Example: Humidification
Control =80% RH *Timeon = 20sec
Hysteresis =5% RH *Timeoff = 10sec
When humidityfalls to75% RH (80- 5),the humidistat outputstarts tocycle: 20 sec.on -10 sec. Off
F01 -
F02 -
It is necessary to change the configuration parameters. To visualize the adjusted parameters, it is not
necessary toinsert thisaccess code.
Refrigeration
Heating
Access code:123 (onehundred and twenty-three)
hermostat operationmode (THERMoutput)T
4.4 - Parameters description
F03 -Minimum setpointallowed to theend user(t
F04 -Maximum setpointallowed to the end user(thermostat)
F05 -Control differential(hysteresis) of thethermostat
F06 -Minimum delayto turn thethermostat outputon
It isto preventthat incorrect highor lowtemperatures be regulated.
It isthe differenceof temperature (hysteresis)between ON andOFF theTHERM output.
It is the minimum timethat thethermostat will keep turned off, itmeans, the space of time betweenthe
last stopant thenext start.
hermostat)
F07- Humidistatoperation mode(HUMID output)
F08 -Minimum setpointallowed to theuser (humidistat)
F09 -Maximum setpointallowed to theuser (humidistat)
F10 -Control differential(hysteresis) of thehumidistat
F11-M
F12 -
F13 -
Dehumidification
Humidification
Electronic limitswhose purposeis prevent thattoo highor too lowsetpoint humiditysare regulated.
It isthe differenceof humidity (hysteresis)between turn ONand turnOFF the HUMIDoutput.
It is the minimumtime thatthe HUMIDoutput will keep turned off, itmeans, thespace oftime between
the laststop antthe next start.
It allowsto adustthe time thatHUMID outputwill keep turnedon.
It allowsto adustthe time thatHUMID outputwill keep turnedoff.
inimum delayto turnthe humidistat outputon
Humidity output(time on)
Humidity output(time off)
Note: F12and F13functions control acyclical program(in seconds) forthe humidistatoutput.
This cyclicalprogram allowsthat pulverized waterhas timeto transform inrelative airhumidity.
Todisable thisfunction, adjust thenwith value“00.0”.
F14 -Auxiliary outputoperation mode(AUX)
F15 -Minimum setpointallowed to theuser (AUXoutput)
F16 -Maximum setpointallowed to theuser (AUXoutput)
Refrigeration
Heating
Dehumidification
Humidification
Intra-range alarm
Extra-range alarm
Independent cyclictimer
Cyclic timer operating only when the temperature reaches the setpoint (THERM output
deactivated)
Cyclic timer operating only when the humidity reaches the setpoint (HUMID output
deactivated)
Cyclic timeroperating whenthe temperature orhumidity reachestheir setpoint
Cyclic timeroperating onlywhen the temperatureand humidityreaches their setpoints.
When changing the value of this function the following parameters will be automatically adjusted with
their defaultvalues: F15,F16, F17 andsetpoint forthe AUXoutput.
Electronic limitswhose purposeis prevent thattoo highor too lowsetpoint valuesare regulated.
The limitswill dependon the operationmode ofthe output adjustedin F14.
It is the difference of temperature or humidity (hysteresis) between turn ON and turn OFF the AUX
output. Thisfunction depends onthe operationmode of theoutput adjustedin F14.
It is theminimum timethat the AUX output willkeep turned off, it means,the spaceof time between the
last stopant thenext start.
Allows configuringthe onor off timescale forAUX output cyclictimer.
F17 -Control differential(hysteresis) of theAUX output
F18 -Minimum delayto turn theAUX outputon
Time baseof AUXoutputtimer
This timeisvalid only when AUX output willbe configured in thecontrol mode (F14 configuredin 0, 1, 2
or 3).
F19 -
Seconds
Minutes
Seconds
Minutes
Seconds
Minutes
Minutes
Seconds
Value
Time on (F20) Time off (F21)
F20 -
F21 -
F22 -
F23 -
F24 -Low roomhumidity alarm
F25 -High roomhumidity alarm
AUX output(time on)
AUX output(time off)
It allowsto adustthe time thatAUX outputwill keepturned on whenset tocyclical timer.
It allowsto adustthe time thatAUX outputwill keepturned off whenset to cyclicaltimer.
Temperaturefor activationof the l
Temperaturefor activationof the high
Humidity foractivation ofthe l humidity
Humidity foractivation ofthe high humidity
Low roomtemperature alarm
High roomtemperature alarm
ow temperaturealarm.
temperature alarm.
ow alarm.
alarm.
F26 -Minimum delayto turn theAUX outputon (alarmmode)
It is theminimum timethat the AUX output willkeep turned off, it means,the spaceof time between the
last stopantthe next start. Thistime is validonlywhen AUX output will beconfigured in thealarmmode
(F14 configuredin 4or 5).
F27 -Buzzer operationmode
F28 -Acting pointof Buzzer bylow temperature
F29 -Acting pointof Buzzer byhigh temperature
F30 -Acting pointof Buzzer bylow humidity
Acting pointof Buzzerby high humidity
F32 -Maximum timeof the activatedTHERM outputto activate thealarm
Intra-range alarm
Extra-range alarm
It isthe inferior valueof temperaturetothe buzzer alarmact as theconfigured Operation Modeof Buzzer
(F27).
It is the superior value of temperature to the buzzer alarm act as the configured Operation Mode of
Buzzer (F27)
It is the inferior value of humidity to the buzzer alarm act as the configured Operation Mode of Buzzer
(F27).
Allows configuring the maximum time the output THERM can stay activated without reaching the
setpoint before activating the audible alarm (BUZZER).To deactivate this function, just decrement the
F31 -
It is the superiorvalue ofhumidity tothe buzzeralarm actas theconfigured OperationMode ofBuzzer
(F27).
value untilthe message is displayed.
Allows configuring the maximum time the output HUMID can stay activated without reaching the
setpoint before activating the audible alarm (BUZZER).To deactivate this function, justdecrement the
value untilthe message is displayed.
Allows configuring the maximum timethe output AUX can stayactivated without reaching the setpoint
before activatingthe audible alarm(BUZZER). Todeactivatethis function, justdecrement the valueuntil
the message is displayed.
Maximum timeof theactivated outputtoactivate the alarm
F34 -Maximum timeof the activatedAUX outputto activate thealarm
F33 - HUMID
F35 -Buzzer time on
F36 -Buzzer time off
F37 -Inhibition timeof Buzzer duringelectrical supply
It isthe timethatthe Buzzer willbe turnedon(cycle on). Toturnit off thesonore alarm(Buzzer) adjust the
value “0”to thisfunction.
It is the time that the buzzer will be turnedoff (cycle off). To turn the sonore alarm (Buzzer)always on,
adjust thevalue “0”to this function.
It isthe timewere the alarmwill keptturned off evenif in alarmcontitions.
It serves to inhibit the buzzer during the time while the system do not reaches the working control
temperature.
F38 -Display mode
F39 -Temperature displayoffset
F40 -Humidity displayoffset
F41 -Network equipmentaddress
Alternated indicationof temperatureand humidity
Only indicationof temperature
Only indicationof humidity
It allows to compensate eventual shunting lines in the reading of temperature proceeding from the
exchange ofthe sensoror cable lenghtalteration.
It allows to compensate eventual shunting lines in the reading of humidity proceeding from the
exchange ofthe sensoror cable lenghtalteration.
This isthe deviceaddress for communicationwith software.
Note: You cannothave twoor more deviceswith thesame address inthe network.
Sitrad
®
5. FUNCTIONS WITHFACILITATED ACCESS
5.1- Registers of minimum and maximum temperature and
humidity
5.2 - To visualize humidity or temperature
Press . Will appear followed for minimumand maximum registeredtemperatures. After that
will appear and theminimum andmaximum registered humidity.
To reset the registers, keep pressed during the visualization of the minimum and maximum
registers untilappear .
If theF38 function isnot in thealternatingwayof visualization (”0”)it´spossible visualize temperatureor
humidity bypressing the key.
Note: