 5°C.
The controller is equipped with a large display (3”) to show and set all the
functions of the unit.
Using the installation kit available, MYCOMFORT can be mounted on the unit
MYCOMFORT MEDIUM - Wall-mounted
microprocessor control, GALLETTI model
MYCOMFORT MEDIUM having the following main
features:
- room air temperature reading and adjustment
- room humidity reading and adjustment
- water temperature reading (water sensor as an
optional)
- manual and automatic adjustment of fan speed
- manual and automatic switching of heating and
cooling mode depending on the water temperature within the heat
exchanger or on the room temperature, with a neutral zone that can be
selected in the range from 2° to 5°C.
- serial por t for Bus connection
The controller is equipped with a large display (3”) to show and set all the
functions of the unit.
Using the installation kit available, MYCOMFORT can be mounted on the
unit
MYCOMFORT LARGE - Wall-mounted
microprocessor control, GALLETTI model
MYCOMFORT LARGE having
the following main features:
- room air temperature reading and adjustment
- room humidity reading and adjustment
- water temperature reading (water sensor as an
optional)
- manual and automatic adjustment of fan speed
- manual and automatic switching of heating and
cooling mode depending on the water temperature
within the heat exchanger or on the room temperature, with a neutral
zone that can be selected in the range from 2° to 5°C.
- clock and hourly timer-programmed operation.
- 2 analogue outputs for controlling modulating devices 0-10V
- 2 digital outputs for controlling (On/Off) external devices (no-voltage
contacts)
- serial por t for Bus connection
The controller is equipped with a large display (3”) to show and set all the
functions of the unit.
Using the installation kit available, MYCOMFORT can be mounted on the
unit
LED503
Recess wall-mounted microprocessor control
The proposed microprocessor control panels for
Galletti indoor units is completed by the LED503
command with LED display that is designed for
recess wall mounting.
CONTROLLER
The control software developed by the Galletti
Software Dept., features:
- manual selection of fan speed;
- automatic selection of fan speed according to the difference between the
set temperature and the room air temperature;
- manual selection of heating/cooling operating mode;
- automatic selection of heating/cooling operating mode;
- control of 1 or 2 ON/OFF valves;
- control of additional heating element;
- on board timer function to detect the actual ambient temperature;
- reading of air ambient temperature, set point, fan speed and mode
selection on the LED display.
All copying, even partial, of this manual is strictly forbidden
21
AP66000265 - 03
AREO
15ACCESSORIES
KP - Power interface for connection of up to 4
units to a single control panel
The KP master sleeve can be installed to control
with a single control panel up to 4 units (connected
in parallel).
This accessory is designed for installation on a
DIN drive, usually placed on electric board.
CST -Delta/star selector for installation in electric panels
Allows the rotational speed switching (off / low-speed / high-speed).
It can be used only on 400 V (3-phase) models. For electrical box
installation.
CSTP - Delta/star selector with box for wall installation
Allows the rotational speed switching (off / low-speed / high-speed). It
can be used only on 400 V (3-phase) models. Supplied with plastic box
for wall installation.
TA - Wall mounted room thermostat
Automatic regulation of the the room temperature:
- only in the heating mode working on the fan motor
assembly;
- only in the cooling mode working on the fan motor
assembly;
- both in cooling and heating mode, with remote
mode selection working on the fan motor assembly.
PAE MM - Motor-driven mixing air intake louver
Allows the mixing of return and fresh air. The amount of
fresh air can be adjusted (motorized louver) within the
range 0-100%. The proportional drive motor (24 V power
supply, voltage transformer included) is equipped with a
shaft-return spring that forces the louver to close (avoiding
the fresh air intake) in case of blackout. The drive motor
can be connected to external auxiliary contacts in order
to force the automatic opening and closing (air extractors, antifreeze
thermostats, etc…). The motor driven fresh air intake louver must be used
together with the dedicated control panel, for proportional opening-closing
(CSD option)
The option is supplied with wall-supports and is usually installed together
with the outdoor fresh-air intake grill (GR option)
GR - Outdoor air intake grille
Galvanised aluminium outdoor fresh-air intake grill.
Equipped with anti-intrusion grill, in order to avoid the
intrusion of dangerous objects from the outside.
DFP - wall mounting board
The DFP option (made in steel of adequate
thickness) allows the installation on indoor
walls. The fan heater is connected to the wall
mounting board by mean of the four tongues in
the back panel of the unit (connection screws
supplied).
TA2 - Wall mounted room thermostat with summerwinter selector
Wall mounted room thermostat with cooling/heating
mode selector.
Automatic regulation of the room temperature both
in heating and cooling mode, working on the fan
motor assembly.
CSD - Wall mounted control panel for opening and
closing of the motor driven air intake louver PAEMM
Designed for wall installation, it allows the proportional
opening and closing from 0 to 100% of thePAE MM motor
driven fresh air intake louver.
PAE - Fresh air intake louver
Allows the fresh air intake from the outside. Usually
installed together with the outdoor fresh-air intake grill
(GR option)
PAE M - Manual mixing fresh air intakelouver
Allows the mixing of return and fresh air. The amount of
fresh air can be adjusted (manual louver) within the range
0-100%. The option is supplied with wall-supports and is
usually installed together with the outdoor fresh-air intake
grill (GR option)
50%
0%100%
DFC - column mounting board
The DFP option (made in steel of adequate
thickness) allows the installation on indoor
columns or walls . The fan heater is connected
to the wall mounting board by mean of the four
tongues in the back panel of the unit
(connection and option mounting screws
supplied).
DFO - Adjustable wall/column mounting
board
The DFO option (made in steel of adequate
thickness) allows to orient the fan heater as
needed (towards left or right), during the
installation on indoor columns or walls. The
fan heater is connected to the wall mounting
board by mean of the four brackets in the back
panel of the unit (connection and option
mounting screws supplied).
R - Protection grill for gymnasium
Protection grill for gymnasium (against ball
impact on adjustable louvers). Option mounting
screws supplied.
D0 -Additional row of louvers
The additional row of louvers air diffuser
allows to orient the air flow on the horizontal
plane, towards left or right. Option mounting
screws supplied.
AP66000265 - 03
All copying, even partial, of this manual is strictly forbidden
22
AREO
15ACCESSORIES
MCSWE - water temperature electronic probe for
MYCOMFORT controls
Water probe for the MYCOMFORT control panel:
automatic selection of the cooling/heating operation
mode.
Connected directly to the microprocessor control
panel, this probe measures the water temperature
inside the heat exchanger.
If the temperature registered is lower than 17°C the unit works in cooling
mode and the temperature range of the control panel will be referred to the
cooling mode (19 / 31°C); if the temperature registered is higher than 37°C
the unit works in heating mode and the temperature range of the control panel
will be referred to the heating mode (14 / 26°C).
If the temperature registered is between 17°C e 37°C the control panel will
disable the unit operation.
LA - Air curtain diffuser
In order to create warm air curtains in proximity of doors and apertures, the fan heater AREO can be
equipped with the air curtain diffuser (option LA). Available in different sizes (models) as indicated
in the table below, it must be chosen depending on installation height and door width.
CAUTION!
The fan heater equipped with air curtain diffuser must be installed in horizontal position: it is not
possible to use it in cooling mode (no possible condensate removal).
During the installation, take to orient the air curtain towards the inner side of the door (floor level).
Model
AREO 32 Air curtain
AREO 33 Air curtain
AREO 42 Air curtain
AREO 43 Air curtain
AREO 52 Air curtain
AREO 53 Air curtain
AREO 62 Air curtain
AREO 63 Air curtain
Fan
Speed
6P270023,70209510,52,5 - 3,01
8P213020,6018158,12,0 - 2,51
6P265027,0023889,72,5 - 3,01
8P210023,3020607,52,0 - 2,51
6P375033,65297117,53,0 - 4,02
8P311030,00265214,32,5 - 3,01
6P370038,40339018,03,0 - 4,02
8P307034,10301214,32,5 - 3,01
6P560040,53357913,13,5 - 4,52
8P430034,80307110,03,0 - 3,52
6P550050,95449814,73,5 - 4,52
8P422043,30382211,13,0 - 3,52
6P810074,30656117,14,5 - 5,53
8P650064,90573213,43,5 - 4,52
6P800089,14786924,64,5 - 5,53
8P642077,20682019,13,5 - 4,52
AirHeatingWaterWaterInstallationDoor Sound
FlowCapacityFlowPressure dropHeightLenghtPower
3
/hkWl/hkPa mmdB A
m
Rated capacity determined at the following conditions:
AREO LA TECHNICAL DATA
66
60
66
60
70
63
70
63
74
68
74
68
78
72
78
72
Heating mode:
water temperature 85 / 75°C, inlet air temperature 20°C
Fan speed:
6 p = 6 poles, 900 rpm
8 p = 8 poles, 700 rpm
All copying, even partial, of this manual is strictly forbidden
23
AP66000265 - 03
Company UNI EN ISO 9001 and OHSAS 18001 certified