Wall-Mount Stanchion Assembly
This manual is provided solely as an installation, operation, and maintenance guide, which contains sensitive business and technical information that is confidential and proprietary to GAI-Tronics. GAI­Tronics retains all intellectual property and other rights in or to the information contained herein, and such information may only be used in connection with the operation of your GAI-Tronics product or system. This manual may not be disclosed in any form; in whole or in part, directly or indirectly, to any third party.
General Information
The Model 234WM-202 Wall-Mount Stanchion Assembly is part of a completely integrated emergency
communications station and is designed to house a GAI-Tronics Model 39x or 27x Series Flush-Mount
Telephone and a Model 540-001or 531A Strobe (each sold separately). The stanchion is a simple, attractive, yet highly visible unit measuring 40.5 inches (1.03 meters) tall.
GAI-Tronics enhanced emergency telephones are designed for isolated high-risk areas requiring emergency communications equipment. Emergency telephone users simply press the clearly labeled emergency push button for immediate connection to a user-programmed central security telephone number.
The strobe creates added visibility to emergency telephone locations by providing a constant-on lamp that automatically flashes when the emergency button is pressed. The telephone is also highly visible; a light mounted in the stanchion shines on the front of the telephone to illuminate the telephone for nighttime use.
The Model 234WM-202 Wall-Mount Stanchion Assembly consists of the Model 84505-202 Wall-Mount
Stanchion and the Model 84503-30x Panel Light Assembly (each packaged separately). The strobe and
the emergency telephone are purchased and packaged separately.
GAI-TRONICS 3030 KUTZTOWN RD. READING, PA 19605 USA
610-777-1374 800-492-1212 Fax: 610-796-5954
VISIT WWW.GAI-TRONICS.COM FOR PRODUCT LITERATURE AND MANUALS
Pub. 42004-308G
Model 234WM-202 Wall- Mount Sta nc hi on Ass embly Page 2 of 11
Installation
The following sections provide information on the installation of the complete wall-mount stanchion.
Fig
ure 1. Model 234WM-202 Wall-Mount Stanchion Assembly
p:\standard ioms - current release\42004 instr. manuals\42004-308g.docx 04/16
Pub. 42004-308G
Model 234WM-202 Wall- Mount Sta nc hi on Ass embly Page 3 of 11
Model 84505-202 Wall-Mount Stanchion Installation
1. Remove and save the two tamper-resistant screws at the top of the stanchion. See Figure 1.
OTE: GAI-Tronics Model 233-001 Security Screwdriver (sold separately) is required to remove the
N
tamper-resistant screws.
2. Remove the wall-mounting assembly from the front panel assembly. Refer to Figure 1. Detach the
chain from the wall-mounting assembly. See Figure 2.
3. Enlarge the conduit entry pilot hole(s) to be used for the stanchion power cables. See Figure 3.
4. Fasten the wall-mounting assembly to a wall or flat surface that can support at least 50 pounds, using
3/8-inch bolts. Refer to Figure 2 for mounting hole dimensions and ADA height requirements.
p:\standard ioms - current release\42004 instr. manuals\42004-308g.docx 04/16
Figure 2. Wall Mounting Instructions
Pub. 42004-308G
Model 234WM-202 Wall- Mount Sta nc hi on Ass embly Page 4 of 11
Grounding Requirements
This unit must be grounded in accordance with the National Electrical Code (NEC) in the United States or the Canadian Electrical Code (CEC) in Canada. A #10 grounding stud has been provided at the base of the stanchion for grounding. Connect the #10 grounding stud to a grounding electrode. A grounding electrode rod is typically 8 feet (2.44 m) long per NEC 250, or 9.84 feet (3 m) long per CEC Rule 10.
Figure 3. Conduit/Surge Protection Locations
p:\standard ioms - current release\42004 instr. manuals\42004-308g.docx 04/16