For professionals. To be kept by the user for future reference
EN
Page 2
■ Installation and maintenance rules
The appliance must be installed and maintained
by an approved professional in accordance with
current regulations and codes of practice.
• Warning, hydraulic unit should not be installed
in an air current.
■ Handling
The outdoor unit must not be placed in a horizontal
position during transport.
If not kept upright during transport, the appliance
could be damaged through displacement of
the refrigerant and damage to the compressor
suspension.
Any damage caused by transportation in a horizontal
position is not covered by the warranty.
If necessary, the outdoor unit may be tilted only
during manual handling (to go through a door or up
a staircase). This operation must be conducted very
carefully and the appliance must be immediately
restored to the upright position.
■ Containment of refrigeration circuits
All refrigeration circuits are sensitive to contamination
from dust and moisture. If such pollutants penetrate
the refrigeration circuit, they can aect the reliability
of the heat pump.
Make sure that the connections and refrigeration
circuits (hydraulic unit, outdoor unit) are
protected correctly.
In the event of a subsequent failure and following
an inspection, the presence of moisture or
foreign bodies in the compressor oil would
automatically void the warranty.
- Check upon receipt that the ttings and refrigeration
circuit caps mounted on hydraulic unit and outdoor
unit are properly seated and secured (cannot be
loosened with bare hands). If this is not the case,
tighten them using a C spanner.
- Check also that the refrigeration connections are
sealed (plastic caps or tubes crimped at the ends
and brazed). If the caps must be removed during
the installation (tubes to be re-cut for example),
put them back as soon as possible.
■ Hydraulic connections
The connection must comply with industry standard
practice according to current regulations.
Remember: Seal everything when tting in
accordance with industry standard practice for
plumbing work:
- Use suitable seals (bre gasket, O-ring).
- Use Teon or hemp tape.
- Use sealing paste (synthetic depending on the
case).
Use glycol/water mix if the minimum ow
temperature is set below 10°C. If you are using a
glycol/water mix, arrange for an annual check on the
quality of the glycol. Use monopropylene glycol only.
The recommended concentration is 30% minimum.
Never use monoethylene glycol.
• In some installations, the presence of dierent
metals can cause corrosion problems; the
formation of metal particles and sludge can
appear in the hydraulic circuit.
• In this case, it is advisable to use a corrosion
inhibitor in the proportions indicated by the
manufacturer.
• You must also ensure that treated water does
not become corrosive.
Page 3
■ Electrical connections
2
1
3
• Before any maintenance operation, ensure
that the general power supply is switched o.
• Specications of electricity supply
The electrical installation must be carried out in
accordance with prevailing rules.
Electrical connections will only be made once all
other installation operations (fastening, assembly,
etc.) have been completed.
Warning!
The contract signed with the energy provider must
be sucient not only to cover the heat pump's power
requirements but also the combined sum of all the
appliances likely to be operating at the same time. If
the power is too low, check the power rating stated
in your contract with your energy provider.
Never use a power socket for the power supply.
The heat pump must be supplied directly with power
(without external switch) by special protected leads
from the electric panel via dedicated bipolar circuit
breakers, C curve for the outdoor unit, C curve for
the electrical heating and domestic water backups
(see tables page 35).
The electrical installation must be tted with a 30mA
RCD.
This appliance is designed to operate using a
nominal voltage of 230 V or 400 V, +/- 10%, 50 Hz
(depending on model).
• General remarks on electrical connections
It is essential to maintain neutral-phase polarity
when making electrical connections.
Rigid wires are preferable for xed installations,
particularly in a building.
Tighten the cables using the cable glands to prevent
the feed wires from being accidentally disconnected.
The earth connection and its continuity must be
ensured.
• Cable glands
To ensure the stability of power (Low Voltage) and
sensor (Extra-Low Voltage) cables, it is essential
that the cable glands are tightened according to the
following recommendations:
Size of cable
gland (PE)
(mm)
PG71 to 51.31
PG91.5 to 63.32.6
PG165 to 124.32.6
Diameter of
cable
(mm)
Cable gland
tightening
torque
(check-nut)
(N.m)
Coupling net
tightening
torque
(N.m)
• Connecting to screw terminals
The use of ring, spade or blade terminals or
caps is prohibited.
- Always select wire that complies with current
standards.
- Bare the end of the wire to around 25 mm.
- With round end pliers, form a loop with a diameter
which matches the tightening screws on the
terminal.
- Tighten the terminal screw rmly onto the
loop created. Insucient tightening can cause
overheating, leading to breakdown or even re.
Rigid wires
25 mm
Loop
Lug on
exible wires
prohibited
Screw and special
washer
Terminal
• Connecting to controller boards
- Remove the corresponding connector and make
the connection.
• 1 package : Hydraulic unit and outside temperature
sensor.
Unpacking and supplies
►
While the courier is still present, carefully check the
general appearance of the appliances and check
that the outdoor unit has not been laid in a horizontal
position.
In the event of a dispute, send any relevant reservations
to the carrier in writing within 48 hours and send a copy
of the letter to Customer Services.
Packing contents list
Heat PumpOutdoor unitHydraulic unit
ModelReferenceCode
Waterstage SHP 16WOYG160LJLWSYG160DJ6
Waterstage SHP TRI 15WOYK150LJL
Waterstage SHP TRI 17WOYK170LJL
Denitions
►
- Split: The heat pump consists of two elements
(an outdoor unit to be installed outdoors and a hydraulic
unit to be installed inside the dwelling).
- Air/water: The surrounding air is the energy source.
This energy is transmitted to the heating circuit water
by the heat pump.
- Inverter: The fan and compressor speeds are
modulated according to the heating requirements.
This technology enables you to save on energy and
operate on a single-phase power supply, whatever
the heat pump's output, by avoiding pulling signicant
amounts of current at start-up.
- COP (Coecient of Performance): This is the
relationship between the energy transmitted to the
heating circuit and consumed electrical energy.
The heat pump transmits the energy contained in the
surrounding air into the dwelling to be heated.
The heat pump consists of four main elements, in which
a refrigerant (R410A) circulates.
- In the evaporator (ref. 13, g. 8, page 12):
The calories are taken from the outside air and
transmitted to the refrigerant. Because it has a low
boiling point, it changes from a liquid to a vapour, even
in cold weather (down to -25°C outside temperature).
- In the compressor (ref. 10, g. 8, page 12):
The vaporised refrigerant is pressurised and takes on
even more calories.
- In the condenser (ref. 14, g. 9, page 13):
The energy of the refrigerant is transmitted to the
heating circuit. The refrigerant returns to its liquid state.
- In the expansion valve (ref. 9, g. 8, page 12):
The liqueed refrigerant is returned to a low pressure
and regains its initial temperature and pressure.
The heat pump is equipped with a controller which
controls the room temperature based on the outdoor
temperature measurement. The room thermostat
(option) provides a corrective action for the temperature
control.
The hydraulic unit is tted with an electrical backup or
boiler connection which intervenes to provide additional
heat during the coldest periods.
• Control functions
- The heating circuit's ow temperature is controlled by
the temperature control.
- Depending on the heating ow temperature,
the outdoor unit's power is modulated by the "Inverter"
compressor.
- Control of the backup electrical heating.
- The daily timer program is used to set the periods
where the ambient temperature is comfortable or
reduced.
- Summer/winter time mode switchover is automatic.
- Management of the boiler backup*.
- Room sensor*: The room sensor provides a corrective
action for the temperature control.
- Control of a second heating circuit*.
- Domestic hot water*: Heating timer program.
- Managing cooling*.
* Where the heat pump is tted with options and associated kits.
• Protective functions
- Anti-legionella cycle for domestic hot water.
- Frost protection: Frost protection cuts in if the heating
circuit's ow temperature falls below 5°C (provided
that the heat pump's electrical power supply is not
interrupted).
Dwelling heat loss (kW)
8
7
6
Backup
5
4
3
HP power
Heat Pump
2
1
0
-20 -15 -10-50510152025
HP +
electrical
backup
Outdoor temperature (°C)
Max
authorised HP
start-up temp.
HP only
46
Water return temperature (°C)
Outdoor temperature (°C)
g. 10 - Examples and operating limits
- 14 -
Waterstage / Installation / 2011 - EN
Page 15
• Domestic hot water (DHW) operating principle
Two domestic hot water (DHW) temperatures can be
set: comfort and reduced.
The default DHW program is set to the comfort
temperature between 00:00 and 05:00 and between
14:30 and 17:00 and to the reduced temperature for the
rest of the day. This optimises electrical consumption
while ensuring comfortable heating and water
temperatures.
The reduced temperature setpoint may be useful to
avoid restarting the DHW too often and for too long
during the day.
The production of domestic hot water (DHW) is started
when the temperature in the tank drops to 7°C below
the temperature setpoint.
The heat pump produces the domestic hot water, which
is then additionally heated, if required, by the tank's
electrical backup or by the boiler. To ensure a DHW
setpoint over 55°C, the electrical backup heating must
be left on.
Depending on the setting, the comfort temperature can
be reached 24h/day or only at night or following the
DHW program.
If the contract signed with the energy provider includes
a day/night tari, the electrical backup is subject to the
supplier’s power tari and the comfort temperature may
only be reached at night.
If no particular contract has been signed, the comfort
temperature can be reached at any time, including
during the day.
The production of DHW takes priority over heating;
nevertheless the production of DHW is managed
by cycles that regulate the amount of time assigned
to heating and production of DHW in the event of
simultaneous demand.
Bend the pipes into position and make holes
for them through the oor or walls either with
their protective caps in place or after brazing.
Keep the protective caps in place or ends
brazed until the appliance is commissioned.
The outdoor unit must be connected to the hydraulic unit
only with brand new separately insulated copper
connections (refrigerant quality).
Maintain the same pipe diameters (g. 19).
Observe the maximum and minimum distances
between the hydraulic unit and the outdoor unit
(g. 19, page 24); the guarantee of performance and
the service lifespan of the system depend on this.
The minimum length of the refrigeration
connections for correct operation is 5 m.
The appliance's warranty will be void if it is operated
with refrigeration connections less than 5 m long
(tolerance +/- 10%).
If the refrigeration connections are exposed to
weathering or UV radiation and the insulation is not
resistant, protection must be provided.
g. 12 - Example of recommendation for layout of
refrigeration connections
- 16 -
Waterstage / Installation / 2011 - EN
Page 17
Page 18
D
Installation of the outdoor unit
►
Installation precautions
▼
The outdoor unit must only be installed
outside. If a shelter is required, it must have
broad openings on all 4 sides and installation
clearances must be observed.
• Choose the location of the appliance after discussion
with the client.
• We recommend choosing a site that is sunny but
sheltered from strong cold prevailing winds.
• The unit must be easily accessible for future installation
and maintenance work (page 20).
• Ensure that connections to the hydraulic unit can be
made easily.
• The outdoor unit is able to withstand bad weather but
avoid installing it in a position where it is likely to be
exposed to signicant dirt or owing water (under a
defective gutter for example).
• Water may ow out of the outdoor unit when it is
operating. Do not install the unit on a paved terrace;
choose a well-drained location (e.g. gravel or sand).
If installation is carried out in an area where the
temperature stays below 0°C for long periods, check
that the presence of ice does not present any danger.
A drainage pipe can also be connected to the outdoor
unit (see g. 14).
• Nothing should obstruct the air circulation through the
evaporator and out from the fan (g. 13).
• Keep the outdoor unit away from heat sources and
ammable products.
• Make sure that the unit does not disturb the
surrounding area or inhabitants (noise level, draught,
low temperature of the ejected air freezing the plants
in its path).
A ≥ 80 mm
B ≥ 100 mm
C ≥ 200 mm
D ≥ 300 mm
E ≥ 500 mm
F ≥ 600 mm
G ≥ 1000 mm
H ≥ 1500 mm
J ≥ 2000 mm
K ≥ 3000 mm
A
B
D
BB
E
H
G
B
G
G
B
A
B
B
B
D
B
B
H
B
B
D
E
E
H
B
J
F
G
g. 13 - Minimum installation clearances around the outdoor unit (all models)
- 18 -
B
B
H
B
B
H
E
B
B
E
Waterstage / Installation / 2011 - EN
H
K
F
Page 19
• The surface on which the appliance is installed must:
- Be permeable (soil, gravel, etc.).
- Support its weight easily.
- Allow a solid fastening base,
- Not transmit any vibration to the dwelling. Anti-vibratory
blocks are available as an option.
• The wall bracket cannot be used where it is likely to
transmit vibrations. Installing the unit on the ground is
preferred.
Positioning Outdoor Unit
▼
The outdoor unit must be raised at least 50 mm above
ground level. In areas prone to snow, this height should
be increased but should not exceed 1.5 m (gure 12).
- Fasten the outdoor unit by means of screws and
rubber tightening or toothed lock washers to prevent
them from coming loose.
H
In areas with heavy snowfall, if the intake and
outlet of the outdoor unit is blocked with snow,
heating may become dicult and a failure is
likely to occur.
Construct a canopy or place the unit on a high stand
(local conguration).
- Place the unit on a solid stand in order to minimise
impacts and vibrations.
- Do not place the unit directly on the ground as this will
cause problems.
Condensate drain pipe
▼
The outdoor unit can generate a large volume
of water (called condensate).
If the use of a drain pipe is necessary:
- Use the elbow provided (C) and connect a 16 mmdiameter hose for draining the condensate.
- Use the plug(s) provided (B) to block the opening of
the condensate drain pan.
Allow for the condensate to ow away under the force of
gravity (waste water, rain water, gravel bed).
If installation is carried out in an area where the
temperature stays below 0°C for long periods,
equip the drain pipe with trace heating to
avoid it icing up. Trace heating must heat not
only the drain pipe but also the bottom of the
appliance's condensate collection tank.
* In areas with heavy snowfall,
(H) must be higher than the average snow layer.
Air
Waterstage / Installation / 2011 - EN
B
4 holes
B
g. 14 - Installation of the outdoor unit evacuation of
condensates
C
(ø 12 mm)
B
- 19 -
Page 20
Installation of the hydraulic unit
►
Installation precautions
▼
• Choose the location of the appliance after discussion
with the client.
• The installation space should comply with current
regulations.
• To facilitate maintenance and allow access to the
various parts, we recommend that you provide
sucient space all the way around the hydraulic unit.
350 mm
mini
300 mm
mini
1000 mm
- If the refrigeration connection is only performed at the
end of the installation, make sure that the refrigeration
circuit caps* remain in place and tight throughout the
installation.
* (Hydraulic unit side and outdoor unit side).
- After each maintenance operation on the refrigeration
circuit and before the nal connection, take care to
put the caps back in position to avoid any pollution
of the refrigeration circuit (sealing with adhesive is
prohibited).
Positioning the hydraulic unit
▼
- Fix the bracket S securely (4 screws and plugs) to a
strong, at wall (not a light partition) ensuring that it is
correctly levelled.
350 mm
min.
mini
538 mm
min.
mini
• In accordance with EN 378-1 -2017 standard
(Refrigerating systems and heat pumps - Safety and
environmental requirements), the system's hydraulic
unit and all refrigeration connections passing through
inhabited areas must comply with the minimum room
volume requirements shown hereafter.
The minimum volume of a room (in m3) is calculated
using the formula: "uid ll load" (in kg) / 0.39.
Alternatively, you must ensure that
- The location has natural ventilation through another
room where the combined volume of the two rooms
is greater than "liquid ll load" (in kg) / 0.39 kg/m³.
The opening between the two rooms must have a door
clearance of at least 1 cm.
- Or that the location is mechanically ventilated.
Be careful not to bring ammable gas
near the heat pump during installation,
in particular when brazing is required.
The appliances are not reproof and should
not therefore be installed in an explosive
environment.
- To avoid condensation inside the condenser, remove
the refrigeration circuit caps only when making the refrigeration connections.
300 mm
mini
min.
118 mm
188 mm
418 mm
min.
mini
(S)
g. 15 - Mounting bracket
- Hook the appliance onto its bracket S.
Weight of the appliance (full of water) = 58Kg
- 20 -
Waterstage / Installation / 2011 - EN
Page 21
10
9
19
C
7
7
C
C
C
6
5
B
B
(S)
4
3
2
1
A
A
TX20
8
19
TX20
g. 16 - Removing the casing
Waterstage / Installation / 2011 - EN
D
12
11
D
TX20
D
11
- 21 -
Page 22
Refrigeration connections
This appliance uses refrigerant R410A.
Comply with the legislation on handling of refrigerants.
Rules and precautions
►
Connections must be made on the same day
the installation is lled with gas (see para.
"Filling the installation with gas", page 26).
• Minimum tools required
- Set of pressure gauges (Manifold) with hoses
exclusively designed for HFCs (Hydrouorocarbons).
- Vacuum gauge with isolation valves.
- Vacuum pump specically for HFCs (using a standard
vacuum pump is allowed if, and only if, it is tted with
Using tools that have been in contact with
HCFCs (R22 for example) or CFCs is prohibited.
The manufacturer declines any liability with
regard to the warranty if the above instructions
are not observed.
• Flared connections
Lubricating with mineral oil (for R12, R22)
is prohibited.
- Lubricate only with polyolester oil (POE). If POE is not
available, t without lubrication
Coat the ared surface
with POE refrigeration oil.
Do not use mineral oil.
described above, condensation will form on the
surface of the insulation material. Lastly, use insulating
sleeves whose thermal conductivity will be less than
or equal to 0.045 W/mK if the temperature is equal to
20°C. The insulation must be impermeable in order to
withstand the passage of vapour during the defrosting
cycles (glass wool is prohibited).
Shaping the refrigeration pipes
►
Bending
▼
The refrigeration pipes must be shaped only on a
bending machine or with a bending spring in order to
avoid any risk of crushing or breaking them.
Remove the insulation material from the section of
pipe to be bent.
Do not bend copper to an angle greater than 90°.
Never bend pipes more than 3 times in the
same place otherwise traces of fracturing may
appear (hardening of the metal).
Creating the arings
▼
- Cut the pipe to an appropriate length with a pipe-cutter
without damaging it.
- Carefully deburr it, holding the pipe pointing downward
to avoid introducing lings into the pipe.
- Remove the ared connection nut situated on the
valve to be connected and slide the pipe into the nut.
- Proceed to are it, letting the pipe protrude out of the
aring tool's tube.
- After aring, check the state of the working radius (L).
This must not present any scratches or signs of
fracturing. Also check the dimension (B).
• Brazing the refrigeration circuit (if necessary)
- Silver brazing (40% minimum recommended).
- Brazing only with dry nitrogen internal ux.
• Other remarks
- After each maintenance operation on the refrigeration
circuit and before nal connection, take care to put
the caps back in position to avoid any pollution of the
refrigeration circuit.
- To eliminate any lings getting into the pipes, use dry
nitrogen to avoid introducing any humidity that may
adversely aect the appliance's operation. In general,
take every precaution to avoid humidity penetrating
into the appliance.
- Proceed with thermal insulation of the gas and liquid
pipes to avoid any condensation. Use pipe insulators
resistant to temperatures over 90°C. In addition, if the
humidity level in areas where the refrigerant pipes are
installed is expected to exceed 70%, protect the pipes
with pipe insulators. Use an insulating material thicker
than 15mm if the humidity level reaches 70 ~ 80%,
and an insulating material thicker than 20mm if
the humidity exceeds 80%. If the recommended
thicknesses are not observed under the conditions
- 22 -
B
-0.4
L
C
C
Flaring tool
Pipe
Dimensions in mm
Pipe ø
LB 0/
9.52 (3/8")2.5 to 2.713.222
15.88 (5/8")2.9 to 3.119.729
g. 17 - Flaring of the ared connections
Waterstage / Installation / 2011 - EN
Nut
are
Page 23
■ Outdoor unit
FrontSideLower
■ Hydraulic unit
Sortie dessousSortie avantSortie latérale
g. 18 - Feeding through ared connections
Waterstage / Installation / 2011 - EN
- 23 -
Page 24
HP modelWaterstage SHP
gasliquid
Outside unit connections5/8"3/8"
Diameter(D1) 5/8"(D2) 3/8"
Refrigeration
connections
Maximum Height Difference
Hydraulic unit connections5/8"3/8"
1 Without additional lling of R410A.
2 Taking into account a possible additional ll of refrigerant R410A (see "Additional lling", page 28).
3 Outdoor unit over hydraulic unit and heating only / Other cases.
Minimum length (L)5
Maximum length 1 (L)15
Maximum length 2 (L)30
2/3
(D)25 / 15
Hydraulic
unit
Outdoor unit
Heat Pump
Hydraulic
Heat
Pump
mini
mini
min.
5m
5m
unit
DL
DL
"Liquid” valve
“Gas” valve
"Liquid" refrigerant
connection
D2 diameter
Flared nut
Flared nut
Flared nut
Flared nut
Outdoor unit
"Gas" refrigerant
connection
D1 diameter
g. 19 - Refrigeration connections (authorised diameters and lengths)
- 24 -
Waterstage / Installation / 2011 - EN
Page 25
Checks and connection
►
The refrigeration circuit is very sensitive
to dust and humidity: check that the area
around the connection is clean and dry before
removing the plugs protecting the refrigeration
connectors.
Indicated blowing value: 6 bar for minimum
30 seconds for connection of 20 m.
Checking the gas connection (large diameter).
Connect the gas connection to the outdoor unit.
Blow dry nitrogen into the gas connection and inspect
its end:
- If water or impurities emerge, use a brand new
refrigeration connection.
Otherwise, proceed with aring and connect the
refrigeration connection to the outdoor unit immediately.
Checking the liquid connection (small diameter).
Connect the liquid connection to the hydraulic unit.
Blow nitrogen into the gas-condenser-liquid
connection system and inspect its end (outdoor unit side).
- If water or impurities emerge, use a brand new
refrigeration connection.
- Otherwise, proceed with aring and connect the
refrigeration connection to the outdoor unit immediately.
UE
1
Azote
Nitrogen
2
Azote
Nitrogen
3
Azote
Nitrogen
g. 21 - Checking refrigeration connections
OU
UE
OU
UE
OU
Gas
Liaison
connection
gaz
Liaison
Gas
connection
gaz
gaz
Gas
Liaison
Liquid
connection
liquide
MH*
HIU
MH*
HIU
Take particular care to position the tube
opposite its connector so as not to risk
damaging the threads. A properly aligned
connector can be attached easily by hand
without much force being required.
- Remove the plugs from the pipes and the refrigeration
connections.
- Warning! Avoid positioning the gas pipe in front of the
pump.
- Comply with the indicated tightening torques.
Holding spanner
Torque wrench
DesignationTightening torque
Flared nut 9.52 mm (3/8")32 to 42 Nm
Flared nut 15.88 mm (5/8")63 to 77 Nm
Plug (A) 3/8"20 to 25 Nm
Plug (A) 5/8"30 to 35 Nm
Plug (B) 3/8", 5/8"10 to 12 Nm
Plug (A) and (B) : see g. 22, page 27.
g. 20 - Tightening torques
Waterstage / Installation / 2011 - EN
- 25 -
Page 26
Filling the installation with gas
Jeu de manomètres
►
This operation is reserved for installers familiar with the legislation for handling refrigerants.
Creating a vacuum with a calibrated vacuum pump is essential (see APPENDIX 1).
Never use equipment used previously with any refrigerant other than a HFC.
Only remove the refrigeration circuit caps when performing the refrigeration connections.
If the outdoor temperature is below +10°C:
- You must use the triple evacuation method
(see APPENDIX 2).
APPENDIX 2
Triple Evacuation Method
- We recommend installing a dehydrator lter
(and this is highly recommended if the outdoor
temperature is below +5°C).
- Connect the Manifold high-pressure hose to the
lling hole (gas connection). A valve must be tted
to the vacuum pump's hose so you can shut it o.
a) Create a vacuum until the desired value is
reached and maintain this value for 30 mins
(see table in APPENDIX 1),
Set of pressure gauges
(Manifold)
(Manifold)
APPENDIX 1
Method for calibrating and checking a vacuum
pump
- Check the vacuum pump's oil level.
- Connect the vacuum pump
to the vacuum gauge as
shown in the diagram.
Flexible
Plugged
hose
bouché
- Pump down for 3 minutes.
- After 3 minutes, the pump
reaches its threshold vacuum limit and the vacuum
gauge's needle stops moving.
- Compare the obtained pressure value against the
table of values. Depending on the temperature, this
pressure should be lower than that shown in the
table.
=> If this is not the case, replace the gasket, hose
or pump.
T °C5°C<T<10°C10°C<T<15°C15°C < T
Pmax
- bar
- mbar
0.009
9
0.015
15
Vacuum
gauge
Vacuomètre
Pompe
Vacuum
pump
à vide
0.020
20
Low
Basse
pression
Pressure
Lo
Hi
Haute
Pressure
pression
High
UE
OU
Connection
Liaison...
Liquid
liquidegaz
Gas
MH
HIU
Vacuum
Vacuomètre
Gauge
Vacuum pump
Pompe à vide
b) Switch o the vacuum pump, close the valve at
the end of the service hose (yellow), connect this
hose to the expansion valve on the nitrogen bottle,
ll to 2 bar, close the hose's valve again,
Nitrogen
Hi
Haute
Pressure
pression
High
UE
OU
Connection
Liaison...
Liquid
liquide
Gas
gaz
MH
HIU
Lo
Azote
c) Connect this hose to the vacuum pump again,
switch it on and slowly open the hose's valve.
Lo
Hi
Haute
Pressure
pression
High
UE
OU
Connection
Liaison...
Liquid
liquide
gaz
Gas
MH
HIU
d) Repeat this operation at least three times.
Remember: performing these operations using
refrigerant is strictly prohibited.
- 26 -
Waterstage / Installation / 2011 - EN
Page 27
Seal test
▼
- Remove the protective plug (B) from the lling hole
(Schrader) in the gas valve (large diameter).
- Connect the high pressure hose from the Manifold to
the lling hole (g. 22).
- Connect the nitrogen bottle to the Manifold (only use
dehydrated nitrogen type U).
- Fill the refrigeration circuit with nitrogen to maximum
10 bar (gas-condenser-liquid connection system).
- Maintain this pressure in the circuit for 30 minutes.
Nitrogen
Hi
High
Haute
Pressure
Lo
pression
Liaison...
Connection
UE
OU
Liquid
liquide
Gas
gaz
MH
HIU
Azote
Max 10 bar
10 bars max.
Min 30 mins
30 mn mini
- If a pressure drop occurs, bring it back down to 1 bar
and look for leaks with a leak detector, repair and
repeat the test.
Lo
Hi
High
Haute
Pressure
pression
UE
OU
Liaison...
liquide
gaz
Vanne fermée,
Contrôle pression
Seal test
Contrôle d’étanchéité
MH
HIU
Valve closed
Creating a vacuum
▼
The triple evacuation method (APPENDIX 2)
is strongly recommended for any installation
and especially when the outdoor temperature
is below 10°C.
- If necessary, calibrate the Manifold pressure gauge(s)
to 0 bar. Adjust the vacuum gauge to current
atmospheric pressure (≈ 1013 mbar).
- Connect the vacuum pump to the Manifold. Connect
a vacuum gauge if the vacuum pump is not equipped
with one.
Lo
Hi
Haute
Pressure
pression
High
UE
OU
Connection
Liaison...
Liquid
liquide
Gas
gaz
MH
HIU
Vacuum
Vacuomètre
Gauge
Vacuum pump
Pompe à vide
- Create a vacuum until the residual pressure* in the
circuit falls below the value given in the following
table (* measured with the vacuum gauge).
T °C5°C<T<10°C10°C<T<15°C15°C < T
Pmax
- bar
- mbar
0.009
9
0.015
15
0.020
20
- Let the pump continue to operate for another 30
minutes minimum after reaching the required vacuum.
- Close the Manifold valve, then stop the vacuum pump
without disconnecting any of the hoses in place.
- Once the pressure is steady and there are no leaks,
empty the nitrogen by leaving the pressure above
atmospheric pressure (between 0.2 and 0.4 bar).
Refrigeration connection
Liaisonfrigorifique (gaz)
(gas)
Bouchon(A)
Vanne3voies
3-way valve
High-pressure hose (red)
Flexible haute pression (rouge)
Allen (hex) key (4 mm)
Clé hexagonale/Allen
Filling hole
Orificedecharge
Plug (B)
Bouchon(B)
Plug (A)
(4mm)
g. 22 - Connecting the hose to the gas valve
Waterstage / Installation / 2011 - EN
- 27 -
Page 28
Filling with gas
▼
Additional lling
▼
If additional lling is required, do it before
lling the hydraulic unit with gas. Refer to
paragraph "Additional lling", page 28.
- Remove the access plugs (A) from the valve controls.
- First of all fully open the liquid valve (small) and
then the gas valve (large) using an Allen (hex) key
(anti-clockwise direction) without using excessive
force against the stop.
- Quickly disconnect the hose from the Manifold.
- Ret the 2 original caps (be sure they are clean) and
tighten them to the recommended tightening torque
indicated in the table g. 20, page 25. A seal is
achieved in the caps only with metal to metal.
The outdoor unit does not contain any additional
refrigerant allowing the installation to be bled.
Bleeding by ushing is strictly forbidden.
Final sealing test
▼
The sealing test must be carried out using a certied
gas detector (sensitivity of 5g/year).
Once the refrigeration circuit has been gassed as
described above, check that all the refrigeration
connectors are gas-tight (4 connectors). If the arings
have been made correctly, there should be no leaks.
If necessary, check the seal of the refrigeration valve
caps.
If the event of a leak:
- Return the gas to the outdoor unit (pump down).
The pressure should not drop below atmospheric
pressure (0 relative bar read on the Manifold) so as not
to contaminate the recovered gas with air or moisture.
- Redo the connection,
- Restart the commissioning procedure.
50 g of R410A
for every additional 1 metre
Length of the
connections
Additional loadNone750 g
The amount needed to ll the outdoor units corresponds
to the maximum distances between the outdoor unit
and the hydraulic unit as dened here page 24. If the
distances are greater, an additional amount of R410A
is required. For each type of appliance, this additional
amount depends on the distance between the outdoor
unit and the hydraulic unit. Any additional lling with
R410A must be carried out by an approved specialist.
• Example of additional ll:
An outdoor unit which is 17 m away from the hydraulic
unit will require an additional ll of:
Additional ll = (17 - 15) x 50 = 100 g
Filling must be carried out after creating a vacuum and
before gassing the hydraulic unit, as follows:
- Disconnect the vacuum pump (yellow hose) and
connect a bottle of R410A in its place in the uid
extraction position.
- Open the bottle’s valve.
- Bleed the yellow hose by loosening it slightly on the
Manifold side.
- Place the bottle on scales with a minimum accuracy of
10g. Note the weight.
- Carefully open the blue valve slightly and check the
value shown on the scales.
- As soon as the value displayed has dropped by the
value for the calculated additional ll amount, close the
bottle and disconnect it.
- Quickly disconnect the hose connected to the
appliance.
- Proceed to ll the hydraulic unit with gas.
15 m30 m max.
Only use R410A !
Only use tools suitable for R410A
(set of pressure gauges).
Always ll in the liquid phase.
Never exceed the maximum length or
dierence in level.
Gas
R410A
Liquid
g. 23 - Gas bottle R410A
- 28 -
Waterstage / Installation / 2011 - EN
Page 29
Recovering the refrigerant in the outdoor unit
▼
Before performing any maintenance, make sure that all power supplies have been cut o.
Stored energy: after cutting o the power supplies,
wait for 1 minute before accessing the internal parts of the equipment.
Perform the following procedures to collect the
refrigerant.
- 1- Switch the start/stop switch to the 0 position
(mark 3, g. 9, page 13). Disconnect the outdoor
unit's power supply.
- 2- Remove the front panel. Open the power control
box. Then turn ON the DIP SW1 on the interface
board,
- 3- Reconnect the power supply. Switch
the start/stop switch to position 1.
(The green and red LEDs start ashing; 1s on / 1s o).
The outdoor unit begins cooling operation about
3 minutes after being switched on.
- 4- The circulation pump starts.
- 5- Close the liquid valve on the outdoor unit maximum
30 secs after the outdoor unit starts.
- 6- Close the gas valve on the outdoor unit when
the pressure is below 0.02 relative bar read on the
Manifold, or 1-2 minutes after the liquid valve has been
closed, while the outdoor unit continues to operate.
- 7- Disconnect the power supply.
- 8- Recovery of the refrigerant is complete.
Notes:
- The pump down operation cannot be activated even
if DIP SW1 is set to ON while the heat pump is in
operation.
- Do not forget to switch DIP SW1 back to OFF after
the pump down operation has been completed.
- Select the heating mode.
- If the pump down operation fails, try the
operation again by turning the machine o and
opening the "liquid" and "gas" valves. Then after
2-3 minutes, restart the pump down operation.
Waterstage / Installation / 2011 - EN
DIP SW
LED2
(Green)
LED1
(Red)
ON
Interface Board
g. 24 - Location of DIP switches and LEDs on the
hydraulic unit interface board
- 29 -
Page 30
Hydraulic connections
Connecting the hydraulic unit to the heating circuit
►
Flushing the installation
▼
Before connecting the hydraulic unit to the installation,
rinse out the heating system correctly to eliminate
any particles that may aect the appliance's correct
operation.
Do not use solvents or aromatic hydrocarbons (petrol,
paran, etc.).
In the case of an old installation, provide a suciently
large decanting pot with a drain on the return from the
boiler and at the lowest point in the system in order to
collect and remove any impurities.
Add an alkaline product and a dispersant to the water.
Flush the installation several times before proceeding
to the nal lling.
Connections
▼
The heating circulation pump is built into the hydraulic
unit.
Connect the central heating pipes to the hydraulic unit
correctly according to the direction of circulation.
The pipe between the hydraulic unit and the heat
collector must be at least one inch in diameter
(26x34 mm).
Calculate the diameter of the pipes based on ow rates
and lengths of the hydraulic systems.
Tightening torque: 15 to 35 Nm.
Use union connectors to make it easier to remove the
hydraulic unit.
Try to use connection hoses to avoid transmitting noise
and vibrations to the building.
Connect the drains from the drain valve and the safety
valve to the main sewer system.
Verify that the expansion system is correctly connected.
Check the expansion vessel pressure (pre-inated to 1
bar) and the safety valve is calibrated.
The ow rate of the installation must be at least equal
to the minimum value mentioned in the specications
table "General characteristics", page 7.
The installation of a regulator (other than those included
in our congurations) which reduces or stops the ow
through the hydraulic unit is prohibited.
- 30 -
Waterstage / Installation / 2011 - EN
Page 31
Volume of the heating system
▼
You must maintain the minimum installation water
volume. Install a buer tank on the return from the
heating circuit in case the volume is lower than this
value. Where the system is tted with one or more
thermostatic valves, you must ensure that this minimum
water volume is able to circulate.
Min. volume in litres PER CIRCUIT (excl. HP)
Appliance
Waterstage SHP 161109855
Waterstage SHP TRI 151029050
Waterstage SHP TRI 1711910660
Filling and bleeding the installation
►
Check the pipe xings, tightness of the connectors and
the stability of the hydraulic unit.
Check the direction in which the water is circulating and
that all the valves are open.
Proceed to ll the installation.
Do not operate the circulation pump during lling. Open
all the drain valves in the installation and the bleeder
valve on the hydraulic unit to expel the air contained in
the pipes.
Close the drain valves and add water until the pressure
in the hydraulic circuit reaches 1 bar.
Check that the hydraulic circuit has been bled correctly.
Check there are no leaks.
After the " Commissioning", page 44, and once the
machine has started, bleed the hydraulic unit again.
Mandatory
Fan-coil
Recommendation
Radiators
Recommendation
Heating-cooling oor
Precise lling pressure is determined by the
water pressure in the installation.
P
g. 25 - Hydraulic unit automatic bleeder valve
Waterstage / Installation / 2011 - EN
- 31 -
Page 32
Heating circulation pump speed settings
►
mCE
1 mbar=10 mmCE=100 Pa
8
7
6
5
4
88
77
3
55
2
1
1
3
0
00,511,52
mCE
1
1 mbar=10 mmCE=100 Pa
8
7
6
88
5
77
Variable pressure
The circulation pump varies the water
pressure depending on the ow rate.
Recommended for an installation tted with
radiators (particularly any system with
thermostatic valves or zone solenoids).
Ne pas utiliser cette zone
Do not use these zones
3
3
/h
1,520,50
m
m/h
4
3
3
55
2
1
1
0
00,511,52
1
1,520,50
g. 26 - Available hydraulic pressures and ow rates
LED O:
The circulation pump is not working, no power supply.
Green LED On:
The circulation pump is operating normally.
Green LED ashing:
Venting mode in operation (10 minutes).
m
Constant pressure
The circulation pump maintains a constant
water pressure whatever the ow rate.
Recommended for an installation with
constant pressure drops such as an underoor heating system.
3
3
/h
m/h
g. 27 - Operating signals of the HP circulation pump
- 32 -
Red/green LED ashing:
Operating error with automatic restart.
Red LED ashing:
Operating error.
Waterstage / Installation / 2011 - EN
Page 33
Variable pressure
Pression variable
Gas venting
Dégazage
Constant pressure
Pression constate
Circulation pump fouled or stuck:
If the motor becomes stuck, a start-up cycle is launched.
If the motor remains stuck, it will be permanently
stopped.
Cut o the power supply to the circulation pump for
30 secs in order to free it and allow a new start-up
cycle to begin.
g. 28 - Circulation pump control button
Waterstage / Installation / 2011 - EN
- 33 -
Page 34
Electrical connections
Before any maintenance operation,
ensure that the general power supply is switched o.
Electrical installation must be performed in accordance with current regulations.
The electrical diagram for the hydraulic unit is shown on g. 43, page 72.
Wireless remote control (option)
Outside sensor
Cable 2 x 0.75 mm²
Interconnection between
outdoor unit and hydraulic unit
Wireless room thermostat (option)
Remote control (option)
Phase, Neutral, Earth, Communication bus)
Cable 4 G 1.5 mm²
Room thermostat (option)
OK
ESC
2
3
1
4
0
bar
Electrical backup power supply
(see table below)
General power supply
(see table below)
g. 29 - Overall layout of electrical connections for a simple installation (1 heating circuit)
or
or
Cable 2 x 0.5 mm²
or
Cable 2 x 0.5 mm²
Electrical
Board
- 34 -
Waterstage / Installation / 2011 - EN
Page 35
Cable dimensions and protection rating
►
These cable dimensions are provided for information purposes only and do not exempt the installer from checking
that these dimensions match requirements and comply with current standards.
• Outdoor Unit Power Supply
Single phase heat pumpElectricity supply 230 V - 50 Hz
Model
Waterstage SHP 166300 W3 G 6 mm²32 A
3 phase heat pumpElectricity supply 400 V - 50 Hz
ModelMaximum power
Waterstage SHP TRI 156770 W
Waterstage SHP TRI 177400 W
Max. power
consumption
Connection cable
(phase, neutral, earth)
Connection cable
(3 phases, neutral, earth)
5 G 2.5 mm²20 A
(1)
(1)
Circuit breaker
C curve
Circuit breaker
C curve
• Interconnection between outdoor unit and hydraulic unit
The hydraulic unit is powered by the outdoor unit by means of a 4 G 1.5 mm² cable
(phase, neutral, earth, communication bus).
• Electrical backup power supply
The hydraulic unit contains a electrical backup circuit (and a second optional) installed in the storage tank.
Heat pumpElectrical backupsElectrical backup power supply
ModelPower
Waterstage SHP 162 x 3 kW26.1 A3 G 6 mm²32 A
Waterstage SHP TRI 15
Waterstage SHP TRI 17
(1)
Cable type 60245 IEC 57 or 60245 IEC 88.
9 kW3 x 13 A4 G 2.5 mm²20 A
Nominal
current
Connection cable
(phase, neutral, earth)
(1)
Circuit breaker
C curve
• DHW power supply (option)
The DHW section is powered directly via a 3 G 1.5 mm² cable (phase, neutral, earth).
Protection by rated circuit breaker (16 A - C curve).
Waterstage / Installation / 2011 - EN
- 35 -
Page 36
Electrical connections on the outdoor unit side
►
Access to connection terminals:
- Remove the front plate. Remove the screws and front panel.
- Make the connections according to the diagram(s) g. 34, page 40.
Use cable clamps to prevent any power cables from being disconnected accidentally.
■ Waterstage SHP 16
Terminal
L N 1 2 3
POWER INDOOR UNIT
Terminal
Cable clamp
Interconnection
between outdoor unit
and hydraulic unit
electricity supply
Main
g. 30 - Access to outdoor unit's terminal block
Interconnection
Main
electricity supply
between outdoor unit
and hydraulic unit
■ Waterstage SHP TRI 15
Waterstage SHP TRI 17
Terminal
L1 L2 L3 N 1 2 3
POWER INDOOR UNIT
Interconnection
Main
electricity supply
g. 31 - Connections of the outdoor unit's terminal block
between outdoor unit
and hydraulic unit
front
side
g. 32 - Feeding cables and refrigeration connections from the outdoor unit
- 36 -
Sortie dessousSortie latérale Sortie avant
lower
Waterstage / Installation / 2011 - EN
Page 37
Page 38
Electrical connections on the hydraulic unit side
►
Access to connection terminals:
- Remove the front panel (2 screws).
- Open the power control box.
- Make the connections according to the diagram (g. 34).
Do not place the sensor and power supply lines parallel
to each other to avoid interference due to voltage spikes
in the power supply.
Make sure that all electrical cables are housed in the
areas provided for this purpose.
Interconnection between outdoor unit
▼
and hydraulic unit
Match up the terminal block markers on the hydraulic
unit to those of the outdoor unit exactly when connecting
the interconnection cables.
An incorrect connection could result in the destruction
of one or other of the units.
Electrical backups
▼
If the heat pump is not installed with a boiler connection:
- Connect the power supply for the backup to the
electrical panel.
Boiler connection (optional)
▼
If the boiler connection option is used, the
electric backup option must not be connected.
- Please refer to the instructions supplied with the boiler
connection kit.
- Please refer to the instructions supplied with the boiler.
Second heating circuit (optional)
▼
- Refer to the instructions supplied with the double
hydraulic circuit kit.
DHW tank with electrical backup heating
▼
(optional)
If the installation is tted with a DHW tank :
- Please refer to the instructions supplied with the DHW kit.
- Please refer to the instructions supplied with the DHW tank.
You must equipped the DHW electrical backup
heating with a manual reset thermostat.
Contract with Energy Supplier
▼
The heat pump can be set to operate within particular
types of energy contract, e.g. o-peak, day/night.
In particular, domestic hot water (DHW) at the comfort
temperature will be produced at o-peak times when
electricity is at its cheapest.
- Connect the "Power Provider" contact to input EX2.
- Set the DHW conguration to "O-Peak".
• 230V on input EX2 = "Peak Hours” information
activated.
Power limitation or EDR (Energy Demand
▼
Reduction)
Power limitation is designed to reduce electricity
consumption when it is too high for the contract signed
with the energy supplier.
- Connect the power limiter device to input EX1.
Heat pump and DHW backups will be shut o in the
event of over-consumption by the dwelling.
• 230 V on input EX1 = power limitation in progress.
switch, etc.) may signal an external problem and stop
the heat pump.
- Connect the external component to input EX3.
• 230 V on input EX3 = heat pump stopped
(system displays Error 369).
- 38 -
Waterstage / Installation / 2011 - EN
Page 39
Power cables
g. 33 - Cable passages
Sensor cables
Waterstage / Installation / 2011 - EN
- 39 -
Page 40
■ Waterstage SHP 16
1 2 3
L
Power supply for
Electrical backup
single phase 230 V
N
5
4
6
towards external
component contact*
Interconnection
between outdoor unit
and hydraulic unit
brown
blue
red
green/yellow
Single phase outdoor unitHydraulic unit
L N
L
Electricity supply
single phase 230 V
1 2 3
N
■ Waterstage SHP TRI 15
Waterstage SHP TRI 17
1 2 3
1 2 3 4 5 6
COMMUN
L1 L2 L3
L1 L2 L3
Power supply for
Electrical backup 3
phase 400 V
5
4
6
towards external
component contact*
brown
blue
red
green/yellow
Interconnection
between outdoor unit
and hydraulic unit
3 phase outdoor unitHydraulic unit
L2 L3 N
L2
L1
Electricity supply
3 phase 400 V
L3
1 2 3L1
N
g. 34 - Connection to terminal blocks and power relay
- 40 -
Waterstage / Installation / 2011 - EN
Page 41
■ Waterstage SHP 16
Safety thermostat
Terminal
Power supply terminal block
Power Relay for electric backup
Cable grommets (power)
HP controller
Cable grommets (sensors)
Interface Board
■ Waterstage SHP TRI 15
Waterstage SHP TRI 17
Safety thermostat
Power supply terminal block
HP controller
Static relay for electric backup
Terminal
g. 35 - Description of the hydraulic unit's electrical control box
Waterstage / Installation / 2011 - EN
Cable grommets (power)
Cable grommets (sensors)
Interface Board
- 41 -
Page 42
Outside sensor
►
The outside sensor is required for correct operation of
the heat pump.
Please see the tting instructions on the sensor’s
packaging.
Place the sensor on the coldest side of the building,
generally the northern or north-western side.
It must not be exposed to morning sun.
It must be installed so as to be easily accessible but at
least 2.5m from the ground.
It is essential that it is not placed near any sources of
heat such as ues, upper parts of doors and windows,
near extractor vents, under balconies and eaves,
or anywhere which would insulate the sensor from
variations in the outdoor air temperature.
- Connect the outside sensor to connector X84
(terminals M and B9) on the heat pump control board.
Room sensor (optional)
►
The room sensor (room unit) is optional.
Please see the tting instructions on the sensor’s
packaging.
The sensor must be installed in the living room area on
an unobstructed wall. It must be installed so as to be
easily accessible.
Avoid direct sources of heat (chimney, television,
cooking surfaces, sun) and draughty areas (ventilation,
door, etc.).
Draughts in buildings are often brought about by cold air
blowing through the electrical ducting. Lag the electrical
ducts if there is a cold draught behind the room sensor.
Installing a room sensor
▼
• Room thermostat
- Connect the sensor to the X86 connector of the heat
pump’s regulator board using the connector provided
(terminals 1, 2).
• Room thermostat radio
- Please refer to the instructions.
Installing a room control unit
▼
• Room control unit
- Connect the sensor to the X86 connector of the heat
pump’s regulator board using the connector provided
(terminals 1, 2 and 3).
• Room control unit radio
- Please refer to the instructions.
Fan convector zone
▼
If the installation is equipped with fan convectors or
dynamic radiators, do not use a room sensor.
- 42 -
Waterstage / Installation / 2011 - EN
Page 43
Power shedding or EJP
Power limitation or EDR
(peak day removal)
(Energy Demand Reduction)
Tariffs, peak times/off-peak times,
Taris, peak times/o-peak times,
External component
contact*
External component contact*
(faults, load
(faults, power limiter, electricity meter)
shedder, power meter)
day / night
day/night
External fault
External fault
EX1
EX2
EX3
X11
X86
L
6
5
or
** Room
thermostat
T55
** Room
control unit
T75
* If the control device does not provide a potential-free contact, the contact must be relayed to create equivalent wiring. In all cases, please
refer to the instruction manuals for the external components (load shedder, power meters) to create the wiring.
** Option
The connection of terminal 3 of the room control unit is not mandatory (lighting of the room control unit).
M B9
654
12 13 2
or
X84
654
13 2
or
** Room control
unit radio
T78
Outside
Outdoor
sensor
sensor
** Room
thermostat
radio T58
g. 36 - Connections on the heat pump controller (accessories and options)
Waterstage / Installation / 2011 - EN
- 43 -
Page 44
Commissioning
- Close the installation's main circuit breaker.
Upon initial start-up (or in winter), to preheat the
compressor, engage the installation's main circuit
breaker (outdoor unit power supply) several
hours before starting any tests.
- Press the heat pump's Start/Stop button.
To ensure that inputs EX1, EX2 and EX3 operate
correctly: Check that the electricity supply's
neutral phase polarity has been respected.
When the power is switched on and every time that the ON/
OFF button is switched o and then switched on again,
the outdoor unit will take approximately 4 minutes to
start up, even if the setting is requesting heating.
- Engage the start/stop switch.
To ensure that inputs EX1, EX2 and EX3 operate
correctly: Check that the live-neutral polarity of
the power supply is correct.
When the power is switched on and every time that the
ON/OFF button is switched o and then switched on
again, the outdoor unit will take approximately 4 minutes
to start up, even if the setting is requesting heating.
The display can show error 370 when the
appliance (re)starts. Do not be concerned,
the communication between the outdoor and
hydraulic unit will re-establish itself in a few
moments.
During the regulator initialisation phase, the display
shows all the symbols and then "Data, update" and then
"State heat pump".
- Make all the specic adjustments to the setting.
(Installation conguration):
- Press OK.
- Hold down the key for 3s and select the level of
access used with the aid of the knob. .
- Conrm with the key OK.
- Parameter the heat pump's setting
(Consult the settings' list
On commissioning (or the case of error 10), the electrical
back-up heaters are liable to start up even if the outdoor
temperature at the time is above the heaters’ trigger
temperature.
The regulating system uses an average initial outdoor
temperature of 0°C and requires some time to update
this temperature.
To avoid this situation, the sensor must be connected
correctly. Re-initialise parameter 8703 (commissioning
level, consumer diagnostic menu).
- 44 -
Waterstage / Installation / 2011 - EN
Page 45
Conguring room thermostat
►
(wireless)
To congure the room thermostat and connect it to the
appropriate heating zone:
- Hold down the presence key for more than 3 seconds.
The room thermostat displays RU and a number
ashes.
- Turn the wheel to choose the zone (1, 2).
If the installation is tted with 2 room thermostats,
- First connect one room thermostat and congure
it in zone 2,
- Then connect the other room thermostat and
congure it as default in zone 1.
Conguring room control unit
►
(wireless)
- Hold down the presence key; the room
thermostat displays P1 and a ashing number.
1: Automatic recording: a correction of the setting
with the button is adopted without any particular
conrmation (timeout) or by pressing the mode key.
2: Recording with conrmation: a correction of the
setting with the button is not adopted until the mode
key is pressed.
- Press the presence key again; the room thermostat
displays P2 and a ashing number.
0: OFF: all the operating elements are engaged.
1: ON: the following operating elements are locked:
- Switching over the heating circuit's operating
mode,
- Adjusting the comfort setting,
- Changing the operating level.
The room thermostat displays OFF for 3 seconds when
a locked button is pressed.
During commissioning, after an initialisation period of
approx. 3 minutes, the user’s language must be set:
- Press OK.
- Choose menu "Operator section".
- Choose language.
- Select the language (English, Deutsch, Français,
Italiano, Nederlands, Español, Português, Dansk…).
In the case of 2 heating circuits.
- Choose the allocation of the room control unit
(room appliance 1 or 2…) line 40* (see page 51).
- According to the allocation selected check and, if
necessary, modify the settings for lines 42*, 44*, 48*
(see page 51).
LineFunction
40IUse as...Room appliance 1, 2, P,
This line regulates the use of the room control unit. Depending on how it is used, other settings will be necessary
(lines 42, 44, 48).
42IAppliance allocation 1Heating circuit 1,
44IOperation HC2 (command HC2)Commonly with HC1,
This function enables you to choose whether you wish the room thermostat (as an option) to act on both zones or just
a single zone.
Setting range
or display
User interface 1, 2, P,
Service appliance
Heating circuit 1 & 2,
Heating circuit 1 & P,
All the heating circuits
Independent
Setting
increment
Basic
setting
Room
appliance 1
Heating
circuit 1
Commonly
with HC1
48IOccupancy control switch functionWithout,
Heating circuit 1,
Heating circuit 2,
Common
* These parameter lines are only accessible from the room control unit.
Waterstage / Installation / 2011 - EN
- 45 -
Page 46
Controller Interface
The user interface, the central ambient unit (option) and the ambient sensor
►
(option)
1
5
2
6
3
7
8
4
9
1
Auto
2
5
Auto
5
3
0 4 8 12 16 20 24
ESC
OK
4
7
11
2
°C
10
11
8
6
- 46 -
Waterstage / Installation / 2011 - EN
Page 47
Ref.Functions- Denition of the functions
Arrêt
Auto
1Selecting the DHW operation
Marche
- Start: Production of DHW in function of the timer programme.
- Stop: Production of the DHW stopped with antifreeze function of the
domestic water active.
- Manual start button: Press the DHW button for 3 s (switches from
"reduced" to "comfort" until the DHW timer programme is switched again).
2Digital display - Check the operation, read the current temperature of the heating
operation, or a possible fault.
- View the settings.
3"ESC" output - Exit the menu.
4Navigation and setting - Setting the comfort temperature value.
- Menu selection
- Setting the parameters.
5Selecting the heating operation
-
Service heating according to the heating programme
(automatic summer/winter switching).
- Permanent comfort temperature.
- Permanent reduced temperature.
- "Stand-by" operation with antifreeze protection (provided that the
electrical power supply of the heat pump is not interrupted).
6Displaying information - Miscellaneous information (see "Information display", page 66).
-Reading the error codes (see " Fault Diagnosis", page 74).
-Information on maintenance, special operation.
7Validation "OK" - Enter the selected menu.
- Validate the parameter settings.
- Validate the comfort temperature value setting.
8Selection of the refresh mode
-Service cooling according to the heating programme
(automatic summer/winter switching).
9Reset
(Press and relief)
- Reset the parameters and cancel the error messages.
Do not use during normal operation
10Setting button - Setting the comfort temperature value.
503U 2nd phase On (start)00:00... --:--10 min--:--
504U 2nd phase O (end)00:00... --:--10 min--:--
505U 3rd phase On (start)00:00... --:--10 min--:--
506U 3rd phase O (end)00:00... --:--10 min--:--
516U Default values, Circuit 1No, YesNo
Yes + OK: The default values memorised in the regulator replace and cancel the customised heating programs.
Your customised settings are therefore lost.
523U 2nd phase On (start)00:00... --:--10 min--:--
524U 2nd phase O (end)00:00... --:--10 min--:--
525U 3rd phase On (start)00:00... --:--10 min--:--
526U 3rd phase O (end)00:00... --:--10 min--:--
536U Default values, Circuit 2No, YesNo
Yes + OK: The default values memorised in the regulator replace and cancel the customised heating programs.
Your customised settings are therefore lost.
561U 1st phase On (start)00:00... --:--10 min00:00
562U 1st phase O (end)00:00... --:--10 min05:00
563U 2nd phase On (start)00:00... --:--10 min14:30
564U 2nd phase O (end)00:00... --:--10 min17:00
Mon-Sun
Mon-Sun
565U 3rd phase On (start)00:00... --:--10 min--:--
566U 3rd phase O (end)00:00... --:--10 min--:--
576U Default valuesNo, YesNo
Yes + OK: The default values memorised in the regulator replace and cancel the customised heating programs.
Your customised settings are therefore lost.
Holidays, heating circuit 1 (For the Holiday program is active, the heating mode should be on AUTO).
Floor heating system = 50 °C / Radiators = 65 °C.
Important Note : Maximum temperature limitation is not a safety function as required by ground heating.
750SRoom inuence1%... 100%1%50%
0.5 °C20 °C
0.5 °C19 °C
If the installation is tted with a room thermostat:
This function enables you to choose the ambient temperature's inuence on the setting.
If no value is entered, the setting is made based on the temperature control.
If the parameter is set at 100%, the setting is only based on the ambient temperature.
760SRoom temperature limitation0.5... 4 °C0.5 °C0.5 °C
As soon as the room temperature = [Setpoint line 710 (ex. 20°C) + Room temperature limitation setpoint line 760
(ex. 0.5 °C)] > 20.5 °C => The heat pump is stopped.
It restarts when the room temperature falls below the setpoint (in the example, Room temperature < 20.0 °C).
780SQuick setbackO, Down to reduced setpoint,
790SOptimum start control max
(Early start to switch to the comfort setting.)
791SOptimum stop control max (Early stop to switch
801SReduced setpoint increase end-30... 10 °C1 °C-5 °C
830SMixer valve boost0... 50 °C1 °C0 °C
834SActuator running time30... 873 s1 s240 s
Down to frost prot setpoint
0... 360 min10 min180 min
0... 360 min10 min30 min
O
Waterstage / Installation / 2011 - EN
- 53 -
Page 54
LineFunction
850IFloor curing function (g. 40)O
- O: Early interruption of the current programme, programme inactive.
- Operational heating.
- Heating ready for occupation.
- Operational heating + ready heating.
- Ready heating + operational heating.
- Manual: Manual mode enables you to programme your own concrete slab drying time.The function ends
automatically after 25 days.
Setting range
or display
Setting
increment
Basic
setting
55
50
45
40
35
30
25
20
Heating ow temperature °C
0 151018 1
X
Heating ready for occupation
Operational
57
heating
1
Operational heating + Heating ready for occupation
g. 40 - Diagram of the concrete slab drying programmes
851IFloor curing setpoint manually
(if line 850 = manual)
This function enables you to set the custom concrete slab drying temperature. This temperature remains xed.
The concrete slab-drying programme stops automatically after running for 25 days.
856IFloor curing day current0... 32
0... 95 °C1 °C25 °C
25
Day
Please comply with the
standards and instructions
of the manufacturer of the
building ! A good performance
of this function is only possible
with an installation correctly
implemented (hydraulic,
electricity and adjustments) !
This function can be stopped
by anticipation when setting the
902U Comfort cooling setpoint17... 40 °C0,5 °C24 °C
903U Reduced setpoint5... 40°C26 °C
908IFlow temp setp at OT° 25°C6... 35 °C0,5 °C20 °C
909IFlow temp setp at OT° 35°C6... 35 °C0,5 °C16 °C
912ICooling limit at OT°8... 35 °C0,5 °C24 °C
913SLock time at end of heating / cooling8... 1001 h24 h
918SSummer comp start at OT°20... 50 °C1 °C26 °C
919SSummer comp end at OT°20... 50 °C1 °C40 °C
920SSummer comp setp increase1... 10 °C1 °C4 °C
923SFlow temp setp min OT° 25°C6... 35 °C0.5 °C18 °C
1Reduced
Protection
924SFlow temp setp min OT° 35°C6... 35 °C0.5 °C18 °C
- 54 -
Waterstage / Installation / 2011 - EN
Page 55
LineFunction
928SRoom inuence1... 100 %1 %80 %
If the installation is tted with a room thermostat:
This function enables you to choose the ambient temperature's inuence on the setting.
If no value is entered, the setting is made based on the temperature control.
If the parameter is set at 100%, the setting is only based on the ambient temperature.
Only with the 2nd circuit kit option (If the installation consists of 2 heating circuits).
Setting range
or display
Setting
increment
Basic
setting
1010U Comfort setpointReduced setpoint…
Comfort setpoint maximum
1012U Reduced setpointFrost protection setpoint…
Comfort setpoint
1014U Frost protection setpoint4 °C… Reduced setpoint0.5 °C8 °C
1016SComfort setpoint maximumComfort temp... 35 °C1 °C28 °C
1020IHeating curve slope0.1... 40.020.5
(see "Recommended settings for the parameters depending on the installation's emitters", page 50 & g. 37, page 49)
1021IO-set of the heating curve (g. 38, page 49)-4.5... 4.5 °C0.5 °C0 °C
1030ISummer / Winter heating limits8... 30 °C0.5 °C18 °C
When the average of the outdoor temperatures over the past 24 hours reaches 18°C, the regulator switches o the
heating (as an economy measure). During summer mode, the display shows "Eco". This function is only active in
automatic mode.
1040IFlow temp setpoint min8... 70 °C1 °C17 °C
(with dynamic radiator, adjust from 30 to 35°C)
1041IFlow temp setpoint max8... 70 °C1 °C60 °C
Floor heating system = 50 °C / Radiators = 65 °C.
Important Note : Maximum temperature limitation is not a safety function as required by ground heating.
1050SRoom inuence1 %... 100 %1 %50 %
0.5 °C20 °C
0.5 °C19 °C
If the installation is tted with a room thermostat:
This function enables you to choose the ambient temperature's inuence on the setting.
If no value is entered, the setting is made based on the temperature control.
If the parameter is set at 100%, the setting is only based on the ambient temperature.
1060SRoom temperature limitation0.5... 4 °C0.5 °C0.5 °C
As soon as the room temperature = [Setpoint line 1010 (ex. 20°C) + Room temperature limitation setpoint line 1060
(ex. 0,5 °C)] > 20,5 °C => The heat pump is stopped.
It restarts when the room temperature falls below the setpoint (in the example, Room temperature < 20,0 °C).
1080SQuick setbackO, Down to reduced setpoint,
Down to frost prot setpoint
1090SOptimum start control max0... 360 min10 min180 min
1091SOptimum stop control max0... 360 min10 min30 min
1100SReduced setpoint increase start-30... 10 °C, --°C1 °C--
1101SReduced setpoint increase end-30... 10 °C, --°C1 °C-5 °C
1130SMixer valve increase0... 50 °C1 °C0 °C
1134SActuator running time30... 873 s1 s240 s
O
Waterstage / Installation / 2011 - EN
- 55 -
Page 56
LineFunction
1150IFloor curing function (g. 40, page 54)O
- O: Early interruption of the current programme, programme inactive.
- Operational heating.
- Heating ready for occupation.
- Operational heating + ready heating.
- Ready heating + operational heating.
- Manual: Manual mode enables you to programme your own concrete slab drying time.The function ends
automatically after 25 days.
Setting range
or display
Setting
increment
Basic
setting
1151IFloor curing setpoint manually
(if line 1150 = manual)
This function enables you to set the custom concrete slab drying temperature. This temperature remains xed.
The concrete slab-drying program stops automatically after running for 25 days.
1202U Comfort cooling setpoint17... 40 °C0.5 °C24 °C
1203U Reduced setpoint5... 40°C26 °C
1208IFlow temp setp at OT° 25°C6... 35 °C0.5 °C20 °C
1209IFlow temp setp at OT° 35°C6... 35 °C0.5 °C16 °C
1212ICooling limit at OT°8... 35 °C0.5 °C24 °C
1213SLock time at end of heating / cooling8... 1001 h24 h
0... 95 °C1 °C25 °C
Reduced, Comfort, Automatic
Comfort
Reduced
Protection
1218SSummer comp start at OT°20... 50 °C1 °C26 °C
1219SSummer comp end at OT°20... 50 °C1 °C40 °C
1220SSummer comp setp increase1... 10 °C1 °C4 °C
1223SFlow temp setp min OT° 25°C6... 35 °C0.5 °C18 °C
1224SFlow temp setp min OT° 35°C6... 35 °C0.5 °C18 °C
1228SRoom inuence1... 100 %1 %80 %
If the installation is tted with a room thermostat:
This function enables you to choose the ambient temperature's inuence on the setting.
If no value is entered, the setting is made based on the temperature control.
If the parameter is set at 100%, the setting is only based on the ambient temperature.
24h / day: The temperature of the DHW is constantly maintained at the DHW comfort setting.
Heating circuit time programme: The DHW is produced according to the programming for the ambient temperature
(with 1 hour in advance when switched on).
Programme 4 / DHW: The DHW programme is separate form the heating circuit programme.
O-peak tari* : The electrical backup heating is only authorised to operate during the o-peak period.
T'prog 4/DHW or low-tari *: The electrical backup heating is authorised to operate during the comfort period or o peak.
* - Connect the "Power Provider" contact to input EX2 (see g. 36, page 43). In the case of a day /night contract,
the electric back-ups for the DHW tank are subject to the power supplier's taris. Switching on the electric back-up for
the DHW tank is only authorised during o-peak hours.
1640ILegionella functionO, Periodically (depending line setting 1641),
Fixed weekday (depending line setting 1642)
155 °C
140 °C
Programme
4 / DHW
O
1641ILegionella function periodically1 to 71 day7
1642SLegionella function weekdayMonday, Tuesday,...Saturday
1644SLegionella funct time
1645SLegionella funct setpoint
1646SLegionella funct duration
1647SLegionella funct circ pumpO, OnO
1660SCirculating pump releaseTime program 3/HCP, DHW release,
Time program 4/DHW, Time program 5
Swimming pool (Only with swimming pool kit option)
2920SWith electrical utility lock (EX1)Locked (Blocked on standby),
Energy meter
3095 --> 3110 : Not used
3113U Energy brought inKwh--
3121 --> 3123 : Not used
3124U Energy brought in heating 1 (N - 1)Kwh--
3125U Energy brought in DHW 1Kwh--
3126U Energy brought in cooling 1Kwh--
Electrical release - start-up with outdoor
temperature
Released : HP = ON _ Back-up DHW = o _ 1st back-up HP = o _ 2nd back-up HP = o _ Boiler = ON
Locked (Blocked on standby) : HP = o _ Back-up DHW = o _ 1st back-up HP = o _ 2nd back-up HP = o _
Boiler = ON
Cumulation of total consumed electrical energy.
Electrical energy consumed = Electrical energy absorbed by outdoor unit + electric energy absorbed by the heating
electrical backup and / or DHW electrical backup (if installed).
-30... 30 °C2 °C
Released
Released
3128 --> 3130 : Not used
3131U Energy brought in heating 2 (N - 2)Kwh--
3132U Energy brought in DHW 2Kwh--
3133U Energy brought in cooling 2Kwh--
3135 --> 3137 : Not used
3138U Energy brought in heating 3 (N - 3)Kwh--
3139U Energy brought in DHW 3Kwh--
3140U Energy brought in cooling 3Kwh--
3142 --> 3144 : Not used
3145U Energy brought in heating 4 (N - 4)Kwh--
3146U Energy brought in DHW 4Kwh--
3147U Energy brought in cooling 4Kwh--
3149 --> 3151 : Not used
3152U Energy brought in heating 5 (N - 5)Kwh--
3153U Energy brought in DHW 5Kwh--
3154U Energy brought in cooling 5Kwh--
- 58 -
Waterstage / Installation / 2011 - EN
Page 59
LineFunction
3156 --> 3158 : Not used
3159U Energy brought in heating 6 (N - 6)Kwh--
3160U Energy brought in DHW 6Kwh--
3161U Energy brought in cooling 6Kwh--
3163 --> 3165 : Not used
3166U Energy brought in heating 7 (N - 7)Kwh--
3167U Energy brought in DHW 7Kwh--
3168U Energy brought in cooling 7Kwh--
3170 --> 3172 : Not used
3173U Energy brought in heating 8 (N - 8)Kwh--
3174U Energy brought in DHW 8Kwh--
3175U Energy brought in cooling 8Kwh--
3177 --> 3179 : Not used
3180U Energy brought in heating 9 (N - 9)Kwh--
3181U Energy brought in DHW 9Kwh--
Setting range
or display
Setting
increment
Basic
setting
3182U Energy brought in cooling 9Kwh--
3184 --> 3186 : Not used
3187U Energy brought in heating 10 (N - 10)Kwh--
3188U Energy brought in DHW 10Kwh--
3189U Energy brought in cooling 10Kwh--
3190SReset xed day storageNo, YesNo
Reset the historical counters (1 to 10). The general counter (parameter 3113) is not reset.
Set the parameter 3197 according to the outdoor unit
Heat PumpOutdoor unitParameter 3197
Waterstage SHP 16
Waterstage SHP TRI 15
Waterstage SHP TRI 17
3264 --> 3267 : Not used
WOYG160LJL5.37
WOYK150LJL4.55
WOYK170LJL5.32
Note: "Energy" Counters increment as of 1 July each year.
Waterstage / Installation / 2011 - EN
- 59 -
Page 60
LineFunction
Additional generator (Boiler connection)
Setting range
or display
Setting
increment
Basic
setting
3692SWith DHW chargingLocked, Substitute,
Complement, Instantly
- DHW Instantly : When DHW request, the HP and the boiler are put into operation. The HP will stop when the primary
return temperature is over 55 °C.
- DHW Substitute : If the outdoor temperature is above 2 °C, the operation of the HP when DHW request last 5 minutes
at least. The HP operating time can be extended depending on the outdoor temperature. The boiler will activate then.
3700SRelease below outdoor temperature-50... 50 °C1 °C2 °C
3720SSwitching integral (for boiler relief)0... 500 °Cmin1 °Cmin100 °Cmin
3723SLocking time1... 120 min1 min30 min
Domestic hot water (DHW)
If the installation is tted with the DHW kit.
5024SSwitching di0... 20 °C1 °C7 °C
5030SCharging time limitation10... 600 min10 min90 min
(with dynamic radiator, adjust 40 min)
5055SRecooling temp10... 95 °C1 °C65 °C
5057SRecooling collectorO, Summer, AlwaysSummer
5061SElectric immersion heater release24h / day, Release of DHW,
Programme 4 / DHW
Substitute
Release of
DHW
5093SWith solar integrationNo, YesYes
Installation conguration
5700IPre-setting1,2,3,... 911
This control enables you to choose one of the 4 pre-selected installation congurations. The hydraulic layouts for the
various congurations are detailed in the section: "Installation Congurations".
- Pre-setting 1: 1 heating circuit with or without electrical back-up, with DHW tank.
- Pre-setting 2: 2 heating circuits with or without electrical back-up, with DHW tank.
- Pre-setting 3: Boiler connection and 1 heating circuit and DHW tank.
- Pre-setting 4: Boiler connection and 2 heating circuits and DHW tank.
- Pre-setting 5 and more: Not used.
5710SHeating circuit 1O, OnOn
5711SCooling circuit 1O, 4-pipe system cooling,
2-pipe system cooling
Set the parameter to "2-pipe system cooling" with the cooling kit.
5715SHeating circuit 2O, OnOn
5716SCooling circuit 2O, 4-pipe system cooling,
2-pipe system cooling
Set the parameter to "2-pipe system cooling" with the cooling kit.
If the installation consists of 2 heating circuits.
5731SDHW controlling element Q3No charging request,
5983SContact type input EX2Normally-closed contact (NC)
Normally-opened contact (NO)
5985SContact type input EX3Normally-closed contact (NC)
Normally-opened contact (NO)
utility lock E6
NO
NC
NO
6098SReadjustm collector sensor-20... 200
6100SReadjustm outdoor sensor-3... 3 °C0.1 °C0 °C
6117SCentral setp compensation1... 100°C5 °C
6120SFrost protection plantOn, OOn
Waterstage / Installation / 2011 - EN
- 61 -
Page 62
LineFunction
6201SReset sensorsNo, YesNo
6205SReset to default parametersNo, YesNo
6220SSoftware version (RVS)0... 99--
6300SInfo 1 OEM0... 65535--
6301SInfo 2 OEM0... 65535--
LPB system
6600SDevice address0... 161
Error
6710U Reset Defaut relaisNo, YesNo
6711U Reset HPNo, YesNo
6800SHistory 1Time, Date, Error code
6802SHistory 2Time, Date, Error code
6804SHistory 3Time, Date, Error code
6806SHistory 4Time, Date, Error code
6808SHistory 5Time, Date, Error code
Setting range
or display
Setting
increment
Basic
setting
6810SHistory 6Time, Date, Error code
6812SHistory 7Time, Date, Error code
6814SHistory 8Time, Date, Error code
6816SHistory 9Time, Date, Error code
6818SHistory 10Time, Date, Error code
Maintenance / special regime
7070SHP interval--, 1... 2401 month--
7071SHP time since maint
Reset ? (no, yes)
7073SCur starts compr1/hrs run (since the 6 last weeks)
Reset ? (no, yes)
7141U Emergency operationO, OnO
O: Heat pump functions normally (with boosters if necessary).
On: Heat pump uses the electric boost system or the boiler connection.
Use the “On” position only in Assist mode or Test mode: may result in high power bills.
7142SEmergency operating function typeManual, AutomaticManual
Manual: Emergency mode is not active when a fault occurs (Emergency mode = OFF).
Automatic: Emergency mode is active when a fault occurs (Emergency mode = ON).
In "Automatic" position, the energy cost can be onerous if the error is not detected and eliminated.
7150ISimulation outdoor temp-50... 50 °C0.5--
0... 2401 month0
0... 120
- 62 -
Waterstage / Installation / 2011 - EN
Page 63
LineFunction
Inputs / outputs test
7700IRelay testNo test
This consists of instructing the regulator's relays one by one and checking their outputs. This enables you to check that
the relays are working and that the cabling is correct. Check that each appliance in the installation is operating correctly.
0: No test, 1: Everything is on STOP, 2: Relay output QX1 : heat pump CC1 (if 1 circuit ) or heat pump CC2 (if 2 circuits),
3: Relay output QX2 : Electrical back-up (1st stage) or Boiler connection distribution valve,
4: Relay output QX3 : Electrical back-up (2nd stage) or Boiler connection contact,
5: Relay output QX4 : DHW distribution valve, 6: Relay output QX5 : DHW Electrical back-up, 7: Relay output QX6 ,
8: Relay output QX31 : Heat circ mix valve open Y1 (or control pilot-wire), 9: Relay output QX32 : Heat circ mix valve close Y2,
10: Relay output QX33 : heat pump CC1 if 2 circuits (mixed circuit, the less hot), 11: Relay output QX34,
12: Relay output QX35 : Swimming pool distribution valve, 13: Relay output QX21 module 1, 14: Relay output QX22 module 1,
15: Relay output QX23 module 1, 16: Relay output QX21 module 2, 17: Relay output QX22 module 2,
18: Relay output QX23 module 2, 19: Not used, 20: Not used, 21: Not used.
The display shows the “Key” symbol. Pressing the Info button displays "Error 368".
Warning: The component being tested is receiving electrical power throughout the test.
7710IOutput UX1 test0... 100%1--
7716IOutput UX2 test0... 100%1--
7722IDigital output DO2O, OnO
7723IHeat pump D3O, OnO
7724IOutputs test UX3 ("Inverter" command)0... 100 %--
7725IVoltage value U4 (Ux3)0... 10 v--
Setting range
or display
Setting
increment
Basic
setting
7804ISensor temperature BX1 (HP ow temperature)-28... 350 °C--
7805ISensor temperature BX2 (HP return temperature)-28... 350 °C--
7806ISensor temperature BX3 (DHW temperature)-28... 350 °C--
7807ISensor temperature BX4 (Outdoor temperature)-28... 350 °C--
7858IInput signal H3
7911IInput EX1 (Power shedding, EJP)0, 230 V--
7912IInput EX2 (Taris day/night)0, 230 V--
7913IInput EX3 (External fault)0, 230 V--
State
8000IState heating circuit 1--
8001IState heating circuit 2--
8003IState DHW--
8004IState cooling circuit 1--
8006IState heat pump--
8007IState solar--
8010IState buer--
8011IState swimming pool--
None, Closed (ooo), Open (---)
Pulse, Frequency Hz, Voltage V
,
None
8022IState supplementary source--
8025IState cooling circuit 2--
Waterstage / Installation / 2011 - EN
- 63 -
Page 64
LineFunction
Generator diagnosis
8400ICompressor 1O, OnO
8402IElectrical resistance ow 1O, OnO
8403IElectrical resistance ow 2O, OnO
8406ICondenser pumpO, OnO
8407SSpeed condenser pump0...100%--
8410U Return temp HP0... 140 °C--
Setpoint (ow) HP--
8412U Flow temp HP0... 140 °C--
Setpoint (ow) HP--
8413U Compressor modulation0... 100%--
8414IModulation electric ow0... 100%--
8425STemp di condensor-50... 140 °C--
8450SHours run compressor 100:00--
Setting range
or display
Setting
increment
Basic
setting
8454SLocking time Heat Pump
Reset ? (no, yes)
8455SCounter number of locks HP
Reset ? (no, yes)
8456SHours run electrical ow
Reset ? (no, yes)
8457SStart counter electrical ow
Reset ? (no, yes)
8458IState smart gridDraw disabled, Draw free,
8460IHeat pump throughput0... 65535 l/min--
Diagnostics consumers
8700U Outdoor temperature-50... 50 °C--
8701U Outdoor temp min
Reset ? (no, yes)
8702U Outdoor temp max
Reset ? (no, yes)
8703IOutdoor temp attenuated
Reset ? (no, yes)
This is the average of the outdoor temperature over a 24-hour period.
This value is used for automatic Summer / Winter switchover (line 730).
0... 2730 h--
0... 65535--
0... 2730 h--
0... 65535--
Draw wish, Draw forced
-50... 50 °C50 °C
-50... 50 °C-50 °C
-50... 50 °C--
Draw free
8704IOutdoor temp composite-50... 50 °C--
The mixed outdoor temperature is a combination of the current outdoor temperature and the average outdoor temperature
calculated by the regulator. This value is used for calculating the initial temperature.
8730IHeating circuit pump, circuit 1O, OnO
8731IMixer valve HC1 openO, OnO
8732IMixer valve HC1 closedO, OnO
8740U Room temperature 10... 50 °C--
Room setting 120 °C
8743U Flow temperature 10... 140 °C--
Flow temperature setpoint 1--
8749IRoom thermostat 1No demand, DemandNo demand
- 64 -
Waterstage / Installation / 2011 - EN
Page 65
LineFunction
8756U Cooling ow temperature 10... 140 °C--
Cooling ow temperature setpoint 1--
8820IDHW pumpO, OnO
8821IEl imm heater DHWO, OnO
8830U DHW (domestic hot water) temperature0... 140 °C--
Various data can be displayed by pressing the
button.
Depending on the type of unit, conguration and
operating state, some of the info lines listed below may
not appear.
- Possible error messages from the error code list
(see table, page 74).
- Possible service messages from the maintenance
code list.
- Possible special mode messages.
- Various data (see below).
DesignationLine
Floor drying current setpoint.-
Current drying day.-
Terminated drying days.-
State heat pump.8006
State supplementary source.8022
State DHW.8003
State swimming pool.8011
State heating circuit 1.8000
State heating circuit 2.8001
State cooling circuit 1.8004
Outdoor temperature.8700
Room temperature 1.
Room setpoint 1.
Flow temperature 1.
Flow temperature setpoint1.
Room temperature 2.
Room setpoint 2.
Flow temperature 2.
Flow temperature setpoint 2.
DHW (domestic hot water) temperature.8830
Heat pump return temperature.
Setpoint (return) HP.
Heat pump ow temperature.
Setpoint (ow) HP.
Swimming pool temperature.
Swimming pool temperature setpoint.
Minimum remaining stop time for compressor 1.-
Minimum remaining running time for compressor 1.-
8740
8743
8770
8773
8410
8412
8900
- 66 -
Waterstage / Installation / 2011 - EN
Page 67
Page 68
Basic Hydraulic Layout
■ Conguration: 1 heating circuit
SA
OU
R
SA*
Rdyn*
OU
SA
PC
SP
- 68 -
MH
SE
Db
CC
PC - Underoor heating system
R - Radiator
Rdyn* - Dynamic radiator
SA* - Room sensor (option/ except with Rdyn)
SE - Outside sensor
SP - Heated oor thermal safety fuse
BT*
Key:
Waterstage / Installation / 2011 - EN
BT* - Buer tank (obligatory with Rdyn)
CC - Heating circulation pump
Db - Flowmeter
MH - Hydraulic unit
Page 69
■ Conguration: 1 heating circuit and mixed hot water tank
Ssa
KS
SA
AE
OU
R
A
AB
SA*
M
B
VD
Rdyn*
OU
SA
PC
SP
MH
SE
Waterstage / Installation / 2011 - EN
Db
CC
PC - Underoor heating system
R - Radiator
Rdyn* - Dynamic radiator
SA* - Room sensor (option/ except with Rdyn)
SSa - Hot water sensor
SE - Outside sensor
SP - Heated oor thermal safety fuse
VD - Distribution valve
BT*
Key:
AE - Electrical backup
BT* - Buer tank (obligatory with Rdyn, if HP>11kW)
CC - Heating circulation pump
Db - Flowmeter
KS - DHW kit
MH - Hydraulic unit
- 69 -
Page 70
Electrical Cabling Plans
Valve
BOBINE
Coil 2 (inj.)
Expansion
(INJECTION)
DETENDEUR 2
Valve
Coil 1
BOBINE
Expansion
DETENDEUR 1
Coil
Valve
VANNE
BOBINE
ELECTRO
Solenoid
4-way
Pressure
PRESSOSTAT
(HAUTE
(High)
Sensor
PRESSION)
Pressure
PRESSOSTAT
MM
SV
Coil
Valve
VANNE
BOBINE
4 VOIES
(BASSE
(Low)
Sensor
PRESSION)
PS
PS
4WV
WH
6
6
YE
5
5
4
4
OR
BU
RD
1 2 3
1 2 3
WH
6
6
YE
4
OR
BU
RD
1 2 3
1 2 3
BU
BU
1 25
1 25
BU
BU
1 24
1 2
BK
WH
1 2 3
1 2 3
RD
BK
WH
2 3
RD
1 2 3
1
BKBKBKBKBK
GN
RD
1
1
M
BK
234
234
(HAUT)
MOTEUR
VENTILATEUR 1
Fan motor 1 (upper)
WHYEBN
RD
567
567
E100
EXT.
EXT.
IN. 2
IN. 1
1 21 2
EXT.
EXT.
CN131 CN132
OUT. 2
1 21 2
OUT. 1
CN136 CN137
CN119CN106CN108CN116CN117
CN118
CN146CN144CN147CN142
1 1
234
234
231
231
1
1
BKBKBK
234
234
1
1
1
1
BK
234
234
Main
234
234
BK
M
BK
CARTE PRINCIPALE
(BAS)
MOTEUR
VENTILATEUR 2
Fan motor 2 (lower)
WHYEBN
567
567
CN122CN104
8
7
6
5
4
1 2 3
DE REGULATION
control board
W006
CN100CN126
1 2 3
CN139
2
1
2
1
WH
WH
CAPTEUR
Pressure
8
7
6
5
4
1 2 3
RD
1 2 3
P
PRESSION
Switch
BK
WH
WH
WH
GR
VT
BU
GN
YE
OR
RD
BN
1 2 3
8
7
6
5
4
1 2 3
1 2 3
8
7
6
5
4
CN150CN20
1 2 3
WH
BK
Fuses
FUSIBLE
W(C)
BKWHRD
TM402
WH
20A250V
3~
MS
V(S)
TM401
231
231
RD
231
231
TM502
TM501
BK
BK
U(R)
CN100
BK
CN501
COMPRESSEUR
Compressor
TM400
CARTE
INVERTER
(Inverter)
Control board
TM100
BK
TM507
FILTRE
CARTE
Filter Board
1 2 3L N
BU
Terminal
BORNIER
TM101
WH
TM508
GN
W503
230 V
supply
L + N ~ 50Hz
Electricity
ELECTRIQUE
ALIMENTATION
MODULE
HYDRAULIQUE
Hydraulic unit
230V
(REFOULEMENT)
(COMPRESSEUR)
SONDE TEMPERATURE
SONDE TEMPERATURE
(EXTERIEURE)
SONDE TEMPERATURE
(TUYAUTERIE)
SONDE TEMPERATURE
Temperature sensor. Pi pe
Temperature sensor. Di sch arg e
Temperature sensor. Outd oor
Temperature sensor. C omp res sor
g. 41 - Outdoor unit electrical cabling single phase
- 70 -
(EVAPORATEUR)
SONDE TEMPERATURE
Temperature sensor. Ev apo rat or
Reactor
REACTANCE
Colour codes
BK Black
BN Brown
BU Blue
GN Green
GY Grey
OG OrangeRD Red
VT Violet
WH White
YE Yellow
Waterstage / Installation / 2011 - EN
Page 71
M
(HAUT)
MOTEUR
VENTILATEUR 1
Fan motor 1 (upper)
M
(BAS)
MOTEUR
VENTILATEUR 2
Fan motor 2 (lower)
3~
MS
COMPRESSEUR
Compressor
REACTANCE
Reactor
Valve
BOBINE
Coil 2 (inj.)
Expansion
(INJECTION)
DETENDEUR 2
Valve
Coil 1
BOBINE
Expansion
DETENDEUR 1
Coil
Valve
VANNE
BOBINE
ELECTRO
Solenoid
Pressure
(HAUTE
(High)
Sensor
PRESSION)
Pressure
PRESSOSTAT
MM
SV
Valve
4-way
BOBINE
(BASSE
Sensor
PRESSOSTAT
PS
4WV
Coil
VANNE
4 VOIES
PS
(Low)
PRESSION)
WH
6
6
YE
5
5
4
4
OR
BU
RD
1 2 3
1 2 3
WH
6
6
YE
4
OR
BU
RD
1 2 3
1 2 3
BU
BU
1 25
1 25
BU
BU
1 24
1 2
BK
WH
1 2 3
1 2 3
RD
BK
WH
2 3
RD
1 2 3
1
1 1
BKBKBKBKBK
GN
RD
1
1
234
234
BK
WHYEBN
567
567
RD
1
1
E100
EXT.
EXT.
IN. 2
IN. 1
1 21 2
EXT.
EXT.
CN131 CN132
OUT. 2
1 21 2
OUT. 1
CN136 CN137
CN119CN106CN108CN116CN117
CN118
CN146CN144CN147CN142
234
234
231
231
1
1
BKBKBK
234
234
BK
WHYEBN
BK
234
234
Main
DE REGULATION
control board
CARTE PRINCIPALE
234
1
234
1
BK
567
567
CN122CN104
1
1
WH
CN100CN126
CN139
2
2
WH
8
7
6
5
4
1 2 3
W006
1 2 3
CAPTEUR
Pressure
8
7
6
5
4
1 2 3
RD
1 2 3
P
PRESSION
Switch
BK
WH
WH
WH
GR
VT
BU
GN
YE
OR
RD
BN
1 2 3
8
7
6
5
4
1 2 3
1 2 3
8
7
6
5
4
CN801CN805
1 2 3
RD
WH
BK
Fuses
20A250V
FUSIBLE
BKWHRD
TM821
TM819
CN802
231
231
BK
RD
WH
231
231
CN501
TM803
TM802
TM801
BK
BK
RD
TM817
TM812
CARTE
INVERTER
(Inverter)
Control board
TM800
RD
W514
FILTRE
CARTE
Filter Board
1 2 3L1 L2 L3 N
BU
RD
TM814
TM801
BK
WH
W515
Electricity
TM802
W516
GN
W507
supply
3 phase
3L + N ~ 50Hz
ELECTRIQUE
ALIMENTATION
MODULE
HYDRAULIQUE
Hydraulic unit
400V
400 V
(REFOULEMENT)
SONDE TEMPERATURE
SONDE TEMPERATURE
Temperature sensor. Di sch arg e
(EXTERIEURE)
(COMPRESSEUR)
SONDE TEMPERATURE
Temperature sensor. Outd oor
SONDE TEMPERATURE
Temperature sensor. C omp res sor
g. 42 - Outdoor unit electrical cabling 3-phase
Waterstage / Installation / 2011 - EN
(TUYAUTERIE)
Temperature sensor. Pi pe
(EVAPORATEUR)
SONDE TEMPERATURE
Temperature sensor. Ev apo rat or
Reactor
REACTANCE
Terminal
BORNIER
Colour codes
BK Black
BN Brown
BU Blue
GN Green
GY Grey
OG OrangeRD Red
VT Violet
WH White
YE Yellow
- 71 -
Page 72
CN21
Option Appoint électrique monophaséElectric back-up Single phase Option
Débitmètre / Flowmeter (SHP)
CN1
FUSE 250V/3.15A
relay (see g. 34, page 40).
Condensation
sensor
Connection to terminal blocks and power
External
component contact
L N
1 2 3
Power limitation
Taris (day/night)
External faults
CN18
2 circuit option
FUSE 250V/6.3A
B1 B2
A1 A2
( ) 3KW
L
L
(=) 6KW
N
00124534-4-B
Single phase electrical backup
g. 43 - Electrical cabling of single phase hydraulic unit (excluding connections made by installer)
Flow
sensor
Connections on the
(see g. 36, page 43).
heat pump controller,
accessories and options
3 2 1
Ou/
Ou/
Or
321
321
Or
Ou/
RP2
RP1
Débitmètre /
Flowmeter
Flow-meter
Or
Return
sensor
00124534-3-B
/
Options
U0531725-B
Caractéristiques fusibles
Fuse specications
Fuse specifications
- 72 -
Waterstage / Installation / 2011 - EN
Page 73
CN21
Débitmètre / Flowmeter (SHP)
CN1
FUSE 250V/3.15A
relay(see g. 34, page 40).
Condensation
sensor
Connection to terminal blocks and power
External
component contact
Power limitation
Taris (day/night)
External faults
CN18
2 circuit option
FUSE 250V/6.3A
1 2 3L1
L2 L3 N
Connections on the
(see g. 36, page 43).
heat pump controller,
accessories and options
3 2 1
Ou/
Ou/
Or
321
321
Or
Ou/Or
Débitmètre /
Flowmeter
Flow-meter
00124534-3-B
Caractéristiques fusibles
Fuse specications
00124534-6-B
3 phase electrical backup
U0531725-B
Fuse specifications
g. 44 - Electrical cabling of 3-phase hydraulic unit (excluding connections made by installer)
Flow
sensor
Return
sensor
/
Options
Waterstage / Installation / 2011 - EN
- 73 -
Page 74
Fault Diagnosis
Depending on whether the fault comes from the outdoor unit or the hydraulic unit, the fault may be indicated by the
digital display or the LED on the interface cards.
Faults in the Hydraulic Unit
►
Faults or breakdowns on the hydraulic unit are indicated by the display on the user interface.
The display shows the symbol.
Press the key for more details on the origin of the fault.
When the error has been resolved, the faults are re-initialised at zero automatically.
Hydraulic unit: Fault visible on the digital display.
ErrorDesignationProbable causesProposed actions
10Outside sensor
32Flow sensor 2
33Flow sensor HP
44Return sensor HP
50DHW sensor 1
60Room sensor 1
65Room sensor 2
83BSB, short circuit
127Legionella temp
212Internal comm failureUnplugged or disconnected sensor.Check the sensor's wiring.
356FlowmeterInsucient ow.
369ExternalExternal safety triggered EX3.-
370Thermodynamic sourceSee details page 74.-
441BX31 no function
442BX24 no function
443BX33 no function
444BX34 no function
516Heat pump missing
Short-circuit.
Unplugged or disconnected sensor.
Faulty sensor.
Other fault.
Wiring problem (between the sensor
or remote control, display and
controller).
Anti-legionella temp setpoint not
reached.
Short-circuit.
Unplugged or disconnected sensor.
Faulty sensor.
Other fault.
Loss of connection between
controller and HP.
Check the sensor's wiring.
Replace the sensor.
Check the wiring.
Check the wiring of the DHW backup /
boiler connection.
Check the opening of the valves of the
installation.
Check the owmeter's wiring.
Replace the owmeter.
Check the sensor's wiring.
Replace the sensor.
Check the wiring between X60 and the
interface board.
Before any maintenance operation,
ensure that the general power supply is switched o.
Frost protection is not available when the heat pump is not powered up.
- 74 -
Waterstage / Installation / 2011 - EN
Page 75
Hydraulic unit: Flashing of the LED visible on the interface card.
Outdoor unit
Error number
111 Flash1 FlashCommunication error between Hydraulic unit and Outdoor unit.
959 Flashes5 FlashesDetection of compressor position error / Compressor start up error.
979 Flashes7 FlashesOutdoor unit fan1 motor error.
989 Flashes8 FlashesOutdoor unit fan2 motor error.
A110 Flashes1 FlashDischarge temperature protection.
A310 Flashes3 FlashesCompressor temperature protection.
A410 Flashs4 FlashsOutdoor unit pressure error.
A510 Flashes5 FlashesLow pressure abnormal.
A910 Flashs9 FlashsCurrent overload error.
-
-
LED 2 (green)LED 1 (red)
Continuous
LED display
Continuous ashing
(1 sec On / 1 sec O)
lighting
Error contents
Pump down operation.
ODefrosting.
Waterstage / Installation / 2011 - EN
- 75 -
Page 76
Faults displayed on the single
►
phase outdoor unit
To access the electronic board, you must remove the
front (right-hand) facing from the outdoor unit.
Faults are coded by LED ashes.
When an error occurs:
The LED "ERROR" (2) blinks.
Press once on the switch "ENTER" (SW109).
The "ERROR" (2) LED blinks several times depending
on the error's type (see below).
g. 45 - Location of switches and LED on single phase
LED displayError contents
1 FlashSerial forward transfer error.
2 FlashesDischarge thermistor error.
3 FlashesPressure switch error.
4 FlashesHeat-exchange thermistor (outlet) error.
6 FlashesExpansion valve thermistor error.
7 FlashesOutdoor temperature thermistor error.
8 FlashesCompressor thermistor error.
9 FlashesTransistor PCB error.
11 FlashesDischarge temperature error (permanent stoppage).
12 FlashesCompressor temperature error (permanent stoppage).
13 FlashesOver current error (permanent stoppage).
15 FlashesCompressor start up error (permanent stoppage).
16 FlashesFan motor 1 error (permanent stoppage).
17 FlashesFan motor 2 error (permanent stoppage).
18 FlashesInverter error.
20 FlashesLow pressure error.
23 FlashesDischarge pressure sensor error.
24 FlashesSuction pressure sensor error.
outdoor unit
Before any maintenance operation,
ensure that the general power supply is switched o.
Frost protection is not available when the heat pump is not powered up.
- 76 -
Waterstage / Installation / 2011 - EN
Page 77
Faults displayed on the 3-phase
►
outdoor unit
To access the electronic board, you must remove the
front (right-hand) facing from the outdoor unit.
Faults are coded by LED ashes.
When an error occurs:
The LED "ERROR" (2) blinks.
Press once on the switch "ENTER" (SW109).
The "ERROR" (2) LED blinks several times depending
on the error's type (see below).
g. 46 - Location of switches and LED on 3-phase
outdoor unit
LED displayError contents
1 FlashSerial forward transfer error.
2 FlashesDischarge thermistor error.
3 FlashesPressure switch error.
4 FlashesHeat-exchange thermistor (outlet) error.
6 FlashesExpansion valve thermistor error.
7 FlashesOutdoor temperature thermistor error.
8 FlashesCompressor thermistor error.
9 FlashesTransistor PCB error.
11 FlashesDischarge temperature error (permanent stoppage).
12 FlashesCompressor temperature error (permanent stoppage).
13 FlashesOver current error (permanent stoppage).
14 FlashesDetection of compressor position error (permanent stoppage).
15 FlashesCompressor start up error (permanent stoppage).
16 FlashesFan motor 1 error (permanent stoppage).
17 FlashesFan motor 2 error (permanent stoppage).
18 FlashesInverter error.
20 FlashesLow pressure abnormal.
23 FlashesDischarge pressure sensor error.
24 FlashesSuction pressure sensor error.
Waterstage / Installation / 2011 - EN
- 77 -
Page 78
Maintenance of the installation
Before any maintenance operation,
ensure that the general power supply is switched o.
Hydraulic checks
►
If frequent rells are required it is absolutely
essential that you check for any leaks. If
relling and a pressure reset are necessary,
check what type of uid was used initially.
Recommended lling pressure: between 1 and 2 bar
(the exact lling pressure is determined by the water
pressure in the installation).
Every year,
- Check the expansion circuit pressure (pre-ination of
1 bar) and the correct operation of the safety valve.
If the installation is tted with a hot water tank:
- Check the safety valve on the cold water supply inlet.
Make it operate as advised by the manufacturer.
- Check the back ow preventer.
Checking the outdoor unit
►
- Remove any dust from the exchanger, if necessary,
while making sure not to damage the blades.
- Straighten the blades using a comb.
- Check that there is nothing blocking the air ow.
- Check the fan.
- Verify that condensate drain is not obstructed.
• Checking the refrigeration circuit
If the amount of refrigerant in the system exceeds
2kg (models > 10kW), the refrigeration circuit must be
checked annually by an approved engineer (they must
have a certicate of competence for the handling of
refrigerants).
- Check there are no leaks (connections, valves…).
Electrical checks
►
- Check the connections and re-tighten if necessary.
- Check the state of the cables and plates.
Other maintenance
Emptying the hydraulic unit
►
- Remove the front panel of the hydraulic unit.
- Open the drain plug,
- Check that the hydraulic unit's bleeder valve opens
automatically,
- Open the installation’s bleeder valve(s).
- 78 -
Distribution valve
►
If the installation is tted with a hot water tank.
Ensure the distribution valve is tted in the correct
direction.
Channel AB: Outlet to the hydraulic unit.
Channel A open: Return from DHW tank.
Channel B open: Return from the heating circuit.
Waterstage / Installation / 2011 - EN
Page 79
Instructions for the end user
Explain to the user how his installation operates, in particular the functions of the room sensor and
the programmes accessible to them via the user interface.
Emphasise that a heated oor has signicant inertia and that therefore any adjustments must be made
gradually.
Also explain to the end user how to check the lling of the heating circuit.
End-of-life of the appliance
The appliances must be dismantled and recycled by a specialised service. The appliances must not, under
any circumstances, be thrown out with household waste, bulky waste or at a tip.
At the end of its service life, please contact your installer or local representative to proceed with its dismantling
and recycling.
This unit is identied by this symbol. It means that all electrical and electronic products must not be included in household waste.
A specic recycling system for this type of product has been set up in European Union countries (*), Norway, Iceland and Liechtenstein.
Do not try to dismantle this product yourself. It may have damaging eects on your health or on the environment.
Reprocessing of the refrigerant, lubricant and other parts may be performed by a qualied installer in compliance with the local and national legislation in force.
This unit must be recycled by a specialised service and in no case may it be thrown away with household waste, rubble or in a landll.
Please contact your installer or local representative for more .
* Depending on the national regulations of each member state.
Waterstage / Installation / 2011 - EN
- 79 -
Page 80
Quick-start procedure
Before switching on the hydraulic unit:
• Check the electric wiring.
• Check the refrigeration circuit and make sure the it has been gassed.
• Check the hydraulic circuit's pressure (1 to 2 bar), check that the heat pump has been bled, along with the rest of
the installation.
• Make sure that ALL DIP SW on the interface board are OFF before starting up.
Start-up check-list
►
Before starting-up
▼
OKNot compliant
Sight checks Outdoor unit (see chapter "Installation of the outdoor unit", page 18).
Location and ttings, condensate evacuation.
Comply with distances from obstacles.
Hydraulic checks Hydraulic unit (see chapter "Installation of the hydraulic unit", page 20).
Connection of pipes, valves and pumps (heating circuit, DHW).
Installation water volume (expansion vessel of adequate capacity?).
No leaks.
Main system pressure and degassing.
Refrigeration connections and checks (see chapters " Refrigeration connections", page 22).
Check the refrigeration circuits (sealing, no dust or humidity).
Connections between units (pipe length, are tightening torque...).
Installation of HP pressure gauges on the gas line (large tube).
Pump down mandatory.
Nitrogen leak test (~ 10 bar).
Opening of refrigeration valves to outdoor unit.
Filling hydraulic unit and pipes with refrigerant.
Electrical checks Outdoor unit (see chapter " Electrical connections", page 34).
Main power supply (230 V or 400 V).
Protection by rated circuit breaker.
Cable dimensions.
Earth connection.
Hydraulic unit (see chapter "Electrical connections on the hydraulic unit side", page 38).
Connection to outdoor unit (L, N, Earth or 3 L, N, Earth).
Sensors connection (positioning and connections).
Distribution valve connections (boiler and DHW) and circulation pump.
Power supply and protection of electric backup (option).
- 80 -
Waterstage / Installation / 2011 - EN
Page 81
Starting-up
▼
Quick Start Procedure (see chapter " Commissioning", page 44 and § " Controller Menu", page 50).
Close the installation's main circuit breaker (outdoor unit power supply)
2 hours before testing => Preheating of the compressor.
Press the On/O Switch => Initialisation takes several seconds.
Operation of the heating circulation pump.
Outdoor unit starts after 4 mins.
Congure Time, Date and Heating circuit, DHW period programs if dierent from the default values.
Congure the hydraulic circuit.
Adjust the heating gradient.
Adjust the max ow setpoint.
Outdoor unit checks
Operation of fan(s), compressor.
Current measurement.
After several minutes measure the dierence in air temperature.
Check condensation and evaporation pressure/temperature.
Hydraulic unit checks
After 15 mins of operation.
Primary water temp. dierence.
Operation of heating, boiler backup, etc.
Control (see chapter " Controller Menu", page 50)
Settings, maintenance, checks.
Program the heating periods.
Adjust the setpoints for the heating circuits if dierent from the default values.
Setpoint display.
OKNot compliant
Explanations of use
The heat pump is ready for operation !
Waterstage / Installation / 2011 - EN
- 81 -
Page 82
Settings sheet
►
SettingDescriptionSet to.Menus
Preliminary settings
20languageoperator
section
1hour / minutestime & date
2day / monthtime & date
3yeartime & date
5700installation cong.conguration
Heating circuit No. 1
if 2 circuits = the least warm one (e.g.: oor)
710comfort setpointHC1 adjust.
712reduced setpointHC1 adjust.
720heating curve slopeHC1 adjust.
741ow temp setpoint maxHC1 adjust.
750room inuenceHC1 adjust.
790 / 791optimis. at switch-on / offHC1 adjust.
834servomotor travel timeHC1 adjust.
850 / 851oor dryingHC1 adjust.
Heating circuit No. 2 (with 2nd circuit option)
= the warmest one (e.g.: radiators)
1010comfort setpointHC2 adjust.
1012reduced setpointHC2 adjust.
1020heating curve slopeHC2 adjust.
1041ow temp setpoint maxHC2 adjust.
1050room inuenceHC2 adjust.
1090 / 1091optimis. at switch-on / offHC2 adjust.
1134servomotor travel timeHC2 adjust.
1150 / 1151oor dryingHC2 adjust.
Domestic Hot Water (with DHW kit)
1610nominal DHW temp. setpointDHW
1612reduced DWH temp. setpointDHW
1620DHW releaseDHW
1640 to 1642 legionella cycleDHW
5024DHW switch-on differ.DHW tank
5030charging time limitationDHW tank
5061heater releaseDHW tank
SettingDescriptionSet to.Menus
Boiler backup
3700OT.switch-on authoris.addit. gen.
3705swith-off delayaddit. gen.
Miscellaneous
6420input H33 function1conguration
6100OT sensor correctionconguration
6120frost protection on/offconguration
6205reset settingsconguration
6220software versionconguration
6711reset heat pumperror
Cooling
5711cooling unit2 pipesconguration
Faults (if a fault occurs, press"Info" key)
No. 10outdoor sensor
No. 33ow temp. sensor
No. 44return temp. sensor
No. 50DHW temp. sensor
No. 60room sensor 1
No. 65room sensor 2
No. 105maintenance message
No. 121HC1 ow T not reached
No. 122HC2 ow T not reached
No. 127leg. prot. T not reached
No. 369external fault (EX3)
No. 370outdoor unit connect error
6711reset heat pumperror
Heat pump
2844switch-off temp maxheat pump
2884OT auth. to start elec. aux.heat pump
2920 Pk day clear (EX1) rel / lockheat pump
Swimming pool (with "swimming pool" kit)
2056generator setpointSw pool
Outdoor unit faults (see page 75)
- 82 -
Waterstage / Installation / 2011 - EN
Page 83
Commissioning technical datasheet
►
SiteInstaller
Outdoor unit
Refrigerant typeRefrigerant load kg
ChecksOperating voltage & current on outdoor unit
Compliance with positioning distancesL/N or L1/NV
Condensate evacuation correctL2/NV
Electric connections / connections tightnessL3/NV
No GAS leaks (unit ID No.: )L/T or L1/TV
Installation refrigeration connection correct (length
m)
Taken in operation when HOTL3/TV
Compressor discharge temperature °CN/EV
Liquid line temp.°C
Condensation
temperature
Tank water output temperature°CΔCondensation Temp.°C
Tank water input temperature°CΔSecondary Temp.°C
Evaporation temperatureLP = bar°C
Suction Temp.°COverheating°C
Battery air input temperature°CΔEvaporation Temp.°C
Battery air output temperature°CΔBattery Temp.°C
Hydraulic network on hydraulic unit
Secondary system
Domestic hot water; tank type
Estimated water volume of secondary systemL
Options & accessories
Power supply for electric backupRoom sensor T75
Correct location of room sensorWireless room sensor T78
2 circuit kit
Boiler connection kit
Cooling kit
Control settings
Conguration type
Essential settings
Serial No.
ModelModel
HP = bar°CUnder-cooling°C
Underoor heating system
Fan coils
}
Hydraulic unit
L2/TV
IcompA
}
}
}
}
}
}
Circulation pump brandTypeLT Radiators
DetailsDHW kit
Serial No.
Waterstage / Installation / 2011 - EN
- 83 -
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.