
All boilers come with a 24 month warranty that covers all
the manufacture of the boilers.
A magnetic filter must be fitted to the system in the horizontal

A load check should be taken into consideration when installing
tube to BS 2871. Part 1 is recommended.
We recommend that a minimum clearance of 450 mm should be
to the boiler plumbing and the internal electrical connections. A

All Fusion Electric Boilers have a 22 mm compression connection
We recommend isolation valves on each side of the magnetic
through the boiler and promote premature boiler shut down
An Auto air vent is integral within the boiler however an addi-
tional auto air vent must be fitted at the cylinder coil if the boiler
Where practical and if at all possible, we recommend that all
We recommend the use of an automatic bypass within this circuit
the heating system (sealed systems). Reference should be made to
to ensure that no debris is trapped in
the flow sensor as this may result in boiler failure. Where existing
the boilers should be set to 1.5 bar. All sealed systems should
to BS 4814, (Specification for Expansion Vessels).

to supply a heat pack that contains the relevant control valves,
that you need to connect the systems controls and plumbing
We also recommend the use of thermostatic radiator valves on all
After the system has been installed the cleansing and inhibiting
thoroughly making sure all drain cocks are fully open and that
the system is completely drained.
Add Fernox Heavy Duty restorer through the header tank or via
to the boiler entering modulation mode, then commission the
Any further information you may require regarding the protection
the normal way. The cleansing agent must be in the system
temperature. A longer period of time would be more beneficial to
the cleansing process especially if excess flux was used.
that for a protector to work correctly, the system must be properly
to prevent overflow ensure the cap is removed prior to starting
We recommend setting to 8l/min.