Gallagher Group C30024X Users Manual

Installation Note
Gallagher T11 Reader
This equipment contains components that can be damaged by electrostatic discharge. Ensure both you and the equipment are earthed before beginning any servicing.
Installation Note | Gallagher T11 Reader
The Gallagher T11 Reader
The Gallagher T11 Reader is a smart card proximity reader. It can be installed as either an entry reader or exit reader. It can be mounted on any standard electrical flush (gang) box, used in New Zealand, Australia, USA and Canada.
The Gallagher T11 Reader uses the “Cardax IV Reader” communications protocol to communicate with the Cardax FT Controller.
Part Number: 3E2513 R1 | 1
Installation Note | Gallagher T11 Reader
Before you begin
Shipment Contents
Check the shipment contains the following items:
1 x Gallagher T11 Reader facia assembly• 1 x Gallagher T11 Reader base• 1 x M3 Torx Post Security screw• 2 x 6-32 UNC screws• 4 x self tapping, pan head, pozi fixing screws•
Power Supply
The Gallagher T11 Reader is designed to operate over a supply voltage range of 9 - 16Vdc measured at the reader terminals. The operating current draw is dependant on the supply voltage at the reader. For the Standard variant at 12Vdc the current draw is 54mA (standby). During card read, beeper and LED activity, the current will momentarily reach 100mA (peak). For the Multi Tech variant at 12Vdc the current draw is 88mA (standby) and will momentarily reach 140mA (peak).
Cabling
The power source should be linear or a good quality switched-mode power supply. The performance of the reader may be affected by a low quality, noisy power supply.
The Gallagher T11 Reader requires a minimum cable size of 4 core 24 AWG
2
(0.2mm
) stranded security cable. This cable allows the transmission of data (2 wires) and power (2 wires). When using a single cable to carry both power supply and data, both the power supply voltage drop and data requirements must be considered. Although the reader is specified to operate at 9Vdc, for good engineering design it is recommended that the voltage at the reader should be approximately 12Vdc.
Examples of approved cables for connecting a single Gallagher T11 Reader to a Controller and power supply, showing maximum cable lengths for each type of cable and the associated circuits are:
Combined
Manufacturer
reference Cable format*
CAT5E 4 twisted pair
Each 2 x 0.2mm
SEC472 4 x 0.2mm
2
Not twisted pairs (24 AWG)
SEC4142 4 x 0.4mm
2
Not twisted pairs (21 AWG)
BELDEN 8723 2 twisted pair
Each 2 x 0.4mm
BELDEN 9842 2 twisted pair
Each 2 x 0.2mm
2
(24 AWG)
2
(22 AWG)
2
(24 AWG)
power and data
in a single cable
Data only in a
single cable
100m (330ft) 300m (1000ft)
100m (330ft) 250m (800ft)
150m (500ft) 150m (500ft)
100m (330ft) 150m (500ft)
100m (330ft) 200m (650ft)
2 | Part Number: 3E2513 R1
* The matching of wire sizes to equivalent wire gauges are only approximate.
Distance between Proximity Readers
The distance separating any two proximity readers must not be less than 200mm (8 inches) in all directions.
200mm
Installation Note | Gallagher T11 Reader
When mounting a proximity reader on an internal wall, check that any reader fixed to the other side of the wall is not less than 200mm (8 inches) away.
Installation
The Gallagher T11 Reader is designed to be mounted on vertically orientated electrical flush (gang) boxes, or any solid flat surface. However installation on metal surfaces, particularly those with a large surface area will reduce read range. The extent to which the range is reduced will depend upon the type of metal used.
The recommended mounting height for the reader is 1.1m (3.6 ft) from the floor level to the centre of the reader device. However this may vary in some countries and you should check local regulations for variations to this height.
200mm
Ensure the building cable has been run out through the flush box.1.
If you are not mounting to a flush box, use the drill template at the back of this installation note as a guide, to drill all five holes. Drill the 13mm (1/2 inch) diameter centre hole (this is the centre hole for which the building cable will exit the mounting surface) and the four fixing holes.
Run the building cabling through the reader base.2.
Part Number: 3E2513 R1 | 3
Installation Note | Gallagher T11 Reader
Secure the base to the flush box using the two 6-32 UNC screws provided. It 3. is important the base of the reader is flush with and tight against the mounting surface.
If you are not mounting to a flush box, secure the base to the mounting surface using the four fixing screws provided.
6-32 UNC screw
Building cable
6-32 UNC screw
Base
Connect the reader tail extending from the facia assembly to the building cable. 4. Connect the wires shown below.
Note: Do not cut the ‘Reserved’ wires, they may be required later.
Positive Red Negative Black Reserved Orange Reserved Green Reserved Brown CDXIV TX White
Cardax IV Reader
CDXIV RX Blue
Fit the facia assembly into the base by clipping the small lip, into the top of 5. the base and holding the top, press the bottom of the facia assembly down into the base.
Insert the M3 Torx Post Security screw (using a T10 Torx Post Security screwdriver) 6. through the hole at the bottom of the base to secure the facia assembly.
Note: The recommended torque for the security screw is 0.7Nm (0.5 lb/ft). It is important not to exceed the maximum torque of 1.5Nm (1.1 lb/ft).
4 | Part Number: 3E2513 R1