Fujitsu AUXK018GLAH, AUXK024GLAH, AUXK030GLAH, AUXK034GLAH, AUXK036GLAH Service Manual

...
Page 1
SERVICE MANUAL
Page 2
CONTENTS
1. TEST RUN
1-3 TEST RUN CONTROL................................................................................................
1-2-1 Check Items Before Power ON............................................................................
1-2-2 Check Items After Power ON...............................................................................
...................................................................................
1-1 EXECUTION PROCEDURE AND EXECUTION PRECAUTIONS.............................
1-2-4 Automatic address setting procedure for indoor units..........................................
01-01 01-03 01-03 01-04
01-07
1-2-3 Automatic address setting procedure for Signal amplifiers.................................. 01-06
01
-15
1-4 FIELD SETTING AND MONITOR MODE LIST FOR OUTDOOR UNIT..................... 01-16
2-1 INPUT / OUTPUT LIST..............................................................................................
2. OUTDOOR UNIT OPERATION CONTROL
2-2 COMPRESSOR OPERATION....................................................................................
02-01 02-02
02-02 02-03
2-2-3 Speed Range of Start,Stop,and Operation..........................................................
2-2-2 Capacity Control.................................................................................................
02-02
2-2-1 Operation / Stop Condition.................................................................................
2-5 SPECIAL OPERATION..............................................................................................
02-08 02-08 02-09
2-5-2 Pre-Heat Operation............................................................................................
2-5-1 Oil Recovery Operation......................................................................................
2-6 PROTECTIVE FUNCTION........................................................................................
02-10 02-10
2-6-1 Protective Function List......................................................................................
2-5-3 Defrost Operation Control..................................................................................
02-09
2-3 FAN CONTROL..........................................................................................................
02-04
2-4 EXPANSION VALVE CONTROL...............................................................................
02-07
02-04
0
2-06
2-3-3 Low noise mode..................................................................................................
02-07
2-3-4 Other Control.......................................................................................................
2-3-1 Cooling Operation...............................................................................................
02-05
2-3-2 Heating Operation...............................................................................................
1-2-5 Indoor unit connection check procedure ............................................................. 01-08
1-2-6 Test run from the outdoor Main PCB ........ ........................................................... 01-09
1-2-7 Test run from the Remote controller ..............................................................
...... 01-10
1-5 FIELD SETTING / FUNCTION SETTING FOR INDOOR UNIT.................................. 01-19
1-6 FIELD SETTING / FUNCTION SETTING FOR OUTDOOR AIR UNIT....................... 01-21
Page 3
CONTENTS
3-2 MASTER CONTROL..................................................................................................
3-1-2 "AUTO" Position...................................................................................................
3-1-1 Fan Speed Setting...............................................................................................
3-1 FAN CONTROL...............
...........................................................................................
3. INDOOR UNIT OPERATION
3-2-1,2 Operation Mode Control.....................................................................................
3-2-3,4 Auto Changeover ..............................................................................................
03-01 03-01
03-01 03-02 03-02 03-05
3-3 LOUVER CONTROL..................................................................................................
3-2-5,6,7,8 "COOL"/"HEAT”Position .............................................................................
03-08 0
3-10
3-5 DRAIN PUMP OPERATION.......................................................................................
3-4 ELECTRONIC EXPANSION VALVE CONTROL......................................................
3-6 FUNCTION..................................................................................................................
03-14 03-14 03-15
3-6-1 Auto Restart.........................................................................................................
03-15
3-6-2 Icing Protection Control.......................................................................................
03-15
3-6-3 Oil Recovery Operation.......................................................................................
03-15
03-16
3-7 TIMER CONTROL......................................................................................................
03-17
3-7-1 Wireless Remote Controller................................................................................
03-17
3-7-2 Group Remote Controller..................................................................................... 03-19
3-7-3 Wired Remote Controller..................................................................................... 03-21
3-8 DX-KIT .............................................................................................
03-25
3-8-1 System configuration .......................................................................................
03-25
3-8-2,3 Fundamental functions .................................................................................... 03-26
3-8-4 Electrical expansion valve control for DX-KIT....................................................... 03-28
3-8-5 Drain pump operation for DX-KIT .................................................................... 03-28
3-8-6 Function .................................................................................. 03-29
....
................................
................................
3-6-4 Outdoor temperature protected operation for outdoor..........................................
Page 4
CONTENTS
5-2-1 Indoor Unit............................................................................................................
5-2 WIRING DIAGRAM....................................................................................................
5-1 REFRIGERANT CIRCUIT..........................................................................................
5. APPENDING DATA
5-3-1 Pressure sensor..................................................................................................
05-01
05-03
05-03
5-2-2 Outdoor Unit.........................................................................................................
05-18
5-3 CHARACTERISTICS OF SENSORS........................................................................
05-22
05-22
5-3-2 Thermistor resistance..........................................................................................
05-23
5-3-3 Saturation temperature and saturation pressure tables (R410A)........................
05-24
5-3-4 Temperature and pressure of refrigerant (Graph)...............................................
05-25
6. DISASSEMBLY PROCESS
4-1-2 Outdoor Unit Display...........................................................................................
4-1-1 Indoor Unit Display..............................................................................................
4-1 NORMAL OPERATION..............................................................................................
4. TROUBLE SHOOTING
4-2 ABNORMAL OPERATION.........................................................................................
4-2-1 Indoor Unit Display..............................................................................................
04-01 04-01
04-02
04-03 04-03
4-2-4 Remote Controller Display...................................................................................
4-2-3 Error Code List for Outdoor Unit..........................................................................
4-2-2 Outdoor Unit Display...........................................................................................
4-3 TROUBLE SHOOTING..............................................................................................
04-04 04-05
4-2-5 Error Code List for Simple and Wired Remote Controller...................................
04-07
4-2-6 Error Code List for Group Remote Controller......................................................
04-07
4-2-7 Troubleshooting - No Error code -
rror Code List for External Switch Controller...
..................................................
04-08
4-2-8
Error Code List for Signal Amplifier....................
.................................................
04-08
4-2-9
Error Code List for Network Convertor
......
.........
.................................................
04-08
4-2-10 .................................................
04-08
04-06
04-09
4-3-1 Trouble Shooting With Error Code (Indoor unit) ..........................................
04-09
4-4 SERVICE PARTS INFORMATION............................................................................ 04-106
5-2-3 DX-KIT .........................................................................................................
05-20
........
E .
..................
. ..
4-3-2 Trouble Shooting With Error Code (Outdoor unit) ..........................................
04-39
. ...
4-3-3 Trouble Shooting With No Error Code ..........................................
04-76
. .....................
4-3-4 Trouble Shooting for Option Parts ..........................................
04-82
...........................
....
Page 5
1. TEST RUN
Page 6
Before execution
Execution 1/2
Location decision
Execution procedure and precautions Reason
1-1 EXECUTION PROCEDURE AND EXECUTION PRECAUTIONS
1. TEST RUN
Sleeve and insert work
Indoor unit installation
Refrigerant piping work
Drain piping work
Duct work
Heat insulation work
Electrical work
Outdoor unit foundation work
Outdoor unit installation
Refrigerant piping connection work
Air tightness test
Vacuum drying
Use new refrigerant piping of the thickness specified by the D&T manual.
Since R410A dedicated tools are necessary, prepare them in advance.
Absolutely avoid use of existing piping. If use of existing piping is unavoidable, the piping must be cleaned.
Use pipe that is not dirty inside. Confirm the design for the piping ( Diameter, Thickness ) When the pipe is left standing, protect it. Confirm the angle of separation tube and header correctly. Finish flaring exactly. Confirm the width across flats dimension and shape of flare nuts. Always blow nitrogen while brazing. Perform flushing before connecting the equipment.
Always make the downward slope of the drain pipe 1/100 or greater and make the horizontal length within 20m.
Use hard polyvinyl chloride pipe as the drain pipe. Support the drain pipe between 1.5m to 2.0m. Use pipe of 1 rank up (VP30 or greater) as central piping.
Prevention of water leakage
Foreign matter, water, etc. in the piping will cause faulty cooling and compressor trouble.
Incorrect pipe diameter will cause faulty cooling
Incorrect angle of separation tube or header will be cause poor cooling or refrigerant noise problem
Refrigerant leakage will cause low performance and abnormal stopping
Prevention of water leakage
Prevention of water leakage
Refrigerant leakage will cause low performance and abnormal stopping.
Refrigerant leakage will cause low performance and abnormal stopping.
Mixing in of vacuum pump oil by reverse flow will cause equipment trouble.
Always use a level and keep the indoor unit level. If the equipment is tilted toward the drain port, install it so that the tilt is within 13/32in.(10mm). Excessive tilt will cause water leakage.
Select the size of the heat insulating material according to the ambient temperature and relative humidity of the refrigerant. Use a heat insulating material having a heat conductivity of 0.043W/ (m.k) or less.
When making flare connections always use a torque wrench and tighten the flare nut positively to the specified torque.
Pressurize the product with nitrogen gas up to the design pressure and conduct a 24Hr air tightness test.
Install a vacuum pump with reverse flow check mechanism or a reverse flow check adapter to a conventional vacuum pump and use.
Pump down sufficiently. Approximately 1 hour or longer after -14.5psi (-0.10MPa) reached. Allow to stand for approximately 1 hour after stopping the vacuum pump and confirm that the needle does not return.
Air purging using refrigerant is strictly prohibited.
1
1
1
2
3
2 3 4 5 6
1
2 3 4
2
3
This function is used for vacuuming the indoor unit and the connection piping.
Note: For starting Vacuuming mode, the refrigerant address setting has to be finished.
When the [vacuuming mode] is set, <Push switch setting, F3:21> EEV of connected all indoor units opens. So, the vacuuming indoor unit and piping becomes easier.
When the vacuuming ends, please turn off the power supply for all of the indoor units and the outdoor unit, [vacuuming mode] is released.
*
Vaccuming mode
recommend the vacuuming mode
Do not install the units in the place not recommended in the installation manual.
The performance may drop significantly due to the protection controlling
Use of a refrigerant other than the specified refrigerant will invite equipment trouble
Confirmation of Refrigerant used
Preparation of execution drawings
Confirmation of installation site
Preparation before execution
Check the characteristics of the refrigerant used and grasp the special features of the refrigerant. If refrigerant must be charged, always charge the refrigerant specified for the product.
*Confirm the product design pressure. < R410A 4.2MPa >
Prepare the design for the system
Secure the necessary pressure resistance.
When performing piping work, observe the following items so that the inside of the piping is clean and air tight.
7 8
01-01
Page 7
[Note] Perform in the power OFF state.
Execution 2/2
Set according to the length of the connection piping. Set to "Standard 40 to 65m" at the factory. Set using the push button SW on the outdoor unit main PCB. < Refer to the Page 01-17 Setting mode F2-00 > Set the pipe length to be the nearest indoor unit from the outdoor unit
Set the refrigerant circuit address and indoor unit address. Can be set by rotary SW on the indoor unit PCB ( Main PCB or Switch
PCB) or from a remote controller or from a push button SW on the outdoor unit Main PCB < Automatic address setting, Refer to the Page 01-07 Setting mode F3-11>
Initial setting
Gas leak test
Use an R410A dedicated leak tester to check for gas leaks.
1
2
3
Confirm the additional refrigerant amount with the installation manual, etc.
Always take the R410A refrigerant from the cylinder liquid phase and charge it using the gas phase. (Do not lay a cylinder with siphon pipe on its side.)
Use an R410A dedicated gauge manifold and charging hose. Charge refrigerant using the liquid pipe. When the defined amount of refrigerant cannot charge using the
liquid pipe, charge refrigerant using the gas pipe while opearting the cooling test run. Charge refrigerant bit by bit with cautious operation of valve for the liquid refrigerant back prevention.
If taken from the air phase, since the composition of the refrigerant which is charged will change, low performance and abnormal stop will occur easily.
Prevent erroneous sealing in of refrigerant.
A leak tester for other than R410A cannot detect leaks.
Set the refrigerant circuit address.
ROTARY SW: REF ADX10, X1
4
Turnover & explanation of operation
Address setting for Indoor unit
Test run & adjustment
Piping length setting
Addition refrigerant charging
5
Indoor unit connection check
[Note] Perform setting by push button SW on the outdoor unit Main PCB in the power ON state
 after all indoor units have stopped operation.
When setting the address of Signal amplifier, please refer to the installation manual of the signal amplifier.
The address setting can be set by automatically from 1 outdoor unit on the network. < Refer to the Page 01-06 Setting mode F3-10 >
Address setting for Signal Amp
- When using signal Amps -
[Note] Manual setting: Set the rotary SW on the PCB in the power OFF state.
Automatic address setting: Perform setting by push button SW on the outdoor unit Main PCB in the
 power ON state after all indoor units have stopped operation.
[Note] Perform in the power ON state after all indoor units have stopped operation
[Note] Manual setting: Set the rotary SW on the PCB in the power OFF state.
Automatic address setting: Perform setting by push button SW on the outdoor unit Main PCB in the
   power ON state after all indoor units have stopped operation.
Dual address setting No. is not allowed in one network.
When the setting is not same as the real piping length, the system may not work correctly.
Dual address setting No. is not allowed in one network.
Dual address setting No. is not allowed in one network.
Normal operation will not be possible without performing the indoor unit connection check.
Before starting the system, check on the number of indoor units and the total capacity. < Refer to the Page 01-08 Setting mode F3-12 >
Execution procedure and precautions Reason
1
2
Confirm the DIP SW setting SET 1: Factory setting, SET 2 : All OFF
If the DIP SW setting is wrong, the sys­tem may not work correctly
3
Confirm the Terminal resister setting SET 5-4 OFF: Disable, ON: Enable
If the Terminal resister setting is wrong, the system may detect transmission error
If the pipe length is set as the farthest indoor unit, the nearest operating indoor unit may be stopped the operation by the icing up protection as by over cooling.
01-02
Page 8
Outdoor unit: AJ*072/090LELAH: 20A / AJ*108LELAH: 25A
Indoor unit:
20A
Leakage current: 100 mA 0.1sec or less
Install a breaker (Included with Earth Leakage Circuit Breaker) in accordance
with the related laws and regulations.
Outdoor unit:
2.5mm2 2 wires + Ground
Outdoor unit side: 400V 3 50Hz
Indoor unit side:
Use crimp-type terminals with insulating sleeves for stranded conductor cable
Power source
Shall be no scratches, deformation, etc. (Be careful of deformation of the front panel)
Shall be checked and entered in the check sheet.
Shall be checked and entered in the check sheet.
Connection points check & loose terminal block screws check
0.33mm
2
, shielded wire used (22AWG)
Connection points check & loose terminal panel screws check
Check whether or not the heat insulation material is installed w
ithout a gap.
DIP SW : SET1 (1 ~4), Factory setting SET2, SET3,SET5-1,2,3: ALL OFF
T Refer to the Installation manual 7.2.2
erminal resistor setting SET5 - 4 OFF: Disable, ON: Enable
Refrigerant circuit address setting (SET : REF AD x10 and REF AD x1)
Comparison of calculated value and value written on electrics box. Entered in check sheet.
Refer to the installation manual 8.3.2
Gas pipe: fully open
Liquid pipe: fully open
There shall be no scratches, deformation, tilting, etc.
Shall be checked and entered in the check sheet.
Shall be installed positively.
Connection points check & loose terminal panel screws check
0.33mm
2
, shielded wire used (22AWG)
Connection points check & loose terminal panel screws check
Connection points check & loose terminal panel screws check
Check whether or not the heat insulation material is installed without a gap.
Refrigerant circuit address (REF AD)
Indoor unit add
ress (IU AD)
At automatic address setting, IU AD/REF AD shall be [0].
Remote controller address (RC AD)
Function setting (Remote controller custom code/ external input switching/
auxiliary heater ON-OFF)
Indoor
unit
Outdoor
unit
Judgement standard
Check
Check contentsProcedure
1-2 TEST RUN METHOD
1-2-1 Check Items Before Power ON
01-03
[Note] If operated with the 3-way valve closed, the oil discharged from the compressor will not be returned and will lead to trouble.
Circuit breaker capacity
Type of power source wiring
Supply power source
Appearance
Serial No.
Drain cap installation
Power source wiring connection
Type of communication line
Communication line connection
Type of remote contr
oller wiring
Remote controller wiring connection
Connection piping
Rotary SW setting
DIP-SW setting
Appearance
Serial No.
Outside air temperature
Power source wiring connection
Type of communication line
Communication line connection
Connection piping
DIP-SW setting
Rotary SW setting
Additional refrigerant amount
3-way valve
Wiring on terminal blocks
Power cable: 6.0mm / Earth cable: 6.0mm Limited wiring length : 62 m
Indoor unit:
2
2
2 wire type : 16 to 22AWG (0.33 to 1.25mm ) 3 wire type : 22AWG (0.33mm )
2 2
230V 1 50Hz
Page 9
Addresses shall be assigned to all indoor units / Signal amps. Check for unset or duplicated addresses. < For the setting, Refer to the page 01-06, 07 >
All the indoor units in the same refrigerant
circuit
shall enter the cooling test run
state.
The outdoor units corresponding to the operation capacity of the indoor
units shall operate. < Test operation procedure, Refer to the page 01-09,10 >
Cooling test run
All of the indoor units operation
(after 30 mins)
Automatic address setting
Address read
Outdoor unit circuit breaker ON
Indoor unit circuit breaker ON
Check lighting of Main PCB LED101 and 7-segment display.
Check whether or not indoor unit OPERATION and TIMER lamps flash alternately.
Address setting/ check
There shall be no Error information on the 7-segment display on the Main PCB.
3 Phase: 342 to 456V
These shall be no abnormal sound or abnormal vibration.
The outdoor fan shall not make a moaning sound. There shall be no discharge air leaking from the outdoor duct.
There shall be no pipe chattering sound or flute sound generated.
HPS: 2.7 ~ 3.0 MPa
LPS: 0.9 ~ 1.0 MPa
TH1: 81°C
TH4: 15°C
TH21: 27°C
TH22: 11°C
TH24: 13°C
Shall operate corresponding to the operation capacity of the indoor units.
Service tool used, output (CSV Excel)
Outdoor unit push button SW operation
<On service tool>
High pressure
Low pressure
Discharge pipe temperature (outdoor unit)
Suction pipe temperature (outdoor unit)
Inlet air temperature (indoor unit)
Heat exchange inlet temperature (indoor unit)
Heat exchange outlet temperature (indoor unit)
Compressor operation
Data output
1-2-2 Check Items After Power ON
Function setting
Are the necessary functions set ? < For the setting, Refer to the page 01-16
〜19 >
Outdoor unit Main PCB push button SW setting/check
[Note]
Cooling test run for each refrigerant circuit. If multiple refrigerant circuits are test run at the same time, refrigerant circuit address setting errors cannot be detected.
Judgement standard
Check
Check contentsProcedure
Power ON
Inlet air temperature and outlet air temperature difference shall be 10°C or greater.
There shall be no abnormal sound or abnormal vibration.
There shall be no water leakage. There shall be no condensation on the drain, cabinet, piping, and discharge port.
Shall operate according to the settings. (ON-OFF, set temperature change)
<Indoor unit service tool + actual measurement>
Outlet air temperature
Abnormal sound/abnormal vibration
Water leakage check
Remote controller operation
<Outdoor unit>
Outdoor Main PCB 7-seg. display
Operation voltage
Abnormal sound/ abnormal vibration
[Note] Turn on all indoor units power in the same refrigerant circuit address.
Indoor unit connection check
Are the number of connecting indoor units correct ? Is the total capacity of indoor units correct ? < For the checking, Refer to the page 01-08 >
Indoor unit
connection check
Address record
Address hold check
All the indoor units and outdoor units of the same refrigerant circuit can be checked on the service tool.
Enter the set addresses in the check sheet.
Check whether or not the address setting is held by the service tool after indoor/outdoor circuit breakers were turned OFF to ON.
[Note] Before connecting service tool, the address setting has to be completed.
01-04
When the system operates with the indoor units remaining no power, it is cause of malfunction.
Page 10
Fan operation
Louver operation (except duct)
Outlet air temperature
Abnormal sound/abnormal vibration
Water leakage check
Remote controller operation
Indoor unit individual operation
Shall be switched to all fan speeds in the cooling mode.
Louver shall be switched to all positions. Shall also swing.
Inlet air temperature and outlet air temperature difference shall be 10°C or greater.
There shall be no abnormal sound or abnormal vibration.
There shall be no water leakage. There shall be no condensation on the drain, cabinet, piping, and discharge port.
Shall operate according to the settings. (ON-OFF, set temperature change)
Judgement standard
Check
Check contentsProcedure
These are representative figures of AJ*108LELAH at the standard condition. ( Indoor : 27
°C,
Outdoor : 35°C ) If conditions are different from those above mentioned, the figures will be changed slightly. It depends on following conditions.
Outdoor unit capacity Indoor and outdoor temperature Indoor unit capacity Pipe length etc
<Indoor unit service tool + actual measurement>
1. Error occured
- Check on the Error code on the Remote controller or Indoor unit or Outdoor unit or Service tool and check the description of the Error code.
< Refer to the Trouble shooting in the Service manual.> < Refer to the Execution of precautions 1-1 and Check item Before power ON 1-2-1>
2. No good performance without error code
- Check if the protection controlling is operating or not Evaporator Icing up protection, High discharge temperature protection,etc.
< Refer to the part of protection controlling in the Service manual >
- Check on the refrigerant circuit Refrigerant amount, Pipe blockage, Wrong position of separation pipes etc.
< Refer to the Execution of precautions 1-1 and Check item Before power ON 1-2-1> < Refer to the regulation of installation in the Installation manual>
Trouble shooting on Test run operation
01-05
Page 11
1-2-3 Automatic address setting for signal amplifiers
When using signal amplifiers
When setting the address of the signal amplifier, please use the factory setting.
(See the installation manual of the signal amplifier)
When the system is normal, nothing will be displayed on the 7 segment display.
When ERROR is displayed, inspect the units.
Use the “MODE/EXIT”, “SELECT”, and “ENTER” buttons on the outdoor unit Main PCB to configure settings according to the procedures below.
1: FUNCTION Setting
First 2 digits Last 2 digits
(the display when the main power is turned on)
(When [F4] to [F9] are displayed, continue to press the "SELECT" button until [ F3 ] is displayed)
MODE/EXIT
SELECT
SELECT
ENTER
SELECT
ENTER
Automatic address setting for signal amplifiers
Press the “SELECT” button until "10" is displayed
Press the “ENTER” button for more than 3 seconds
* Setting is complete when the number of unit is displayed
End
ENTER
MODE/EXIT
SWITCH POSITION
SW107 SW108 SW109
MODE
/EXIT
SELECT ENTER
LED101
(GREEN)
POWER
MODE
LED105 LED104
LED102
(RED)
ERROR
Push button switch
7 Segment LED Lamp
Outdoor unit printed circuit board
*
01-06
Page 12
SWITCH POSITION
SW107 SW108 SW109
MODE
/EXIT
SELECT ENTER
LED101
(GREEN)
POWER
MODE
LED105 LED104
LED102
(RED)
ERROR
Push button switch
7 Segment LED Lamp
Outdoor unit printed circuit board
Check that the rotary switch IU AD on the indoor unit Main PCB is set to “00”. If it is not set to “00”, it means the address of that device is not set.
(Factory default is “00”).
Turn on the power of the indoor and outdoor units.
When the system is normal, nothing will be displayed on the 7 segment display.
When ERROR is displayed, inspect the units.
Use the “MODE/EXIT”, “SELECT”, and “ENTER” buttons on the outdoor unit Main PCB to configure settings according to the procedures below.
1: FUNCTION Setting
First 2 digits Last 2 digits
(the display when the main power is turned on)
(When [F4] to [F9] are displayed, continue to press the “SELECT” button until [F3] is displayed.)
M
SELECT
SELECT
ENTER
1-2-4 Automatic address setting for Indoor units
It may take about 10 minutes for completing the processing.
End
First 2 digits Last 2 digits
Press the “SELECT” button until “11” is displayed.
Press the “ENTER” button for more than 3 seconds.
Automatic address setting for indoor units
The number of indoor units with normal settings will be displayed at the first 2 digits of the 7 segment display. The number of indoor units with error will be displayed at the last 2 digits.
NOTE) After the “ENTER” button is pressed, the end processing will occur for about 30 seconds.
During this period, the 7 segment will blink.
ENTER
SELECT
ENTER
Error
Found
01-07
Page 13
SWITCH POSITION
SW107 SW108 SW109
MODE
/EXIT
SELECT ENTER
LED101
(GREEN)
POWER
MODE
LED105 LED104
LED102
(RED)
ERROR
Push button switch
7 Segment LED Lamp
Outdoor unit printed circuit board
1-2-5 Indoor unit connection check
Please perform the indoor unit connection check according to following procedures.
MODE/EXIT
SELECT
SELECT
SELECT
ENTER
LED105
LED104
ENTER
Set to Function mode [F3].
(When [F4] to [F9] are displayed, continue to press the “SELECT” button until [F3] is displayed.)
Press the “SELECT” button until “12” is displayed.
When indoor unit connection check can not be performed
Turn on the powerof indoor unit and outdoor unit.
Press the
“ENTER” button for
more than 3 seconds.
This will be displayed when the Indoor unit connection check starts.
MODE/EXIT
SELECT
ENTER
ENTER
ENTER
(*1)
(*2)
(*1) The number of connected indoor units
(*2) Volume ratio of the indoor units connection
Ex.) When 8 units are connected
Ex.) When the ratio is 120%
Please refer to the following “Error code” for details
[ Note ] Error code
22.1: Connecting Indoor units capacity error
24.2: Connecting number of indoor unit error
26.1: Dual address number is existing
Other Error code: Refer to the Trouble shooting
When it finishes normally, nothing will be displayed on 7 segment display.
When error occurs
Confirm the number of connected indoor units and the volume ratio of the indoor units connection.
Exit indoor unit connection check mode.
01-08
Page 14
1-2-6 Test Run From Outdoor Main PCB
All the indoor units connected to the outdoor unit can be test-operated by push button setting.
LED105 LED104LED105 LED104 LED105 LED104LED105 LED104
LED105 LED104
LED105 LED104
LED105 LED104
[ Cooling test run ]
[ Heating test run ]
[ Test run stop ]
LED105 LED104
LED105 LED104
LED105 LED104
LED105 LED104
Press the ENTER button for at least 3 seconds.
Press the "ENTER" button or Time out ( 5 seconds)
TIXE / EDOM
< Pursuance completion >
< Monitoring condition >
< Mode select condition >
< Return to mode select condition >
< Function select condition >
[ Function mode ]
SWITCH POSITION
SW107 SW108 SW109
MODE
/EXIT
SELECT ENTER
LED101
(GREEN)
POWER
MODE
LED105 LED104
LED102
(RED)
ERROR
Push button switch
7 Segment LED Lamp
Outdoor unit printed circuit board
TEST RUN SETTING
[ Monitoring mode ] [ Setting mode ]
[ Error history mode ]
For a detailed description of push button operation, refer to the [D&T manual Chapter 6. SYSTEM DESIGN]
LED105 LED104
< Return to monitoring condition >
example, Normal indicate : [ Cooling mode ]
[ Central control setting
Forced reset ]
There are the following 2 methods of resetting test operation.
(1) Automatic reset when 60 minutes has elapsed.
(2) Reset when operation stop was performed.
Note
SELECT
SELECT
SELECT
SELECT
SELECT
SELECT
ENTER
ENTER
ENTER
TIXE / EDOM
01-09
Page 15
1-2-7 Test Run From Remote Controller
Press the TEST RUN button on the remote controller, while the air conditioner is running.
To end test run operation, press the remote controller START / STOP button.
When the air conditioner is being test run, the OPERATION and TIMER lamps of indoor unit flash slowly at the same time.
START / STOP button
TEST RUN button
2. Standard wireless remote controller
Stop the indoor unit. Push the button and button simultaneously for more than two seconds. The air conditioner will start to conduct a test run and " " will display on the remote controller display. However, the , setting button does not have function, but all other buttons, displays, and protection functions will operate.
To stop test run, push the START / STOP button of the standard wired remote controller. For the operation method, refer to the operating manual and perform operation check. Check that there are no abnormal sounds or vibration sounds during test run operation.
Perform the test operation for 60 minutes.
1. Standard wired remote controller
UTY - LNH
UTY - RNK
Stop the indoor and outdoor units. Push the remote controller button and button simultaneously for more than three seconds. The air conditioner will start to conduct a test run and " " will display on the temperature display.
SET
However the setting button does not have function but all other buttons, displays and protection functions will operate.
To stop test running press the button of the simple remote controller. For the operation method refer to the operating manual and perform operation check. Check that there are no abnormal sounds or vibration sounds during test run operation.
3. Simple remote controller
UTY - RSK
TIMER MODE
CLOCK ADJUST
TEST RUN
RESET
TIMER
SLEEP
FILTER RESET
SWING
SET
SET
ECONOMY
FANMODE
START
STOP
SET
TEMP.
TIMER MODE DAY
SET BACK
CLOCK ADJUST
DAY OFF
TIMER DELETE TIMER SET
FAN MODE
SET TEMP.
START / STOP
01-10
Page 16
[ Select All (F2) ]: All of R.C.Group (Indoor units) [ Identify Unit (F3) ] : Specific R.C.Group (Indoor unit)
Setup Menu
Indoor unit Special Setting
Test Operation
Central Controller Setting
Indoor unit Special setting
Indoor Unit Set Temp. Range
Filter Sign
R.C. Prohibition
Group
Select All
Identify Unit
Clear Unit
On
Select All
Details
Off
Operation
Help
Setup Menu
Monitor Group
1
2
Monitor - All
UTY-DCG
On
Coll
25.0
05/31 03:59
05/31 03:59
05/31 03:59
Test Operation
05/31 03:59
RCG_05
Test run operating procedure
4. Central remote controller
LED lamp
[ Arrow ] [ MENU ]
[ OK ]
[ CANCEL ]
Function buttons( F1-5 )
< Monitor screen : 9 units display >
< Password verification >
1) Press Button
2) Press the [ Setup Menu (F2) ] button
5) Press the [ Select All (F2) ] button or [ Identify Unit (F3) ] button
6) Press the [ Start (F5) ] button
3) Shift Indoor unit special setting by pressing the [ ] button and [ ] button
4) Shift the Test Operation by pressing the [ ] button and [ ] button
01-11
Page 17
Test run operating procedure
<Monitor screen (icon)>
<Monitor screen (list)>
(1)
(1)
(2)
( * )
(1)
(1)
(2)
( * )
5. Touch panel controller
UTY - DTG
(1) Select the objective you want to test run. Select the objective icon or list at the monitor screen. (Multiple selections is possible) Select all the devices registered as objectives by pressing "Select All" on the monitor screen.
(2) After objective selection at (1), switch to the <Setting screen> by pressing "Operation".
On
C
1
On
On
On
On
On
On
On
On
Office B
Conference
A
Conference B
Meeting 1
Meeting
2
Parking lot
Meeting
3
EntranceRestrantRoom
101
Office A
PC Room
Top Up
Down
List
Heat
Auto
Cool
26.0 C
24.0
C
Auto
22.0
C
Auto
24.0 C
21.5 C
Heat
21.5 C
21.5 C
Cool
Off
Off
Off
All
21.0
C
Heat
All
Lange Group
Lange Group
Top Up
Down
List
Office A
PC Room
Room 101
Restrant
Entrance
Meeting 1
Off
Off
Off
Mixed
Heat
Auto
Cool
24.0 C
26.0 C
Low
Auto
21.5 C
High
Office B
Mixed Mixed Mixed
Mixed
Name
Expand
Status Mode
Set Temp
Fan
R/C Prohibit
On
On
On
Status: On
Status: On
10/11.2008.Mar. 02:20 PM
10/11.2008.Mar. 02:20 PM
Monitor Mode
Monitor Mode
Heat
21.0
C
Off
On
Operation
Clear All
Select All
Schedule
Setting
Off
On
Operation
Clear All
Select All
Setting
Schedule
Group Error
Schedule Filter Sign Op. Controlled Op. Restricted
RC Prohibition All On/Off On
Mode Temp. Timer
Filter
Mode Set Temp.
Group Error
Schedule Filter Sign
Op.Controlled Op.Restricted
01-12
Page 18
<Setting screen>
(3) Switch to the <Details setting screen> by pressing "Optional Setting" on the setting screen.
<Details setting screen>
(4) Send (start) test run by pressing "Start" and then pressing "OK" on the details setting screen.
During sending, the slave screen shown below is displayed. When sending is completed, the sending slave screen and details settingscreen are closed.
To interrupt test run, select the device being test run and execute an operation stop command.
(*) At the monitor screen, test run is reset by stopping operation of the objective devices by pressing "OFF".
(*) Or test operation is reset by stopping operation of the objective
devices by pressing "Off" of Operation and then pressing "OK" on the setting screen.
(3)
(4)
(5)
( * )
Cancel
Off
On
OK
Transferring data. Please wait.
On
On
Reset
Cancel
Stand by (Defrost) Stand by (Oil Recovery) Test Operation
Start
Air Flow Direction
Economy
Anti Freeze
Filter Sign
Operation
Test
Up
Down
Swing
Swing
Left Right
Off
Off
Special State
Status: On
1
2
3
4
5
1
2
3
4
SettingOptional
Cancel
OK
On
Off
Auto
Auto
Cool
Dry
Fan
Heat
Operation Controlled
High
Med
Low
Quiet
Meeting Room
24.0 C
operation
R/C Prohibition
Mode Set Temp. Fan
Optional
Setting
All
On/Off
Filter
Timer
Temp.
Mode
On
10/11.2008.Mar. 02:20 PM
10/11.2008.Mar. 02:20 PM
Air Flow Direction Economy Anti Freeze Filter Sign Test Operation
Control Unit :
Operation Setting
Operation Setting
OK
Status: On
01-13
Test run continues for 60 minutes.
Page 19
(1) Press "Menu" on the monitor screen. the < Main Menu screen > is displayed. (2) Press "Next Page" and press "Maintenance" (3) Press "Next Page" and press "Test Run". the <Test run screen > is displayed. (4) Press "OK"
The test run continues for 60 minutes.
To interrupt test run before it is complet, return to the "Monitor Mode Screen",
and press ON/ OFF.
< Monitor Mode Screen >
< Main Menu Screen >
< Maintenance Screen >
UTY - RNR
< Test Run Screen >
01-14
6. 2-Wire type wired remote controller
Page 20
1-3 TEST RUN CONTROL
01-15
1. When the test run signal is transmitted from standard wired, wireless remote controller, simple remote controller, transmitted network, and outdoor unit.
(1) The test run operation starts and the electric expansion valve is controlled to a maximum flow, regardless of the temperature condition. (2) Frost prevention operation has priority over item(1). (3) Whether state of the indoor unit operates or stops, All units in the same refrigerant circuit will start to conduct a test run in accordance with the operation mode set by push switch of outdoor unit ( see 1 - 2 - 3 ). (4) After 60 minutes passes, the test run stops. (5) Test running initialization is shown below.
Fan speed Hi Hi
Room Temperature Indication 18 30
Hi Hi
18 30
Vertical Air Direction Panel
Swing
Operating Mode
Cooling Heating Cooling Heating
OFF OFF
Position
1
Position
4
EXCEPT FOR THE DUCT MODEL DUCT TYPE
CEILING TYPE
COMPACT FLOOR
COMPACT CASSETTE TYPE
COMPACT WALL MOUNTED TYPE
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
*Example
Set the air outlet selection switch to
Set the air outlet selection switch to
1
2
3
4
1
2
3
4
Page 21
1-4 FIELD SETTING AND MONITOR MODE LIST FOR OUTDOOR UNIT
Push switch on outdoor unit PCB
[ F1 ]
Monitor mode
Setting Mode
ITEM CODE No.
Information contents
Classification
00
Connected number of indoor unit
The number of the communicating unit is displayed
Device and system
01
Software version :
Software version of outdoor unit
[ ] [ ] [ ] [ ] [ ] displays by five items
02 Software version of INV PCB
It skips when there is no suffix
03
Software version of communication PCB
Operation of each part
10 Rotational speed of outdoor unit fan motor
11 Rotational speed of INV compressor
12 Current value of INV compressor
The rotational speed of the outdoor unit fan motor is displayed
[ rpm ]
The rotational speed of the compressor is displayed [ rps ]
Current value of INV compressor is displayed [ A ]
13
14 Pulse of EEV1
Pulse of EEV1 is displayed [ pls ]
15 Pulse of EEV2
Pulse of EEV2 is displayed [ pls ]
Time guard 20 Accumulated current time
21 INV compressor accumulated time
[ Cooling ]
22 INV compressor accumulated time
[ Heating ]
Accumulated current time is displayed
[ 10 hour ]
Accumulated time is displayed in the cooling operation of the
INV compressor
[ 10 hour ]
Accumulated time is displayed in the heating operation of the
23
INV compressor
[ 10 hour ]
Refrigerant cycle data 1
Refrigerant cycle data 2
30
Information on Thermistor 1
(
INV compressor discharge temperature sensor
)
32
33
34
The value of the Thermistor 1 is displayed
31
The value of the Thermistor 3 is displayed
The value of the Thermistor 4 is displayed
35
C ] or [°F ]
C ] or [°F ]
C ] or [°F ]
The value of the Thermistor 7 is displayed
The value of the Thermistor 9 is displayed
C ] or [°F ]
C ] or [°F ]
The value of the pressure sensor 1 is displayed [ MPa ] or [ psi ]
The value of the pressure sensor 2 is displayed [ MPa ] or [ psi ]
36
37
38
39
Forbidden
Forbidden
50 Information on pressure sensor 1
( High pressure sensor )
51 Information on pressure sensor 2
( Low pressure sensor )
Refrigerant
40
cycle data 4
Refrigerant cycle data 3
01-16
Information on Thermistor 5
(
Heat-exchanger (outlet) temperature sensor )
Information on Thermistor 7
(
Liquid temperature sensor 2 )
Forbidden
Information on Thermistor 9
( Sub-cool heat-exchanger (outlet) temperature sensor )
Information on Thermistor 10
( INV compressor temperature sensor )
Information on Thermistor 4
( Outdoor temperature sensor )
( Suction temperature sensor )
Information on Thermistor 3
Forbidden
Forbidden
Forbidden
The value of the Thermistor 10 is displayed
C ] or [°F ]
The value of the Thermistor 5 is displayed
C ] or [°F ]
Page 22
Push switch on outdoor unit PCB
[ F2 ]
Monitor mode
Setting Mode
ITEM CODE No.
ITEM CODE No.
Information contents DefaultClassification
00
10 11
12
13,14
20
21
25,26,27
28
29
30
35,36,37 38,39
00 01 02
00
03
00 01
04 00 01 02 03
00
1010
00 00
02
00
01
00
02 03
Pipe length setting
Cooling capacity shift
Heating capacity shift
16,17
00
Forbidden Switching between forced stop or
Operation mode selecting method
22,23,24 Forbidden
Change of unit (Temperature)
Change of unit (Pressure)
Energy saving level setting
40-65m 0-40m 65-90m 90-120m
10 Forbidden
Forbidden Factory default
Factory default
Factory default Factory defaultForbidden
Normal mode
Factory defalt
Save energy mode +2
°C
High power mode 1 -2 °C High power mode 2 -4
°C
Normal mode Save energy mode -2
°C
High power mode 1 +2°C High power mode 2 +4°C
Forced stop
Factory default
Celsius (
°C)
Disable (°F) MPa
psi Level 1 (stop) Level 2 (operated at 40% capacity) Level 3 (operated at 60% capacity) Level 4 (operated at 80% capacity) Level 5 (operated at 100% capacity)
Emergency stop Priority given to the first command Priority given to the external input of outdoor unit Priority given to the master indoor unit
Forbidden
Install
Correction
Change of
emergency stop
00 01 00 01 00
31,34,35
Forbidden
00
01 02 03 04
function 1
Change of
function 2
01-17
40
41
42
50,51,60, 61,64
Capacity priority setting
Low noise mode setting
Low noise level setting
Forbidden
Factory defalut
Level 1
Off (quiet priority) On (capacity priority) Off (Normal) On (Low noise mode operation is always done)
00 01 00
00
00
01
Low noise
setting 1
70
71
72
3737
Electricity meter No. setting 1
( Set the ones digit and tens digit of the No. of the electricity meter connected to CN135 )*1
Electricity meter No. setting 2
( Set the ones digit and tens digit of the No. of the electricity meter connected to CN135 )*1
Electricity meter pulse setting 1
( Set the ones digit and tens digit of the No. of
Electricity meter pulse setting 2
Setting number x00~x99 ( Refer to Design & Technical Manual for details.)
Setting number 0xx~2xx ( Refer to Design & Technical Manual for details.)
Setting number xx00~xx99 ( Refer to Design & Technical Manual for details.)
Setting number 00xx~99xx ( Refer to Design & Technical Manual for details.)
00
00
00
00
00~99
00~02
00~99
00~99
the electricity meter pulse setting connected
to CN135 )*2
( Set the ones digit and tens digit of the No. of
the electricity meter pulse setting connected
to CN135 )*2
Change of
function 4
Change of
function 3
*1 : When electricity meter No. is set to "000" and "201 to 299", the pulses input to CN135 become ineffective.
Available setting number is "001" to "200"
*2 : When the electricity meter pulse setting is set to "0000", the pulses input to CN135 become ineffective.
Available setting number is "0001" to "9999"
Level 2
01
Page 23
Push switch on outdoor unit PCB
[ F3 ]
Monitor mode
Setting Mode
ITEM CODE No.
Setting Function
Classification
Meaning of Error History Number
ITEM CODE No.
Information contents
Classification
00
Cooling test run
Forced thermostat-ON in Cooling.
01
Heating test run
Forced thermostat-ON in Heating.
02
03,04
Test run stop
Forbidden
Test run is stopped.
10
Signal amplifier automatic address
11
12
Indoor unit automatic address
Indoor unit connection check
Automatic address setting operates for indoor unit of same
The number of indoor units and the total capacity of indoor units
Automatic address setting operates for signal amplifier.
refrigerant circuit.
of same refrigerant circuit.
21
Vacuuming mode
Vacuuming mode operates Refer to page 01-01 for the function.
30
31
Error history clear
Forbidden
All the abnormal code histories are cleared.
32
Current time clear
Accumulated current time becomes [ 0 ]
33
INV compressor accumulated time clear
Accumulated time of the INV compressor becomes [ 0 ]
35
Field setting all clear
Return to default the all set items.
36
Clear memorized information of “F3 - 12” ( Indoor unit connection check )
The information of the number of indoor units and the total
40
Abnormal reset
It was displayed when abnormality occurs, and the total
41
Maximum memorized indoor unit number reset
Maximum memorized indoor unit number is reset
91
Forced Central control function release
When the centralized control device failure, and the centralized control setting cannot be released, this function is used.
All the limitations set with the centralized control device are released.
“E14.5 : Indoor unit number shortage ” error is cleared.
code is reset.
This is a function that uses to clear abnormal display after the repair is completed.
Please operate the switch after power off or power on the outdoor unit.
capacity of indoor units are cleared.
Forced
Push switch on outdoor unit PCB
[ F9 ]
Monitor mode
00
1 time ago (Newest)
01
2 time ago
02
3 time ago
03
4 time ago
04
5 time ago
05
6 time ago
06
7 time ago
07
8 time ago
08
9 time ago
09
10 time ago
When the error occurred, the error code is memorized up to 10 on Main PCB.
If the memorized error code becomes over 10, the oldest one will be erased.
Error history
operation
Install and maintenance 1
Install and maintenance 2
Refer to Chapter 4.TROUBLE SHOOTING
4-3-2 Error Code List for Outdoor unit
Compressor Motor Loss of Synchronization Compressor 1 Temperature Abnormal Inverter Compressor Start Up Error Discharge Temperature 1 Abnormal Low Pressure Abnormal Current Sensor 1 Error Trip Detection Rush Current Limiting Resistor Temp Rise Protection Outdoor Unit FAN motor 1 Lock Error Outdoor Unit FAN motor 2 Lock Error
*
< Reset Error Item List By Abnormal Reset Setting >
Reset
Specialty function
Clear
01-18
20
Forbidden
37
Forbidden
90
Forbidden
Page 24
Function
Function
number
Setting number Default Details
Filter
indicator
interval
11
00 Standard
Adjust the lter cleaning interval notification. If the notification is too early, change to setting 01. If the notification is too late, change to setting 02.
01 Longer 02 Shorter
Filter
indicator
action
13
00 Enable
Enable or disable the lter indicator. Setting 02 is for use with a central remote control.
01 Disable
02
Display only on
central remote
control
Ceiling
airow
20
00 Standard
Regulate the airow according to the needs of the installation location. When set to 01, the air ow will be stronger. (Cassette type only)
01 High Ceiling
Vertical
airow
direction
23
00 Standard
Adjust the ver tical air ow direction. All air ow direction louvers are adjusted together.
(Cassette type only)
01 Raise
Horizontal
swing
airow
direction
24
00 Standard
Adjust the horizontal swing airow direction.
(For horizontal swing equipped models)
01 Left half
02 Right half
Static pressure 26
00 SP mode 00
01
02
Indoor unit address 00
Ref. circuit address 00
00~63
00~99
Model name
Range of static
pressure
Normal static
pressure
ARXK07GCLH
SP mode 00 to 03 10 PaARXK09GCLH ARXK12GCLH ARXK14GCLH
SP mode 00 to 05 15 PaARXK18GCLH ARXK24GCLH ARXD04GALH
SP mode 00 to 09
(0 to 90 Pa)
25Pa
ARXD07GALH ARXD09GALH ARXD12GALH ARXD14GALH ARXD18GALH
ARXD24GALH
SP mode 00 to 05
(0 to 50 Pa)
ARX A24GBLH
SP mode 00 to 14
40Pa
ARX A30GBLH
50Pa
ARX A36GBLH SP mode 00 to 12 ARX A45GBLH SP mode 00 to 11 60Pa ARXC36GBTH SP mode 02 to 16 100Pa ARXC72GBTH SP mode 04 to 27
150PaARXC90GBTH SP mode 05 to 24 ARXC96GATH SP mode 05 to 29 ARXN18GATH SP mode 05 to 10
50Pa
ARXN24GATH SP mode 05 to 15 ARXN30GATH
SP mode 05 to 25
ARXN34GATH ARXN36GATH
60Pa
ARXN45GATH
Please refer to "Chapter04 7.FAN PERFORMANCE CURVE" for the characteristics of each indoor unit.
01 SP mode 01
02 SP mode 02
03 SP mode 03
04 SP mode 04
05 SP mode 05
06 SP mode 06
07 SP mode 07
08 SP mode 08
09 SP mode 09
10 SP mode 10
11 SP mode 11
12 SP mode 12
13 SP mode 13
14 SP mode 14
15 SP mode 15
16 SP mode 16
17 SP mode 17
18 SP mode 18
19 S
P mode 19
20 SP mode 20
21 SP mode 21
22 SP mode 22
23 SP mode 23
24 SP mode 24
25 SP mode 25
26 SP mode 26
27 SP mode 27
28 SP mode 28
29 SP mode 29
31 Normal SP
Cool air tem-
perature trigger
30
00 Standard
Adjust the cool air trigger temperature. To lower the trigger
temperature, use setting 01. To raise the trigger temperature,
use setting 02.
01 Adjust (1)
02 Adjust (2)
Heat air tem-
perature trigger
31
00 Standard
Adjust the heat air trigger temperature. To lower the trigger
temperature by 6 degrees C, use setting 01. To lower the trigger temperature by 4 degrees C, use setting 02. To raise the trigger temperature, use setting 03.
01 Adjust (1) 02 Adjust (2) 03 Adjust (3)
FUNCTION
FUNCTION
SETTING
1-5 FIELD SETTING / FUNCTION SETTING FOR INDOOR UNIT
Address
01-19
Page 25
Function
Function
number
Setting number Default Details
*1 Auto
restart
40
00 Enable
Enable or disable automatic system restart after a power outage.
01 Disable
Cool Air
Prevention
43
00 Super low
Restrain the cold airow with making the airow lower when star ting heating operation. To correspond to the ventilation, set to 01.
01
Follow the setting
on the remote
controller
External
control
46
00 Start /Stop
Allow an external controller to start or stop the system, or to perform an emergency stop, or to perform a forced stop.
* If an emergency stop is performed from an external controller, same
refrigerant system will be disabled.
* If forced stop is set,indoor unit stops by the input to the external input
terminals,and Start /Stop by a remote controller is restricted.
01 Emergency stop
02 Forced stop
Error report target
47
00 All
Change the target for reporting errors. Errors can either be reported in all locations, or only on the wired remote.
01
Display only on
central remote
control
Fan setting
when cooling
thermostat OFF
49
00
Follow the setting
on the remote
controller
When set 00, Indoor unit is continued operation based upon Central remote controller or individual controller set. Once indoor unit received signal from External controller, Indoor unit changed Fan mode forcibly.
When set 01, Indoor unit is continued operation based upon Central remote controller or individual controller set. Once indoor unit received signal from External controller, Indoor unit stop forcibly.
Connection of the wired remote controller (2-wire type or 3-wire type) and switching its
thermistor are necessary.
01 Stop
*1 : Auto restart is an emergency function such as for power failure etc.
Do not start and stop the indoor unit by this function in normal operation. Be sure to operate by the control unit, converter or external input device.
FUNCTION
SETTING
FUNCTION
SETTING
01-20
Page 26
Function
Function
number
Setting number Default Details
Filter
indicator
interval
11
00 Standard
Adjust the lter cleaning interval notication. If the notication is too early, change to setting 01. If the notication is too late, change to setting 02.
01 Longer 02 Shorter
Filter
indicator
action
13
00 Enable
Enable or disable the lter indicator. Setting 02 is for use with a central remote control.
01 Disable
02
Display only on
central remote
control
Static pressure 26
05 SP mode 05
Model name
Range of static
pressure
Normal static
pressure
ARXH054GTAH
SP mode 05 to 19
(50 to 185 Pa)
185Pa
ARXH072GTAH
SP mode 05 to 20
(50 to 200 Pa)
200Pa
ARXH096GTAH
SP mode 05 to 22
(50 to 220 Pa)
200Pa
06 SP mode 06
07 SP mode 07
08 SP mode 08
09 SP mode 09
10 SP mode 10
11 SP mode 11
12 SP mode 12
13 SP mode 13
14 SP mode 14
15 SP mode 15
16 SP mode 16
17 SP mode 17
18 SP mode 18
19 SP mode 19
20 SP mode 20
21 SP mode 21
22 SP mode 22
31 Normal SP
*1 Auto
restart
40
00 Enable
Enable or disable automatic system restart after a power outage.
01 Disable
Cool Air
Prevention
43
00 Prohibited
Setting change prohibited.
01
Follow the setting
on the remote
controller
External
control
46
00 Start /Stop
Allow an external controller to start or stop the system, or to perform an emergency stop, or to perform a forced stop.
* If an emergency stop is performed from an external controller, same
refrigerant system will be disabled.
* If forced stop is set,indoor unit stops by the input to the external input
terminals,and Start/Stop by a remote controller is restricted.
01 Emergency stop
02 Forced stop
Error report target
47
00 All
Change the target for reporting errors. Errors can either be reported in all locations, or only on the wired remote.
01
Display only on
central remote
control
Humidier
contro
l
63
00 mode 00
Select control conditions of external output. "Mode 0 0" is output when heating thermostat is ON, "Mode 01" is output in heating operation, "Mode 02" is output in heating operation and in fan operation.
01 mode 01
02 mode 02
1-6 FIELD SETTING / FUNCTION SETTING FOR OUTDOOR AIR UNIT
01-21
Page 27
2. OUTDOOR UNIT OPERATION CONTROL
Page 28
2-1 INPUT / OUTPUT LIST
2. OUTDOOR UNIT
02-01
Input / output or kind of detail Control range
Discharge pressure sensor <HIGH> Pressure sensor Measure range 0.0 to 5.0MPa Suction pressure sensor <LOW> Pressure sensor Measure range 0.0 to 1.7MPa Discharge temperature sensor <TH1> Themistor <Blue>
Measure range 10 to 130
Heat exchanger temperature sensor <TH5> Themistor < >
Measure range -35 to 70
Sub-cool heat exchanger (outlet) sensor<TH9> Themistor < White>
Measure range -35 to 70
Liquid temperature sensor <TH7> Themistor <Green>
Measure range -35 to 70
Suction temperature sensor <TH4> Themistor <Red>
Measure range -35 to 70
Outdoor temperature sensor <TH3> Themistor < - >
Measure range -25 to 58
Operation current sensor Current sensor
Rotary SW & DIP-SW & Push SW
Electronic expansion valve 1 (Main) EEV coil Operating voltage DC12V Electronic expansion valve 2 (SC-Hex) EEV coil Operating voltage DC12V
4-way valve 4-way valve coil AC220-240V, 50/60Hz 6/5 W Crank case heater
For Inverter Compressor AC240V, 35W
Base heater Field supply
AC220-240V, 35W
LON WORKS Inverter communication
External input 1 (CN131) (
Low noise mode operation) External input 2 (CN132) (Cooling / Heating priority) External input 3 (CN133) (Outdoor unit operation peak control) External input 4 (CN134) (Emergency stop operation)
Dry contact input
Single LED 101 Single LED 102
LED display
Address and function setting
Display the information on operation,
error and
setting with single LED and
7 segment LED.
Control output: DC 0/12-24V, Max.30mA Control output: DC 0/12-24V, Max.
30
mA
External output 1 (CN136) (Error display) External output 2 (CN137) (Operation display)
ON (Error) / OFF (Normal) ON (Operation) / OFF (Stop)
Communication Input / Output
External Input / Output
I N P U T
O
U T P U T
Compressor temperature sensor <TH10> Themistor < - > Measure range 10 to 130
Pressure switch
Pressure switch
Open 4.2MPa Short 3.2MPa
Fan motor 1 (Upper) DC Brushless motor
7 Segment LED
Compressor
Indoor unit Outdoor unit
Fan motor 2 (Lower) DC Brushless motor
DC Inverter compressor
Brown
Page 29
2-2-1 Operation / Stop Condition
When cooling requirement capacity or heating requirement capacity from either of the indoor units in the same refrigerant circuit is input, the compressor operates. When all the indoor units in no "cooling requirement capacity" or "heating requirement capacity",
the compressor is stopped. But in the following case, the compressor operates in accordance with operation of each mode.
During 3 minute restart prevention operation Icing protection Failure (Refer to chapter 4, TROUBLE SHOOTING ) Under expansion valve initialization At protective operation
Emergency stop Defrost operation
02-02
2-2 COMPRESSOR OPERATION
2-2-2 Capacity Control
(1) Capacity of compressor operation
By the operation of DC inverter rotary compressor, the amount of required refrigerant circulation acceding to cooling and heating load can be supplied from compressor efficiently.
DC inverter rotary compressor is able to control the amount of required refrigerant circulation in details.
Cooling/Heating load
Capacity of
compressor operation
Total capacity
Peak cut stop operation
Inverter Compressor
Page 30
(2) Target low-pressure and high-pressure control
In order to make the evaporation pressure of the indoor unit at the proper pressure on a variety of operations, capacity of the compressor will be controlled by low-pressure sensor of the outdoor unit.
In order to make the condensation pressure of the indoor unit at the proper pressure on a variety of operations, capacity of the compressor will be co
ntrolled by high-pressure sensor of the outdoor unit.
Target low-pressure and high pressure temperature depends on system capacity, capacity of compressor operation, pipe length, and capacity shift switch settings.
<Cooling>
<Heating>
02-03
2-2-3 Speed Range of Start, Stop, And Operation
On stop mode : 0 rps
On operating mode : 15 - 120 rps
(1) Heating starting process
*The compressr starting process in cool mode does not have the limitated hold controlling.
For Heating operation only, the upper limit speed at starting is made 40rps and is raised in +10rps increments every 60 seconds.
Speed
Time
0
40rps
60sec
Target speed
180
sec
60sec
50rps
60rps
70rps
60sec
240
sec
300
sec
360
sec
80rps
10rps
10rps
The compressor operates at the upper limit speed if the target speed is higher than the upper limit speed.
The compressor operates at the target speed if the target speed is lower than the upper limit speed.
60sec
10rps
Page 31
Switching conditions of step
2-3 FAN CONTROL
2-3-1 Cooling Operation
Fan step
11
10
9
8
7
6
5
4
3
2
1
0
680 680 660 660 590 510 520
400 440
330 380 300 300 300 450
0
300
0
0
0 0 0
Fan speed (rpm)
02-04
(Conditions which lower the fan speed) High-pressure saturation low limit of target high-pressure
saturation range and heat sink temperature
(Conditions which raise the fan speed) High-pressure saturation upper limit of target high-pressure saturation or heat sink temperature
Fan step
9
7
4
0
Outside air temperature sensor detected value
TAOUT 30°C
30°C TAOUT 20°C
20°C TAOUT 10°C
10°C TAOUT
The initial speed of the outdoor unit is detected by out door temperature sensor.
30 37.4
40.4
46.6
54
High-pressure saturation temperature
Outdoor temperature
Upper limit of target high-pressure saturation temp.
Low limit of target high-pressure saturation temp.
Target high-pressure saturation temp.
Thereafter, the high-pressure is monitoring at a set time interval and the fan speed is changed by the following conditions.
The fan is controlled to keep high puressure saturation temperature within the target range as follows
780 740 660 660 590 510 520
400 440
330 380 300 300 300 450
0
300
0
0
0 0 0
790 710 700 620 590 510 520
400 440
330 380 300 300 300 450
0
Intermittent 1
0
0
0 0 0
Step
Upper FAN Lower FAN
AJ*072LELAH
AJ*090LELAH AJ*108LELAH
13
12
-
-
-
-
-
-
-
-
960 880 870
790
Intermittent 2
300
Intermittent 1
Intermittent 2
Intermittent 1
Intermittent 2
Intermittent 1 : 14 sec. ON (300rpm), 17 sec. OFF
Intermittent 2 : 19 sec. ON (300rpm), 17 sec. OFF
47.8
55°C: 8&10HP 60°C: 12HP
60°C: 8&10HP 65°C: 12HP
Page 32
02-05
2-3-2 Heating Operation
Switching conditions of step
Fan step
8HP&10HP: 11 / 12HP: 13
6
0
Outside air temperature sensor detected value
TAOUT 0°C
0°C TAOUT 5°C
5°C TAOUT
Thereafter, the high-pressure is monitoring at a set time interval and the fan speed is changed by the following conditions.
(Condition which lowers the fan speed)
Low-pressure 0.85MPa and heat sink temperature
(Condition which raises the fan speed)
Low-pressure saturation 0.74MPa or heat sink temperature
The initial speed of the first boot outdoor unit is detected by outdoor air temperature sensor value (TAOUT).
Fan step
11
10
9
8
7
6
5
4
3
2
1
0
680 680 660 660 590 510 520
400 440
330 380 300 300 300 450
0
300
0
0
0 0 0
Fan speed (rpm)
780 740 660 660 590 510 520
400 440
330 380 300 300 300 450
0
300
0
0
0 0 0
790 710 700 620 590 510 520
400 440
330 380 300 300 300 450
0
Intermittent 1
0
0
0 0 0
Step
Upper FAN Lower FAN
AJ*072LELAH
AJ*090LELAH AJ*108LELAH
13
12
-
-
-
-
-
-
-
-
960 880 870
790
Intermittent 2
300
Intermittent 1
Intermittent 2
Intermittent 1
Intermittent 2
Intermittent 1 : 14 sec. ON (300rpm), 17 sec. OFF
Intermittent 2 : 19 sec. ON (300rpm), 17 sec. OFF
55° C: 8&10HP 60° C: 12HP
60° C: 8&10HP 65° C: 12HP
Page 33
02-06
Capacity priority s etting
Operation mode
Low noise level se tting
ON
OFF
520
8
ON
ON
COOL
HEAT
«
Low noise mode and operation contents
»
( PUSH SW ) ( PUSH SW )
Normal operation
Low capacity
Not switched for 30 minutes after being once switched.
* Automatic switching
«
Settings and corresponding operations
»
LOW NOISE MODE
* Automatic switching
* Low capacity Compressor capacity is low or High-pressure is high (high-pressure saturation 58°C) at cooling or Low-pressure is low (low-pressure saturation 0°C) at heating
Operation in low noise mode
When the low noise mode setting ON from PUSH SW or EXTERNAL INPUT, the outdoor unit operates in
the low noise mode as follows.
LOW NOISE MODE
The operating sound lowers from about 3 to 5 dB more than the rated value
Capacity does not become low even when switched to low noise mode
The operating noise is reduced by limiting the rotational speed of the compressor and fan motor
2-3-3
Low noise mode
400
48
590
9
510
63
700
10
620
80
520
8
400
55
590
9
510
65
700
10
620
85
Max FAN Step
Max FAN Step
Max Compressor Speed
Max Compressor Speed
Upper FAN Lower FAN
Upper FAN Lower FAN
L Level 1
ow Noise Mode
AJ*072LELAH
AJ*090LELAH AJ*108LELAH
440
7
COOL
HEAT
330
35
520
8
400
47
520
8
400
54
440
7
330
37
520
8
400
48
520
8
400
58
Max FAN Step
Max FAN Step
Max Compressor Speed
Max Compressor Speed
Upper FAN Lower FAN
Upper FAN Lower FAN
L Level 2
ow Noise Mode
Page 34
To accurately detect the outside air temperature, the fan is operated while the outdoor unit is stopped.
2-3-4 Other Control
02-07
EEV 1
EEV 2
EEV is controlled so that the system reaches closer to the target discharge temperature that is calculated from high and low pressure.
< Cooling mode >
< Heating mode >
3000
pulses basically.
Initialization conditions
Control range
operation stop
3000 Plulses
55 - 500 pulses 0 pulses
40 pulses
2-4 EXPANSION VALVE CONTROL
Cooling
Heating
Operation mode
160 - 3000 pulses
Cooling
Heating
When power turned on When operation stopped
Page 35
2-5 SPECIAL OPERATION
2-5-1 Oil Recovery Operation
Purpose of the operation
The amount of refrigerant lubricant oil which has been transported to the indoor units and the connection pipe with the refrigerant will become large as the operation time of compressor increases. It is necessary to recover the oil back into the outdoor unit for a certain time interval in order to prevent compressors from dama
ging due to lack of lubrication oil.
During the oil recovery operation, appears on the display of wired and central remote controller, and appears on the simple remote controller. The operation indicators (LED) of the indoor units flash slowly.
Others
02-08
< Start condition >
Compressor accumulated operation time since last cooling oil recovery operation exceeds 3 hours (first time : 1hour)
< End condition >
30 seconds have elapsed since the start and "suction temperature - low pressure saturation temperature 5deg" or 6 minutes
have elapsed since the start.
< Operation >
COMPRESSOR: The rotation speed varies depending on the operation state. EEV Opening (Indoor/Outdoor unit): Controlled pulse (as normal operation mode). FAN speed (Indoor/Outdoor unit) : Controlled fan speed (as normal operation mode).
3. Oil Recovery in Heating operation
1. Oil Recovery in Cooling operation
< Start condition >
Compressor accumulated operation time since the last heating oil recovery exceeds 8 hours (first time : 1hour)
< End condition > After 4 minutes have elapsed
< Operation >
COMPRESSOR: The rotation speed varies depending on the operation state. EEV Opening (Indoor/Outdoor unit) : Controlled pulse (as no
rmal operation mode)
FAN speed (Indoor/Outdoor unit) : Controlled fan speed (as normal operation mode)
< Start condition >
LP < 0.13Mpa
< End condition >
HP- LP 0.7Mpa and LP 0.18Mpa or LP 0.52Mpa or 15 minutes have elapsed since the start.
< Operation >
COMPRESSOR: The rotation speed varies depending on the operation state. EEV Opening (Indoor/Outdoor unit): Controlled pulse (as normal operation mode). FAN speed (Indoor/Outdoor unit) : Controlled fan speed (as normal oper
ation mode).
2. Oil Recovery in Cooling start-up operation
Page 36
02-09
2-5-3 Defrost Operation Control
Accumulated heating operation time is 40 minutes or longer [Accumulated heating operation time is reset at the end of cooling operation or defrosting operation.] and an outdoor unit satisfies condition or below
Condition : "Heat exchange temperature -2°C" accumulated operating time is 180 minutes or longer
Condition : After the following all condition satisfied, "heat exchange temperature defrosting start judgment temperature and during heat exchange liquid temperature drop" accumulated time:10minutes
(a) accumulated heating operation time 30 minutes (b) 10 minutes have elapsed after outdoor unit starting (c) 5 minutes have elapsed since oil recovery
* Defrosting start and end judgment temperature are determined by the outdoor temperature.
Defrosting start judgment temperature = 0.8 x outdoor temperature - 11.6 (However, -27.6°C to - 6°C)
At all outdoor units, heat exchange liquid temperature end judgment temperature or when 15 minutes have elapsed from the start
Defrosting end judgment temperature = 0.39 x outdoor temperature + 12.7 (However, 5 to 12°C range)
If the calculated result is lower than -27.6 , the judgment temperature is defined as -27.6 If the calculated result is higher than -6 , the judgment temperature is defined as -6
2-5-2 Pre-heat Operation
This pre-heat operation protects the start up failure by preventing the refrigerant from soaking into the oil in compressor.
Crankcase heater ON: 30 minutes elapsed since installed compressors stopped
(However, ON when power turned on)
*It doesn't control according to the temperature.
If the calculated result is lower than 5 , the judgment temperature is defined as 5 If the calculated result is higher than 12 , the judgment temperature is defined as 12
OFF: Compressor starts
Outdoor temperature <2 and Compressor stop count exceed 20 times at less than 10 minutes of accumulated heating operation time
Defrost Operation Start Condition 1
Defrost Operation Start Condition 2
Defrost Operation End Condition
Page 37
2-6 PROTECTIVE FUNCTION
02-10
2-6-1 Protective Function List
Protective Function
Detect Parts
Operating Condition
Operation
Discharge Temp Protection 1
Discharge Temp Thermistor
Discharge Temp Protection 2
Discharge Temp Thermistor
High Pressure Protection 4
High Pressure Sensor
COOL HEAT
<Starting conditions> 3 minutes have elapsed since the start of operation and (discharge temperature 105°C or suction SH 10°C accumulated time 30 minutes)
<Reset conditions> Discharge temperature 100°C and suctionSH 7°C
EEV of operating indoor unit gradually opened
<Starting conditions> Cooling: Discharge temperature 100°C
<Reset conditions> Discharge temperature 95°C
EEV2 + 30pls/30 secs
Discharge Temp Protection 4
Discharge Temp Thermistor
< starting condition> Discharge temperature 110°C
<Pattern reset condition>
Discharge temperature 1 05°C
Compressor speed -6rps every 30 secs Speed rise prohibited, when discharge temperature becomes lower than 105 , prohibit the rotational speed rise of the compressor.
Discharge Temp Protection 5
Discharge Temp Thermistor
<Starting conditions> Discharge temperature 95°C and EEV1=3000 pls
<Reset conditions> 2 minutes have elapsed and (discharge temperature 90°C or EEV1 400pls)
Expansion valve of stopped indoor unit gradually opened (upper limit 200pls)
Discharge Temp Protection Stop
Discharge Temp Thermistor
<Pattern starting condition> Discharge temperature fixed value (120°C)
<Pattern reset condition> 3 minutes have elapsed and discharge temperature 85°C
Compressor stopped
<Pattern starting condition> Pattern generated 2 times within 40 minutes
<Pattern reset condition> Error reset (push button SW) executed after power turned on again
Compressor stopped (permanent stop) Error disp
lay
High Pressure Protection 3
High Pressure Sensor
<Starting conditions> Fixed time has elapsed and high-pressure 3.50MPa (* Fixed time at start of operation: 10 secs, after operation execution: 20 secs)
<Reset conditions> Operation (fan speed 1 step increase) complete
Fan speed 1 step increase
High-pressure 3.50MPa High-pressure 3.50MPa
Fan lowest speed Upper 300 rpm Lower 0 rpm
DISPLAY
P1
EA11
<Starting conditions>
High-pressure 3.20MPa
Compressor capacity lowered/every 15 secs
HP 3.68 MPa
After 25 seconds have elapsed and,
HP 3.60 MPa
Compressor capacity rise prohibited
<Reset conditions>
High-pressure 3.20MPa
HP 3.8 MPa After 25 seconds have elapsed and ,
HP 3.68 MPa
Compressor capacity lowered every 30 secs
Compressor temperature 1 10°C
and
<Starting conditions>
<Reset conditions>
<Starting conditions> <Reset conditions>
<Starting conditions> <Reset conditions>
High Pressure Protection 5
High Pressure Sensor
High Pressure Sensor
Abnormal High Pressure protection Control
Page 38
02-11
Protective Function
Detect Parts
Operating Condition
Operation
Low Pressure Protection 1
Low Pressure Sensor
COOL HEAT
High Pressure Protection Stop 1
High Pressure Sensor
<Pattern starting condition> High-pressure 4.00MPa
<Pattern reset condition> 5 minutes have elapsed and high-pressure 3.50MPa
Compressor stopped
<Pattern starting condition> Pattern generated 3 times within 60 minutes.
<Pattern reset condition> 10 minutes have elapsed and high-pressure 3.50MPa
Pressure Switch
<Pattern starting condition> Pressure SW operated (Operated by high-pressure 4.20MPa)
<Pattern reset condition> 5 minutes have elapsed and pressure SW operation reset (Reset by high-pressure 3.2MPa)
Compressor stopped
High Pressure Protection Stop 2
<Pattern starting condition> Pattern generated 3 times within 60 minutes.
<Pattern reset condition> 10 minutes have elapsed and pres
sure SW operation reset
(Reset by high-pressure 3.2MPa)
Compressor stopped Error display
<Starting conditions> 3 minutes have elapsed and low-pressure 0.18MPa
<Reset conditions> 3 minutes have elapsed and low-pressure 0.22MPa
EEV of stopped indoor unit opened quickly (450pls)
Abnormal Low Pressure Protection Control
Low Pressure Sensor
<Starting condition>
Low-pressure 0.16MPa
Compressor capacity lowered every 180 secs,
Low Pressure Protection Stop
Low Pressure Sensor
<Pattern starting condition> Low-pressure 0.05MPa or low-pressure 0.10MPa continues for 10 mins
<Pattern reset condition> 3 minutes have elapsed and low-pressure 0.17MPa
<Pattern starting condition> Pattern generated 5 times within 180 minutes.
<Pattern reset condition> Error reset (push button SW) executed after power turned on again.
Compressor stopped (permanent stop) Error display
<Reset condition>
3 minutes have elapsed and low-pressure 0.18MPa
Compressor stopped
DISPLAY
Compressor Temp Protection Stop
Compressor Temp Thermistor
<Pattern starting condition> Compressor temperature fixed value (130°C)
<Pattern reset condition> 3 minutes have elapsed and discharge temperature 90°C
Compressor stopped
Compressor stopped (permanent stop) Error display
<Pattern starting condition> Pattern generated 2 times within 40 minutes
<Pattern reset condition> Error reset (push button SW) executed after power turned on a
gain
P2
EA41
EA31
EA42
P4
P3
EA51
when the Low-pressure becomes more than
0.17MPa, prohibit compressor capacity rise
.
P2
Compressor stopped
Compressor Temp Protection
Compressor Temp Thermistor
Compressor temperature fixed value (115°C)
Compressor stopped
<Starting condition>
<Reset condition>
Compressor temperature < fixed value (110°C)
Discharge temperature < fixed value (105°C)
and
Page 39
02-12
Protective Function
Detect Parts
Operating Condition
Operation
Overcurrent Break Stop (Compressor)
Overcurrent Protection Circuit
COOL HEAT
Compressor stopped
Heatsink Temp Thermistor
<Pattern starting condition>
Heat sink temperature 95°C
<Pattern reset condition> 3 minutes have elapsed and heat sink temperature
Compressor stopped
Heatsink Temp Protection Stop
<Pattern starting condition> Pattern generated 3 times within 60 minutes.
<Pattern reset condition> 10 minutes have elapsed and heat sink temperature
Compressor stopped Error display
<Patte
rn star
ting condition>
Current value Cooling: 14.8A (8,10HP) / 17.7A (12HP)
Heating: 23.5A
<Pattern reset condition> Current value Cooling: 22.5A / Heating: 23.5A
Frequency Maximum Setting Protection (Compressor)
<Pattern starting condition> Current value Cooling:
<Pattern reset condition> Current value Cooling: 23.0A / Heating: 24.0A
Current Detector Circuit
Compressor is stopped when the over currernt protectioncircuit in the inverter PCBoad detects an abnormal current duringthe operation. If it repeated 5 times, the compressor becomes permanentstop.
Compressor is stopped when the over current protection circuit in the inverter PC Board detects an abnormal current at the time of start up. Compressor becomes permanent stop if it re
peated over the number
of set time.
<Reset condition> Error reset (push button SW) executed after power turned on again.
Compressor speed lowered
Compressor speed rise prohibited
Pattern and start current value changed by outside temperature
DISPLAY
E941
E931
(permanent stop)
(permanent stop)
EAC4
Protective function
Detect device
Operation
Cool
Heat
Display
Outdoor Unit Reverse phase, Missing phase Wire Error
Main PCB Reverse phase prevention circuit
E615
Operating condition
1 Reverse phase prevention circuit detected reversed phase input or input was not normal at the time of power ON.
2 Reverse phase prevention circuit detected open-phase after power ON.
Reverse phase prevention circuit detects normal condition
System Stop Error indication
<
Starting condition>
<
Reset condition>
74°C
74°C
15.8A (8,10HP) / 18.7A (12HP)
Page 40
3. INDOOR UNIT OPERATION
Page 41
3-1 FAN CONTROL
03-01
3-1-1 Fan Speed Setting
3. INDOOR UNIT OPERATION
AUTO
HIGH MED LOW
Press the FAN CONTROL button to set the fan speed.
Fan speed setting
3-1-2 "AUTO" Position
Fan speed zone
Hi zone
Med zone
Low zone
When the room temperature decreases
When the room temperature increases
3. DRY OPERATION
1. COOLING OPERATION
2. HEAT OPERATION
• Expansion
valve
• Indoor fan motor
ON OFF
OPEN CLOSE
ON
ON
ON
ON ON ON
ON
ON
30s
30s
5s
3min
5s
2min30s
The indoor fan always rotates at "Lo" speed.
TIME -->
2
TR-TS
1
2
TR-TS
1
TR-TS
2
TR-TS
2
3
TR-TS
3
TR-TS
(1) When the TS is changed. (2) When the operation mode is changed from other mode to "COOL". (3) When the fan control is changed from other position to "AUTO".
The fan speed is determined automatically in accordance with the condition "(TR(corrected room temperature) - TS (corrected set temperature)" as shown on the right. However, the fan speed zone is determined in the manner as the room temperature increases for the following cases.
Same as Cooling operation, fan speed is decided by the difference between the room temperature and the set temperature.
(1) The indoor fan starts operation 5 seconds after the electric expansion valve opens. However, when the indoor unit just starts its operation or the operation mode is changed from other to "DRY" and the refrigerant circulation is not stopped, the fan will rotate immediately without a delay time of 5 seconds. (2) The indoor fan will stop in 30 seconds when the refrigerant circulation stops. (3) The indoor fan will stop immediately when the indoor unit is stopped by pushing the stop button or by a setting of ON timer. (4) When the refrigerant circulation is stopped due to a lower room temperature for more then 3 minutes, the fan will rotate 2 minutes at intervals of 3 minutes. (5) When the indoor unit just starts its operation or the operation mode is changed from other to "DRY" and the refrigerant circulation is stopped, the fan will rotate for 1 minute and then it will operate according to the statement (4).
2min
Fan speed zone
Low zone
Med zone
Hi zone
When the room temperature decreases
When the room temperature increases
-2
TR-TS
-2
-3
TR-TS
-3
TR-TS
-2
TR-TS
-1
-2
TR-TS
-1
TR-TS
Page 42
3-2 MASTER CONTROL
03-02
3-2-1 Operation Mode Control
(2) Cool, Dry and Heat Mode
Indoor fan motor
Operates according to
the AIR FLOW-MODE
setting.
See the fan control
page.
Cool Dry
Drain pump
Turns ON-OFF by the drain pump control function
Electrical expansion valve
Pulse controlled by
the temperature differ-
ence calculation and
frost prevent fuction
Each operation mode is controlled as below. (1) Stop mode
Indoor fan motor : OFF Electric expansion valve Drain pump
: Stop pulse : Turns ON-OFF by the drain pump control function
Operates according to
the AIR FLOW-MODE
setting, and besides
cold air prevention
operation
Pulse controlled by
the temperature dif-
ference calculation
and frost prevent
function
Heat
Pulse controlled by
the temperature dif-
ference.
(3) Priority mode
The purpose of the priority mode is to restrict operation commands (heating, cooling, dry) from the connected indoor units. There are 3 priority modes of Neutral, Cooling Priority, and Heating Priority. The operation modes restricted by each of these modes are as follows:
Priority mode
Neutral
Cooling priority
Heating priority
Restricted operation mode
No restrictions
Heating
Cooling, dry
Neutral
Cooling priority
Heating priority
Cooling priority
Heating priority
1. Priority mode decision methods Method 1. (Default value) The initial priority mode is made Neutral and is shifted to Cooling Priority when cooling and to Heating Priority when heating depending on which operation mode (cooling, heating) was input first. After shifting to Cooling Priority or Heating Priority, the priority mode shifts to Neutral only when there was a Stop input from all the indoor units.
Method 2. (Management by outdoor unit) Operation mode management is made "Management by outdoor unit" by outdoor unit PUSH-SW (field setting). The priority mode shifts to Cooling Priority or Heating Priority in accordance with input from the outdoor unit regardless of the current mode.
Page 43
03-03
Cooling priority
Heating priority
Method 3. (Management by indoor unit) Operation mode management is made "Management by indoor unit" by outdoor unit PUSH-SW (field setting). Then the master indoor unit is set by wired remote controller. Thereupon the priority mode shifts to Cooling Priority or Heating Priority in accordance with input from the master indoor unit regardless of the current priority mode. The priority mode is fixed at either cooling or heating even if the master indoor unit stops Cooling/heating switching can be performed by the master indoor unit only.
(4) Opposite operation mode When the operation mode commanded from an indoor unit (remote controller) and the operation mode allowed by the system (cooling and dry operation for cooling only type and operation mode allowed by priority mode for heat pump type) do not match, it is indicated by blinking of an LED.
Timer lamp: 3 secs ON/1 sec OFF repeated
Page 44
03-04
3-2-1 Operation Mode Control for Outdoor air unit
(2) Cool and Heat Mode
Outdoor air unit fan motor
Operates according to the
HIGH MODE setting.
Cool
Drain pump
Turns ON-OFF by the drain pump control function
Electrical expansion valve
Solenoid valve
Pulse controlled by the
temperature difference
calculation and
freeze prevention control
Each operation mode is controlled as below.
(1) Stop mode
Outdoor air unit fan motor : OFF Electric expansion valve Drain pump
: Stop pulse : Turns ON-OFF by the drain pump control function
Solenoid valve : Cl
osed
Operates according to the
HIGH MODE setting.
Heat
Pulse controlled by the
temperature difference.
Each operation mode is controlled as below.
Fan
Operates according to the
HIGH MODE setting.
Stop pulse
Closed at all times
Opened at thermostat off
and compressor on.
Closed at other operation.
Closed at all times
Page 45
03-05
Cooling priority
Heating priority
Method 3. (Management by indoor unit)
Operation mode management is made "Management by indoor unit" by Outdoor unit PUSH-SW (field setting). Then the master indoor unit is set by wired remote controller. Thereupon the priority mode shifts to Cooling Priority or Heating Priority in accordance with input from the master indoor unit regardless of the current priority mode. The priority mode is fixed at either cooling or heating even if the master indoor unit stops Cooling/Heating switching can be performed by the master indoor unit only.
(4) Opposite operation mode
When the operation mode commanded from an indoor unit (remote controller) and the operation mode allowed by the system (cooling and dry operation for cooling only type and operation mode allowed by priority mode for heat pump type) do not match, it is indicated by blinking of an LED.
Timer lamp: 3 secs ON/1 sec OFF repeated
(3) Priority mode
The purpose of the priority mode is to restrict operation commands (heating, cooling) from the connected outdoor air units. There are 3 priority modes of Neutral, Cooling Priority, and Heating Priority. The operation modes restricted by each of these modes are as follows:
Priority mode
Neutral
Cooling priority
Heating priority
Restricted operation mode
No restrictions
Heating
Cooling
Neutral
Cooling priority
Heating priority
Cooling priority
Heating priority
1. Priority mode decision methods
Method 1. (Default value)
The initial priority mode is made Neutral and is shifted to Cooling Priority when cooling and to Heating
Priority when heating depending on which operation mode (cooling, heating) was input first.
After shifting to Cooling Priority or Heating Priority, the priority mode shifts to Neutral only when there
was a Stop input from all the indoor units.
Method 2. (Management by Outdoor unit)
Operation mode management i
s made "Management by Outdoor unit" by Outdoor unit PUSH-SW (field setting). The priority mode shifts to Cooling Priority or Heating Priority in accordance with input from the Outdoor unit regardless of the current mode.
Page 46
03-06
3-2-2 Auto Changeover
Operation flow chart
START
Room temp.
Room temp.
Ts+2°C ?
COOLING OPERATION
HEATING OPERATION
YES
YES
NO
NO
NO
NO
YES
YES
AUTO CHANGEOVER operation
TS : Setting temperature
Ts- 2°C ?
[Method]
1. Switch operation mode management to "Management by indoor unit" by outdoor unit DIP-SW.
2. Set the master indoor unit by wired remote controller.
3. Judge cooling/heating by the difference between the master indoor unit's setting temperature and the room temperature.
Thermostat remains
in OFF state for 6 minutes or
longer?
System stops
or operation command other than
auto changeover operation?
NO
NO
Thermostat remains
in OFF state for 6 minutes or
longer?
System stops
or operation command other than
auto changeover operation?
YES
YES
Page 47
03-07
3-2-2 Auto Changeover Heating / Cooling Operation for Outdoor air unit
Operation flow chart
START
Suction airflow temp.
Suction airflow temp.
Ts+5°C ?
COOLING OPERATION
HEATING OPERATION
YES
YES
NO
NO
NO
NO
YES
YES
AUTO CHANGEOVER operation
TS : Setting temperature
Ts- 5°C ?
Setting Method
1. Switch operation mode management to "Management by outdoor air unit" by Outdoor unit PUSH-SW.
2. Set the master outdoor air unit by wired remote controller.
3. Judge cooling/heating by the difference between the master outdoor air unit's setting temperature and the suction airflow temperature
Thermostat remains
in OFF state for 6 minutes or
longer?
System stops
or operation command other than
auto changeover operation?
NO
NO
Thermostat remains
in OFF state for 6 minutes or
longer?
System stops
or operation command other than
auto changeover operation?
YES
YES
Function is available when an outdoor air unit set as the administrative indoor unit (Management Outdoor air unit). Refer to the setting Method
Page 48
03-08
3-2-3 "COOL" Position
An example for COOLING TEMPERATURE CONTROL time chart (Manual setting)
When using the cooling mode, set the temperature to a value lower than the current room temperature, otherwise the indoor unit will not start the cooling operation and only the fan will rotate.
Indoor fan
Ts
Opening of EEV
100% 0%
Refrigerant flow
ON OFF
ON OFF
Temperature
Ts + 0.5 C
TR
3Min.
Ts : Corrected setting temperature T
R : Corrected room temperature
: The thres hold temperature of start of refrigrant flow
: The thres hold temperature of stop of refrigrant flow
Ts - 0.5 C
Ts + 0.5 C
Ts - 0.5 C
Ts + 0.5 C Ts - 0.5 C
: The thres hold temperature of start of refrigrant flow
: The thres hold temperature of stop of refrigrant flow
Ts + 0.5 C Ts - 0.5 C
3-2-4 "HEAT" Position
(1) When using the heating mode, set the temperature to a value higher than the current room temperature, otherwise the indoor unit will not start the heating operation.
(3)
An example for HEATING TEMPERATURE CONTROL time chart (Manual setting)
During defrosting, the OPERATION indicator lamp flashes 6 sec. ON and 2 sec. OFF, and repeat. The heating operation will be tem
porarily interrupted.
Indoor fan
Ts
Opening of EEV
100% 0%
Refrigerant flow
ON OFF
ON OFF
Temperature
T
R
4Min.
1Min.
4Min.
1Min.
4Min.
1Min.
Ts : Corrected setting temperature T
R : Corrected room temperature
: Duration of cold air prevention
(2) After the start of heating operation, the fan of indoor unit will not rotate until the heater exchange is warmed up to blow out warm air.
Page 49
03-09
3-2-4 "COOL" Position for Outdoor air unit
An example for COOLING TEMPERATURE CONTROL time chart (Manual setting)
When using the cooling mode, set the temperature to a value lower than the discharge airflow temperature, otherwise the outdoor air unit will not start the cooling operation and only the fan will rotate.
Outdoor air unit fan
Ts
Opening of
EEV
100%
0%
Refrigerant flow
ON OFF
ON OFF
Discharge airflow
Temperature
Outdoor temp.
Ts : Corrected setting temperature
Ts - 5°C
Ts + 0.5°C : The thres hold temperature of start of refrigerant flow Ts - 5°C : The thres hold temperature of stop of refrigerant flow
3-2-5 "HEAT" Position for Outdoor air unit
(1) When using the heating mode, set the temperature to a value higher than the discharge airflow temperature, otherwise
the outdoor air unit will not start the heating operation.
(2)
An example for HEATING TEMPERATURE CONTROL time chart (Manual setting)
During defrosting, the OPERATION indicator lamp flashes 6 sec. ON and 2 sec. OFF, and repeat. The heating operation will be temporarily interrupted.
Excess capacity area
Compressor ON (6 minutes)
Compressor ON (6 minutes)
Compressor OFF (3 minutes)
Compressor ON (6 minutes)
5 minutes has passed at excess capacity area
5 minutes has passed at excess capacity area
Compressor ON (6 minutes)
Compressor OFF (3 minutes)
Outdoor air unit fan
Ts
Opening of
EEV
100%
0%
Refrigerant flow
ON OFF
ON OFF
Discharge airflow
Temperature
Outdoor temp.
Ts : Corrected setting temperature
Ts +5°C
Ts - 0.5°C : The thres hold temperature of start of refrigerant flow Ts + 5°C for 5 minutes or more
: The thres hold temperature of stop of refrigerant flow
Excess capacity area
Page 50
3-3 LOUVER CONTROL
03-10
Instructions relating to heating ( ) are applicable only to heat pump type outdoor unit.
Begin air conditioner operation before performing this procedure.
Vertical Air Direction Adjustment
This instructions are applicable to "LARGE CEILING TYPE", "UNIVERSAL FLOOR/CEILING TYPE", "CASSETTE TYPE", "WALL MOUNTED TYPE", "COMPACT WALL MOUNTED TYPE" and "COMPACT FLOOR TYPE" .
Press the VERTICAL AIR FLOW DIRECTION SET button.
LARGE CEILING TYPE
UNIVERSAL FLOOR/CEILING TYPE
Example : When set to vertical air direction.
DANGER!
(1) ADJUSTING THE DIRECTION OF AIR CIRCULATION
WALL MOUNTED TYPE
1
2
3
4
1
2
3
4
1
2
3
4
3
4
2
1
Never place fingers or foreign objects inside the outlet ports, since the internal fan opertes at high speed and could cause personal injury.
Always use the remote control umit's AIR FLOW DIRECTION button to adjust the UP/DOWN air direction flaps or RIGHT/LEFT air direction louvers. At tempting to move them manually could result in improper operation; in this case, stop operation and restart. The louvers should begin to operate properly again. When used in a room with infants, children, elderly or sick persons, the air direction and room temperature should be considered carefully when making settings.
COMPACT WALL MOUNTED TYPE
COMPACT FLOOR TYPE
CASSETTE TYPE
1
3
4
2
1
2
3
4
Press the VERTICAL AIRFLOW DIRECTION button. The temperature display will change to the vertical airflow direction setting display.
Use the air direction adjustments within the ranges shown above.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
During Cooling mode : Horizontal flow During Heating mode : Downward flow
During AUTO mode operation, for the first minute after beginning operation, airflow will be horizontal , the air direction cannot be adjusted during this period.
1 4
1
Cooling & Dry : 1 , 2 , 3 , 4
Heating : 1 , 2 , 3 , 4
Press the VERTICAL AIRFLOW DIRECTION button to change the vertical louvre position. The position number will appear on the display.
1
2
3
4
Page 51
Horizontal Air Direction Adjustment
This instructions are applicable to "LARGE CEILING TYPE", "UNIVERSAL FLOOR/CEILING TYPE" and "WALL MOUNTED TYPE".
Press the HORIZONTAL AIR FLOW DIRECTION SET button.
LARGE CEILING TYPE
UNIVERSAL FLOOR/CEILING TYPE
WALL MOUNTED TYPE
Example : When set to horizontal air direction.
(2) SWING OPERATION
Instructions are applicable to "LARGE CEILING TYPE", "UNIVERSAL FLOOR / CEILING TYPE", "CASSETTE TYPE", "WALL MOUNTED TYPE", "COMPACT WALL MOUNTED TYPE" and "COMPACT FLOOR TYPE".
Begin air conditioner operation before performing this procedure.
To select Vertical airflow SWING Operation
This instructions are applicable to "LARGE CEILING TYPE", "UNIVERSAL FLOOR/CEILING TYPE", "CASSETTE TYPE", "WALL MOUNTED TYPE", "COMPACT WALL MOUNTED TYPE" and "COMPACT FLOOR TYPE".
1
3
4
5
2
03-11
1
2
3
4
5
Press the VERTICAL SWING button for more than two seconds.
The remote controller's Vertical Swing Display will light up. In this mode, the UP/DOWN air direction flaps will swing automat­ically to direct the air flow both up and down.
Example : When set to vertical swing.
1
3
4
5
2
Press the HORIZONTAL AIRFLOW DIRECTION button. The temperature display will change to the horizontal airflow direction setting display.
Press the HORIZONTAL AIRFLOW DIRECTION button to change the horizontal louvre position. The position number will appear on the display.
Cooling & Dry : 1 , 2 , 3 , 4 , 5
Heating : 1 , 2 , 3 , 4 , 5
To Stop Vertical airflow SWING Operation
Press the VERTICAL SWING button for more than two seconds once and again.
The remote controller's Vertical Swing Display will go out. Airflow direction will return to the setting before swing was begun.
Page 52
Instructions are applicable to "LARGE CEILING TYPE", "UNIVERSAL FLOOR / CEILING TYPE", "CASSETTE TYPE", "WALL MOUNTED TYPE", "COMPACT WALL MOUNTED TYPE", and "COMPACT FLOOR TYPE".
About Vertical Airflow SWING Operation
About Horizontal Airflow Swing Operation
Air flow direction set Range of swing
Air swing range
To select Horizontal Airflow SWING Operation
This instructions are applicable to "LARGE CEILING TYPE", "UNIVERSAL FLOOR / CEILING TYPE", "WALL MOUNTED TYPE".
Press the HORIZONTAL SWING button for more than two seconds.
The remote controller's Horizontal Swing Display will light up. In this mode, the RIGHT/LEFT air direction louvers will swing automatically to direct the airflow both right and left.
To stop Horizontal airflow SWING Operation
Press the HORIZONTAL SWING button for more than two seconds once and again.
The remote controller's Horizontal Swing Display will go out. Airflow direction will return to the setting before swing was begun.
Example : When set to horizontal swing.
Range of swing
03-12
The SWING operation may stop temporarily when the air conditioner's fan is not operating, or when operating at very low speeds.
The swing operation is not available depending on the model. Please refer to the operating manual for the indoor unit.
The SWING operation may stop temporarily when the air conditioner's fan is not operating, or when operating at very low speeds.
The swing operation is not available depending on the model. Please refer to the operating manual for the indoor unit.
Left and right swing range can be changed in 3 steps by field setting.
( Factory setting)
Function Number Setting Value
24
00
01
02
Left and right swing range
1 to 5 (All range)
1 to 3
3 to 5
1 to 4 (All range)
1
2
3
4
Page 53
3-4 ELECTRONIC EXPANSION VALVE CONTROL
03-13
3-5 DRAIN PUMP OPERATION
1. Initialization
2. Operation Control
When starting up
Automatic operatic control
Automatic PI control is performed based on the indoor unit heat exchanger outlet temp and inlet temp.
Room temperature control
The room temperature is controlled so that it reaches to the set-up temperature based on the difference between the room temperature and the set-up temperature, and the change of indoor unit temperature. if the room temperature becomes 0.5 C lower than the set-up temperature, EEV is fully closed.
3. Special Control
(1) When cooling and refrigerant circulation starts, the drain pump starts simultaneously. (2) The drain pump operates continuously for 3 minutes after the refrigerant circulation stopped. (3) When the refrigent circulation is stopped by a start of indoor heat exchanger frost prevention operation, the drain pump will turn off in 1 hour after the end of indoor heat exchanger frost prevention operation. (4) When the water level in the drain pan rises up and then the float switch functions:
Microcomputer stops the refrigerant circulation and indoor fan motor operation. Drain pump operates continuously for 3 minutes after the float switch is turned off.
(Almost condensing water may be drained) (5) When the float switch turns ON continuously for 3 minutes, 'FAILURE INDICATION' operates. (6) Whe
n the float switch turns OFF within 3 minutes, the unit starts cooling operation.
1 2
When the power is turned ON. When it has passed the limited time since the last initialization.
When indoor unit stopping
Oil recovery operation : Controlled pulse. Test run operation : Controlled pulse. Icing protection control : Fully closed. Pump down operation : Fully open. Defrost operation : Controlled pulse
Outdoor unit Condition
EEV Condition
Cooling
Heating
Fully closed
Slightly open
(Cooling) Move to the cooling control base pulse in steps. (Heating) Move to the heating control base pulse in steps.
OFF
Fully closed
Page 54
3-4 ELECTRONIC EXPANSION VALVE CONTROL for Outdoor air unit
03-14
3-5 DRAIN PUMP OPERATION for Outdoor air unit
1. Initialization
2. Operation Control
When starting up
Automatic operatic control Automatic PI control is performed based on the indoor unit heat exchanger outlet temp and inlet temp.
Discharge airflow temperature control The discharge airflow temperature is controlled so that it reaches to the set-up temperature based on the difference between the discharge airflow temperature and the set-up temperature. Cooling operation: 1) If the discharge airflow temperature becomes 5°C lower than the set-up temperature,
EEV is fully closed.
2) If the suction airflow temperature becomes 0.5°C lower than the set-up temperature, EEV is fully closed.
Heating operation: 1) If the discharge airflow t
emperature becomes 5°C higher than the set-up temperature
for 5 minutes or more, EEV is fully closed.
2) If the suction airflow temperature becomes 0.5°C higher than the set-up temperature, EEV is fully closed.
3. Special Control
(1) When cooling and refrigerant circulation starts, the drain pump starts simultaneously. (2) The drain pump operates continuously for 3 minutes after the refrigerant circulation stopped. (3) When the refrigent circulation is stopped by a start of indoor heat exchanger frost prevention
operation, the drain pump will turn off in 1 hour after the end of indoor heat exchanger frost prevention operation.
(4) When the water level in the drain pan rises up and then the float sw
itch functions: Microcomputer stops the refrigerant circulation and indoor fan motor operation. Drain pump operates continuously for 3 minutes after the float switch is turned off. (Almost condensing water may be drained)
(5) When the float switch turns ON continuously for 3 minutes, 'FAILURE INDICATION' operates. (6) When the float switch turns OFF within 3 minutes, the unit starts cooling operation.
1 2
When the power is turned ON. When it has passed the limited time since the last initialization.
When indoor unit stopping by Thermo-OFF condition.
Oil recovery operation : Controlled pulse(Maximum 1400 puls) Test run operation : Controlled pulse. Freeze prevention control : Fully closed. Vacuuming operation : Fully open. Defrost operation : Controlled pulse(Maximum 1400 puls)
Outdoor unit Condition
EEV Condition
Cooling
Heating
Fully closed
Fully closed
(Cooling) Move to the cooling control base pulse in steps. (Heating) Move to the heating control base pulse in steps.
OFF
Fully closed
Page 55
3-6 FUNCTION
03-15
3-6-1 Auto Restart
The air conditioner restarts with the previous setting operation.
3-6-2 Icing Protection Control
3-6-3 Oil Recovery Operation
[Oil recovery operation] : It periodically returns the residual refrigerant ion oil in the indoor unit and the connection piping back to the outdoor unit , and prevents the compressor oil level from decreasing.
6 sec ON 2 sec OFF Blinking
Indoor unit LED : Operation LED
Indoor fan : Same operation before oil recovery operation.
Indoor EEV : Control pulse
During the above operation, a refrigerant noise may be from the indoor unit.
The icing of the indoor heat exchanger is prevented during the cooling and dry mode operation.
(1) Starting Condition Compressor is operation more than 3 minutes. When "Heat exchanger inlet temperature T
A" continues *4 minutes or more.
Compressor is operation more than 3 minutes. When "Heat exchanger outlet temperature T
A" continues 4 minutes or more.
(2) Operation
EEV is closed.
Fan is at the setting amount.
(3) Completing Condition Heat exchanger inlet and middle temperature T
B
After more than 5 minutes
*
Drain pump turns off at 60 minutes past the completion of the icing protection operation.
TA
TB
1°C
7°C
Page 56
03-16
3-6-4 Outdoor temperature protected operation for Outdoor air unit
1. COOL OPERATION
The contents of operation is controlled as following based on the suction airflow temperature.
a) Operation mode management is made
"Management by indoor unit", and
outdoor air unit is master indoor unit.
b) Cases Other than (a)
b) Cases Other than (a)
2. HEAT OPERATION
The contents of operation is controlled as following based on the suction airflow temperature.
Cooling operation
Heat
ing operation
Fan operation
3. FAN OPERATION
The contents of operation is controlled as following based on the suction airflow temperature.
a) Operation mode management is made
"Management by indoor unit", and
outdoor air unit is master indoor unit.
-5°C
18°C
Suction airflow temperature rises
Suction airflow temperature drops
20°C
10°C
5°C
-7°C
Forced thermostat off and Fan off
Cooling operation
Fan operation
18°C
Suction airflow temperature rises
Suction airflow temperature drops
20°C
10°C
5°C Forced thermostat off and Fan off
Heating operation
Fan operation
19°C
Suction airflow temperature rises
Suction airflow temperature drops
21°C
-5°C
-7°C Forced thermostat off and Fan off
Heating operation
Fan operation
5°C
Suction airflow temperature rises
Suction airflow temperature drops
10°C
-5°C
-7°C Forced thermostat off and Fan off
Fan operation
5°C
Suction airflow temperature rises
Suction airflow temperature drops
10°C
Forced thermostat off and Fan off
Page 57
3-7 TIMER CONTROL
03-17
3-7-1 Wireless Remote Controller
There are following 4 kinds of timer modes are available.
ON Timer OFF Timer PROGRAM Timer SLEEP Timer
1. ON / OFF TIMER
3. SLEEP TIMER
2. PROGRAM TIMER
To set the PROGRAM timer
1
2
3
4 5
Select "OFF TIMER" Adjust the OFF time. Select "ON TIMER"
Adjust the ON time.
(About 5 seconds later, the entire display. will reappear.)
Select "PROGRAM TIMER"
(Either OFF ON or OFF ON will display.) (If the ON timer has been se­ lected to operate first, the unit will stop operating at this point.)
Select "CANCEL".
The air conditioner will return to normal op­eration.
To cancel the TIMER
*To change operating conditions
If you wish to change the operating conditions (ON/OFF,Mode, Fan Speed, Temperature Setting), after making the time set­ting, wait until the entire display reappears, then press the ap­propriate buttons to change to the desired operating condition.
Press the START/ STOP button to start the air conditioner, and then proceed as follows.
The timer functions cannot be used when this controller is used together with the remote controller (Wired type). A beeping sound is made when a signal is received.
To set the ON / OFF timer
1
2
Adjust the OFF or ON time.
(About 5 seconds later, the entire display will reappear.)
Press the TIMER MODE button to select "OFF TIMER" or "ON TIMER"
CANCEL OFF TIMER ON TIMER
PROGRAM TIMER (OFF ON, OFF ON)
Press the START/ STOP button to start the air conditioner, and then proceed as follows.
To set the SLEEP timer
(Both the indoor unit's OPERATION indi­ cator lamp (green) and the TIMER indi­ cator lamp (orange) will light.)
Select "CANCEL".
The air conditioner will re­turn to normal operation.
Adjust the OFF time.
(About 5 seconds later,the entire display will reappear.)
1
2
To change the timer settings
1 2
*To cancel the TIMER
Press the SLEEP button once again.
Set the time using the TIMER SET buttons.
Unlike other timer functions, the SLEEP timer is designed to set the duration of time in which the unit does not operate. The SLEEP timer can be set regardless of whether the indoor unit is operating or stopped.
* Even ON/OFF and Sleep timer are valid.
* Even ON/OFF and Program timer are valid.
UTY - LNH
*To stop air conditioner operation during timer operating
Page 58
03-18
Sleep timer
The sleep timer function automatically corrects the temperature thermostat setting according to the time setting to prevent excessive cooling and heating while sieeping.
Cooling operation / dry operation Heating operation
When the sleep timer is set, the set temperature automatically rises 1°C every hour.The set temperature can rise up to a maximum of 2°C
Timer setting
60min.
1°C
2°C
When the sleep timer is set, the set temperature sutomatically drops 1°C every 30 minutes. The set temperature can drop to a maximum of 4°C
1 C
2 C
3 C
4 C
30min.
60min.
90min.
Timer setting
Page 59
03-19
2
1
3
4
3-7-2 Group Remote Controller
UTY - CGG
WEEKLY TIMER
Different schedules can be set for each day of the week. Four timers can be set for each day. Operation on/off time, operation mode, and temperature can be specified for each timer.
1. WEEKLY TIMER
The timer function is not available depending on the initial setting.
Note: When a time is not set, the weekly timer cannot be started.
Different schedules can be set for each day of the week.
Four timers can be set for each day
Press the ALL TIMER button to start or cancel the WEEKLY timers for all indoor units.
If any of the indoor units are in the timer mode, pressing this button cancels the timers for all indoor units. If none of the indoor units are in the timer mode, pressing this button starts the timers for all indoor units.
Press the Select button to select the indoor unit.
Press the PROGRAM (CLOCK AD­JUST) button.
* Do not press this button for two sec­ onds or more, otherwise you will en­ ter the time setting mode.
Press the Select button to select the indoor unit.
* If all indoor units are selected, the times for all of the registered indoor unit timers are set at once.
ı ˇ ı
Day of the week setting
S M T W T F S
ALL
All indoor units
SUN MON TUE WED THU FRI SAT
Press the Timer Mode (DELETE) button to start or cancel the WEEKLY timers.
The timer does not start if the time is not set.
Press the DAY button to select the day of the week.
* For ALL, all of the days can be set together when a appears around each day.
To start / cancel the WEEKLY timer operation
To set the WEEKLY timer
Press the Set Time buttons to set the time in 10-minute increments. * Hold down a Set Time button to adjust the time quickly.
* The time already set at another timer is skipped at the relevant indoor unit.
Decrement Increment
Timer setting
Page 60
03-20
7
8
NOTES
To delete the operating time
5
6
Operating setting
Raise
Lower
Press the Start/Stop button or the Mode button or the Set Temperature button to set the operation.
* For the operations that can be set, refer to "Operation mode setting", "Room tem­ perature setting", and "To start /stop operation" , in "OPERATION". * Only the current operation settings are displayed.
ex.TIMER-1 will start operation at 8:00 on COOL.
Setting the next timer for the same day:
TIMER-1 TIMER-2 TIMER-3 TIMER-4
Then press the ENTER button to proceed to the time setting, and repeat steps from to .
4 5
Repeat steps to to set the timer for another day of the week.
3 5
Be careful for pressing the ENTER button without any operation setting because the time that is set will be cancelled.
When the operating time is set, the mark appears.
ex. TIMER-1 will start operation at 8:00 on COOL with a set­ ting of 20 C
1. Press the ENTER button to confirm the set timer.
2. Press again the PROGRAM (CLOCK ADJUST) button to complete the weekly timer setting.
*
flashes for two seconds.
ı ˇ ı
Setting the timer for the other indoor units:
Before setting the timer for other indoor units, press the ENTER button to confirm the settings. * The display switches to the next timer.
Repeat steps to to set the timer for other indoor units.
2 6
1. If the Timer Mode (DELETE) button is pressed during steps to , the operat­ ing time for the selected day will be deleted. * If all the days are selected, the operating times for all of the days of the se­ lected timer will be deleted.
2. Press the ENTER button to confirm the deletion.
3 7
AM
(1) The WEEKLY timer does not operate when the HEAT timer is set if a HEAT PUMP MODEL in the air conditioning system is operating in the cooling mode. In addition, the WEEKLY timer does not operate when the COOL or DRY timer is set if a HEAT PUMP MODEL in the air conditioning system is operating in the heating mode. (2) Even if the timer operation is set, the timer lamp of the indoor unit
does not light up. (The timer lamp is used for wireless remote controller only.) (3) If the same time is set in Timer-1 to Timer-4 of an indoor unit, the timer setting of the smallest number will be effective.
Page 61
03-21
3-7-3 Wired Remote Controller
UTY - RNK
ON / OFF TIMER WEEKLY TIMER TEMPERATURE SET BACK TIMER
1. ON / OFF TIMER
The timer function is not available depending on the model.
To set the ON/OFF timer
Press the timer mode button to se­lect the ON timer or OFF timer. It is switched every time as shown in the below diagram when the button is pressed.
2
Press the DELETE button to cancel the timer mode. The timer mode can also be canceled by changing the timer mode using the timer mode button.
1
NON STOP
OFF TIMER
ON TIMER
WEEKLY TIMER
No display
Press the set time buttons to set the time. After the time is set, the timer will start automatically. The amount of time until the OFF timer operates that is displayed on the timer display decreases as time passes.
From 1 to 24 hours
ex. OFF timer set for 6 hours
To cancel
SUMOTUWETH FR
SA
Page 62
03-22
2. WEEKLY TIMER
The timer function is not available depending on the model.
Press the timer mode button to select the weekly timer.
2
Press the SET button for 2 sec­onds or more.
1
3
SUMOTUWETH FR
SA
3 6 9
12 15 18 21
Day of the week setting
Press the DAY button to select the day of the week, and then press the TIMER SET button to confirm the setting.
For ALL, all of the days can be set together when a each day.
appears around
ALL SU MO TU WE TH FR SA
SUMOTUWETH FR
SA
3 6 9
12 15 18 21
1
2
Weekly timer setting
4
Time setting (ON / OFF timer)
Press the SET TIME buttons to set the ON time in 30-minute increments, then press the TIMER SET button to proceed to the OFF time setting. Set the OFF time in the same way. If necessary, set the second weekly timer settings in the same way.
When the operating time is set, the
mark appears.
6
Press the TIMER SET button for 2 seconds or more to complete the weekly timer settings.
To delete the operating time
If the TIMER DELETE button is pressed during steps or , the operating time for the selected day will be deleted. If all the days are selected, the operating times for all of the days will be deleted.
3
4
ex. The timer is set for 7:00-18:00.
5
Repeat steps and to set the weekly timer for another day of the week.
3 4
ON-1 OFF-1 ON-2 OFF-2
Time setting (Independent OFF timer)
1
2
1
Press the TIMER MODE button to change to the independent OFF timer setting. * The time setting process is the same as the ON/OFF timer. Press the TIMER MODE button to return to the ON/OFF timer setting.
Switching from ON/OFF timer to independent OFF timer
The independent timer will flash on the display.
ON-2 OFF-2 OFF-2 OFF-3
Page 63
03-23
SUMOTUWETH FR
SA
3 6 9
12 15 18 21
SUMOTUWETH FR
SA
3 6 9
12 15 18 21
To start
When the weekly timer is selected, the timer starts automatically.
To cancel
Press the TIMER DELETE button to cancel the timer mode. The timer mode can also be canceled by changing the timer mode using the TIMER MODE button.
1
During the weekly timer, press the TIMER SET button for 2 seconds or more to set the day.
Select the day to set the DAY OFF.
Press the DAY (DAY OFF) button for 2 seconds or more to set the DAY OFF.
Press the TIMER SET button for 2 seconds or more to c
omplete the
DAY OFF setting.
2 3 4
To cancel
Follow the same procedures as those for setup.
ex. The DAY OFF is set for Monday.
NOTES
The DAY OFF setting is only available for days for which weekly settings already exist. If the operating time carries over to the next day (during a next day setting), the effective DAY OFF range will be set as shown below.
Normal Next day setting
Setting dayPreceding day Next day Setting dayPreceding day Next day
The DAY OFF setting can only be set one time. The DAY OFF setting is cancelled automatically after the set day has passed.
Flashing mark: indicates the DAY OFF.
ON OFF ON OFF
DAY OFF
WEEKLY WEEKLY
WEEKLY
WEEKLY
ON
OFF ON OFF
DAY OFF
To start /cancel the WEEKLY timer operation
To set the DAY OFF (for a holiday)
3 6 9
12 15 18 21
The operating time for the current day is displayed.
ex.Operating time 7:00-18:00 Indpnd. OFF time 21:00
The independent timer will flash on the display.
NOTES
(1) PRECAUTIONS DURING WEEKLY TIMER SETUP Setup is not possible in the following cases, so amend the time. Be sure to set the ON time first, then the OFF time. If either the ON time or the OFF time is not set cor rectly, the timer will not operate properly. The WEEKLY 2 settings cannot be set earlier than the WEEKLY 1 settings. The WEEKLY 1
and WEEKLY 2 time spans cannot
overlap.
(2) The earliest OFF time you can set is 30 minutes after the ON time. (3) The OFF time can be carried over to the next day. (4) The earliest independent OFF time you can set is 30 min­ utes after the last OFF time. (5) An independent OFF time can be set up to 0:00 hours of the next day.
(6) Even if the timer operation is set, the timer ind
icator lamp of the indoor unit does not light up. (The timer indicator lamp is used for wireless remote controllers only.)
Page 64
03-24
3. TEMPERATURE SET BACK TIMER
The timer function is not available depending on the model.
Press the SET BACK button to change to the SET BACK con­firmation display. The SET BACK operating time and the set temperature will be displayed.
2
Press the SET button for 2 seconds or more.
1
3
Day setting Operating time setting
Follow step and in "To set the WEEKLY timer". The DELETE button is also used as described in the procedures for the weekly timer.
4
NOTES
The SET BACK timer only changes the set temperature, it cannot be used to start or stop air conditioner operation. The SET BACK timer can be set to operate up to two times per day but only one temperature setting can be used. The SET BACK timer can be used together with the ON, OFF, and weekly timer functions. The SET BACK operating time is displayed only in the SET BACK confirmation display.
(Refer to step 1 for the SET BACK confirmation display. ) During the COOL/DRY mode, the air conditioner will operate at a minimum of 18°C even if the SET BACK temperature is set to 17°C or lower. Room temperatures as low as 10, 12, and 14°C cannot be set depending on the model.
SET BACK
SUMOTUWETH FR
SA
3 6 9
12 15 18 21
SUMOTUWETH FR
SA
3 6 9
12 15 18 21
ex. When setting all days together
Temperature setting
Press the set temperature buttons to set the temperature. (The temperature setting range is the same as the range for the operation mode.)
ex. Operating time 15:00 - 22:00
5
Repeat steps and . Press the SET button for 2 sec­onds or more to complete the temperature SET BACK timer settings.
3 4
ON OFF
24°C
24°C
28°C
SET BACK temperature
Normal temperature
To start
SET BACK
Press the SET BACK button. The SET BACK confirmation display appears for 5 seconds, and then the timer starts automatically.
ex. Display during SET BACK timer operation (The operating time will not be displayed.)
To cancel
Press the SET BACK button, and then press the DELETE button while the SET BACK confirmation display is dis­played. Even if the SET BACK button is pressed again, the SET BACK timer will be cancelled.
SUMOTUWETH FR
SA
3 6 9
12 15 18 21
If there is no existing SET BACK tempera­ture setting, " - - " will be displayed for the temperature.
SUMOTUWETH FR
SA
1
3
2
4
1
2
Temperature SET BACK timer setting
To start /cancel the temperature SET BACK timer operation
3 4
Page 65
3-8 DX-KIT
HEXFAN
TH: Intake/Discharge, HEX inlet/outlet
HEX
FAN
TH: HEX inlet/outlet
TH: Intake/Discharge
FGL RC.
LON
FGL Products
FGL Products
LON
External Controller (DDC)
Universal remote Controller
1. FGL remote/controller connection
The DX kit is controlled by a VRF operation device and use the external output of the DX kit to performe the AHU operation
indirectly.
Control devices can be unified with FGL devices.
2. External controller connection
Air conditioning control (thermostat-control) can be designed on-site. (Air conditioning control by DX is also possible.) Control equipment suited to the application can be connected.
Interface External input External output
Contents
Fan ON/OFF Thermostat ON/OFF
Interface External input
External output
Contents Operation ON/OFF Operation mode Cool/Heat Set temperature or capacity request (Analog input)
Error Operation ON/OFF Error Special operation (defrost)
Remarks
Typical indoor unit is required for mode changing. Temperature setting:
When thermo-control is performed by DX kit.
Capacity request:
When the thermo-control is performed by external controller.
Information on error occurred at external controller
Information on error occurred at VRF system The Fan operation can be stopped with the communication siginal of special operation
External Input/Output
External output
External refrigerant cycle
External refrigerant cycle
DX-Kit
DX-Kit
Fan abnormal intput
3-8-1 SYSTEM CONFIGURATION
03-25
Page 66
1. FGL remote/controller connection
2. External controller connection
Air conditioning control system (SET3-3) Set temperature objective
Thermostat OFF conditions
Operation (ON/OFF/Mode/ Set temperature Fan control
Intake temperature control
Intake temperature (Room temperature)
Cooling: 18 to 30 Heating: 10 to 30
Cooling
Intake temperature < Setting temperature -0.5
Heating
Intake temperature > Setting temperature +0.5
FGL controller
Fan control commands are output from the DX kit external output terminal
Discharge temperature control
Discharge temperature
Cooling: 14 to 25 Heating: 17 to 28
Cooling
Discharge temperature < Setting temperature -5.0
Heating
Discharge temperature > Setting temperature +5.0 for 5 minutes
Air conditioning control system (SET3-3)
Analog input system (SET3-2)
Temperature
Setting range
Thermostat
OFF conditions
Capacity
input range
Thermostat OFF
conditions
Operation (ON/OFFMode/ Set temperature When error generated at external equipment Fan control
Intake temperature control
Set temperature input / Capacity input Selection Intake temperature (Room temperature)
Cooling: 18 to 30 Heating: 10 to 30
Cooling
Intake temperature < Setting temperature -0.5
Heating
Intake temperature > Setting temperature +0.5
0%, 5% to 100%
Controlled by external controller and EEV closed by making the capacity input 0% in cooling mode.
EEV slightly opened when the Compressor operating in heating mode
Controlled by external controller, input to DX Kit external input terminal
*Operation from FGL controller is disabled.
(Only monitoring is possible)
Wh
en fanmotor locked or another error was generated at the external equipment, the refrigerant cycle is
stopped by inputting an error signal to the DX Kit external input terminal. (EEV is Closed)
Control is perfomed by external equipment, but when you want to stop the fan during defrosting, use the defrost signal that is output from the DX Kit external output terminal.
Outlet temperature control
Set temperature input / Capacity input Selection Discharge temperature
Cooling: 14 to 25 Heating: 17 to 28
Cooling
Discharge temperature < Setting temperature -5.0
Heating
Discharge temperature > Setting temperature +5.0 for 5 minutes
Capacity input Temperature setting
3-8-2 FUNDAMENTAL FUNCTIONS
03-26
Page 67
Cooling operation
An example for COOLING TEMPERATURE CONTROL time chart
When using the cooling mode, set the temperature to a value lower than the target controlling temperature, otherwise the External refrigeration cycle equipment will not start the cooling operation.
Indoor fan*
Ts
Opening of EEV
100%
0%
Refrigerant flow
ON OFF
ON OFF
Temperature
T
R
3Min.
Ts: Corrected Setting temperature
: The threshold temperature of start of refrigerant flow : The threshold temperature of stop of
Ts + 0.5 C Ts - 0.5 C
(1) When using the heating mode, set the temperature to a value higher than the current room temperature, otherwise
the indoor unit will not start the heating operation.
(3)
An example for HEATING TEMPERATURE CONTROL time chart
During defrosting, the OPERATION indicator lamp flashes 6 sec. ON and 2 sec. OFF, and repeat. The heating operation will be temporarily interrupted.
Indoor fan*
Ts
Opening of EEV
100%
0%
Refrigerant
flow
ON OFF
ON OFF
Temperature
T
R
.
Ts : Corrected Setting temperature
T
R : Target controlling temperature (Air intake temperature or Air discharge temperature)
: Duration of cold air prevention
(2) After the start of heating operation, the fan of indoor unit will not rotate until the heater exchange is warmed up to
blow out warm air.
TR: Target controlling temperature (Air intake temperature or Air discharge temperature)
+ 0.5 C: Air intake ctrl + C: Air discharge ctrl
- 0.5 C: Air intake ctrl
- 5.0 C: Air discharge ctrl
Ts
Ts
+ 0.5 C: Air intake ctrl + 5.0 C: Air discharge ctrl
- 0.5 C: Air intake ctrl
- 0.5 C: Air discharge ctrl
Ts
Ts
Air intake temp controlling
: The threshold temperature of start of : The threshold temperature of stop of
Ts + C Ts - 5.0 C
Air discharge temp controlling
: The threshold temperature of start of : The threshold temperature of stop of
Ts - 0.5 C Ts + 0.5 C
Air intake temp controlling
: The threshold temperature of start of
Ts - 0.5 C Ts + 5.0 C: The threshhold temperature of stop of refrigerant flow
*When the EEV operates with the minimum pulse, and it keeps for 5 minutes.
Air discharge temp controlling
0.5
0.5
refrigerant flow
refrigerant flow refrigerant flow
refrigerant flow refrigerant flow
refrigerant flow
Heating operation
3-8-3 FUNDAMENTAL FUNCTIONS
03-27
Page 68
1. Initialization
2. Operation Control
When starting up
Automatic operatic control
Automatic PI control is performed based on the indoor unit heat exchanger outlet temp and inlet temp.
Discharge airflow temperature control
The discharge airflow temperature is controlled so that it reaches to the set-up temperature based on the difference between the discharge airflow temperature and the set-up temperature. Cooling operation: 1) If the discharge airflow temperature becomes 5°C lower than the set-up temperature, EEV is fully closed.
2) If the suction airflow
temperature becomes 0.5°C lower than the set-up temperature, EEV is fully closed. Heating operation:
If the suction airflow temperature becomes 0.5°C higher than the set-up temperature, EEV is fully closed.
ture
3. Special Control
(1) When cooling and refrigerant circulation starts, the drain pump starts simultaneously. (2) The drain pump operates continuously for 3 minutes after the refrigerant circulation stopped. (3) When the refrigent circulation is stopped by a start of indoor heat exchanger frost prevention operation, the drain pump will turn off in 1 hour after the end of indoor heat exchanger frost prevention
operation.
(4) When the water level in the drain pan rises up and then the float switch functions:
Microcomputer stops the refrigerant circulation and indoor fan motor operation. Drain pump operates continuously for 3 minutes after the float switch is turned off.
(Almost condensing water may be drained) (5) When the float switch turns ON continuously for 3 minutes, 'FAILURE INDICATION' operates. (6) Whe
n the float switch turns OFF within 3 minutes, the unit starts cooling operation.
1 2
When the power is turned ON. When it has passed the limited time since the last initialization.
When indoor unit stopping by Thermo-OFF condition.
Oil recovery operation : Controlled pulse(Maximum 1400 puls) Test run operation : Controlled pulse. Freeze prevention control : Fully closed. Vacuuming operation : Fully open. Defrost operation : Controlled pulse(Maximum
1400 puls)
Outdoor unit Condition
EEV Condition
Cooling
Heating
Fully closed
Fully closed
(Cooling) Move to the cooling control base pulse in steps. (Heating) Move to the heating control base pulse in steps.
OFF
Fully closed
3-8-4 ELECTRICAL EXPANSION VALVE CONTROL for DX-KIT
3-8-5 DARIN PUMP OPERATION for DX-KIT
03-28
Page 69
Auto Restart
The air conditioner restarts with the previous setting operation.
Freeze Prevention Control
Oil Recovery Operation / Defrost Operation
[Oil recovery operation / Defrost operation] : It periodically returns the residual refrigerant ion oil in the indoor unit and the connection piping back to the outdoor unit , and prevents the compressor oil level from decreasing.
6 sec ON 2 sec OFF Blinking
IR Receiver Unit LED: Operation LED
FAN output: Same operation before oil recovery operation in cooling operation or dry operation.(Heating operation: Stop)
DX-KIT EEV
: Control pulse
During the above operation, a refrigerant noise might hear from the EEV Kit.
The icing of the indoor heat exchanger is prevented during the cooling and dry mode operation.
(1) Starting Condition Compressor is operation more than 3 minutes. When "Heat exchanger inlet temperature T
A" continues *4 minutes or more.
Compressor is operation more than 3 minutes. When "Heat exchanger outlet temperature T
A" continues 4 minutes or more.
(2) Operation
EEV is closed.
Fan is at the setting amount.
(3) Completing Condition Heat exchanger inlet and middle temperature T
B
After more than 5 minutes
*
Drain pump turns off at 60 minutes past the completion of the icing protection operation.
TA
TB
1°C
7°C
3-8-6 FUNCTION
03-29
Page 70
4. TROUBLE SHOOTING
Page 71
Continuous lighting(lowered light)Anti Freeze
Operation LEDTest Operation
Operation LED
Power Failure
Oil Recovery
Operation LED
Defrosting
Timer LED
Timer LED
Timer LED
Continuous lighting(lowered light)Timer LEDTimer
Continuous lighting
Operation LED
Operation
Flashing PatternIndication LampIndication type
04-01
Opposite Operation Mode
4-1 NORMAL OPERATION
4. TROUBLESHOOTING
4-1-1 Indoor Unit Display
Filter Filter LED Continuous lighting
ON
OFF
ON
OFF
1 sec
1 sec
6 sec 2 sec
ON
OFF
ON
OFF
Operation LED
Timer LED
Filter LED
Maintenance Mode
1 sec 1 sec
1 sec
1 sec
3 sec 1 sec
ON
OFF
1 sec 1 sec
ON
OFF
Page 72
LED101
Inverter Compressor Operation Indication
Low Noise Mode
Compressor Temperature Protection is stopped
Low Pressure Protection is stopped
High Pressure Protection is stopped
Discharge Temp. Protection is stopped
Defrost Operation
Oil Recovery Operation
Heating Mode
Cooling Mode
Idling(stop)
Indication type 7 Segment LED Pattern
4-1-2 OUTDOOR UNIT DISPLAY
LED104
LED105
POWER
MODE
ERROR
(GREEN)
LED102
(RED)
Blank
"C" OO "L"
"H" EA "T"
"O" IL "R" ECOVERY
"D" E "F" ROST
"P" ROTECT "1"
"P" ROTECT "2"
"P" ROTECT "3"
"P" eak "C" ut
"L" OW "N" OISE
Blinking
Description
POWER LED101
ERROR LED102
ON
ON
OFF
OFF
"P" ROTECT "4"
ON OFF
1 sec 1 sec
Peak Cut Mode
<Starting condition> Discharge temp fixed value 120°C Release condition> 3 minutes have elapsed and discharge temperature 85°C
<Starting condition> Compressor temp fixed value 130°C <Release condition> 3 minutes have elapsed and discharge temperature 90°C
<Starting condition> Low pressure 0.05MPa or low pressure 0.10MPa continues for 10 mins <Release condition> 3 minutes have elapsed and low pressure 0.17MPa
<Starting condition> High pressure 4.20MPa <Release condition> 5 minutes have elapsed and high pressure 3.20MPa
Refer to 02-08 page for operation.
Refer to 02-09 page for operation.
Refer to 02-06 page for operation.
04-02
Page 73
Indoor Unit Water Drain Abnormal
Outdoor Unit Error
Indoor Unit Fan Motor 1 Error
Indoor Unit Heat Ex. Sensor Error
Room Temperature Sensor Error
Peripheral device Communication Error
Indoor Unit Main PCB Error
Indoor Unit Power Frequency Abnormal
Network Communication Error
Wired Remote Controller Communication Error
Error Content s
4, 6, 30 66~
27
17, 18, 19
20
21
28
29
26
24, 25
14, 15, 16
13
7, 8
4, 5, 6
Continuous flash2 times flash1 times flash
Continuous flash
Continuous flash6 times flash1 times flash
Continuous flash1 times flash3 times flash
2 times flash3 times flash
Continuous flash
1 times flash4 times flash
9 times flash3 times flash
Continuous flash
2 times flash4 times flash
Continuous flash
1 times flash
5 times flash
10 times flash4 times flash
Continuous flash
Continuous flash
3 times flash5 times flash
9 times flash5 times flash
15 times flash9 times flash
Continuous flash
Continuous flash
Continuous flash
Continuous flash
4 times flash1 times flash
1, 2, 3
Trouble
shooting
Filter LEDTimer LEDOperation LED
Please refer the flashing pattern as follows.
04-03
4-2 ABNORMAL OPERATION
4-2-1 Indoor Unit Display
Indoor Unit Power Supply Error For Fan Motor 1(2)
Outdoor Air Unit Temperature Sensor Error
Indoor Unit Fan Motor 2 Error
* LED Display when Option receiver unit installed.
Error Indication Flashing Pattern
0.1s / 0.1s
4.0s
1.0s
0.5s 0.5s
0.5s 0.5s 0.5s 0.5s
1.0s
0.5s 0.5s
0.5s 0.5s
3.0s
1.0s
4.0s
1 cycle
ON
ON
ON
OFF
OFF
OFF
Operation LED
Timer LED
Filter LED
Example : Indoor Unit Main PCB Error (Operation LED : 3 times, Timer LED : 2 times)
Depending on contents of Outdoor unit, it may not indicate. (Refer to "TROUBLE LEVEL OF SYSTEM")
9 times flash hsalf suounitnoChsalf semit 2
Address setting Error
6 times flash hsalf suounitnoChsalf semit 2
Connection Unit Number Error in Wired Remote
Controller System
Indoor Unit Communication circuit (Wired Remote Controller) Error
10 times flash3 times flash
Continuous flash
hsalf suounitnoC
Indoor Unit EEV coil 1 Error
2 times flash
5 times flash
9, 10
11, 12
22, 23
Page 74
4-2-2 Outdoor Unit Display
LED101
POWER LED101
ERROR LED102
MODE
EXIT
SELECT ENTER
SW107
SW108 SW109
POWER
MODE
ERROR
(GREEN)
LED102
(RED)
0.1sec 0.1sec
ON
ON
OFF
OFF
POWER MODE LED : on ERROR LED : blink
ERROR transition
"Err." and quantity are alternately shown.
When there is more than one error, display is changed by "SELECT" short press.
When more than one indoor unit is abnormal, display is changed by "SELECT" short press.
"ENTER" short press"ENTER" short press
"ENTER" short press"ENTER" long press
*
Short press : less than 3 seconds Long press : more than 3 seconds
Annunciation
Type of errors
Address
"SELECT" short press display change
"SELECT" short press display change
If some error is newly occured or resolved during transition, it is reflected after going
back to "Annunciation".
* Only in the case of "indoor unit abnormal (E.5U.1)", indoor unit address is shown by ENTER long press.
LED display
Operation button
ex : discharge thermistor 1 abnormal ex : indoor unit abnormal
04-04
Page 75
Trouble
shooting
Error Contents
4-2-3 Error Code List for Outdoor Unit
Error Code
Auto Address Setting Error
Indoor Unit Error
Initial Setting Error
Inverter PCB short interruption detection
Inverter Error
Inverter Communication Error
Outdoor Unit EEPROM Access Error
EEPROM Data corrupted Error
Outdoor Unit transmission PCB Parallel Communication Error
38
37
36
34
33
35
Signal Amplifier Auto Address Setting Error
Trouble
shooting
Error Contents
High Pressure Switch Error
Suction Pressure Sensor Error
Current Sensor Error
SC HE. Liquid Outlet Temp Sensor Error < TH7 >
SC HE. Gas Outlet Temp. Sensor Error < TH9 >
Discharge Pressure Sensor Error
Heat Sink Temp. Sensor Error
Suction Gas Temp. Sensor Error < TH4 >
Outdoor Temp. Sensor Error < TH3 >
Heat Ex. Liquid pipe Temp. Sensor Error < TH5 >
50
49
48
47
46
45
44
43
42
41
39
- - - -
2 8 . 1
5 U . 1
6 2 . 6
6 1
. 5
6 2 . 3
6 2 . 8
6 3 . 1
6 7 . 2
2 8 . 4
6 9 . 1
7 1 . 1
7 2 . 1
7 3 . 3
7 4 . 1
7 5 . 1
7 7 . 1
8 2 . 2
8 3 . 2
8 4 . 1
8 6 . 1
6 8. 2
Compressor Temp. Sensor Error < TH10 >
Discharge Temp. Sensor Error < TH1 >
40
Outdoor unit FAN Motor 1 Under voltage
Outdoor unit Fan Motor 1 Lock Error
(Start up Error)
Compressor Motor Loss of Synchronization
Trip Detection
Inverter Compressor Start Up Error
Outdoor unit Fan Motor 1 Temperature Abnormal
55
54
53
52
51
Error Code
8 6 . 3
8 6 . 4
9 3 . 1
9 4 . 1
9 5 . 5
9 7 . 1
9 8 . 5
9 A . 1
9 A . 2
A 1 . 1
A 3 . 1
Discharge Temperature Abnormal
62
A 4 . 1
61
60
60
30
1 29
31
32
6
1 4 . 5
The number of Indoor unit shortage
579 7 . 4
9 7 . 5
56
58
rorrE ) 1 evlaV noisnapxE ( lioC
9
8 .
1
rorrE ) 2 evlaV noisnapxE ( lioC
4
1 4 . 2
Outdoor unit Network communication abnormal 2
Outdoor Unit Reverse phase missing, phase wire Error
Rush current limiting resistor temp rise protection
A 4 . 2
A 5 . 1
A C . 4
Outdoor unit Fan Motor 2 Lock Error
(Start up Error)
Outdoor unit Fan Motor 2 Temperature Abnormal
Compressor Temperature Abnormal
High Pressure Abnormal
High Pressure Protection 1
Low Pressure Abnormal
Outdoor unit Heat Sink temp. Abnormal
56
58
66
65
64
63
04-05
Outdoor unit FAN Motor Driver Abnormal
9 7 . 9
59
Outdoor unit FAN Motor Driver Abnormal
9 8 . 9
59
Page 76
<< WIRED REMOTE CONTROLLER 3 wire type >> UTY-RNKU
<< WIRED REMOTE CONTROLLER 2 wire type >> UTY-RNRU
<< WIRED REMOTE CONTROLLER 2 wire type >> UTY-RNRU
If an error occurs, the following display will be shown. (
will appear in the set room temperature display.)
If
is displayed, immediately conta ct authorized
service personnel.
Unit number (usually 0) Error code
Ex. Error code display
ERROR CODE DISPLAY
<< SIMPLE REMOTE CONTROLLER >> UTY-RSKU , UTY-RHKU
Error code
Ex. Error code display
Faulty unit No. (Remote controller address)
ERROR CODE DISPLAY
<< GROUP REMOTE CONTROLLER >> UTY-CGGY
The air conditioning system must be inspected if “ : “ (error code) appears on the timer and Clock Display, or the
operation lamp is flashing.
Model code
Error code
Ex. Error code display
ERROR CODE DISPLAY
Model code
: Outdoor unit : Indoor unit : Group remote controller : Convertor
*1 ;
*1
If an error occurs, the following display will be shown. (
will appear in the set room temperature display.)
If
is displayed, immediately contact authorized
service personnel.
4-2-4 Remote Controller Display
1. Touch the [Status] on the Monitor mode screen.
2. Touch the [Error Information] on the Status screen.
2-digit numbers are corresponding to the error code
If an error occurred, an error icon appears on the Monitor mode screen.
Ex. Error code display
If an error occurs, the following display will be shown. (" " will appear in the "Monitor Mode Screen")
This appears automatically on the display if an error occurs.
Fri 10:00AM
5 /1 Page3 /1 Page
Mode Set Temp.
Air Flow Direction
Economy
1 3
02-01
14,15, 41, 44
VT HZ
Off Off
Anti Freeze
Address
Error Code
Status Menu
BackMonitor
Fan
Error InformationStatus
Next Page
Next Page
Error Information
Error code
2-wire remote controller address
04-06
Page 77
Trouble
shooting
Error Contents
4-2-5 Error Code List for Simple and Wired Remote Controller
Error Code
Trouble
shooting
Error Contents
Error Code
1 2
1 4
1 6
- -
2 6
3 1
3 2
4 1
4 2
5 1
5 3
Indoor Unit Main PCB Error
Indoor Unit Power Frequency Abnormal
Address Setting Error
Initial Setting Error
Network Communication Error
Remote Controller
Communication Error
Indoor Unit Fan Motor Error
Indoor Unit Heat Ex. Sensor Error
Room Temperature Sensor Error
Water Drain Abnormal
6 2
6 3
6 7
6 9
Inverter PCB short interruption detection
Inverter Error
Outdoor Unit Main PCB Error
Outdoor Unit tr
ansmissio
n PCB Parallel
Communication Error
8 2
8 3
8 4
8 6
9 3
9 4
9 5
9 7
Current Sensor Error
Liquid Pipe Temperature Sensor Error
Sub-cool Heat Ex. Gas Temperature Sensor Error
Pressure Sensor Error
Outdoor Unit Fan Motor 1 Error
Compressor Motor loss of Synchronization
Trip Detection
Inverter Compressor Start Up Error
A 1
A 3
A 4
A 5 Low Pressure Abnormal
High Pressure Abnormal
Compressor Temperature Abnormal
Discharge Temperature Abnormal
4-2-6 Error Code List for Group Remote Controller
Trouble
shooting
Error Contents
Error Code
Trouble
shooting
Error Contents
Error Code
1 4
1 6
3 1
3 2
1 2
Remote Controller
Communication Error
Indoor Unit Main PCB Error
Indoor Unit Power Frequency Abnormal
Peripheral device Communication Error
Network Communication Error
4 1
4 2
5 1
9 U
Indoor Unit Fan Motor Error
Indoor Unit Heat Ex. Sensor Error
Room Temperature Sensor Error
Water Drain Abnormal
Outdoor Unit Error
7, 8
13
14, 15, 16
22, 23
21
26
30 66
30
34, 36
13
21
14, 15, 16
22, 23
26
28
37
38
40
47
48
49
53
55
54
56 59
61
62
63, 64
65
A C Outdoor unit Heat Sink temp. Abnormal 66
90
Group Remote controller Hardware Error
4C
88
rorrE erawtfoSAC
C 1
Main PCB Error
9 8
Outdoor Unit Fan Motor 2 Error
9 A
Coil ( Expansion Valve ) Error
60
7 1
7 2
7 3
7 4
7 5
7 7 Heat Sink Temperature Sensor Error
Suction Gas Temperature Sensor Error
Outdoor Temperature Sensor Error
Heat Ex. liquid pipe Temperature Sensor Error
Compressor Temperature Sensor Error
Discharge Temperature Sensor Error 41
44
42
43
45
46
Indoor Unit Fan Motor 2 Error
5 9
29
2725
4 A
Outddor Air Unit Temperature Sensor Error
24, 25,
3 9
3 A
Indoor Unit Power Supply Error for Fan Motor 1(2)
20
17, 18, 19
2 9
Connection Unit Number Error in
Wired Remote Controller System
11, 12
4, 5, 6
5 3
5 9
28
29
Indoor Unit EEV Coil 1 (2) Error
2725
4 A
Outdoor Air Unit Temperature sensor Error
24, 25
3 9
Indoor Unit Power Supply Error for Fan Motor 1(2)
17, 18, 19
2 9
Connection Unit Number Error in Wired Remote Controller System
11, 12
1, 2, 3
2 6
Address Setting Error 9, 10
Indoor Unit Fan Motor 2 Error
4, 6,
1, 2, 3, 91
4, 5, 6, 7, 94
Peripheral device Communication Error
7, 8, 87
9, 10, 92
Indoor Unit Communication circuit (WRC) Error
Indoor Unit EEV coil 1 (2) Error
6 1 Outdoor Unit Reverse phase missing, phase wire Error
33
6 8
Rush current limiting resistor temp rise protection 39
50, 51, 52
1 5
Scan Error
93
80, 84
3 A
Indoor unit Communication circuit (WRC) Error
20
1 5
Incompatible Indoor units connected
95
Thermo sensor Icon on the display is brinking: The integrated room temperature sensor Error --> Refer to the Trouble shooting No. 96
04-07
56 59
Page 78
4-2-8 Error Code List for External Switch Controller (UTY-TEKX)
Trouble
shooting
Error Contents
Error indiction LED1
0.5sec ON / 0.5sec OFF
0.5sec ON / 1.0sec OFF
ON, but SW1 or SW2 not operate
Power Supply Error
Switch Operation Error
Transmission Error
The abnormality in connection of remote controller cable
73
74
76
75
4-2-9 Error Code List for Signal Amplifier (UTY-VSGXZ1)
Trouble
shooting
Error Contents
Error indication of converter
- -
2 6
C 1
- -
Power Supply Error
Main PCB Error
Address Setting Error
Communication Error
77
78
80
Communication Error B
81
Communication Error A
82
79
4-2-10 Error Code List for Network Convertor (UTY-VGGXZ1)
Trouble
shooting
Error Contents
C 1
1 2
C A
- -
Power Supply Error
Software Error
Communication Error with Remote Controller
Main PCB Error
83
84
88
2 6
Refrigerant circuit address setting error
89
85, 86
LED “D14” Flashing or Lighting
Error indication of converter
1 6
Peripheral device Communication abnormal
87
OFF
LED “D9” Flashing or Lighting
4-2-7 Trouble shooting - No Error code -
Trouble
shooting
Error condition
Indoor Unit - No Power
Outdoor unit - No Power
No operation (Power is ON )
No Cooling
Abnormal Noise
Indoor Unit - No Power(Outdoor air unit)
67
68
69
70
71
72
No Error Code
System Abnormal
04-08
4-2-11 Error Code List for Wireless LAN Adaptor
Trouble
shooting
Error Contents
Wireless LAN adaptor Error OR Communication Error between Indoor Unit and Wireless LAN Router
99
97, 98
100
LED1 LED2
101, 102
ON Flashing Fast Communication Error between Wireless LAN Router and Wireless LAN adaptor
Flashing Fast ON Communication Error between Indoor unit and Wireless LAN adaptor
OFF OFF Wireless LAN adapter Non-Energized OR Wireless LAN adaptor Sleep mode
Flashing Fast Flashing Fast
Page 79
Trouble shooting 1 E12.1 INDOOR UNIT Error Method:
Wired Remote Controller Communication Error
Indicate or Display:
Indoor Unit : Operation LED 1 times Flash, Timer LED 2 Times Flash, Filter LED Continuous Flash. < 1 2 >
Outdoor Unit : E.5 U.1
Error Code : 1 2
Detective Actuators:
Indoor unit controller PCB circuit Wired Remote Control (3 wire / 2 Wire type)
Detective details:
Upon receiving the signal more than 1 time from Wired Remote or other Indoor unit, but the same signal has not been received more than 1 minute (3 Wire type). 2.5 minute (2 Wire type)
Check Point 2 : Check Remote and Controller PCB
Check terminal voltage of controller PCB Connector CNC01. (Power supply for Remote)
If DC12V, Remote Control failure (Controller PCB is OK) >>> Replace Remote controller If DC0V, Controller PCB failure (Remote is OK) >>> Replace Controller PCB
-In case of re-installation is done due to removed connector or incorrect wiring,
turn on the power again.
Check Point 1 : Check the connection of terminal
After turning off the power, check & correct the followings.
Indoor Unit - Check the connection of terminal between remote control and Indoor unit, or between Indoor units, and
check if there is a disconnection or short of the cable.
OK
Forecast of Cause :
1. Terminal connection abnormal 2. Wired Remote Control failure 3. Controller PCB failure
4-2-12 TROUBLE SHOOTING WITH ERROR CODE
DC
04-09
Page 80
Trouble shooting 2 E12.2 INDOOR UNIT Error Method:
Wired Remote Controller signal Error
Indicate or Display:
Indoor Unit : Operation LED 1 times Flash, Timer LED 2 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E.5 U.1,
Remote Controller : 1 2
Detective Actuators:
Indoor unit Controller PCB circuit Wired Remote Control (3 wire type)
Detective details:
More than 1 time of Token (Communication between wired remote controllers) is received, but it was not received more than 1 minute.
Forecast of Cause :
1. Terminal connection abnormal 2. Mis-setting 3. Wired Remote Control failure 4. Controller PCB failure
Check Point 1 : Check the connection of terminal
After turning off the power, check & correct the followings.
Indoor Unit - Check the connection of terminal between remote control and Indoor unit, or between Indoor units, and check if there is a disconnection or short of the cable.
Check Point 2 : Check Remote and Controller PCB
Check terminal voltage of Controller PCB Connector CNC01. (Power supply for Remote)
If DC12V, Remote Control failure (Controller PCB is OK) >>> Replace Remote lIf DC0V, Controller PCB failure (Remote is OK) >>> Replace Conroller PCB
In case of re-installation is done due to removed connector or incorrect wiring, turn on the power again.
DC
OK
04-10
Page 81
Trouble shooting 3 E12.3 INDOOR UNIT Error Method:
Number excess of device in Wired remote contorller system (2 Wires RC)
Indicate or Display:
Indoor Unit : Operation LED 1 times Flash, Timer LED 2 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E.5 U.1
Error Code : 1 2
Detective Actuators:
Wired remote controller ( 2-Wire ) Indoor unit Controller PCB circuit
Detective details:
When the number of connecting Indoor unit and Remote controller in one RCgroup exceeds more than 32 units.
Check Point 2 : Check Indoor unit controller PCB
The number of connecting indoor unit and Remote controller in one RCgroup were less than 32 units.
Forecast of Cause :
1. Wrong wiring of RCgroup 2. Indoor unit controller PCB failure
Check Point 1 : Wire installation Wrong RCgroup setting
Wrong wire connection in RCgroup (Please refer to the installation manual)
Change controller PCB and check the Error after setting remote controller address
Check if controller PCB damage
04-11
OK
Page 82
OUTDOOR UNIT Error Method ::
Outdoor Unit Network Communication 2 Error
OK
Communication PCB connection check
Communication PCB check
OK
Communication line connection, open check
OK
OK
OK
Outdoor unit Main PCB
Check Point 1 : Noise, momentary open, voltage drop
Check if temporary voltage drop was not generated. Check if momentary open was not generated. Check if ground is connection correctly or there are no related cables near the power line.
Check Point 2 : Check the indoor unit power supply
Main power ON check
Power cable connection and open check
Check Point 3 : Check the communication line connection
Detective Actuators:
Forecast of Cause :
No communication for 180 seconds or more from an indoor unit which received communication once.
No communication for 180 seconds or more from all indoor units that once received communication.
Check Point 4 : Check the Terminal resistor setting
Terminal resistor setting check
Check Point 6 : Replace Main PCB (outdoor unit/ indoor unit)
Check Point 5 : Check the communication PCB (outdoor unit/ indoor unit)
Change Main PCB and set up the original address.
Detective details:
1. Noise, momentary open, voltage drop 2. Indoor unit power off
3. Communication line connection defective 4. Terminal resistor setting mistake
5. Communication PCB mounting defective, Communication PCB defective
6. Control PCB defective
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash, Filter LED Continuous Flash. / Operation LED 1 times Flash, Timer LED 4 Times Flash, Filter LED Continuous Flash. *
Outdoor Unit : E. 1 4. 2
Error Code : 9 U / 1 4 / 1 6 / 1 4. 2
Trouble shooting 4 E14. 2
Indicate or Display:
Refer to SERVICE INFORMATION Network communication Abnormal
* Indoor unit indicates 9 U or 1 4 Peripheral device indicates 1 4 or 1 6
04-12
Page 83
Trouble shooting 5 E14. 3 INDOOR UNIT Error Method: Indoor unit Network communication Error
Indicate or Display:
Indoor Unit : Operation LED 1 times Flash, Timer LED 4 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E.1 4. 1 / 1 4. 2 *
Error Code : 1 4 / 1 6 / 9 U / 14.1 / 14.2 / 14.3 *
Detective Actuators:
Indoor unit Controller PCB circuit Indoor unit Communication PCB
Detective details:
When the cut-off of network communication is detected (more than 90 seconds passed since the last receipt of Outdoor unit signal).
Check Point 2 : Check the connection
After turning off the power, check and correct followings.
Is Indoor Communication PCB loose?
Check loose or removed connection of communication line Indoor unit => Outdoor unit.
When the signal amplifier is connected , Check the error indication of signal amplifier. ( Refer to the installation manual)
Check Point 3 : Check Communication PCB
Replace Communication PCB of the Indoor units that have the error.
OK
Forecast of Cause :
1. Outside cause 2.Connection failure 3. Communication PCB failure 4. Controller PCB failure
Check Point 1 : Check if any outside cause such as voltage drop or noise
Instant voltage drop ----- Check if there is any electric equipment with a large load within the same circuit. Momentary power failure ----- Check contact failure or leak current in power supply circuit
>>Check power supply for Outdoor Unit as well.
Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave). And check the complete insulation of grounding.
>>If the same symptom does not reappear after resetting the power, possibility of noise is high.
Check Point 4 : Check Controller PCB
OK
Replace controller PCB of the Indoor units that have the error.
* Outdoor unit indicates 1 4.1 or 1 4.2 (No communication from 14.3 Error Indoor unit) Peripheral device indicates 1 4 or 1 6
Refer to SERVICE INFORMATION Network communication Abnormal
04-13
Page 84
Trouble shooting 6 E14. 5
OUTDOOR UNIT Error Method:
The number of Indoor unit shortage Error
Indicate or Display: Outdoor Unit : E.1 4. 5
Error Code : 9 U / 1 4 / 1 6 / 1 4. 5 / 1 4. 3 *
Detective Actuators:
Outdoor unit Main PCB
Detective details:
When the indoor unit number decreases for 180 seconds from the memorized maximum indoor units number after power(Breaker) ON.
Communication PCB connection check
Communication PCB check
Communication line connection, open check
Check Point 5 : Check the communication PCB (indoor unit/ outdoor unit)
1. Indoor unit power off 2. Noise, momentary open, voltage drop
3. Communication line connection defective 4. Terminal resistor setting mistake
5. Communication PCB mounting defective, Communication PCB defective
6. Controller PCB defective
Check Point 2 : Noise, momentary open, voltage drop
Check if temporary voltage drop was not generated. Check if momentary open was not generated. Check if ground is connection correctly or there are no related cables near the power line.
Check Point 2 : Check the indoor unit power supply
Main power ON check
Power cable connection and open check
Check Point 3 : Check the communication line connection
Check Point 4 : Check the Terminal resistor setting
Terminal resistor setting check
Check Point 6 : Replace Main PCB and Communication PCB (indoor unit/ outdoor unit)
Change Main PCB and Communication PCB, and set up the original address.
Forecast of Cause :
Check Point 1 : Find the indoor unit that the communication is lost.
Check system drawing and service tool.
OK
OK
OK
OK
OK
OK
Attention!!
If the failure indoor unit is pinpointed and it needs to erase the error indication, it can be reset by function setting (F3-41: Maximum memorized indoor unit number reset).
Caution!!
Even if normal, this error occurs temporarily by the timing of the power ON of outdoor unit, indoor unit, and signal amplifier.
In this case, please wait for 5 minutes after turning on all the equipments.
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash, Filter LED Continuous Flash. /
Refer to SERVICE INFORMATION Network communication Abnormal
*Peripheral device indicates 14,16
04-14
Page 85
Trouble shooting 7 E16. 1 INDOOR UNIT Error Method:
Transmission PCB Connection Error
Indicate or Display:
Indoor Unit : Operation LED 1 times Flash, Timer LED 6 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E.1 4.1, 1 4.2 *
Error Code : 1 6 *
Detective Actuators:
Indoor unit Controller PCB circuit Indoor unit Communication PCB
Detective details:
When Parallel communication error (Communication reset occurs continuously more than specified times) is detected.
Check Point 3 : Replace Communication PCB
Replace Communication PCB ( If the symptom does not change, replace Controller PCB and set up the original address.
Check Point 1-2 : Check outside cause such as noise
Check the complete insulation of the grounding. Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
Check Point 1-1 : Reset the power
Check Point 2 : Check Connection
YES
NO
Does LED error indication reappear?
Check if Indoor Communication PCB is removed.
OK
Forecast of Cause :
1. Connection failure 2. Outside cause 3. Communication PCB failure 4. Controller PCB failure
* Outdoor unit indicates 1 4.1 or 14.2 (No communication from Indoor unit) Peripheral device indicates 1 6 ( 1 6.4 Error) Service Tool indicates 14.3 ( Missing Error Indoor unit)
04-15
Page 86
Trouble shooting 8 E16. 4 INDOOR UNIT Error Method: Communication Error Between Controller and Indoor unit
Indicate or Display:
Indoor Unit : No Display
Outdoor Unit : No Display
Error Code : 1 6 (Peripheral Unit )
Detective Actuators:
Indoor unit Controller PCB circuit Indoor unit Communication PCB
Detective details:
When the cut-off of network communication is detected (more than 90 seconds passed since the last receipt of Outdoor unit signal).
Check Point 2 : Check the connection
After turning off the power, check and correct followings.
Is Indoor Communication PCB loose?
Check loose or removed connection of communication line Indoor unit => Outdoor unit.
Refer to SERVICE INFORMATION Network communication Abnormal
When the signal amplifier is connected , Check the error indication of signal amplifier - Refer to the Installation manual-
Check Point 3 : Check Communication PCB
Replace Communication PCB of the Indoor units that have the error.
OK
Forecast of Cause :
1. Outside cause 2.Connection failure 3. Communication PCB failure 4. Controller PCB failure
Check Point 1 : Check if any outside cause such as voltage drop or noise
Instant voltage drop ----- Check if there is any electric equipment with a large load within the same circuit. Momentary power failure ----- Check contact failure or leak current in power supply circuit
>>Check power supply for Outdoor Unit as well.
Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave). And check the complete insulation of grounding.
>>If the same symptom does not reappear after resetting the power, possibility of noise is high.
Check Point 4 : Check Controller PCB
OK
Replace controller PCB of the Indoor units that have the error.
04-16
Page 87
Trouble shooting 9 E26. 4 INDOOR UNIT Error Method:
Address Duplication in Wired remote contorller system
Indicate or Display:
Indoor Unit : Operation LED 2 times Flash, Timer LED 6 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E.5 U.1
Error Code : 2 6
Detective Actuators:
Wired remote controller ( 2-Wire ) Indoor unit Controller PCB circuit
Detective details:
When the duplicated address number exists in one RCgroup
Check Point 3 : Check Indoor unit controller PCB
Forecast of Cause : 1. Wrong wiring of RCgroup 2. Wrong remote address setting 3. Indoor unit controller PCB failure
4. Remote controller failure
Check Point 1 : Wire installation
Wrong wire connection in RCgroup (Please refer to the installation manual)
Change controller PCB and check the Error after setting remote controller address
Check if controller PCB damage
Check Point 2 : Wrong RCgroup setting
The duplicated address number is not existing in one RCgroup
04-17
Page 88
Trouble shooting 10 E26. 5 INDOOR UNIT Error Method:
Address setting Error in Wired remote contorller system
Indicate or Display:
Indoor Unit : Operation LED 2 times Flash, Timer LED 6 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E.5 U.1
Error Code : 2 6
Detective Actuators:
Wired remote controller ( 2-Wire ) Indoor unit Controller PCB circuit
Detective details:
When the address number set by auto setting and manual setting are mixed in one RC group
Check Point 3 : Check Indoor unit controller PCB
Forecast of Cause : 1. Wrong wiring of RCgroup 2. Wrong remote address setting 3. Indoor unit controller PCB failure
4. Remote controller failure
Check Point 1 : Wire installation
Wrong wire connection in RCgroup (Please refer to the installation manual)
Check if controller PCB damage Change controller PCB and check the Error after setting remote controller address
Check Point 2 : Wrong RCgroup setting
The given address number by auto setting (00) and the manual set number (Except 00) were not existing in one RCG. The remote controller address setting by U.I. were not existing same address.
04-18
Page 89
Trouble shooting 11 E29. 1 INDOOR UNIT Error Method:
Connection unit number error (Indoor unit in Wired remote controller system)
Indicate or Display:
Indoor Unit : Operation LED 2 times Flash, Timer LED 9 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E.5 U.1
Error Code : 2 9
Detective Actuators:
Wired remote controller ( 2-Wire ) Indoor unit Controller PCB circuit
Detective details:
When the number of connecting indoor units are out of specified rule.
Check Point 2 : Check Indoor unit controller PCB
Forecast of Cause :
1. Wrong wiring/ Number of I.U, RC in RCgroup 2. Indoor unit controller PCB defective
Check Point 1 : Wire installation
Wrong number of connceting indoor unit
Change controller PCB and check the Error after setting remote controller address
Check if controller PCB damage
04-19
Page 90
Trouble shooting 12 E29. 2 INDOOR UNIT Error Method:
Connection unit number error (Remote controller)
Indicate or Display:
Indoor Unit : No Display
Outdoor Unit : No Display
Error Code : 2 9
Detective Actuators:
Wired remote controller ( 2-Wire )
Detective details:
When the number of connecting remote controller are out of specified rule.
Check Point 2 : Check Indoor unit controller PCB
Forecast of Cause :
1. Wrong wiring / Wrong number of connecting RC in RCgroup 2. Remote controller PCB defective
Check Point 1 : Wire installation
Wrong number of connceting remote controller
Change controller PCB and check the Error after setting remote controller address
Check if controller PCB damage
04-20
Page 91
Trouble shooting 13 E31. 3
INDOOR UNIT Error Method: Indoor unit Power Frequency Abnormal
Indicate or Display:
Indoor Unit : Operation LED 3 times Flash, Timer LED 1 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E.5 U.1
Error Code : 3 1
Detective Actuators:
Indoor Unit Controller PCB Circuit
Detective details:
When 5 continuous failures occurred at Power frequency test.
Forecast of Cause :
1. Outside cause 2. Installation failure 3. Defective connection of electric components
4. Controller PCB defective
Check Point 2 : Check Installation condition
NO
Check Point 3 : Check connection of electric components
YES
Check Cable/Breaker
Check loose or removed connection >> If Installation defect is found, correct it by referring to Installation Manual.
OK
Check power supply voltage (AC198 - 264V between
Indoor unit terminal 1 and 2)
Check connection of Connector (any lose connector or
incorrect wiring)
Check any shortage or corrosion on PCB.
OK
Check Point 1-1 : Reset Power Supply
Does abnormal LED indication show again?
Check Point 1-2 : Check outside cause (Voltage drop or noise, etc.)
Instant drop ---- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line (Neon bulb or electric equipment that may cause harmonic wave). Check the complete insulation of grounding.
Check Point 4 : Replace Controller PCB
Change Controller PCB and set up the original address.
AC
04-21
Page 92
Trouble shooting 14 E32. 1 INDOOR UNIT Error Method:
Indoor unit PCB Model Information Error
Indicate or Display:
Indoor Unit : Operation LED 3 times Flash, Timer LED 2 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E.5 U.1
Error Code : 3 2
Detective Actuators:
Indoor Unit Controller PCB Circuit
Detective details:
3 continuous failure of lead test of EEPROM at Power ON, or Apparent Model information error from EEPROM. Also, Error on Model information upon model information test of EEPROM, or Model information of EEPROM not possible to recover.
Forecast of Cause :
1. Outside cause 2. Connection failure of electric components 3. Controller PCB defective
Check Point 1-2 : Check outside cause (Voltage drop or noise, etc.)
Instant drop --- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line (Neon bulb or electric equipment that may cause harmonic wave). Check the complete insulation of grounding.
Check Point 3 : Replace Controller PCB
Change Controller PCB and set up the original address.
Check Point 1-1 : Reset Power Supply
Check Point 2 : Check Indoor Unit electric components
YES
NO
Does abnormal LED indication show again?
Check all connectors (loose connector or incorrect wiring)
Check any shortage or corrosion on PCB.
OK
Note : EEPROM
EEPROM(Electronically Erasable and Programmable Read Only Memory) is a non­volatile memory which keeps memorized information even if power is turned off. It can change the contents electronically. To change the contents, it uses higher voltage than normal, and it can not change a partial contents. (Rewriting shall be done upon erasing the all contents.) There is a limit in a number of rewriting.
04-22
Page 93
Trouble shooting 15
E32. 3
INDOOR UNIT Error Method:
Indoor unit EEPROM Access Error
Indicate or Display:
Indoor Unit : Operation LED 3 times Flash, Timer LED 2 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E.5 U.1
Error Code : 3 2
Detective Actuators:
Indoor Unit Controller PCB Circuit
Detective details:
When 3 continuous failure occurred on lead test of EEPROM.
Forecast of Cause :
1. Outside cause 2. Defective connection of electric component 3. Controller PCB defective
Check Point 1-2 : Check outside cause (Voltage drop or noise, etc.)
Instant drop --- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line (Neon bulb or electric equipment that may cause harmonic wave). Check the complete insulation of grounding.
Check Point 3 : Replace Controller PCB
Change Controller PCB and set up the original address.
Check Point 1-1 : Reset Power Supply
Check Point 2 : Check Indoor Unit electric components
YES
NO
Does abnormal LED indication show again?
Check all connectors (loose connector or incorrect wiring)
Check any shortage or corrosion on PCB.
OK
04-23
Page 94
Trouble shooting 16 E32. 7 INDOOR UNIT Error Method:
Indoor unit microcomputer self-check error
Indicate or Display:
Indoor Unit : Operation LED 3 times Flash, Timer LED 2 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E.5 U.1
Error Code : 3 2
Detective Actuators:
Indoor Unit Controller PCB Circuit
Detective details:
When the error is detected by the self-diagnosis of a microcomputer
Forecast of Cause :
1. Outside cause 2. Defective connection of electric component 3. Controller PCB defective
Check Point 1-2 : Check outside cause (Voltage drop or noise, etc.)
Instant drop --- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line (Neon bulb or electric equipment that may cause harmonic wave). Check the complete insulation of grounding.
Check Point 3 : Replace Controller PCB
Change Controller PCB and set up the original address.
Check Point 1-1 : Reset Power Supply
Check Point 2 : Check Indoor Unit electric components
YES
NO
Does abnormal LED indication show again?
Check all connectors (loose connector or incorrect wiring)
Check any shortage or corrosion on PCB.
OK
04-24
Page 95
Trouble shooting 17 INDOOR UNIT Error Method: Indoor Unit power supply error for FAN motor 1 (Outdoor Air unit)
Indicate or Display: Outdoor Unit : E.5 U.1
Error Code : 39.1
Detective Actuators:
Indoor Unit Controller PCB Circuit Indoor Unit filter PCB Circuit
Detective details:
When the DC power inpu t for Fan motor < W500 - W5 01 on the Filter PCB> becomes lower voltage t han the specified voltage.
Check Point 2 : Check wire connection
Wire lose connection / damage between the CN21on the Controller PCB and CN250 on the Filter PCB In case of Model 72, between W530 (W531) on the filter PCB and capacitor.
>>If there is abnormal on the wire, replace it
OK
Forecast of Cause :
1. Noise momentary open, voltage drop 2. Wire conne ction 3. Fan motor
4.
Peripheral electric devices 5. Filter PCB 6. Controller PCB
Check Point 1 : Check if any outside cause such as voltage drop or noise
Instant voltage drop ----- Check if there is any electric equipment with a large load within the same circuit. Momentary power failure ----- Check contact failure or leak current in power supply circuit Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave). And check the complete insulation of grounding.
>>If the same symptom does not reappear after resetting the power, possibility of noise is high.
OK
Check Point 3 : Check rotation of Fan / wire resistance
Rotate the applicable fan by hand when operation is off.
OK
Disconnect the connector from the controller PCB and Check resistance value of Motor connector
Check Point 4 : Check peripheral devices, Posistor, Capacitor, Diode bridge
Check resistance value, short circuit, visible damage
>>If there is abnormal , replace it
Check Point 5 : Replace Filter PCB
Change filter PCB
Check Point 6 : Replace Controller PCB
Change Controller PCB and set up the original address.
OK
NG
E.39.1
04-25
Page 96
Trouble shooting 18 INDOOR UNIT Error Method: Indoor Unit power supply error for FAN motor 2 (Outdoor Air unit)
Indicate or Display: Outdoor Unit : E.5 U.1
Error Code : 39.2
Detective Actuators:
Indoor Unit Controller PCB Circuit Indoor Unit filter PCB Circuit
Detective details:
When the DC power inpu t for Fan motor < W530 - W5 31 on the Filter PCB> becomes lower voltage t han the specified voltage.
Check Point 2 : Check wire connection
Wire lose connection / damage between the CN21on the Controller PCB and CN250 on the Filter PCB In case of Model 72, between W530 (W531) on the filter PCB and capacitor.
>>If there is abnormal on the wire, replace it
OK
Forecast of Cause :
1. Noise momentary open, voltage drop 2. Wire conne ction 3. Fan motor
4.
Peripheral electric devices 5. Filter PCB 6. Controller PCB
Check Point 1 : Check if any outside cause such as voltage drop or noise
Instant voltage drop ----- Check if there is any electric equipment with a large load within the same circuit. Momentary power failure ----- Check contact failure or leak current in power supply circuit Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave). And check the complete insulation of grounding.
>>If the same symptom does not reappear after resetting the power, possibility of noise is high.
OK
Check Point 3 : Check rotation of Fan / wire resistance
Rotate the applicable fan by hand when operation is off.
OK
Disconnect the connector from the controller PCB and Check resistance value of Motor connector
Check Point 4 : Check peripheral devices, Posistor, Capacitor, Diode bridge
Check resistance value, short circuit, visible damage
>>If there is abnormal , replace it
Check Point 5 : Replace Filter PCB
Change filter PCB
Check Point 6 : Replace Controller PCB
Change Controller PCB and set up the original address.
OK
NG
E.39.2
04-26
Page 97
Trouble shooting 19 E39. 3 INDOOR UNIT Error Method:
Indoor Unit Power Supply Error of AC24V System
Indicate or Display:
Outdoor Unit : E.5 U.1 Error Code : 3 9
Detective Actuators:
Indoor Unit Power Supply PCB Circuit Indoor Unit Power Trans Indoor Unit Controller PCB
Detective details:
When the AC voltage of the Power Trans output , Is lower than 24V.
Check Point 2 : Check the connection of terminal
After turning off the power, check & correct of followings.
Check Point 3 : Check the Power Trans and Power Supply PCB
Check terminal voltage of Power Trans and Power Supply PCB connector CN113 (AC24V IN). If AC 0V, Power Trans is failure
>>Replace Power Trans
OK
Forecast of Cause : lamronbA noitcennoC lanimreT . 1 lamronbA ylppuS rewoP .2
3. Power Trans
4. Power Supply PCB 5. Controller PCB 6. Cable Connection failure
>>Check the connection of terminal between Power Trans and Power Supply PCB(CN113), and Check if there is a disconnection or short of the cable.
If AC24V, To the Check Point 4.
Check Point 1 : Check the Power Supply PCB and Controller PCB
Check the connection of connection terminal between Power Supply PCB(CN24) and Controller PCB(CN114) and check if there is a disconnection or short of the cable.
OK
AC
Check Point 4 : Replace the Power Supply PCB
Replace Power Supply PCB.
OK
Check Point 5 : Replace the Controller PCB
Replace Controller PCB and set up the original address.
OK
04-27
Page 98
Trouble shooting 20 E3A. 1 INDOOR UNIT Error Method:
Indoor unit communication circuit (WRC) microcomputers communication Error
Indicate or Display:
Indoor Unit : Operation LED 3 times Flash, Timer LED 10 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E.5 U.1
Error Code : 3 A
Detective Actuators:
Wired remote controller ( 2-Wire ) Indoor unit Controller PCB circuit
Detective details:
When the indoor unit(s) detects the configuration of RCG abnormal or the indoor unit detects lack of primaly -remote controller.
Check Point 2 , 3: Check Indoor unit controller PCB
Forecast of Cause : 1. Terminal connection abnormal 2. Wired remote controller failure
3. Indoor unit controller PCB defective
Check Point 1 : Check the connection of terminal
Indoor unit - Check the connection of terminal between remote control and indoor unit, or between Indoor units and check if there is a disconnection or short of the cable.
Check terminal voltage of controller PCB connector CNC01 (Power supply for remote)
If DC12V, Remote control failure (Controller PCB is OK) >>> Replace Remote controller If DC0V, Controller PCB failure (Remote is OK) >>> Replace Controller PCB
In case of re-installation is done due to remobed connector or incorrect wiring, turn on the power again.
After turning off the power supply, check & correct the followings
04-28
Page 99
Trouble shooting 21 E41. 1 INDOOR UNIT Error Method:
Inlet air temp. Sensor Error
Indicate or Display:
Indoor Unit : Operation LED 4 times Flash, Timer LED 1 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E.5 U.1
Error Code : 4 1
Detective Actuators:
Indoor Unit Controller PCB Circuit Inlet air temp Sensor
Detective details:
When Inlet air temp. sensor open or shortage is detected
Forecast of Cause :
1. Connector defective connection 2. Sensor defective 3. Controller PCB defective
Check Point 2 : Remove connector and check Sensor resistance value
Sensor characteristics (Rough value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 1 : Check connection of Connector
Check if connector is loose or removed Check erroneous connection Check if sensor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
6.5
35
8.0
30
10.012.515.820.225.933.6
3.032.772.502.221.941.661.391.15
3.683.483.27
2520151050
Temperature (
°C)
3.64.35.3
504540
OK
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Corresponding connector
If the voltage does not appear, replace Controller PCB and set up the original address.
Cassette type
Duct type
Compact Wall mounted type
Wall mounted type
Floor / Ceiling type
Compact Floor type
CN8
Room temp. Sensor (Black Wires)
Model Type
Resistance Value (k )
Temperature (°C)
DC
Voltage Value (V)
Voltage Value (V)
Resistance Value (k )
04-29
Page 100
Sensor Characteristics (Rough value)
If Thermistor is either open or shorted, replace it and reset the power.
Trouble shooting 22 E42. 1 INDOOR UNIT Error Method:
Indoor unit Heat Ex. inlet temp. sensor Error
Indicate or Display:
Indoor Unit : Operation LED 4 times Flash, Timer LED 2 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E.5 U.1
Error Code : 4 2
Detective Actuators:
Indoor Unit Controller PCB Circuit Heat Exchanger Inlet temp. Sensor
Detective details:
When open or shorted Heat Exchanger Inlet temp. sensor is detected
Forecast of Cause :
1. Connector defective connection 2. Sensor defective 3. Controller PCB defective
Check Point 1 : Check connection of Connector
Check if connector is loose or removed Check erroneous connection Check if thermistor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
OK
OK
Check Point 2 : Remove connector and check sensor resistance value
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Corresponding connector
Heat Ex Inlet temp. Sensor (Black Wires)
Model Type
32.4
35
40.0
30
49.862.579.1100.9129.8168.6
3.032.772.502.221.931.651.391.14
2520151050
Temperature (
°C)
17.821.626.3
3.693.493.27
504540
Temperature (°C)
DC
Voltage Value (V)
Resistance Value (k )
Voltage Value (V)
Resistance Value (k )
04-30
If the voltage does not appear, replace Controller PCB and set up the original address.
Cassette type Duct type Compact Wall mounted type Wall mounted type Floor / Ceiling type Compact Floor type
CN5 or CN9 CN9 CN5 or CN20 CN5 or CN9 CN9 CN5
Loading...