Fujitsu AUY12FBAB, AUY14FBAB, AUY18FBAB Installation Instruction Sheet

LO
HI
Gas
Liquid
R410A
1
OUTDOOR UNIT
(1) Install the unit where it will not be tilted by more than
5˚.
(2) When installing the outdoor unit where it may exposed
to strong wind, fasten it securely.
(1) If possible, do not install the unit where it will exposed to direct sun-
light. (If necessary, install a blind that does not interfere with the air flow.)
(2) Install the outdoor unit in a place where it will be free from being dir ty
or getting wet by rain as much as possible. (3) Install the unit when connection to the indoor unit is easy. (4) Do not place animals and plants in the path of the warm air. (5) Take the air conditioner weight into account and select a place where
noise and vibration are small. (6) Select a place so that the warm air and noise from the air conditioner
do not disturb neighbors. (7) Provide the space shown in Fig. 3 so that the air flow is not blocked.
Also for efficient operation, leave open three of the four directions
front, rear, and both sides. (8) During heating operation, drain water flows from the outdoor unit.
Therefore, install the outdoor unit in a place where the drain water
flow will not be obstructed. (Reverse cycle model only)
Fig. 3
INSTALLATION PROCEDURE
Install the air conditioner as follows:
SPLIT TYPE AIR CONDITIONER
INSTALLATION INSTRUCTION SHEET
(PART NO. 9359992097)
WARNING
This mark indicates procedures which, if improperly performed, might lead to the death or serious injury of the user.
CAUTION
This mark indicates procedures which, if improperly performed, might possibly result in personal harm to the user, or damage to property.
This air conditioner uses new refrigerant HFC (R410A).
The basic installation work procedures are the same as conventional refrigerant (R22) models. However, pay careful attention to the following points:
(1) Since the working pressure is 1.6 times higher than that of conventional refrigerant (R22) models, some of the piping and
installation and service tools are special. (See the table below.) Especially, when replacing a conventional refrigerant (R22) model with a new refrigerant R410A model, always replace the conventional piping and flare nuts with the R410A piping and flare nuts.
(2) Models that use refrigerant R410A have a different charging port thread diameter to prevent erroneous charging with con-
ventional refrigerant (R22) and for safety. Therefore, check beforehand. [The charging port thread diameter for R410A is 1/2 UNF 20 threads per inch.]
(3) Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with refrigerant (R22) models. Also, when
storing the piping, securely seal the openings by pinching, taping, etc.
(4) When charging the refrigerant, take into account the slight change in the composition of the gas and liquid phases, and
always charge from the liquid phase side whose composition is stable.
Special tools for R410A
Copper pipes
It is necessary to use seamless copper pipes and it is desirable that the amount of residual oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or discolored portion (especially on the interior surface). Otherwise, the expansion valve or capillary tube may become blocked with contaminants. As an air conditioner using R410A incurs pressure higher than when using R22, it is necessary to choose adequate materials. Thicknesses of copper pipes used with R410A are as shown in Table 1. Never use copper pipes thinner than 0.8 mm (Nominal diameter is 1/4 in., 3/8 in., 1/2 in.), even when it is available on the market.
For authorized service personnel only.
(1) For the air conditioner to operate satisfactorily, install it as outlined in this installation instruction sheet.
(2) Connect the indoor unit and outdoor unit with the air conditioner piping and cords available from our standards parts. This
installation instruction sheet describes the correct connections using the installation set available from our standard parts.
(3) Installation work must be performed in accordance with national wiring standards by authorized personnel only.
(4) Do not turn on the power until all installation work is complete.
Be careful not to scratch the air conditioner when handling it.
After installation, explain correct operation to the customer, using the operating manual.
Let the customer keep this installation instruction sheet because it is used when the air conditioner is serviced or moved.
Refrigerant
R410A
Contents of change
Pressure is high and cannot be measured with a conventional gauge. To prevent erroneous mixing of other refrigerants, the diameter of each port has been changed. It is recommended the gauge with seals –0.1 to 5.3 MPa (–76 cmHg to 53 kgf/cm2) for high pressure. –0.1 to 3.8 MPa (–76 cmHg to 38 kgf/cm
2
) for low pressure. To increase pressure resistance, the hose material and base size were changed. A conventional vacuum pump can be used by installing a vacuum pump adapter. Special gas leakage detector for HFC refrigerant R410A.
Tool name
Gauge manifold
Charge hose
Vacuum pump
Gas leakage detector
Table 1 Thicknesses of Annealed Copper Pipes
Nominal
diameter (inch)
1/4
3/8
1/2
Thickness (mm)
R410A [ref.] R22
0.80 0.80
0.80 0.80
0.80 0.80
Outer diameter
(mm)
6.35
9.52
12.70
INDOOR UNIT INSTALLATION
1. Position the ceiling hole and hanging bolts as shown in Fig. 4.
Fig. 4
(4 directions)
(3 directions)
100 mm (4”) or more
Piping position
(2
directions
)
100 mm (4”) or more
100 mm (4”) or more
(2
directions
)
SELECTING THE MOUNTING POSITION
Pipe
Pipe
INDOOR UNIT
(1) Install the indoor unit on a place having a sufficient strength so that it
withstands against the weight of the indoor unit.
(2) The inlet and outlet ports should not be obstr ucted; the air should be
able to blow all over the room. (3) Leave the space required to service the air conditioner. (Fig. 2) (4) The ceiling rear height is 250 mm (9-3/8”) or more. (5) A place from where the air can be distributed evenly throughout the
room by the unit. (6) A place from where drainage can be extracted outdoors easily.
Fig. 2
Especially, the installation place is very important for the split type air con­ditioner because it is very difficult to move from place after the first instal­lation. Decide the mounting position together with the customer as follows: The discharge direction can be selected as shown below.
Fig. 1
CAUTION
Since 2-way outlet as shown below causes performance problems, do not set it.
Strong and durable ceiling
Obstruction
250 mm (9-3/8”) or more
1,000 mm (39”) or more
1,000 mm (39”) or more
STANDARD PARTS
The following installation parts are furnished. Use them as required.
INDOOR UNIT ACCESSORIES
Name and Shape
Coupler heat insulation
Special nut A (large flange)
Special nut B (small flange)
Template
Remote control unit
Battery (penlight)
Remote control unit holder
Tapping screw (ø3 × 12)
Q’ty
2
4
4
1
1
2
1
2
Application
For indoor side pipe joint
For installing indoor unit
For installing indoor unit
For ceiling hole cutting
Use for air conditioner operation
For remote control unit
For mounting the remote control unit
For remote control unit holder installation
440 mm (17-5/16”)
(Hanging bolt position)
606 mm (23-27/32”)
( 650 mm) (Grille measurement)
( 650 mm (25-15/32”) (Hanging bolt position)
400 mm (15-3/4”)
66 mm (2-19/32”)
2. Hanging preparations
Firmly fasten the hanging bolts as shown in Fig. 5 or by another method.
Fig. 5
Hanging bolt
M10
Hole-in anchor Hole-in plug
Concrete
Insert
(5-5/32)
131 mm
(4-3/8)
111 mm
47 mm (1-27/32)
60 mm (2-3/8)
Drain pipe (I. D. ø32 mm)
600 mm ( 23-5/8) (Ceiling opening measurement)
46 mm (1-27/32)
86 mm (3-3/8)
250 mm (9-27/32)
54 mm (2-1/8)
3. Body installation
(1) Install special nut A, then special nut B onto the hanging bolt. (Fig. 7) (2) Raise the body and mount its hooks onto the hanging bolt between
the special nuts. (Fig. 7) (3) Turn special nut B to adjust the height of the body. (Fig. 7) (4) Leveling
Using a level, or vinyl hose filled with water, fine adjust so that the
body is level.
Perform final tightening by tightening the double nut firmly.
Fig. 7
Vinyl hose
Special nut A
Special nut B
Hook
Hanging bolt
30 mm or more
After installing the body, tighten the nuts.
15 mm (19/32”)
Ceiling
Fig. 8
2
INSTALLING DRAIN PIPE
Note: Install the drain pipe.
Install the drain pipe with downward gradient (1/50 to 1/100) and so there are no rises or traps in the pipe.
Use general hard polyvinyl chloride pipe (VP25) [outside diameter 32 mm (1-1/4)] and connect it with adhesive (polyvinyl chloride) so that there is no leakage.
When the pipe is long, install supporters.
Do not perform air bleeding.
Always heat insulate the indoor side of the drain pipe.
When desiring a high drain pipe height, raise it up to 400 mm (15) or
less from the ceiling within a range of 150 mm (6) from the body. A rise dimension over this range will cause leakage.
Fig. 9
Max. 400 mm (15”)
Rise
Trap
Supporter
1.5 to 2.0 m (5 to 6.5 ft)
Air bleeding
150 mm (6) or less
4
CONNECTING THE PIPING
Do not use the existing (for R22) piping and flare nuts.
If the existing materials are used, the pressure inside the refrigerant cycle will rise and cause breakage, injury, etc. (Use the special R410A materials.)
CAUTION
(1) Do not use mineral oil on flared part.
Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
(2) While welding the pipes, be sure to blow dry nitrogen
gas through them.
(3) The maximum lengths of this product are shown in ta-
ble 2. If the units are further apart than this, correct operation can not be guaranteed.
1. FLARING
(1) Cut the connection pipe to the necessary length with a pipe cutter. (2) Hold the pipe downward so that cuttings will not enter the pipe and
remove the burrs.
(3) Insert the flare nut (always use the flare nut attached to the indoor
and outdoor units respectively) onto the pipe and perform the flare processing with a flare tool. Use the special R410A flare tool, or the conventional (for R22) flare tool. When using the conventional flare tool, always use an allowance ad­justment gauge and secure the A dimension shown in table 4.
Fig. 11
Check if [L] is flared uniformly and is not cracked or scratched.
Die
A
Pipe
L
When bending the pipe, do not bend it as is. The pipe will be collapsed. In this case, cut the heat insulating pipe with a sharp cutter as shown in Fig. 13, and bend it after exposing the pipe. After bending the pipe as you want, be sure to put the heat insulating pipe back on the pipe, and secure it with tape.
CAUTION
(1) To prevent breaking of the pipe, avoid sharp bends.
Bend the pipe with a radius of curvature of 150 mm or over.
(2) If the pipe is bent repeatedly at the same place, it will
break.
Extend the pipe by unwinding it.
Fig. 13
Cut line
Pipe
Heat insulating pipe
Cutter
3. Connection pipes
(1) Indoor unit side
Fig. 14
CAUTION
(1) Be sure to apply the pipe against the port on the in-
door unit correctly. If the centering is improper, the flare nut cannot be tightened smoothly. If the flare nut is forced to turn, the threads will be damaged.
(2) Do not remove the flare nut from the indoor unit pipe
unit immediately before connecting the connection pipe.
When the flare nut is tightened properly by your hand, hold the body side coupling with a separate spanner, then tighten with a torque wrench. (Fig.
15)
Fig. 15
2. Bending pipes
The pipes are snapped by your hands. Be careful not to collapse them.
Fig. 12
Do not bend the pipes in an angle more than 90°. When pipes are repeatedly bent or stretched, the material will harden, making it difficult to bend or stretch them any more. Do not bend or stretch the pipes more than three times.
Indoor unit
Small pipe
Large pipe
Tighten with two wrenches.
Wrench (fixed)
Flare nut
Connection pipe
Indoor unit pipe
Torque wrench
To prevent gas leakage, coat the flare surface with alkylbenzene oil (HAB). Do not use mineral oil.
VACUUM PROCESS
CAUTION
(1) Do not purge the air with refrigerants but use a vacuum
pump to vacuum the installation! There is no extra re­frigerant in the outdoor unit for air purging!
(2) Use a vacuum pump for R410A exclusively. Using the
same vacuum pump for different refrigerants may dam­age the vacuum pump or the unit.
1. VACUUM
(1) Remove the cap, and connect the gauge manifold and the vacuum
pump to the charging valve by the service hoses.
(2) Vacuum the indoor unit and the connecting pipes until the pressure
gauge indicates –0.1 MPa (–76 cmHg).
(3) When –0.1 MPa (–76 cmHg) is reached, operate the vacuum pump
for at least 15 minutes.
(4) Disconnect the service hoses and fit the cap to the charging valve to
the specified torque.
(5) Remove the blank caps, and fully open the spindles of the 2-way and
3-way valves with a hexagon wrench (Torque : 6 to 7 N · m (60 to 70 kgf · cm).
(6) Tighten the blank caps of the 2-way valve and 3-way valve to the
specified torque.
5
- Continued on back -
CAUTION
(1) When moving and installing the air conditioner, do not
mix gas other than the specified refrigerant (R410A) inside the refrigerant cycle.
(2) When charging the refrigerant R410A, always use an
electronic balance for refrigerant charging (to meas­ure the refrigerant by weight).
(3) When charging the refrigerant, take
into account the slight change in the composition of the gas and liquid phases, and always charge from the liquid phase side whose composi­tion is stable.
(4) Add refrigerant from the charging valve after the com-
pletion of the work.
(5) If the units are further apart than the maximum pipe
length, correct operation can not be guaranteed.
3. GAS LEAKAGE INSPECTION
CAUTION
After connecting the piping, check the joints for gas leak­age with gas leak detector.
Fig. 6
1,000 mm (39) or more
CONNECTION PIPE REQUIREMENT
Table 2
10 cm (4”) or more
10 cm (4”) or more
60 cm (2’) or more
60 cm (2’) or
more
60 cm (2’) or more
[12000 and 14000 BTU/h models]
Air
30 cm (1’) or more
30 cm (1’) or more
60 cm (2’) or more
30 cm (1’) or more
60 cm (2’) or more
[18000 BTU/h model]
MODEL
Diameter
Maximum length
Maximum Height (between indoor and outdoor)
Small Large
12000 BTU/h model
14000 and 18000
BTU/h models
6.35 mm (1/4 in.) 6.35 mm (1/4 in.)
9.52 mm (3/8 in.) 12.70 mm (1/2 in.)
20 m (66 ft) 20 m (66 ft)
8 m (26 ft) 8 m (26 ft)
CAUTION
Install heat insulation around both the gas and liquid pipes. Failure to do so may cause water leaks. Use heat insulation with heat resistance above 120 °C. (Re­verse cycle model only) In addition, if the humidity level at the installation location of the refrigerant piping is expected to exceed 70%, install heat insulation around the refrigerant piping. If the ex­pected humidity level is 70-80%, use heat insulation that is 15 mm or thicker and if the expected humidity exceeds 80%, use heat insulation that is 20 mm or thicker. If heat insulation is used that is not as thick as specified, condensation may form on the surface of the insulation. In addition, use heat insulation with heat conductivity of
0.045 W/(m·K) or less (at 20 °C).
ELECTRICAL REQUIREMENT
Electric wire size and fuse capacity:
Table 3
Use pipe with water-resistant heat insulation.
Always use H07RN-F or equivalent to the connection cord.
Install the circuit breaker nearby the units. (Both indoor unit and out-
door unit)
MODEL
Power supply cord (mm2)
Connection cord (mm2)
Fuse capacity (A)
MAX. MIN. MAX. MIN.
12000 and 14000
18000 BTU/h model
BTU/h models
3.0 3.0
2.0 2.5
2.5 2.5
1.5 1.5
15 20
Application
For mounting grille
For mounting grille
For mounting grille
For discharged air
Name and Shape
Bolt
Washer
Spring washer
Blower cover insulation
GRILLE ACCESSORIES
Q’ty
4
4
4
2
OUTDOOR UNIT ACCESSORIES
Application
For outdoor unit drain piping work [Heat & Cool model (Reverse cycle) only]
Q’ty
1
2
1
Name and Shape
Drain pipe
Drain cap
18000 BTU/h model
12000 and 14000 BTU/h models
3
Air flow
Bottom
603 mm (23-23/32”)
Drain pipe mounting hole
Bottom plate
Drain pipe
343 mm (13-1/2
)
Drain cap
[18000 BTU/h model]
Air flow
Bottom
504 mm (21-1/4)
Drain pipe mounting hole
Bottom plate
Drain pipe
285 mm (11-7/32”)
Drain cap
OUTDOOR UNIT
INSTALLATION
Set the unit on a strong stand, such as one made of concrete blocks to minimize shock and vibration.
Do not set the unit directly on the ground because it will cause trouble.
Since the drain water flows out of the outdoor unit during heating op-
eration, install the drain pipe and connect it to an commercial 16 mm hose. (Heat & Cool model (Reverse cycle) only)
When installing the drain pipe, plug all the holes (• hole at one place or two places) other than the drain pipe mounting hole in the bottom of the outdoor unit with putty so there is no water leakage. (Fig. 10) (Heat & Cool model (Reverse cycle) only)
CAUTION
Installation in cold regions. Do not use the accessory drain pipe and drain cap. (If the drain pipe and drain cap are used, the drain water in the pipe may freeze in extremely cold weather.)
Fig. 10
[12000 and 14000 BTU/h models]
Table 4 Pipe outside diameter
Pipe outside
diameter
6.35 mm (1/4 in.)
9.52 mm (3/8 in.)
12.70 mm (1/2 in.)
A (mm)
Conventional (R22) flare tool Clutch type Wing nut type
1.0 to 1.5 1.5 to 2.0
1.0 to 1.5 1.5 to 2.0
1.0 to 1.5 2.0 to 2.5
Flare tool for
R410A, clutch type
0 to 0.5 0 to 0.5 0 to 0.5
CAUTION
Be sure to connect the large pipe after connecting the small pipe completely.
(2) Outdoor unit side
Tighten the flare nut of the connection pipe at the outdoor unit valve connector. The tightening method is the same as that as at the indoor side.
Table 5 Flare nut tightening torque
Do not remove the cap from the connection pipe before connecting the pipe.
Flare nut
6.35 mm (1/4 in.) dia.
9.52 mm (3/8 in.) dia.
12.70 mm (1/2 in.) dia.
Tightening torque
14 to 18 N · m (140 to 180 kgf · cm)
33 to 42 N · m (330 to 420 kgf · cm)
50 to 62 N · m (500 to 620 kgf · cm)
Connecting pipe
Blank cap
Hexagon wrench
3-way valve
Charging port
Cap
Service hose with valve core
Outdoor unit
Use a 4 mm hexagon wrench.
Fig. 16
Gauge manifold
Vacuum pump
Service hose
[12000 and 14000 BTU/h models]
CAUTION
Use a clean gauge mani­fold and charging hose for R410A exclusively.
Gauge manifold
Vacuum pump
Service hose
[18000 BTU/h model]
t
CAUTION
Use a clean gauge mani­fold and charging hose for R410A exclusively.
t
2. Additional charge
Refrigerant suitable for a piping length of 7.5 m is charged in the outdoor unit at the factory. When the piping is longer than 7.5 m, additional charging is necessary. For the additional amount, see the table below.
Table 7
6
INSTALLING THE COUPLER
HEAT INSULATION
After checking for gas leaks, insulate by wrapping insulation around the two parts (large and small) of the indoor unit coupling, using the coupler heat insulation.
Fig. 18
CAUTION
Must fit tightly against body without any gap.
Body
Be sure to overlap the insulation
Coupler heat insulation
No gap
Coupler heat insulation
Table 6
Tightening torque
20 to 25 N · m (200 to 250 kgf · cm)
20 to 25 N · m (200 to 250 kgf · cm)
25 to 30 N · m (250 to 300 kgf · cm)
10 to 12 N · m (100 to 120 kgf · cm)
9.52 mm (3/8 in.)
12.70 mm (1/2 in.)
Blank cap (2-way valve)
Blank cap
(3-way valve)
Charging port cap
7.5 m (25 ft)
None
None
12000 and 14000 BTU/h
models
g/m
(oz/ft)
10 m (33 ft)
25 g
(0.9 oz)
50 g
(1.8 oz)
15 m (49 ft)
75 g
(2.6 oz)
150 g
(5.3 oz)
20 m
(66 ft)
125 g
(4.4 oz)
250 g
(8.8 oz)
10 g/m
(0.35 oz/3.3 ft)
20 g/m
(0.71 oz/3.3 ft)
Additional refrigerant
Pipe length
18000 BTU/h model
Fig. 17
(m3/min)
80 70 60 50 40 30 20 10 0
0
2468
12000 and 14000 BTU/h models
18000 BTU/h model
L=5m
DUCT STATIC PRESSURE
(Pa)
NL
1
(L)2(N)
3456
NL
1
(L)2(N)
345
NL1
(L)2(N)
3456
NL1
(L)2(N)
3
JM1
JM2
JM3
10
REMOTE CONTROL UNIT
INSTALLATION
Install the remote control unit so that the front is facing the photocell. (Fig. 36)
Fig. 36
Install the remote control unit with a distance of 5 m between the re­mote control unit and the grille photocell as the criteria. However, when installing the remote control unit, check that it operates positively.
CAUTION
(1) Check that the indoor unit correctly receives the sig-
nal from the remote control unit, then install the remote control unit holder.
(2) Select the remote control unit holder selection site by
paying careful attention to the following: Avoid places in direct sunlight. Select a place that will not be affected by the heat from a stove, etc.
Remote control unit
Photocell
1. REMOTE CONTROL UNIT HOLDER
INSTALLATION
Install the remote control unit holder to a wall, pillar, etc. with the tap­ping screws.
Fig. 37
1 Set
Remote Control Unit holder fixing
Remote Control Unit mounting
2 Push
Remote control unit
Tapping screws (small)
Remote control unit holder
2. SWITCHING REMOTE CONTROL UNIT SIGNAL CODES
Air conditioner settings
Fig. 38
Indoor unit Printed circuit board
Table 8
Jumper wire
JM3
Connect
Disconnect
Connect
Disconnect
Remote control unit
signal code
A (Primary setting)
B
C
D
JM2
Connect
Connect
Disconnect
Disconnect
(4) Press the MASTER CONTROL button again to return to the clock
display and change the signal code.
Confirm the setting of the remote control unit signal code and the printed circuit board setting. If these are not confirmed, the remote control unit cannot be used to oper­ate for the air conditioner.
Remote control unit settings
(1) Press the START/STOP button and display only the clock.
Fig. 39
(2) Press the MASTER CONTROL button continuously for more than five
seconds to display the current signal code.
Fig. 40
(3) Change the signal code with the button ( ).
Fig. 41
11
TEST RUNNING
Perform test operation and check items 1 and 2 below.
For the operation method, refer to the operating manual.
The outdoor unit may not run, depending on the room temperature.
In this case, the ‘TEST RUN’ signal is received during air conditioner operation (use a metallic object to short the two metal contacts under the battery compartment lid and send the ‘TEST RUN’ signal from the remote control unit).
Fig. 42
Short the two metal contacts under the battery compartment lid.
To end test operation, press the remote control unit START/STOP but­ton. (When the air conditioner is run by pressing the remote control unit TEST RUN button, the OPERATION and TIMER lamps will simultane­ously flash slowly.)
SWING TIMER OPERATION
MANUAL
AUTO
OPERATION LAMP (Red)
SWING LAMP (Orange)
TIMER LAMP (Green)
Operation can be checked by lighting and flashing of the grille display section OPERATION and TIMER lamps. Perform judgment in accordance with the following.
Test running
When the air conditioner is run by pressing the remote control unit test run button, the OPERATION and TIMER lamps flash slowly at the same time.
Error
The OPERATION, TIMER and SWING lamps operate as follows (Table 9) according to the error contents.
Error display
OPERATION
lamp
TIMER lamp
SWING
lamp
Error contents
Model information abnormal (permanent type)
Drain abnormal (permanent type)
Indoor fan abnormal
Room air temperature thermistor open circuit
Room air temperature thermistor short circuit
Piping thermistor open circuit
Piping thermistor short circuit
Goes off
Goes off
Goes off
Goes off
Blinks
Goes off
Blinks
Blinks
Blinks
Blinks
Blinks
Blinks
Blinks
Pulses 4 times
Pulses 6 times
Pulses 2 times
Pulses 3 times
Table 9
CHECK ITEMS
(1) INDOOR UNIT
(1) Is operation of each button on the remote control unit normal? (2) Does each lamp light normally? (3) Do not air flow direction louvers operate normally? (4) Is the drain normal? (5) Is there any abnormal noise and vibration during operation?
(2) OUTDOOR UNIT
(1) Is there any abnormal noise and vibration during operation? (2) Will noise, wind or drain water from the unit disturb the neighbors? (3) Is there any gas leakage?
Do not operate the air conditioner in the test running state for a long time.
12
OPENING THE DUCT
CONNECTION HOLE
Fig. 43
Fresh air
Distribution duct
Distribution duct
CAUTION
(1) When performing hole opening work, be careful not to
damage the drain pan.
(2) When connecting the distribution duct, to make the air
flow easily, block the outlet port with the blower cover insulation as shown by the hatched lines in Fig. 43. For the blocking direction, refer to Fig. 26.
1. DIMENSION
(1) Fresh air duct connection hole and screw positions.
Fig. 44
Unit: mm
79
55
50
36
74
50.8
(2) Distribution duct connection hole and screw positions.
Fig. 45
Unit: mm
6-ø3.3 Self tapping screw holes (for 4mm) P.D 170
130
284
45˚
ø150
CAUTION
The air conditioner cannot take in fresh air by itself. When connecting a fresh air duct, always use a duct fan.
OUTLET AIR
Fig. 46
Duct (inside dia. 150 mm)
Static pressure required to take in fresh air
L
FRESH AIR
Fig. 47
P
Duct
Duct Fan
(m3/min)
70
60 50 40 30
20 10
0
0 0.1 0.2 0.3
(Pa)
DUCT STATIC PRESSURE
13
INSTALLING THE OPTION
PARTS (ADDITIONAL GRILLE)
THE ADDITIONAL GRILLE
Mount the assembled additional grille to the indoor unit (grille) that has been removed from the main unit.
Make sure all areas are properly installed the reinforcement plate.
Mount 4 additional grilles. (Fig. 49)
After confirming proper meshing of the additional grilles, secure them
in place using the 8 screws provided.
Fig. 48
Fig. 49 Illustration of completed mounting
POSITION THE CEILING HOLE AND HANGING BOLTS
Fig. 50
CAUTION
When installing the additional grille, please refer to the in­stallation instruction sheet supplied with the additional grille.
Additional grille
Screw (long)
Reinforcement plate
Screw (short)
Indoor unit (grille)
Additional grille
A
Indoor unit (grille)
Reinforcement plate
400mm (15-3/4”)
606mm(23-27/32)
720mm( 28-11/32)
770mm ( 30-5/16)
(Hanging bolt position)
(Ceiling opening measurement)
(Grille measurement)
(Hanging bolt position)
PART NO. 9359992097
9
POWER
(1) The rated voltage of this product is 230 V A.C. 50 Hz.
(2) Before turning on the verify that the voltage is within
the 198 V to 264 V range.
(3) Always use a special branch circuit and install a spe-
cial breaker to supply power to the air conditioner.
(4) Use a circuit breaker matched to the capacity of the air
conditioner. (Install in accordance with standard)
(5) The circuit breaker is installed in the permanent wir-
ing. Always use a circuit that can trip all the poles of the wiring and has an isolation distance of at least 3 mm between the contacts of each pole.
(6) Perform wiring work in accordance with standards so
that the air conditioner can be operated safely and posi­tively.
(7) Install a leakage circuit breaker in accordance with the
related laws and regulations and electric company standards.
CAUTION
(1) The power source capacity must be the sum of the air
conditioner current and the current of other electrical appliances. When the current contracted capacity is in­sufficient, change the contracted capacity.
(2) When the voltage is low and the air conditioner is diffi-
cult to start, contact the power company the voltage raised.
(3) This air conditioner must be connected to a power
source that has an electrical impedance of 0.25 or less or has a supply current of 100 A or greater. If the power supply does not meet the specifications, con­tact the power company.
8
(Piping direction)
Blower cover insulation
A-A Section view
A
A
2 direction example
Fit the blower cover insulation.
Motor cover assembly
Wire Wire hook
Wire hook
Wire
Bolting the grille assembly to the body
Install the grille assembly to the body with the four bolts, spring washers, and washers.
GRILLE INSTALLATION
1. Blower cover insulation
Install the blower cover insulation only when the outlet direction is not specified. Two blower cover insulations are packed with the grille assembly. Install the blower cover insulation at the diffuser position shown in Fig. 26. At the time, use the piping position as the criteria.
Fig. 26
2. Installing grille assembly to body
Hang the grille assembly on the wires attached to the indoor unit as shown in Fig. 27.
Fig. 27
No gap between ceiling and grille around entire periphery.
Display PCB wire harness
Fig. 28
Wireless unit connection wire wiring
Connect the connector in accordance part A detail view. Then clamp the lead wire with clamp so that it does not touch the rotating parts.
Fig. 29
Bolt
Washer
A
Fig. 30 Part A detail view
Display PCB wire harness
Wire (Louver)
Joint wire (Louver)
(2) Close the intake grille, then slide the two grille stoppers outward.
Fig. 32
2. Removing the intake grille
(1) Slide the two grille stoppers inward, then open the intake grille.
Fig. 33
(2) Remove the grille hook screws, then open the intake grille.
Fig. 34
(3) Open the intake grille so that it is at an angle of 20° to 40°, then
remove the grille.
Fig. 35
Grille hook
INSTALLING/REMOVING THE INTAKE GRILLE
1. Installing the intake grille
(1) Fully inser t the intake grille hooks into the rectangular holes in the
panel.
Fig. 31
Grille stopper
Grille stopper
Intake grille
Panel
Rectangular hole
Grille hook
CAUTION
(1) The louver angle cannot be changed if the power is not
on, (If moved by hand, it may be damaged.)
(2) The grille assembly is directional relative to the air con-
ditioner body.
(3) Install so that there is no gap between the grille as-
sembly and the air conditioner body.
A. Solid wire
Strip 25 mm (15/16
)
Insulation
Loop
B. Strand wire
Strip 10 mm (3/8
)
Round terminal
Wire
Screw with special washer
Round terminal
Terminal board
Wire
Screw with special washer
Round terminal
HOW TO CONNECT WIRING TO THE TERMINALS
A. For solid core wiring (or F-cable)
(1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip
the insulation to about 25 mm (15/16) of expose the solid wire.
(2) Using a screwdriver, remove the terminal screw(s) on the terminal
board.
(3) Using pliers, bend the solid wire to form a loop suitable for the
terminal screw.
(4) Shape the loop wire properly, place it on the terminal board and
tighten securely with the terminal screw using a screwdriver.
B. For strand wiring
(1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip
the insulation to about 10 mm (3/8) of expose the strand wiring.
(2) Using a screwdriver, remove the terminal screw(s) on the terminal
board.
(3) Using a round terminal fastener or pliers, securely clamp a round
terminal to each stripped wire end.
(4) Position the round terminal wire, and replace and tighten the ter-
minal screw using a screwdriver.
Fig. 19
7
ELECTRICAL WIRING
(1) Remove the control box cover and install the connection cord.
(Figs. 20 and 21)
Fig. 20
Control box cover
1
(L)
2
(N)
345
Connection cord
Terminal board
Cord clamp
1
(L)
2
(N)
3456
Connection cord
Terminal board
Cord clamp
[12000, 14000 and 18000 BTU/h Heat & Cool models (Reverse cycle)]
Fig. 23
Terminal cover
[18000 BTU/h Cooling model]
Terminal board
Control box
Cord clamp
Insulation tube
Power supply cord
Connection cord
Terminal board
Control box
Cord clamp
Insulation tube
Power supply cord
Connection cord
[18000 BTU/h Heat & Cool model (Reverse cycle)]
Insulation tube
Insulation tube (Use VW-1,
0.5 to 1.0 mm thick, PVC tube as the insulation tube)
After passing the connection cord through the insulation tube, fasten it with the cord clamp.
Connection cord
Cord clamp
Connection cord
Green/Yellow
1
(L)
2
(N)
3
4
5
L
N
1
(L)
2
(N)
3
4
5
EARTH
EARTH
Green/Yellow
1(L)
2(N)
3
4
5
6
L
N
1(L)
2(N)
3
4
5
6
EARTH
EARTH
Indoor unit side terminal
Power supply
Outdoor unit side terminal
[12000,14000 and 18000 BTU/h Heat & Cool models (Reverse cycle)]
Indoor unit side terminal
Power supply
Outdoor unit side terminal
8
Wire
1. Indoor unit side
WARNING
(1) Before starting work, check that power is not being sup-
plied to indoor unit and the outdoor unit.
(2) Match the terminal board numbers and connection cord
colors with those of the outdoor unit side. Erroneous wiring may cause burning of the electric parts.
(3) Connect the connection cords firmly to the terminal
board. Imperfect installation may cause a fire.
(4) Always fasten the outside covering of the connection
cord with the cord clamp. (If the insulator is chafed, electric leakage may occur.)
(5) Always connect the ground wire.
Fig. 21
[12000 and 14000 BTU/h Cooling models]
Connection cord
Terminal board
Cord clamp
2. Outdoor unit side
(1) Before starting work, check that power is not being
supplied to the indoor unit and outdoor unit.
(2) Match the terminal board numbers and connection cord
colors with those of the indoor unit side. Erroneous wiring may cause burning of the electric parts.
(3) Connect the connection cords and the power supply
cord firmly to the terminal board. Imperfect installation may cause a fire.
(4) Always fasten the outside covering of the connection
cord and the power supply cord with cord clamps. (If the insulator is chafed, electric leakage may occur.)
(5) Always connect the ground wire.
(1) Remove the terminal cover of the outdoor unit, and insert the end of
the connection cord and the power supply cord into the terminal board.
(2) Fasten the connection cord and the power supply cord with the cord
clamps.
(3) Install the terminal cover.
Terminal board
Cord clamp
Insulation tube
Connection cord
Power supply cord
65 mm
80 mm
Control box
CAUTION
When routing the ground wires, leave slack as shown in the illustrations.
[12000 and 14000 BTU/h Heat & Cool models (Reverse cycle)]
Terminal board
Cord clamp Insulation tube
Connection cord
Power supply cord
Control box
45 mm
65 mm
Fig. 25
[12000 and 14000 BTU/h Cooling models]
Fig. 24
[18000 BTU/h Cooling model]
[18000 BTU/h Cooling model]
Terminal cover
Fig. 22
[12000 and 14000 BTU/h Cooling models]
45 mm
45 mm
45 mm
45 mm
Indoor unit side terminal
Power supply
Outdoor unit side terminal
1(L
)
2
( N )
345
L
N
1
(L)
2
(N)
3
EARTH
Green/Yellow
1
(L)
2
(N)
3
4
5
EARTH
Spring washer
Loading...