Fujitsu AWYZ24LBC, AOYZ14LBT, AOYZ24LBT, AWYZ14LBC, AWYZ18LBC Installation Manual

...
For authorized service personnel only.
(1) For the room air conditioner to operate satisfactory, install it as outlined in this installation manual. (2) Connect the indoor unit and outdoor unit with the air conditioner piping and cords available standards parts. This
installation manual describes the correct connections using the standard accessories and the parts specified in
this installation manual. (3) Have installation work done by authorized service personnel only. (4) Never cut the power cord, lengthen or shorten the cord, or change the plug. (5) Also do not use an extension cord. (6) Plug in the power cord plug firmly. If the receptacle is loose, repair it before using the room air conditioner.
(7) Do not turn on the power until all installation work is complete.
WARNING
Be careful not to scratch the air conditioner when handling it.
After installation, explain correct operation to the customer, using the operating manual.
Let the customer keep this installation manual because it is used when the air conditioner is serviced or
moved.
The maximum length of the piping is 20 m. The maximum height difference of the piping is 15 m, if the units are further apart than these, correct operation can not be guaranteed.
STANDARD ACCESSORIES
The following installation accessories are supplied. Use them as required.
Name and Shape Q’ty Name and Shape Q’ty
Connection pipe assembly
Connection cord
Wall pipe
Decorative tape
Vinyl tape
Wall cap
Saddle
Drain hose
Tapping screws
Sealant
Name
Wall hook bracket
Remote control unit
Battery
Tapping screw(big)
Drain pipe
Cloth tape
1
1
2
8
1
One set of following parts are necessary in istallation of this product.
ELECTRICAL REQUIREMENT
Always make the air conditioner power supply a special branch circuit and provide a special switch and receptacle. Do not extend the power cord.
1
1
2
Tapping screw(small)
Remote control unit holder
Seal A
1
Decide the mounting position with the customer as follows:
1. INDOOR UNIT
(1) Install the indoor unit level on a strong wall which is not subject to
vibration.
(2) The inlet and outlet ports should not be obstructed : the air should
be able to blow all over the room. (3) Install the unit near an electric outlet or special branch circuit. (4) Do not install the unit where it will be exposed to direct sunlight. (5) Install the unit where connection to the outdoor unit is easy. (6) Install the unit where the drain pipe can be easily installed. (7) Take servicing, etc. into consideration and leave the spaces shown
in (Fig. 2). Also install the unit where the dustbox and the filter can
be removed.
2. OUTDOOR UNIT
(1) If possible, do not install the unit where it will be exposed to direct
sunlight. (If necessary, install a blind that does not interfere with
the air flow.) (2) Do not install the unit where a strong wind blows or where it is very
dusty. (3) Do not install the unit where people pass. (4) Take your neighbors into consideration so that they are not dis-
turbed by air blowing into their windows or by noise. (5) Provide the space shown in Fig. 2 so that the air flow is not blocked.
Also for efficient operation, leave open three of the four directions
front, rear, and both sides.
WARNING
Install at a place that can withstand the weight of the indoor and outdoor units and install positively so that the units will not topple or fall.
CAUTION
(1) Do not install where there is the danger of com-
bustible gas leakage. (2) Do not install near heat sources. (3) If children under 10 years old may approach the
unit, take preventive measures so that they can-
not reach the unit. (4) Install the indoor unit on the wall where the height
from the floors more than 230 cm.
SELECTING THE MOUNTING POSITION
[Indoor unit piping direction]
The piping can be connected in the six directions indicated by 1, 2, 3, 4, 5 and 6 in (Fig. 1). When the piping is connected in
direction 1 or 6, cut along the piping groove in the side of the front panel with a hacksaw. When connecting the piping in direction 2 or 4, cut a notch in the thin wall at the front bottom of the front panel.
INSTALLATION DIAGRAM OF INDOOR AND OUTDOOR UNITS
Fig. 2
Fig. 1
3Rear piping
1Right piping
2Bottom piping
4Left-bottom
piping
5Left-rear piping
Fig. 3
54 cm
32 cm
Drain hose
Outdoor unit bottom
6Left piping
NOTE:
In places where the outdoor temperature drops to 0˚C or lower, the drain water may freeze and may stop up the drain or cause other outdoor unit trouble. Therefore take measures so that the drain water will not freeze and clog the drain.
CAUTION
Be sure to remove the top grille at the position where
the front panel is installed and removed.
• Be careful that the top grille may fall and cause per­sonal injury.
CAUTION
Install the open panel and top grill securely. If installation is imperfect, the open panel or top grill may fall off and cause injury.
FRONT PANEL REMOVAL AND INSTALLATION
REMOVING THE FRONT PANEL
(1) Open the open panel, and then remove the top cover and dust box. (For the re-
moval method of dust box, please refer to the OPERATING MANUAL or Dust Box)
(2) Remove the top grille. (For the removal method of top grille, please refer to
the OPERATING MANUAL) (3) Remove the screw cap, and then remove the fixed screws (3 places). (4) Press the under cover with hand at [✗] mark and pull out, and remove inside
hooks (2 places) from the wall hook bracket. (5) Remove the top hooks of under cover (2 places at left and right). (6) Remove the front fixed screws (7 places). (7) Push the lower side of front panel to outside, and remove the lower hooks
from the body. (8) After pull out the upper hooks inside the front panel (2 places at right side and
left upper body, 1 place in the center upper body), pull them back, and re-
move the front panel.
INSTALLING THE FRONT PANEL
(1) Cover the front panel onto the body from the front side, and mount the upper,
central and lower hooks. (2) Install the front fixed screws (2 places at left and right side above the body, 1
place in the center of the body, 2 places under the body, 2 places in the center,
altogether 7 places). (3) Install the top hooks of under cover (2 places at left and right). (4) Install the inside hooks (2 places) and front hooks (2 places) of under cover. (5) Install fixed screws (3 places) and screw cap. (6) Install the top grille. (7) Fix with screws, install top cover and dust box.
Fig. 4
POWER
WARNING
Under cover
[] mark
Front fixed screws (7 places)
Front panel
Screw cap
Fixed screw
Wall hook bracket
Top hook (2 places at left and right)
Front hook (2 places)
Inside hooks (2 places)
PUMP DOWN OPERATION (FORCED COOLING OPERATION)
CAUTION
(1) During the pump down operation, make sure that the compressor is turned off before you
remove the refrigerant piping.
(2)
Do not remove the connection pipe while the compressor is in operation with 2 way or 3 way valve open. This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury.
Upper holes (2 places at left and right)
Lower fixed places (2 places)
Upper middle hooks
Central fixed places (2 places)
Body
Upper hooks (2 places at left and right)
Upper central hooks
Front panel
Central hooks (2 places)
Lower hooks (2 places)
Explain the following to the cus­tomer in accordance with the oper­ating manual: (1) Starting and stopping method,
operation switching, tempera-
ture adjustment, timer, air flow
switching, and other remote
control unit operations.
(2) Dustbox, air filter and top grill
removal and cleaning, and how
to use the air louvers.
(3) Give the operating and instal-
lation manuals to the cus-
tomer.
CUSTOMER GUIDANCE
To avoid discharging refrigerant into the atmosphere at the time of relocation or disposal, recover refrig­erant by doing the cooling operation or forced cooling operation according to the following procedure. (When the cooling operation cannot start in winter, and so on, start the forced cooling operation.) 1 Do the air purging of the charge hose by connecting the charging hose of gauge manifold to the
charging port of 3 way valve and opening the low-pressure valve slightly.
2 Close the valve stem of 2 way valve completely. 3 Start the cooling operation or following forced cooling operation.
When using the remote control unit Press the TEST RUN button after starting the cooling operation by the remote control unit. The operation indicator lamp and timer indicator lamp will begin to flash simultaneously during test run. When using the MANUAL AUTO button of the indoor unit (The remote control unit is lost, and so on.) Keep on pressing the MANUAL AUTO button of the indoor unit for more than 10 seconds. (The forced cooling operation cannot start if the MANUAL AUTO button is not kept on pressing for more than 10 seconds.)
4 Close the valve stem of 3 way valve when the reading on the compound pressure gage becomes
0.05~0 Mpa (0.5~0 kg/cm
2
).
5 Stop the operation.
• Press the START/STOP button of the remote control unit to stop the operation.
• Press the MANUAL AUTO button when stopping the operation from indoor unit side. (It is not necessary to press on keeping for more than 10 seconds.)
[INDOOR UNIT]
6.7 cm or over
Wall hook bracket
6.5 cm or over
5 cm or over
(Wall cap)
Connection Cord
Conform to Type245 IEC57
[OUTDOOR UNIT]
10 cm or over
60 cm or over
10 cm or over
30 cm or over
30 cm or over
150 cm or over
230 cm or
over
Open panel
*The filters come out
of the front of the indoor unit.
Front panel
Remote control unit
Remote control unit holder
40 cm or over
5 cm or over
• Do not directly install it on the ground, otherwise it will cause failure.
(1) The rated voltage of this product is 230 V AC 50 Hz. (2) Before turning on the power, check if the voltage is within the 220
V -10 % to 240 V +10 % range.
(3) Always use a special branch circuit and install a special recep-
tacle to supply power to the room air conditioner.
(4) Use a circuit breaker and receptacle matched to the capacity of
the air conditioner.
(5) Do not extend the power cord. (6) Perform wiring work in accordance with standards so that the
air conditioner can be operated safely and positively.
(7) Install a leakage circuit breaker in accordance with the related
laws and regulations and electric company standards.
CAUTION
(1) The power source capacity must be the sum of the air conditioner current and the current of other electrical appliances. When the
current contracted capacity is insufficient, change the contracted capacity.
(2) When the voltage is low and the air conditioner is difficult to start, contact the power company the voltage raised.
SPLIT TYPE ROOM AIR CONDITIONER
INSTALLATION MANUAL
(PART No. 9314963018-02) (Z14LB/Z18LB)
The basic installation work procedures are the same as conventional refrigerant (R22) models.
However, pay careful attention to the following points:
(1) Since the working pressure is 1.6 times higher than that of conventional refrigerant(R22) mod-
els, some of the piping and installation and service tools are special.(See the table below.) Especially, when replacing a conventional refrigerant(R22) model with a new refrigerant R410A model, always replace the conventional piping and flare nuts with the R410A piping and flare nuts.
(2) Models that use refrigerant R410A have a different charging port thread diameter to prevent
erroneous charging with conventional refrigerant(R22) and for safety. Therefore, check beforehand.[The charging port thread diameter for R410A is 1/2 threads per inch.]
(3) Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with
refrigerant(R22) models. Also, when storing the piping, securely seal the opening by pinching, taping, etc.
(4) When charging the refrigerant, take into account the slight change in the composition of the gas
and liquid phases, and always charge from the liquid phase side whose composition is stable.
This air conditioner uses new refrigerant HFC (R410A).
Special tools for R410A
Copper pipes
It is necessary to use seamless copper pipes and it is desirable that the amount of residual oil is less than 40 mg/10m. Do not use copper pipes having a collapsed, deformed or discolored portion (especially on the interior surface). Otherwise, the ex­pansion value or capillary tube may become blocked with con­taminants. As an air conditioner using R410A incurs pressure higher than when using R22, it is necessary to choose adequate materials. Thicknesses of copper pipes used with R410A are as shown in Table1.Never us copper pipes thinner than 0.8mm even when it is available on the market.
Tool name
Gauge manifold
Charge hose
Vacuum pump
Gas leakage detector
Contents of change
Pressure is high and cannot be measured with a conventional gauge. To prevent erroneous mixing of other refrigerants, the diameter of each port has been changed. It is recommended the gauge with seals-0.1 to 5.3 MPa (-1 to 53 bar) for high pressure.
-0.1 to 3.8 MPa (-1 to 38 bar) for low pressure. To increase pressure resistance, the hose material and base size were changed. A conventional vacuum pump can be used by installing a vacuum pump adapter. Special gas leakage detector for HFC refrigerant R410A.
Table 1 Thicknesses of Annealed Copper Pipes
Thickness (mm)
Nominal diameter
1/4
1/2
Outer diameter
(mm)
6.35
12.7
R410A
0.80
0.80
[ref.] R22
0.80
0.80
(1) Do not use the existing (for R22) piping and flare nuts.
• If the existing materials are used, the pressure inside the refrigerant cycle will rise and cause breakage, injury, etc.(Use the special R410A materials.)
(2) When installing and relocating the air conditioner, do not mix gases other than the specified refrigerant(R410A)
to enter the refrigerant cycle.
• If air or other gas enters the refrigerant cycle, the pressure inside the cycle will rise to an abnormally high value and cause breakage, injury, etc.
WARNING
CAUTION
When installing pipes shorter than 3m, sound of the outdoor unit will be transferred to the indoor unit, which will cause large operating sound or some abnormal sound.
05L314_9314963018-02 2005.12.12, 10:371
INDOOR UNIT
CUTTING THE HOLE IN THE WALL FOR THE CONNECTING PIPING
(1) Cut a 65 mm diameter hole in the wall at the position shown in
(Fig. 5).
(2) When cutting the wall hole at the inside of the wall hook bracket, cut
the hole within the range of the left and right center marks 40 mm below the wall hook bracket. When cutting the wall hole at the outside of the wall hook bracket, cut the hole at least 10 mm below over.
(3) Cut the hole so that the outside end is lower (5 to 10 mm) than the
inside end.
(4) Always align the center of the wall hole. If misaligned, water leakage
will occur.
(5) Cut the wall pipe to match the wall thickness, stick it into the wall cap,
fasten the cap with vinyl tape, and stick the pipe through the hole. (The connection pipe is supplied in the installation set.) (Fig. 5)
(6) For left piping and right piping, cut the hole a little lower so that drain
water will flow freely. (Fig. 5)
INSTALLING THE WALL HOOK BRACKET
(1) Install the wall hook bracket so that it is correctly positioned horizon-
tally and vertically. If the wall hook bracket is tiled, water will drip to the floor.
(2) Install the wall hook bracket so that it is strong enough to withstand
the weight of an adult.
Fasten the wall hook bracket to the wall with 8 or more screws through
the holes near the outer edge of the bracket.
Check that there is no rattle at the wall hook bracket.
FORMING THE DRAIN HOSE AND PIPE
WARNING
If the wall pipe is not used, the cord interconnecting the indoor and outdoor units may touch metal and cause electric leakage.
[Rear piping, Right piping, Bottom piping]
Install the indoor unit piping in the direction of the wall hole and bind
the drain hose and pipe together with vinyl tape. (Fig. 7)
Install the piping so that the drain hose is at the bottom.
Wrap the pipes of the indoor unit that are visible from the outside
with decorative tape.
[For Left rear piping, Left piping]
Interchange the drain cap and the drain hose.
Fig. 5
Fig. 6
Fig. 7
Right outlet
Piping (on top)
Drain hose (on bottom)
Rear outlet
Bind with vinyl tape
Drain cap
Drain hose
Bottom outlet
Remove the drain cap by pulling at the projection at the end of the cap with pliers, etc.
For left outlet piping, cut off the piping outlet cutting groove with a hacksaw.
CAUTION
Install the wall hook bracket horizontally and perpen­dicularly.
Wall hook bracket
Leveling method
Hang weight
from here.
Tapping screw (size: large; quantity: 8)
Wall hook bracket
String
Weight
Lower
Centering marks
Fasten with vinyl tape
(Wall cap)
(Wall pipe)
(Inside) Wall (Outside)
Lower
65 mm hole
65 mm hole
Wall hook bracket
10 mm or over
5~10 mm
CAUTION
(1) In order to align the drain hose and drain cap, be
sure to insert securely and vertically. Incline inser­tion will cause water leakage.
(2) When inserting, be sure not to attach any material
besides water. If any other material is attached, it will cause deterioration and water leakage.
(3) After removing drain hose, be sure not to forget
mounting drain cap.
(4) Be sure to fix the drain hose with tape to the bottom
of piping.
(5) Prevent drain water frozen under low tempera-
ture environment.
When installing indoor unit's drain hose outdoors, necessary measure for frost protection should be taken to prevent drain water frozen.
• Under low temperature environment (when outdoor tempera-
ture under 0 °C), after cooling operation is executed, water in the drain hose could be frozen. Once drain water is frozen, the drain hose will be blocked and water leakage may be resulted for indoor unit.
1. Check if the piping connections are secure.
2. Check that the stems of 2-way valve and 3-way valve are closed fully.
3. Connect the gauge manifold charge hose to the charging port of the 3-way valve (side with the projection for pushing in the valve core).
4. Open the low pressure side valve of the gauge manifold fully.
5. Operate the vacuum pump and start pump down.
6. Slowly loosen the flare nut of the 3-way valve and check if air enters, then retighten the flare nut. (When the flare nut is loosened the operating sound of the vacuum pump changes and the reading of the compound pressure gauge goes from minus to zero.)
OUTDOOR UNIT
OUTDOOR UNIT INSTALLATION
AIR PURGE
Always use a vacuum pump to purge the air. Refrigerant for purging the air is not charged in the outdoor unit at the factory.
Close the high pressure side valve of the gauge manifold fully and do not operate it during the following work.
Set the unit on a strong stand, such as one made of concrete blocks
to minimize shock and vibration.
Do not set the unit directly on the ground because it will cause trouble.
Connector cover removal
Remove the tapping screws.
7. Pump down the system for at least 15 minutes, then check if the compound pressure gauge reads -0.1 MPa (-76 cmHg, -1 bar).
8. At the end of pump down, close the low pressure side gauge of the gauge manifold fully and stop the vacuum pump.
9. Slowly loosen the valve stem of the 3-way valve. When the compound pressure gauge reading reaches 0.1-0.2 MPa, retighten the valve stem and disconnect the charge hose from the 3-way valve charging port. (If the stem of the 3-way valve is opened fully before the charge hose is disconnected, it may be difficult to disconnect the charge hose.)
10. Fully open the valve stems of the 2-way valve and 3-way valve
using a hexagon wrench. (After the valve stem begins to turn, turn it with a torque of less than 2.9 N•m (30 kgf•cm) until it stops turning.)
11. Firmly tighten the 2-way valve and 3-way valve blank cap and
the charging port cap.
Fig. 11
Table 4
Tightening torque
Blank cap (2-way valve) 19.6 to 24.5 N•m (200 to 250 kgf•cm)
Blank cap (3-way valve) 27.4 to 31.4 N•m (280 to 320 kgf•cm)
Charging port cap 12.3 to 15.7 N•m (125 to 160 kgf•cm)
CAUTION
During installation, make sure that the refrigerant pipe is attached firmly before you run the compres­sor. Do not operate the compressor under the condi­tion of refrigerant piping not attached properly with 2-way or 3-way valve open. This may cause abnor­mal pressure in the refrigeration cycle that leads to breakage and even injury.
LO
HI
Fig. 12
Flare nut
3-way valve
-0.1 MPa (-76 cmHg
-1 bar)
High pressure side valve (closed)
Low pressure side valve
Blank cap
Charge hose
Vacuum pump
2-way valve
Valve stem
Charge hose
Charging port cap
Charging port
Gauge manifold
Compound pressure gauge
Pressure gauge
WARNING
(1)
Install the unit where it will not be tilted by more than 5°.
(2) When installing the outdoor unit where it may ex-
posed to strong wind, fasten it securely.
CAUTION
(1) Refrigerant must not be discharged into atmosphere. (2) After connecting the piping , check the joints for
gas leakage with gas leak detector.
Tapping screw
Rear hooks
Connector cover
Front hooks
Installing the connector cover
(1) After inserting the two front hooks, then insert the rear hook. (2) Tighten the tapping screws.
For left piping and left rear piping, align the marks on the wall hook
bracket and shape the connection pipe.
Bend the connection piping at the bend radius of 70 mm or more and
install no more than 35 mm from the wall.
After passing the indoor piping and drain hose through the wall hole,
hang the indoor unit on the hooks at the top and bottom of the wall hook bracket.
[Installing the indoor unit]
Hang the indoor unit from the hooks at the top of the wall hook bracket.
Insert the spacer, etc. between the indoor unit and the wall hook
bracket and separate the bottom of the indoor unit from the wall.
Fig. 8
CONNECTING THE PIPING
CONNECTION
(1) Install the outdoor unit wall cap (supplied with the optional installation set
or procured at the site) to the wall pipe. (2) Connect the outdoor unit and indoor unit piping. (3)
After matching the center of the flare surface and tightening the nut hand tight,
tighten the nut to the specified tightening torque with a torque wrench.(Table 2)
FLARING
(1) Cut the connection pipe to the necessary
length with a pipe cutter. (2) Hold the pipe downward so that cuttings
will not enter the pipe and remove the burrs. (3) Insert the flare nut onto the pipe and flare
the pipe with a flaring tool.
Insert the flare nut (always use the flare nut attached to the indoor and outdoor units re­spectively) onto the pipe and perform the flare processing with a flare tool. Use the special R410A flare tool, or the conv­entional (for R22) flare tool. When using the conventional flare tool, always use an allowance adjustment gauge and se­cure the A dimension shown in table 3.
Check if [L] is flared uniformly and is not cracked or scratched.
Table 2 Flare nut tightening torque
Fig. 9
Flare nut
6.35 mm dia.
12.7 mm dia.
Tightening torque
15.7 to 17.6 N•m
(160 to 180 kgf•cm)
49.0 to 53.9 N•m
(500 to 550 kgf•cm)
Tightening torque standard
(using a 20 cm wrench)
Wrist strength
Arm strength
A (mm)
Table 3 Pipe outside diameter
Pipe outside
diameter
ø 6.35 mm (1/4”) ø 12.7 mm (1/2”)
Flash tool for
R410A, clutch type
0 to 0.5 0 to 0.5
Conventional (R22) flare tool
Clutch type
1.0 to 1.5
1.0 to 1.5
Wing nut type
1.5 to 2.0
1.5 to 2.0
After hooking the indoor unit to the top hook, hook the fittings of the indoor unit to the two bottom hooks while lowering the unit and pushing it against the wall.
Upper hooks
(Lower projections)
Lower slots
Indoor unit
Connection piping
Small piping
Wall hook bracket
Alignment marks
Large piping
Indoor unit
Wall hook bracket
(Spacer)
Tighten with two wrenches.
Torque wrench
Wrench (fixed)
Flare nut
Indoor unit pipe
Connection pipe
To prevent gas leakage, coat the flare surface with refrigerator oil.
9314963018-02
(1) Open the open panel. (2) Remove the top cover. (3) Remove the cord clamp. (4) Route the connection cord from behind the indoor unit.
(1) Match the terminal block numbers and connection
cord colors with those of the outdoor unit. Erroneous wiring may cause burning of the elec­tric parts.
(2) Connect the connection cords firmly to the terminal
block. Imperfect installation may cause a fire.
(3) Always fasten the outside covering of the connec-
tion cord with the cord clamp. (If the insulator is
chafed, electric leakage may occur.) (4) Securely earth the power cord plug. (5) Do not use the earth screw for an external connec-
tor. Only use for interconnection between two units.
Fig. 10
Top cover
CAUTION
(5) Connect the end of the connection cord securely to the terminal block. (6) Secure the connection cord with the cord clamp. (7) Install the top cover with the screw. (8) Close the open panel.
INDOOR UNIT WIRING
Cord clamp
Open panel
Connection cord
Connec­tion cord
Screw
Cord clamp
Screw
Screw
Open panel
CAUTION
(1) Fasten a flare nut with a torque wrench as instructed in this
manual. If fastened too tight, the flare nut may be broken after a long period of time and cause a leakage of refrigerant.
(2) During installation, make sure that the refrigerant pipe is at-
tached firmly before you run the compressor. Do not operate the compressor under the condition of refrigerant piping not attached properly with 2-way or 3-way valve open. This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury.
40 mm
12 mm
35 mm
12 mm
5 mm
5 mm
FINISHING
(1) Insulate between pipes.
For rear, right, and bottom piping, overlap the connection pipe heat insula­tion and indoor unit pipe heat insulation and bind them with vinyl tape so that there is no gap.
For left and left rear piping, butt the connection pipe heat insulation and indoor unit pipe heat insulation together and bind them with and vinyl tape so that there is no gap.
For left and left rear piping, wrap the area which accommodates the rear piping housing section with cloth tape.
For left and left rear piping, bind the connection cord to the top of the pipe with vinyl tape.
For left and left rear piping, bundle the piping and drain hose together by wrapping them with cloth tape over the range within which they fit into the rear piping housing section.
(2) Temporarily fasten the connection cord along the connection pipe with vi-
nyl tape. (Wrap to about 1/3 the width of the tape from the bottom of the pipe so that water does not enter.)
(3) Fasten the connection pipe to the outside wall with saddles, etc. (4) Fill the gap between the outside wall pipe hole and the pipe with sealer so
that rain water and wind cannot blow in.
(5) Fasten the drain hose to the outside wall, etc.
Fig. 15
Fig. 16
Left piping
Connec­tion cord
Drain hose
Connection piping
For connection from the left rear
(Wall pipe)
Connection
cord
Connection piping
Drain hose
Holder
Drain hose
(Included with the piping set sold separately or obtained locally)
Lifted up
Bent
Immersed in water
BAD
BAD BAD
(Saddle)
(Outside wall cap)
(Sealer putty)
(Outdoors)
Wall
Pipe
Pipe
Drain hose
Cloth tape
Wrap with cloth tape
Overlap the insulation
Butt connection pipe (heat insulation) against the indoor unit pipe (heat insulation) and wrap with seal A so that there is no gap.
Connection pipe (heat insulation)
Vinyl tape
Indoor unit pipe (heat insullation)
Seal A
Be sure to install around the drain hose connector.
As the screw is inside, be sure to use screwdriver treated with
magnet.
Removal method of drain hose
Remove the screw at the left
of drain hose and pull out drain hose.
Installation method of drain hose
Vertically insert the drain hose
till the drain furniture aligns with the screw hole of drain cock. After inserting and be­fore replacing, please reinstall and fix the removed screws.
Screw
Drain furniture
Drain hose
Drain cock
Drain furniture
Drain hose
Screw hole
Screw
TEST RUNNING
1. INDOOR UNIT
(1) Is operation of each button on the remote control unit normal? (2) Does each lamp light normally? (3) Do the air flow-direction louver operate normally? (4) Is the drain normal?
2. OUTDOOR UNIT
(1) Is there any abnormal noise and vibration during operation? (2)
Will noise, wind, or drain water from the unit disturb the neighbors?
(3) Is there any gas leakage?
Test run button
Fig. 17
Die
A
Pipe
Perform test operation and check items 1 and 2 below.
For the test operation method, refer to the operating manual.
The outdoor unit, may not operate, depending on the room temperature. In this case, press the test run button on the remote control unit while the air conditioner is running, (Point the transmitter section of the remote control unit toward the air conditioner and press the test run button with the tip of a ball-point pen, etc.)
To end test operation, press the remote control unit START/STOP button.
(When the air conditioner is run by pressing the test run button, the OPERA­TION indicator lamp and TIMER indicator lamp will simultaneously flash slowly.)
Connection cord wiring
Run the connection cord to the rear of the outdoor unit within the A range of the arrows shown in the figure. (The connector cover becomes difficult to install.)
25mm
12mm
5mm
5mm
12mm
30mm
Earth screw
Sheath
Cord clamp
(1) Match the terminal block numbers and connection
cord colors with those of the indoor unit. Erroneous wiring may cause burning of the elec­tric parts.
(2) Connect the connection cords firmly to the terminal
block. Imperfect installation may cause a fire.
(3) Always fasten the outside covering of the connec-
tion cord with the cord clamp. (If the insulator is
chafed, electric leakage may occur.) (4) Securely earth the power cord plug. (5) Do not use the earth screw for an external connec-
tor. Only use for interconnection between two units.
CAUTION
Fig. 14
Connection cord
OUTDOOR UNIT WIRING
(1) Remove the outdoor unit connector cover. (2) Bend the end of the cord as shown in the figure. (3) Connect the end of the connection cord fully into the terminal block. (4) Fasten the sheath with a cord clamp. (5) Install the connector cover.
Connection cord
Cord clamp
Control box
Outdoor unit terminal blockIndoor unit terminal block
Connection cord
Earth screw
Earth screw
Fig. 13
Additional charge
Refrigerant suitable for a piping length of 15 m is charged in the outdoor unit at the factory. When the piping is longer than 15 m, additional charging is necessary. For the additional amount, see the table below.
Table 5
Between 15 m and 20 m, when using a connection pipe other than that in the table, charge additional refrigerant with 20g/1 m as the criteria.
Pipe length
Additional refrigerant
15 m
None
20 m
100 g
CAUTION
(1)
When adding refrigerant, add the refrigerant from the charging port at the completion of work.
(2) The maximum length of the piping is 20 m. If the
units are further apart than this, correct operation can not be guaranteed.
05L314_9314963018-02 2005.12.12, 10:372