Furman MP15, MP20, MP15Q, MP20Q User Manual

Furman Sound, Inc.
+12V STATUS REM GND DELAY
MINIPORT #1
MINIPORT #2
+12V STATUS REM GND DELAY
+12V STATUS REM GND DELAY
MINIPORT #1
MINIPORT #2
+12V STATUS REM GND DELAY
TO OTHER UNITS
TO
OTHER UNITS
OPTIONAL LEDS
UNIT 2
UNIT 1
ADD GROUND
FOR > 150' RUNS
OPTIONAL LEDS
UNIT 2
UNIT 1
ADD GROUND
FOR > 150' RUNS
1997 South McDowell Blvd. Petaluma, California 94954-6919 USA Phone: 707-763-1010 Fax: 707-763-1310 Web: http://www.furmansound.com E-mail: techsupport@furmansound.com
MiniPort AC Power Relays
MODELS MiniPort-15/15Q, MiniPort-20/20Q
Instruction Sheet
MiniPort-20 Wiring Diagram
Figure 1. Connections for single or multiple MiniPort-20 units, Mo­mentary or Maintained mode.
For control from more than one location, use Momentary Mode and parallel switch connections.
General Information
MiniPort-20
in the U.S. and Canada. The MiniPort-15Q
4-9935
Figure 2. Connections for amplier inrush current reduction, using delayed turn-on feature. (Turn-off is not delayed.)
If using the delay feature and momen­tary switches, rst unit must be in Mo­mentary Mode, all others in Maintained Mode. For control from more than one location, parallel switch connections to Unit 1.
Th e Mi n iPo r t-20 Power Relay provides a 20 amp relay switched 120 VAC outlet, with a terminal strip that allows remote con tro l via safe, inex pen sive, low voltage Class 2 control wiring. The MiniPort-15 is identical to the MiniPort-20, but is rated at 15 amps. Both units include an internal 12 VDC supply. They are housed in a rugged all-metal enclosure and come equipped with a heavy duty, 10 foot AC cord. The MiniPort-20 and -15 are listed by Underwriters’ Laboratories (UL) for use
and 20Q, (see other side), are designed for quad box mounting and have fewer features.
The MiniPort-20 and MiniPort-15 can be used independently with an RS-1 System Control Panel, or with any other momentary or maintained-action SPST switch. MiniPorts can also be used with the Furman PowerLink or PowerPort for extra capacity.
With the addition of a PS-REL AC Relay, the MiniPort can also be used to extend the capacity of a Furman PS-8R or PS-PRO Power Sequencer — or any product with a switched outlet, such as a receiver/amp controlled with a wireless remote. When used in this manner, the MiniPort is switched on or off when the outlet that the PS-REL is plugged into goes on or off.
Momentary vs. Maintained Contact Switching
An on-off switch of either kind may be used to actuate the Min iPort. Maintained swi tch es, suc h as most tog gle switches, push-on/push-off button switches, and the Furman RS-1 locking key switch, stay open until thrown, then stay closed until thrown again. Momentary switches, usually pushbutton types, are normally open and stay closed only as long as the button is pressed.
Maintained switches are most convenient when there is only one remote switch location; momentary switches allow turn-on or turn-off from multiple locations.
MiniPorts come factory-co nfigured for mai ntained op­eration. They may be easily converted to momentary operation by moving a jumper on the MiniPort’s circuit board. To do this, rst disconnect the unit from AC power. Remove the four screws that secure the bottom cover. In the middle of the circuit board (a s viewed from the bottom of the unit) , ther e are two pairs of terminals, one labeled “MAINTAINED” and the other “MOMENTARY.” There is a small black jumper linking the MAINTAINED terminals. Slide it up and off, and replace it securely over the MOMENTARY terminals. Reattach the cover.
Maintained Mode
In the simplest conguration, to control a single MiniPort from a single remote location, connect a maintained-action SPST switch to the REM and +12V terminals. Power will be available at the MiniPort-20’s AC outlet when the switch is open, and will be removed when it is closed. If the cable run is greater than 150 feet, we recommend that the REM wire be tied to ground during on operation rather than leaving it oating, using an SPDT switch as shown in Figure 1.
Momentary Mode
In Momentary Mode, the MiniPort-20 and MiniPort-15 have “memory” — they only need a momentary signal on the remote terminal to change their state from OFF to ON, or ON to OFF.
960049-2146
NC
POWER
MAX LOAD 20 A
120 VAC 60 Hz
8-15VDC
TO TURN ON
CLASS 2 WIRING
-
POWER RELAY
MINIPORT-20Q
+
When rst plugged in (or after power is lost and reapplied for any reason) the memory state is OFF, meaning that no power will be available at the outlet. It will stay OFF until turned ON by a momentary connection of the REM terminal to +12V. It will then stay ON until turned OFF by a second momentary connection. The ON or OFF state begins on the rising edge of the signal.
The Furman RS-1 Remote System Control Panel is an attractively nished key switch designed for use in single-gang wall mount boxes.It can control, from one location, most Furman power products that have remote capability. The RS-2 Remote System Control Panel is identical to the RS-1 in most respects, but with a momentary function rather than maintained. The RS-2 is ideal for installations requiring multiple remote switches.
IMPORTANT NOTE REGARDING MOMENTARY MODE:
If multiple MiniPorts are being controlled in Momentary Mode, power loss to any one of the units will likely cause its memory to be different than that of the other units. Not only will this be irritating, it can also be dangerous, as it may be ON when the others are OFF. To correct this potential problem (as exists in any simple momentary switch product), our thoughtful engineers devised a simple method of holding the switch down (REM to +12) for at least four seconds. This resets all units to the OFF condition, and avoids having to disconnect AC power from all units.
Linking Multiple Units
Multiple MiniPorts may be connected together so that all are controlled by a single switch closure. All the units must be set to the same mode depending on the type of switch or switches to be used (use momentary mode and momentary switches if more than one switch is required.) All the units must be paralleled by tying together all the +12V terminals, all the REM terminals, and all the GND terminals (see Figure 1).
Multiple MiniPorts may be linked so that they all turn on simultaneously, as discussed above, or in a delayed sequence. In a delayed sequence, only the turn-ons are delayed (all turn-offs occur simultaneously.) This feature is particularly use­ful in staggering the turn-on of large power amps to avoid large inrush currents that might trip the house circuit breakers. The delay interval is approximately two to three seconds (the rst unit turns on with the switch closure, the second in the chain about 3 seconds later, the third unit 3 seconds after the second, etc.)
The choice of delayed or simultaneous linking is available regardless of whether maintained or momentary switching is used. However, if delayed linking is used with momentary switching, only the rst MiniPort should be set to momentary mode, and all momentary switches should be connected in parallel between the rst unit’s +12V and REM terminals. The second and subsequent MiniPorts must be left in maintained mode. See Figure 2.
Optional Remote LED Indicator
The MiniPort terminal labeled STATUS is an output that may be used to illuminate an LED at a remote location to indicate that power is available at the MiniPort’s outlets. If it is HIGH (+12V rel­ative to the GND terminal), the unit is ON; if LOW, the unit is OFF. Simply connect the indicator LED between STATUS and GND (do not use a series resistor). If multiple units are used, a separate LED must be used to indicate the status of each. Do not connect the STATUS terminals of multiple units together.
Knockout Holes
Both the MiniPort-15 and the MiniPort-20 come equipped with two knockout holes for permanent installation with 1/2" conduit — one on the top surface, the other on the bottom. Use of the bottom knockout hole requires removing the AC cord. The National Electrical Code allows for up to eleven 14awg conductors of THHN/THWN/THWN-2 type in 1/2” conduit (MiniPort-15) or up to eight 12awg conductors (MiniPort-20). For grounding and other details, please consult a licensed electrician.
MiniPort 20-Q/15Q Quad Box Power Relays
The new 20-amp MiniPort-20Q and the MiniPort-15Q (15 amps) provide a pair of remotely-activated, relay­controlled outlets, set up for mounting in any standard el e ctrica l quad box , either directly or with a “mud ring” attached.
Du e to the spa c e limitations of a quad box, the MiniPort “Q” models have a smaller feature set than the MiniPort-15 and MiniPort-20.
Mi n iPor t -Q’s have no internal power supply; a maintained 8-15 VDC supply capable of sup­plying 10 mA is required to turn on the outlets.
Th i s can be sup p lied by a Furman Pow erLin k, ASD-120, or a PS-8R (with a simple internal modication to the PS-8R.)
Solder pads are available on the circuit board to allow control wiring from inside the quad box.
Dimensions
The MiniPorts’ body dimensions are: 5.5" (H) x 3.75" (W)
x 2" (D). The baseplate is 5.25" square.
Differences From the Earlier MiniPort
The MiniPort-20 and MiniPort-15 are upgraded versions of an earlier product designated simply “MiniPort”. These new MiniPorts are equipped for remote operation using either maintained or momentary contact switches to initiate the turn-on or turn-off. (The original MiniPort required maintained contact switches.) Also, a Delay Out terminal has been added to permit sequenced turn-on when multiple MiniPorts are linked. Finally, the new MiniPorts have the previously described knockout holes at top and bottom for permanent installation with 1/2" metal conduit.
Three Year Limited Warranty
All Furman MiniPort models are protected by a limited three year warranty, covering defects in materials and workmanship, provided that the registration card is lled out and returned by the customer. Otherwise, a one year warranty applies. Products must have a proof of purchase from a Furman authorized dealer. During this period, Furman will make any necessary repairs without charge for parts or labor. Shipping charges to the factory or repair station must be prepaid by the owner; return shipping charges (via UPS Ground) will be paid by Furman. This warranty applies only to the original owner and is not transferable. Also, it does not apply to repairs done other than by the Furman factory or its Authorized Repair Stations.
This warranty may be cancelled by Furman at its sole discretion if the unit has been subjected to physical abuse or has been modied in any way without writ­ten authorization from Furman. Furman’s liability under this warranty is limited to repair or replacement of the defective unit.
Furman will not be responsible for incidental or consequential damages resulting from the use or misuse of its products. Some states do not allow the exclusion of incidental or consequential damages, so the above limitations may not apply to you. This warranty gives you specic legal rights, and you may also have other rights which vary from state to state.
Service
Before retu rn in g any equ ip ment for repai r, please be sure that it is adequately packed and cushioned against damage in shipment, and that it is insured. We suggest that you save the original packaging and use it to ship the product for servicing. Also, please enclose a note giving your name, address, phone number and a description of the problem.
NOTE: All equ ip ment being returned for repair must have a Retu rn Authorization (RA) Number. To get an RA Number, please call the Furman Service Department (707-763-1010 ext. 40) between 8 a.m. and 5 p.m. U.S. Pacic Time.
Please display your RA Number prominently on the front of all packages.
Loading...