Full Gauge Controls MT-530 Super User Manual

TEMPERATURE AND HUMIDITY
DIGITAL CONTROLLER WITH
SERIAL COMMUNICATION
4.2 - Parameters configuration
- Access thefunction F01 pressing simultaneously thekeys and for 2 seconds until appearing , releasingafter that.Soon it willappear , andthen press (short touch).
- Usethe keys and to enteracess code(123) and, whenready press to confirm.
-After selecting thefunction, press (short touch)to visualizethe value configuredfor thatfunction.
- Usethe keys and tochange the value,and when ready, press tomemorizethe configured
value andreturn tothe menu offunctions.
- Toleavethe menu offunctions andreturn to normaloperation, press until appear .
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
4. CONFIGURATIONS
4.1 - Temperature and humidity adjust (SETPOINTS):
- Press for 2seconds until appears, then releaseit. The indication and theadjusted
temperature forTHERM outputwill appear.
- Usethe keys and to changethe valueand thenpress to recordit.
- Now and adjustedhumidity forHUMID outputwill appear.
- Usethe keys and to changethe valueand thenpress again.
-Then, ifthe AUXoutput issetto control(F14 =0, 1,2 or3)itmay appear or .
- Usethe keys and to changethe valuefor theAUX outputand thenpress to recordit.
SET
SET
SET
SET
4.4 - Parameters description
MT-530 %uper
1. DESCRIPTION
MT-530 %uper is an instrument that indicates and controls the environment temperature and humidity,indicated for lowandaverage relative airhumidity (from 20to85%, without condensation)and temperature of -10 to 70ºC. Its sensors of temperature and humidity are joined in an only bulb, that reduces thespace inwiring of theinstallation. The instrumenthas serialcommunication for connectionwith the via Internet. Product complieswith ULInc. (UnitedStatesand Canada).
®
SITRAD
2. APPLICATION
3. TECHNICAL SPECIFICATIONS
• Humidificators/dehumidificators
• Grainsdrying
• Laboratories
• Surgicalrooms
• Climatizedcellars
• Informationtechnology centers
MT-530Super - 115or 230 Vac±10%(50/60Hz) MT-530LSuper -12or 24 Vac/dc
-10 to70.0 ºC±1.5°C (with resolutionof 0.1°C) 14 to158 ºF ±3°F (with resolutionof 1°F)
20 to85%RH ±5%RH (withresolution of 0.1%RH)
5(3)A/250Vac1/8HP (eachoutput)
71 x28 x71 mm
0 to50°C 32 to122°F
10 to90% RH(without condensation)
- PowerSupply:
- ControlTemperature:
- ControlHumidity:
- Loadcurrent:
- Dimensions:
- Operationtemperature:
- Operationhumidity:
DescriptionFun
Access code: 123 (one hundred and twenty-three)
hermostat operation mode (THERM output)
Minimum setpoint allowed to the user (thermostat)
Maximum setpoint allowed to the user (thermostat)
Control differential (hysteresis) of the thermostat
Minimum delay to turn the thermostat output on
Humidistat operation mode (HUMID output)
Minimum setpoint allowed to the user (humidistat)
Maximum setpoint allowed to the user (humidistat)
Control differential (hysteresis) of the humidistat
Minimum delay to turn the humidistat output on
Humidity output (time on)
Humidity output (time off)
Auxiliary output operation mode (AUX)
Minimum setpoint allowed to the user (AUX output)
T
CELSIUS
FAHRENHEIT
Min.
-99
0 - refrig.
-10.0
-10.0
0
0
0 - dehum.
0
0
0
0
0
0
0
0
Max.
999
1 - heat
70.0
70.0
20.0
999
1 - hum.
100
100
20.0
999
999
999
10
100
Unit
-
-
°C
°C
°C
seg.
-
%RH
%RH
%RH
sec.
sec.
sec.
-
-
Standard
-
-10.0
70.0
1.5
0
0 - refrig.
1 - hum.
0
100
5
0
5
5
5
0
Min.
-99
0 - refrig.
14
14
0
0
0 - dehum.
0
0
0
0
0
0
0
0
Max.
999
1 - heat
158
158
36
999
1 - umid.
100
100
20.0
999
999
999
10
100
Unit
-
-
°F
°F
°F
seg.
-
%RH
%RH
%RH
sec.
sec.
sec.
-
-
Standard
-
0 - refrig.
14
158
3
0
1 - hum.
0
100
5
0
5
5
5
0
Maximum setpoint allowed to the user AUX output
Control differential (hysteresis) of the AUX output
Minimum delay to turn the AUX output on
Time base of AUX output timer
AUX output (time on)
AUX output (time off)
Minimum delay to turn the AUX output on (alarm mode)
Acting point of Buzzer by low temperature
Acting point of Buzzer by high temperature
Acting point of Buzzer by low
Acting point of Buzzer by high
Maximum time of the activated THERM output to activate the alarm
Maximum time of the activated HUMID output to activate the alarm
()
Buzzer operation mode
humidity
humidity
Low room temperature alarm
High room temperature alarm
Low room humidity alarm
High room humidity alarm
0
0
0
0
0
0
-10.0
-10.0
0
0
0
0
-10.0
-10.0
0
0
0
0
100
20.0
999
999
999
999
70.0
70.0
100
100
999
1
70.0
70.0
100
100
999
999
-
-
sec.
-
sec.
sec.
°C
°C
%RH
%RH
min.
-
°C
°C
%RH
%RH
min.
min.
100
5
0
0
5
5
-10.0
70.0
0
100
0
1
-10.0
70.0
0
100
0
0
0
0
0
0
0
0
14
14
0
0
0
0
14
14
0
0
0
0
100
20.0
999
999
999
999
158
158
100
100
999
1
158
158
100
100
999
999
100
5
0
0
5
5
14
158
0
100
0
1
14
158
0
100
0
0
-
-
sec.
-
sec.
sec.
°F
°F
%RH
%RH
min.
-
°F
°F
%RH
%RH
min.
min.
Maximum time of the activated AUX output to activate the alarm
Buzzer time on
Buzzer time off
Inhibition time of Buzzer during electrical supply
Display mode
Temperature display offset
Humidity display offset
Network equipment address RS-485
0
0
0
0
0
-5.0
-20.0
0
999
999
999
999
2
5.0
20.0
247
sec.
min.
-
°C
%RH
-
min.
sec.
0
1
1
0
0
0
0
1
0
0
0
0
-9
-20.0
0
0
999
999
999
2
9
20.0
247
999
1
1
0
0
0
0
1
0
sec.
min.
-
°F
%RH
-
min.
sec.
E251415
Ver.02
MT530SP02-01T-12400
TH
E
R
M
HU
M
ID
M
T-530
Super
A
U
X
B
U
Z
Z
Example: Humidification
Control =80% RH *Timeon = 20sec Hysteresis =5% RH *Timeoff = 10sec When humidityfalls to75% RH (80- 5),the humidistat outputstarts tocycle: 20 sec.on -10 sec. Off
F01 -
F02 -
It is necessary to change the configuration parameters. To visualize the adjusted parameters, it is not necessary toinsert thisaccess code.
Refrigeration Heating
Access code:123 (onehundred and twenty-three)
hermostat operationmode (THERMoutput)T
4.4 - Parameters description
F03 -Minimum setpointallowed to theend user(t
F04 -Maximum setpointallowed to the end user(thermostat)
F05 -Control differential(hysteresis) of thethermostat
F06 -Minimum delayto turn thethermostat outputon
It isto preventthat incorrect highor lowtemperatures be regulated.
It isthe differenceof temperature (hysteresis)between ON andOFF theTHERM output.
It is the minimum timethat thethermostat will keep turned off, itmeans, the space of time betweenthe last stopant thenext start.
hermostat)
F07- Humidistatoperation mode(HUMID output)
F08 -Minimum setpointallowed to theuser (humidistat)
F09 -Maximum setpointallowed to theuser (humidistat)
F10 -Control differential(hysteresis) of thehumidistat
F11-M
F12 -
F13 -
Dehumidification Humidification
Electronic limitswhose purposeis prevent thattoo highor too lowsetpoint humiditysare regulated.
It isthe differenceof humidity (hysteresis)between turn ONand turnOFF the HUMIDoutput.
It is the minimumtime thatthe HUMIDoutput will keep turned off, itmeans, thespace oftime between the laststop antthe next start.
It allowsto adustthe time thatHUMID outputwill keep turnedon.
It allowsto adustthe time thatHUMID outputwill keep turnedoff.
inimum delayto turnthe humidistat outputon
Humidity output(time on)
Humidity output(time off)
Note: F12and F13functions control acyclical program(in seconds) forthe humidistatoutput.
This cyclicalprogram allowsthat pulverized waterhas timeto transform inrelative airhumidity. Todisable thisfunction, adjust thenwith value“00.0”.
F14 -Auxiliary outputoperation mode(AUX)
F15 -Minimum setpointallowed to theuser (AUXoutput)
F16 -Maximum setpointallowed to theuser (AUXoutput)
Refrigeration Heating Dehumidification Humidification Intra-range alarm Extra-range alarm Independent cyclictimer Cyclic timer operating only when the temperature reaches the setpoint (THERM output deactivated) Cyclic timer operating only when the humidity reaches the setpoint (HUMID output deactivated) Cyclic timeroperating whenthe temperature orhumidity reachestheir setpoint
Cyclic timeroperating onlywhen the temperatureand humidityreaches their setpoints. When changing the value of this function the following parameters will be automatically adjusted with their defaultvalues: F15,F16, F17 andsetpoint forthe AUXoutput.
Electronic limitswhose purposeis prevent thattoo highor too lowsetpoint valuesare regulated. The limitswill dependon the operationmode ofthe output adjustedin F14.
It is the difference of temperature or humidity (hysteresis) between turn ON and turn OFF the AUX output. Thisfunction depends onthe operationmode of theoutput adjustedin F14.
It is theminimum timethat the AUX output willkeep turned off, it means,the spaceof time between the last stopant thenext start.
Allows configuringthe onor off timescale forAUX output cyclictimer.
F17 -Control differential(hysteresis) of theAUX output
F18 -Minimum delayto turn theAUX outputon
Time baseof AUXoutputtimer
This timeisvalid only when AUX output willbe configured in thecontrol mode (F14 configuredin 0, 1, 2 or 3).
F19 -
Seconds
Minutes
Seconds
Minutes
Seconds
Minutes
Minutes
Seconds
Value
Time on (F20) Time off (F21)
F20 -
F21 -
F22 -
F23 -
F24 -Low roomhumidity alarm
F25 -High roomhumidity alarm
AUX output(time on)
AUX output(time off)
It allowsto adustthe time thatAUX outputwill keepturned on whenset tocyclical timer.
It allowsto adustthe time thatAUX outputwill keepturned off whenset to cyclicaltimer.
Temperaturefor activationof the l
Temperaturefor activationof the high
Humidity foractivation ofthe l humidity
Humidity foractivation ofthe high humidity
Low roomtemperature alarm
High roomtemperature alarm
ow temperaturealarm.
temperature alarm.
ow alarm.
alarm.
F26 -Minimum delayto turn theAUX outputon (alarmmode)
It is theminimum timethat the AUX output willkeep turned off, it means,the spaceof time between the last stopantthe next start. Thistime is validonlywhen AUX output will beconfigured in thealarmmode (F14 configuredin 4or 5).
F27 -Buzzer operationmode
F28 -Acting pointof Buzzer bylow temperature
F29 -Acting pointof Buzzer byhigh temperature
F30 -Acting pointof Buzzer bylow humidity
Acting pointof Buzzerby high humidity
F32 -Maximum timeof the activatedTHERM outputto activate thealarm
Intra-range alarm Extra-range alarm
It isthe inferior valueof temperaturetothe buzzer alarmact as theconfigured Operation Modeof Buzzer (F27).
It is the superior value of temperature to the buzzer alarm act as the configured Operation Mode of Buzzer (F27)
It is the inferior value of humidity to the buzzer alarm act as the configured Operation Mode of Buzzer (F27).
Allows configuring the maximum time the output THERM can stay activated without reaching the setpoint before activating the audible alarm (BUZZER).To deactivate this function, just decrement the
F31 -
It is the superiorvalue ofhumidity tothe buzzeralarm actas theconfigured OperationMode ofBuzzer (F27).
value untilthe message is displayed.
Allows configuring the maximum time the output HUMID can stay activated without reaching the setpoint before activating the audible alarm (BUZZER).To deactivate this function, justdecrement the value untilthe message is displayed.
Allows configuring the maximum timethe output AUX can stayactivated without reaching the setpoint before activatingthe audible alarm(BUZZER). Todeactivatethis function, justdecrement the valueuntil the message is displayed.
Maximum timeof theactivated outputtoactivate the alarm
F34 -Maximum timeof the activatedAUX outputto activate thealarm
F33 - HUMID
F35 -Buzzer time on
F36 -Buzzer time off
F37 -Inhibition timeof Buzzer duringelectrical supply
It isthe timethatthe Buzzer willbe turnedon(cycle on). Toturnit off thesonore alarm(Buzzer) adjust the value “0”to thisfunction.
It is the time that the buzzer will be turnedoff (cycle off). To turn the sonore alarm (Buzzer)always on, adjust thevalue “0”to this function.
It isthe timewere the alarmwill keptturned off evenif in alarmcontitions. It serves to inhibit the buzzer during the time while the system do not reaches the working control temperature.
F38 -Display mode
F39 -Temperature displayoffset
F40 -Humidity displayoffset
F41 -Network equipmentaddress
Alternated indicationof temperatureand humidity Only indicationof temperature Only indicationof humidity
It allows to compensate eventual shunting lines in the reading of temperature proceeding from the
exchange ofthe sensoror cable lenghtalteration.
It allows to compensate eventual shunting lines in the reading of humidity proceeding from the
exchange ofthe sensoror cable lenghtalteration.
This isthe deviceaddress for communicationwith software.
Note: You cannothave twoor more deviceswith thesame address inthe network.
Sitrad
®
5. FUNCTIONS WITHFACILITATED ACCESS
5.1- Registers of minimum and maximum temperature and humidity
5.2 - To visualize humidity or temperature
Press . Will appear followed for minimumand maximum registeredtemperatures. After that will appear and theminimum andmaximum registered humidity.
To reset the registers, keep pressed during the visualization of the minimum and maximum
registers untilappear .
If theF38 function isnot in thealternatingwayof visualization (”0”)it´spossible visualize temperatureor humidity bypressing the key.
Note:
6. SIGNALLING
Led THERMon ­Led HUMIDon ­LedAUXon ­Led BUZZon -
T
H
Auxiliar
- Irregulartemperature sensor
- Irregularhumidity sensor
-
hermostat outputon
umidistat outputon
output on
Invalid configurationparameters;
- Inthis situationthe outputs areturned off;
- Checkwhich parametershave invalid dataand correctthem to returnto normaloperation.
Buzzer activated
7. SELECTION OFTHE UNIT (Cº /Fº)
In order to define the unit that theinstrument will operatein, enter function“F01” with the access code “231” and confirm withthe key. Press the key andthe indication willappear. Press
to choosebetween or and confirm.After selectingtheunit the message will appear, and the instrument will return to the function “F01”. Every time that the unit is changed, the parameters shouldbe reconfigured,since they assumethe “standard”values.
SET
SET
8. WIRING DIAGRAM
2
3
4
5
6
7
8
10
11
12
COMMON
THERM (NO)
HUMID (NO)
Above specified current
use contactors.
Power supply
and relays
common
0
1
Loads
supply
AUX (NO)
115V (12V )
230V (24V )
Loads
L3
L2
L1
- Dehumidificator
- Humidificator
- Contactor
- Solenoid
- Alarm
L3
- Dehumidificator
- Humidificator
- Contactor
- Solenoid
L2
- Contactor
- Solenoid
L1
9
Yellow
Green
Orangr and
Brown
Red
Serial communication
RS-485
A
B
Temperature and humidity sensor Cable: SB56 Violet protector
To the terminal of
the distribution box
9-8 9-7
115V 230V
MT-530 Super
12V 24V
MT-530L Super
IMPORTANT
1: 2:
3:
According tothe chaptersfrom the IEC60364standard:
Install on powersupply
Sensor cables and computer signals can be together, however not at the same place where power
supply andload wirespass for
Install suppresorof transientin parallel toloads toincrease the usefulllife ofthe relays
protectors againstover voltage
Wiring diagram of suppresors in contactors
Suppresor
A1
A2
A1 e A2 are the contactor coils.
Wiring diagram of suppresor for direct drive
Load
Suppresor
For direct activation the maximum specified current should be taken into consideration.
Note: Thesensor cablelenght can beincreased bythe user until200 metersusing 4 x0,20mm² cable.
AB
RS-485 Network
RS-485Serial Interface
®
Device used to establish the connection FullGauge Controls’ instrumentswith the Sitrad
.
Instrument
RS-485 Network
External
mesh
®
Integrating Controllers, RS-485 Serial Interface and Computer
A
B
A
A
BB
A
B
A
A
BB
A
B
A
A
BB
A
B
A
B
A
B
A
A
BB
A
B
Serial interface
RS-485
Full Gauge
MOD 64
A
A
BB
A
B
terminal
grounded
Distribution Box
Used toconnect morethan one instrumentto the Interface.The wire's connectionsmust be madein agreement with the followingrules: terminal ofthe instrument connects to the terminal of the distribution box, that must beconnected with the terminal of the Interface. Repeatthe actionfor terminals and , being the cable shield.
A
AA
B
The terminal of distributionbox must be connected tothe respective terminals of each instrument.
OUT1
OUT2
O
U
T
3
P
C
T
-4
0
0
R
p
lu
s
OUT4
A
L
MR
P
U
M
P
A
U
X1
A
U
X
2
M
IC
R
O
S
O
L
II
p
lu
s
ENVIRONMENTALINFORMATION Package:
Products:
Disposal:
The packages material are 100% recyclable. Just dispose it through specialized recyclers.
The electro components of Full Gauge controllers can be recycled or reused if it is disassembled forspecialized companies.
Do notburn or throwin domestic garbagethe controllers whichhave reached theend-of­life. Observe the respectively law in your region concerning the environmental responsible manner of dispose its devices. In case of any doubts, contact Full Gauge controls forassistance.
PROTECTIVE :VINYL
This adhesive vinyl (included inside the packing) protects the instruments against water drippings,as in commercialrefrigerators, for example.Do the applicationafter finishing theelectrical connections.
Remove the protective paper and applythe vinyl onthe entire superior part of the device, folding theflapsasindicated by the arrows.
72 mm
Dimension of the clipping
for setting of the instrument
in panel
29 mm
Loading...