Full Gauge Controls MT-516RVTi plus User Manual

MT-516RVTi plus
TEMPERATURE CONTROLLER
WITH CYCLICAL TIMER AND VOLTAGE MONITOR
Ver. 06
MT516RVTI06-02T-10811
UL-Underwriters Laboratories
1.DESCRIPTION
The integrates a heating or cooling thermostat with a cyclical timer and a TrueRMSvoltagemonitor.ThroughtheF13 andF14 functionsispossibletodetermine thevoltage limits that the thermostat output can be active, this way protecting the compressor. Using True RMS* technology the controller iscapable of measuringthe voltages ina varietyof different situationsin the electricalgrid,thusprovidinggreater precisionin theprotection ofthe componentsof theapplication. ProductcomplieswithULInc.(United Statesand Canada).
•Milkcoolingtanks
•Chambersandcounters
•Heatpumps
MT-516RVTi plus
*TrueRMS:Is therealand effectivevoltage valuewhichalso includesthevoltage generatedbyhigh frequency noisein thedistributing network(harmonic distortion).This isthe actualvoltage appliedto theconnected load (example: electricmotor, compressor). This method allows the precise voltage measurement for any type of waveform.Othermeasurementmethodsgivecorrect value ofapplied voltage onlyfor perfect sinewaveforms.
3.TECHNICAL SPECIFICATION
4.CONFIGURATIONS
4.1- Control temperature adjust(SETPOINT)
-Electricpowersupply:
-Controltemperature:
-Maximumcurrent:
-Dimensions:
-Operatingtemperature:
-Operatinghumidity:
115or 230Vac±10%(50/60Hz)
-50to105°C(decimalresolution between- 10and 100ºC)
-58to221ºF
8(3)A/ 250Vac1/4HP(each output)
71x28x71mm
0 to 50°C/ 32to 122°F
10to90%RH(without condensation)
-Press fortwosecondsuntil appearsonthedisplay. Theactualcontroltemperaturewill appear.
-Usethe and keys tochange thevalue andpress whenready.
SET
SET
DescriptionFun
Access code: 123(one hundredand twentythree) Temperatureindicationoffset Thermostat operating mode Minimum setpoint allowedfor theend user Maximum setpoint allowedfor theend user Control temperature differential(hysteresis) Delay for turningthe compressoron Cyclical timer´s timebase Cyclical timer´s ontime Cyclical timer´s offtime Initial state ofcyclical timer Cyclical timer alwayson whenthe compressoris on Minimum working voltage(protection) Maximum working voltage(protection) Voltageindication offset Voltageconfirmation delay Display indication mode Equipment address inthe RS-485network
(1)
(2)
(3)
(3)
(3)
(4)
F01 F02 F03 F04 F05 F06 F07 F08 F09 F10 F11 F12 F13 F14 F15 F16 F17 F18
-
0.0°C / 0°F 0-cooling
4.0°C / 39°F
5.0°C / 41°F
1.0°C / 2°F 180 sec.
1-min.
3 sec./min.
12 sec./min.
1-on
1-yes 195 Volts 260 Volts
0 Volts
10 sec.
0 1
-
-5.0°C / -9°F 0-cooling
-50°C / -58°F
-50°C / -58°F
0.1°C / 1°F 0 sec. 0-sec.
1 sec./min. 1 sec./min.
0-off
0-no 90 Volts 90 Volts
-50 Volts 1 sec.
0 1
-
5.0°C / 9°F 1-heating
105°C/221°F 105°C/221°F
20.0°C / 36°F 999 sec.
1-min. 999 sec./min. 999 sec./min.
1-on
1-yes 260 Volts 260 Volts
50 Volts
30 sec.
2
247
4.2 - Parameters table
Minimum
Maximum
Default
(1)
(3)
(4)
F02-Temperatureindication offset
F12-Cyclicaltimeralwaysonwhenthecompressorison:
F13/F14/F16-Operationofthevoltagemonitor
F17-Displayindicationmode
The F02 functions allows for the correction of any changes in the reading, resulting from a change in the sensor or alteration ofthe lengthof the cable.
This function works for some applications, as for example, on cooling tanks for milk, where the timer commands the agitator thatmust remain on whilecooling istaking place.
If the value ofthe voltage exceeds the limits setin F13 and F14 the compressorwill be automatically turned off afterthe time setin function F16 haslapsed. The led“VOLTS”will slowly blinkalong withthe Indication ofthe gridvoltage on thedisplay. In the event that the voltagereturns to the limits established, the compressor will only be turnedon again after the time scheduled inthe F16function has ended. Todeactivate thevoltage monitoring,all you haveto do isadjust functionsF13 and F14to thesame value.
Function F17allows youto choose themeasurement thatwill be displayedduring normaloperation:
Temperature Voltage Temperatureand voltage
(2)
4.3- Selection of theunit (°C /°F)
4.4- Parameters alteration
In orderto definethe temperature unitthat the instrumentwill operate, enter the accesscode “231” in thefunction .The indication willappear.Press or tochoose between or
andconfirmwith .After selectingtheunitthe indication willappearand theinstrument willreturn tothefunction .Whenever thetemperatureunit ismodified,the parameters should be reconfigured,sincetheywillassume thedefault values.
- Access functionF01 by pressing the and keys at the sametime for 2 seconds. When the message appearsreleasethe keysand waitfor the indication.
-Pressthe buttontoaccess thefunction anduse and to enterthe code123.Whenready pressagainthe buttontoconfirmthe codeand quitthe functionF01.
- Select otherfunctions by pressing or . Toaccess the desired function press the key quickly.
-Adjust thefunction`snew valuewith the and keysand press to saveand returntothe functionsmenu.
- To exit the functions menuand return to normal operation press the button until the message
appearsonthedisplay.
SET
SET
SET
SET
SET
SET
5.FUNCTIONS WITH FACILITATED ACCESS
5.1- Minimum andmaximum logs
5.2- Cyclicaltimer On/Off status change
5.3- Cyclicaltime visualization
5.4- Temperature,voltage and frequencyvisualization
Pressand releasethe key quickly. Theindication will appearfollowed bythe minimumand maximum logged voltages. Shortly after the last voltage the indication will be shown and the minimumandmaximumtemperatureswill bedisplayed.
toresetthe minimumandmaximumlogs justkeeppressingthe keyduring thevisualization
ofthelogs.Themessage willappearindicatingthe successfulloperation.
Tochange theoutput ofthecyclical timerfrom"on" to"off" or viceversa justpressthe key untilthe
appearsonthedisplay.
To visualize the current status (on/off) time that has already lapsed on the cyclical timer press
quickly.
Toconsultthe voltageandfrequencyof theelectrical gridwhenthecontroller isconfigured todisplaythe temperaturejust push the keyquickly. Thecurrent voltagevalue willbe displayedfollowed by the frequencyindication andit`s value. To visualize the temperature while the controller is displaying the voltage press the key like explainedabove.
Note:
SET
SET
6.SIGNALLING
Iftheinstrument shows onthe displayitmeans thataparameter isoutofacceptable rangeandit mustbecorrected.
THERM­VOLTS(always on) ­VOLTS(blinking slowly) ­VOLTS(blinking quickly) ­TIMER-
Thermostatoutputactive;
Indicatesthevoltagevisualization;
Indicatesvoltageinoutrange condition;
Indicatesanerroronthe voltagemeasurement;
Cyclicaltimeroutputactive.
-Sensordisconnectedortemperature outof thespecified range.
72 mm
29 mm
7. WIRING DIAGRAM
Note: The length of the cable for the sensor may be increased by the user up to 200 meters, using PP2x24AWGcable.Forimmersionin wateruse thermometricwell.
1
2
4
5
678
9
10
11
12
3
THERM
TIMER
AB
VOLTMETER
COMMON
Load 1
Load 2
0
115V
230V
RS-485 serial
communication
Sensor
6-7 6-8
115V 230V
MT-516RVTiplus
- Belt
-Agitator
- Water ’pump
- Contact
Load1 Load2
Power
supply
Loads
supply
VOLTMETER: Connect the borne9 toborne 7, when the instrument issupplied in115Vacor borne 9 toborne 8,when the instrument is in 230Vac.supplied
- Cooler
- Heater
- Contact
- Solenoid
Dimension of the clipping
for setting of the instrument
in panel
Integrating Controllers, RS-485 Serial Interface and Computer
RS-485 Network
RS-485Serial Interface
®
Device used to establish the connection Full Gauge Controls’ instrumentswith the Sitrad
.
or
RS232
Power supply
USB
115 230Vac
www.sitrad.com
M B AM B A M B A
MOD 64
AB
OU
T1
O
UT
2
O
UT
3
w
w
w
.
fu
ll
g
a
u
g
e
.
c
o
m
P
C
T
-4
0
0
R
p
lu
s
O
U
T
4
A
L
M
R
P
U
M
P
A
U
X
1
A
U
X
2
w
w
w
.f
u
ll
g
a
u
g
e
.c
o
m
M
IC
R
O
S
O
L
IIp
lu
s
Instrument
ABAB
A
A
BB
AB
A
A
BB
AB
A
A
BB
AB
A
A
BB
AB
AB
RS-485 Network
terminal grounded
External
mesh
Distribution Box
Used to connect more than one instrument to the Interface. The wire's connectionsmustbemadeinagreementwiththefollowingrules:terminal of theinstrument connects to theterminal of the distribution box,thatmust be connectedwiththe terminal of the Interface.Repeat theaction for terminals
and ,being thecable shield.
theinstrumentsdo not have terminal .
A
A
A B P.S .:
®
IMPORTANT 1:
2: 3:
Accordingtothechaptersfrom theIEC60364 standard:
Install onpowersupply Sensor cablesand computer signals can betogether, howevernot at thesame place wherepower
supplyandloadwirespass for
Installsuppresoroftransientin parallelto loadsto increasethe usefulllife ofthe relays
protectorsagainstovervoltage
For more information contact our application eng. department through e-mail
or dial+55 513475.3308.support@fullgauge.com
Wiring diagramof suppresors in contactors
Suppresor
A1
A2
A1 e A2 are the contactor coils.
Wiring diagramof suppresor for direct drive
Load
Suppresor
For direct activationthe maximum specified current shouldbe taken into consideration.
PROTECTIVE VINYL:
This adhesive vinyl(included inside the packing) protects theinstruments against waterdrippings,asincommercial refrigerators,for example. Dotheapplicationafterfinishing theelectrical connections.
Remove the protective paper andapplythe vinylontheentire superior part of the device, foldingthe flapsasindicated by thearrows.