Full Gauge Controls MT-518Ri User Manual

1. DESCRIPTION
MT-518Ri is a temperature controller with two outputs that can be configured as double stage of refrigeration, double stage of heating or heating and refrigeration. Its second output also can be configured for alarm intra, extra-range or, even , relative extra-range. Product complies with CE (European Union) and UL Inc. (United States and Canada).
2. APPLICATION
• Winter/Summer automatic system in air conditioning
- Power supply: MT-518Ri 115 or 230 Vac ± 10% (50/60Hz) MT-518RiL 12 or 24 Vac/dc
- Control temperature: -50 to 105ºC (decimal resolution between -10 and 100 ºC)
- Input: NTC sensor
- Load current: 8(3)A/250Vac 1/4HP each output
- Dimensions: 71 x 28 x 71mm
- Operation temperature: 0 to 50 ºC
- Operation humidity: 10 to 90% RH (without condensation)
UL-Underwriters Laboratories
MT-518Ri
DIGITAL TEMPERATURE CONTROLLER
WITH TWO STAGES
Ver. 12
MT518V12-01T-10873
CLASSIFICATION ACCORDING TO IEC60730-2-9 STANDARD:
- Temperature limit of the installation surface: 50°C
- Type of construction: Built-in electronic controller
- Automatic action: Type 1
- Control of pollution: Level 2
- Impulse voltage: 1,5kV
- Temperature for the test of sphere pressure: 75°C and 125°C
- Insulation: Class II
4. CONFIGURATIONS
4.1 - Control temperatures adjust (SETPOINTS)
- Press for 2 seconds until appears, then release it. will appear and the adjusted
temperature for 1st stage.
- Use the keys and to change the value and then press to record it.
- Now and the adjusted temperature for 2st stage will appear. ( only if F08 = 0 or F08 = 1).
- Use the keys and to change the value and then press again.
SET
SET
SET
Description
Min
Max
Unit
Fun
4.2 - Parameters table
Configuration parameters protected by access code.
Note: F02 function allows to correct eventual shuting lines in the reading, proceeding of the sensor exchange or alteration of sensor length.
(4)
2nd stage operation
mode:
0 - refrigeration 1 - heating 2 - alarm (inside of range) 3 - alarm (outside of range) 4 - relative alarm (outside of range)
(1)
First stage
operation mode:
0 - refrigeration 1 - heating
F01 F02 F03 F04 F05 F06 F07 F08 F09 F10 F11 F12 F13 F14 F15
Access code 123 (one hundred and twenty-three) Display (offset)
(1)
1st stage operation mode Minimum setpoint allowed to the end user (1st stage) Maximum setpoint allowed to the end user (1st stage) Control differential (hysteresis) of 1st stage Minimum delay to turn on the 1st stage output
(2)
2nd stage operation mode Minimum setpoint allowed to the end user (2nd stage) Maximum setpoint allowed to the end user (2nd stage) Control differential (hysteresis) of 2nd stage Minimum delay to turn on the 2nd stage output Alarm delay when the instrument is powered on Alarm output time on Alarm output time off
-
-5.0 0
-50
-50
0.1 0 0
-50
-50
0.1 0 0 0 0
-
5.0 1
105 105
20.0 999
4 105 105
20.0 999 999 999 999
-
°C
­°C °C °C
sec.
­°C °C °C
sec.
min.
sec. sec.
4.3 - Parameters alteration
Access the function F01 pressing simultaneously the keys and for 2 seconds until appearing , releasing after that. Soon it will appear , and then press (short touch).
- Use the keys and to enter with the access code (123), and then press to enter.
- Use the keys and to access the desired function.
- After selecting the function, press (short touch) to display the configured value for that function.
- Use the keys and to change the value and then press to record the new value and return to the functions menu.
- To return to the normal operation, press until appear.
5. FUCTIONS WITH FACILITATED ACCESS
Registers of minimum and maximum temperatures
Press . The minimum registered temperature appears and after soon the maximum registered temperature. Nota: To reset the registers, keep the key pressed during the visualization of the minimum and maximum temperatures until to be showed.
SET
SET
SET
SET
SET
If the instrument is configured as alarm, set the F09 and F10 act points normally and ignore ST2 and F11. If the temperature goes out the specified range and ring the alarm, press and to inhibit the sound.
6. SIGNALING
ST1 - 1st stage output on ST2 - 2nd stage output on
- Detached sensor or temperature outside the specified range With F08=4 the ST2 output is activated when the temperature reaches a value equal ST1 minus the configurated value in F09 (ST1-F09), or when the temperature reaches a value equal ST1 plus the configurated value in F10 (ST1+F10) Ex. :
- Temperature in ST1 = 25 ºC
- Value in F08 = 4
- Value in F09 = 2
- Value in F10 = 5
The ST2 output will be kept on when the temperature is below 23 ºC (25-2) or above 30 ºC (25+5). If ST1 value is changed to 24 ºC the alarm values will be automatically modified to 22 and 29 ºC. IF the functions F14 and F15 are set with zero, the ST2 output will be kepped on while the alarm condition persist.
SET
ensoS
r
Power supply
Load 1
COMMON
Loads
supply
ST1 (NO)
ST2 (NO)
1
2
3
4
5
6
7
8
9
10
11
12
115 V (12 V)
230 V (24 V)
0
72 mm
29 mm
7. WIRING DIAGRAM
7 - 8 7 - 9
115V 230V
12V 24V
MT-518Ri MT-518RiL
Load 2
- Refrigerator
- Heating
- Contactor
- Solenoid
- Refrigerator
- Heating
- Contactor
- Solenoid
Load 1 Load 2
Above specified current use contactors.
Dimension of the clipping for
setting of the instrument
IMPORTANT
For more information contact our application eng. department through e-mail support@ fullgauge.com or dial +55 51 3475.3308.
According to the chapters of norm IEC 60364:
1: Install protector against overvoltage on the power supply 2: Sensor cables and signal cables of the computer may be joined, but not in the same electric conduit
through which the electric input and the activation of the loads run 3: Install transient suppresors (RC filters) parallel to the loads as to increase the product life of the relays.
Contact suppresor connection diagram
Suppresor
A1
A2
A1 e A2 are the contactor coils.
Diagram for suppresor installation for direct drive load inputs
Load
Suppresor
For direct activation the maximum specified current should be taken into consideration.
Note: The user can increase the length of the sensor cable to up to 200 meters, by using PP 2 X 24 A WG cable. For immersion in water, use thermometric well.
PROTECTIVE VINYL:
This adhesive vinyl (included inside the packing) protects the instruments against water drippings, as in commercial refrigerators, for example. Do the application after finishing the electrical connections.
UL-Underwriters Laboratories
MT518V12-01T-10873
SET
Loads
72 mm
29 mm
- Refrigerator
- Heating
- Contactor
- Solenoid
Dimension of the clipping for
setting of the instrument
Load
For direct activation the maximum specified current should be taken into consideration.
Remove the protective paper and apply the vinyl on the entire superior part of the device, folding the flaps as indicated by the arrows.
Loading...