The Schneider Electric brand and any trademarks of Schneider Electric SE and its
subsidiaries referred to in this guide are the property of Schneider Electric SE or its
subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and
furnished for informational use only. No part of this guide may be reproduced or
transmitted in any form or by any means (electronic, mechanical, photocopying,
recording, or otherwise), for any purpose, without the prior written permission of
Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the guide
or its content, except for a non-exclusive and personal license to consult it on an "as
is" basis. Schneider Electric products and equipment should be installed, operated,
serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information
contained in this guide may be subject to change without notice.
To the extent permitted by applicable law, no responsibility or liability is assumed by
Schneider Electric and its subsidiaries for any errors or omissions in the informational
content of this material or consequences arising out of or resulting from the use of the
information contained herein.
Connect the Signal Cables......................................................................35
Final Installation ........................................................................................37
990-91138A-0013
Important Safety Instructions — SAVE THESE
INSTRUCTIONSMaintenance Bypass Cabinet with Input/Output Transformer
Important Safety Instructions — SAVE THESE
INSTRUCTIONS
Read these instructions carefully and look at the equipment to become familiar
with it before trying to install, operate, service or maintain it. The following safety
messages may appear throughout this manual or on the equipment to warn of
potential hazards or to call attention to information that clarifies or simplifies a
procedure.
The addition of this symbol to a “Danger” or “Warning” safety
message indicates that an electrical hazard exists which will result in
personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential
personal injury hazards. Obey all safety messages with this symbol
to avoid possible injury or death.
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
Failure to follow these instructions will result in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result
in death or serious injury.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.
Failure to follow these instructions can result in injury or equipment
damage.
NOTICE
NOTICE is used to address practices not related to physical injury. The safety
alert symbol shall not be used with this type of safety message.
Failure to follow these instructions can result in equipment damage.
Please Note
Electrical equipment should only be installed, operated, serviced, and maintained
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction,
installation, and operation of electrical equipment and has received safety training
to recognize and avoid the hazards involved.
990-91138A-0015
Maintenance Bypass Cabinet with Input/Output Transformer
FCC Statement
NOTE: This equipment has been tested and found to comply with the limits for
a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed
and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a
residential area is likely to cause harmful interference in which case the user
will be required to correct the interference at his own expense.
Any changes or modifications not expressly approved by the party responsible for
compliance could void the user’s authority to operate the equipment.
Safety Precautions
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Important Safety Instructions — SAVE THESE
INSTRUCTIONS
DANGER
Read all instructions in the installation manual before installing or working on
this product.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not install the product until all construction work has been completed and the
installation room has been cleaned.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The product must be installed according to the specifications and requirements
as defined by Schneider Electric. It concerns in particular the external and
internal protections (upstream breakers, battery breakers, cabling, etc.) and
environmental requirements. No responsibility is assumed by Schneider Electric
if these requirements are not respected.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The UPS system must be installed according to local and national regulations.
Install the UPS according to:
•IEC 60364 (including 60364–4–41- protection against electric shock, 60364–
4–42 - protection against thermal effect, and 60364–4–43 - protection
against overcurrent), or
•NEC NFPA 70, or
•Canadian Electrical Code (C22.1, Part 1)
depending on which one of the standards apply in your local area.
Failure to follow these instructions will result in death or serious injury.
6990-91138A-001
Important Safety Instructions — SAVE THESE
INSTRUCTIONSMaintenance Bypass Cabinet with Input/Output Transformer
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
•Install the product in a temperature controlled indoor environment free of
conductive contaminants and humidity.
•Install the product on a non-flammable, level and solid surface (e.g.
concrete) that can support the weight of the system.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The product is not designed for and must therefore not be installed in the
following unusual operating environments:
•Damaging fumes
•Explosive mixtures of dust or gases, corrosive gases, or conductive or
radiant heat from other sources
•Moisture, abrasive dust, steam or in an excessively damp environment
•Fungus, insects, vermin
•Salt-laden air or contaminated cooling refrigerant
•Pollution degree higher than 2 according to IEC 60664-1
•Exposure to abnormal vibrations, shocks, and tilting
•Exposure to direct sunlight, heat sources, or strong electromagnetic fields
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not drill or cut holes for cables or conduits with the gland plates installed and
do not drill or cut holes in close proximity to the UPS.
Failure to follow these instructions will result in death or serious injury.
WARNING
HAZARD OF ARC FLASH
Do not make mechanical changes to the product (including removal of cabinet
parts or drilling/cutting of holes) that are not described in the installation manual.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
NOTICE
RISK OF OVERHEATING
Respect the space requirements around the product and do not cover the
ventilation openings when the product is in operation.
Failure to follow these instructions can result in equipment damage.
990-91138A-0017
Maintenance Bypass Cabinet with Input/Output Transformer
Additional Safety Precautions After Installation
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not install the UPS system until all construction work has been completed
and the installation room has been cleaned. If additional construction work is
needed in the installation room after this product has been installed, turn off the
product and cover the product with the protective packaging bag the product
was delivered in.
Failure to follow these instructions will result in death or serious injury.
Electrical Safety
This manual contains important safety instructions that should be followed during
the installation and maintenance of the product.
Important Safety Instructions — SAVE THESE
INSTRUCTIONS
DANGER
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
•Electrical equipment must be installed, operated, serviced, and maintained
only by qualified personnel.
•Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices.
•Disconnection devices for AC and DC must be provided by others, be readily
accessible, and the function of the disconnect device marked for its function.
•Turn off all power supplying the product before working on or inside the
equipment.
•Before working on the product, check for hazardous voltage between all
terminals including the protective earth.
•The product contains an internal energy source. Hazardous voltage can be
present even when disconnected from the mains supply. Before installing or
servicing the product, ensure that the product is OFF and that utility/mains
and batteries are disconnected. Wait five minutes before opening the
product to allow the capacitors to discharge.
•The product must be properly earthed/grounded and due to a high leakage
current, the earthing/grounding conductor must be connected first.
Failure to follow these instructions will result in death or serious injury.
When the input is connected through external isolators that, when opened, isolate
the neutral or when the automatic backfeed isolation is provided external to the
equipment or is connected to an IT power distribution system, a label must be
fitted at the input terminals, and on all primary power isolators installed remotely
from the installation area and on external access points between such isolators
and the product, by the user, displaying the following text (or equivalent in a
language which is acceptable in the country in which the product is installed):
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Risk of voltage backfeed. Before working on this circuit: Isolate the product and
check for hazardous voltage between all terminals including the protective
earth.
Failure to follow these instructions will result in death or serious injury.
8990-91138A-001
Important Safety Instructions — SAVE THESE
INSTRUCTIONSMaintenance Bypass Cabinet with Input/Output Transformer
Battery Safety
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
•Battery circuit breakers must be installed according to the specifications and
requirements as defined by Schneider Electric.
•Servicing of batteries must only be performed or supervised by qualified
personnel knowledgeable of batteries and the required precautions. Keep
unqualified personnel away from batteries.
•Disconnect charging source prior to connecting or disconnecting battery
terminals.
•Do not dispose of batteries in a fire as they can explode.
•Do not open, alter, or mutilate batteries. Released electrolyte is harmful to
the skin and eyes. It may be toxic.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Batteries can present a risk of electric shock and high short-circuit current. The
following precautions must be observed when working on batteries
•Remove watches, rings, or other metal objects.
•Use tools with insulated handles.
•Wear protective glasses, gloves and boots.
•Do not lay tools or metal parts on top of batteries.
•Disconnect the charging source prior to connecting or disconnecting battery
terminals.
•Determine if the battery is inadvertently grounded. If inadvertently grounded,
remove source from ground. Contact with any part of a grounded battery can
result in electric shock. The likelihood of such shock can be reduced if such
grounds are removed during installation and maintenance (applicable to
equipment and remote battery supplies not having a grounded supply
circuit).
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
When replacing batteries, always replace with the same type and number of
batteries or battery packs.
Failure to follow these instructions will result in death or serious injury.
NOTICE
RISK OF EQUIPMENT DAMAGE
•Wait until the system is ready to be powered up before installing batteries in
the system. The time duration from battery installation until the UPS system
is powered up must not exceed 72 hours or 3 days.
•Batteries must not be stored more than six months due to the requirement of
recharging. If the UPS system remains de-energized for a long period,
Schneider Electric recommends that you energize the UPS system for a
period of 24 hours at least once every month. This charges the batteries,
thus avoiding irreversible damage.
Failure to follow these instructions can result in equipment damage.
990-91138A-0019
Maintenance Bypass Cabinet with Input/Output TransformerSpecifications
Specifications
Specifications for Maintenance Bypass Cabinet with Input
Transformer (GVSBPIT25, GVSBPIT50, GVSBPIT75)
Continuous operation limited to maximum 110% load.
13/1019/1526/2032/2638/3151/4164/5182/67100/81
15/1223/1631/2538/3146/3761/4977/6195/75115/92
2842566983111139167208
100 at 240 V (for UIB/MBB/UOB)
Trip Settings for Maintenance Bypass Cabinet with Input Transformer
NOTE: Ir, tr, and li must be set during installation. Set the breaker settings per
system kW rating as listed in the table below. Changing the settings to other
than the listed settings will change the 125% and 150% overload operation,
and will impact system performance.
UPS ratingBreaker typeIr settingTr at 6 Ir
setting
Ir settingTr at 6 Ir
setting
li (x In) setting
UIB/MBB/UOBUIBMBB/UOBUIB/MBB/UOB
10 kWHJF36150CU31X500.5500.51.5
15 kWHJF36150CU31X600.55041.5
20 kWHJF36150CU31X800.57041.5
25 kWHJF36150CU31X1000.58041.5
30 kWJJF36250CU31X110410041.5
40 kWJJF36250CU31X150415041.5
50 kWJJF36250CU31X2000.517521.5
60 kWJJF36250CU31X250422512
75 kWJJF36250CU31X250425022
10990-91138A-001
SpecificationsMaintenance Bypass Cabinet with Input/Output Transformer
Recommended Upstream Protection for Maintenance Bypass Cabinet with Input
Transformer
For 480 V Input
UPS ratingBreaker typeIr settingTr at 6 Ir settingli (x In) setting
10 kWHJL36060U31X1546
15 kWHJL36060U31X2546
20 kWHJL36060U31X3046
25 kWHJL36060U31X3546
30 kWHJL36060U31X45412
40 kWHJL36060U31X60412
50 kWHJL36100U31X7048
60 kWJJL36250CU31X1000.52
75 kWJJL36250CU31X1000.52
For 600 V Input
UPS ratingBreaker typeIr settingTr at 6 Ir settingli (x In) setting
10 kWHJL36060U31X1516
15 kWHJL36060U31X2046
20 kWHJL36060U31X2546
25 kWHJL36060U31X3046
30 kWHJL36060U31X35812
40 kWHJL36060U31X45812
50 kWHJL36060U31X60412
60 kWJJL36250CU31X1000.52
75 kWJJL36250CU31X1000.52
990-91138A-00111
Maintenance Bypass Cabinet with Input/Output TransformerSpecifications
Recommended Cable Sizes for Maintenance Bypass Cabinet with Input Transformer
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
All wiring must comply with all applicable national and/or electrical codes. The
maximum allowable cable size is 4/0 AWG.
Failure to follow these instructions will result in death or serious injury.
NOTE: Overcurrent protection and cable lugs are to be provided by others.
Cable sizes in this manual are based on Table 310.15 (B)(16) of the National
Electrical Code (NEC) with the following assertions:
•90 °C (194 °F) conductors (75 °C (167 °F) termination)
•An ambient temperature of 30 °C (86 °F)
•Use of copper or aluminum conductors
If the ambient temperature is greater than 30 °C (86 °F), larger conductors are to
be selected in accordance with the correction factors of the NEC.
Equipment grounding conductors/Protective Earth (PE in this manual) are sized in
accordance with NEC Article 250.122 and Table 250.122.
NOTE: DC cables are only connected in the maintenance bypass cabinet in
top cable entry systems. In bottom cable entry systems, the DC cables are
connected directly in the UPS.
NOTE: The DC cable sizes given here are recommendations – Always follow
the specific instructions in the battery solution documentation for DC cable
sizes.
1.Neutral conductor is sized to handle 1.73 times phase current in case of high harmonic content from non-linear loads. If few or no
harmonic currents are expected, neutral conductor can be sized as phase conductor.
12990-91138A-001