Fujitsu Siemens Computers AU* G45LRLA, AR* G45LMLA, AO* G45LETL, AR* G54LHTA, AO* G54LETL Service Instruction

...
SPLIT TYPE ROOM AIR CONDITIONER
Cassette type Duct type Ceiling type
Models Indoor unit Outdoor unit
AU* G45LRLA AR* G45LMLA AR* G45LHTA AB* G45LRTA
AU* G54LRLA AR* G54LHTA
AO* G45LETL AO* G54LETL
INVERTER
SERVICE
INSTRUCTION
R410A
CONTENTS
1. SPECIFICATIONS
1. DESCRIPTION OF EACH CONTROL OPERATION
1-1 COOLING OPERATION..............................................................................................
1-4 AUTO CHANGEOVER OPERATION.........................................................................
1-5 INDOOR FAN CONTROL...........................................................................................
1-6 OUTDOOR FAN CONTROL.......................................................................................
1-7 COMPRESSOR CONTROL.......................................................................................
01-01
1-2 HEATING OPERATION..............................................................................................
01-02
1-3 DRY OPERATION.......................................................................................................
01-03
01-04 01-06 01-09
01-10
1-8 TIMER OPERATION CONTROL................................................................................
01-11
1-9 ELECTRONIC EXPANSION VALVE CONTROL.......................................................
01-15
1-10 TEST OPERATION CONTROL...............................................................................
01-15
1-11 PREVENT TO START FOR 3 MINUTES (3 MINUTES ST).....................................
01-16
1-12 4-WAY VALVE EXTENSION SELECT.....................................................................
01-16
1-13 AUTO RESTART......................................................................................................
01-16
1-14 PUMP DOWN...........................................................................................................
01-17
1-15 COMPRESSOR PREHEATING...............................................................................
01-18
1-16 10°C HEAT OPERATION (For AB type)..................................................................
01-18
1-20 VARIOUS PROTECTIONS.......................................................................................
01-22
1-21 COMPRESSOR STOP CONTROL...........................................................................
01-24
1-19 OFF DEFROST OPERATION CONTROL................................................................
01-21
2-1 ERROR DISPLAY......................................................................................................
2. TROUBLE SHOOTING
2-2 TROUBLE SHOOTING WITH ERROR CODE..........................................................
2-3 TROUBLE SHOOTING WITH NO ERROR CODE....................................................
2-4 SERVICE PARTS INFORMATION............................................................................
02-01
02-30
02-04
02-35
1-18 DEFROST OPERATION CONTROL........................................................................
01-19
1-17 ECONOMY OPERATION.........................................................................................
01-18
1-27 DESCRIPTION OF DISPLAY UNIT..........................................................................
01-27
1-24 LOW NOISE OPERATION.......................................................................................
01-25
1-25 PEAK CUT OPERATION..........................................................................................
01-25
1-26 DRAIN PUMP OPERATION (For AU/ AR type)......................................................
01-26
1-23 EXTERNAL ELECTRICAL HEATER CONTROL.....................................................
01-25
1-22 FRESH AIR CONTROL............................................................................................
01-24
1 . DESCRIPTION OF EACH CONTROL OPERATION
R410A
Cassette/ Duct/ Ceiling type
INVERTER
1-1. COOLING OPERATION
A sensor (room temperature thermistor) built in the indoor unit will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor. * If the room temperature is 2°C higher than a set temperature, the compressor operation frequency will attain to maximum performance.
* If the room temperature is 2.5°C lower than a set temperature, the compressor will be stopped.
* When the room temperature is between +2°C to -2.5°C of the setting temperature, the compressor frequency is controlled within the range shown in Table1. However, the maximum frequency is limited in the range shown in Figure 1 based on the fan speed mode and the outdoor temperature.
minimum frequency
maximum frequency
16rps
16rps
16rps 16rps
93rps
90rps
85rps
100rps
AU* G45LRLA AR* G45LMLA AB* G45LRTA AR* G45LHTA AU* G54LRLA AR* G54LHTA
Hi Me Lo Qu
93rps 93rps 78rps 73rps
75rps 75rps 68rps 56rps
68rps 68rps 56rps 47rps
44rps 44rps 44rps 29rps
100rps 100rps 85rps 76rps
78rps 78rps 73rps 62rps
73rps 73rps 62rps 50rps
44rps 44rps 44rps 29rps
85rps 85rps 78rps 68rps
77rps 77rps 68rps 62rps
76rps 76rps 68rps 56rps
---
---
---
---
90rps 90rps 85rps 73rps
85rps 85rps 76rps 68rps
81rps 81rps 73rps 62rps
---
---
---
---
A zone B zone C zone
AU* G45LRLA AR* G45LMLA AB* G45LRTA
AU* G54LRLA
D-F zone A zone B zone C zone D-F zone A zone B zone
C zone
AR* G45LHTA
AR* G54LHTA
D-F zone
( Table 1 : Compressor Frequency Range )
( Fig. 1 : Limit of Maximum Frequency based on Outdoor Temperature )
01-01
A zone B zone C zone D-F zone
Fan speed mode
1. DESCRIPTION OF EACH CONTROL OPERATION
Outdoor air temperature
A zone
B zone
C zone
D zone
E zone
F zone
When the room temperature rises
When the room temperature drops
36°C
32°C
21°C
12°C
2°C
34°C
30°C
19°C
10°C
0°C
1-2. HEATING OPERATION
A sensor (room temperature thermistor) built in the indoor unit will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor. * If the room temperature is lower 3°C than a set temperature, the compressor operation frequency will attain to maximum performance.
* If the room temperature is higher 2.5°C than a set temperature, the compressor will be stopped.
* When the room temperature is between +2.5°C to -3°C of the setting temperature, the compressor frequency is controlled within the range shown in Table2.
( Table 2 : Compressor Frequency Range )
01-02
minimum frequency
maximum frequency
16rps
110rps
AU* G45LRLA AR* G45LMLA AB* G45LRTA AR* G45LHTA AU* G54LRLA AR* G54LHTA
1-3. DRY OPERATION
The compressor rotation frequency shall change according to set temperature and room temperature variation which the room temperature sensor of the indoor unit has detected as shown in the Table 3.
( Table 3 : Compressor frequency )
( Fig.2 : Compressor Control based on Room Temperature )
01-03
Ts : Setting temperature
Ts+0.5°C
Ts+1.5°C
Operating frequency
44rps
X zone
0rps
Y zone
Room Room temperature temperature
X zone
Y zone
AU* G45LRLA AR* G45LMLA AB* G45LRTA AR* G45LHTA AU* G54LRLA AR* G54LHTA
Compressor
ON
OFF
Indoor fan Setting air flow
OFF
10 30 60 180 60 180 60 10 30
(sec)
S-Lo
Compressor
ON
OFF
Lo
OFF
30 180 120 180 30
(sec)
Indoor fan
ON
5 30 5
( Fig 3-2 : Indoor Fan Control for AR*G45/ 54LHTA )
( Fig 3-1 : Indoor Fan Control for AU*G45/ 54LRTA, AR*G45LMLA, AB*G45LRTA )
Indoor fan air flow *1
*1 : AU*G45LRLA ---> 470rpm, AU*G54LRLA ---> 480rpm AB*G45LRTA ---> 680rpm, AR*G45LMLA ---> 670rpm,
1-4. AUTO CHANGEOVER OPERATION
01-04
When the air conditioner is set to the Auto mode by remote controller, operation starts in the optimum mode from among the Heating, Cooling, Dry and Monitoring mode. During operation, the optimum mode is automatically switched in accordance with temperature changes. The temperature can be set between 18°C and 30°C in 1°C steps.
When operation starts, indoor fan and outdoor fan are operated for around 3 minutes. Room temperature and outdoor temperature are sensed, and the operation mode is selected in accordance with the table below. <Monitoring mode>
Cooling mode
25°C
Heating mode
( Table 4 : Operation mode selection table )
Room temperature (TR)
TR> Ts+2°C
Ts+2°C TR Ts -2°C
*Middle zone
TR < Ts -2°C Heating
When Cooling or Dry mode was selected at and air flow mode is Auto, the air conditioner operates as follow.
The same operation as COOLING OPERATION AND DRY OPERATION of page 01-01 is performed. When the room temperature has remained at set temperature -1.5°C, operation is automatically switched to Dry mode. If the room temperature reaches set temperature +2°C during Dry mode, operation returns to Cooling.
When Heating was selected at , the same operation as HEATING OPERATION of page 01-02 is performed.
When the compressor was stopped for 6 consecutive minutes by the temperature control function after the Cooling(Auto:Dry) or Heating mode was selected at above, operation is switched to Monitoring and the operation mode is selected again.
1
1
2
3
1
4
1
( Fig.4 : Outdoor temperature zone selection )
Cooling
(Autmatic dry)
Operation mode
*If it's Middle zone, operation mode of indoor unit is selected as below.
(1). Same operation mode is selected as outdoor unit.
If outdoor unit is operating in Cooling, Dry, and Heating mode, indoor unit will be operated by the same operation mode.
(2). Selected by the outdoor temperature.
If outdoor unit is operating in other than Cooling, Dry, and Heating mode, indoor unit will be operated according to the outdoor temperature as below.
Cooling
Cooling
Dry
Dry
Compressor stop
When the room temperature drops
When the room temperature rises
Ts +2°C
Ts -0.5°C
Ts -1.5°C
Ts +1°C
Ts -1.5°C
Ts -2.5°C
( Fig.5 : Auto changeover : Cooling - Dry )
TR : Room temperature Ts : Setting temperature
TR : Room temperature Ts : Setting temperature
( Air flow mode : Auto )
01-05
START
Room temp.
Ts+2°C?
COOLING (AUTO:DRY)
OPERATION
HEATING OPERATION
YES
YES
NO
NO
NO
AUTO CHANGEOVER operation flow chart
TS : Setting temperature
Room temp.
Ts -2°C?
Thermostat remains
in OFF state for 6 minutes or
longer?
System stops
or operation command other than
auto changeover operation?
NO
Thermostat remains
in OFF state for 6 minutes or
longer?
System stops
or operation command other than
auto changeover operation?
Middle zone
NO
Operation mode of
outdoor unit : Cooling or Dry?
YES
NO
Operation mode of outdoor unit
: Heating?
YES
NO
YES
Outdoor temperature
25°C?
NO
YES
YES
NO
YES
YES
1-5. INDOOR FAN CONTROL
1. Fan speed
( Table 5 : Indoor Fan Speed )
2. FAN OPERATION
The airflow can be switched in 5 steps such as Auto, Quiet, Lo, Me, Hi, while the indoor fan only runs. The High Static Pressure Duct type is 4 steps such as Auto, Lo, Me, Hi.
01-06
AU* G45LRLA
Operation mode
Air flow mode
Speed (rpm)
Hi Me+ Me Lo Quiet Cool air prevention Hi Me Lo Quiet *Soft Quiet
690 650 610 550 470 300 690 610 550 470 300 470 270
Heating
Cooling Fan
Dry S-Lo
AU* G54LRLA
Operation mode
Air flow mode
Speed (rpm)
Hi Me+ Me Lo Quiet Cool air prevention Hi Me Lo Quiet *Soft Quiet
720 680 630 570 480 300 720 630 570 480 300 480 270
Heating
Cooling Fan
Dry S-Lo
*Note, during Economy operation and operation mode is Fan, air flow is 1 step downs. (Hi > Me, Me > Lo, Lo > Quiet, Quiet > Soft Quiet)
AB* G45LRTA
Operation mode
Air flow mode
Speed (rpm)
Hi Me+ Me Lo Quiet Cool air prevention Hi Me Lo Quiet *Soft Quiet
1200 1100 1000 830 680 500 1200 1000 830 680 500 680 250
Heating
Cooling Fan
Dry S-Lo
AR* G45LMLA
Operation mode
Air flow mode
Speed (rpm)
Hi Me+ Me Lo Quiet Cool air prevention Hi Me Lo Quiet *Soft Quiet
1300
--­1020 840 670
--­1310 1020 840 670 420 670 420
Heating
Cooling Fan
Dry S-Lo
*Note, during Economy operation and operation mode is Fan, air flow is 1 step downs. (Hi > Me, Me > Lo, Lo > Quiet, Quiet > Soft Quiet)
AR* G45/ 54LHTA (Normal static pressure: 100Pa)
Operation mode
Air flow mode
Speed (rpm)
Hi Me Lo
1300 1150 1000
Heating Cooling Fan
4. HEATING OPERATION
Switch the airflow [Auto], and the indoor fan motor will run according to a room temperature, as shown in Fig.7. On the other hand, if switched in [Hi] ~ [Lo], the indoor motor will run at a constant airflow of [Heat] operation modes Lo, Me, Hi, as shown in Table 5.
01-07
( Fig.7 : Airflow change - over ( Heating : Auto ) )
3. COOLING OPERATION
Switch the airflow [Auto], and the indoor fan motor will run according to a room temperature, as shown in Fig.6. On the other hand, if switched in [Hi] ~ [Lo], the indoor motor will run at a constant airflow of [Cool] operation modes Lo, Me, Hi, as shown in Table 5.
( Fig.6 : Airflow change - over ( Cooling : Auto ) )
When the room temperature rises
When the room temperature drops
TR : Room temperature Ts : Setting temperature
TR-Ts > 2°C
=
1°C > TR-Ts
2°C > TR-Ts > 1°C
=
TR-Ts > 2.5°C
=
1.5°C > TR-Ts
2.5°C > TR-Ts > 1.5°C =
Hi mode
Me mode
Lo mode
*1
When the room temperature rises
When the room temperature drops
TR-Ts > -1°C
=
-2°C > TR-Ts
-1°C > TR-Ts > -2°C =
TR-Ts > -1.5°C
=
-2.5°C > TR-Ts
-1.5°C > TR-Ts > -2.5°C =
Lo mode
Me mode
Hi mode
*1 : Contains a condition to the following
When the operation mode is set to AUTO mode at the start of operation. When the setting temperature was changed. When the operation mode was changed to Cooling mode. When the airflow mode was changed to AUTO mode.
5. COOL AIR PREVENTION CONTROL (Heating mode)
6. DRY OPERATION
Refer to the Fig. 3-1, 3-2. During the dry mode operation, the fan speed setting can not be changed.
7. [For AU*G45/ 54LRTA, AR*G45LMLA, AB*G45LRTA] MOISTURE RETURN PREVENTION CONTROL (Cooling mode& Dry mode)
Switch the airflow [Auto] at cooling mode, and the indoor fan motor will run as shown in Fig.3-1.
8. [For AU*G45/ 54LRTA, AR*G45LMLA, AB*G45LRTA] INDOOR UNIT FAN (CONTROL FOR ENERGY SAVING (Cooling mode))
Switch the airflow at cooling mode, and the indoor fan motor will run as shown in Fig.3-1. It depends on the Function setting "Indoor unit fan control for energy saving".
01-08
The maximum value of the indoor fan speed is set as shown in Fig.8, based on the detected temperature by the indoor heat exchanger sensor on heating mode. When the compressor does not operate, the indoor fan motor operates [S-Lo] or [Stop] mode.
( Fig.8 : Cool Air Prevention Control )
[ AU*G45/ 54LRLA, AB*G45LRTA ]
[ AR*G45LMLA ]
*Hi or setting fan mode
*Lo or setting fan mode
37°C
29°C
32°C
24°C
Indoor heat exchanger temperature rises
Indoor heat exchanger temperature drops
Cool air prevention
S-Lo
S-Lo
42°C
30°C
34°C
Indoor heat exchanger temperature rises
Indoor heat exchanger temperature drops
Hi
*Me+ or setting fan mode
*Lo or setting fan mode
*Lo or setting fan mode
*Lo or setting fan mode
39°C
37°C
37°C
32°C
24°C
*Lower speed is selected.
42°C
30°C
34°C
Indoor heat exchanger temperature rises
Indoor heat exchanger temperature drops
Hi
*Me+ or setting fan mode
*Lo or setting fan mode
39°C
37°C
37°C
32°C
24°C
*Lower speed is selected.
*Lower speed is selected.
Hi
*Lo or setting fan mode
*Lo or setting fan mode
37°C
29°C
32°C
24°C
Indoor heat exchanger temperature rises
Indoor heat exchanger temperature drops
*Lower speed is selected.
13 min. later
13 min. later
[ AR*G45/ 54LHTA ]
Setting fan mode
stop
27°C
Indoor heat exchanger temperature
Setting fan mode
Lo
27°C
Indoor heat exchanger temperature
13 min. later
1-6. OUTDOOR FAN CONTROL
1. Outdoor Fan Motor
Following table shows the fan speed of the outdoor unit.
*
The outdoor fan speed changes in the range mentioned above depending on the compressor frequency and outdoor temperature. (When the compressor frequency and outdoor temperature increase, the outdoor fan speed also changes to the higher speed. When the compressor frequency and outdoor temperature decrease, the outdoor fan speed also changes to the lower speed.)
*
It runs at 500rpm for 20 seconds after starting up the outdoor fan. However, the fan operates at 200rpm when the initial rotation speed is 300rpm or less.
01-09
( Table 6 : Fan speed of the outdoor unit )
AO* G45LETL AO* G54LETL
After operating the defrost control function on heating mode except economy operation, its speed becomes 900rpm(Upper) / 880rpm(Lower) regardless of the compressor speed. However, it returns to the normal speed control when the defrosting operation does not function for 240 minutes after releasing the defrost operation or when the outdoor temperature sensor detection value becomes higher than 5.
*
The compressor and the fan start-up at the same time, and the fan stops after the compressor stops and 60 seconds has passed.
*
The fan doesn't operates fan 10 seconds after the fan stops.
*
Cooling / Dry Heating
Upper fan /Lower fan
850/800, 780/750, 750/700 540/520, 360/340, 290/270 480/ 0 , 400/ 0, 350/ 0 280/ 0
900/880, 850/830, 780/750 720/700, 570/550, 500/480 370/350, 300/280, 220/200
1-7. COMPRESSOR CONTROL
1. OPERATION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as shown in Table 7.
Cooling Heating
Min
Max
Min Max
Dry
(Table 7 : Compressor Operation Frequency Range)
01-10
AO* G45LETL
16rps 16rps
93rps
----
85rps
----
----
100rps
----
90rps
AO* G54LETL
16rps 16rps
110rps 110rps
44rps 44rps
2. OPERATION FREQUENCY CONTROL AT START UP
The compressor frequency soon after the start-up is controlled as shown in Fig.9.
(Fig.9 : Compressor Control at Start-up)
39
90
57
68
180 420
85
(rps)
Upper
limit
speed
(sec)480
Elapsed time
39
200
57
68
700 840
85
(rps)
Upper
limit
speed
(sec)1010
Elapsed time
39
90
57
68
210 270
85
(rps)
Upper
limit
speed
(sec)300
Elapsed time
Ta : Outdoor temperature
< Normal start-up > Immediate start-up after power-ON (cooling)
Immediate start-up after power-ON (Hearting Ta < 10)
Immediate start-up after power-ON (Hearting Ta > 10)
=
45LRLA 45LMLA 45LRTA
45LHTA 54LRLA 54LHTA
1-8. TIMER OPERATION CONTROL
1. ON / OFF TIMER
OFF timer : When the clock reaches the set time, the air conditioner will be turned off.
Operation mode
Stop mode
Set time of timer
ON timer : When the clock reaches the set time, the air conditioner will be turned on.
Operation mode
Stop mode
Set time of timer
The weekly timer allows up to two ON and OFF time to set up per day.
Use this timer function to set operating time for each day of the week.
Operation mode
The operating time can be set in 30 min increments only. The OFF time can be carried over to next day. The ON timer and the OFF timer functions cannot be set with using the weekly timer.
Both ON and OFF time must be set.
2. WEEKLY TIMER
2-1. WEEKLY TIMER
Stop mode
Stop mode
Stop mode
Operation mode
Operation mode
Set time
Set time Set time Set time
01-11
AR-WAE1E
1-8-1 Wired Remote Controller (with AU, AR model)
ON / TIMER OFF / TIMER
WEEKLY TIMER
TEMPERATURE SET BACK TIMER
01-12
The DAY OFF setting is only available for days for which weekly settings already exist.
The DAY OFF setting can only be set one time. The DAY OFF setting is cancelled automatically after the set day has passed.
Normal
Next day setting
If the operating time carries over to the next day (during a next day setting), the effective DAY OFF range will be set as shown below.
2-2. DAY OFF setting
Stop mode
Stop mode
Operation mode
Stop mode
Operation mode
Preceding day Next day
DAY OFF
Stop mode
Stop mode
Operation mode
Stop mode
Operation mode
DAY OFF
Setting day
Preceding day Next daySetting day
The SET BACK timer only changes the set temperature for 7 days, it cannot be used to start or stop air conditioner operation.
The SET BACK timer can be set to operate up to two times per day but only one temperature setting can be used.
During the COOL/DRY mode, the air conditioner will operate at a minimum of 18°C even if the SET BACK temperature is set to 17°C or lower.
3. TEMPERATURE SET BACK TIMER
Case of SET BACK timer on the Cooling operation. ( Setting temperature :22°C, SET BACK temperature :26°C)
SET BACK setting
Operation temperature
Operation temperature
26°C
22°C
26°C
22°C
24°C
*1
ON OFF OFFON
*1: During the SET BACK function, the setting temperature is changed.
Change the setting temperature: 22°C 24°C
01-13
AR- RAH2E
1. ON / OFF TIMER
OFF timer : When the clock reaches the set time, the air conditioner will be turned off.
Operation mode
Stop mode
Set time of timer
ON timer : When the clock reaches the set time, the air conditioner will be turned on.
Operation mode
Stop mode
Set time of timer
2. PROGRAM TIMER
ON / TIMER OFF / TIMER
PROGRAM TIMER
SLEEP TIMER
The program timer allows the OFF timer and ON timer to be used in combination one time.
Operation mode
Operation will start from the timer setting (either OFF timer or ON timer) whichever is closest to the clock's current timer setting. The order of operations is indicated by the arrow in the remote control unit's display.
SLEEP timer operation cannot be combined with ON timer operation.
Stop mode
Stop mode
Stop mode
Operation mode
Operation mode
Set time
Set time Set time Set time
1-8-2 Wireless Remote Controller (with AB model)
01-14
3. SLEEP TIMER
If the sleep timer is set, the room temperature is monitored and the operation is stopped automatically. If the operation mode or the set temperature is change after the sleep timer is set, the operation is continued according to the changed setting of the sleep timer from that time ON.
Set temperature rises
( Ts : Set temperature )
Stop of operation
Set temperature lowers
( Ts : Set temperature )
Ts
Stop of operation
In the COOLING operation mode
When the sleep timer is set, the setting temperature is increased 1 degC. It increases the setting temperature another 1 degC after 1 hour. After that, the setting temperature is not changed and the operation is stopped at the time of timer setting.
Ts
+1°C
+2°C
-2°C
-1°C
-4°C
-3°C
Set
60min
In the HEATING operation mode
When the sleep timer is set, the setting temperature is decreased 1 degC. It decreases the setting temperature another 1 degC every 30 minutes. Upon lowering 4 degC, the setting temperature is not changed and the operation stops at the time of timer setting.
Set
30min
60min
90min
1-9. ELECTRONIC EXPANSION VALVE CONTROL
1-10. TEST OPERATION CONTROL
01-15
Under the condition where the air conditioner stops, press the MASTER CONTROL button and the FAN CONTROL button simultaneously for 2 seconds or more, and the test operation control mode will appear. During test running, " " will display on the remote controller display. Set the test operation mode, and the compressor will continue to run regardless of whatever the room temperature sensor detects. The test operation mode is released if 60 minutes have passed after setting up the test operation.
With Wired Remote Controller
The most proper opening of the electronic expansion valve is calculated and controlled under the present operating condition based on the following values. The compressor frequency, the temperatures detected by the discharge temperature sensor, the indoor heat exchanger sensor, the outdoor heat exchanger sensor, and the outdoor temperature sensor.
Pulse range
53~480 pulse
(1) Pulse range of EEV
(2) The EEV is set up at 480 pulses when the compressor is stopped.
(3) Initialization (Input of 528 pulses toward closing direction) is operated under the following condition.
* When the power is turned on.
* 4 hours has passed since the last initialization, and 3 minutes has passed after the compressor stop. (If 12 hours has passed since the last initialization, the compressor is compulsorily stopped.)
AO* G45LETL AO* G54LETL
Cooling / Dry
Heating
Operation
Under the condition where the air conditioner runs, press the TEST RUN button, and the test operation control mode will appear. During test running, the Operation LED and Timer LED of the air conditioner body blinks simultaneously. Set the test operation mode, and the compressor will continue to run regardless of whether the room temperature sensor detects. The test operation mode is released if 60 minutes have passed after setting up the test operation.
With Wireless Remote Controller
The compressor won't enter operation status for 3 minutes after the compressor is stopped, even if any operation is given.
At the time when the air conditioner is switched from the cooling mode to heating mode, the compressor is stopped, and the 4-way valve is switched in 3 minutes later after the compressor stopped.
When the power was interrupted by a power failure, etc. during operation, the operation contents at that time are memorized and when power is recovered, operation is automatically resumed with the memorized operation contents. When the power is interrupted and recovered during timer operation, timer operation is canceled, but only setting time is memorized.
[Operation contents memorized when the power is interrupted]
Operation mode Set temperature
Set air flow
Timer mode and timer time (Set by wireless remote controller)
10°C HEAT (Wireless remote controller is in use)
ECONOMY
1-11. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST )
1-12. 4-WAY VALVE EXTENSION SELECT
1-13. AUTO RESTART
01-16
WARNING
Never touch electrical components such as the terminal blocks except the button on the display board. It may cause a serious accident such as electric shock.
During the pump-down operation, make sure that the compressor is turned off before you remove the refrigerant piping. Do not remove the connection pipe while the compressor is in operation with 2-way or 3-way valve open. This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury.
CAUTION
Perform the pump down operation before disconnecting any refrigerant pipe or electric cable.
Collect refrigerant from the service port or the 3-way valve if pump down cannot be performed.
In case of a group control system installation, do not turn the power off pump down is completed in all outdoor units. (Group control system installation described in “SPECIAL INSTALLATION METHODS” in the installation manual of the indoor unit.)
Operate [PUMP DOWN] button on the display board in the manner described below.
LED display part
Button part
14.1. Preparation for pump down
Confirm that the power is off, and then open the service panel
14.2. Pump down procedure
(1) Check the 3-way valves (both the liquid side and gas side) are opened.
(2) Turn the power on.
POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE (L1) (L2) (L3) (L4) (L5) (L6)
Sign “ ”: Lights off, “ ”: Lights on
(3) Press [PUMP DOWN] button for 3 seconds or more after 3 minutes after power on.
LED display lights on as shown in the above figure, and the fans and the compressor start operating.
If the [PUMP DOWN] button is pressed while the compressor is operating, the • compressor will stop, then start again in about 3 minutes.
(4) LED display will change as shown below about 3 minutes after the compressor
starts. Fully close the 3-way valve on the liquid pipe side at this stage.
If the valve on the liquid pipe side is not closed, the pump down cannot be • performed.
(5) When LED display changes as shown in the below figure, close the 3-way valve on
the gas pipe side tightly.
If the valve on the gas pipe side is not closed, refrigerant may flow into the piping• after the compressor stops.
Step (5)
Closing direction
Step (4)
Hexagon wrench
Liquid pipe
Gas pipe
Closing direction
(6) LED display changes after 1 minute as shown in the figure below
Fans and compressor stop automatically.
If the pump down is successfully completed (the above LED display is shown), the • outdoor unit remains stopped until the power is turned off.
(7) Turn the power off.
PUMP DOWN is completed.
(Note)
To stop pump down, press the [PUMP DOWN] button again.• To start the pump down again after the compressor is automatically stopped due to an • error, turn the power off and open the 3-way valves. Wait 3 minutes, turn the power on and start the pump down again.
When starting the operation after completion of the pump down, turn the power off, • and then open the 3-way valves. Wait 3 minutes, turn the power on and perform a test run in the “COOL” operation mode.
If an error occurs, recover the refrigerant from service port.
SW1 SW2 SW3 SW4 SW5
POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE (L1) (L2) (L3) (L4) (L5) (L6)
Sign “ ”: Lights off, “ ”: Lights on
POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE (L1) (L2) (L3) (L4) (L5) (L6)
Sign “ ”: Lights off, “ ”: Lights on
POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE (L1) (L2) (L3) (L4) (L5) (L6)
Sign “ ”: Lights off, “ ”: Lights on
POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE (L1) (L2) (L3) (L4) (L5) (L6)
Sign “ ”: Lights off, “ ”: Lights on
POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE (L1) (L2) (L3) (L4) (L5) (L6)
Sign “ ”: Lights off
01-17
1-14. PUMP DOWN
1-15. COMPRESSOR PREHEATING
01-18
When the outdoor temperature is lower than 20°C and the all operation mode has been stopped for 30 minutes, power is applied to the compressor and the compressor is heated. (By heating the compressor, warm air is quickly discharged when operation is started.) When operation was started and when the outdoor temperature rises to 26°C or greater, preheating is ended.
1-16. 10°C HEAT OPERATION (For AB type)
10°C HEAT operation functions by pressing 10°C HEAT button on the remote controller. 10°C HEAT operation is almost the same operation as below settings.
Mode Heating
Setting temperature 10°C
Fan mode AUTO
( Table8 )
1-17. ECONOMY OPERATION
The ECONOMY operation functions by pressing ECONOMY button on the remote controller. The ECONOMY operation is almost the same operation as below settings.
Mode Cooling/ Dry Heating
Target temperature Setting temp.+1°C Setting temp.-1°C
( Table9 )
01-19
1-18. DEFROST OPERATION CONTROL
1. CONDITION OF STARTING THE DEFROST OPERATION
Integratingdefrost
(Constant monitoring)
If the compressor continuous operation time is less than 10 minutes, the OFF number of the compressor is counted. If any defrost operated, the compressor OFF count is cleared.
2. CONDITION OF THE DEFROST OPERATION COMPLETION
Defrost operation is released when the conditions becomes as shown in Table 13.
( Table 13 : Condition of defrost release )
Release Condition
Outdoor heat exchanger temperature is higher than 10°C or Compressor operation time has passed 15 minutes.
The defrost operation starts as shown in the following Table 10, 11, and 12.
From 2nd and later
defrost after
starting operation
Less than 35 minutes More than 35 minutes
Does not operate
Compressor integrating operation time
( Table 10 : Condition of 1st defrost operation)
1st defrost
after
starting operation
Compressor integrating operation time
Less than 22 minutes More than 22 minutes More than 62 minutes
Does not operate
Outdoor heat exchanger temperature
Below -9°C
Outdoor heat exchanger temperature
Below -10°C
Outdoor heat exchanger temperature
Below -5°C
More than 240 minutes
( For long continuous operation )
Less than 10 minutes
( For intermittent operation )
Compressor integrating operation time
Outdoor heat exchanger temperature
Below -3°C
OFF count of the compressor
40 times
( Table 12 : Condition of Integrating defrost operation)
( Table 11 : Condition of 2nd defrost operation)
01-20
3. Defrost Flow Chart
The defrosting shall proceed by the integrating operation time, outdoor temperature and outdoor heat exchanger temperature as follows.
(Not defrosted for 10 minutes)
Heating operation start : Compressor ON
Outdoor heat exchanger temperature: Over 10°C
or
Compressor ON time: Maximum 15 minutes
Defrost end
Compressor integrating operation: Over 22 minutes
Compressor integrating operation: Over 62 minutes
Outdoor heat exchanger temperature: Below - 9°C
Outdoor heat exchanger temperature: Below - 5°C
Compressor integrating operation: Over 35 minutes
2nd and later defrost
Compressor : OFF Outdoor fan motor : OFF 30 sec later 4-way valve : OFF 36 sec later compressor : ON
Compressor integrating operation: Over 240 minutes
Integrating defrost
(Constant monitoring)
Defrost Indicator: [Operation lamp] 7 sec ON / 2 sec OFF
Defrost start
Outdoor heat exchanger temperature: Below - 10°C
Outdoor heat exchanger temperature: Below - 3°C
Compressor OFF count : 40 times
1st defrost
1-19. OFF DEFROST OPEARTION CONTROL
01-21
1. OFF DEFROST OPERATION CONDITION
When operation stops in the [Heating operation] mode, if frost is adhered to the outdoor unit heat exchanger, the defrost operation will proceed automatically. In this time, if indoor unit operation lamp flashes slowly (7 sec ON / 2 sec OFF), the outdoor unit will allow the heat exchanger to defrost, and then stop.
In heating operation, the outdoor heat exchanger temperature is less than -4°C, and compressor operation integrating time lasts for more than 30 minutes, and compressor operation contiguous time lasts for more than 10 minutes.
OFF Defrost Flow Chart
Heating operation stop
Outdoor heat exchanger temperature : Below -4°C and Compressor integrating operation : Over 30 minutes and Compressor contiguous operation: Over 10 minutes
Defrost start
Defrost Indicater: [Operation lamp] 7 sec ON / 2 sec OFF
Outdoor heat exchanger temperature : Over 10°C
or
Compressor ON time : Maximum 15 minutes
Defrost end
2. OFF DEFROST RELEASE CONDITION
Release Condition
Outdoor heat exchanger temperature is higher than 10°C or Compressor operation time has passed 15 minutes.
( Table 14 : OFF Defrost Release Condition )
OFF defrost operation is released when the conditions becomes as shown in Table 14.
1-20. VARIOUS PROTECTIONS
01-22
1. DISCHARGE GAS TEMPERATURE OVERRISE PREVENSION CONTROL
The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas temperature.
104°C 101°C 110°C
When the discharge temperature becomes higher than Temperature ,the compressor frequency is decreased 14rps, and it continues to decrease the frequency for 14rps every 120 seconds until the temperature becomes lower than Temperature .
When the discharge temperature becomes lower than Temperature , the control of the compressor frequency is released.
When the discharge temperature becomes higher than Temperature ,the compressor is stopped and the indoor unit LED starts blinking.
(Table15 : Discharge Temperature Over Rise Prevension Control / Release Temperature)
Temperature
Temperature
Temperature
[ Heating ]
[ Cooling ]
T0 > 50°C
=
T0: Outdoor temperature
Outdoor unit fan speed (rpm)
T0 < -15°C
50°C > T0 > 46°C
=
46°C > T0 > 40°C
=
40°C > T0 > 38°C
=
38°C > T0 > 31°C
=
31°C > T0 > 19°C
=
19°C > T0 > 13°C
=
13°C > T0 > 7°C
=
7°C > T0 > 0°C
=
0°C > T0 > -5°C
=
-5°C > T0 > -10°C
=
-10°C >T0 > -15°C
=
850/800 780/750 750/700 540/520 360/340 290/270 480/ 0 400/ 0 350/ 0 280/ 0
12.5/12.0 6.5/ 6.0
5.0/ 4.5
8.0/ 7.5
9.0/ 8.5
9.0/ 8.5
10.0/ 9.5
10.0/ 9.5
10.0/ 9.5 6.0/ 5.5
10.5/10.0
12.5/12.0
12.0/11.5 10.0/ 9.5
12.5/12.0
13.0/12.5
14.5/14.0
15.5/15.0 11.5/11.0
11.0/10.5
13.5/13.0
13.5/13.0
14.5/14.0
15.0/14.5
15.5/15.0
16.0/15.5
13.5/13.0
16.5/16.0
17.5/17.0
19.5/19.0 19.0/18.5 16.5/16.0
T0 > 20°C
=
T0: Outdoor temperature
Outdoor unit fan speed (rpm)
T0 < 12°C
20°C > T0 > 12°C
=
900/880 850/830 780/750 720/700 570/550 500/480 370/350 300/280 220/200
16.5/16.0
14.5/14.0
19.5/19.0
The compressor frequency is controlled so that the outdoor unit input current does not exceeds the current limit value that was set up with the outdoor temperature. The compressor frequency returns to the designated frequency of the indoor unit at the time when the frequency becomes lower than the release value.
(Table 16 : Current Release Operation Value / Release Value)
2. CURRENT RELEASE CONTROL