Fujitsu AUXK018GLAH, AUXK024GLAH, AUXK030GLAH, AUXK034GLAH, AUXK036GLAH Service Manual

...
SERVICE MANUAL
CONTENTS
1. TEST RUN
1-3 TEST RUN CONTROL................................................................................................
1-2-1 Check Items Before Power ON............................................................................
1-2-2 Check Items After Power ON...............................................................................
...................................................................................
1-1 EXECUTION PROCEDURE AND EXECUTION PRECAUTIONS.............................
1-2-4 Automatic address setting procedure for indoor units..........................................
01-01 01-03 01-03 01-04
01-07
1-2-3 Automatic address setting procedure for Signal amplifiers.................................. 01-06
01
-15
1-4 FIELD SETTING AND MONITOR MODE LIST FOR OUTDOOR UNIT..................... 01-16
2-1 INPUT / OUTPUT LIST..............................................................................................
2. OUTDOOR UNIT OPERATION CONTROL
2-2 COMPRESSOR OPERATION....................................................................................
02-01 02-02
02-02 02-03
2-2-3 Speed Range of Start,Stop,and Operation..........................................................
2-2-2 Capacity Control.................................................................................................
02-02
2-2-1 Operation / Stop Condition.................................................................................
2-5 SPECIAL OPERATION..............................................................................................
02-08 02-08 02-09
2-5-2 Pre-Heat Operation............................................................................................
2-5-1 Oil Recovery Operation......................................................................................
2-6 PROTECTIVE FUNCTION........................................................................................
02-10 02-10
2-6-1 Protective Function List......................................................................................
2-5-3 Defrost Operation Control..................................................................................
02-09
2-3 FAN CONTROL..........................................................................................................
02-04
2-4 EXPANSION VALVE CONTROL...............................................................................
02-07
02-04
0
2-06
2-3-3 Low noise mode..................................................................................................
02-07
2-3-4 Other Control.......................................................................................................
2-3-1 Cooling Operation...............................................................................................
02-05
2-3-2 Heating Operation...............................................................................................
1-2-5 Indoor unit connection check procedure ............................................................. 01-08
1-2-6 Test run from the outdoor Main PCB ........ ........................................................... 01-09
1-2-7 Test run from the Remote controller ..............................................................
...... 01-10
1-5 FIELD SETTING / FUNCTION SETTING FOR INDOOR UNIT.................................. 01-19
1-6 FIELD SETTING / FUNCTION SETTING FOR OUTDOOR AIR UNIT....................... 01-21
CONTENTS
3-2 MASTER CONTROL..................................................................................................
3-1-2 "AUTO" Position...................................................................................................
3-1-1 Fan Speed Setting...............................................................................................
3-1 FAN CONTROL...............
...........................................................................................
3. INDOOR UNIT OPERATION
3-2-1,2 Operation Mode Control.....................................................................................
3-2-3,4 Auto Changeover ..............................................................................................
03-01 03-01
03-01 03-02 03-02 03-05
3-3 LOUVER CONTROL..................................................................................................
3-2-5,6,7,8 "COOL"/"HEAT”Position .............................................................................
03-08 0
3-10
3-5 DRAIN PUMP OPERATION.......................................................................................
3-4 ELECTRONIC EXPANSION VALVE CONTROL......................................................
3-6 FUNCTION..................................................................................................................
03-14 03-14 03-15
3-6-1 Auto Restart.........................................................................................................
03-15
3-6-2 Icing Protection Control.......................................................................................
03-15
3-6-3 Oil Recovery Operation.......................................................................................
03-15
03-16
3-7 TIMER CONTROL......................................................................................................
03-17
3-7-1 Wireless Remote Controller................................................................................
03-17
3-7-2 Group Remote Controller..................................................................................... 03-19
3-7-3 Wired Remote Controller..................................................................................... 03-21
3-8 DX-KIT .............................................................................................
03-25
3-8-1 System configuration .......................................................................................
03-25
3-8-2,3 Fundamental functions .................................................................................... 03-26
3-8-4 Electrical expansion valve control for DX-KIT....................................................... 03-28
3-8-5 Drain pump operation for DX-KIT .................................................................... 03-28
3-8-6 Function .................................................................................. 03-29
....
................................
................................
3-6-4 Outdoor temperature protected operation for outdoor..........................................
CONTENTS
5-2-1 Indoor Unit............................................................................................................
5-2 WIRING DIAGRAM....................................................................................................
5-1 REFRIGERANT CIRCUIT..........................................................................................
5. APPENDING DATA
5-3-1 Pressure sensor..................................................................................................
05-01
05-03
05-03
5-2-2 Outdoor Unit.........................................................................................................
05-18
5-3 CHARACTERISTICS OF SENSORS........................................................................
05-22
05-22
5-3-2 Thermistor resistance..........................................................................................
05-23
5-3-3 Saturation temperature and saturation pressure tables (R410A)........................
05-24
5-3-4 Temperature and pressure of refrigerant (Graph)...............................................
05-25
6. DISASSEMBLY PROCESS
4-1-2 Outdoor Unit Display...........................................................................................
4-1-1 Indoor Unit Display..............................................................................................
4-1 NORMAL OPERATION..............................................................................................
4. TROUBLE SHOOTING
4-2 ABNORMAL OPERATION.........................................................................................
4-2-1 Indoor Unit Display..............................................................................................
04-01 04-01
04-02
04-03 04-03
4-2-4 Remote Controller Display...................................................................................
4-2-3 Error Code List for Outdoor Unit..........................................................................
4-2-2 Outdoor Unit Display...........................................................................................
4-3 TROUBLE SHOOTING..............................................................................................
04-04 04-05
4-2-5 Error Code List for Simple and Wired Remote Controller...................................
04-07
4-2-6 Error Code List for Group Remote Controller......................................................
04-07
4-2-7 Troubleshooting - No Error code -
rror Code List for External Switch Controller...
..................................................
04-08
4-2-8
Error Code List for Signal Amplifier....................
.................................................
04-08
4-2-9
Error Code List for Network Convertor
......
.........
.................................................
04-08
4-2-10 .................................................
04-08
04-06
04-09
4-3-1 Trouble Shooting With Error Code (Indoor unit) ..........................................
04-09
4-4 SERVICE PARTS INFORMATION............................................................................ 04-106
5-2-3 DX-KIT .........................................................................................................
05-20
........
E .
..................
. ..
4-3-2 Trouble Shooting With Error Code (Outdoor unit) ..........................................
04-39
. ...
4-3-3 Trouble Shooting With No Error Code ..........................................
04-76
. .....................
4-3-4 Trouble Shooting for Option Parts ..........................................
04-82
...........................
....
1. TEST RUN
Before execution
Execution 1/2
Location decision
Execution procedure and precautions Reason
1-1 EXECUTION PROCEDURE AND EXECUTION PRECAUTIONS
1. TEST RUN
Sleeve and insert work
Indoor unit installation
Refrigerant piping work
Drain piping work
Duct work
Heat insulation work
Electrical work
Outdoor unit foundation work
Outdoor unit installation
Refrigerant piping connection work
Air tightness test
Vacuum drying
Use new refrigerant piping of the thickness specified by the D&T manual.
Since R410A dedicated tools are necessary, prepare them in advance.
Absolutely avoid use of existing piping. If use of existing piping is unavoidable, the piping must be cleaned.
Use pipe that is not dirty inside. Confirm the design for the piping ( Diameter, Thickness ) When the pipe is left standing, protect it. Confirm the angle of separation tube and header correctly. Finish flaring exactly. Confirm the width across flats dimension and shape of flare nuts. Always blow nitrogen while brazing. Perform flushing before connecting the equipment.
Always make the downward slope of the drain pipe 1/100 or greater and make the horizontal length within 20m.
Use hard polyvinyl chloride pipe as the drain pipe. Support the drain pipe between 1.5m to 2.0m. Use pipe of 1 rank up (VP30 or greater) as central piping.
Prevention of water leakage
Foreign matter, water, etc. in the piping will cause faulty cooling and compressor trouble.
Incorrect pipe diameter will cause faulty cooling
Incorrect angle of separation tube or header will be cause poor cooling or refrigerant noise problem
Refrigerant leakage will cause low performance and abnormal stopping
Prevention of water leakage
Prevention of water leakage
Refrigerant leakage will cause low performance and abnormal stopping.
Refrigerant leakage will cause low performance and abnormal stopping.
Mixing in of vacuum pump oil by reverse flow will cause equipment trouble.
Always use a level and keep the indoor unit level. If the equipment is tilted toward the drain port, install it so that the tilt is within 13/32in.(10mm). Excessive tilt will cause water leakage.
Select the size of the heat insulating material according to the ambient temperature and relative humidity of the refrigerant. Use a heat insulating material having a heat conductivity of 0.043W/ (m.k) or less.
When making flare connections always use a torque wrench and tighten the flare nut positively to the specified torque.
Pressurize the product with nitrogen gas up to the design pressure and conduct a 24Hr air tightness test.
Install a vacuum pump with reverse flow check mechanism or a reverse flow check adapter to a conventional vacuum pump and use.
Pump down sufficiently. Approximately 1 hour or longer after -14.5psi (-0.10MPa) reached. Allow to stand for approximately 1 hour after stopping the vacuum pump and confirm that the needle does not return.
Air purging using refrigerant is strictly prohibited.
1
1
1
2
3
2 3 4 5 6
1
2 3 4
2
3
This function is used for vacuuming the indoor unit and the connection piping.
Note: For starting Vacuuming mode, the refrigerant address setting has to be finished.
When the [vacuuming mode] is set, <Push switch setting, F3:21> EEV of connected all indoor units opens. So, the vacuuming indoor unit and piping becomes easier.
When the vacuuming ends, please turn off the power supply for all of the indoor units and the outdoor unit, [vacuuming mode] is released.
*
Vaccuming mode
recommend the vacuuming mode
Do not install the units in the place not recommended in the installation manual.
The performance may drop significantly due to the protection controlling
Use of a refrigerant other than the specified refrigerant will invite equipment trouble
Confirmation of Refrigerant used
Preparation of execution drawings
Confirmation of installation site
Preparation before execution
Check the characteristics of the refrigerant used and grasp the special features of the refrigerant. If refrigerant must be charged, always charge the refrigerant specified for the product.
*Confirm the product design pressure. < R410A 4.2MPa >
Prepare the design for the system
Secure the necessary pressure resistance.
When performing piping work, observe the following items so that the inside of the piping is clean and air tight.
7 8
01-01
[Note] Perform in the power OFF state.
Execution 2/2
Set according to the length of the connection piping. Set to "Standard 40 to 65m" at the factory. Set using the push button SW on the outdoor unit main PCB. < Refer to the Page 01-17 Setting mode F2-00 > Set the pipe length to be the nearest indoor unit from the outdoor unit
Set the refrigerant circuit address and indoor unit address. Can be set by rotary SW on the indoor unit PCB ( Main PCB or Switch
PCB) or from a remote controller or from a push button SW on the outdoor unit Main PCB < Automatic address setting, Refer to the Page 01-07 Setting mode F3-11>
Initial setting
Gas leak test
Use an R410A dedicated leak tester to check for gas leaks.
1
2
3
Confirm the additional refrigerant amount with the installation manual, etc.
Always take the R410A refrigerant from the cylinder liquid phase and charge it using the gas phase. (Do not lay a cylinder with siphon pipe on its side.)
Use an R410A dedicated gauge manifold and charging hose. Charge refrigerant using the liquid pipe. When the defined amount of refrigerant cannot charge using the
liquid pipe, charge refrigerant using the gas pipe while opearting the cooling test run. Charge refrigerant bit by bit with cautious operation of valve for the liquid refrigerant back prevention.
If taken from the air phase, since the composition of the refrigerant which is charged will change, low performance and abnormal stop will occur easily.
Prevent erroneous sealing in of refrigerant.
A leak tester for other than R410A cannot detect leaks.
Set the refrigerant circuit address.
ROTARY SW: REF ADX10, X1
4
Turnover & explanation of operation
Address setting for Indoor unit
Test run & adjustment
Piping length setting
Addition refrigerant charging
5
Indoor unit connection check
[Note] Perform setting by push button SW on the outdoor unit Main PCB in the power ON state
 after all indoor units have stopped operation.
When setting the address of Signal amplifier, please refer to the installation manual of the signal amplifier.
The address setting can be set by automatically from 1 outdoor unit on the network. < Refer to the Page 01-06 Setting mode F3-10 >
Address setting for Signal Amp
- When using signal Amps -
[Note] Manual setting: Set the rotary SW on the PCB in the power OFF state.
Automatic address setting: Perform setting by push button SW on the outdoor unit Main PCB in the
 power ON state after all indoor units have stopped operation.
[Note] Perform in the power ON state after all indoor units have stopped operation
[Note] Manual setting: Set the rotary SW on the PCB in the power OFF state.
Automatic address setting: Perform setting by push button SW on the outdoor unit Main PCB in the
   power ON state after all indoor units have stopped operation.
Dual address setting No. is not allowed in one network.
When the setting is not same as the real piping length, the system may not work correctly.
Dual address setting No. is not allowed in one network.
Dual address setting No. is not allowed in one network.
Normal operation will not be possible without performing the indoor unit connection check.
Before starting the system, check on the number of indoor units and the total capacity. < Refer to the Page 01-08 Setting mode F3-12 >
Execution procedure and precautions Reason
1
2
Confirm the DIP SW setting SET 1: Factory setting, SET 2 : All OFF
If the DIP SW setting is wrong, the sys­tem may not work correctly
3
Confirm the Terminal resister setting SET 5-4 OFF: Disable, ON: Enable
If the Terminal resister setting is wrong, the system may detect transmission error
If the pipe length is set as the farthest indoor unit, the nearest operating indoor unit may be stopped the operation by the icing up protection as by over cooling.
01-02
Outdoor unit: AJ*072/090LELAH: 20A / AJ*108LELAH: 25A
Indoor unit:
20A
Leakage current: 100 mA 0.1sec or less
Install a breaker (Included with Earth Leakage Circuit Breaker) in accordance
with the related laws and regulations.
Outdoor unit:
2.5mm2 2 wires + Ground
Outdoor unit side: 400V 3 50Hz
Indoor unit side:
Use crimp-type terminals with insulating sleeves for stranded conductor cable
Power source
Shall be no scratches, deformation, etc. (Be careful of deformation of the front panel)
Shall be checked and entered in the check sheet.
Shall be checked and entered in the check sheet.
Connection points check & loose terminal block screws check
0.33mm
2
, shielded wire used (22AWG)
Connection points check & loose terminal panel screws check
Check whether or not the heat insulation material is installed w
ithout a gap.
DIP SW : SET1 (1 ~4), Factory setting SET2, SET3,SET5-1,2,3: ALL OFF
T Refer to the Installation manual 7.2.2
erminal resistor setting SET5 - 4 OFF: Disable, ON: Enable
Refrigerant circuit address setting (SET : REF AD x10 and REF AD x1)
Comparison of calculated value and value written on electrics box. Entered in check sheet.
Refer to the installation manual 8.3.2
Gas pipe: fully open
Liquid pipe: fully open
There shall be no scratches, deformation, tilting, etc.
Shall be checked and entered in the check sheet.
Shall be installed positively.
Connection points check & loose terminal panel screws check
0.33mm
2
, shielded wire used (22AWG)
Connection points check & loose terminal panel screws check
Connection points check & loose terminal panel screws check
Check whether or not the heat insulation material is installed without a gap.
Refrigerant circuit address (REF AD)
Indoor unit add
ress (IU AD)
At automatic address setting, IU AD/REF AD shall be [0].
Remote controller address (RC AD)
Function setting (Remote controller custom code/ external input switching/
auxiliary heater ON-OFF)
Indoor
unit
Outdoor
unit
Judgement standard
Check
Check contentsProcedure
1-2 TEST RUN METHOD
1-2-1 Check Items Before Power ON
01-03
[Note] If operated with the 3-way valve closed, the oil discharged from the compressor will not be returned and will lead to trouble.
Circuit breaker capacity
Type of power source wiring
Supply power source
Appearance
Serial No.
Drain cap installation
Power source wiring connection
Type of communication line
Communication line connection
Type of remote contr
oller wiring
Remote controller wiring connection
Connection piping
Rotary SW setting
DIP-SW setting
Appearance
Serial No.
Outside air temperature
Power source wiring connection
Type of communication line
Communication line connection
Connection piping
DIP-SW setting
Rotary SW setting
Additional refrigerant amount
3-way valve
Wiring on terminal blocks
Power cable: 6.0mm / Earth cable: 6.0mm Limited wiring length : 62 m
Indoor unit:
2
2
2 wire type : 16 to 22AWG (0.33 to 1.25mm ) 3 wire type : 22AWG (0.33mm )
2 2
230V 1 50Hz
Addresses shall be assigned to all indoor units / Signal amps. Check for unset or duplicated addresses. < For the setting, Refer to the page 01-06, 07 >
All the indoor units in the same refrigerant
circuit
shall enter the cooling test run
state.
The outdoor units corresponding to the operation capacity of the indoor
units shall operate. < Test operation procedure, Refer to the page 01-09,10 >
Cooling test run
All of the indoor units operation
(after 30 mins)
Automatic address setting
Address read
Outdoor unit circuit breaker ON
Indoor unit circuit breaker ON
Check lighting of Main PCB LED101 and 7-segment display.
Check whether or not indoor unit OPERATION and TIMER lamps flash alternately.
Address setting/ check
There shall be no Error information on the 7-segment display on the Main PCB.
3 Phase: 342 to 456V
These shall be no abnormal sound or abnormal vibration.
The outdoor fan shall not make a moaning sound. There shall be no discharge air leaking from the outdoor duct.
There shall be no pipe chattering sound or flute sound generated.
HPS: 2.7 ~ 3.0 MPa
LPS: 0.9 ~ 1.0 MPa
TH1: 81°C
TH4: 15°C
TH21: 27°C
TH22: 11°C
TH24: 13°C
Shall operate corresponding to the operation capacity of the indoor units.
Service tool used, output (CSV Excel)
Outdoor unit push button SW operation
<On service tool>
High pressure
Low pressure
Discharge pipe temperature (outdoor unit)
Suction pipe temperature (outdoor unit)
Inlet air temperature (indoor unit)
Heat exchange inlet temperature (indoor unit)
Heat exchange outlet temperature (indoor unit)
Compressor operation
Data output
1-2-2 Check Items After Power ON
Function setting
Are the necessary functions set ? < For the setting, Refer to the page 01-16
〜19 >
Outdoor unit Main PCB push button SW setting/check
[Note]
Cooling test run for each refrigerant circuit. If multiple refrigerant circuits are test run at the same time, refrigerant circuit address setting errors cannot be detected.
Judgement standard
Check
Check contentsProcedure
Power ON
Inlet air temperature and outlet air temperature difference shall be 10°C or greater.
There shall be no abnormal sound or abnormal vibration.
There shall be no water leakage. There shall be no condensation on the drain, cabinet, piping, and discharge port.
Shall operate according to the settings. (ON-OFF, set temperature change)
<Indoor unit service tool + actual measurement>
Outlet air temperature
Abnormal sound/abnormal vibration
Water leakage check
Remote controller operation
<Outdoor unit>
Outdoor Main PCB 7-seg. display
Operation voltage
Abnormal sound/ abnormal vibration
[Note] Turn on all indoor units power in the same refrigerant circuit address.
Indoor unit connection check
Are the number of connecting indoor units correct ? Is the total capacity of indoor units correct ? < For the checking, Refer to the page 01-08 >
Indoor unit
connection check
Address record
Address hold check
All the indoor units and outdoor units of the same refrigerant circuit can be checked on the service tool.
Enter the set addresses in the check sheet.
Check whether or not the address setting is held by the service tool after indoor/outdoor circuit breakers were turned OFF to ON.
[Note] Before connecting service tool, the address setting has to be completed.
01-04
When the system operates with the indoor units remaining no power, it is cause of malfunction.
Fan operation
Louver operation (except duct)
Outlet air temperature
Abnormal sound/abnormal vibration
Water leakage check
Remote controller operation
Indoor unit individual operation
Shall be switched to all fan speeds in the cooling mode.
Louver shall be switched to all positions. Shall also swing.
Inlet air temperature and outlet air temperature difference shall be 10°C or greater.
There shall be no abnormal sound or abnormal vibration.
There shall be no water leakage. There shall be no condensation on the drain, cabinet, piping, and discharge port.
Shall operate according to the settings. (ON-OFF, set temperature change)
Judgement standard
Check
Check contentsProcedure
These are representative figures of AJ*108LELAH at the standard condition. ( Indoor : 27
°C,
Outdoor : 35°C ) If conditions are different from those above mentioned, the figures will be changed slightly. It depends on following conditions.
Outdoor unit capacity Indoor and outdoor temperature Indoor unit capacity Pipe length etc
<Indoor unit service tool + actual measurement>
1. Error occured
- Check on the Error code on the Remote controller or Indoor unit or Outdoor unit or Service tool and check the description of the Error code.
< Refer to the Trouble shooting in the Service manual.> < Refer to the Execution of precautions 1-1 and Check item Before power ON 1-2-1>
2. No good performance without error code
- Check if the protection controlling is operating or not Evaporator Icing up protection, High discharge temperature protection,etc.
< Refer to the part of protection controlling in the Service manual >
- Check on the refrigerant circuit Refrigerant amount, Pipe blockage, Wrong position of separation pipes etc.
< Refer to the Execution of precautions 1-1 and Check item Before power ON 1-2-1> < Refer to the regulation of installation in the Installation manual>
Trouble shooting on Test run operation
01-05
1-2-3 Automatic address setting for signal amplifiers
When using signal amplifiers
When setting the address of the signal amplifier, please use the factory setting.
(See the installation manual of the signal amplifier)
When the system is normal, nothing will be displayed on the 7 segment display.
When ERROR is displayed, inspect the units.
Use the “MODE/EXIT”, “SELECT”, and “ENTER” buttons on the outdoor unit Main PCB to configure settings according to the procedures below.
1: FUNCTION Setting
First 2 digits Last 2 digits
(the display when the main power is turned on)
(When [F4] to [F9] are displayed, continue to press the "SELECT" button until [ F3 ] is displayed)
MODE/EXIT
SELECT
SELECT
ENTER
SELECT
ENTER
Automatic address setting for signal amplifiers
Press the “SELECT” button until "10" is displayed
Press the “ENTER” button for more than 3 seconds
* Setting is complete when the number of unit is displayed
End
ENTER
MODE/EXIT
SWITCH POSITION
SW107 SW108 SW109
MODE
/EXIT
SELECT ENTER
LED101
(GREEN)
POWER
MODE
LED105 LED104
LED102
(RED)
ERROR
Push button switch
7 Segment LED Lamp
Outdoor unit printed circuit board
*
01-06
SWITCH POSITION
SW107 SW108 SW109
MODE
/EXIT
SELECT ENTER
LED101
(GREEN)
POWER
MODE
LED105 LED104
LED102
(RED)
ERROR
Push button switch
7 Segment LED Lamp
Outdoor unit printed circuit board
Check that the rotary switch IU AD on the indoor unit Main PCB is set to “00”. If it is not set to “00”, it means the address of that device is not set.
(Factory default is “00”).
Turn on the power of the indoor and outdoor units.
When the system is normal, nothing will be displayed on the 7 segment display.
When ERROR is displayed, inspect the units.
Use the “MODE/EXIT”, “SELECT”, and “ENTER” buttons on the outdoor unit Main PCB to configure settings according to the procedures below.
1: FUNCTION Setting
First 2 digits Last 2 digits
(the display when the main power is turned on)
(When [F4] to [F9] are displayed, continue to press the “SELECT” button until [F3] is displayed.)
M
SELECT
SELECT
ENTER
1-2-4 Automatic address setting for Indoor units
It may take about 10 minutes for completing the processing.
End
First 2 digits Last 2 digits
Press the “SELECT” button until “11” is displayed.
Press the “ENTER” button for more than 3 seconds.
Automatic address setting for indoor units
The number of indoor units with normal settings will be displayed at the first 2 digits of the 7 segment display. The number of indoor units with error will be displayed at the last 2 digits.
NOTE) After the “ENTER” button is pressed, the end processing will occur for about 30 seconds.
During this period, the 7 segment will blink.
ENTER
SELECT
ENTER
Error
Found
01-07
SWITCH POSITION
SW107 SW108 SW109
MODE
/EXIT
SELECT ENTER
LED101
(GREEN)
POWER
MODE
LED105 LED104
LED102
(RED)
ERROR
Push button switch
7 Segment LED Lamp
Outdoor unit printed circuit board
1-2-5 Indoor unit connection check
Please perform the indoor unit connection check according to following procedures.
MODE/EXIT
SELECT
SELECT
SELECT
ENTER
LED105
LED104
ENTER
Set to Function mode [F3].
(When [F4] to [F9] are displayed, continue to press the “SELECT” button until [F3] is displayed.)
Press the “SELECT” button until “12” is displayed.
When indoor unit connection check can not be performed
Turn on the powerof indoor unit and outdoor unit.
Press the
“ENTER” button for
more than 3 seconds.
This will be displayed when the Indoor unit connection check starts.
MODE/EXIT
SELECT
ENTER
ENTER
ENTER
(*1)
(*2)
(*1) The number of connected indoor units
(*2) Volume ratio of the indoor units connection
Ex.) When 8 units are connected
Ex.) When the ratio is 120%
Please refer to the following “Error code” for details
[ Note ] Error code
22.1: Connecting Indoor units capacity error
24.2: Connecting number of indoor unit error
26.1: Dual address number is existing
Other Error code: Refer to the Trouble shooting
When it finishes normally, nothing will be displayed on 7 segment display.
When error occurs
Confirm the number of connected indoor units and the volume ratio of the indoor units connection.
Exit indoor unit connection check mode.
01-08
1-2-6 Test Run From Outdoor Main PCB
All the indoor units connected to the outdoor unit can be test-operated by push button setting.
LED105 LED104LED105 LED104 LED105 LED104LED105 LED104
LED105 LED104
LED105 LED104
LED105 LED104
[ Cooling test run ]
[ Heating test run ]
[ Test run stop ]
LED105 LED104
LED105 LED104
LED105 LED104
LED105 LED104
Press the ENTER button for at least 3 seconds.
Press the "ENTER" button or Time out ( 5 seconds)
TIXE / EDOM
< Pursuance completion >
< Monitoring condition >
< Mode select condition >
< Return to mode select condition >
< Function select condition >
[ Function mode ]
SWITCH POSITION
SW107 SW108 SW109
MODE
/EXIT
SELECT ENTER
LED101
(GREEN)
POWER
MODE
LED105 LED104
LED102
(RED)
ERROR
Push button switch
7 Segment LED Lamp
Outdoor unit printed circuit board
TEST RUN SETTING
[ Monitoring mode ] [ Setting mode ]
[ Error history mode ]
For a detailed description of push button operation, refer to the [D&T manual Chapter 6. SYSTEM DESIGN]
LED105 LED104
< Return to monitoring condition >
example, Normal indicate : [ Cooling mode ]
[ Central control setting
Forced reset ]
There are the following 2 methods of resetting test operation.
(1) Automatic reset when 60 minutes has elapsed.
(2) Reset when operation stop was performed.
Note
SELECT
SELECT
SELECT
SELECT
SELECT
SELECT
ENTER
ENTER
ENTER
TIXE / EDOM
01-09
1-2-7 Test Run From Remote Controller
Press the TEST RUN button on the remote controller, while the air conditioner is running.
To end test run operation, press the remote controller START / STOP button.
When the air conditioner is being test run, the OPERATION and TIMER lamps of indoor unit flash slowly at the same time.
START / STOP button
TEST RUN button
2. Standard wireless remote controller
Stop the indoor unit. Push the button and button simultaneously for more than two seconds. The air conditioner will start to conduct a test run and " " will display on the remote controller display. However, the , setting button does not have function, but all other buttons, displays, and protection functions will operate.
To stop test run, push the START / STOP button of the standard wired remote controller. For the operation method, refer to the operating manual and perform operation check. Check that there are no abnormal sounds or vibration sounds during test run operation.
Perform the test operation for 60 minutes.
1. Standard wired remote controller
UTY - LNH
UTY - RNK
Stop the indoor and outdoor units. Push the remote controller button and button simultaneously for more than three seconds. The air conditioner will start to conduct a test run and " " will display on the temperature display.
SET
However the setting button does not have function but all other buttons, displays and protection functions will operate.
To stop test running press the button of the simple remote controller. For the operation method refer to the operating manual and perform operation check. Check that there are no abnormal sounds or vibration sounds during test run operation.
3. Simple remote controller
UTY - RSK
TIMER MODE
CLOCK ADJUST
TEST RUN
RESET
TIMER
SLEEP
FILTER RESET
SWING
SET
SET
ECONOMY
FANMODE
START
STOP
SET
TEMP.
TIMER MODE DAY
SET BACK
CLOCK ADJUST
DAY OFF
TIMER DELETE TIMER SET
FAN MODE
SET TEMP.
START / STOP
01-10
[ Select All (F2) ]: All of R.C.Group (Indoor units) [ Identify Unit (F3) ] : Specific R.C.Group (Indoor unit)
Setup Menu
Indoor unit Special Setting
Test Operation
Central Controller Setting
Indoor unit Special setting
Indoor Unit Set Temp. Range
Filter Sign
R.C. Prohibition
Group
Select All
Identify Unit
Clear Unit
On
Select All
Details
Off
Operation
Help
Setup Menu
Monitor Group
1
2
Monitor - All
UTY-DCG
On
Coll
25.0
05/31 03:59
05/31 03:59
05/31 03:59
Test Operation
05/31 03:59
RCG_05
Test run operating procedure
4. Central remote controller
LED lamp
[ Arrow ] [ MENU ]
[ OK ]
[ CANCEL ]
Function buttons( F1-5 )
< Monitor screen : 9 units display >
< Password verification >
1) Press Button
2) Press the [ Setup Menu (F2) ] button
5) Press the [ Select All (F2) ] button or [ Identify Unit (F3) ] button
6) Press the [ Start (F5) ] button
3) Shift Indoor unit special setting by pressing the [ ] button and [ ] button
4) Shift the Test Operation by pressing the [ ] button and [ ] button
01-11
Test run operating procedure
<Monitor screen (icon)>
<Monitor screen (list)>
(1)
(1)
(2)
( * )
(1)
(1)
(2)
( * )
5. Touch panel controller
UTY - DTG
(1) Select the objective you want to test run. Select the objective icon or list at the monitor screen. (Multiple selections is possible) Select all the devices registered as objectives by pressing "Select All" on the monitor screen.
(2) After objective selection at (1), switch to the <Setting screen> by pressing "Operation".
On
C
1
On
On
On
On
On
On
On
On
Office B
Conference
A
Conference B
Meeting 1
Meeting
2
Parking lot
Meeting
3
EntranceRestrantRoom
101
Office A
PC Room
Top Up
Down
List
Heat
Auto
Cool
26.0 C
24.0
C
Auto
22.0
C
Auto
24.0 C
21.5 C
Heat
21.5 C
21.5 C
Cool
Off
Off
Off
All
21.0
C
Heat
All
Lange Group
Lange Group
Top Up
Down
List
Office A
PC Room
Room 101
Restrant
Entrance
Meeting 1
Off
Off
Off
Mixed
Heat
Auto
Cool
24.0 C
26.0 C
Low
Auto
21.5 C
High
Office B
Mixed Mixed Mixed
Mixed
Name
Expand
Status Mode
Set Temp
Fan
R/C Prohibit
On
On
On
Status: On
Status: On
10/11.2008.Mar. 02:20 PM
10/11.2008.Mar. 02:20 PM
Monitor Mode
Monitor Mode
Heat
21.0
C
Off
On
Operation
Clear All
Select All
Schedule
Setting
Off
On
Operation
Clear All
Select All
Setting
Schedule
Group Error
Schedule Filter Sign Op. Controlled Op. Restricted
RC Prohibition All On/Off On
Mode Temp. Timer
Filter
Mode Set Temp.
Group Error
Schedule Filter Sign
Op.Controlled Op.Restricted
01-12
<Setting screen>
(3) Switch to the <Details setting screen> by pressing "Optional Setting" on the setting screen.
<Details setting screen>
(4) Send (start) test run by pressing "Start" and then pressing "OK" on the details setting screen.
During sending, the slave screen shown below is displayed. When sending is completed, the sending slave screen and details settingscreen are closed.
To interrupt test run, select the device being test run and execute an operation stop command.
(*) At the monitor screen, test run is reset by stopping operation of the objective devices by pressing "OFF".
(*) Or test operation is reset by stopping operation of the objective
devices by pressing "Off" of Operation and then pressing "OK" on the setting screen.
(3)
(4)
(5)
( * )
Cancel
Off
On
OK
Transferring data. Please wait.
On
On
Reset
Cancel
Stand by (Defrost) Stand by (Oil Recovery) Test Operation
Start
Air Flow Direction
Economy
Anti Freeze
Filter Sign
Operation
Test
Up
Down
Swing
Swing
Left Right
Off
Off
Special State
Status: On
1
2
3
4
5
1
2
3
4
SettingOptional
Cancel
OK
On
Off
Auto
Auto
Cool
Dry
Fan
Heat
Operation Controlled
High
Med
Low
Quiet
Meeting Room
24.0 C
operation
R/C Prohibition
Mode Set Temp. Fan
Optional
Setting
All
On/Off
Filter
Timer
Temp.
Mode
On
10/11.2008.Mar. 02:20 PM
10/11.2008.Mar. 02:20 PM
Air Flow Direction Economy Anti Freeze Filter Sign Test Operation
Control Unit :
Operation Setting
Operation Setting
OK
Status: On
01-13
Test run continues for 60 minutes.
(1) Press "Menu" on the monitor screen. the < Main Menu screen > is displayed. (2) Press "Next Page" and press "Maintenance" (3) Press "Next Page" and press "Test Run". the <Test run screen > is displayed. (4) Press "OK"
The test run continues for 60 minutes.
To interrupt test run before it is complet, return to the "Monitor Mode Screen",
and press ON/ OFF.
< Monitor Mode Screen >
< Main Menu Screen >
< Maintenance Screen >
UTY - RNR
< Test Run Screen >
01-14
6. 2-Wire type wired remote controller
1-3 TEST RUN CONTROL
01-15
1. When the test run signal is transmitted from standard wired, wireless remote controller, simple remote controller, transmitted network, and outdoor unit.
(1) The test run operation starts and the electric expansion valve is controlled to a maximum flow, regardless of the temperature condition. (2) Frost prevention operation has priority over item(1). (3) Whether state of the indoor unit operates or stops, All units in the same refrigerant circuit will start to conduct a test run in accordance with the operation mode set by push switch of outdoor unit ( see 1 - 2 - 3 ). (4) After 60 minutes passes, the test run stops. (5) Test running initialization is shown below.
Fan speed Hi Hi
Room Temperature Indication 18 30
Hi Hi
18 30
Vertical Air Direction Panel
Swing
Operating Mode
Cooling Heating Cooling Heating
OFF OFF
Position
1
Position
4
EXCEPT FOR THE DUCT MODEL DUCT TYPE
CEILING TYPE
COMPACT FLOOR
COMPACT CASSETTE TYPE
COMPACT WALL MOUNTED TYPE
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
*Example
Set the air outlet selection switch to
Set the air outlet selection switch to
1
2
3
4
1
2
3
4
1-4 FIELD SETTING AND MONITOR MODE LIST FOR OUTDOOR UNIT
Push switch on outdoor unit PCB
[ F1 ]
Monitor mode
Setting Mode
ITEM CODE No.
Information contents
Classification
00
Connected number of indoor unit
The number of the communicating unit is displayed
Device and system
01
Software version :
Software version of outdoor unit
[ ] [ ] [ ] [ ] [ ] displays by five items
02 Software version of INV PCB
It skips when there is no suffix
03
Software version of communication PCB
Operation of each part
10 Rotational speed of outdoor unit fan motor
11 Rotational speed of INV compressor
12 Current value of INV compressor
The rotational speed of the outdoor unit fan motor is displayed
[ rpm ]
The rotational speed of the compressor is displayed [ rps ]
Current value of INV compressor is displayed [ A ]
13
14 Pulse of EEV1
Pulse of EEV1 is displayed [ pls ]
15 Pulse of EEV2
Pulse of EEV2 is displayed [ pls ]
Time guard 20 Accumulated current time
21 INV compressor accumulated time
[ Cooling ]
22 INV compressor accumulated time
[ Heating ]
Accumulated current time is displayed
[ 10 hour ]
Accumulated time is displayed in the cooling operation of the
INV compressor
[ 10 hour ]
Accumulated time is displayed in the heating operation of the
23
INV compressor
[ 10 hour ]
Refrigerant cycle data 1
Refrigerant cycle data 2
30
Information on Thermistor 1
(
INV compressor discharge temperature sensor
)
32
33
34
The value of the Thermistor 1 is displayed
31
The value of the Thermistor 3 is displayed
The value of the Thermistor 4 is displayed
35
C ] or [°F ]
C ] or [°F ]
C ] or [°F ]
The value of the Thermistor 7 is displayed
The value of the Thermistor 9 is displayed
C ] or [°F ]
C ] or [°F ]
The value of the pressure sensor 1 is displayed [ MPa ] or [ psi ]
The value of the pressure sensor 2 is displayed [ MPa ] or [ psi ]
36
37
38
39
Forbidden
Forbidden
50 Information on pressure sensor 1
( High pressure sensor )
51 Information on pressure sensor 2
( Low pressure sensor )
Refrigerant
40
cycle data 4
Refrigerant cycle data 3
01-16
Information on Thermistor 5
(
Heat-exchanger (outlet) temperature sensor )
Information on Thermistor 7
(
Liquid temperature sensor 2 )
Forbidden
Information on Thermistor 9
( Sub-cool heat-exchanger (outlet) temperature sensor )
Information on Thermistor 10
( INV compressor temperature sensor )
Information on Thermistor 4
( Outdoor temperature sensor )
( Suction temperature sensor )
Information on Thermistor 3
Forbidden
Forbidden
Forbidden
The value of the Thermistor 10 is displayed
C ] or [°F ]
The value of the Thermistor 5 is displayed
C ] or [°F ]
Push switch on outdoor unit PCB
[ F2 ]
Monitor mode
Setting Mode
ITEM CODE No.
ITEM CODE No.
Information contents DefaultClassification
00
10 11
12
13,14
20
21
25,26,27
28
29
30
35,36,37 38,39
00 01 02
00
03
00 01
04 00 01 02 03
00
1010
00 00
02
00
01
00
02 03
Pipe length setting
Cooling capacity shift
Heating capacity shift
16,17
00
Forbidden Switching between forced stop or
Operation mode selecting method
22,23,24 Forbidden
Change of unit (Temperature)
Change of unit (Pressure)
Energy saving level setting
40-65m 0-40m 65-90m 90-120m
10 Forbidden
Forbidden Factory default
Factory default
Factory default Factory defaultForbidden
Normal mode
Factory defalt
Save energy mode +2
°C
High power mode 1 -2 °C High power mode 2 -4
°C
Normal mode Save energy mode -2
°C
High power mode 1 +2°C High power mode 2 +4°C
Forced stop
Factory default
Celsius (
°C)
Disable (°F) MPa
psi Level 1 (stop) Level 2 (operated at 40% capacity) Level 3 (operated at 60% capacity) Level 4 (operated at 80% capacity) Level 5 (operated at 100% capacity)
Emergency stop Priority given to the first command Priority given to the external input of outdoor unit Priority given to the master indoor unit
Forbidden
Install
Correction
Change of
emergency stop
00 01 00 01 00
31,34,35
Forbidden
00
01 02 03 04
function 1
Change of
function 2
01-17
40
41
42
50,51,60, 61,64
Capacity priority setting
Low noise mode setting
Low noise level setting
Forbidden
Factory defalut
Level 1
Off (quiet priority) On (capacity priority) Off (Normal) On (Low noise mode operation is always done)
00 01 00
00
00
01
Low noise
setting 1
70
71
72
3737
Electricity meter No. setting 1
( Set the ones digit and tens digit of the No. of the electricity meter connected to CN135 )*1
Electricity meter No. setting 2
( Set the ones digit and tens digit of the No. of the electricity meter connected to CN135 )*1
Electricity meter pulse setting 1
( Set the ones digit and tens digit of the No. of
Electricity meter pulse setting 2
Setting number x00~x99 ( Refer to Design & Technical Manual for details.)
Setting number 0xx~2xx ( Refer to Design & Technical Manual for details.)
Setting number xx00~xx99 ( Refer to Design & Technical Manual for details.)
Setting number 00xx~99xx ( Refer to Design & Technical Manual for details.)
00
00
00
00
00~99
00~02
00~99
00~99
the electricity meter pulse setting connected
to CN135 )*2
( Set the ones digit and tens digit of the No. of
the electricity meter pulse setting connected
to CN135 )*2
Change of
function 4
Change of
function 3
*1 : When electricity meter No. is set to "000" and "201 to 299", the pulses input to CN135 become ineffective.
Available setting number is "001" to "200"
*2 : When the electricity meter pulse setting is set to "0000", the pulses input to CN135 become ineffective.
Available setting number is "0001" to "9999"
Level 2
01
Push switch on outdoor unit PCB
[ F3 ]
Monitor mode
Setting Mode
ITEM CODE No.
Setting Function
Classification
Meaning of Error History Number
ITEM CODE No.
Information contents
Classification
00
Cooling test run
Forced thermostat-ON in Cooling.
01
Heating test run
Forced thermostat-ON in Heating.
02
03,04
Test run stop
Forbidden
Test run is stopped.
10
Signal amplifier automatic address
11
12
Indoor unit automatic address
Indoor unit connection check
Automatic address setting operates for indoor unit of same
The number of indoor units and the total capacity of indoor units
Automatic address setting operates for signal amplifier.
refrigerant circuit.
of same refrigerant circuit.
21
Vacuuming mode
Vacuuming mode operates Refer to page 01-01 for the function.
30
31
Error history clear
Forbidden
All the abnormal code histories are cleared.
32
Current time clear
Accumulated current time becomes [ 0 ]
33
INV compressor accumulated time clear
Accumulated time of the INV compressor becomes [ 0 ]
35
Field setting all clear
Return to default the all set items.
36
Clear memorized information of “F3 - 12” ( Indoor unit connection check )
The information of the number of indoor units and the total
40
Abnormal reset
It was displayed when abnormality occurs, and the total
41
Maximum memorized indoor unit number reset
Maximum memorized indoor unit number is reset
91
Forced Central control function release
When the centralized control device failure, and the centralized control setting cannot be released, this function is used.
All the limitations set with the centralized control device are released.
“E14.5 : Indoor unit number shortage ” error is cleared.
code is reset.
This is a function that uses to clear abnormal display after the repair is completed.
Please operate the switch after power off or power on the outdoor unit.
capacity of indoor units are cleared.
Forced
Push switch on outdoor unit PCB
[ F9 ]
Monitor mode
00
1 time ago (Newest)
01
2 time ago
02
3 time ago
03
4 time ago
04
5 time ago
05
6 time ago
06
7 time ago
07
8 time ago
08
9 time ago
09
10 time ago
When the error occurred, the error code is memorized up to 10 on Main PCB.
If the memorized error code becomes over 10, the oldest one will be erased.
Error history
operation
Install and maintenance 1
Install and maintenance 2
Refer to Chapter 4.TROUBLE SHOOTING
4-3-2 Error Code List for Outdoor unit
Compressor Motor Loss of Synchronization Compressor 1 Temperature Abnormal Inverter Compressor Start Up Error Discharge Temperature 1 Abnormal Low Pressure Abnormal Current Sensor 1 Error Trip Detection Rush Current Limiting Resistor Temp Rise Protection Outdoor Unit FAN motor 1 Lock Error Outdoor Unit FAN motor 2 Lock Error
*
< Reset Error Item List By Abnormal Reset Setting >
Reset
Specialty function
Clear
01-18
20
Forbidden
37
Forbidden
90
Forbidden
Function
Function
number
Setting number Default Details
Filter
indicator
interval
11
00 Standard
Adjust the lter cleaning interval notification. If the notification is too early, change to setting 01. If the notification is too late, change to setting 02.
01 Longer 02 Shorter
Filter
indicator
action
13
00 Enable
Enable or disable the lter indicator. Setting 02 is for use with a central remote control.
01 Disable
02
Display only on
central remote
control
Ceiling
airow
20
00 Standard
Regulate the airow according to the needs of the installation location. When set to 01, the air ow will be stronger. (Cassette type only)
01 High Ceiling
Vertical
airow
direction
23
00 Standard
Adjust the ver tical air ow direction. All air ow direction louvers are adjusted together.
(Cassette type only)
01 Raise
Horizontal
swing
airow
direction
24
00 Standard
Adjust the horizontal swing airow direction.
(For horizontal swing equipped models)
01 Left half
02 Right half
Static pressure 26
00 SP mode 00
01
02
Indoor unit address 00
Ref. circuit address 00
00~63
00~99
Model name
Range of static
pressure
Normal static
pressure
ARXK07GCLH
SP mode 00 to 03 10 PaARXK09GCLH ARXK12GCLH ARXK14GCLH
SP mode 00 to 05 15 PaARXK18GCLH ARXK24GCLH ARXD04GALH
SP mode 00 to 09
(0 to 90 Pa)
25Pa
ARXD07GALH ARXD09GALH ARXD12GALH ARXD14GALH ARXD18GALH
ARXD24GALH
SP mode 00 to 05
(0 to 50 Pa)
ARX A24GBLH
SP mode 00 to 14
40Pa
ARX A30GBLH
50Pa
ARX A36GBLH SP mode 00 to 12 ARX A45GBLH SP mode 00 to 11 60Pa ARXC36GBTH SP mode 02 to 16 100Pa ARXC72GBTH SP mode 04 to 27
150PaARXC90GBTH SP mode 05 to 24 ARXC96GATH SP mode 05 to 29 ARXN18GATH SP mode 05 to 10
50Pa
ARXN24GATH SP mode 05 to 15 ARXN30GATH
SP mode 05 to 25
ARXN34GATH ARXN36GATH
60Pa
ARXN45GATH
Please refer to "Chapter04 7.FAN PERFORMANCE CURVE" for the characteristics of each indoor unit.
01 SP mode 01
02 SP mode 02
03 SP mode 03
04 SP mode 04
05 SP mode 05
06 SP mode 06
07 SP mode 07
08 SP mode 08
09 SP mode 09
10 SP mode 10
11 SP mode 11
12 SP mode 12
13 SP mode 13
14 SP mode 14
15 SP mode 15
16 SP mode 16
17 SP mode 17
18 SP mode 18
19 S
P mode 19
20 SP mode 20
21 SP mode 21
22 SP mode 22
23 SP mode 23
24 SP mode 24
25 SP mode 25
26 SP mode 26
27 SP mode 27
28 SP mode 28
29 SP mode 29
31 Normal SP
Cool air tem-
perature trigger
30
00 Standard
Adjust the cool air trigger temperature. To lower the trigger
temperature, use setting 01. To raise the trigger temperature,
use setting 02.
01 Adjust (1)
02 Adjust (2)
Heat air tem-
perature trigger
31
00 Standard
Adjust the heat air trigger temperature. To lower the trigger
temperature by 6 degrees C, use setting 01. To lower the trigger temperature by 4 degrees C, use setting 02. To raise the trigger temperature, use setting 03.
01 Adjust (1) 02 Adjust (2) 03 Adjust (3)
FUNCTION
FUNCTION
SETTING
1-5 FIELD SETTING / FUNCTION SETTING FOR INDOOR UNIT
Address
01-19
Function
Function
number
Setting number Default Details
*1 Auto
restart
40
00 Enable
Enable or disable automatic system restart after a power outage.
01 Disable
Cool Air
Prevention
43
00 Super low
Restrain the cold airow with making the airow lower when star ting heating operation. To correspond to the ventilation, set to 01.
01
Follow the setting
on the remote
controller
External
control
46
00 Start /Stop
Allow an external controller to start or stop the system, or to perform an emergency stop, or to perform a forced stop.
* If an emergency stop is performed from an external controller, same
refrigerant system will be disabled.
* If forced stop is set,indoor unit stops by the input to the external input
terminals,and Start /Stop by a remote controller is restricted.
01 Emergency stop
02 Forced stop
Error report target
47
00 All
Change the target for reporting errors. Errors can either be reported in all locations, or only on the wired remote.
01
Display only on
central remote
control
Fan setting
when cooling
thermostat OFF
49
00
Follow the setting
on the remote
controller
When set 00, Indoor unit is continued operation based upon Central remote controller or individual controller set. Once indoor unit received signal from External controller, Indoor unit changed Fan mode forcibly.
When set 01, Indoor unit is continued operation based upon Central remote controller or individual controller set. Once indoor unit received signal from External controller, Indoor unit stop forcibly.
Connection of the wired remote controller (2-wire type or 3-wire type) and switching its
thermistor are necessary.
01 Stop
*1 : Auto restart is an emergency function such as for power failure etc.
Do not start and stop the indoor unit by this function in normal operation. Be sure to operate by the control unit, converter or external input device.
FUNCTION
SETTING
FUNCTION
SETTING
01-20
Function
Function
number
Setting number Default Details
Filter
indicator
interval
11
00 Standard
Adjust the lter cleaning interval notication. If the notication is too early, change to setting 01. If the notication is too late, change to setting 02.
01 Longer 02 Shorter
Filter
indicator
action
13
00 Enable
Enable or disable the lter indicator. Setting 02 is for use with a central remote control.
01 Disable
02
Display only on
central remote
control
Static pressure 26
05 SP mode 05
Model name
Range of static
pressure
Normal static
pressure
ARXH054GTAH
SP mode 05 to 19
(50 to 185 Pa)
185Pa
ARXH072GTAH
SP mode 05 to 20
(50 to 200 Pa)
200Pa
ARXH096GTAH
SP mode 05 to 22
(50 to 220 Pa)
200Pa
06 SP mode 06
07 SP mode 07
08 SP mode 08
09 SP mode 09
10 SP mode 10
11 SP mode 11
12 SP mode 12
13 SP mode 13
14 SP mode 14
15 SP mode 15
16 SP mode 16
17 SP mode 17
18 SP mode 18
19 SP mode 19
20 SP mode 20
21 SP mode 21
22 SP mode 22
31 Normal SP
*1 Auto
restart
40
00 Enable
Enable or disable automatic system restart after a power outage.
01 Disable
Cool Air
Prevention
43
00 Prohibited
Setting change prohibited.
01
Follow the setting
on the remote
controller
External
control
46
00 Start /Stop
Allow an external controller to start or stop the system, or to perform an emergency stop, or to perform a forced stop.
* If an emergency stop is performed from an external controller, same
refrigerant system will be disabled.
* If forced stop is set,indoor unit stops by the input to the external input
terminals,and Start/Stop by a remote controller is restricted.
01 Emergency stop
02 Forced stop
Error report target
47
00 All
Change the target for reporting errors. Errors can either be reported in all locations, or only on the wired remote.
01
Display only on
central remote
control
Humidier
contro
l
63
00 mode 00
Select control conditions of external output. "Mode 0 0" is output when heating thermostat is ON, "Mode 01" is output in heating operation, "Mode 02" is output in heating operation and in fan operation.
01 mode 01
02 mode 02
1-6 FIELD SETTING / FUNCTION SETTING FOR OUTDOOR AIR UNIT
01-21
2. OUTDOOR UNIT OPERATION CONTROL
2-1 INPUT / OUTPUT LIST
2. OUTDOOR UNIT
02-01
Input / output or kind of detail Control range
Discharge pressure sensor <HIGH> Pressure sensor Measure range 0.0 to 5.0MPa Suction pressure sensor <LOW> Pressure sensor Measure range 0.0 to 1.7MPa Discharge temperature sensor <TH1> Themistor <Blue>
Measure range 10 to 130
Heat exchanger temperature sensor <TH5> Themistor < >
Measure range -35 to 70
Sub-cool heat exchanger (outlet) sensor<TH9> Themistor < White>
Measure range -35 to 70
Liquid temperature sensor <TH7> Themistor <Green>
Measure range -35 to 70
Suction temperature sensor <TH4> Themistor <Red>
Measure range -35 to 70
Outdoor temperature sensor <TH3> Themistor < - >
Measure range -25 to 58
Operation current sensor Current sensor
Rotary SW & DIP-SW & Push SW
Electronic expansion valve 1 (Main) EEV coil Operating voltage DC12V Electronic expansion valve 2 (SC-Hex) EEV coil Operating voltage DC12V
4-way valve 4-way valve coil AC220-240V, 50/60Hz 6/5 W Crank case heater
For Inverter Compressor AC240V, 35W
Base heater Field supply
AC220-240V, 35W
LON WORKS Inverter communication
External input 1 (CN131) (
Low noise mode operation) External input 2 (CN132) (Cooling / Heating priority) External input 3 (CN133) (Outdoor unit operation peak control) External input 4 (CN134) (Emergency stop operation)
Dry contact input
Single LED 101 Single LED 102
LED display
Address and function setting
Display the information on operation,
error and
setting with single LED and
7 segment LED.
Control output: DC 0/12-24V, Max.30mA Control output: DC 0/12-24V, Max.
30
mA
External output 1 (CN136) (Error display) External output 2 (CN137) (Operation display)
ON (Error) / OFF (Normal) ON (Operation) / OFF (Stop)
Communication Input / Output
External Input / Output
I N P U T
O
U T P U T
Compressor temperature sensor <TH10> Themistor < - > Measure range 10 to 130
Pressure switch
Pressure switch
Open 4.2MPa Short 3.2MPa
Fan motor 1 (Upper) DC Brushless motor
7 Segment LED
Compressor
Indoor unit Outdoor unit
Fan motor 2 (Lower) DC Brushless motor
DC Inverter compressor
Brown
2-2-1 Operation / Stop Condition
When cooling requirement capacity or heating requirement capacity from either of the indoor units in the same refrigerant circuit is input, the compressor operates. When all the indoor units in no "cooling requirement capacity" or "heating requirement capacity",
the compressor is stopped. But in the following case, the compressor operates in accordance with operation of each mode.
During 3 minute restart prevention operation Icing protection Failure (Refer to chapter 4, TROUBLE SHOOTING ) Under expansion valve initialization At protective operation
Emergency stop Defrost operation
02-02
2-2 COMPRESSOR OPERATION
2-2-2 Capacity Control
(1) Capacity of compressor operation
By the operation of DC inverter rotary compressor, the amount of required refrigerant circulation acceding to cooling and heating load can be supplied from compressor efficiently.
DC inverter rotary compressor is able to control the amount of required refrigerant circulation in details.
Cooling/Heating load
Capacity of
compressor operation
Total capacity
Peak cut stop operation
Inverter Compressor
(2) Target low-pressure and high-pressure control
In order to make the evaporation pressure of the indoor unit at the proper pressure on a variety of operations, capacity of the compressor will be controlled by low-pressure sensor of the outdoor unit.
In order to make the condensation pressure of the indoor unit at the proper pressure on a variety of operations, capacity of the compressor will be co
ntrolled by high-pressure sensor of the outdoor unit.
Target low-pressure and high pressure temperature depends on system capacity, capacity of compressor operation, pipe length, and capacity shift switch settings.
<Cooling>
<Heating>
02-03
2-2-3 Speed Range of Start, Stop, And Operation
On stop mode : 0 rps
On operating mode : 15 - 120 rps
(1) Heating starting process
*The compressr starting process in cool mode does not have the limitated hold controlling.
For Heating operation only, the upper limit speed at starting is made 40rps and is raised in +10rps increments every 60 seconds.
Speed
Time
0
40rps
60sec
Target speed
180
sec
60sec
50rps
60rps
70rps
60sec
240
sec
300
sec
360
sec
80rps
10rps
10rps
The compressor operates at the upper limit speed if the target speed is higher than the upper limit speed.
The compressor operates at the target speed if the target speed is lower than the upper limit speed.
60sec
10rps
Loading...
+ 225 hidden pages