Furman Sound SB-1000 User Manual

Page 1
SB-1000 MANUAL
Page 2
SB-1000 MANUAL
1
FEATURES
600 Watt / 1000VA capacity
3 minute back-up at full 5 amp load.
32 minute back-up with typical computer / monitor
Adjustable output voltage for 110/115/120
RS-232 Interface performs
monitoring functions and provides orderly computer shutdown
Phone/fax line protection
19 inch rack mount ears included
UL - CUL listed
INTRODUCTION
Please read and save this manual!
Thank you for selecting the Furman SB-1000 or
SB-1000E uninterruptible power supply (UPS).
This manual is a guide to install and use the
UPS. It includes important safety instructions for operation and correct installation of the UPS. If you should have any problems with the UPS, please refer to this manual before calling customer service.
Please save the packaging materials! The UPS‘s shipping materials are designed to provide protection during delivery. These materials are invaluable if you ever have to return the UPS for service. Damage during transit is not covered under the warranty.
Intelligent Microprocessor Control
The UPS is a microprocessor-controlled unit. The SB-1000 provides reliable power during
AC swells, sags and interference.
Furthermore, in order to save the battery energy, the UPS will automatically turn off under backup mode if none of the connected equipment is activated.
Advanced Battery Management
The UPS conveys its battery’s status with the
use of visual and audible indicators located internally and on its front panel. Its self-test function (which occurs when the unit is activated) detects a weak battery before it is put into service.
S A F E T Y I N F O R M AT I O N
SAVE THESE INSTRUCTIONS – This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries.
Servicing of the UPS and/or
replacement of the batteries should be performed by authorized Furman service professionals only.
FEAT U R E S
Front Panel
1 “UPS1” Power Switch
Turns power ON/OFF to the UPS1 outlets on
the rear panel.
2 “UPS2” Power Switch
Turns power ON/OFF to the UPS2 outlets on
rear panel.
3 “Bypass” Power Switch
Turns power ON/OFF to the BYPASS outlet
on rear panel.
Page 3
SB-1000 MANUAL
2
UPS1
Test
Switch
Off
On
Silence BuzzerUPS2
Bypass
Battery Fault
AC Normal
Battery in use
UPS1
Test
Switch
Off
On
Silence BuzzerUPS2
Bypass
Remote
Port
OUT
BREAKER
INPUT
BYPASS
UPS2
UPS1
TEL/MODEM
IN
Battery Fault
AC Normal
Battery in use
SB-1000 / SB-1000 E Front Panel
1 2 3 4 5 6 7 8
4 “Battery Fault” Indicator
The indicator will light when the battery is
weak. Recharge the battery for at least four hours. If the light remains after recharging, replacement of the batteries may be necessary by a Furman service professional.
5 “AC Normal / Battery in use” Indicator
When indicator is ON, the power condition is
normal. When indicator is flashing, the unit is in Battery backup mode.
software to support WINDOWS, DOS, NOVELL operating systems.
2 Phone/Fax Protection Ports
3 Circuit Breaker Protection
Serves as a current overload and fault protection.
4 IEC AC input
The AC power cord plugs in here.
6 “Test Button”
Use this button to put the unit into battery backup mode to check for proper operation. It also turns off the alarm when in backup
5 Bypass Outlet
This provides a convenient surge protected
outlet for items not requiring sag/swell protection or backup during power failure.
mode.
6 UPS2 Outlets
7 Main Power Switch
This can be used as the master on/off switch
for your equipment connected to the UPS.
8 optional rack ears (supplied)
Rear Panel
1 Communication Function
Provides RS-232 interface and UPSMON
These outlets have battery backup protection
and can be controlled by the UPS2 power switch on the front panel.
7 UPS1 Outlets
These outlets have battery backup protection
and can be controlled by the UPS1 power
switch on the front panel.
SB-1000 Rear Panel
1 2 3 4 5 6 7
Page 4
SB-1000 MANUAL
3
UPS1
Test
Switch
Off
On
Silence BuzzerUPS2
Bypass
Remote
Port
Remote
Port
OUT
BREAKER
BREAKER
INPUT
INPUT
BYPASS
BYPASS
UPS2
UPS2
UPS1
UPS1
TEL/MODEM
IN
OUT
TEL/MODEM
IN
Battery Fault
AC Normal
Battery in use
SB-1000 E Rear Panel
1 2 3 4 5 6 7
INSTA L L ATION
Inspect the UPS upon receipt. Any damage to the packaging or unit is not covered under warranty. Contact your parcel carrier.
1) Recharge the batteries
The UPS may be used immediately upon
receipt. Recharging the batteries at least eight hours before using the UPS is recommended. Energy loss may occur during shipping or storage. To recharge the battery, simply plug the UPS into an AC outlet. Once the power cord is connected, the UPS batteries will automatically start charging.
2) Connect the loads
Plug your primary equipment into the battery power-supplied outlets UPS 1 and UPS 2 . Plug your peripheral equipment to the bypass outlet. Do not plug high-current equipment such as power amplifiers, projectors, and large mixing consols into the UPS 1 or 2 outlets, as they may cause the circuit breaker to trip. It is recommended that heavy loads be connected to the bypass outlet.
3) Connect the telephone
If you wish to protect a fax or modem, connect the telephone cable from the wall outlet to the “IN” jack. Connect the telephone cable
(provided) from the “OUT” jack to the fax
or modem. These ports are not for network protection.
4) Connect to the utility power
Plug the UPS to a grounded AC receptacle.
Avoid using extension cords. If used, make sure they are rated for at least 15 amps.
5) UPS self-test
The UPS will conduct a self-test each time it
is switched on. Do not add or remove any equipment while the UPS conducts this self­test; wait until the Power indicator lights up, once completed, switch on your equipment.
6) Overload protection
If an overload situation (more than 5 amps
load) is detected during self-test, the UPS audible alarm will activate, emitting a long beep and then will automatically shut down the system. If this occurs, unplug at least one piece of equipment from the battery supplied outlets. Switch off the UPS, wait 5 seconds and check to make sure the circuit breaker is set, then switch it on again.
7) Optimal battery status
To maintain the optimal status of the battery,
leave the UPS plugged in at all times.
8) Self-protection feature
The UPS is equipped with a self-protection
feature which prevents people from tampering with the unit and subsequently damaging it. It is programmed so that once it is switched off, the user must wait 5 seconds before switching it on again.
9) Storage
Cover and store the UPS with the battery fully charged. During extended storage, recharge the batteries every three months to ensure battery life.
Page 5
SB-1000 MANUAL
4
OPERAT I O N
1) Operation check
It is recommended that the user perform a simulation test when using the UPS for the first time or when adding an additional piece of equipment. Conduct a simulation-test: first, switch on the UPS and wait for the power indicator to light up, then simply unplug the UPS to simulate a utility failure.
2) Check the power requirement of your equipment
A. Make sure the total power of your equipment
does not exceed rating capacity. (600W /
1000VA)
B. Also make sure the equipment you plugged into the Battery Power-Supplied outlets does not require total power exceeding the capacity of the UPS (600W / 1000VA). Otherwise, overload may occur and cause the circuit breaker to trip.
3) Limited rating power of UPS
When a utility failure occurs, the UPS output
outlets will supply power to your equipment from its battery, and the alarm will beep every 5 seconds. Be sure that your equipment is running under the limited rating power. Plug the UPS back into the existing power source. Repeat the test a few times to make sure the UPS works properly and to determine the expected runtime.
SOFTWARE & COMPUTER INTERFA C E
1) Power Monitoring Software
The UPSMON series software acts as
a standard RS-232 interface to perform monitoring functions, and then provides an orderly shutdown of a computer in the event of power failure. Moreover, UPSMON displays all the diagnostic symptoms on monitor, such as Voltage, Frequency, and Battery level, etc.
The software is available for DOS, Windows
3.1x, Windows 95/97/2000/ME/XP, Windows NT or later, Novell Netware.
2) Characteristics of the computer interface port
The computer interface port has the following
characteristics:
The communication port on the back of the
UPS may be connected to the host computer.
This port allows the computer to monitor the
status of the UPS and control the operation of the UPS, in some cases. Its major functions normally include some or all of the following:
To broadcast a warning when power fails
To close any open file before the batteries are exhausted
To turn-off the UPS
BAT T E RY C A B I N E T
1) Battery life of the UPS
The battery life of the UPS is about 3-6 years
under normal usage.
2) Battery Replacement
Once the UPS’s batteries is no longer useful,
it must be replaced. Please contact Furman service personnel for replacement (see service section).
Page 6
SB-1000 MANUAL
5
ONE YEAR LIMITED WARRANTY
Furman Sound, Inc., having its principal place of business at 1997 South McDowell Blvd., Petaluma, CA 94954 (“Manufacturer”) warrants its SB-1000 (the “Product”) as follows:
Manufacturer warrants to the original Purchaser of the Product that the Product sold hereunder will be free from defects in material and workmanship for a period of one year from the date of purchase. The battery is warranted for a period of 90 days. The Purchaser of the product is allowed fifteen days from the date of purchase to complete warranty registration by mail or on-line at the Furman website. If the Product does not conform to this Limited Warranty during the warranty period (as herein above specified), Purchaser shall notify Manufacturer in writing of the claimed defects. If the defects are of such type and nature as to be covered by this warranty, Manufacturer shall authorize Purchaser to return the Product to the Furman factory or to an authorized Furman repair location. Warranty claims should be accompanied by a copy of the original purchase invoice showing the purchase date; this is not necessary if the Warranty Registration was completed either via the mailed in warranty card or on-line website registration. Shipping charges to the Furman factory or to an authorized repair location must be prepaid by the Purchaser of the product. Manufacturer shall, at its own expense, furnish a replacement Product or, at Manufacturer’s option, repair the defective Product. Return shipping charges back to Purchaser will be paid by Manufacturer.
THE FOREGOING IS IN LIEU OF ALL
OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED
TO THE IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. Manufacturer does not warrant against damages or defects arising out of improper or abnormal use of handling of the Product; against defects or damages arising from improper installation, against defects in products or components not manufactured by Manufacturer, or against damages resulting from such non­Manufacturer made products or components.
This warranty shall be cancelable by
Manufacturer at its sole discretion if the product is modified in any way without written authorization from Furman Sound. This warranty also does not apply to Products upon which repairs have been affected or attempted by persons other than pursuant to written authorization by Manufacturer.
THIS WARRANTY IS EXCLUSIVE. The sole
and exclusive obligation of Manufacturer shall be to repair or replace the defective Product in the manner and for the period provided above. Manufacturer shall not have any other obligation with respect to the Products or any part thereof, whether based on contract, tort, strict liability or otherwise. Under no circumstances, whether based on this Limited Warranty or otherwise, shall Manufacturer be liable for incidental, special, or consequential damages. Manufacturer’s employees or representatives’ ORAL OR OTHER WRITTEN STATEMENTS DO NOT CONSTITUTE WARRANTIES, shall not be relied upon by Purchaser, and are not a part of the contract for sale or this limited warranty.
This Limited Warranty states the entire
Page 7
SB-1000 MANUAL
6
obligation of Manufacturer with respect to the Product. If any part of this Limited Warranty is determined to be void or illegal, the remainder shall remain in full force and effect.
S E R V I C E
Before returning any equipment for repair, please be sure that it is adequately packed and cushioned against damage in shipment, and that it is insured. We suggest that you save the original packaging and use it to ship the product for servicing. Also, please enclose a note giving your name, address, phone number and a description of the problem.
NOTE: All equipment being returned for repair must have a Return Authorization (RA) Number. To get an RA Number, please call the Furman Service Department: (707) 763-1010, ext. 121. Please display your RA Number prominently on the front of all packages.
Page 8
SB-1000 MANUAL
TROUBLESHOOTING
The UPS has a self-protect feature that prevents it from being damaged as a result of overheating. If the temperature is higher than 131°F (55°C), wait for a while and let the UPS become cool.
Problems Possible Cause Solution
Full-time Bypass outlets stop providing power to the equipment
UPS doesn’t perform to its expected runtime.
UPS cannot be turned on.
Circuit breaker button popped up as a result of overload.
Batteries are undercharged or depleted due to frequent power outages.
The power required by your equipment slightly exceeds the capacity of the UPS.
The batteries are slightly worn-out.
The UPS is designed to prevent damage to equipment.
The batteries are worn-out. Replace the batteries by following the
Mechanical problem. Contact your sales representative.
Unplug at least one piece of equipment from the Full-time Bypass outlets. Switch off UPS, wait 5 seconds, reset the circuit breaker (press down breaker button), then switch on UPS.
Recharge the batteries by leaving the UPS plugged in and switched on.
Unplug at least one piece of equipment from the UPS outlets.
Call the service personnel to replace the battery.
Switch UPS off, wait for 5 seconds, then switch UPS on.
instructions in this manual.
Page 9
SB-1000 MANUAL
SPECIFICATIONS
Input: Capacity: 1000VA / 600W Voltage: +/-25% at line input Frequency: 50 or 60 Hz +/-10% (auto sensing)
Output: Voltage (on battery): Simulated sine wave at 110V/115V/120V or 220V/230V/240V +/- 5% Frequency (on battery): 50 or 60 Hz +/- 5% AC Line Voltage Regulation: Input Voltage Range: 90 VAC to 150 VAC (E-Version Input Voltage Range: 175 VAC to 290 VAC) Output Voltage Range: 109 VAC to 131 VAC (E-Version Output Voltage Range: 201 VAC to 252 VAC) Transfer Time: 2-4 milliseconds, including detection time
Protection and Filtering: EMI/RFI filter: 10 dB at 0.15 MHz, 50dB at 30MHz Overload Protection: UPS automatic shutdown if overload exceeds 110% of nominal at 60 seconds and 130% at 3 seconds Unit Input: Circuit breaker for overload & short circuit protection 10Base-T Cable Port: Phone/Fax (UTP, RJ-45) compatible jacks Short Circuit: UPS output cut off immediately or input fuse protection
Batteries: Type: Sealed, maintenence-free lead acid Typical Recharge Time: 8 hours to 90% full capacity Protection: Automatic self test & discharge protection, Replace battery indicator Back-up Time: 3 - 180 min. (depending on computer load)
Physical: Net Weight: 26 lbs Shipping Weight: 29 lbs Dimension: 14.8” W (19” with rack ears) x 13.8” D x 1.75” H
Alarm: Battery Back-up: Slow beeping sound (about 0.47 Hz) Battery Low: Rapid beeping sound (about 1.824 Hz) Overload: Continuous beeping sound
Interface: RS-232C port interface: RS-232C Bi-directional communication port
Environment: Ambient Operation: 3,500 meters max. elevation, 0-95% humidity non-condensing, 0-40 deg C Audible Noise: <40dBA (1 meter from surface) Storage Condition: 15,000 meter max.
Page 10
SB-1000 MANUAL
Page 11
SB-1000 MANUAL
Page 12
SB-1000 MANUAL
Furman Sound, Inc.
Petaluma, California 94954-6919 USA
1997 South McDowell Blvd.
Phone: 707-763-1010
Fax: 707-763-1310
Web: www.furmansound.com
E-mail: info@furmansound.com
Loading...