Fujitsu AUXB07GA* H, AUXB14GA* H, AUXB12GA* H, AUXB09GA* H, AUXB24GA* H Service Manual

...
Large Capacity Multi VRF System
DC Inverter Control Compressor
Long Piping System Design
High Efficiency Refrigerant R410A
Multi Air Conditioning System for Buildings
SERVICE MANUAL
CONTENTS
5-2-1 Indoor Unit..........................................................................................................
5-2 WIRING DIAGRAM..................................................................................................
5-1 REFRIGERANT CIRCUIT........................................................................................
5. APPENDING DATA
05-01
05-03
05-03
5-2-2 Outdoor Unit....................................................................................................... 05-18
5-3 SATURATION TABLE (R410A)............................................................................. 05-20
5-3-1 Saturation temperature and saturation pressure tables (R410A)......................
05-20
5-3-2 Temperature and pressure of refrigerant (Graph).............................................
05-21
6. DISASSEMBLY PROCESS
4-1-2 Outdoor Unit Display...........................................................................................
4-1-1 Indoor Unit Display..............................................................................................
4-1 NORMAL OPERATION..............................................................................................
4. TROUBLE SHOOTING
4-2 ABNORMAL OPERATION.........................................................................................
4-2-2 Indoor Unit Display..............................................................................................
04-01 04-01
04-02
04-03
04-04
4-2-4 Remote Controller Display...................................................................................
4-2-3 Outdoor Unit Display...........................................................................................
04-04
4-2-5 Trouble shooting index - Error code List -...........................................................
04-06
4-2-7 Trouble level of system........................................................................................
04-08
4-2-8 Error History mode...............................................................................................
04-09
04-05
4-3 SERVICE INFORMATION -Network communication abnormal - ........................................ 04-100
4-5 SERVICE PARTS INFORMATION............................................................................. 04-105
4-2-1 Error code Display..............................................................................................
04-03
4-2-6 Trouble shooting index - No Error code - ...........................................................
04-07
4-2-9 Trouble shooting with Error code.........................................................................
04-10
4-2-10 Trouble shooting No Error code........................................................................
04-82
4-4 SERVICE INFORMATION......................................................................................... 04-101
4-4-1 Back up operation ..............................................................................................
04-101
4-2-2 Work procedure after the backup operation..........................................................
04-103
1. TEST RUN
Before execution
Execution
Execution zone decision
Confirmation of refrigerant used
Preparation of execution drawings
Confirmation of installation site
Preparations before execution
Execution procedure and precautions Reason
01-01
1-1 EXECUTION PROCEDURE AND EXECUTION PRECAUTIONS
1. TEST RUN
Sleeve and insert work
Indoor unit installation
Refrigerant piping work
Drain piping work
Duct work
Heat insulation work
Electrical work
Foundation work for products
Refrigerant piping connection work
Air tightness test
Vacuum drying
Check the characteristics of the refrigerant used and grasp the special features of the refrigerant. If refrigerant must be charged, always charge the refrigerant specified for the product. Confirm the product design pressure. R410A 4.2 MPa
Use new refrigerant piping of the thickness specified by the D&T manual. Since R410A dedicated tools are necessary, prepare them in advance. Absolutely avoid use of existing piping. If use of existing piping is unavoidable, the piping must be cleaned.
Use of a refrigerant other than the specified refrigerant will invite equipment trouble.
Secure the necessary pressure resistance.
Use pipe that is not dirty inside. When the pipe is left standing, protect it. Finish flaring exactly. Confirm the width across flats dimension and shape of flare nuts. Always blow nitrogen while brazing. Perform flushing before connecting the equipment.
Always make the downward slope of the drain pipe 1/100 or greater and make the horizontal length within 20m. Use hard polyvinylchloride pipe as the drain pipe. Support the drain pipe between 1.5 to 2.0m. Use pipe of 1 rank up (VP30 or greater) as central piping.
Prevention of water leakage
Foreign matter, water, etc. in the piping will cause faulty cooling and compressor trouble. Refrigerant leakage will cause low performance and abnormal stopping.
Prevention of water leakage
Prevention of water leakage
Refrigerant leakage will cause low performance and abnormal stopping.
Refrigerant leakage will cause low performance and abnormal stopping.
Mixing in of vacuum pump oil by reverse flow will cause equipment trouble. Prevents degradation of the oil by completely removing water and air.
Always use a level and keep the indoor unit level. If the equipment is tilted toward the drain port, install it so that the tilt is within 10mm. Excessive tilt will cause water leakage.
When performing piping work, observe the following items so that the inside of the piping is clean and air tight.
Select the size of the heat insulating material according to the ambient temperature and relative humidity of the refrigerant. Use a heat insulating material having a heat conductivity of 0.043W/ (m
.
k) or less.
When making flare connections always use a torque wrench and tighten the flare nut positively to the specified torque.
Pressurize the product with nitrogen gas up to the design pressure and conduct a 24Hr air tightness test.
Install a vacuum pump with reverse flow check mechanism or a reverse flow check adaptor to a conventional vacuum pump and use. Pump down sufficiently. Approximately 1 hour or longer after -0.10MPa reached. Allow to stand for approximately 1 hour after stopping the vacuum pump and confirm that the needle does not return. Air purging using refrigerant is strictly prohibited.
1
2
1
1
1
2
3
2 3 4 5 6
1
2 3 4
2
3
Vacuuming mode
This function is used for vacuuming the indoor unit and the connection piping.
When the [vacuuming mode] is set, <Push switch setting, F3:21> EEV of connected all indoor units opens. So, the vacuuming indoor unit and piping becomes easier.
When the vacuuming ends, please turn off the power supply for all of the indoor units, and outdoor unit, [vacuuming mode] is released.
*
recommend the vacuuming mode
*
Products installation work
*Refer to warning or caution in the attached installation manual of each products
Note: For starting Vacuuming mode, the refrigerant address setting has to be finished.
01-02
Execution
Perform the auto address setting of Signal amp. at first, and the next perform the auto­ address setting of indoor unit. When you perform the autoaddress setting for the indoor unit address setting needs to be done at first.
Pre-commisioning
"Before Power ON"
Gas leak test
Use an R410A dedicated leak tester to check for gas leaks.
1
2
3
Confirm the additional refrigerant amount with the installation manual, etc. Always take the R410A refrigerant from the cylinder liquid phase and charge it using the gas phase. (Do not lay a cylinder with siphon pipe on its side.) Use an R410A dedicated gauge manifold and charging hose.
If taken from the air phase, since the composition of the refrigerant which is charged will change, low performance and abnormal stop will occur easily. Prevent erroneous sealing in of refrigerant.
A leak tester for other than R410A cannot detect leaks.
Handover & explanation of operation
In case of "Auto Address setting"
Test run & adjustment
Addition refrigerant charging
1
2
3
Power source installation inspection
Field setting and setting inspection
Transmission wire installation inspection
4
Piping installation inspection
Before starting the installed system, the final inspection is necessary. When you find out any incorrect install­ ation or wrong setting, revise it before starting the system
Pre-commisioning
"After Power ON"
1
2
3
Connect Service Tool
Power source inspection
Error indication inspection
4
Transmission wire connection inspection
When you see any abnormal things, turn OFF the power supply first, and revise it with power OFF state.
Note :
Other Field setting with power ON state, and adjustment
Check operating condition by using service tool. For the judgment of operating condition, refer to the operation check sheet.
When you see any abnormal things, stop the system, and revise it with power OFF state.
1-2 Check Items Before Power ON
01-03
Check Item Check contents Judgement Present Status
Ref. circuit name: _________________
Power Source
Outdoor
Unit
Power supply 3 / 4W / (342 - 456V) / 50Hz
Circuit Breaker Size (A)
For AJ* 072L : 20A For AJ* 090/ 108L : 25A For AJ* 126/ 144/ 162L : 40A
Master (AJ* ____L) :_____(A)
Slave-1(AJ* ____L) :_____(A)
Slave-2(AJ* ____L) :_____(A)
Leakage current : 100mA, 0.1 sec or less
Yes / No
Power Line Wire Size (mm
2
)
Check the breaker capacity vs. wire size
20A=4mm
2
, 25A=6mm2, 40A=10mm2,
60A=16mm
2
, 80A=22mm2, 100A=38mm
2
Master : ______ (mm2)
Slave- 1: ______ (mm
2
)
Slave- 2: ______ (mm2)
Power line Wiring
Note: One Outdoor Unit must have one individual Circuit Breaker
Example :
Complied
Not complied
* Japanese Standard
* Note: Regulation of wire size and circuit breaker differs from each locality, please refers in accordance with local rule
Check Item Check contents Judgement Present Status
Ref. circuit name: _________________
Power Source
Indoor Unit
Power supply
1 / (198 - 264V) / 50Hz
Circuit Breaker Size (A)
(Check, Leakage current vs.
numb er of IUs)
20A breaker f or one circuit
Leakage current as follows:
No. of units vs. leakage current:
30mA for 12 nos. (IUs) 100mA for 40 nos. (IUs) 200mA for 81 nos. (IUs) 300mA for 122 nos. (IUs)
Note: MCA for total connected units (IU) less than 15A for 20A breaker capacity
MCA means, minimum circuit ampere
Circuit number -1
Breaker ca pa city: _______ (A)
Nos. of Co nnected units: ______ (IU)
Circuit number -2
Breaker ca pa city: ______ (A)
Nos. of connected units: ______ _ (IU)
Circuit number -3
Breaker ca pa city: _______ (A)
Nos. of Connected
units: _______ (I U)
Power line wire size (mm2)
Wire size 2.5mm
2
(for 20A breaker)
________ (m m2)
Power line wiring
Example for one circuit
Complied
Not complied
* Note: Regulation of wire size and circuit breaker differs from each locality, please refers in accordance with local rule
1-2-1 Power source Inspection sheet
Outdoor units AJY072 AJY072AJY126
Sub Breaker
Sub Breaker
Sub Breaker
40A
20A
20A
Power cable 10mm
2
Power cable 4mm
2
Power cable 4mm
2
Sub Breaker
Terminal board
20A
Power cable
2.5mm
2
Indoor units
01-04
Check Item Check contents Judgement
Present
Status
No. of outdoor unit for one ref. circuit: ______, Ref. circuit name: _________________
Outdoor
Unit
Outlook
Appearance Shall be no deformation
OK / NG
Serial No. Master: Slave -1: Slave -2:
Power source & transmission wiring Connection points & loose screws check
OK / NG
Connection piping Is it insulated properly without gap?
OK / NG
Outdoor air temperature Checked & entered the value
( )
Setting
DIP-SW setting
OU Address (SET 3-1 & SET 3 -2)
Note:setting for Master & Slave units
(Default : OFF - OFF)
Master (OFF - OFF)
Y / N
Slave-1 (OFF - ON)
Y / N
Slave-2 (ON - OFF)
Y / N
No. of Slave Unit (SET 3- 3 & SET 3 -4)
Note:setting for Master unit only
(Default : OFF- OFF)
NO Slave (OFF- OFF)
Y / N
1 x Slave (OFF- ON)
Y / N
2 x Slave (ON - OFF)
Y / N
No. of OU (SET 5 -1 & SET 5 -2)
Note:setting for Master & Slave units
(Default : OFF-OFF)
1 x OU (OFF - OFF)
Y / N
2 x OU (OFF - ON)
Y / N
3 x OU (ON - OFF)
Y / N
Terminal Register (SET 5 - 4)
Note : setting for Master units
OFF or ON (Default : OFF)
Y / N
Rotary-SW setting
Ref. Add. (among Master & Slave units) Ref ADx10 & Ref ADx1
Y / N
SET-5
SET-3
x 10 x 1
REF- AD
Check contents
Ref. circuit name: _________________, Ref. address: ____ (00
99)
Model
Name &
Serial
No.
Outlook Function setting by DIP-SW (Off / On) Add. Setting (by Rotary-SW)
Access hole for maintenance
(For Duct type & Cassette
type units)
RC wiring connection points:
(loose / deform)
Refrigerant pipes insulation
Drain pipes installation
Wired RC setting (DIP SW
1
)
2 wire /
3 wire
(default:
2 wire)
External Input (edge/pulse)
SET
2
­2
( default: OFF )
Wireless RC custom code
SW
1
SET
3
­1
( default: OFF )
Wireless RC custom code
SW
2
SET
3
­2
( default: OFF )
Drain Pump SW (for Slim duct)
SET
4
­1
( default: OFF )
Ref. Add.
(REF AD x
10
)
Ref. Add.
(REF AD x
1 )
IU Add.
(IU AD x
10
)
IU Add.
(IU AD x
1
)
RC Add.
(RC AD)
Y /
N
Y /
N
Y /
N
Y /
N
Y / NY /
N
Y /
N
Y /
N
Y /
N
Y /
N
Y /
N
Y /
N
Y /
N
Y / NY /
N
Y /
N
Y /
N
Y /
N
Y /
N
Y /
N
Y /
N
Y /
N
Y / NY /
N
Y /
N
Y /
N
Y /
N
Y /
N
Y /
N
Y /
N
Y /
N
Y / NY /
N
Y /
N
Y /
N
Y /
N
IU Add.
Ref. Add.
RC Add
1-2-2 Outdoor unit field setting inspection sheet
1-2-3 Indoor unit field setting inspection sheet
01-05
Check Item Check contents Judgement Present Status
Number of ref. circuit connected in the network system: ______, Ref. addresses: ______________(00 - 99)
VRF Network System
Transmission wire
Outlook
Is it LonWorks compatible?
Yes / No
Maker name?
Wire specification 0.33mm
2
, shield wire
(mm2)
Transmission line connection points
Between Master OUs
Must be properly connected (Between Master OUs) Master OUs
Terminal: Z1 & Z2
Yes / No
Between Master OU & Slave OU or In between Salve OUs
Must be properly connected (Between Master OU and Slave OU / Slave OU and Slave OU )
Terminal: H1 & H2
Yes / No
Shield wire connection
Both ends of shield wire must be grounded
Yes / No
Wiring connection Wiring connection per terminal (
2)
Yes / No
1-2-4 Transmission wire installation inspection sheet 1/3
1-2-4 Transmission wire installation inspection sheet 2/3
Indoor unit
Outdoor unit (Master unit)
Refrigerant system
Check Item Check contents Judgement Present Status
Number of ref. circuit connected in the network system: ______, Ref. addresses:_______________(00 99)
VRF Network System
Network wiring
Total transmission line length
Wiring length
3600m
(Value ta ken from Network Design Drawing)
(m)
Network wiring layout
Do not make a loop configuration Looped / Not looped
No. of network segment
( * 1)
No. of network segment 41
( * 1)
Create one Network Segment based on the following conditions,
Condition -1: if the transmission line length 500m
Condition -2: if a total number of connected units
64 connected units
( * 2)
( *2) connected units mean a total of ( Indoor Units + Master Outd oor Units
+ TPC Units + System Controller Units + Network Convertor f o r LonWorks Unit + Central RC Units + Network Convertor Units + BACnet Gateway Unit + Signal Amplif ier Units + Service Tool Unit + Web Monitoring To ol Unit)
01-06
Check Item Check contents Judgement Present Status
Number of ref. circuit connected in the network system : ______, Ref. addresses :_______ _______________(00
99)
VRF Network System
Network Conf iguration
No. of IUs & OUs
For one VRF Network System
(IU
400 & OU 100)
IU number : _____
OU num ber: _____
No. of System Controller
One System Controller per VRF Network System
No. of Touch panel controller (TPC)
Connectable No s. 16
Total 16 Nos.
Per VRF Network System
(including one Network
Converter for LonWorks)
TPC: _____
No. of Central RC (CRC)
Connectable No s. 16
CRC: ______
No. of Network Convert f or Group RC
Connectable No s. 64
Group RC: _____
No. of Signal Amplifier (SA) 40
Detail contents:
No. of SA (filter mode OFF) 8 No. of SA (filter mode ON ) 32
One per 500m transm ission lin e length OR, One per 400m transm ission line length between
units OR, One per every 64 nu mber of connected units OR, One per every ma ster OU if tota l n um ber of
connected Indoor Units
320
Number of Signal Amplifier :____ ____
No. of Network Convertor ( 100)
One for each separa te Room Air- conditioning system Tota l:_______
No. of BACnet Gateway
One BACnet Gateway per VRF Network System Tota l: _______
Terminal Register
One per Network Segment (refer to table -9) Tota l: _______
No. of Network Convertor for LonWorks
One per VRF Network System (IU 128 & OU 100)
NOTE: Special VRF Network system con figuration
IU number : _____
OU num ber: _____
Check Item Check contents Judgement Present Status
Number of ref. circuit connected in the network system : ______, Ref. addresses :_______________________(00
99)
VRF Network System
Terminal Resistance of transmission line
Terminal resistance of transmission line: From device with connected terminal resistance (OU or SA) to the most distance device
50 ohm ( Resistance value) 180 ohm
OK / Not OK In- between OU (add____) & SA (add___)
OK / Not OK In- between SA (add____)
OK / Not OK In- between OU (add____) & SA (add___)
1-2-4 Transmission wire installation inspection sheet 3/3
Distance from termination resistor (m)
0 ~100 ~ 200 ~ 300 ~400 ~500
Approximate resistance (Ω)
0 ~ 50
A short circuit somewhere or 2 or more termination resistors are connected
50
60
70
80
90 100 110 120 130 140 150 160 170 180
190 ~ Faulty contact or wiring length over 500 m
1K ~ Faulty contact, open circuit, or no termination resistor
01-07
Check Item Check contents Judgement Present Status
Ref. circuit name : _________________________________, Ref. address: ______________ (00
99)
Refrigerant system piping
Outlook
Insulation & Fastening Insulated without gap & properly fastened (Yes / No)
Yes / No
Suction line filter Is there any external filter in the suction line
Yes / No
Oil Trap If Distance between OUs 2m ,
Place oil trap both at suction & at Discharge line
Yes / No
Not applicable
Piping
Actual Pipe Length
Actual Pipe Length
Actual Pipe Length
1 outdoor unit connected2 outdoor units connected3 outdoor units connected
Between Master OU and farthest IU
(
165m)
Between Master OU and farthest IU
( 165m)
Between Master OU and farthest IU
(
165m)
(
700m )
(m)
Between first separation tube and farthest IU
(farthest IU) - (closest IU)
(
60m )
(farthest IU) - (closest IU)
(
60m )
(farthest IU) - (closest IU)
( 60m )
(
90m )
Between first separation tube and farthest IU
(
90m )
Between farthest OU and first OU branch kit
(
12m )
Between first separation tube and farthest IU
(
90m )
Between OU and OU branch kit
( 3m )
Between OU and OU branch kit
(
3m )
(m)
Total Pipe Length
(
1000m)
Total Pipe Length
(
1000m)
Total Pipe Length
(m)
(m)
(m)
(m)
(m)
(m)
(m)
(m)
(m)
(m)
(m)
(m)
(m)
(m)
(m)
(m)
(m)
(m)
(m)
(m)
(m)
(m)
Height Difference
Height Difference
Height Difference
Between OU and IU (when OU is installed above)
( 50m)
Between OU and IU (when OU is installed above)
( 50m)
Between OU and IU (when OU is installed above)
( 50m)
(
40m)
(
15m)
(m)
Between OU and IU (when OU is installed below)
( 40m)
Between OU and IU (when OU is installed below)
( 40m)
Between OU and IU (when OU is installed below)
(m)Between IUs
(
15m)
Between IUs
(
15m)
Between IUs
(
0.5m )
Between OUs
(
0.5m )
Between OUs
1-2-5 Piping installation inspection sheet
01-08
Check Item Check contents Judgement Present Status
Ref. circuit name: ____________________________, Ref. address :________(00
99)
Additional Charged Refrigerant
Outdoor Unit
OU Model Name Additional Refrigerant Amount for OU
AJ* 072L / AJ* 090L / AJ* 108L
AJ* 126L / AJ* 144L / AJ* 162L
AJ* 072L / AJ* 090L : 0 (kg)
AJ* 108L / AJ* 126L / AJ* 144L / AJ* 162L : 3.3 (kg)
(kg)
Connecting
Pipe
Liquid Pipe Length Additional Refrigerant Amount based on the liquid pipe length
@ 6.35mm (m)
For pipe diam eter 6.35m m : 0.021 kg/m
For pipe diam eter 9.52m m : 0.058 kg/m
For pipe diam eter 12.7mm : 0.114 kg/m
For pipe diam eter 15.88mm : 0.178 kg/m
For pipe diam eter 19.0
5mm : 0.268 kg/m
(kg)
@ 9.52mm (m)
(kg)
@ 12 .7mm (m)
(kg)
@ 15 .88m m (m )
(kg)
@ 19 .05m m (m )
(kg)
Total Additional Amount of Charged Refrigerant
(kg)
Note: In the refrigerant system, overall refrigerant amount
31.5 kg (for 1 OU), 63.0 kg (for 2 OUs) and 94.5 kg (for 3 OUs)
Overall refrigerant amount (kg) in the refrigerant system = Factory charged refrigerant (kg) for OU
+ Total additional amount of charged refrigerant (kg) [= Additional charged refrigerant for OU + Additional charged refrigerant for connecting pipe]
Factory charged refrigerant f or outdoor unit :
AJ* 072L or AJ* 090L : 11.7 (kg) AJ* 108L or AJ* 126L or AJ* 144L or AJ* 162L : 11.8(kg)
Check Item Check contents Judgement Present Status
Ref. circuit name: ____________________________, Ref. address :________(00
99)
Outdoor Unit
3-way valves
opening
3-way valve of each OU at
- Discharge pipe side
- Suction pipe side
- Liquid pipe side
Master OU ( all 3 -way valve must be full open )
Yes / No
Slave-1 OU ( all 3-way valve must be full open )
Yes / No
Slave-2 OU ( all 3-way valve must be full open )
Yes / No
1-2-6 Refrigerant charge amount inspection sheet
1-2-7 3-way valve opening inspection sheet
01-09
Check Item Check contents Judgement Present Status
Ref. circuit name _______________________, Ref. address ________(00
99)
Power Source
Outdoor Unit
Actual Power Supply (V)
Between R-S / S-T / T-R
< 3, 4Wire + ground, 50Hz >
AC (380 - 415V)
10%
Incom ing volta ge per brea ker
Master (V): R-S:_____ / S -T:____ / T-R:____
Slave -1 (V): R-S:_____ / S -T:____ / T-R:____
Slave -2 (V): R-S:_____ / S -T:____ / T-R:____
Indoor Unit
Actual Power Supply (V)
< 1, 2Wire + ground, 50Hz >
Incom ing volta ge per brea ker
Breaker-1 (V): _______
Breaker -2 (V): _______
Breaker -3 (V): _______
_______
Check Contents Judgement Present Status
Ref. circuit name ________________________, Ref. address ________(00
99)
For each refrigerant system
Outdoor unit Check PCB- Lighting status
Ma ster
LED101 (g reen light)
Judgment : must be ON
Yes / No
Note : LED102 (Red) mu st not be flash & must not be ON
7-SEG LED
Judgment : ‘Sn’ displayed
Yes / No
LED101: Yes No 7-SEG :
Yes No
Slave -1
LED101: Yes No 7-SEG :
Yes No
Slave -2
LED101: Yes No 7-SEG :
Yes No
Indoor unit Check LED & RC display status
IU address _______
IU address _______
IU address ____ ___
IU address ____ ___
IU address _______
IU address _______
IU address _______
IU address ____ ___
IU address ____ ___
IU address _______
IU address _______
Indoor Unit
For Wall mounted, Universal, Celling & Small Cassette
Check IU opera tion LED & timer LED condition
Judgment : must be fla shing a lterna te ly
Yes / No
For Large Cassette a nd Duct type IU
Check Wired RC (3- wire) display screen
Judgment : Clock display “AM 12:00” will appear
Yes / No
Check Wired RC (2-wire) display screen
Judgment : La ngua ge selection screen will ap pea r
Yes / No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
Yes No
AC (220 - 240V) 10%
Overview of system operation check procedure
Step-1: Connect Service Tool PC to the VRF V-III system.
Do scaning of refrigerant system which should be commissioned.
Step-2: Compare the number of installed units (OU and IU) with the System List data obtained from the Service Tool.
Step-3: Operate all Indoor Units under Test Mode Cooling (Select Test mode either cool or heat based on ambient temperature.).
Step-3-1: During operation, check the IU thermistor value Step-3-2: After 1-hour operation, check the Refrigerant System
Step-4: After 1-hour Test run operation (excluding special operation), Step-4-1: Switching the operation mode of IU from cool to heat.
- Check the IU thermistor value Step-4-2: When all IUs run under heating, continue operation minimum 15min. And check the Refrigerant system
1-3-2 Error indication check sheet
1-3 Check Items After Power ON
1-3-1 Power source check sheet
01-10
Check Contents Check items Checking method Judgement Present Status
Ref. circuit : Name ____ _____ _____ ___, Ref. address ________(select f rom 00 to 99) Design value Check status
Installed units and their addresses check
Number of IU IU address
Checked by
Service Tool
Number of units and their
address appeared in the
System List must be same
as the Actual Design value
Judgment:
(OK / Not OK)
Connected number of IU ______
IU add _____
IU add _____
IU add _____
IU add _____
IU add _____
IU add _____
IU add _____
IU add _____
IU add _____
IU add _____
IU add _____
IU add _____
IU add _____
IU add _____
IU add _____
OK
Not OK
1-3-3 Installed unit and their addresses check sheet
01-11
Check Contents Check items Checking method Judgement Present Status
Ref. circuit : Name ____ _____ _____ ___, Ref. address ________(select f rom 00 to 99)
Design val ue
Check status
Transmission line connection confirmation check
Cooling status Operate all Indoor
Units under Test-run Cooling Mode by using Commissioning Function of Service Tool
Judgment Point during test-mode cooling :
For Indoor Unit
-Thermistor value
(TH21 - TH22) 8
(Yes / No)
IU add _____ Yes / No
IU add _____
Yes / No
IU add _____
Yes / No
IU add _____
Yes / No
IU add _____
Yes / No
IU add _____
Yes / No
IU add _____
Yes / No
IU add _____ Yes / No
IU add _____
Yes / No
IU add _____
Yes / No
IU add _____
Yes / No
IU add _____
Yes / No
IU add _____
Yes / No
IU add _____
Yes / No
IU add _____
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Check Contents Check items Checking method Judgement Present Status
Ref. circuit : Name ____ _____ _____ ___, Ref. address ________(select f rom 00 to 99)
Design val ue
Check status
Transmission line connection confirmation
Heating status
Switching the opera tion of IU from cool to heat, Control function of Service To ol
Judgment Point after switching IU mode from cool to heat :
For Indoor Unit
- Thermistor value
(TH24 > TH2 1)
(Yes / No)
IU
IU
IU add _____
IU add _____
IU add _____
IU add _____
IU add _____
IU add _____
IU add _____
IU add _____
IU add _____
IU add _____
IU add _____
IU add _____
IU add _____
IU add _____
IU add _____
1-3-4 Transmission line connection check sheet
Note: The following check method by using test-run is necessary for checking of incorrect transmission wire connection.
01-12
Check Contents Judgement Present Status
Refrigerant Circuit : Name _________________, Address ________(00
99)
Conducted by
Service Tool
Degree of sub-cool at OU sub - cooler side should be,
5
Tsc 20 AND
Pulse value EEV3 should be,
Yes / No
Discharge refrigerant pressure should be,
2.5MPa Pd 3.3MPa
Yes / No
Suction refrigerant pressure should be,
0.7MPa Ps 1.2MPa
Yes / No
Discharge refrigerant temp. should be,
Discharge refrigerant superheat should be,
Yes / No
IU refg. superheat should be, 2 Pulse value IU EEV should be, EEV 1000P
Yes / No
Ps between Master & Slave OUs should be,
Ps 0.2 MPa
Yes / No
Air temperature of each IU should be,
Tair c ooling
>
8
Yes / No
No water fall from IU No abnormal noise from IU
Yes / No
EEV3 400P
Td 100
AND
Tshd > 10
Tshe 20 AND
Tsc
EEV3 P
Pd MPa
Ps MPa
Td
Tshd
Tshe
IU EEV P
Ps MPa
Tair c ooling
Tsc = Saturated liquid temperature of HPS - TH5
Tshd = TH1- Saturated liquid temperature of HPS
Tshe = TH24 - TH22 Tair c ooling = TH21 - Outlet Air temperature
Td = TH1
Pd = HPS Ps = LPS
Reference mark of Service tool
Check Contents Judgement Present Status
Refrigerant Circuit : Name _________________, Address ________(00
99)
Test-run operation
Heating mode
Conducted by
Service Tool
Discharge refrigerant pressure should be,
Suction refrigerant pressure should be,
Discharge refrigerant temperature should be,
Discharge refrigerant superheat should be,
Degree of sub cool (at IU side) should be,
Refrigerant superheat (at OU side) should be,
Pd between Master & S lave OUs should be,
T
OUHE
at each OU connected in series should be,
Air temperature of each IU should be,
2.5MPa Pd 3.3MPa
0.3MPa Ps 1.2MPa
Td 100
AND
Tshd > 10
Tsc 7
AND
4
Tshe1 & Tshe2 5
2
T
> 5
OUHE*
Ps 0.2 MPa
Tair heating > 15
Tsc = Saturated liquid temperature of HPS - TH22
Tshd = TH1- Saturated liquid temperature of HPS
Tshe1 = TH7 - Saturated vapor temperature of LPS
Tair heating = TH21 - Outlet Air temperature
Reference mark of Service tool
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Tsc
Pd MPa
Ps MPa
Td
Tshd
Tshe
Ps MPa
Tair heating
TOUHE
Tshe2 = TH8 - Saturated vapor temperature of LPS
T = TH4 - TH9
OUHE 1
T = TH4 - TH10
OUHE 2
Test-run operation
Cooling mode
1-3-5 Operation check sheet
01-13
All the indoor units connected to the outdoor unit can be test-operated by push button setting. (Only for master unit)
LED105 LED104LED105 LED104 LED105 LED104LED105 LED104
LED105
LED104
LED105 LED104
LED105 LED104
[ Cooling test run ]
[ Heating test run ]
[ Test run stop ]
LED105 LED104
LED105 LED104
LED105 LED104
LED105 LED104
(3) Press the ENTER button ( SW109 )
(5) Hold down the ENTER button ( SW109 ) for at least 3 seconds.
(6) Press the ENTER button ( SW109 ) or Time out ( 5 seconds)
(1) Press the MODE / EXIT button ( SW107 ) once.
< Pursuance completion >
< Monitoring condition >
< Mode select condition >
< Return to mode select condition >
< Fuction select condition >
[ Function mode ]
SWITCH POSITION
SW107 SW108 SW109
MODE
/EXIT
SELECT ENTER
LED101
(GREEN)
POWER
MODE
LED105 LED104
LED102
(RED)
ERROR
Push button switch
7 Segment LED Lamp
Outdoor unit printed circuit board
TEST RUN SETTING
(2)Press SELECT button
[ Monitoring mode ] [ Setting mode ] [ Error history mode ]
For a detailed description of push button operation, refer to the [D&T manual Chapter 6. SYSTEM DESIGN]
(4)Press SELECT button
LED105 LED104
< Return to monitoring condition >
(7) Press the MODE / EXIT button
example, Normal indicate : [ Cooling mode ]
[ Central control setting Forced reset ]
1-4 Test Run Operation
1-4-1 Test Run From Outdoor unit PC Board
1-4-2 Test Run From Remote Controller
Short two metal contacts under the battery compartment lid, while the air conditioner is running. To stop test run operation, push button of the wireless
remote controller. When the air conditioner is being test run, the OPERATION and TIMER lamps of indoor unit flash slowly at the same time.
START/STOP button
Test run button
2. Standard wireless remote controller
Stop the indoor unit. Push the button and button simultaneously for more than two seconds. The air conditioner will start to conduct a test run and " " will display on the remote controller display. However, the , setting button does not have function, but all other buttons, displays, and protection functions will operate.
To stop test run, push the START / STOP button of the standard wired remote controller. For the operation method, refer to the operating manual and perform operation check. Check that there are no abnormal sounds or vibration sounds during test run operation.
Perform the test operation for 60 minutes.
1. Standard wired remote controller
UTY - LNH
UTY - RNK
button
button and
Stop the indoor and outdoor units. Push the remote controller simultaneously for more than three seconds. The air conditioner will start to conduct a test run and " " will display on the temperature display.
SET
However the setting button does not have function but all other buttons, displays and protection functions will operate.
To stop test running press the button of the simple remote controller. For the operation method refer to the operating manual and perform operation check. Check that there are no abnormal sounds or vibration sounds during test run operation.
3. Simple remote controller
UTY - RSK
01-14
TIMER MODE
CLOCK ADJUST
TEST RUN
RESET
TIMER
SLEEP
FILTER RESET
SWING
SET
SET
ECONOMY
FANMODE
ON OFF
SET
TEMP.
TIMER MODE DAY
SET BACK
CLOCK ADJUST
DAY OFF
TIMER DELETE TIMER SET
FAN MODE
SET TEMP.
START / STOP
01-15
UTY - DTG
(1) Select the objective you want to test run. Select the objective icon or list at the monitor screen. (Multiple selections is possible) Select all the devices registered as objectives by pressing "Select All" on the monitor screen. (2) After objective selection at (1), switch to the <Setting screen> by pressing "Operation". (3) Switch to the <Detail setting screen > by pressing "Optional setting" on the setting screen, (4) Press "Start" button and OK on the details setting screen.
Test run continues for 60 minutes. To interrupt test run, select the device being the test run and excute an operation stop. At the monitor screen, test run can cancel by selecting objective device and press OFF.
4. Touch panel controller
On
On
Reset
Cancel
Stand by (Defrost) Stand by (Oil Recovery) Test Operation
Start
Air Flow Direction
Economy
Anti Freeze
Filter Sign
Operation
Test
Up
Down
Swing
Swing
Left Right
Off
Off
Special State
1
2
3
4
5
1
2
3
4
SettingOptional
10/11.2008.Mar. 02:20 PM
Operation Setting
OK
Status: On
<Setting screen>
Cancel
Off
On
OK
Status: On
Cancel
OK
On
Off
Auto
Auto
Cool
Dry
Fan
Heat
Operation Controlled
High
Med
Low
Quiet
Meeting Room
24.0 C
operation
R/C Prohibition
Mode Set Temp. Fan
Optional
Setting
All
On/Off
Filter
Timer
Temp.
Mode
On
10/11.2008.Mar. 02:20 PM
Air Flow Direction Economy Anti Freeze Filter Sign Test Operation
Control Unit :
Operation Setting
<Detail Setting screen>
[ Select All ]: All of R.C.Group (Indoor units) [ Identify Unit ] : Specific R.C.Group (Indoor unit)
Indoor unit Special Setting
Test Operation
Indoor Unit Set Temp. Range
Filter Sign
R.C. Prohibition
Group
Select All
Identify Unit
Clear Unit
UTY-DCG
05/31 03:59
Test Operation
05/31 03:59
RCG_05
(1) Press " " button. (2) Press "Set up Menue" and input password. (3) Select "Indoor unit special setting" by presing or button. (4) Select "Test operation by presing" or button (5) Press the "Select ALL button" or "ldentify unit" button
(6) Press the " Start " button The test run continues for 60 minutes. To interrupt test run before it is complet, return to the "Monitor Mode Screen", and press ON/ OFF.
5. Central remote controller
(1) Press "Menu" on the monitor screen. the < Main Menu screen > is displayed. (2) Press "Next Page" and press "Maintenance" (3) Press "Next Page" and press "Test Run". the <Test run screen > is displayed. (4) Press "OK" The test run continues for 60 minutes. To interrupt test run before it is complet, return to the "Monitor Mode Screen", and press ON/ OFF.
6. 2-wire type wired remote controller
< Monitor Mode Screen >
< Main Manu Screen >
< Maintenance Screen >
UTY - RNR
< Test Run Screen >
01-16
1-5 TEST RUN CONTROL
01-17
1. When the test run signal is transmitted from standard wired, wireless remote controller, simple remote controller, transmitted netwwork, and outdoor unit.
(1) The test run operation starts and the electric expansion valve is controlled to a maximum flow, regardless of the temperature condition. (2) Frost prevention operation has priority over item(1).
(3) Whether state of the indoor unit operates or stops, All units in the same refrigerant circuit will start to conduct a test run in accordance with the operation mode set by push switch of outdoor unit ( see 1 - 2 - 3 ). (4) After 60 minutes passes, the test run stops. (5) Test running initialization is shown below. * The temperature controlling on the test run operates regardless of setting temperature.
Fan speed Hi Hi Hi Hi
Vertical Air Direction Panel
Swing
Operating Mode
Cooling Heating Cooling Heating
OFF OFF
Position
1
Position
4
EXCEPT FOR THE DUCT MODEL DUCT TYPE
COMPACT CASSETTE TYPE
COMPACT WALL MOUNTED TYPE
1
2
3
4
*EXAMPLE
1
2
3
4
4
3
2
1
CEILING TYPE
4
3
2
1
Push switch on outdoor unit PCB
00 Connected number of indoor unit The number of the communicating unit is displayed
01
Software version :
[ ] [ ] [ ] [ ] [ ] displays by five items
It skips when there is no suffix
02 Software version of INV PCB
03
Software version of communication PCB
Operation of each part
10 Rotational speed of outdoor unit
fan motor
The rotational speed of the outdoor unit fan motor is displayed [ 0 ~ 999 ] rpm
11 Rotational speed of INV
compressor
The rotational speed of the compressor is displayed [ 0 ~ 999 ] rps
12 Current value of INV compressor Current value of INV compressor is displayed
[ 0.00 ~ 99.99 ] A
14 Pulse of EEV1 Pulse of EEV1 is displayed
[ 0 ~ 9999 ] pls
15 Pulse of EEV2 Pulse of EEV2 is displayed
[ 0 ~ 9999 ] pls
Time guard 20 Accumulated current time Accumulated current time is displayed
[ 0 ~ 9999 ]
10hour
21 INV compressor accumulated time
[ Cooling ]
Accumulated time is displayed in the cooling operation of the INV compressor [ 0 ~ 9999 ]
10hour
22 INV compressor accumulated time
[ Heating ]
Accumulated time is displayed in the heating operation of the INV compressor [ 0 ~ 9999 ]
10hour
Refrigerant cycle data 1
30 Information on Thermistor 1 The value of the Thermistor 1 is displayed
[ -99.9 ~ 999.9 ]
C or F
31 Information on Thermistor 2 The value of the Thermistor 2 is displayed
[ -99.9 ~ 999.9 ]
32 Information on Thermistor 3 The value of the Thermistor 3 is displayed
[ -99.9 ~ 999.9 ]
33 Information on Thermistor 4 The value of the Thermistor 4 is displayed
[ -99.9 ~ 999.9 ]
34 Information on Thermistor 5 The value of the Thermistor 5 is displayed
[ -99.9 ~ 999.9 ]
35 Information on Thermistor 6 The value of the Thermistor 6 is displayed
[ -99.9 ~ 999.9 ]
36 Information on Thermistor 7 The value of the Thermistor 7 is displayed
[ -99.9 ~ 999.9 ]
37 Information on Thermistor 8 The value of the Thermistor 8 is displayed
[ -99.9 ~ 999.9 ]
38 Information on Thermistor 9 The value of the Thermistor 9 is displayed
[ -99.9 ~ 999.9 ]
39 Information on Thermistor 10 The value of the Thermistor 10 is displayed
[ -99.9 ~ 999.9 ]
40 Information on Thermistor 11 The value of the Thermistor 11 is displayed
[ -99.9 ~ 999.9 ]
50 Information on pressure sensor 1
( High pressure sensor )
The value of the pressure sensor 1 is displayed
Refrigerant cycle data 3
If unit is [MPa], it is displayed as [ 0.00 ~ 9.99 ]
[psi], it is displayed as [ 0.0 ~ 999.9 ]
51 Information on pressure sensor 2
( Low pressure sensor )
The value of the pressure sensor 2 is displayed If unit is [MPa], it is displayed as [0.00 ~ 9.99]
[psi], it is displayed as [ 0.0 ~ 999.9 ]
[ F1 ]
Monitor mode
Setting Mode
ITEM CODE No.
Information contents
ITEM CODE No.
Refrigerant cycle data 2
C or F
C or F
C or F
C or F
C or F
C or F
C or F
C or F
C or F
C or F
Device and system
Software version of outdoor unit
Classification
01-18
1-6 Field Setting And Monitor Mode List for Outdoor unit
( Discharge temperature sensor 1)
( Outdoor temperature sensor )
( Suction temperature sensor )
( Liquid temperature sensor 1)
(Liquid temperature sensor 2)
( Sub-cool H-Ex (outlet) sensor )
(Heat exchanger 1 gas sensor1)
(Heat exchanger 2 gas sensor2)
(Heat exchanger 1 liquid sensor)
(Heat exchanger 2 liquid sensor)
(Compressor temperature sensor)
16 Pulse of EEV3 Pulse of EEV3 is displayed
[ 0 ~ 9999 ] pls
Install 00 Pipe length setting 00 40-65m
Setting mode
01 0-40m 02 65-90m 03 90-120m
04 120-165m
Correction 10 Sequential start shift 00
01 21sec. Delay 02 42sec. Delay 03 63sec. Delay
11
Cooling capacity shift 00 Normal mode
01 Save energy mode (+2 ) 02 High power mode 1 (-2 C) 03 High power mode 2 (-4 C)
12
Heating capacity shift
00 Normal mode 01 Save energy mode (-2 C) 02 High power mode 1 (+2 C) 03 High power mode 2 (+4 C)
13,14,15 (Forbidden) 00
01
01 Emergency stop
21 Operation mode selecting method 00 Priority given to the first command
01 Priority given to the external input of outdoor unit 02 Priority given to the master indoor unit
22 Snow falling protection fan mode 00 Valid
01 Invalid
23 Interval setting for snow falling 00 Standard (30min)
01 Short 1 (5min) 02 Short 2 (10min) 03 Short 3 (20min)
24 High static pressure mode 00 Standard
01 High static pressure 1 (equivalent to 30Pa) 02 High static pressure 2 (equivalent to 82Pa)
25 00
01
Change of 30 Energy saving level setting 00 Level 1 (stop)
01 Level 2 (operated at 40% capacity) 02 Level 3 (operated at 60% capacity) 03 Level 4 (operated at 80% capacity)
Low noise 40 Capacity priority setting 00 Off (quiet priority)
01 On (capacity priority)
41 Low noise mode setting 00 Off (Normal)
01 On (Low noise mode operation is always done)
42 Low noise mode operation 00 Level 1 (55dB)
01 Level 2 (50dB)
[ F2 ]
Normal
20
*1 : If one of compressor fails, backup operation will be performed by the remaining compressors.( For starting the system SET4-2 switching is required) *2 : If one of compressor fails, all units will be abnormal stop. *3 : When electricity meter No. is set to "000" and "201 to 299", the pulses input to CN135 become ineffective. Available setting number is "001" to "200" *4 : When the electricity meter pulse setting is set to "0000", the pulses input to CN135 become ineffective. Available setting number is "0001" to "9999"
00 Batch stop
Change of
function 1
Switching between batch stop or emergency stop
protection fan mode
setting 1
(in low noise mode)
level setting
function 2
C
01-19
Push switch on outdoor unit PCB
03
(Forbidden)
(Forbidden)
04 Level 5 (operated at 100% capacity)
26 00
01
27 00
01
28 00
01
29 00
01
(Forbidden)
(Forbidden)
(Forbidden)
(Forbidden)
(Forbidden)
70
Electricity meter No. setting 1
(Set the ones digit and tens digit of the No of the electricity meter connected to CN135.)
00~99*3Setting number x00~x99 00
71
Electricity meter No. setting 2
(Set the hundreds digit of the No. of the electricity meter connected to CN135.)
00~02*3Setting number 0xx~2xx 00
72
Electricity meter pulse setting 1
(Set the ones digit and tens digit of the No. of the electricity meter pulse setting connected to CN135.)
00~99*4Setting number xx00~xx99 00
73
Electricity meter pulse setting 2
(Set the hundreds digit and thousands digit of the electricity meter pulse setting connected to CN135.)
00~99*4Setting number 00xx~99xx 00
Change of function 3
( Refer to Design & Technical Manual for details.)
( Refer to Design & Technical Manual for details.)
( Refer to Design & Technical Manual for details.)
( Refer to Design & Technical Manual for details.)
Setting Mode
ITEM CODE No.
Setting Function
ITEM CODE No.
Classification
Defalt
04
17
Height difference between indoor units
00 Standard
Height difference
01 02 03
(Forbidden)
(Forbidden)
(Forbidden)
04
32 00
01
33 00
01
(Forbidden)
(Forbidden)
If installing the indoor units (even only one set) to a lower floor than the outdoor unit, and the height difference between the indoor units is 3m or greater (i.e., if installing the indoor units on separate floors), set “02 (height difference)”.
Push switch on outdoor unit PCB
Forced operation
00 Cooling test run Forced thermostat-ON in Cooling
Function mode
01 Heating test run Forced thermostat-ON in Heating
02 Test run stop Test run is stopped
Install and maintenance 1
10 Signal amplifier automatic address Automatic address setting operates for
signal amplifier
11 Indoor unit automatic address
21 Vacuuming mode Vacuuming mode operates
Refer to page 01-01 for the function
Clear 30 Error history clear All the abnormal code histories are cleared
32 Current time clear Accumulated current time becomes [ 0 ]
33 INV compressor accumulated time
clear
Accumulated time of the INV compressor becomes [ 0 ]
35 Field setting all clear Return to default the all set items
Abnormal 40 Abnormal reset It was displayed when abnormality occurs,
and abnormal code is reset
This is a function that uses to clear abnormal display after the repair is completed Please operate the switch after power off or power on the outdoor unit
Specialty function
91 Foreced Central control function
forced release
When the centralized control device failure, and the centralized control setting cannot be released, this function is used
All the limitations set with the centralized control device are released
Setting Mode
ITEM CODE No.
Setting Function
Default
ITEM CODE No.
Install and maintenance 2
Automatic address setting operates for indoor unit of same refrigerant circuit
[ F3 ]
01-20
*
<< Error code which manual error release will be required >> A5.1Low pressure abnormal
84.1 Current sensor 1 error
93.1 Inverter compressor start up error
94.1 Trip detection A1.1 Discharge temperature 1 abnormal A3.1 Compressor 1 temperature abnormal
97.1 Outdoor unit fan motor lock error
97.5 Fan motor temperature abnormal
97.9 Fan motor driver abnormal
68.2 Rush current limiting resister temp rise protection
95.5 Compressor motor loss of synchronization A6.3 Outdoor heat exchanger 1 gas temperature abnormal A6.4 Outdoor heat exchanger 2 gas temperature abnormal A4.1 High pressure Abnormal
86.4 High pressure SW 1 Error
Push switch on outdoor unit PCB
1 time ago (Newest)
Error History Mode
2 times ago
5 times ago
Meaning of Error History Number
ITEM CODE No.
Information contents
[ F9 ]
00
01
02
03
04
05 06 07 08
09
Error history
10 times ago (Oldest)
4 times ago
3 times ago
6 times ago 7 times ago 8 times ago 9 times ago
When the error occurred, the error code is memorized up to 10 on Main PCB.
If the memorized error code becomes over 10, the oldest one will be erased.
Refer to Chapter TROUBLE SHOOTING
Error Code List of Outdoor unit
03,04
(Forbidden)
31
(Forbidden)
01-21
1-7 Field Setting / Function Setting for Indoor unit
Setting Mode
ITEM CODE No.
Setting Function
Default
Indoor unit field setting setting by remote controller
Address
01 Indoor unit address 00~63 00~63 00 02 Refrigerant circuit address 00~99 00~99 00
Filter 11 Filter indicator Interval 00 Default
01
Longer
02 Shorter
13 Filter sign display 00 Enable
01 Disable 02 Display only on central remote control
Airflow 20 Ceiling airflow 00 Default
(Cassette type only) 01 High ceiling
23 Vertical airflow direction 00 Default
01 Raise
24 Horizontal swing airflow direction 00 Default
01 Left half 02 Right half
Correction 30
Cool air temperature trigger
00 Default (0
°C
)
01 Temperature overshoot setting (+2
°C)
02 Temperature undershoot setting (-2
°C)
31 Heat air temperature trigger 00 Default (0°C)
01 Temperature undershoot setting (-6
°C)
02 Temperature slightly undershoot setting (-4
°C)
03 Temperature overshoot setting (+4
°C)
Change of 40 Auto restart *1 00 Enable
01 Disable
43 Cool air prevention 00 Super low
01 Follow the setting on the remote controller
46 External control 00 Start / Stop
01 Emergency stop
47 Error report target 00 All
01 Display only for central remote control
ITEM CODE No.
Function 1
Classification
26
32
00 01 02 03 04 05 06 07 08 09 31
0 Pa 10 Pa 20 Pa 30 Pa 40 Pa 50 Pa 60 Pa 70 Pa 80 Pa 90 Pa 25 Pa (Standard)
Static Pressure setting
- Slim Duct Only -
The Range of static pressure is different from one model to other.
Temperature correction in Auto
00 01
Disable Enable (Nonfunctional on J2 Series)
02 Foreced stop (Start/Stop by RC is restricted)
49 FAN Setting when cooling thermo-
stat OFF *2
01
00
Follow the setting on the remote controller Foreced stop
*1: Auto restart is an emargency function such as for power failure etc. Do not start and stop the indoor unit by this function in normal operation. Be sure to operate by the control unit, converter or external input device. *2: Fan Setting when cooling thermostat OFF, Connection of the wired remote controller (2-wire type or 3-wire type) and switching its thermistor are necessary.
Model name Range of static pressure
ARXD04
ARXD18
ARXD07/09/12/14 0 to 90 Pa
ARXD24 0 to 50 Pa
01-22
1-8 Field Setting / Function Setting for Outdoor air unit
Setting Mode
ITEM CODE No.
Setting Function
Default
Indoor unit field setting
Address
setting by remote controller
01 Indoor unit address 00~63 00~63 00 02 Refrigerant circuit address 00~99 00~99 00
Filter 11 Filter indicator Interval 00 Default
01
Longer
02 Shorter
13 Filter sign display 00 Enable
01 Disable 02 Display only on central remote control
Airflow
Change of Function 1
40 Auto restart *1 00 Enable
01 Disable
43 Cool air prevention 00 Super low
01 Follow the setting on the remote controller
46 External control 00 Start / Stop
01 Emergency stop
47 Error report target
63 Humidifier control *2
00 All 01 Display only for central remote control
ITEM CODE No.
Classification
26
05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 31
SP mode 05 SP mode 06 SP mode 07 SP mode 08 SP mode 09 SP mode 10 SP mode 11 SP mode 12 SP mode 13 SP mode 14 SP mode 15 SP mode 16 SP mode 17 SP mode 18 SP mode 19 SP mode 20 SP mode 21 SP mode 22 Normal SP
Static Pressure setting
- Outdoor air unit Only -
The Range of static pressure is different from one model to other.
02
Foreced stop (Start/Stop by RC is restricted)
00 01 02
mode 00 mode 01 mode 02
*1: Auto restart is an emargency function such as for power failure etc. Do not start and stop the indoor unit by this function in normal operation. Be sure to operate by the control unit, converter or external input device. *2: Select control conditions of external output. "Mode 00" is output when heating thermostat is ON, "Mode 01" is output in heating operation, "Mode 02" is output in heating operation and in fan operation.
Model name
ARXH054GTAH ARQH140GTAH
ARXH072GTAH ARQH224GTAH
ARXH096GTAH ARQH280GTAH
Range of static pressure
SP mode 05 to 19 (50 to 185 Pa)
SP mode 05 to 20 (50 to 200 Pa)
SP mode 05 to 22 (50 to 220 Pa)
Normal static pressure
185 Pa
200 Pa
200 Pa
2. OUTDOOR UNIT OPERATION CONTROL
: Capillary
: Strainer
02-01
2-1 REFRIGERANT CIRCUIT
1 Compressor temp. Sensor 1 Detects the compressor temperature
No. Part name Function
2 Discharge temp. Sensor 1 Detects the discharge temperature
High pressure Swithch Detects abnormal high pressure (4.20 MPa)3
4 Check valve Comp. pressure equaization
Oil Separator Separates oil and refrigerant5
6 Compressor (Inverter) Operation range ( 20 rps - 90 rps )
7 Bypass / Oil return Valve HP-LP bypass in protection, Returns the oil to COMP
8 Oil return Valve Returns the oil to Compressor
9 High pressure Sensor Detects the High pressure
10 Bypass Valve
HP-LP bypass in protection / Comp. pressure equalization
11 Suction gas temp. Sensor
Collects refrigerant and the returned oil
12 Low pressure Sensor
Detects the temp of refrigerant
13 Acuumulator
Detects Low pressure
14 4-Way-Valve 1 Changes operation mode of HEX 1
Changes operation mode of HEX 24-Way-Valve 215
16 Service port Measure High pressure for Service
17 Heat-Ex 1 gas temp. Sensor Detects the temperature of refrigerant
Heat-Ex 2 gas temp. Sensor Detects the temperature of refrigerant
18 Heat Exchanger 1 Operates as Condenser / Evaporator
Heat Exchanger 2 Operates as Condenser / Evaporator
19
20
21 Outdoor unit FAN (Motor) Control FAN speed for heat exchange of HEX
22 Outdoor temp. Sensor Detects the ambient temperature
23 Heat-Ex 1 liquid temp. Sensor Detects the temperature of refrigerant
Heat-Ex 2 liquid temp. Sensor Detects the temperature of refrigerant24
25 Pressure regulation valve Operates in regulated pressure (4.00MPa)
26 Outdoor unit EEV1 Controls the flow of ref. based on target pressure
27 Outdoor unit EEV2 Controls the flow of ref. based on target pressure
29 Liquid pipe temp. Sensor 1 Detects the temperature of liquid refrigerant
Outdoor unit EEV3 Controls ref. subcooling /Operats in protection30
31 Sub-Cool Heat exchanger Subcool of liquid refrigerant
32
Sub-Cool HEX gas outlet temp Sensor
Detects the temperature of refrigerant
33 Liquid pipe temp. Sensor 2 Detects the temperature of liquid refrigerant
36 3way-valve (Liquid) Open / Close for Liquid line
37 3way-valve (Gas) Open / Close for Gas line
38 Service port Measure Low pressure for Service
39 I.U HEX outlet temp. Sensor Detects the temperature of refrigerant
Detects the temperature of room
Room temp. Sensor40
41 Indoor unit FAN (Motor) Controlled by setting / protection / Thermo OFF
Changes operation mode
42 I.U Heat Exchanger Operates as Condensor / Evapolator
Indoor unit EEV Controlled by setting / protection / Thermo OFF
43 I.U HEX inlet temp. Sensor Detects the temperature of refrigerant
44
4-Way-Valve 345
Prevents the liquid refrigerant return at cooling
Check valve46
Function
Part name
No.
2. OUTDOOR UNIT
EEV21
LIQUID LINE
FAN21
Indoor unit1
Outdoor unit
HEX21
GAS LINE
TH21
TH22
TH24
SCHEX
CMP (INV)
ACM
LPS
HEX1
TH11
TH1
HPSW1
SV2
SV3
TH3
TH2
EEV2
EEV1
TH4
EEV3
TH6
TH5
TH7
TH8
TH9
TH10
4WV 1
CMP ACM
OS
HPS
FAN1
4WV 3
4WV 2
HEX2
SV1
6
38
EEV21
FAN21
Outdoor air unit (ARXH054/ 096GTAH)
HEX21
TH21
TH25
TH22
TH24
: Capillary
: Strainer
02-02
2-1-1 REFRIGERANT CIRCUIT for Outdoor air unit
51
No. Part name Function
52
53
54
55
56
57
58
59
Heat exchanger outlet thermistor Detects the temperature of refrigerant
Detects the temperature of suction airflow
Suction airflow temp. thermistor
Detects the temperature of discharge airflow
Discharge airflow temp. thermistor
Heat exchanger Operates as Condensor / Evapolator
Fan motor Controlled by setting / protection / Thermo OFF
Heat exchanger inlet thermistor Detects the temperature of refrigerant
Fan motor Controlled by setting / protection / Thermo OFF
Electric expansion valve Controlled by setting / protection / Thermo OFF
Solenoid valve (Bypass) Opens at Thermo OFF in Heating mode
51
52
59
53
56
54
57
58
EEV21
FAN22
Outdoor air unit (ARXH072GTAH)
HEX21
TH21
TH25
TH22
TH24
51
52
59
53
56
54
FAN21
55
57
58
Loading...
+ 211 hidden pages