General Information
Product Overview
The Model 12576-503 and 12576-50315 (15-foot cord)
Desktop Access Panels with LCD Display are
components of GAI-Tronics’ ADVANCE system.
The operation of each access panel is programmed at
the ADVANCE system control cabinet. Operating
capabilities include: voice paging, party line
communication (with other access panels or
Page/Party
alarms, and a text display of the system operating
status.
The access panel speaker can broadcast page and alarm
audio. A sounder (sonalert) can annunciate system
alarm/trouble conditions or communication requests to
the access panel operator.
®
stations), activation/reset of emergency
Figure 1. Model 12576-503 Desktop Access
Panel with LCD Display
Fea tures
120 V ac, 50/60 Hz input power Sonalert with volume control
Handset with pressbar paging switch Speaker with volume control
24 push-button switches with associated LEDs
(software configurable)
Lamp test push button Audio accessory port
LCD text display
Three push-button switches without LEDs
(software configurable)
GAI-Tronics Corporation 400 E. Wyomissing Ave. Mohnton, PA 19540 USA
610-777-1374 800-492-1212 Fax: 610-796-5954
V
ISIT WWW.GAI-TRONICS.COM FOR PRODUCT LITERATURE AND MANUALS
Pub. 42004-733L2C
Model 12576-503 & 12576-50315 Desktop Access Panels with LCD Display Page 2 of 13
NOTES:
If this unit is to be used as a replacement for a GAI-Tronics Model 727-001/12576-500 Desktop Access
Panel with Docking Station, it will be necessary to make changes to the ADVANCE configuration file
before use. Please contact GAI-Tronics Service for details.
This unit should only be used with the supplied power supply. Use with any other power supply will
result in damage to the unit.
Installation
Important Safety Instructions
1. Read, follow, and retain instructions – All safety and operating instructions should be read and
followed before operating the unit. Retain instructions for future reference.
2. Heed warnings – Adhere to all warnings on the unit and in the operating instructions.
3. Attachments – Attachments not recommended by the product manufacturer should not be used, as
they may cause hazards.
4. Servicing – Opening or removing covers may expose you to dangerous voltage or other hazards.
Refer all servicing to qualified service personnel.
5. This permanently connected apparatus must have a UL Listed circuit breaker incorporated in the
electrical installation of the building.
USA and Canada Consult the National Electrical Code (NFPA 70), Canadian Standards Association
(CSA 22.1), and local codes for specific requirements regarding your installation. Class 2 circuit wiring
must be performed in accordance with NEC 725.55.
e:\standard ioms - current release\42004 i nstr. manuals\4 2004-733l2c.doc
07/14
Pub. 42004-733L2C
Model 12576-503 & 12576-50315 Desktop Access Panels with LCD Display Page 3 of 13
Mounting
Remove the access panel from its protective packing. Simply position the access panel on a sturdy
horizontal surface in a convenient location where the handset and push buttons are readily accessible.
Figure 2. Access Panel - Top View
e:\standard ioms - current release\42004 i nstr. manuals\4 2004-733l2c.doc
07/14
Pub. 42004-733L2C
Model 12576-503 & 12576-50315 Desktop Access Panels with LCD Display Page 4 of 13
Field Wiring
Data (T X/RX)
An eight-pin data port (RJ45 jack) on the rear of the unit connects the
access panel data line to the ADVANCE system control cabinet.
A twisted pair cable (minimum Category 3) should be used for this
connection.
Observe cable conductor polarity (+/−) when making connections at
the control cabinet: (+ connects to + and − connects to −). No
damage will occur if the polarity is reversed, but the access panel will
not function. Maximum cable distance to the control cabinet is 3 km
when using No. 24 AWG (Category 3) cable.
Refer to Figure 3 for RJ45 jack pin out detail and Figure 5 for the
Figure 3. Data Connection Detail
data port location.
OTE: Pin 5 (+) and pin 4 (−) should be used for new installations. Pin 3 (+) and pin 4 (−) are used
N
when replacing a Model 727-001 Desktop Access Panel.
Power
The access panel is supplied with a 120 V ac/12 V dc wall plug power supply. Plug the power cord into
the power connector on the rear of the unit. Plug the other end into an ac electrical outlet (120 V ac @
50/60 Hz). Refer to Figure 5 for power connector location.
OTE: The access panel does not have an on/off power switch and will power up immediately upon
N
plugging in the power cable. The ADVANCE control cabinet must also be powered and running before
the access panel is operational. LEDs on the access panel will flash, the sounder will “beep” and the
display will read “No communication with ADVANCE” until data communication is established with the
ADVANCE control cabinet.
WARNING
The power supply included with the Model 12576-503 or 12576-50315 Access
Panel is specifically designed for this unit and must not be used with any other 12576 series or 727 series
Desktop Access Panels.
Ground
A customer ground for additional ESD protection is located on the back of the unit. Ensure the unit is
properly grounded in accordance with local and national electrical code guidelines.
e:\standard ioms - current release\42004 i nstr. manuals\4 2004-733l2c.doc
07/14
Pub. 42004-733L2C
Model 12576-503 & 12576-50315 Desktop Access Panels with LCD Display Page 5 of 13
Audio Accessory Port
An eight-pin audio port (RJ45 jack) on the rear of the unit is
available to connect GAI-Tronics Model XAAB002A Audio
Accessory Box to the access panel. Optional accessories, such
as microphones, headsets, footswitches, etc., can be connected
to the audio accessory box (sold separately). Refer to Pub.
43004-026 for more detailed information.
Alternatively, the audio port can be used to connect an external
audio source and contact closure directly to the access panel.
It also has a line level (0.775 Vrms) audio output which can be
connected directly to external devices, such as an amplifier.
Refer to Figure 4 for the external audio connection detail and
Figure 4. Audio Connection Detail
Figure 5 for the audio accessory port location.
Figure 5. Access Panel Rear View
e:\standard ioms - current release\42004 i nstr. manuals\4 2004-733l2c.doc