This manual is provided solely as an operational, installation, and maintenance guide and contains
sensitive business and technical information that is confidential and proprietary to GAI-Tronics.
GAI-Tronics retains all intellectual property and other rights in or to the information contained herein,
and such information may only be used in connection with the operation of your GAI-Tronics product or
system. This manual may not be disclosed in any form, in whole or in part, directly or indirectly, to any
third party.
General Information
Product Overview
The Model 12576-502 Desktop Access Panel is a
component of GAI-Tronics’ ADVANCE system.
The operation of each access panel is programmed
at the ADVANCE system control cabinet.
Operating capabilities include: voice paging, party
line communication (with other access panels or
Page/Party
emergency alarms.
The access panel speaker can broadcast page and
alarm audio. A sounder (sonalert) can annunciate
system alarm /trouble conditions or communication
requests to the access panel operator.
®
stations), and activation/reset of
Figure 1. Model 12576-502 Access Panel
Fea tures
• 120 V ac, 50/60 Hz input power • Sonalert with volume control
• Handset with pressbar paging switch • Speaker with volume control
• 24 push-button switches with associated LEDs
(software configurable)
• Lamp test push button • Audio accessory port
• 3 push-button switches (without LEDs)
(software configurable)
GAI-Tronics Corporation 400 E. Wyomissing Ave. Mohnton, PA 19540 USA
610-777-1374 800-492-1212 Fax: 610-796-5954
V
ISIT WWW.GAI-TRONICS.COM FOR PRODUCT LITERATURE AND MANUALS
Pub. 42004-732L2A
Model 12576-502 Desktop Access Panel Page: 2 of 11
Installation
Important Safety Instructions
1. Read, follow, and retain instructions – All safety and operating instructions should be read and
followed before operating the unit. Retain instructions for future reference.
2. Heed warnings – Adhere to all warnings on the unit and in the operating instructions.
3. Attachments – Attachments not recommended by the product manufacturer should not be used, as
they may cause hazards.
4. Servicing – Opening or removing covers may expose you to dangerous voltage or other hazards.
Refer all servicing to qualified service personnel.
5. This permanently connected apparatus must have a UL Listed 15-amp circuit breaker incorporated in
the electrical installation of the building.
USA and Canada Consult the National Electrical Code (NFPA 70), Canadian Standards Association
(CSA 22.1), and local codes for specific requirements regarding your installation. Class 2 circuit wiring
must be performed in accordance with NEC 725.55.
Mounting
Remove the access panel from its protective packing. Simply position the access panel on a sturdy
horizontal surface in a convenient location where the handset and push buttons are readily accessible.
Figure 2. Access Panel - Top View
f:\standard ioms - current release\42004 instr. manuals\42004-732l2a.doc
08/10
Pub. 42004-732L2A
Model 12576-502 Desktop Access Panel Page: 3 of 11
Field Wiring
Data (T X/RX)
An 8-pin data port (RJ45 jack) on the rear of the unit connects the
access panel data line to the ADVANCE system control cabinet. A
twisted pair cable (minimum Category 3) should be used for this
connection.
Observe cable conductor polarity (+/-) when making connections at
the control cabinet: (+ connects to +) and (- connects to -). No
damage will occur if the polarity is reversed, but the access panel will
not function. Maximum cable distance to the control cabinet is 3 km
when using No. 24 AWG (Category 3) cable.
Refer to Figure 3 for RJ45 jack pin out detail and Figure 5 for the data port location.
OTE:Pin 5 (+) and pin 4 (-) should be used for new installations. Pin 3 (+) and pin 4 (-) are used when
N
replacing the Model 727-001 Desktop Access Panel.
Figure 3. Data Connection Detail
Power
The access panel is supplied with a 120 V ac/12 V dc wall plug power supply. Plug the power cord into
the power connector on the rear of the unit. Plug the other end into an ac electrical outlet (120 V ac @
50/60 Hz). Refer to Figure 5 for power connector location.
OTE: The access panel does not have an on/off power switch and will power up immediately upon
N
plugging in the power cable. The ADVANCE control cabinet must also be powered and running before
the access panel is operational. LEDs on the access panel will flash and the sounder will “beep” until data
communication is established with the ADVANCE control cabinet.
f:\standard ioms - current release\42004 instr. manuals\42004-732l2a.doc
08/10
Pub. 42004-732L2A
Model 12576-502 Desktop Access Panel Page: 4 of 11
Audio Accessory Port
An 8-pin audio port (RJ45 jack) on the rear of the unit is
available to connect the GAI-Tronics Model XAAB002A
Audio Accessory Box to the access panel. Optional
accessories, such as microphones, headsets, footswitches, etc.,
can be connected to the audio accessory box (sold separately).
Refer to Pub. 43004-026 for more detailed information.
Alternatively, the audio port can be used to connect an external
audio source and contact closure directly to the access panel.
It also has a line level (0.775 Vrms) audio output which can be
connected directly to external devices, such as an amplifier.
Figure 4. Audio Connection Detail
Refer to Figure 4 for the external audio connection detail and
Figure 5 for the audio accessory port location.
Figure 5. Access Panel Rear View
f:\standard ioms - current release\42004 instr. manuals\42004-732l2a.doc