WSYA100DG6Waterstage Comfort 8WOYA080LFCA
Waterstage Comfort 10WOYA100LFTA
Waterstage High Power 11 single phaseWOYG112LCTA
Waterstage High Power 14 single phaseWOYG140LCTA
Waterstage High Power 11 3-phaseWOYK112LCTA
Waterstage High Power 16 3-phaseWOYK160LCTA
WSYG140DG6
WSYK160DG9Waterstage High Power 14 3-phaseWOYK140LCTA
Contents
Safety instructions
Overall view of the installation
Please comply with the following instructions in order to avoid any risk of injury or inappropriate use
of the appliance.
• Start-up
" Do not switch the appliance on until every llings have been done.
" Do not try to install this appliance yourself.
" This heat pump requires an appropriately qualied person to install it.
" The installation must always be connected to the Earth and tted with a protective circuit breaker.
" Do not modify the electricity supply.
" The appliances are not reproof and should therefore not be installed in a potentially explosive
atmosphere.
• Use
" Do not let children insert foreign bodies into the fan protection grill or climb on top of the outdoor
unit. The ns on the air exchanger are extremely ne and cause cuts.
" Nothing should obstruct the air circulation through the evaporator and from the fan.
" The outdoor unit must only be installed outdoor (outdoors). If a shelter is required, it must have
broad openings on the 4 walls and observe the installation clearances (see with your installer).
" Do not climb on the top of the outdoor unit.
" The room in which the appliance is operating must be correctly ventilated in order to prevent any
loss of oxygen if there is an escape of refrigerant gas.
" Consult your Installer before making any changes or modications to the premises where the
appliance is installed.
" Do not place any heat source under the room control unit.
• Maintenance
" Do not try to repair this appliance yourself.
" This appliance does not contain any components capable of being repaired by the user himself.
Removing one or other of the covers can expose you to dangerous electrical voltages.
" In any case, switching off the current is not sufcient to protect you from any external electrical
shocks (capacitors).
" Do not open the outdoor unit or the hydraulic unit while they are operating.
" Switch off the power supply if there are any abnormal noises, smells or smoke coming from the
appliance and contact your installer.
" Switch off the power to the appliance before you clean it.
" Do not use aggressive cleaning liquid or solvents to clean the body work.
" Do not use a pressure washer to clean the outdoor unit. This could damage the air exchanger
and the water might penetrate into the electrical circuits.
Operation manual "1534 - EN"
- 3 -
Page 4
Air to Water Heat Pump Split system
2 Overall view of the installation
2 1 Precautions and warnings regarding
your installation
2 1 1 The outdoor unit
The outdoor unit contains the equipment for capturing
energy from the ambient air.
Your installer has placed this unit in a location that
enables it to operate in an optimum manner.
Nothing should obstruct the air circulation through the
evaporator and from the fan.
The water that the air contains condenses and ows
from the external unit.
In cold periods, this water freezes in contact with the
exchanger and is drained away by regular defrosting
cycles. The control system automatically controls the
defrosting cycle, whose operation can lead to the quite
normal emission of steam.
2 1 2 The hydraulic unit
The hydraulic unit contains the heat pump complete
control system, in charge of controlling the heating
comfort level (and the production of domestic hot water -
if the installation is tted with a DHW tank with electrical
back-up heating).
The heat pump is equipped with an electrical back-up
system, which is designed to provide additional heat
during the coldest periods.
2 1 4 The radiators
To ensure the function of the regulation with room
inuence, it's necessary that the room in which the room
thermostat is installed has no thermostatic valve or that
they must be completely open.
2 1 5 Floor-heating systems
New oor-heating systems require to be initially heated
slowly to avoid any problems with cracking. Check
with your installer that this initial heating procedure
has indeed been performed before using your heating
system freely.
The great stability in a regulation system for oor-heating
systems avoids sharp differences in temperature.
However, this stability involves a reaction time of the
order of several hours, (approx 6 hours).
Any changes to the setting must be made slowly, leaving
the installation time to react. Adjusting the system to
exaggerated setting or in an untimely manner always
results in signicant temperature uctuations during
course of the day.
Similarly if your dwelling has a oor-heating system,
do not reduce the heating or switch it off if you will be
absent for a short period. The reheating period is always
quite long (approx 6 hours).
2 1 3 Control system
Y our installer has carefully adjusted your installation. Do
not modify setting parameters without his agreement. If
in doubt, do not hesitate to contact him.
The control system for your heating system is designed
in ow temperature for the water based on the outdoor
temperature (water control).
The installation of a room thermostat (option) allows to
improve operation of the regulation (the inuence of the
room temperature is taken into account).
2 1 6 Fan convectors / Dynamic radiators
with integrated control system
Do not use a room sensor in the area.
2 1 7 Domestic hot water (DHW)
When the DHW production is required, the heat pump
adapts to this demand with higher priority.
No space heating is produced while the domestic hot
water is being prepared.
Domestic hot water (DHW) is produced by the heat
pump and then topped up, if necessary, by electrical
backup heating or the boiler.
To ensure a DHW setting over 45°C, the electrical backup heating or the boiler must be left on (Optional boiler
connection kit).
The electrical back-up heating enables anti-legionella
cycles to be conducted efciently.
- 4 -
Operation manual "1534 - EN"
Page 5
Air to Water Heat Pump Split system
2 2 End of life of the device
Disassembly and recycling shall be handled by a
qualied body. Wild disposal is strickly prohibited.
At the end-of-life of the equipment, please contact
your installor or any local representant to proceed to
disassembly and recycling.
2 3 Overall view of the installation
Your heat pump has been congured by your installer. It
is composed of the following main elements:
-The outdoor unit is positioned, as its name indicates,
outdoor your dwelling and extracts energy from the
outdoor air.
-The hydraulic unit positioned in your boiler room, cellar,
garage or even your kitchen, transfers the energy to
the heating circuit (and the domestic hot water).
-The outdoor sensor detects the outdoor temperature.
Optional equipment:
-Room thermostat.
-Room control unit.
Heat pumps are systems that can be connected to any
form of low temperature heat distribution systems :
the heat captured by the heat pump can therefore be
used in different ways:
-Floor-heating systems.
-Radiators or fan coil heaters.
-Domestic hot water (DHW).
Room thermostat
Control options
or T55
Outdoor
Outdoor
sensor
sensor
or
OR
T58
Room thermostat
(wired or radio)
Hydraulic unit
The hydraulic unit
Room control unitT75 or T78
or/and
or/and
Remote control
(wired or radio)
Options
Options
depending
depending
on the system
on the system
congurations
congurations
2nd circuit kit
2nd circuit kit
DHW kit
DHW kit
Boiler connexion
Boiler connexion
kit
kit
Control options
Heating circuit
Heating circuit
Floor heating system
Floor heating system
Heating circuit
Heating circuit
Radiators
Radiators
DHW tank with electrical
DHW tanks
back-up heating
with electrical back-up
Boiler
Boiler
Outdoor unit
The outdoor unit
Operation manual "1534 - EN"
gure 1 - Overall view of the conguration of a complete installation
- 5 -
Page 6
Air to Water Heat Pump Split system
3 Operation of the installation
3 1 User interface, Room control unit (option) and Room thermostat (option)
1
5
2
6
3
7
8
4
User interface
9
1
Auto
5
2
3
0 4 8 12 16 20 24
ESC
OK
7
Auto
5
11
2
4
8
°C
10
6
Room control unit T75 / T78Room thermostat T55 / T58
Remote control (option)Room thermostat (option)
gure 2 -
11
- 6 -
Operation manual "1534 - EN"
Page 7
Off
Auto
Air to Water Heat Pump Split system
Ref Functions- Denitions
1Selecting of the DHW operating mode
(Domestic hot water).
On
2Digital display.
3Exit "ESC".
4Navigation and setting.
5Selecting the heating mode.
- If the installation is tted with a DHW tank.
- On: Production of DHW according to the time program.
- Off: Preparing the domestic hot water for stopping with the anti-frost function
active.
- Manual start button: Hold down the DHW key for 3 seconds. Switch from
"reduced" to "comfort" until the next time the ECS timer switches over.
- Operating control. Readout of the current temperature, of the heating mode
and of any faults
.
- View the settings.
- Quit the menu.
- Selecting the menu.
- Setting parameters.
- Adjusting the ambient temperature setpoint.
-
Heating operating according to the heating program
(Summer/winter mode switchover is automatic).
- Constant comfort temperature.
- Constant reduced temperature.
- Stand-by mode with anti-frost protection
(Provided that the heat pump's electrical power supply is not interrupted).
6Information display.
- Various data (see page 18).
- Reading error codes (see Installation and operating manual).
- Information concerning maintenance, special mode.
7Conrm "OK". - Input into the selected menu.
- Conrmation of the parameter settings.
- Conrmation of the adjustment to the comfort temp. setting.
8Selecting cooling mode.
- If the installation is tted with the cooling kit:
- Cooling operating according to the heating program
(Summer/winter mode switchover is automatic).
9RESET button
(Brief press)
- Reinitialising the parameters and cancelling error messages.
Do not use during normal operation
10Control knob. - Adjusting the ambient temperature setpoint.
11Presence key .
• The installation and 1st start up of the appliance
must be done by a qualied installer. That person will
also give you instructions on starting and running the
appliance.
• Ensure that the installation is fully lled with water
and has been correctly bled and that there is a
sufcient pressure of 1,5 to 2 bars on the manometer
(ref. 2, gure 5).
• Close the installation's main circuit breaker.
In winter, so that the compressor can be
preheated, close the installation's main circuit
breaker (outdoor unit's power supply) some
hours before pressing the on/off button.
3 4 Quick start-up
Once your installer has started your installation for the
rst time:
• Engage the start/stop switch.
During the regulator initialisation phase, the
display shows all the symbols and then "Data,
update" and then "State heat pump".
• Select the "AUTO" heating mode (gure 6).
• Select the DHW mode (gure 6).
• Adjust the date and time if necessary (gure 7).
Press OK
_______________
Time and date
Operator section
Select menu
hour and date
1. User interface
2. Manometer (installation hydraulic pressure)
3. Start/stop switch
gure 5 - Start-up
Press OK
1
Select one of the
Time and date
Hours / minutes
lines :
hour / minutes
or day / month
or years
2
Press OK
3
Make all the
settings
Time and date
Hours / minutes
Press OK to
conrm each
setting
gure 6 - Selecting the heating mode AUTO
and Select the DHW mode
Operation manual "1534 - EN"
Press heating mode key to
return to basic display
gure 7 - Setting the time and the date
- 9 -
Page 10
Air to Water Heat Pump Split system
3 5 Setting the time
Keys Display example Description
1
AUTO
Basic display
If the basic display is not shown,
Room temperature
4812 16 20 24
0
press ESC to return to it
Press OK to conrm.
2
AUTO
Turn the knob
Select menu hour and date
Time and date
Operator section
4812 16 20 24
0
Press OK to conrm.
3
AUTO
Turn the knob
Time and date
Hours / minutes
4812 16 20 24
0
Select line 1 Hours / minutes
Press OK to conrm.
4
Time and date
Hours / minutes
0
AUTO
4812 16 20 24
The hour display ashes
Turn the knob to set the time
Press OK to conrm.
5
Time and date
Hours / minutes
0
AUTO
4812 16 20 24
The minutes display ashes
Turn the knob to set the minutes
Press OK to conrm.
6
AUTO
The setting are recorded
Turn the knob to make other settings
Time and date
Hours / minutes
04812162024
or
Press heating mode key to return to
basic display.
- 10 -
gure 8 -
Operation manual "1534 - EN"
Page 11
Air to Water Heat Pump Split system
3 6 Structure
of the "End user" control menu
Basic
display
Brief
press
End user
Time of day and date
Operator sectionLanguage
Time prog heating circuit 1
Time prog heating circuit 2
Time program 4/DHW
CommissioningEngineerOEM
Hours / minutes
Day / Month
Year
Pre-selection
1st phase on
1st phase off
2nd phase on
2nd phase off
3rd phase on
3rd phase off
Monday, Tuesday, …
5011st phase On (start)00:00... --:--10 min6:00
5021st phase Off (end)00:00... --:--10 min22:00
5032nd phase On (start)00:00... --:--10 min--:-5042nd phase Off (end)00:00... --:--10 min--:-5053rd phase On (start)00:00... --:--10 min--:-5063rd phase Off (end)00:00... --:--10 min--:-516Default values, Circuit 1No, Y esNo
Yes + OK: The default values memorised in the regulator replace and cancel the customised heating programs.
Your customised settings are therefore lost.
Monday, Tuesday, …
5211st phase On (start)00:00... --:--10 min6:00
Setting
increment
Basic
setting
Mon-Sun
Mon-Sun
5221st phase Off (end)00:00... --:--10 min22:00
5232nd phase On (start)00:00... --:--10 min--:-5242nd phase Off (end)00:00... --:--10 min--:-5253rd phase On (start)00:00... --:--10 min--:-5263rd phase Off (end)00:00... --:--10 min--:-536Default values, Circuit 2No, Y esNo
Yes + OK: The default values memorised in the regulator replace and cancel the customised heating programs.
Your customised settings are therefore lost.
5611st phase On (start)00:00... --:--10 min00:00
5621st phase Off (end)00:00... --:--10 min05:00
5632nd phase On (start)00:00... --:--10 min14:30
5642nd phase Off (end)00:00... --:--10 min17:00
5653rd phase On (start)00:00... --:--10 min--:-5663rd phase Off (end)00:00... --:--10 min--:-576
Default valuesNo, Y esNo
Monday, Tuesday, …
Mon-Sun
Yes + OK: The default values memorised in the regulator replace and cancel the customised heating programs.
Your customised settings are therefore lost.
Holidays, heating circuit 1 (For the Holiday program is active, the heating mode should be on AUT
Holidays, heating circuit 2 (For the Holiday program is active, the heating mode should be on AUT
If the installation consists of 2 heating circuits (Only with the 2nd circuit kit option).
651PreselectionPeriod 1 to 8Period 1
652Period Start (Day / Month)01.01... 31.121
653Period End (Day / Month)01.01... 31.121
658Operating levelFrost protection, ReducedFrost
Heating adjustment, circuit 1
710Comfort setpointRed u c e d setpoint…
Comfort setpoint maximum
712Reduced setpointFrost protection setpoint…
Comfort setpoint
714Frost protection setpoint4 °C… Reduced setpoint0,5 °C8 °C
Cooling circuit 1
If the installation is tted with the cooling kit (Only with the cooling kit option).
901Operating modeProtection, Automatic, Reduced,
Comfort
Setting
increment
O).
0,5 °C20 °C
0,5 °C19 °C
Basic
setting
protection
Protection
902Comfort cooling setpoint17... 40 °C0,5 °C24 °C
903Reduced setpoint5... 40°C26 °C
Heating adjustment, Circuit 2
Only with the 2nd circuit kit option (If the installation consists of 2 heating circuits).
1010Comfort setpointRed u c e d setpoint…
Comfort setpoint maximum
1012Reduced setpointFrost protection setpoint…
Comfort setpoint
1014Frost protection setpoint4 °C… Reduced setpoint0,5 °C8 °C
Cooling circuit 2
If the installation is tted with the cooling kit (Only with the cooling kit option).
1201Operating modeProtection, Automatic, Reduced,
Comfort
1202Comfort cooling setpoint17... 40 °C0,5 °C24 °C
1203Reduced setpoint5... 40°C26 °C
Domestic hot water
If the installation is tted with the DHW kit.
1600Operating modeOff, On, EcoOn
1610Nominal setpointReduced setpoint (line 1612)…
65 °C
0,5 °C20 °C
0,5 °C19 °C
Protection
155 °C
The backup electrical system is required to reach this level.
1612Reduced setting8 °C...
Nominal setting (line 1610)
Swimming pool (Only with swimming pool kit option)
2055Setpoint solar heating8... 80 °C26 °C
2056Setpoint source heating8... 35 °C22 °C
- 14 -
140 °C
Operation manual "1534 - EN"
Page 15
Air to Water Heat Pump Split system
LineFunctionSetting range
or display
Energy meter
3113U Amount of gas brought in--
Cumulation of total consumed electrical energy.
Electrical energy consumed = Electrical energy absorbed by outdoor unit + electric energy absorbed by the heating
electrical backup and / or DHW electrical backup (if installed).
3124U Energy brought in heating 1 (N - 1)--
3125U Energy brought in DHW 1--
3126U Energy brought in cooling 1--
3131U Energy brought in heating 2 (N - 2)--
3132U Energy brought in DHW 2--
3133U Energy brought in cooling 2--
3138U Energy brought in heating 3 (N - 3)--
3139U Energy brought in DHW 3--
3140U Energy brought in cooling 3--
3145U Energy brought in heating 4 (N - 4)--
3146U Energy brought in DHW 4--
Setting
increment
Basic
setting
3147U Energy brought in cooling 4--
3152U Energy brought in heating 5 (N - 5)--
3153U Energy brought in DHW 5--
3154U Energy brought in cooling 5--
3159U Energy brought in heating 6 (N - 6)--
3160U Energy brought in DHW 6--
3161U Energy brought in cooling 6--
3166U Energy brought in heating 7 (N - 7)--
3167U Energy brought in DHW 7--
3168U Energy brought in cooling 7--
3173U Energy brought in heating 8 (N - 8)--
3174U Energy brought in DHW 8--
3175U Energy brought in cooling 8--
3180U Energy brought in heating 9 (N - 9)--
3181U Energy brought in DHW 9--
3182U Energy brought in cooling 9--
3187U Energy brought in heating 10 (N - 10)--
3188U Energy brought in DHW 10--
3189U Energy brought in cooling 10--
Error
6711Reset HPNo, Y esNo
Note: "Energy" Counters increment as of 1 July each year.
Operation manual "1534 - EN"
- 15 -
Page 16
Air to Water Heat Pump Split system
LineFunctionSetting range
Maintenance / special regime
7141Emergency operationOff, OnOff
Off: Heat pump functions normally (with boosters if necessary).
On: Heat pump uses the electric boost system or the boiler connection.
Use the “On” position only in Assist mode or Test mode: may result in high power bills.
Generator diagnosis
8410Return temp HP0... 140 °C--
Setpoint (ow) HP--
8412Flow temp HP0... 140 °C--
Setpoint (ow) HP--
8413Compressor modulation0... 100%--
Diagnostics consumers
8700Outdoor temperature-50... 50 °C-8701Outdoor temp min
Reset ? (no, yes)
8702Outdoor temp max
Reset ? (no, yes)
or display
-50... 50 °C50 °C
-50... 50 °C-50 °C
Setting
increment
Basic
setting
8740Room temperature 10... 50 °C--
Room setting 120 °C
8743Flow temperature 10... 140 °C--
Flow temperature setpoint 1--
8756Cooling ow temperature 10... 140 °C--
Cooling ow temperature setpoint 1--
8830DHW (domestic hot water) temperature0... 140 °C--
DHW temperature setpoint50 °C
- 16 -
Operation manual "1534 - EN"
Page 17
Air to Water Heat Pump Split system
Operation manual "1534 - EN"
- 17 -
Page 18
Air to Water Heat Pump Split system
3 8 Information display
Various data can be displayed by pressing the info
button.
Depending on the type of unit, conguration and
operating state, some of the info lines listed below may
not appear.
-Possible error messages: The display shows the "Bell" symbol .
-Consult your heating technician
-Service messages ; Special mode messages:
The display shows the “Key” symbol .
-Consult your heating technician
-Various data (see below).
DesignationLine
Floor drying current setpoint .Current drying day.Terminated drying days.State heat pump.8006
State supplementary source.8022
State DHW.8003
State swimming pool.8011
State heating circuit 1.8000
State heating circuit 2.8001
State cooling circuit 1.8004
Outdoor temperature.8700
Room temperature 1.
Room setpoint 1.
Flow temperature 1.
Flow temperature setpoint1.
Room temperature 2.
Room setpoint 2.
Flow temperature 2.
Flow temperature setpoint 2.
DHW (domestic hot water) temperature.8830
Heat pump return temperature.
Setpoint (return) HP.
Heat pump ow temperature.
Setpoint (ow) HP.
Swimming pool temperature.
Swimming pool temperature setpoint.
Minimum remaining stop time for compressor 1.Minimum remaining running time for compressor 1.-
8740
8743
8770
8773
8410
8412
8900
3 9 Details
If the electrical power supply has been cut off while
the heat pump is operating (electrical power failure or
unprogrammed pressing of the on/off switch on the
hydraulic unit) the display will show error 370 when
the appliance restarts. Do not be concerned, the
communication between the outdoor and hydraulic unit
will re-establish itself in a few moments.
- 18 -
Operation manual "1534 - EN"
Page 19
Air to Water Heat Pump Split system
3 10 Operation of the DHW system
The key enables you to switch the DHW (domestic hot
water) mode on and off. The selection is shown by a
bar, which appears under the corresponding symbol.
Manual activation: Hold down the DHW key for 3
seconds (Switch from "reduced" to "nominal" until the
next time the DHW timer switches over).
To ensure a DHW setting over 45°C, the electrical backup heating or the boiler must be left on.
In order to optimise operation of the DHW, it is possible to:
-Program the timer settings (parameters 560 to 576),
-Adjust the comfort temperature set point (parameter 1610),
-Adjust the reduced temperature set point (parameter 1612).
Press the info key to obtain the details on the DHW
(temperature setting operation).
3 11 Selecting cooling mode
If the installation is tted with the cooling kit.
The key activates and deactivates cooling mode.
gure 10 - Select the DHW mode
Brief
press
gure 11 - Information key
Details of any error
Operating values
...
3 12 Pilot wire
(if kit regulation extension AVS 55)
It's possible to order up to 15 electric heaters via output
"pilot wire".
The "pilot wire" handles only the hourly operation
of electric heaters (comfort mode / reduced mode
commutation and Frost protection mode).
The comfort temperature setting should be done
directly on the electric heater(s). The "pilot wire" does
not handle the temperature of the electric heaters.
Refer to the manual supplied with the electric heater(s).
Put the electric heaters on "PROG" mode or "AUTO"
mode for piloting by the regulation board.
The difference between the comfort temperature and
the reduced temperature is from 3,5 ° C.
Frost protection temperature is set directly on the
electric heaters. Refer to the manual supplied with the
electric heater(s).
In the absence of signal, electric heaters operating in
It is possible to command the switching of the heating
mode to the "freeze" protection mode / reduced
(and vise versa) on the heat pump using a modem contact.
The telephone command switches the current heat
pump settings to "freeze" protection mode / reduced
(and vise versa). In accordance with the setting, any
temperature requests from the heating circuits and the
DHW are ignored or activated.
The "freeze" protection mode / reduced must not be
selected on the heat pump and/or the remote control.
See with your installer.
Operation manual "1534 - EN"
3 14 Conguring room control unit (option)
In the event that the room control unit (see gure 2),
is used, on start-up, after initialising for around
3 minutes, the language needs setting:
-Press OK.
-Choose menu "Operator section".
-Choose language "Language" English.
- 19 -
Page 20
Air to Water Heat Pump Split system
4 Maintenance
In order to insure your appliance operates correctly for
many years, the maintenance operations described
below are required at the start of each heating season.
Generally, these are performed as part of a service
contract.
4 1 Regular checks
-Periodically check the water pressure in the heating
circuit (Refer to the pressure recommended by the
installer - between 1 to 2 bar).
-If lling and re-pressurization are required, check what
type of uid has been used initially (If in any doubt,
contact your installer).
-If frequent rells are required it is essential that you
look for any leaks.
-The frequent water supply is at risk of scaling for
the Heat exchanger and degrades performance
and longevity of it
4 2 Checking the outdoor unit
Dust off the heat exchanger if necessary, being careful
not to damage the ns.
Check that there is nothing obstructing the passage of air.
• Checking the refrigeration circuit
When the refrigerant charge is in excess of 2kg
(models > 8 kW) it is compulsory to have an approved
after sales service check the refrigeration circuit every
year (with a certicate of capacity for the handling of
refrigerants). Consult your heating technician.
LED Off:
The pump does not work, no electrical power.
Green LED on:
The pump works normally.
- 20 -
Green LED blink:
Venting operating mode (10 minutes).
Green/Red LED blink:
Operating error with automatic reboot.
Red LED blink:
Operating error.
gure 14 - Operation signals the HP circulator
Operation manual "1534 - EN"
Page 21
Air to Water Heat Pump Split system
Operation manual "1534 - EN"
- 21 -
Page 22
Air to Water Heat Pump Split system
ErP performance values
• ErP Denition
"ErP" includes two directives that are part of the program for the reduction of green house gas emission :
- Eco-design directive sets efency thresholds and prohibits the sale of any product with efciency lower than the set thresholds.
- According to labelling directive, energetic efciency shall be displayed to encourage end-users to purchase energy-efcient products.
pump
Type of temperature control (* = Outdoor sensor ;** =
Room unit)
169%169%156%155%
* class II ** class VI* class II ** class VI* class II ** class VI* class II** class VI
Bonus2%4%2%4%2%4%2%4%
Seasonal space heating energy efciency of
package under average climate
171%173%171%173%158%160%157%159%
Energy class of packageA++A++A++A++A++A++A++A++
Seasonal space heating energy efciency of
package under warmer climate
219%221%223%225%220%222%205%207%
Seasonal space heating energy efciency of
package under colder climate
The energy efciency of the package of products provided for in this che may not correspond to its actual energy efciency once installed in
a building, as the efciency is inuenced by further factors such as heat loss in the distribution system and the dimensioning of the products in
relation to building size and characteristics.
Electrical back up heater consumption is taken into account in the performance calculation.
pump
Type of temperature control (* = Outdoor sensor ;** =
Room unit)
115%115%118%113%
* classe II** classe VI* classe II** classe VI* classe II** classe VI* classe II** classe VI
Bonus2%4%2%4%2%4%2%4%
Seasonal space heating energy efciency of
package under average climate
117%119%117%119%120%122%115%117%
Energy class of packageA+A+A+A+A+A+A+A+
Seasonal space heating energy efciency of
package under warmer climate
140%142%141%143%144%146%136%138%
Seasonal space heating energy efciency of
package under colder climate
The energy efciency of the package of products provided for in this che may not correspond to its actual energy efciency once installed in
a building, as the efciency is inuenced by further factors such as heat loss in the distribution system and the dimensioning of the products in
relation to building size and characteristics.
Electrical back up heater consumption is taken into account in the performance calculation.
A
A
NA
- 22 -
Operation manual "1534 - EN"
Page 23
Air to Water Heat Pump Split system
Outdoor sensor included in the package
Controller classII
Contribution to engery efciency2%
UTW-C55XA
UTW-C58XD
Room unit references
Controller classVI
Contribution to engery efciency4%
Hydraulic unit referenceWSYG140DG6WSYG140DG6WSYK160DG9WSYK160DG9WSYK160DG9
Seasonal space heating energy efciency of
heat pump
Type of temperature control (* = Outdoor
sensor ; ** = Room unit )
151%148%154%150%149%
* classe II** classe VI* classe II** classe VI* classe II** classe VI* classe II** classe VI* classe II** classe
VI
Bonus2%4%2%4%2%4%2%4%2%4%
Seasonal space heating energy efciency of
package under average climate
153%155%150%152%156%158%152%154%151%153%
Energy class of packageA++A++A++A++A++A++A++A++A++A++
Seasonal space heating energy efciency of
package under warmer climate
Seasonal space heating energy efciency of
package under colder climate
196%198%189%191%196%198%193%195%194%196%
123%125%120%122%126%128%124%126%121%123%
The energy efciency of the package of products provided for in this che may not correspond to its actual energy efciency once installed in
a building, as the efciency is inuenced by further factors such as heat loss in the distribution system and the dimensioning of the products in
relation to building size and characteristics.
Electrical back up heater consumption is taken into account in the performance calculation.
Hydraulic unit referenceWSYG140DG6WSYG140DG6WSYK160DG9WSYK160DG9WSYK160DG9
Seasonal space heating energy efciency of
heat pump
Type of temperature control (* = Outdoor
sensor ; ** = Room unit )
109%113%112%117%117%
* classe II** classe VI* classe II** classe VI* classe II** classe VI* classe II** classe VI* classe II** classe
VI
Bonus2%4%2%4%2%4%2%4%2%4%
Seasonal space heating energy efciency of
package under average climate
111%113%115%117%114%116%119%121%119%121%
Energy class of packageA+A+A+A+A+A+A+A+A+A+
Seasonal space heating energy efciency of
package under warmer climate
Seasonal space heating energy efciency of
package under colder climate
119%121%130%132%125%127%135%137%141%143%
102%104%102%104%102%104%102%104%102%104%
The energy efciency of the package of products provided for in this che may not correspond to its actual energy efciency once installed in
a building, as the efciency is inuenced by further factors such as heat loss in the distribution system and the dimensioning of the products in
relation to building size and characteristics.
Electrical back up heater consumption is taken into account in the performance calculation.
- 24 -
Operation manual "1534 - EN"
Page 25
Air to Water Heat Pump Split system
Outdoor sensor included in the package
Controller classII
Contribution to engery efciency2%
UTW-C55XA
UTW-C58XD
Room unit references
Controller classVI
Contribution to engery efciency4%
UTW-C74TXF
UTW-C74HXF
UTW-C78XD
Operation manual "1534 - EN"
- 25 -
Page 26
Air to Water Heat Pump Split system
- 26 -
Operation manual "1534 - EN"
Page 27
Air to Water Heat Pump Split system
Operation manual "1534 - EN"
- 27 -
Page 28
Air to Water Heat Pump Split system
- 28 -
Operation manual "1534 - EN"
Page 29
Air to Water Heat Pump Split system
Operation manual "1534 - EN"
- 29 -
Page 30
Air to Water Heat Pump Split system
- 30 -
Operation manual "1534 - EN"
Page 31
Air to Water Heat Pump Split system
Operation manual "1534 - EN"
- 31 -
Page 32
This appliance is marked with this symbol. This means that electrical and electronic products shall not be mixed with general household waste.
European Community countries(*), Norway, Iceland and Liechtenstein should have a dedicated collection system for these products.
Do not try to dismantle the system yourself as this could have harmful effects on your health and on the environment.
The dismantling and treatment of refrigerant, oil and other parts must be done by a qualied installer in accordance with relevant local and national regulations.
This appliance must be treated at a specialized treatment facility for re-use, recycling and other forms of recovery and shall not be disposed of in the municipal waste stream.
Please contact the installer or local authority for more information.
* subject to the national law of each member state
Date of installation :
Contact of your heating technician or your after-sales service.
Subject to modications without notice. Non contractual document.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.