In the case of a
conventional fan, the air
outlet range was narrow
as the air ow moved to
the motor side which
meant the velocity of air
passing through the heat
exchanger was uneven.
2-stage turbo fan
A evenly spread air distribution across
the heat exchanger is possible due
to the new 2 stage turbo fan which
produces two separate air ow
streams.
1-stage
2-stage
Heat exchange
efciency:
20%UP
wing type) and wing number (7 blades
each)
Designed by CFD- analysis (uid) simulations
Laminar wing
Airow runs through smoothly
along the laminar wing
No airow separation
Quiet
Spin direction
Airow direction
Quiet
Adoption of laminar wing
MULTI TYPE
2, 3 ROOMS TYPE
Easy maintenance
z
Maintenance of fan motor and fan
Maintenance of the fan motor and fan can be done easily after taking off the panel as the bell mouth of the fan
can be removed easily.
A : Fan motor B : 2-stage turbo fan
C : Bell-mouth D : Panel
Long life lter
: standard equipment
Adaptation of transparent drainage parts
During installation, maintenance and operation, the drain pump and
kit can be checked easily.
Compact design
z
Grille cover
Easy installation by taking off ceiling panel of 23-5/8in. x 23-5/8in.(600mm x 600mm) size
High lift drain pump
z
- (01 - 01) -
MULTI TYPE
Height
Drain pump built-in
7-13/16 in.
(198mm)
Max.
33-7/16 in.
(850mm)
0
[in.WG (Pa )]
Air flow rate
Static pressure range
[CFM (m3/h)]
0.36 (90)
2, 3 ROOMS TYPE
MODELS : ARU7RLF, ARU9RLF, ARU12RLF, ARU18RLF
SLIM DUCT TYPE1-1-2.
MULTI TYPE
2, 3 ROOMS TYPE
Slim design and wide range of static
pressure for exible installation.
FEATURES
Slim design
z
This model is slim design, it can install at
the place where a ceiling is narrow.
Drain por t
Drain pump
Compact design
z
Condensate lift-up to 33-7/16in. (850mm)
Drain hose is standard accessory
Selectable with a wide range of
z
static pressure
Air - intake
z
Air intake direction can be selected to
match the installation site.
Bottom sideBack side
Flexible installation
z
Ceiling concealed
Wall concealed
By using DC fan motor, it is possible
to change of static pressure range 0 to
0.36in. WG (0 to 90Pa). The change of
static pressure range is possible by remote
controller.
- (01 - 02) -
Filter (Accessory)
z
Filter (ARU07/09/12/18: 2pcs.)
MULTI TYPE
“MIN. HEAT”
Button ON
Indoor unit
operation START
68
°F
(20°C)
50
°F
(10°C)
2, 3 ROOMS TYPE
MODELS : ASU7RLF1, ASU9RLF1, ASU12RLF1
FEATURES
WALL MOUNTED TYPE 1-1-3.
MULTI TYPE
2, 3 ROOMS TYPE
High efcient compact design
z
Making the tube thin:
0.276inch (7mm)
Thin:
Volume reduction of heat
exchanger:
Quiet operation
z
▼
0.197inch (5mm)
30%
More comfortable airow
z
INDOOR UNIT
Airow mode can be set in 4 steps and more detailed airow setting is possible.
21dB only at cooling operation (22dB at heating operation).
Fan speedNoise level
dB(A)
Quiet
21
(ASU7/9/12RLF1)
MIN. HEAT Operation
z
*Only available with Wireless RC.
The room temperature can be set to go no lower than 50°F (10°C),
thus ensuring that the room does not get too cold when not occupied
Caution)
When the room temperature is higher than 50°F (10°C), “ •
temperature at 50°F (10°C) when the temperature drops below 50°F (10°C).
MIN. HEAT
When “ •
Powerful operation
z
” operation stops, the room set temperature quickly returns to the preset temperature.
*Only available with Wireless RC.
MIN. HEAT
” operation does not start. Operation star ts and maintains the room
20 minutes continuous operation by maximum airow and maximum compressor speed is
possible. Rapid cooling and heating makes the room comfortable quickly.
- (01 - 03) -
MULTI TYPE
Outside air conditions: 35.6oF (2o C) 60%
( F)
Operation contents: Heating
Set temperature (Max set temp)
86
o
F (30oC), Air flow Hi
o
( C)
o
Vertical flap : Downward
Horizontal flap : Center
Power diffuser
(full open)
8492 90 88 86
2933 32 31 30
46
o
(24/30)
16
7 (2.1)
3 (1)
0
10 (3)20 (6)30 (9)40 (12)
ft.(m)
ft.(m)
Power diffuser
Outside air conditions: 95oF (35oC) 40%
( F)
Operation contents: Cooling
Set temperature (Min set temp)
64oF (18oC), Air flow Hi
o
Vertical flap : Upward
Horizontal flap : Center
64586062
( C)
o
18151617
7 (2.1)
3 (1)
0
ft.(m)
10 (3)20 (6)30 (9)40 (12)
ft.(m)
Organic coating fin used
heat exchanger
Pre Filter
Antibacterial deodorizing pre-filter with special ceramic powder
“Horizontal airow” does not blow cool air directly at the
z
Air conditioner lter features
z
Easy maintenance
z
Simplication of drain pan cleaning
improves maintenance-ability.
occupants in the room
Long-life*
Ion deodorization lter
The lter deodorizes by powerfully decomposing
absorbed odors using the oxidizing and reducing
effects of ions generated by the ultra-ne-particle
ceramic.
(*The lter can be used for approx. 3 years if it is washed
under water to restore its surface action when it is dirty.)
Using different lters at both sides
É
Apple-catechin lter
Fine dust, invisible mold spores, and harmful
microorganisms are absorbed onto the lter by
static electricity, and further growth is inhibited and
deactivated by the polyphenol extracted from apples.
- (01 - 04) -
MULTI TYPE
Cooling
at operation
start
Prevents cold air
from falling
at stable
operation
at operation
start
HeatingWindowPrevents cold
draft from
window
at stable
operation
Beneath
standard window
Standard concave
portion
Wall
Half concealed
Min.
27-9/16
(700)
Min.
23-1/4
(590)
Max.
3-1/8
(80)
Min.
28-3/4
(730)
Min.37 (940)
Max.
5-7/8
(150)
23-5/8
(600)
29-1/8
(740)
7-7/8
(200)
27-9/16
(700)
Remo
v
a
ble pane
l
Back view
Drain hose
Piping
1
6
2
5
3
4
Apple-catechin
Filter
Ion Deodorization
Filter
2, 3 ROOMS TYPE
MODELS : AGU9RLF, AGU12RLF, AGU15RLF
FEATURES
FLOOR TYPE 1-1-4.
2-Fan & Wide airow
z
Flexible & easy installation
z
Unit: in. (mm)
MULTI TYPE
2, 3 ROOMS TYPE
Filter features
z
ion deodorization lter
The lter deodorizes by powerfully decomposing absorbed odors using the oxidizing and reducing
effects of ions generated by the ultra-ne-particle ceramic.
Using different lters at both sides
Apple-catechin lter
Apple-catechin lter uses static electricity to clean ne particles and dust in
the air.
Easy maintenance
z
Removable and washable panel
Flexible piping connection
z
6 direction of drain & piping
- (01 - 05) -
OUTDOOR UNIT1-2.
Heating capacity
Rated capacity
47°F
(8°C)
5°F
(-15°C)
-15°F
(-26°C)
100%
80%
60%
-4°F
(-20°C)
Workable down to -15°F(-26°C) outdoor temperature &
Powerful operation even at low outdoor temperature
Outdoor unit has a built- in heater to keep it from freezing during the freezing cold mid-winter season.
The air conditioner uses highly cold resistant components that were desinge d to prevent freezing
and meet CSA standards to provide comfortable herating even whrn temperature fall to -15°F(-26°C).
Equipped with a base heater that prevents
condensate from freezing.
Cultivated base design discharges melted
water through many holes.
Without a heater, freezing condensate can
cause noise, damage to blade, condense r,
and system performance.
Powerful heating at low
ambient te mperature.
Base Pan Heater
Base heater
Without
base heater
With
base heater
MULTI TYPE
2, 3 ROOMS TYPE
MULTI TYPE
2, 3 ROOMS TYPE
- (01 - 06) -
LINE UP1-3.
MULTI TYPE
2, 3 ROOMS TYPE
MODEL
INDOOR UNIT
MULTI TYPE
2, 3 ROOMS TYPE
AUU7RLF
AUU9RLF
AUU12RLF
AUU18RLF
ASU7RLF1
ASU9RLF1
ASU12RLF1
AGU9RLF
AGU12RLF
AGU15RLF
ARU7RLF
ARU9RLF
ARU12RLF
ASU18RLF
ARU18RLF
OUTDOOR UNIT
AOU18RLXFZHAOU24RLXFZH
Indoor units that can be connected to each outdoor unit
4 mode timer setup available (ON / OFF / PROGRAM /SLEEP). ●
Can be used jointly with wired remote controllers . ●
Easy to change custom code (max. 4 custom codes) by button operation. ●
Built-in timers
z
Select from four different timer programs (ON/OFF/PROGRAM/SLEEP).
Program timer
z
The program timer operates the ON and OFF timer once within a 24 hour period.
MULTI TYPE
2, 3 ROOMS TYPE
Sleep timer
z
The sleep timer function automatically corrects the temperature thermostat setting according to the
time setting to prevent excessive cooling and heating while sleeping.
Cooling operation / dry operation
When the sleep timer is set, the set temperature
automatically rises 2°F (1°C) every hour. The set
temperature can rise up to a maximum of 4°F (2°C).
Simple function setting
z
Heating operation
When the sleep timer is set, the set temperature
automatically drops 2°F (1°C) every 30 minutes. The
set temperature can drop to a maximum of 8°F (4°C).
Setting of the air conditioner selection function is performed by remote controller.
Switching remote controller custom code
z
Code selector switch eliminates unit
•
being wrongly switched.
(Up to 4 custom codes can be set.)
*I.U.=Indoor unit
- (01 - 09) -
FUNCTIONS (UTY-LNHUM)
2
4
9
3
1
16
15
5
10
13
11
12
14
8
7
6
17
18
19
21
24
23
22
20
MULTI TYPE
2, 3 ROOMS TYPE
MODE button1
Selects the operating mode (AUTO, COOL, DRY, FAN, HEAT).
/Start / end R.C. custom code change. (Max 4 codes)
MULTI TYPE
2, 3 ROOMS TYPE
MIN.HEAT button2
SET TEMP. button ( ▲ / ▼ )3
Sets the indoor temp./ Sets R.C. custom code.
ECONOMY button4
SLEEP button5
Pressed to select sleep timer.
FAN button6
Selects the fan speed (AUTO, HIGH, MED, LOW, QUIET).
START/STOP button7
Pressed to start and stop operation.
SET button (Vertical)8
Air ow direction vertical set button.
SET button (Horizontal)9
Air ow direction horizontal set button.
SWING button10
Air ow direction swing button.
TIMER MODE button11
Pressed to select the timer mode. (OFF TIMER, ON TIMER,
PROGRAM TIMER, TIMER RESET)
TIMER set ( + / - ) button12
Sets the current time and on-off time.
CLOCK ADJUST button13
Sets the current time.
RESET button14
Used when replacing batteries.
TEST RUN button15
Used when testing the air conditioner after installation.
Display panel
Signal transmitter16
Temperature set indicator17
Operating mode indicator18
Sleep indicator19
Transmit indicator20
Fan speed indicator21
Swing indicator22
Timer mode indicator23
Clock indicator24
Note: Functions will be different due to type of indoor unit.
For details, please see operation manual.
- (01 - 10) -
SYSTEM DIAGRAM
6-11/16 (170)
2-3/16 (56)
3/4 (19)
2-3/8 (60.4)
1-3/16 (30.2)
Ø1/8 (3.5)
1/8 x 1/4 (3.5 x 6.5)
(HOLE)
(HOLE)
1-1/16 (26.2)
1 (25.5)
3-3/4 (95)
6-1/16 (154.7)
MULTI TYPE
2, 3 ROOMS TYPE
MULTI TYPE
2, 3 ROOMS TYPE
Control signal might not be recognized in following cases: ●
(i) A curtain or a wall, etc. exists between transmitter and receiver.
(ii) There is an instant-start type (inverter type, etc.) uorescent lamp
Signal transmitter
Signal receiver
window
in the room.
Air conditioner might not work correctly when strong light hits the ●
signal receiver window. Shut off the direct sunlight and also make
illuminator far away from the receiver window.
DIMENSIONS
Controller
z
Unit : in. (mm)
Top View
Holder
z
Front ViewRear View
Side View
Front ViewSide ViewBottom View
- (01 - 11) -
MULTI TYPE
2, 3 ROOMS TYPE
PACKING LIST
Name and shapeQuantityApplication
MULTI TYPE
2, 3 ROOMS TYPE
Remote controller holder 1
Tapping screw 2
Battery
[ 1.5V (R03 / AAA) ]
SPECIFIC ATIONS
Dimensions [H x W x D]: in. (mm)6-11/16 (170) x 2-3/16 (56) x 3/4 (19)
Weight : oz. (g)3 (85) [w/o batteries]
2For remote controller
Use as remote controller holder
For remote controller holder installation
- (01 - 12) -
MULTI TYPE
60min.
2°F (1°C)
4°F (2°C)
Timer setting
30min.
60min.
90min.
8°F
(4°C)
Timer setting
6°F
(3°C)
4°F
(2°C)
2°F
(1°C)
ABCD
AB
C
D
Mixed-up
I.U. I.U. I.U. I.U.
I.U. I.U. I.U. I.U.
After code change
REG1U
2, 3 ROOMS TYPE
MODEL: AR-REG1U
MULTI TYPE
2, 3 ROOMS TYPE
FEATURES
Built-in timers
z
4 mode timer setup available (ON / OFF / PROGRAM / SLEEP).
Easy operation.
Easy to change custom code (max. 4 custom codes) by button operation.
Select from four different timer programs (On / Off / Program / Sleep).
Program timer
z
The program timer operates the on and off timer once within a 24-hour period.
Sleep timer
z
The sleep timer function automatically corrects the temperature thermostat setting according to
the timer setting to prevent excessive cooling and heating while sleeping.
Cooling operation/dry operation
When the sleep timer is set, the set temperature
automatically rises 2°F (1°C) every hour. The set
temperature can rise up to a maximum of 4°F (2°C).
Heating operation
When the sleep timer is set, the set temperature
automatically drops 2°F (1°C) every 30 minutes. The
set temperature can drop to a maximum of 8°F (4°C).
Simple function setting
z
Setting of the air conditioner selection function is performed by remote controller.
Switching remote controller custom code
z
Code selector switch eliminates unit
•
being wrongly switched.
(Up to 4 custom codes can be set.)
*I.U.=Indoor unit
To change the temperature unit
z
Easy to change the temperature unit (
°F ↔ °C) by button operation.
- (01 - 13) -
MULTI TYPE
REG1U
REG1U
2, 3 ROOMS TYPE
FUNCTIONS (AR-REG1U)
MULTI TYPE
2, 3 ROOMS TYPE
Signal
transmitter
MIN. HEAT
button
TEMP.
button
POWERFUL
button
Start/Stop
button
ECONOMY button
TIMER ON button
TIMER OFF button
TIMER SELECT button
TIMER SLEEP button
TIMER CANCEL button
MODE button
CLOCK ADJUST button
FAN button
SWING button
SET button
RESET button
°C / °F switching button
Display panel
Mode indicator
Temperature indicator
Send indicator
To facilitate explanation, the accompanying illustration has been drawn to show all possible indicators; in actual operation,
however, the display will only show those indicators appropriate to the current operation.
SPECIFIC ATION
Transmit indicator
Fan Speed indicator
Swing indicator
Clock & Timer
indicator
DIMENSIONS [H × W × D]: in. (mm)8-1/16 (205) × 2-3/8 (61) × 11/16 (17)
WEIGHT oz. (g)4.3 (122)
ACCESSORYHolder
- (01 - 14) -
NOTE: Some button operations may
not be available for all units
or systems.
For details, refer to the
operation manual.
MULTI TYPE
8-1/16 (205)
11/16
(17)
2-3/8
(61)
Ø1/8 (Ø3.5)
1-15/16 (48.5)
4-3/16 (106.8)
5-7/8 (150)
1/8 (3.5)
1/4 (6.5)
2-3/4 (69.3)
1-1/16 (26.2)
3/16 (5.5)
2, 3 ROOMS TYPE
SYSTEM DIAGRAM
MULTI TYPE
2, 3 ROOMS TYPE
Control signal might not be recognized in following cases: ●
(i) A curtain or a wall, etc. exists between transmitter and receiver.
Signal transmitter
Signal receiver
window
(ii) There is an instant-start type (inverter type, etc.) uorescent lamp
in the room.
Air conditioner might not work correctly when strong light hits the ●
signal receiver window. Shut off the direct sunlight and also make
illuminator far away from the receiver window.
DIMENSIONS
Controller
z
[Unit: in.(mm)]
Top View
Holder
z
Front ViewFront View
Side View
Front ViewSide ViewBottom View
- (01 - 15) -
MULTI TYPE
2, 3 ROOMS TYPE
PACKING LIST
Name and shapeQuantityApplication
MULTI TYPE
2, 3 ROOMS TYPE
Remote controller holder 1
Tapping screw 2
Battery
[ 1.5V (LR03 / AAA) ]
SPECIFIC ATIONS
Dimensions [H x W x D]: in.(mm)8-1/16 (205) × 2-3/8 (61) × 11/16 (17)
Weight: oz.(g)4.3 (122) [w/o batteries]
2For remote controller
Use as remote controller holder
For remote controller holder installation
- (01 - 16) -
WIRED REMOTE CONTROLLER 2-2.
76°F (24°C)
0369 12 15 18 21
O'clock
12 369 12 369
time
AMPM
84°F (28°C)
0369 12 15 18 21
O'clock
12 369 12 369
time
AMPM
76°F 84°F 76°F
0 3 6 9 12 15 18 21
O'clock
12 3 6 9 12 3 6 9
time
AMPM
76°F (24°C)
84°F (28°C)
24°C 28°C 24°C
MULTI TYPE
2, 3 ROOMS TYPE
(For Compact cassette type, Slim duct type)
MULTI TYPE
2, 3 ROOMS TYPE
FEATURES
Various timer setup (ON/OFF/WEEKLY) are possible. ●
Equipped with weekly timer as standard function. ●
(Start/Stop function is twice per day for a week)
When setting up a timer, start/stop and a temperature setup can ●
be changed.
When a failure occurs,the error code is displayed. ●
Error history.(Last 16 error codes can be accessed.) ●
The room temperature can be controlled by being detective the ●
temperature accurately with Built-in thermo sensor.
Powerful features and compact size
z
Individual
control
Accurate and comfortable
z
Indoor temperature can be detected accurately by the inclusion of a
thermo sensor in the body of the wired controller.
Our system can correspond to various scenes.
This wired remote controller and the optional remote sensor allows
exibility in sensor location, and suitable for all requirements.
Thermo
sensor
Weekly
timer
Setback
timer
Wired
remote
controller
Sensor part
Thermo sensor
indicator
Control part for
changing the
thermo sensor
Built-in timers
z
Weekly timerSetback timer
Possible to set ON/OFF time to operate twice each day of the
week.
Example : setup sc reen
(Set to Wedne sday: 8:0 0 to 20:00.)
Easy-to-understa nd time ba r display
Screen
after setup
Possible to set temperature for two time spans and for each
day of the week.
At "Weekly timer" + "Set back timer" setup
Easy-to-understand operation
z
Timer
area
Operation
area
Simple installation
z
Components are compatible with standard switch
boxes. Flat back surface allows equipment to be
installed wherever it is needed.
Example : setup sc reen
(Set from S unday to Sat urday: 12:0 0 to 15:00, 28 °C .)
[Variable timer control]
The operation/display sections are zoned according
to time and operation, enabling variable programming
to match application.
- (01 - 17) -
European
switch b ox
JIS box
FUNCTIONS
7
Display
13
12
11
10
2
8
9
16
15
14
1
3
5
4
6
18
17
1920 21
2223 24252726
MULTI TYPE
2, 3 ROOMS TYPE
START/STOP button1
Pressed to start and stop operation.
MULTI TYPE
2, 3 ROOMS TYPE
SET TEMP. button2
Selects the setting temperature.
MODE button3
Selects the operating mode ( AUTO , COOL , DRY
FAN , HEAT ).
,
FAN button4
Selects the fan speed ( AUTO , HIGH
LOW , QUIET ).
,
MED ,
Vertical air ow direction and swing button5
Press for two seconds to change the swing mode
Horizontal air ow direction and swing button6
Press for two seconds to change the swing mode.
Built-in thermo sensor7
Detect room temperature.
TIMER MODE (CLOCK ADJUST) button8
Display panel
Selects the timer mode (OFF TIMER, ON TIMER, WEEKLY TIMER)
Set the current time.
DAY (DAY OFF) button9
Temporarily cancels of one day timer.
SET BACK button10
Pressed select the set back timer.
SET TIME button11
Pressed to select the set back timer.
TIMER DELETE button12
The schedule of a weekly timer is deleted.
TIME SET button13
Sets the date, hour, minute and on-off time.
ECONOMY (THERMO SENSOR) button14
FILTER RESET button15
Operation lamp16
Lights during operation and when the timer is on.
Timer and clock indicator17
Operation mode indicator18
Fan speed indicator19
Operation lock indicator20
Temperature indicator21
Displayed temperature is set temperature.
Defrost indicator22
Indicates during the oil recovery and defrosting operation.
1) Modify the remote controller cable as per below methods.
Use a tool to cut off the terminal on the end of the remote controller cable and then remove ●
the insulation from the cut end of the cable as shown in Fig.
Connect the remote controller cable and connecting cable as shown in Fig. ●
Be sure to insulate the connection between the cables. ●
Connecting
cable
White
Red
Black
Insulated
connection
Remote controller
cable
White
Red
Black
2) Method of connecting remote controller cable
Connecting cable made by above-mentioned 1) is connected with PCB of Indoor unit. ●
Remote controller
cable
Connecting
cable
Indoor unit PCB
- (01 - 21) -
MULTI TYPE
2, 3 ROOMS TYPE
PACKING LIST
Name and shapeQuantityApplication
MULTI TYPE
2, 3 ROOMS TYPE
Remote controller cable
[33ft(10m)]
Screw
(M4 x 16mm)
Binder 1
Connecting cable
Screw *1
(M4 x 14mm)
Cable clamper *1
Installation manual
Operating manual
Use only if the remote controller cable must be modied for the indoor unit model.
*1:
*1 1
For connecting the remote controller
1
For installing the remote controller
2
For remote controller and remote controller cable
binding
For connecting the remote controller cable to the
Wall mounted type indoor unit
For installing the remote controller cable to the
1
indoor unit
For installing the remote controller cable to the
1
indoor unit
1
1
WIRING SPECIFICATIONS
UseCable sizeWire typeRemarks
Remote controller
cable
SPECIFIC ATIONS
Dimensions [H x W x D]: in.(mm)4-3/4 (120) x 4-3/4 (120) x 11/16 (18)
Weight: oz. (g)5.6 (160)
PART (OPTIONAL)
Model name
22AWG
( 0.33 mm
Wall mounted type
ASU7RLF1
ASU9RLF1
ASU12RLF1
UT Y-XCBXZ2
2
)
Polar 3 coreUse sheathed PVC cable
* The communication kit is needed for connecting the wired remote controller to the Wall mounted type.
- (01 - 22) -
SPECIFICA TIONS3.
COMPACT CASSETTE TYPE3-1.
MULTI TYPE
2, 3 ROOMS TYPE
Model nameAUU7RLFAUU9RLFAUU12RLFAUU18RLF
Power source1ø 208/230V 60Hz
Available voltage range187-26 4V
Capacity7,000 Btu/h class9,000 Btu/h class12,000 Btu/h class 18,000 Btu/h class
Input powerW18182339
Running currentA0.150.150.190.30
High
Cooling
Airow
Fan
Sound pressure level *
Heat
exchanger
Dimensions
(H × W × D)
Weight
Connection
pipe
Operation range
Drain hose
Cassette
grille
Remote controller typeWired [Wireless(option)]
NOTE :
• The protective function might work when using it outside the operation range.
*: These are the measured values in the manufacturer’s anechoic chamber.
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the
specied values here.
rate
Heating
Fan Type × Q'tyTurbo × 1
Fan Motor OutputW54
Cooling
Heating
Dimension (H × W × D)in. (mm)
Fin pitchFPI21
Rows × Stages2 × 10
Pipe typeCopper tube
Fin TypeAluminum
Net
Gross10-7/16 × 28-3/4 × 24-5/8 (265 × 730 × 625)
Net
Gross40 (18)
Net
Gross4-3/4 × 30-1/8 × 29-3/4 (120 × 765 × 755)
Net
Gross10 (4.5)
CFM
(m3/h)
dB (A)
in. (mm)
lbs. (kg)
in. (mm)
°F (°C)64 to 90 (18 to 32)
%RH 80 or less
in. (mm)
lbs. (kg)
318 (540)318 (540)359 (610)441 (750)
33333742
8-1/4 × 51-9/16 × 1/2 + 8-1/4 × 49-3/16 × 1/2
(210 × 1,310 × 13.3 + 210 × 1,250 × 13.3)
9-5/8 × 22-7/16 × 22-7/16 (245 × 570 × 570)
33 (15)
Ø1/4 (Ø6.35)
WHITE
(Approximate colour of MUNSELL N 9.25 /)
1-15/16 × 27-9/16 × 27-9/16 (49 × 700 × 700)
5.7 (2.6)
MULTI TYPE
2, 3 ROOMS TYPE
- (01 - 23) -
SLIM DUCT TYPE3-2.
MULTI TYPE
2, 3 ROOMS TYPE
Model nameARU7RLFARU9RLFARU12RLFARU18RLF
Power source1ø 208/230V 60Hz
Available voltage range187-26 4V
Capacity
Input powerW33495873
Running currentA0.300.300.350.44
High
Cooling
Airow
Fan
Recommended static pressurein.WG (Pa)
Sound pressure level *
Heat
exchanger
Enclosure
Dimensions
(H × W ×D)
Weight
Connection
pipe
Drain hose
Operation range
Remote controller typeWired [Wireless(option)]
NOTE :
• Specications are based on the following conditions.
Standard static pressure : 0.10in.WG (25Pa)
• The protective function might work when using it outside the operation range.
*: These are the measured values in the manufacturer’s anechoic chamber.
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the
specied values here.
rate
Heating
Fan type × Q'tySirocco × 2Sirocco × 3
Fan motor outputW80818181
Cooling
Heating
Dimension (H × W × D)in. (mm)
Fin pitchFPI20
Rows × Stages2 × 143 × 14
Pipe typeCopper tube
Fin TypeAluminum
MaterialGALVANIZED STEEL SHEET
Color-
Model nameASU7RLF1ASU9RLF1ASU12RLF1
Power source1ø 208/230V 60Hz
Available voltage range187-26 4V
Capacity7,000 Btu/h class9,000 Btu/h class12,000 Btu/h class
Input powerW151722
Running currentA0.130.150.19
High
Cooling
Airow
Fan
Sound pressure level *
Heat
exchanger
Enclosure
Dimensions
(H × W ×D)
Weight
Connection
pipe
Drain hose
Operation range
Remote controller typeWireless [Wired(option)]
NOTE :
• The protective function might work when using it outside the operation range.
*: These are the measured values in the manufacturer’s anechoic chamber.
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the
specied values here.
rate
Heating
Fan type × Q'tyCross ow × 1
Fan motor outputW303030
Cooling
Heating
Dimension (H × W × D)in.(mm)
Fin pitchFPIMain: 23, Sub: 18
Rows × StagesMain: 2 x 20, Sub: 1 x 4
Pipe typeCopper tube
Fin TypeAluminum
MaterialPolystyrene
Color
Net
Gross10-5/8 × 34-13/16 × 14-3/4 (270 × 884 × 336)
Net
Gross23 (10.5)
Model nameASU18RLF
Power source1ø 208/230V 60Hz
Available voltage range187-26 4V
Capacity18,000 Btu/h class
Input powerW41
Running currentA0.32
High
Cooling
Airow
Fan
Sound pressure level *
Heat
exchanger
Enclosure
Dimensions
(H × W × D)
Weight
Connection
pipe
Drain hose
Operation range
Remote controller typeWireless [Wired(option)]
NOTE :
• The protective function might work when using it outside the operation range.
*: These are the measured values in the manufacturer’s anechoic chamber.
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the
specied values here.
rate
Heating
Fan type × Q'tyCross ow ×1
Fan motor outputW42
Cooling
Heating
Dimension (H × W × D)in. (mm)
Fin pitchFPIMain: 21, Sub: 18
Rows × StagesMain: 2 x 18, Sub: 1 x 4
Pipe typeCopper tube
Fin TypeAluminum
MaterialPolystyrene
Color
Net
Gross12-9/16 x 42-15/16 x 16-7/8 (319 × 1,090 × 429)
Net
Gross40 (18)