Fujitsu ARU12RLF, AUU12RLD, ARU18RLF, AUU9RLF, ASU7RLF1 Design & Technical Manual

...
Page 1
DESIGN & TECHNICAL MANUAL
AIR CONDITIONER
Multi: 5 rooms type
INDOOR
AUU7/9/12/18RLF ARU7/9/12RLF ARU18RLF ARU24RLF
ASU7/9/12/15RLF1 ASU18/24RLF AGU9/12/15RLF
OUTDOOR
DR_MU002EF_05
2016.09.23
Page 2
Notices:
• Product specifications and design are subject to change without notice for future improvement.
• For further details, please check with our authorized dealer.
Copyright © 2016 Fujitsu General Limited. All rights reserved.
Page 3
CONTENTS
Part 1. INDOOR UNIT ........................................................................1
1. Product features ......................................................................................2
1-1. Model lineup ..............................................................................................................2
1-2. Features ..................................................................................................................... 6
1-3. Control system design .............................................................................................15
1-4. Outdoor unit .............................................................................................................16
2. Remote controller ..................................................................................18
2-1. Wireless remote controller (UTY-LNHUM) ..............................................................18
2-2. Wireless remote controller (AR-REG1U) .................................................................21
2-3. Wired remote controller (UTY-RNNUM) ..................................................................24
2-4. Simple remote controller (UTY-RSNUM) .................................................................31
2-5. Central remote controller (UTY-DMMUM) ............................................................... 38
3. Specifications ........................................................................................44
3-1. Compact cassette type ............................................................................................44
3-2. Slim duct type ..........................................................................................................45
3-3. Wall mounted type ...................................................................................................47
3-4. Floor type .................................................................................................................49
4. Dimensions ............................................................................................50
4-1. Compact cassette type ............................................................................................50
4-2. Slim duct type ..........................................................................................................52
4-3. Wall mounted type ...................................................................................................57
4-4. Floor type .................................................................................................................61
5. Wiring diagrams .....................................................................................62
5-1. Compact cassette type ............................................................................................62
5-2. Slim duct type ..........................................................................................................63
5-3. Wall mounted type ...................................................................................................64
5-4. Floor type .................................................................................................................66
6. Air velocity and temperature distributions ..........................................67
6-1. Compact cassette type ............................................................................................67
6-2. Slim duct type ..........................................................................................................73
6-3. Wall mounted type ...................................................................................................83
6-4. Floor type .................................................................................................................90
7. Fan performance ....................................................................................91
7-1. Slim duct type ..........................................................................................................91
8. Airflow ...................................................................................................101
8-1. Compact cassette type ..........................................................................................101
8-2. Slim duct type ........................................................................................................102
8-3. Wall mounted type .................................................................................................103
8-4. Floor type ...............................................................................................................104
9. Noise level curve .................................................................................105
9-1. Compact cassette type ..........................................................................................105
Page 4
CONTENTS (continued)
9-2. Slim duct type ........................................................................................................ 107
9-3. Wall mounted type ................................................................................................. 110
9-4. Floor type .............................................................................................................. 113
9-5. Sound level check point ........................................................................................ 115
10. Electrical characteristics ....................................................................117
11. Safety devices ......................................................................................118
12. External input and output ...................................................................119
12-1.External input ........................................................................................................ 119
12-2.External output ..................................................................................................... 122
13. Function settings .................................................................................129
13-1.Indoor unit (setting by jumper wire) ...................................................................... 129
13-2.Indoor unit (setting by wireless remote controller) ................................................ 130
13-3.Indoor unit (setting by wired remote controller) .................................................... 143
13-4.Indoor unit (setting by simple remote controller) .................................................. 146
13-5.Function details .................................................................................................... 150
13-6.Wired remote controller ........................................................................................ 155
13-7.Simple remote controller ....................................................................................... 157
13-8.Central remote controller ...................................................................................... 158
14. Accessories ..........................................................................................159
14-1.Compact cassette type ......................................................................................... 159
14-2.Slim duct type ....................................................................................................... 161
14-3.Wall mounted type ................................................................................................ 162
14-4.Floor type .............................................................................................................. 164
15. Optional parts ......................................................................................165
15-1.Controller .............................................................................................................. 165
15-2.Cassette grille ....................................................................................................... 166
15-3.Others ...................................................................................................................167
16. Installation precautions ......................................................................170
16-1.Indoor unit installation precautions ....................................................................... 170
Page 5
CONTENTS (continued)
Part 2. OUTDOOR UNIT ................................................................173
1. Specifications ......................................................................................174
1-1. Model: AOU45RLXFZ ............................................................................................174
2. Dimensions ..........................................................................................176
2-1. Model: AOU45RLXFZ ............................................................................................176
3. Installation space .................................................................................177
3-1. Model: AOU45RLXFZ ............................................................................................177
4. Refrigerant circuit ................................................................................180
4-1. Model: AOU45RLXFZ ............................................................................................180
5. Wiring diagram .....................................................................................181
5-1. Model: AOU45RLXFZ ............................................................................................181
6. Capacity table ......................................................................................182
6-1. Combinations .........................................................................................................182
6-2. Cooling capacity ....................................................................................................189
6-3. Heating capacity ....................................................................................................211
7. Capacity compensation rate for pipe length and height difference 229
7-1. Model: AOU45RLXFZ ............................................................................................229
8. Additional charge calculation .............................................................233
8-1. Model: AOU45RLXFZ ............................................................................................233
9. Airflow ...................................................................................................234
9-1. Model: AOU45RLXFZ ............................................................................................234
10. Operation noise (sound pressure) .....................................................235
10-1.Noise level curve ...................................................................................................235
10-2.Sound level check point ........................................................................................236
11. Electrical characteristics ....................................................................237
12. Safety devices ......................................................................................238
13. Function settings .................................................................................239
13-1.Setting methods ....................................................................................................239
13-2.Outdoor unit low noise operation function (option) ............................................... 242
14. Check and test .....................................................................................243
14-1.Check run ..............................................................................................................243
14-2.Test run ................................................................................................................. 249
14-3.Error code .............................................................................................................251
14-4.Pump down ...........................................................................................................254
15. Accessories ..........................................................................................256
16. Optional parts ......................................................................................257
17. Installation precautions ......................................................................258
17-1.Outdoor unit installation precautions .....................................................................258
Page 6
CONTENTS (continued)
Page 7
Part 1. INDOOR UNIT
COMPACT CASSETTE TYPE:
AUU7/9/12/18RLF
SLIM DUCT TYPE:
ARU7/9/12/18/24RLF
WALL MOUNTED TYPE:
ASU7/9/12/15RLF1
ASU18/24RLF
FLOOR TYPE:
AGU9/12/15RLF
Page 8
- 2 -
MULTI TYPE
5 rooms type
1. Product features
Implemented core technology provides easy-to-use product operations that realize a comfortable space.
1-1. Model lineup
Indoor units that can be connected to each outdoor unit
●: Connectable / -: Not connectable
Indoor unit
AUU7RLF
AUU9RLF AUU12RLF AUU18RLF
ARU7RLF ARU9RLF
ARU12RLF
ARU18RLF
ARU24RLF
ASU7RLF1
ASU9RLF1 ASU12RLF1 ASU15RLF1
ASU18RLF ASU24RLF
AGU9RLF AGU12RLF AGU15RLF
Outdoor unit
AOU45RLXFZ
Outdoor unit
Compact
cassette
Slim duct Wall mounted Floor
AUU7—18RLF ARU7—24RLF ASU7—15RLF1
ASU18
24RLF
AGU9—
15RLF
kBtu Class 7 9 12 18 7 9 12 18 24 7 9 12 15 18 24 9 12 15
5 Rooms AOU45RLXFZ ●●●●●●●●●●●●●●●●●●
Page 9
- 3 -
MULTI TYPE
5 rooms type
Indoor unit connection patterns
5 rooms
AOU45RLXFZ
No. room 1 room 2 room 3 room 4 room 5 total
11818———36 21224———36 31524———39 41824———42 52424———48 6 7 7 24 38 7 7 9 18 34 8 7 9 24 40 9 7 12 18 37
1071224——43 11 7 15 15 3 7 1271518——40 1371524——46 1471818——43 1571824——49 16 9 9 18 36 17 9 9 24 42 1891215——36 1991218——39 2091224——45 2191515——39 2291518——42 2391524——48 2491818——45 2591824——51 26 12 12 12 36 27 12 12 15 39 28 12 12 18 42 29 12 12 24 48 30 12 15 15 42 31 12 15 18 45 32 12 15 24 51 33 12 18 18 48 34 12 18 24 54 35 15 15 15 45 36 15 15 18 48 37 15 15 24 54 38 15 18 18 51 39 18 18 18 54 40 7 7 7 15 36 41 7 7 7 18 39 42 7 7 7 24 45 43 7 7 9 12 35 44 7 7 9 15 38 45 7 7 9 18 41 46 7 7 9 24 47 47 7 7 12 12 38 48 7 7 12 15 41 49 7 7 12 18 44 50 7 7 12 24 50 51 7 7 15 15 44 52 7 7 15 18 47 53 7 7 15 24 53 54 7 7 18 18 50
Page 10
- 4 -
MULTI TYPE
5 rooms type
557999—34 56 7 9 9 12 37 57 7 9 9 15 40 58 7 9 9 18 43 59 7 9 9 24 49 60 7 9 12 12 40 61 7 9 12 15 43 62 7 9 12 18 46 63 7 9 12 24 52 64 7 9 15 15 46 65 7 9 15 18 49 66 7 9 18 18 52 67 7 121212—43 68 7 121215—46 69 7 121218—49 70 7 121515—49 71 7 121518—52 72 7 151515—52 739999—36 74 9 9 9 12 39 75 9 9 9 15 42 76 9 9 9 18 45 77 9 9 9 24 51 78 9 9 12 12 42 79 9 9 12 15 45 80 9 9 12 18 48 81 9 9 12 24 54 82 9 9 15 15 48 83 9 9 15 18 51 84 9 9 18 18 54 85 9 121212—45 86 9 121215—48 87 9 121218—51 88 9 121515—51 89 9 121518—54 90 12 12 12 12 48 91 12 12 12 15 51 92 12 12 12 18 54 93 12 12 12 18 54 94 12 12 15 15 54 957777735 967777937 9777771240 9877771543
9977771846 100 7 7 7 7 24 52 1017779939 102 7 7 7 9 12 42 103 7 7 7 9 15 45 104 7 7 7 9 18 48 105 7 7 7 9 24 54 106 7 7 7 12 12 45 107 7 7 7 12 15 48 108 7 7 7 12 18 51 109 7 7 7 15 15 51 110 7 7 7 15 18 54
1117799941 112 7 7 9 9 12 44 113 7 7 9 9 15 47
AOU45RLXFZ
Page 11
- 5 -
MULTI TYPE
5 rooms type
7: 7,000Btu/h, 9: 9,000Btu/h, 12: 12,000Btu/h, 15: 14,000Btu/h, 18: 18,000Btu/h, 24: 24,000Btu/h
114 7 7 9 9 18 50 115 7 7 9 12 12 47 116 7 7 9 12 15 50 117 7 7 9 12 18 53 118 7 7 9 15 15 53 1197 7 12121250 1207 7 12121553 1217999943 1227 9 9 9 1246 1237 9 9 9 1549 1247 9 9 9 1852 125 7 9 9 12 12 49 126 7 9 9 12 15 52 1277 9 12121252 1289999945 1299 9 9 9 1248 1309 9 9 9 1551 1319 9 9 9 1854 132 9 9 9 12 12 51 133 9 9 9 12 15 54 1349 9 12121254
AOU45RLXFZ
Page 12
- 6 -
MULTI TYPE
5 rooms type
1-2. Features
Compact cassette type
Models: AUU7RLF, AUU9RLF, AUU12RLF, and AUU18RLF
2-stage turbo fan High efficiency design by 2 stage structure
Quiet quality Optimization of wing form (laminar wing type) and wing number (7 blades each)
Easy maintenance
a Maintenance of fan motor and fan
Maintenance of the fan motor and fan can be done easily after taking off the panel as the bell mouth of the fan can be removed easily.
A: Fan motor
B: 2-stage turbo fan
C: Bell-mouth
D: Panel
b Air filter
Standard equipment
c Adaption of transparent drainage parts
During installation, maintenance and operation, the drain pump and kit can be checked easily.
+
2 stage
Wind velocity
Fast
Slow
Previous turbo fan
In the case of a conventional fan, the air outlet range was narrow
the motor side which meant the velocity of air passing through the heat exchanger was uneven.
2-stage turbo fan
A evenly spread air distr ibution across the heat exchanger is possible due to the new 2 stage turbo fan which
streams.
1-stage
2-stage
Heat exchange
20%UP
Laminar wing
along the laminar wing
Quiet
Spin direction
Quiet
Adoption of laminar wing
A
B
C
D
b
c
a
Grille cover
Page 13
- 7 -
MULTI TYPE
5 rooms type
Compact design Easy installation by taking off ceiling panel of 23-5/8 in × 23-5/8 in (600 mm × 600 mm) size.
High lift drain pump
22-7/16 in. (570 mm)
22-7/16 in. (570 mm)
27-9/16 in (700 mm)
Page 14
- 8 -
MULTI TYPE
5 rooms type
Slim duct type
Models: ARU7RLF, ARU9RLF, ARU12RLF, ARU18RLF, and
ARU24RLF
Slim design This model is slim design, it can install at the place where a ceiling is narrow.
Compact design Condensate lift-up to 33-7/16 in.
Selectable with a wide range of static pressure By using DC fan motor, it is possible to change of static pressure range 0 to 0.36 inWG (0 to 90 Pa). The change of static pressure range is possible by remote controller.
* 24 model is 0 to 0.20 inWG (0 to 50 Pa).
Air intake Air intake direction can be selected to match the installation site.
Slim design and wide range of static pressure for flexible installation.
Height
Drain pump built-in
7-13/16 in (198mm)
Drain pump
Drain port
Max.
33-7/16 in (850 mm)
Drain hose is standard accessory
0
[inWG (P a )]
Air fl ow rate
Static pressure range
[CFM (m3/h)]
0.36 (90)
Bottom side
Back side
Page 15
- 9 -
MULTI TYPE
5 rooms type
Flexible installation
Filter (Accessory)
Ceiling concealed
Wall concealed
Filter (ARU07/09/12/18: 2pcs.) (ARU24: 3pcs.)
Page 16
- 10 -
MULTI TYPE
5 rooms type
Wall mounted type
Models: ASU7RLF1, ASU9RLF1, ASU12RLF1, and ASU15RLF1
Quiet operation Airflow mode can be set in 4 steps and more detailed airflow setting is possible. 21 dB only at cooling operation (22 dB at heating operation).
MIN. HEAT Operation *Not operable from the wired remote controller that is connected individually.
The room temperature can be set to go no lower than 50 °F (10 °C), thus ensuring that the room does not get too cold when not occupied.
!
CAUTION
• When the room temperature is higher than 50 °F (10 °C), “MIN. HEAT” operation does not start. Operation starts and maintains the room temperature at 50 °F (10 °C) when the temperature drops below 50 °F (10 °C).
• When “MIN. HEAT” operation stops, the room set temperature quickly returns to the preset temperature.
Powerful operation *Only available with Wireless RC.
20 minutes continuous operation by maximum airflow and maximum compressor speed is possible. Rapid cooling and heating makes the room comfortable quickly.
High efficient compact design More comfortable airflow
Making the tube thin:
Thin:
0.276inch (7mm)
0.197inch (5 mm)
Volume re duct ion of heat
exchanger:
30%
Fan speed Noise level
Quiet
21
dB(A)
(7/9/12 TYPE)
“MIN. HEAT”
Button ON
Indoor unit operation START
68
°F
(20 °C)
50
°F
(10 °C)
Page 17
- 11 -
MULTI TYPE
5 rooms type
Models: ASU18RLF and ASU24RLF
Simple and elegant appearance design
Compact and slim design
“Vertical airflow” provides powerful floor level heating
"Horizontal airflow" does not blow cool air directly at the occupants in the room
39-5/16 in (998 mm)
Outside air conditions: 35.6 oF (2 oC) 60%
( F)
Operation contents: Heating Set temperature (Max. set temp.) 86 oF (30 oC), Airflow: Hi
o
( C)
o
Vertical flap: Downward Horizontal flap: Center
Power diffuser
(full open)
8492 90 88 86
2933 32 31 30
O
utsi
d
Oper
a
Set te
46
o
(24/30)
16
7 (2.1)
3 (1)
0
10 (3) 20 (6) 30 (9) 40 (12)
ft (m)
ft (m)
Power diffuser
Outside air conditions: 95 oF (35 oC) 40%
( F)
Operation contents: Cooling Set temperature (Min. set temp.) 64 oF (18 oC), Airflow Hi
o
Vertical flap: Upward Horizontal flap: Center
6458 60 62
( C)
o
1815 16 17
7 (2.1)
3 (1)
0
ft (m)
10 (3) 20 (6) 30 (9) 40 (12)
ft (m)
Page 18
- 12 -
MULTI TYPE
5 rooms type
Air conditioner filter features
Long-life* Ion deodorization filter
The filter deodorizes by powerfully decomposing absorbed odors using the oxidizing and re­ducing effects of ions generated by the ultra-fine-particle ceramic.
(*The filter can be used for approx. 3 years if it is washed under water to restore its surface action when it is dirty.)
Apple-catechin filter
Fine dust, invisible mold spores, and harmful microorganisms are absorbed onto the filter by static electricity, and further growth is inhibited and deactivated by the polyphenol extracted from apples.
Easy maintenance Simplification of drain pan cleaning improves maintenance-ability.
Using different filters at both sides
Organic coating fin used heat exchanger
Air filter
Ion deodorization filter
Apple-catechin filter
Page 19
- 13 -
MULTI TYPE
5 rooms type
Floor type
Models: AGU9RLF, AGU12RLF, and AGU15RLF
2-fan and wide airflow
Flexible and easy installation
Filter features
The filter deodorizes by powerfully decomposing absorbed odors using the oxidizing and re­ducing effects of ions generated by the ultra-fine-particle ceramic.
Apple-catechin filter uses static electricity to clean fine particles and dust in the air.
Ion deodorization filter
Using different filters at both sides
Apple-catechin filter
Cooling
at operation start
Prevents cold air from falling
at stable operation
at operation start
Heating
WindowPrevents cold draft from window
at stable operation
Beneath
standard window
Standard concave
portion
Wall
Half concealed
Min.
27-9/16
(700)
Min.
23-1/4
(590)
Max. 3-1/8
(80)
Min.
28-3/4
(730)
Min.37 (940)
Max. 5-7/8 (150)
23-5/8
(600)
29-1/8
(740)
7-7/8 (200)
27-9/16
(700)
Unit: in (mm)
Apple-catechin filter
Ion deodorization
filter
Page 20
- 14 -
MULTI TYPE
5 rooms type
Easy maintenance Removable and washable panel
Flexible piping connection 6 directions of drain and piping
Removable panel
Back view
Drain hose
Piping
1
6
2
5
3
4
Page 21
- 15 -
MULTI TYPE
5 rooms type
1-3. Control system design
Advanced integrated control system
Air conditioning
central control
Air conditioning
individual control
System
Central
remote controller
UTY-DMMUM
Wired remote controller
UTY-RNNUM
Simple remote controller
UTY-RSNUM
Wireless remote controller
UTY-LNHUM
AR-REG1U
IR receiver unit
UTY-LRHUM
Outdoor unit
Transmission line
Remote controller line
Central remote controller line
Page 22
- 16 -
MULTI TYPE
5 rooms type
1-4. Outdoor unit
Simple system from installation to management
New system can be connected up to 5 indoor units. So, it can decrease outdoor unit and other unit than previous system. And total management can be done by only one optional controller.
Top class High energy efficiency and powerful operation
High energy efficiency and powerful operation has been achieved by advanced technologies.
Previous 5 Rooms Multi System
<Case1> Single + 4 Rooms multi
New 5 Rooms multi system
5 Rooms multi system
• Decrease outdoor units
• Without Branch box
<Case2> 8 Rooms multi system
Central Remote Controller
(Option)
• From individual control to central control
TOP
CLASS
19.7
10.3
SEER
HSPF
DC inverter control
Large propeller fan
DC fan motor
Large heat exchanger
Compact and high performance DC twin rotary compressor
CoolingCapacity
45,000
Btu/h
HeatingCapacity
48,000
Btu/h
Page 23
- 17 -
MULTI TYPE
5 rooms type
Easy installation
By using centralized valve method, new outdoor unit can be done vacuuming and opening valve only one time.
Previous multi system
• Required vacuuming up to 4* times
New multi system
• Required vacuuming only one time
*: In the case of 4 rooms multi system.
:Wiringline :Pipingline
Automaticwiringand pipingcheck
Automatic connection mistakefix
A
B
C
D
E
A
B
C
D
E
Page 24
- 18 -
MULTI TYPE
5 rooms type
2. Remote controller
2-1. Wireless remote controller (UTY-LNHUM)
Features
Program timer
The program timer operates the on and off timer once within a 24-hour period.
Sleep timer
The sleep timer function automatically corrects the temperature thermostat setting according to the time setting to prevent excessive cooling and heating while sleeping.
Simple function setting
Setting of the air conditioner selection function is performed by remote controller.
Switching remote controller custom code
Code selector switch eliminates unit being wrongly switched. (Up to 4 codes can be set.)
* I.U.: Indoor unit
• 4 kinds of timer setup (on/off/program/sleep) are possible.
• Can be used jointly with wired remote controllers.
• Easy to change custom code (max. 4 custom codes) by button operation.
Cooling operation/Dry operation
When the sleep timer is set, the set temperature automatically rises 2 °F (1 °C) every hour. The set temperature can rise up to a maximum of 4 °F (2 °C).
Heating operation
When the sleep timer is set, the set temperature automatically drops 2 °F (1 °C) every 30 minutes. The set temperature can drop to a maximum of 8 °F (4 °C).
60 min
2 °F (1 °C)
4 °F (2 °C)
Timer setting
30 min
60 min
90 min
Timer setting
2°F (1°C)
4°F (2°C)
6°F (3°C)
8°F (4°C)
AB CD
ABCD
Mixed-up
I.U. I.U. I.U. I.U.
I.U. I.U. I.U. I.U.
After code change
Page 25
- 19 -
MULTI TYPE
5 rooms type
Overview
Display panel
a FAN button
Selects the fan speed (AUTO, HIGH, MED, LOW, and QUIET).
b START/STOP button
Starts and stops operation.
c SET button (vertical)
Adjusts the vertical airflow direction.
d SET button (horizontal)
Adjusts the horizontal airflow direction.
e SWING button
Sets the automatic swing operation and selects swing mode (Up/down, Left/right, Up/down/left/right, and Stop swing).
f RESET button
Used when replacing batteries.
g Timer set (- / +) button
Sets the current time and on-off time.
h TEST RUN button
Only used for the initial test in the unit installation.
i CLOCK ADJUST button
Used for adjusting the clock.
j TIMER MODE button
Selects the timer mode (off timer, on timer, program timer, and timer reset).
k SLEEP button
Pressed to select sleep timer.
l ECONOMY button
m MIN. HEAT button
n SET TEMP. (temperature) ( / ) button
• Sets desired temperature.
• Sets remote controller custom code.
o MODE button
• Switches operation mode (AUTO, COOL, DRY, FAN, and HEAT).
• Starts/ends the remote controller custom code (max. 4 types) change.
p Signal transmitter
q Signal transmit indicator
r Fan speed indicator
s Swing indicator
t Timer mode indicator
u Clock indicator
v Sleep indicator
w Operating mode indicator
x Temperature indicator
NOTE: Functions may differ by type of the indoor unit.
For details, refer to the operation manual.
o
p
j
k
l
n
m
b
d
e
a
f
i
g
h
c
q
r
s
t
u
v
w
x
Page 26
- 20 -
MULTI TYPE
5 rooms type
Specifications
Controller
Holder
Unit: in (mm)
Size (H × W × D) in (mm) 6-11/16 × 2-3/16 × 3/4 (170 × 56 × 19) Weight oz (g) 3 (85) (without batteries)
Unit: in (mm)
Size (H × W × D) in (mm) 6-1/16 × 2-3/8 × 1-1/16 (154.7 × 60.4 × 26.2) Weight oz (g) 10 (28)
Front view Side view Rear view
6-11/16 (170)
3/4 (19)
2-3/16 (56)
Top view
Front view Side view Bottom view
2-3/8 (60.4)
1-3/16 (30.2)
Ø1/8 (3.5)
1/8 x 1/4 (3.5 x 6.5)
(hole)
(hole)
1-1/16
(26.2)
1 (25.5)3-3/4 (95)
6-1/16 (154.7)
Page 27
- 21 -
MULTI TYPE
5 rooms type
2-2. Wireless remote controller (AR-REG1U)
Features
Simple function setting
Setting of the air conditioner selection function is performed by remote controller.
Program timer
The program timer operates the on and off timer once within a 24-hour period.
Sleep timer
The sleep timer function automatically corrects the temperature thermostat setting according to the time setting to prevent excessive cooling and heating while sleeping.
Switching remote controller custom code
Code selector switch eliminates unit being wrongly switched. (Up to 4 codes can be set.)
* I.U.: Indoor unit
Temperature unit switchable
Easy to change the temperature unit between °F and °C by button operation.
• 4-mode timer setup (on, off, program, and sleep) available.
• Easy operation.
• Easy to change custom code (max. 4 custom code).
• Can be used jointly with wired remote controllers.
Cooling operation/Dry operation
When the sleep timer is set, the set temperature automatically rises 2 °F (1 °C) every hour. The set temperature can rise up to a maximum of 4 °F (2 °C).
Heating operation
When the sleep timer is set, the set temperature automatically drops 2 °F (1 °C) every 30 minutes. The set temperature can drop to a maximum of 8 °F (4 °C).
REG1U
60 min
2 °F (1 °C)
4 °F (2 °C)
Timer setting
30 min
60 min
90 min
Timer setting
2°F (1°C)
4°F (2°C)
6°F (3°C)
8°F (4°C)
ABC D
ABCD
Mixed-up
I.U. I.U. I.U. I.U.
I.U. I.U. I.U. I.U.
After code change
Page 28
- 22 -
MULTI TYPE
5 rooms type
Overview
AR-REG1U
NOTE: Functions may differ by type of the indoor unit. For details, refer to the operation manual.
Display panel
To facilitate explanation, the accompanying illustration has been drawn to show all possible indicators; in actual operation, however, the display will only show those indicators appropriate to the current operation.
REG1U
REG1U
Signal
transmitter
MIN. HEAT
button
TEMP.
button
POWERFUL
button
Start/Stop
button
MODE button
FAN button
ECONOMY button
SWING button
SET button
ON TIMER button
OFF TIMER button
TIMER SELECT button
SLEEP TIMER button
TIMER CANCEL button
RESET button
°C / °F switching button
CLOCK ADJUST button
Mode indicator
Clock and Timer indicator
SEND indicator
Transmit indicator
Temperature indicator
Fan speed indicator
Swing indicator
Page 29
- 23 -
MULTI TYPE
5 rooms type
Specifications
Controller
Holder
Unit: in (mm)
Size (H × W × D) in (mm) 8-1/16 × 2-3/8 × 11/16 (205 × 61 × 17) Weight oz (g) 4.3 (122) (without batteries)
Unit: in (mm)
Size (H × W × D) in (mm) 5-7/8 × 2-3/4 × 1-1/16 (150 × 69.3 × 26.2) Weight oz (g) 1 (27)
Top view
Front view Side view
8-1/16 (205)
11/16 (17)
2-3/8
(61)
1-15/16 (48.5)
3/16 (5.5)
1-1/16 (26.2)
2-3/4 (69.3)
1/4 (6.5)
Front View Side View
Bottom View
Ø 1/8 (Ø3.5) (Hole)
5-7/8 (150)
4-3/16 (106.8)
Hole
(1/83.5)
2-R
Page 30
- 24 -
MULTI TYPE
5 rooms type
2-3. Wired remote controller (UTY-RNNUM)
Features
High performance and compact size
Accurate and comfortable
Indoor temperature can be detected accurately by the inclusion of a thermo sensor in the body of the wired controller.
Our system can correspond to various scenes. This wired remote controller and the optional remote sensor allows flexibility in sensor location,
and suitable for all requirements.
Built-in timers
• Various timer setup available (on, off, and weekly).
• Equipped with weekly timer as standard function. (Start/stop function is twice per day for a week.)
• When setting up the timer, operation mode and temperature setup can be changed.
• When a failure occurs, the error code is displayed.
• Error history. (Last 16 error codes can be accessed.)
• The room temperature can be controlled by detecting the temperature accurately with built-in thermo sensor.
Weekly timer Setback timer
Possible to set on/off time to operate twice each day of the week.
Possible to set temperature for two time spans and for each day of the week.
At
“Weekly timer” + “Set back timer” setup
Sensor part
Thermo sensor indicator
Control part for changing the thermo sensor
76 °F (24 °C)
036912151821
O'clock
1236912369
time
AM PM
Easy-to-understand time bar indicator
Screen after setup
Example: (Set to Wednesday: 8:00 to20:00)
84 °F (28 °C)
036912151821
O'clock
1236912369
time
AM PM
Example: setup screen (Set from Sunday to Saturday: 12:00 to 15:00, 28 °C.)
76 °F 84 °F 76 °F
036912151821
O'clock
12 3 6 9 12 3 6 9
time
AM PM
76°F (24 °C)
84 °F (28 °C)
24 °C 28 °C 24 °C
Page 31
- 25 -
MULTI TYPE
5 rooms type
Easy-to-understand operation
[Variable timer control]
The operation/display sections are zoned according to time and operation, enabling variable programming to match application.
Simple installation
Components are compatible with standard switch boxes. Flat-back surface allows equipment to be installed wherever it is needed.
System diagram
Electrical wiring
1 remote controller 2 remote controllers
A, B, C: Remote controller cable
A ≤ 1,640 ft (500 m);B + C ≤ 1,640 ft (500 m)
1 remote controller 2 remote controllers
Timer area
Operation area
European switch box
JIS box
A
Indoor unit
Remote controller
Primary
Secondary
BC
Indoor unit
Remote controllers
Indoor unit
Remote controller
123
123
Remote controller
1 (Red): 12 V 2 (White): Signal 3 (Black): COM
1 (Red): 12 V 2 (White): Signal 3 (Black): COM
Primary
Secondary
Indoor unit
123
123 123
Remote controller
Remote controllers
Page 32
- 26 -
MULTI TYPE
5 rooms type
Overview
Display panel
a START/STOP button
Starts and stops operation.
b SET TEMP. button
Selects the setting temperature.
c MODE button
Selects the operating mode (AUTO , HEAT ,FAN , COOL , and DRY ).
d FAN button
Selects the fan speed AUTO ,QUIET , LOW , MED , and HIGH ).
e ECONOMY (THERMO SENSOR) button
Turns the economy-efficient mode on and off.
f TIMER MODE (CLOCK ADJUST) button
Selects the timer mode (off timer, on timer, and
weekly timer). Sets the current time.
g DAY (DAY OFF) button
Temporarily cancels one day timer.
h SET BACK button
Selects the set back timer.
i Set time button
Pressed to set time.
j TIMER DELETE button
Deletes the weekly timer schedule.
k TIMER SET button
Sets the date, hour, minute, and on-off time.
l Vertical airflow direction and swing button
Push for 2 seconds to change the swing mode.
m Horizontal airflow direction and swing
button
Push for 2 seconds to change the swing mode.
n FILTER RESET button
o Operation lamp
Lights during operation and when the timer is on.
p Timer and clock indicator
q Operation mode indicator
r Fan speed indicator
s Operation lock indicator
t Temperature indicator
u Function indicators
Defrost indicator
Thermo sensor indicator
Economy indicator
Vertical swing indicator
Horizontal swing indicator
Filter indicator
NOTE: Functions may differ by type of the indoor unit.
For details, refer to the operation manual.
b f g h
i
j k
a c d
e
l
m
n
o
pqrst
u
Page 33
- 27 -
MULTI TYPE
5 rooms type
Specifications
Dimensions and other specifications on the wired remote controller are as follows.
Unit: in (mm)
Size (H × W × D) in (mm) 4-3/4 × 4-3/4 × 11/16 (120 × 120 × 18) Weight oz (g) 5.6 (160) Cable length (accessory) ft (m) 33 (10) Power V 12
4-3/4 (120)
4-3/4 (120)
4-3/4 (120)
11/16 (18)
Side viewFront view
Page 34
- 28 -
MULTI TYPE
5 rooms type
Installation
Connection pattern
NOTE: Connection pattern is different according to type of Indoor unit.
Pattern A
Connect the end of remote controller cable directly to the exclusive terminal block.
NOTE: It may be failed if it is connected to the outdoor unit or the terminal block for power supply.
Indoor unit types Connection pattern
Compact cassette type
Pattern A
Slim duct type
Wall mounted type
ASU7RLF1, ASU9RLF1, ASU12RLF1,
and ASU15RLF1
Pattern B
ASU18RLF and ASU24RLF
Pattern C
Floor type
PCB
M4 screw
Terminal block
Remote controller cable
Remote controller terminal block
Outdoor unit or Power supply terminal block or Remote controller terminal block
Page 35
- 29 -
MULTI TYPE
5 rooms type
Pattern B
1. Modify the remote controller cable as follows:
• Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in following figure.
• Connect the remote controller cable and connecting cable as shown in following figure.
• Be sure to insulate the connection between the cables.
2. Connect the remote controller cable.
• Connect the cable made in step 1. to the terminal (*1) of optional communication kit.
• Connect the cable from the terminal (*2) of communication kit to the indoor unit PCB.
*1: CNC01 (for ASU7/9/12/15RLF1: UTY-XCBXZ2)
*2: CND01 (for ASU7/9/12/15RLF1: UTY-XCBXZ2)
13/16 in.
(20 mm)
Remote controller cable
Connecting cable
White Red
White
Red
Black
Insulated connection
Black
Remote controller cable
Connecting cable Terminal
(*1)
Terminal (*2)
Communication kit
Indoor unit PCB
Page 36
- 30 -
MULTI TYPE
5 rooms type
Pattern C
1. Modify the remote controller cable as follows:
• Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in following figure.
• Connect the remote controller cable and connecting cable as shown in following figure.
• Be sure to insulate the connection between the cables.
2. Connect the remote controller cable.
• Connect the cable made in step 1. to the indoor unit PCB.
Wiring specifications
Optional parts
The communication kit is needed for connecting the wired remote controller to the compact wall mounted type.
Use Cable size Wire type Remarks
Remote controller cable
22AWG (0.33 mm2)
Polar 3 core Use sheathed PVC cable.
Wall mounted Model name
ASU7/9/12/15RLF1 UTY-XCBXZ2
13/16 in.
(20 mm)
Remote controller cable
Connecting cable
White Red
White
Red
Black
Insulated connection
Black
Remote controller cable
Connecting cable
Indoor unit PCB
Page 37
- 31 -
MULTI TYPE
5 rooms type
2-4. Simple remote controller (UTY-RSNUM)
Features
Easy-to-understand operation
• Provides access to basic operations, such as start/stop, fan speed, operation mode and room temperature setting.
• A large start/stop button is provided in the center of the remote controller unit for easy opera­tion.
• Following an error display, diagnostics can be carried out on the controller.
LCD backlight
• LCD backlight enables easy operation in a dark room.
• Backlight activates during all button operations, and lasts 10 seconds in operating mode and 5 seconds in stop mode after a button is pressed.
Simple installation
Can be mounted on the European switch box (installation dimension: 2-3/8 in [60 mm]) or the JIS built-in box (installation dimension: 3-5/16 in [83.5 mm]).
• Easy operation.
• Built-in backlight function.
• Easy installation with a slim shape with no bulge in the back.
• Error history. (Last 16 error codes can be accessed.)
• Can be installed onto switch box. (applies to European and other country's standard)
˚
F
3-5/16 in (83.5 mm)
2-3/8 in (60 mm)
Page 38
- 32 -
MULTI TYPE
5 rooms type
System diagram
Electrical wiring
1 remote controller 2 remote controllers
A, B, C: Remote controller cable
A≤1,640 ft (500 m);B+C≤1,640 ft (500 m)
1 remote controller 2 remote controllers
A
Indoor unit
Remote controller
Primary
Secondary
BC
Indoor unit
Remote controllers
Indoor unit
Remote controller
123
123
Remote controller
1 (Red): 12 V 2 (White): Signal 3 (Black): COM
1 (Red): 12 V 2 (White): Signal 3 (Black): COM
Primary
Secondary
Indoor unit
123
123 123
Remote controller
Remote controllers
Page 39
- 33 -
MULTI TYPE
5 rooms type
Overview
Display panel
a START/STOP button
Starts and stops operation.
b Display backlight button
Lights during operation.
c Operation lamp
Lights during operation.
d FAN button
Selects the fan speed (AUTO ,HIGH , MED , LOW , and QUIET ).
e SET TEMP. button
Selects the setting temperature.
f MODE button
Selects the operating mode (AUTO , COOL , DRY , FAN , HEAT ).
g Standby indicator
Indicates during the oil recovery and defrosting opera­tion.
h Power source indicator
Indicates the main power is on.
i Central control indicator
Indicates when function is locked.
j Fan speed indicator
Deletes the weekly timer schedule.
k Set temperature
• Indicates error history number in error code history display mode.
• Indicates indoor unit address in address display mode.
l Operating mode indicator
m Indicator
• Upper:
–Indicates the error code in error code history
display mode and in self diagnosis mode.
–Indicates the refrigerant system address in
address display mode.
• Lower: Indicates the remote controller address in error code history display mode, address display mode, and self diagnosis mode.
a
b c
d
e
f
g
h
i
j
k
l
m
Page 40
- 34 -
MULTI TYPE
5 rooms type
Specifications
Dimensions and other specifications on the wired remote controller are as follows.
Unit: in (mm)
Size (H × W × D) in (mm) 4-3/4 × 2-15/16 × 9/16 (120 × 75 × 14) Weight oz (g) 3.2 (90) Cable length (accessory) ft (m) 33 (10) Power V 12
4-3/4 (120)
2-15/16 (75)
1-15/16 (49)
1-9/16 (39)
15/16 (23.5)
9/16 (14)
3/16 (4)
7/16 (11)
3/16 (4.5)
1/2 (12.5)
hole x 2
hole x 2
5/16 (8)
2-3/8 (60)
1/4 (6)
11/16 (18)
3/8 (9)
1-7/8 (47.5)
3-5/16 (83.5)
Front View Side View Rear View
Page 41
- 35 -
MULTI TYPE
5 rooms type
Installation
Connection pattern
NOTE: Connection pattern is different according to type of Indoor unit.
Pattern A
Connect the end of remote controller cable directly to the exclusive terminal block.
NOTE: It may be failed if it is connected to the outdoor unit or the terminal block for power supply.
Indoor unit types Connection pattern
Compact cassette type
Pattern A
Slim duct type
Wall mounted type
ASU7RLF1, ASU9RLF1, ASU12RLF1,
and ASU15RLF1
Pattern B
ASU18RLF and ASU24RLF
Pattern C
Floor type
PCB
M4 screw
Terminal block
Remote controller cable
Remote controller terminal block
Outdoor unit or Power supply terminal block or Remote controller terminal block
Page 42
- 36 -
MULTI TYPE
5 rooms type
Pattern B
1. Modify the remote controller cable as follows:
• Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in following figure.
• Connect the remote controller cable and connecting cable as shown in following figure.
• Be sure to insulate the connection between the cables.
2. Connect the remote controller cable.
• Connect the cable made in step 1. to the terminal (*1) of optional communication kit.
• Connect the cable from the terminal (*2) of communication kit to the indoor unit PCB.
*1: CNC01 (for ASU7/9/12/15RLF1: UTY-XCBXZ2)
*2: CND01 (for ASU7/9/12/15RLF1: UTY-XCBXZ2)
13/16 in.
(20 mm)
Remote controller cable
Connecting cable
White Red
White
Red
Black
Insulated connection
Black
Remote controller cable
Connecting cable Terminal
(*1)
Terminal (*2)
Communication kit
Indoor unit PCB
Page 43
- 37 -
MULTI TYPE
5 rooms type
Pattern C
1. Modify the remote controller cable as follows:
• Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in following figure.
• Connect the remote controller cable and connecting cable as shown in following figure.
• Be sure to insulate the connection between the cables.
2. Connect the remote controller cable.
• Connect the cable made in step 1. to the indoor unit PCB.
Wiring specifications
Optional parts
The communication kit is needed for connecting the wired remote controller to the compact wall mounted type.
Use Cable size Wire type Remarks
Remote controller cable
22AWG (0.33 mm2)
Polar 3 core Use sheathed PVC cable.
Wall mounted Model name
ASU7/9/12/15RLF1 UTY-XCBXZ2
13/16 in.
(20 mm)
Remote controller cable
Connecting cable
White Red
White
Red
Black
Insulated connection
Black
Remote controller cable
Connecting cable
Indoor unit PCB
Page 44
- 38 -
MULTI TYPE
5 rooms type
2-5. Central remote controller (UTY-DMMUM)
Features
Central and individual control
The temperature, airflow volume, and remote control prohibition settings of all indoor units can be batched.
Easy-to-understand operation
• Large backlit LCD.
• Large easy-to-see operation panel.
Easy installation
• Central remote controller is connected directly to the indoor unit, making the installation process easier.
• Once the controller is connected, it can automatic register and display all the indoor units.
Outdoor unit low noise operation
Users can choose from 2 low noise levels, depending on the installation environment.
• Large and full-dot liquid crystal screen.
• The backlit LCD enables easy operation in a dark room.
• Wide and large keys easy to press, user-intuitive arrow key.
100%
58dB
0
0
Heat load
Air conditioning load factor
Low noise operation
Operating sound
Capacity
Down
(time)
Page 45
- 39 -
MULTI TYPE
5 rooms type
Minimum heat (All) operation
While this function is selected, all indoor units start the minimum heat operation when all the in­door units are stopped by operation of the [On/Off button].
• When the room temperature is higher than 50 °F (10 °C), MIN. HEAT operation dose not start. Operation starts and maintains the room temperature at 50 °F (10 °C) when the temperature drops below 50 °F (10 °C).
• When "MIN, HEAT" operation stops, the room set temperature quickly returns to the preset temperature.
Economy (All) operation
• If all the indoor and outdoor units are changed to economy mode, this can save more energy than setting of each indoor unit individually.
• Economy operation is energy saving, as the set temperature of indoor unit is shifted by 2 °F (1 °C) and the maximum electric value of the outdoor unit is suppressed.
Example: Cooling operation
Schedule timer
Operation setting can be changed 4 times in each day of a week, and 2 types of the schedule can be set to suit users' preference.
Example
Prohibited settings
The remote controller operation of all indoor units comes with a lock function to prevent unap­proved operations in the various rooms. The central remote controller also has a key lock func­tion to prevent children from playing with it, etc.
50
°F
70
°F
Indoor unit operation START
“All MIN. HEAT” operation
All indoor units
ON
OFF
(
21
)
°C
(
10
)
°C
Temp.
Economy operation
Shift
setting
temp
Control maximum current
Normal operation
Time
Set temperature
yadnuS~yadrutaSyadirF~yadnoM
AM7
AM7 AM7PM12 PM1 PM1 PM6PM11 PM11
AM8PM12 PM1 PM6 PM10PM5 PM11 Time
T
emp.
T
emp.
T
emp.
T
emp.
Time
Time
Time
Summer season pattern
Winter season pattern
Cool Cool Cool Cool Cool Cool
Heat
Heat
Heat Heat
Heat
Heat
Page 46
- 40 -
MULTI TYPE
5 rooms type
Electrical wiring
Example: Wiring diagram when 3 indoor units are connected.
NOTE: Maximum length of remote controller cable is 1,650 ft (500 m).
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
Central remote controller
Page 47
- 41 -
MULTI TYPE
5 rooms type
Overview
Specifications
Dimensions and other specifications on the wired remote controller are as follows.
Wiring specifications
a Display panel (with backlight)
b Screen switch button (Left)
c Menu button
d Cancel button
e Cursor button
f Screen switch button (Right)
g Power indicator
h On / Off button
i Enter button
Unit: in (mm)
Size (H × W × D) in (mm) 4-3/4 × 4-3/4 × 13/16 (120 × 120 × 21.3) Weight oz (g) 7.8 (220) Cable length (accessory) ft (m) 33 (10) Power V 12
Use Cable size Wire type Remarks
Remote controller cable
22AWG (0.33 mm
2
)
Polar 3 core Use sheathed PVC cable
a
b
c
d
e
f g
h
i
4-3/4 (120)
4-3/4 (120)
13/16 (21.3)
1-3/16
(30)
1-13/16 (45.3)
1/2 (12.5)
3/16 (4.5)
3/16 (4.5)
5/8 (15.3)
2-1/2 (63.5)
3-5/16 (83.5)
7/8
(23)
3/8 (9)
3/16 (4.5)
1-5/16
(33.5)
Front View Side View Rear View
Page 48
- 42 -
MULTI TYPE
5 rooms type
Installation
1. Remove the insulation of the remote controller cable.
2. Insert the flat-blade screwdriver and remove the front case and rear case by twisting it slightly.
3. Install the rear case to the wall, box, etc. with 2 screws (M4 × 16 mm). Fix the 2 screws in either horizontal or vertical position.
A. When mounting on the box:
Attach the case after leading the cable.
B. When the cable is along the wall:
• Mount the rear case on the wall.
• Remove knock out hole for cable routing in the front case.
!
CAUTION
When connecting the remote controller cable, take measures to prevent the water or insects coming into the remote controller through the cable, such as to provide the trap or close the hole for cabling with the putty.
4. Configure the DIP switch setting with referring Chapter 13-8. "Central remote controller" on page 158.
5/16
(8)
5/16 (8)
5/16 (8)
1-3/16 (30)
1-3/4 (45)
2-3/16 (55)
1. 12V (Red)
2. Signal (White)
3. COM (Black)
Unit: in (mm)
Flat screwdriver
Front case
Hooks (2 places)
Rear case
Screws
Box
Remote controller cable
Rear case
Putty
Putty
Putty
Trap
Trap
Trap
Page 49
- 43 -
MULTI TYPE
5 rooms type
5. Connect the cable to the terminals on the front case. Fix the cable together with the sheath by using the cable tie. Cut off the excess cable tie.
!
CAUTION
• Be careful to avoid breaking the cable by over-tightening the binder.
• When connecting the remote controller cables, do not over-tighten the screws.
6. Attach the front case.
• Adjust the upper part of the front case first, then insert the front case until it clicks.
• When inserting the front case, do not pinch the cable.
!
CAUTION
Insert the front case firmly. If improperly attached, it will cause the front case to fall off.
Tightening torque
Terminal screw 7 to 10 lbf • in (0.8 to 1.2N • m)
1. 12 V (Red)
2. Signal (White)
3. COM (Black)
Cable tie
Hole for binder
Remote controller cable (sheath)
2 mm (1/16 in)
Prohibited
Good
Prohibited
Front case
Good
Click!
Prohibited Prohibited Prohibited
Page 50
- 44 -
MULTI TYPE
5 rooms type
3. Specifications
3-1. Compact cassette type
Model name AUU7RLF AUU9RLF AUU12RLF AUU18RLF
Power supply 208/230 V ~ 60 Hz
Available voltage range 187—264 V
Capacity Btu/h class 7,000 9,000 12,000 18,000
Input power W 18 18 23 39
Running current A 0.15 0.15 0.19 0.30
Fan
Airflow rate
Cooling
HIGH
CFM (m3/h)
318 (540) 318 (540) 359 (610) 441 (750)
MED 288 (490) 288 (490) 312 (530) 359 (610)
LOW 259 (440) 259 (440) 277 (470) 306(520)
QUIET 230 (390) 230 (390) 241 (410) 241 (410)
Heating
HIGH 318 (540) 318 (540) 359 (610) 471 (800)
MED 288 (490) 288 (490) 312 (530) 418 (710)
LOW 259 (440) 259 (440) 277 (470) 353 (600)
QUIET 230 (390) 230 (390) 241 (410) 265 (450)
Typ e × Q'ty Turbo fan × 1
Motor output W 54
Sound pressure level *2
Cooling
HIGH
dB (A)
33 33 37 42
MED 31 31 33 37
LOW 29 29 31 33
QUIET 27 27 28 29
Heating
HIGH 34 34 37 44
MED 32 3 2 3 3 40
LOW 29 29 31 37
QUIET 27 27 28 30
Heat exchanger type
Dimensions (H × W × D) in (mm) 8-1/4 × 51-9/16 × 1/2 + 8-1/4 × 49-3/16 × 1/2 (210 × 1,310 × 13.3 + 210 × 1,250 × 13.3)
Fin pitch FPI 21
Rows × Stages 2 × 10
Pipe type Copper tube
Fin type Aluminum
Dimensions (H × W × D)
Net
in (mm)
9-5/8 × 22-7/16 × 22-7/16 (245 × 570 × 570)
Gross 10-7/16 × 28-3/4 × 24-5/8 (265 × 730 × 625)
Weight
Net
lb (kg)
33 (15)
Gross 40 (18)
Connection pipe
Size
Liquid
in (mm)
Ø1/4 (Ø6.35)
Gas Ø3/8 (Ø9.52) Ø1/2 (Ø12.70)
Method Flare
Operation range
Cooling
°F (°C) 64 to 90 (18 to 32)
%RH 80 or less
Heating °F (°C) 60 to 88 (16 to 31)
Drain hose
Material Hard PVC
Size in (mm) Ø 3/4(I.D.), Ø 1-1/16(O.D.) [Ø 20.7 (I.D.), Ø 26.6 (O.D.)]
Cassette grille
Model name UTG-CCGF
Material PS
Color
White
(Approximate color of MUNSELL N 9.25 /)
Dimensions (H × W × D)
Net
in (mm)
1-15/16 × 27-9/16 × 27-9/16 (49 × 700 × 700)
Gross 4-3/4 × 30-1/8 × 29-3/4 (120 × 765 × 755)
Weight
Net
lb (kg)
5.7 (2.6)
Gross 10 (4.5)
Remote controller type Wired (Wireless [option])
NOTES:
• The protective function might work when using it outside the operation range. *: These are the measured values in the manufacturer’s anechoic chamber.
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
Page 51
- 45 -
MULTI TYPE
5 rooms type
3-2. Slim duct type
Model name ARU7RLF ARU9RLF ARU12RLF
Power supply 208/230 V ~ 60 Hz
Available voltage range 187—264 V
Capacity Btu/h class 7,000 9,000 12,000
Input power W 33 49 58
Running current A 0.30 0.30 0.35
Fan
Airflow rate
Cooling
HIGH
CFM (m3/h)
324 (550) 353 (600) 383 (650)
MED 288 (490) 324 (550) 353 (600)
LOW 277 (470) 294 (500) 324 (550)
QUIET 259 (440) 265 (450) 283 (480)
Heating
HIGH 324 (550) 353 (600) 383 (650)
MED 288 (490) 324 (550) 353 (600)
LOW 277 (470) 294 (500) 324 (550)
QUIET 259 (440) 265 (450) 283 (480)
Type × Q'ty Sirocco fan × 2
Motor output W 80 81
Recommended static pressure inWG (Pa) 0 to 0.36 (0 to 90)
Sound pressure level *
Cooling
HIGH
dB (A)
28 28 29
MED 26 27 28
LOW 25 26 27
QUIET 24 25 26
Heating
HIGH 28 28 29
MED 26 26 28
LOW 25 25 27
QUIET 24 24 24
Heat exchanger type
Dimensions (H × W × D) in (mm)
11-9/16 × 19-11/16 × 1-1/16
(294 × 500 × 26.6)
11-9/16 × 19-11/16 × 1-9/16
(294 × 500 × 39.9)
Fin pitch FPI 20
Rows × Stages 2 × 14 3 × 14
Pipe type Copper tube
Fin type Aluminum
Enclosure
Material Galvanized steel sheet
Color -
Dimensions (H × W × D)
Net
in (mm)
7-13/16 × 27-9/16 × 24-7/16 (198 × 700 × 620)
Gross 10-13/16 × 37-3/16 × 30-3/8 (274 × 945 × 772)
Weight
Net
lb (kg)
37 (17) 40 (18)
Gross 49 (22) 51 (23)
Connection pipe
Size
Liquid
in (mm)
Ø1/4 (Ø6.35)
Gas Ø3/8 (Ø9.52)
Method Flare
Drain hose
Material Hard PVC
Size in (mm) Ø 3/4 (I.D.), Ø 1-1/16 (O.D.) [Ø 20.7 (I.D.), Ø 26.6 (O.D.)]
Operation range
Cooling
°F (°C) 64 to 90 (18 to 32)
%RH 80 or less
Heating °F (°C) 60 to 88 (16 to 31)
Remote controller type Wired (Wireless [option])
NOTES:
• Specifications are based on the following conditions. – Standard static pressure: 0.10 inWG (25 Pa)
• The protective function might work when using it outside the operation range.
• *Sound pressure level: – Measured values in manufacturer’s anechoic chamber. – Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
Page 52
- 46 -
MULTI TYPE
5 rooms type
Model name ARU18RLF ARU24RLF
Power supply 208/230 V ~ 60 Hz
Available voltage range 187—264 V
Capacity Btu/h class 18,000 24,000
Input power W 73 111
Running current A 0.44 0.66
Fan
Airflow rate
Cooling
HIGH
CFM (m3/h)
554 (940) 783 (1,330)
MED 518 (880) 730 (1,240)
LOW 483 (820) 648 (1,100)
QUIET 441 (750) 607 (1,030)
Heating
HIGH 554 (940) 783 (1,330)
MED 518 (880) 730 (1,240)
LOW 483 (820) 648 (1,100)
QUIET 441 (750) 607 (1,030)
Type × Q 'ty Sirocco × 3 Sirocco × 4
Motor output W 81
Recommended static pressure inWG (Pa) 0 to 0.36 (0 to 90) 0 to 0.20 (0 to 50)
Sound pressure level *2
Cooling
HIGH
dB (A)
32 33
MED 31 32
LOW 30 30
QUIET 29 29
Heating
HIGH 33 35
MED 32 34
LOW 31 32
QUIET 29 29
Heat exchanger type
Dimensions (H × W × D) in (mm)
11-9/16 × 27-9/16 × 1-9/16
(294 × 700 × 39.9)
11-9/16 × 35-7/16 × 1-9/16
(294 × 900 × 39.9)
Fin pitch FPI 20
Rows × Stages 3 × 14
Pipe type Copper tube
Fin type Aluminum
Enclosure
Material Galvanized steel sheet
Color -
Dimensions (H × W × D)
Net
in (mm)
7-13/16 x 35-7/16 x 24-7/16
(198 × 900 × 620)
7-13/16 x 43-5/16 x 24 -7/16
(198 × 1,100 × 620)
Gross
10-13/16 x 45-1/16 x 30-3/8
(274 × 1,145 × 772)
10-13/16 x 52-15/16 x 30-3/8
(274 × 1,345 × 772)
Weight
Net
lb (kg)
49 (22) 55 (25)
Gross 60 (27) 68 (31)
Connection pipe
Size
Liquid
mm (in)
Ø1/4 (Ø6.35)
Gas Ø1/2 (Ø12.70) Ø5/8 (Ø15.88)
Method Flare
Drain hose
Material HARD PVC
Size in (mm) Ø 3/4(I.D.), Ø 1-1/16(O.D.) [Ø 20.7 (I.D.), Ø 26.6 (O.D.)]
Operation range
Cooling
°F (°C) 64 to 90 (18 to 32)
%RH 80 or less
Heating °F (°C) 60 to 88 (16 to 31)
Remote controller type Wired (Wireless [option])
NOTES:
• Specifications are based on the following conditions. – Standard static pressure: 0.10 inWG (25 Pa)
• The protective function might work when using it outside the operation range.
• *Sound pressure level: – Measured values in manufacturer’s anechoic chamber. – Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
Page 53
- 47 -
MULTI TYPE
5 rooms type
3-3. Wall mounted type
Model name ASU7RLF1 ASU9RLF1 ASU12RLF1 ASU15RLF1
Power supply 208/230 V ~ 60 Hz
Available voltage range 187—264 V
Capacity Btu/h cl ass 7,000 9,000 12,000 14,000
Input power W 15 17 22 28
Running current A 0.13 0.15 0.19 0.25
Fan
Airflow rate
Cooling
HIGH
CFM (m3/h)
330 (560) 353 (600) 388 (660) 430 (730)
MED 294 (500) 306 (520) 330 (560) 353 (600)
LOW 253 (430) 253 (430) 265 (450) 312 (530)
QUIET 182 (310) 182 (310) 182 (310) 212 (360)
Heating
HIGH 330 (560) 353 (600) 388 (660) 430 (730)
MED 294 (500) 306 (520) 330 (560) 362 (615)
LOW 253 (430) 253 (430) 277 (470) 330 (560)
QUIET 194 (330) 194 (330) 194 (330) 221 (375)
Type × Q 'ty Cross flow fan × 1
Motor output W 30
Sound pressure level *
Cooling
HIGH
dB (A)
36 37 40 42
MED 32333638
LOW 29293033
QUIET 21212125
Heating
HIGH 36 37 40 42
MED 32333638
LOW 29293135
QUIET 22222227
Heat exchanger type
Dimensions (H × W × D) in (mm)
Main: 12-5/8 × 24-13/16 × 13/16 (320 × 630 × 20)
Sub: 3-5/16 × 24-13/16 × 1/2 (84 × 630 × 13.3)
Fin pitch FPI Main: 23, Sub: 18
Rows × Stages Main: 2 × 20, Sub: 1 × 4
Pipe type Copper tube
Fin type Aluminum
Enclosure
Material Polystyrene
Color
White
(Approximate color of MUNSELL N9.25 /)
Dimensions (H × W × D)
Net
in (mm)
10-9/16 × 33-1/16 × 8 (268 × 840 × 203)
Gross 10-5/8 × 34-13/16 × 14-3/4 (270 × 884 × 336)
Weight
Net
lb (kg)
19 (8.5)
Gross 23 (10.5)
Connection pipe
Size
Liquid
in (mm)
Ø1/4 (Ø6.35)
Gas Ø3/8 (Ø9.52) Ø1/2 (Ø12.70)
Method Flare
Drain hose
Material PP + LLDPE
Size in (mm) Ø 9/16(I.D.), Ø 5/8 to Ø 11/16(O.D.) [Ø 13.8(I.D.), Ø 15.8 to Ø 16.7(O.D.)]
Operation range
Cooling
°F (°C) 64 to 90 (18 to 32)
%RH 80 or less
Heating °F (°C) 60 to 88 (16 to 31)
Remote controller type Wireless (Wired [option])
NOTES:
• The protective function mi ght work when using it outside the operation range.
• *So und pressure level: – Measured values in manufacturer’s anechoic chamber. – Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
Page 54
- 48 -
MULTI TYPE
5 rooms type
Model name ASU18RLF ASU24RLF
Power supply 208/230 V ~ 60 Hz
Available voltage range 187—264 V
Capacity Btu/h class 18,000 24,000
Input power W41 69
Running current A0.32 0.53
Fan
Airflow rate
Cooling
HIGH
CFM (m3/h)
542 (920) 659 (1,120)
MED 4 36 (740) 530 (900)
LOW 365 (620) 436 (740)
QUIET 32 4 (550) 365 (620)
Heating
HIGH 542 (920) 647 (1,100)
MED 4 36 (740) 530 (900)
LOW 365 (620) 436 (740)
QUIET 32 4 (550) 365 (620)
Type × Q'ty Cross flow fan ×1
Motor output W 42
Sound pressure level *
Cooling
HIGH
dB (A)
43 49
MED 37 42
LOW 33 37
QUIET 31 33
Heating
HIGH 44 48
MED 37 42
LOW 33 37
QUIET 31 33
Heat exchanger type
Dimensions (H × W × D) in (mm)
Main: 15-7/8 × 33-3/4 × 1-1/16 (378 × 832 × 26.6)
Sub: 3-5/16 × 33-3/4 × 1/2 (84 × 832 × 13.3)
Fin pitch FPI Main: 21, Sub: 18
Rows × Stages Main: 2 × 18, Sub: 1 × 4
Pipe type Copper tube
Fin type Aluminum
Enclosure
Material Polystyrene
Color
White
(Approximate color of MUNSELL N9.25 /)
Dimensions (H × W × D)
Net
in (mm)
12-5/8 × 39-1/4 × 9 (320 × 998 × 228)
Gross 12-9/16 × 42-15/16 × 16-7/8 (319 × 1,090 × 429)
Weight
Net
lb (kg)
31 (14)
Gross 40 (18)
Connection pipe
Size
Liquid
mm (in)
Ø1/4 (Ø6.35)
Gas Ø1/2 (Ø12.70) Ø5/8 (Ø15.88)
Method Flare
Drain hose
Material PVC
Size in (mm) Ø 1/2(I.D.), Ø 5/8(O.D.) [Ø 12(I.D.), Ø 16(O.D.)]
Operation range
Cooling
°F (°C) 64 to 90 (18 to 32)
%RH 80 or less
Heating °F (°C) 60 to 88 (16 to 31)
Remote controller type Wireless (Wired [option])
NOTES:
•The protective function might work when using it outside the operation range.
•*Sound pressure level: –Measured values in manufacturer’s anechoic chamber. –Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
Page 55
- 49 -
MULTI TYPE
5 rooms type
3-4. Floor type
Model name AGU9RLF AGU12RLF AGU15 RLF
Power supply 208/230 V ~ 60 Hz
Available voltage range 187—264 V
Capacity Btu/h class 9,000 1 2,000 14,000
Input power W 16 20 23
Running current A 0.15 0.18 0.20
Fan
Airflow rate
Cooling
HIGH
CFM (m3/h)
312 (530) 353 (600 ) 383 (650)
MED 259 (440) 288 (490) 306 (520)
LOW 212 (360) 224 (380) 235 (400)
QUIET 159 (270) 159 (270) 159 (270)
Heating
HIGH 312 (530) 353 (600) 383 (650)
MED 270 (460) 300 (510) 318 (540)
LOW 224 (380) 241 (410) 253 (430)
QUIET 159 (270) 159 (270) 159 (270)
Typ e × Q'ty Cross flow fan × 2
Motor output W 16
Sound pressure level *
Cooling
HIGH
dB (A)
39 42 44
MED 34 36 38
LOW 28 30 31
QUIET 22 22 22
Heating
HIGH 39 42 44
MED 35 38 39
LOW 30 32 33
QUIET 22 22 22
Heat exchanger type
Dimensions (H × W × D) in (mm) 14-7/8 × 21-5/8 × 1-1/16 ( 378 × 550 × 26.6)
Fin pitch FPI 21
Rows × Stages 2 x 18
Pipe type Copper tube
Fin type Aluminium
Enclosure
Material Polystyrene
Color
White
(Approximate color of MUNSELL N9.25/)
Dimensions (H × W × D)
Net
in (mm)
23-5/8 × 29-1/8 × 7-7/8 (600 × 740 × 200)
Gross 27-9/16 × 32-5/16 × 12-3/16 (700 × 820 × 310)
Weight
Net
lb (kg)
31 (14)
Gross 37 (17)
Connection pipe
Size
Liquid
in (mm)
Ø1/4 (Ø 6.35)
Gas Ø3/8 (Ø 9.52) Ø1/ 2 (Ø 12.70)
Method Flare
Drain hose
Material PVC
Size in (mm) Ø 9/16 (I.D.), Ø 11/16 (O.D.) [Ø 13.8 (I.D.), Ø 16.7 (O.D.)]
Operation range
Cooling
°F (°C) 64 to 90 (18 to 32)
%RH 80 or less
Heating °F (°C) 60 to 86 (16 to 30)
Remote controller type Wireless (Wired [option])
NOTES:
• The protective function mi ght work when using it outside the operation range.
• *So und pressure level: – Measured values in manufacturer’s anechoic chamber. – Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
Page 56
- 50 -
MULTI TYPE
5 rooms type
4. Dimensions
4-1. Compact cassette type
Models: AUU7RLF, AUU9RLF, AUU12RLF, and AUU18RLF
(Drain hose)
20-7/8 (530): Hanging bolt position
4 (102)
5-5/16 (135)
9-13/16 (250)
27-9/16 (700)
27-9/16 (700)
2-15/16 (75)
1-3/16 (30)
1-3/16 (30)
10-5/16 (262)
21-1/4 (540): Hanging bolt position
22-7/16 (570): Indoor unit
22-13/16 to 26 (580 to 660)
: Ceiling openings
Cassette grille mounting state
Top view
5-14/16 to 7-7/8 (150 to 200)
Min. 17-11/16 (450)
Min. 17-11/16 (450)
Maintenance space
Side view
8-7/16 (215)
4-13/16 (123)
2-5/16 (58)
4-1/2 (114)
5-3/4 (146)
4-1/4
(108)
4 (102)
9-5/8 (245)
1-3/16 (30)
1-9/16 (40)
3-7/8 (99)
Drain port
Control box
Ceiling
Drain port
Be sure to leave maintenance space for future service at the designated position.
Bottom view
1-3/16 (30)
1-15/16 (49)
Side view
Unit: in. (mm)
Page 57
- 51 -
MULTI TYPE
5 rooms type
Installation space
3-way direction setting
NOTES:
• To set “3-direction”, optional Air outlet shutter plate (UTR-YDZB) must be installed, and the “outlet-direction” need to be switched to “3-way” by remote controller. *When installing the indoor unit, be careful about the maintenance space.
• The ceiling height cannot be set in the 3-way outlet mode. Therefore, ceiling height setting change by function setting 20 is prohibited. For details, refer to Chapter 13-5. "Contents of function
setting" on page 150.
Maximum height from floor to ceiling (Unit: mm)
Model name AUU7 AUU9 AUU12 AUU18
Standard mode
107
(2,700)
High Ceiling mode -
119
(3,000)
40 (1,000) or more
40 (1,000)
or more 95 (2,400) or more
11 (262) or more
Strong and durable ceiling
Obstruction
Floor
Unit: in (mm)
4 (100) or more
*
Unit: in (mm)
Page 58
- 52 -
MULTI TYPE
5 rooms type
4-2. Slim duct type
Models: ARU7RLF, ARU9RLF, and ARU12RLF
Rear view
View A
Top view
Side view
Front view
Bottom view
(Drain hose)
Drain port
2 (51)
22-5/8 (574)
6-17/8 (174)
2-13/16 (71)
6 (152)
3-15/16 (100) x 6 = 23-5/8 (600)
3-7/32 (82)
1-7/8 (48)
25-9/16 (650)
28-7/8 (734)
1-3/16 (30)
14-13/16 (377)
6-9/16 (167)
4-11/16 (119)
3-1/2 (89)
3-1/16 (78)
2-3/16 (55)
1-7/8 (47)
3/8 (10)
24-7/16 (620)
14-5/8 (371)
10-3/8 (264)
5-11/16 (144)
2-11/16 (69)
25-9/16 (650)
26-1/8 (664)
27-9/16 (700)
1-11/16 (43)
13/16 (20)
7-13/16 (198)
6-5/8 (168)
5-15/16 (151)
3-1/16 (78) 2-3/16 (55)
Unit: in (mm)
Page 59
- 53 -
MULTI TYPE
5 rooms type
Model: ARU18RLF
Rear view
View A
Top view
Side view
Front view
Bottom view
(Drain hose)
Drain port
2 (51)
30-1/2 (774)
6-7/8 (174)
2-13/16 (71)
6 (152)
3-7/16 (87)
2-3/16 (56)
33-7/16 (850)
36-3/4 (934)
3-15/16 (100) x 8 = 31-1/2 (800)
1-3/16 (30)
14-13/16 (377)
6-9/16 (167)
4-11/16 (119)
3-1/2 (89)
3-1/16 (78)
2-3/16 (55)
1-7/8 (47)
3/8 (10)
24-7/16 (620)
14-5/8 (371)
10-3/8 (264)
5-11/16 (144)
2-11/16 (69)
33-7/16 (850)
34 (864)
35-7/16 (900)
1-11/16 (43)
13/16 (20)
7-13/16 (198)
6-5/8 (168)
5-15/16 (151)
3-1/16 (78)
2-3/16 (55)
Unit: in (mm)
Page 60
- 54 -
MULTI TYPE
5 rooms type
Model: ARU24RLF
Rear view
View A
Top view
Side view
Front view
Bottom view
(Drain hose)
Drain port
38-3/8 (974)
2 (51)
6-7/8 (174)
2-13/16 (71)
6 (152)
44-5/8 (1,134)
2-3/16 (56)
3-7/16 (87)
3-15/16 (100) x 10 = 39-3/8 (1,000)
41-5/16 (1,050)
1-3/16 (30)
14-13/16 (377)
6-9/16 (167)
4-11/16 (119)
3-1/2 (89)
3-1/16 (78)
2-3/16 (55)
1-7/8 (47)
6/16 (10)
24-7/16 (620)
14-5/8 (371)
10-6/16 (264)
5-11/16 (144)
2-11/16 (69)
43-5/16 (1,100)
1-11/16 (43)
13/16 (20)
7-13/16 (198)
6-5/8 (168)
5-15/16 (151)
3-1/16 (78)
2-3/16 (55)
Unit: in (mm)
Page 61
- 55 -
MULTI TYPE
5 rooms type
Installation space
Left side
Strong and durable ceiling
Indoor unit
Right side
4 (100) or more
12 (300) or more
Service access Ceiling
99 (2,500) or more
(When no ceiling)
Floor
10 (240) or more
1 (20) or more
1 (20) or more
12 (300) or more
Unit: in (mm)
1 (10)
or less
1 (10)
or less
Left side
Strong and durable floor
Right side (PIPE side)
Grille
Inlet air
Strong and durable floor
6
(150)
or more
4 (100)
or more
12 (300)
or more
1 (20)
or more
1 (20)
or more
6 (150)
or more
Unit: in (mm)
Left side
Strong and durable floor
Right side (PIPE side)
Duct
Grille
Inlet air
Strong and durable floor
6
(150)
or more
4 (100)
or more
12 (300)
or more
1 (20)
or more
1 (20)
or more
6 (150)
or more
Unit: in (mm)
Page 62
- 56 -
MULTI TYPE
5 rooms type
Maintenance space
Provide a service access for inspection purposes as shown below. Do not place any wiring or illumination in the service space, as they will impede service.
Service access
Unit
Control box
or more
Service space
12 (300)
12 (300)
or more
4 (100)
or more
Unit: in (mm)
Page 63
- 57 -
MULTI TYPE
5 rooms type
4-3. Wall mounted type
Models: ASU7RLF1, ASU9RLF1, ASU12RLF1, and ASU15RLF1
33-1/16 (840) 8 (203)
10-9/16 (268)
(33-1/16 (840))
1-3/4 (45)
2-1/16 (52)
14-5/16 (364)
Ø2-9/16 (Ø65) for pipe inlet
12-5/8 (321)
3-7/16 (88)
Ø2-9/16 (Ø65) for pipe inlet
12-3/8 (315)
4-9/16 (116)
1-5/8(41)
10-9/16 (268)
13-7/8 (353)
3-1/16 (78)
11/16 (18)7/16 (11)
1-5/8 (41)
Unit: in (mm)
Page 64
- 58 -
MULTI TYPE
5 rooms type
Installation space
71 (1,800) or more
60 (1,500) or more
1 (25) or more
Outline of unit
3 (70) or more
3 (52) or more
2 (45) or more
3 (63) or more
6 (130) or more
Unit: in (mm)
Page 65
- 59 -
MULTI TYPE
5 rooms type
Models: ASU18RLF and ASU24RLF
39-5/16 (998)
17-1/4 (438)
15-5/8 (397)
12-5/8 (320): Unit size
2 (51)
2 (51)
13/16 (20)
2-5/8 (67)1-1/8 (28)
35-9/16 (903)
Ø 3-1/8 (80) hole
39-5/16 (998): Unit size
Outline of unit
Piping inlet
Unit center
9 (228)
12-5/8 (320)
20-1/2 (520)
20-1/2 (520)
23-1/4 (590)
28-3/8 (721)
Ø 3-1/8 (80) hole
Piping inlet
11/16 (17)
1 (25)
ø1-1/4 (32)
ø5/8 (16)
ø1/8 (12)
7/16 (11)
Unit: in (mm)
Page 66
- 60 -
MULTI TYPE
5 rooms type
Installation space
3 (63) or more
4 (80) or more
3 (53) or more
3 (52) or more
4 (80) or more
Outline of unit
5 (120) or more
60 (1,500) or more
71 (1,800) or more
Unit: in (mm)
Page 67
- 61 -
MULTI TYPE
5 rooms type
4-4. Floor type
Models: AGU9RLF, AGU12RLF, and AGU15RLF
Installation space
23-5/8 (600)
7-7/8 (200)
Side view
Front view
29-1/8 (740)
Unit: in (mm)
4 (80)
or more
2 (50)
or more
from the floor
4 (80) or more
4 (100) or more
4 (100) or below
Unit: in (mm)
Page 68
- 62 -
MULTI TYPE
5 rooms type
5. Wiring diagrams
5-1. Compact cassette type
Models: AUU7RLF, AUU9RLF, AUU12RLF, and AUU18RLF
Page 69
- 63 -
MULTI TYPE
5 rooms type
5-2. Slim duct type
Models: ARU7RLF, ARU9RLF, ARU12RLF, ARU18RLF, and
ARU24RLF
Page 70
- 64 -
MULTI TYPE
5 rooms type
5-3. Wall mounted type
Models: ASU7RLF1, ASU9RLF1, ASU12RLF1, and ASU15RLF1
Page 71
- 65 -
MULTI TYPE
5 rooms type
Models: ASU18RLF and ASU24RLF
Page 72
- 66 -
MULTI TYPE
5 rooms type
5-4. Floor type
Models: AGU9RLF, AGU12RLF, and AGU15RLF
Page 73
- 67 -
MULTI TYPE
5 rooms type
6. Air velocity and temperature distributions
6-1. Compact cassette type
Models: AUU7RLF and AUU9RLF
• Air velocity distribution
Measuring conditions
Fan speed Operation mode
HIGH FAN
Top vi e w Vertical airflow direction louver: Up
Side view Vertical airflow direction louver: Up
7 (2.0)
7 (2.0)
7 (2.0)
7 (2.0)
3 (1.0)
3 (1.0)
3 (1.0)
3 (1.0)
2 (0.5)
2 (0.5)
2 (0.5)
2 (0.5)
1 (0.25)
1 (0.25)
1 (0.25)
1 (0.25)
Unit: ft/s (m/s)
(m)(ft)
00
3
3
7
7
10
10
13
13
1
1
2
2
3
3
4
4
(m) (ft)
0 0
11 33771010 1313
2233 44
7 (2.0)
3 (1.0)
2 (0.5) 2 (0.5)
1 (0.25) 1 (0.25)
Unit: ft/s (m /s)
(m)(ft)
0
0
3
7
9
1
2
2.7
(m)
(ft)
0 0
11 33771010 1313
2233 44
Page 74
- 68 -
MULTI TYPE
5 rooms type
• Air velocity distribution
• Air temperature distribution
Measuring conditions NOTE: Reference data
Fan speed Operation mode Outlet directions
HIGH HEAT 4-way air outlet
Side view Vertical airflow direction louver: Down
Side view Vertical airflow direction louver: Down
7 (2.0) 7 (2.0)
5 (1.5) 5 (1.5)
3 (1.0) 3 (1.0)
2 (0.5) 2 (0.5)
1 (0.25) 1 (0.25)
Unit: ft/s (m /s)
(m)(ft)
0
0
3
7
9 8
1
2
2.7
2.5
(m)
(ft)
0 0
11 33771010 1313
2233 44
86
(3 0) 8 6 (3 0)
82
(28)
82
(28)
79
(26)
79 (26)
75 (24)
75
(24)
72 (22) 72 (22)
Unit: °F (°C)
(m)(ft)
0
0
3
7
9 8
1
2
2.7
2.5
(m) (ft)
0 0
11 33771010 1313
2233 44
Page 75
- 69 -
MULTI TYPE
5 rooms type
Model: AUU12RLF
• Air velocity distribution
Measuring conditions
Fan speed Operation mode
HIGH FAN
Top vi e w Vertical airflow direction louver: Up
Side view Vertical airflow direction louver: Up
7 (2.0)
7 (2.0)
7 (2.0)
7 (2.0)
3 (1.0)
3 (1.0)
3 (1.0)
3 (1.0)
2 (0.5)
2 (0.5)
2 (0.5)
2 (0.5)
1 (0.25)
1 (0.25)
1 (0.25)
1 (0.25)
Unit: ft/s (m/s)
4
3
2
1
0
1
2
3
4
43
210
1
2
34
(m)
(m)
0
3
7
(ft)
3
7
10
13
10
13
13
10
7
3
0
3
7
10
13
(ft)
7 (2.0)
3 (1.0)
2 (0.5)
2 (0.5)
1 (0.25)
1 (0.25)
43
2
1
0
1
2
34
(m)
0
1
2
2.7
(m)
Unit: ft/s (m/s)
0
3
7
9
(ft)
13
10
7
3
0
3
7
10
13
(ft)
Page 76
- 70 -
MULTI TYPE
5 rooms type
• Air velocity distribution
• Air temperature distribution
Measuring conditions NOTE: Reference data
Fan speed Operation mode Outlet directions
HIGH HEAT 4-way air outlet
Side view Vertical airflow direction louver: Down
Side view Vertical airflow direction louver: Down
5 (1.5) 5 (1.5)
3 (1.0) 3 (1.0)
2 (0.5) 2 (0.5)
1 (0.25) 1 (0.25)
43
2
1
0
1
2
34
(m)
0
1
2
2.7
(m)
Unit: ft/s (m/s)
0
3
7
9
13
10
7
3
0
3
7
10
13
(ft)
2.5
8
86 (30) 86 (30)
82 (28) 82 (28)
79 (26) 79 (26)
75 (24) 75 (24)
72 (22) 72 (22)
43
2
1
0
1
2
34
(m)
0
1
2
2.7
(m)
Unit: ft/s (m/s)
0
3
7
9
13
10
7
3
0
3
7
10
13
(ft)
2.5
8
Page 77
- 71 -
MULTI TYPE
5 rooms type
Model: AUU18RLF
• Air velocity distribution
Measuring conditions
Fan speed Operation mode
HIGH FAN
Top vi e w Vertical airflow direction louver: Up
Side view Vertical airflow direction louver: Up
7 (2.0)
7 (2.0)
7 (2.0)
7 (2.0)
3 (1.0)
3 (1.0)
3 (1.0)
3 (1.0)
2 (0.5)
2 (0.5)
2 (0.5)
2 (0.5)
1 (0.25)
1 (0.25)
1 (0.25)
1 (0.25)
Unit: ft/s (m/s)
4
3
2
1
0
1
2
3
4
43
210
1
2
34
(m)
(m)
0
3
7
(ft)
3
7
10
13
10
13
13
10
7
3
0
3
7
10
13
(ft)
7 (2.0)
3 (1.0)
2 (0.5)
2 (0.5)
1 (0.25)
1 (0.25)
43
2
1
0
1
2
34
(m)
0
1
2
2.7
(m)
Unit: ft/s (m/s)
0
3
7
9
(ft)
13
10
7
3
0
3
7
10
13
(ft)
Page 78
- 72 -
MULTI TYPE
5 rooms type
• Air velocity distribution
• Air temperature distribution
Measuring conditions NOTE: Reference data
Fan speed Operation mode Outlet directions
HIGH HEAT 4-way air outlet
Side view Vertical airflow direction louver: Down
Side view Vertical airflow direction louver: Down
5 (1.5) 5 (1.5)
3 (1.0) 3 (1.0)
2 (0.5) 2 (0.5)
1 (0.25) 1 (0.25)
7 (2.0) 7 (2.0)
43
2
1
0
1
2
34
(m)
0
1
2
2.7
(m)
Unit: ft/s (m/s)
0
3
7
9
13
10
7
3
0
3
7
10
13
(ft)
2.5
8
86 (30) 86 (30)
82 (28) 82 (28)
79 (26) 79 (26)
75 (24) 75 (24)
72 (22) 72 (22)
43
2
1
0
1
2
34
(m
0
1
2
2.7
(m)
Unit: ft/s (m/s)
0
3
7
9
13
10
7
3
0
3
7
10
13
(ft)
2.5
8
Page 79
- 73 -
MULTI TYPE
5 rooms type
6-2. Slim duct type
Model: ARU7RLF
NOTE: This data is measured after installing optional Auto louver grille kit.
• Air velocity distribution
Measuring conditions
Fan speed Operation mode
HIGH FAN
Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center
Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right
Side view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center
2
1
0
1
2
(m)
Unit: ft/s (m/s)
7
3
0
3
7
(ft)
7 (2)
3 (1)
2 (0.5)
(m)
0
12 3
456
7
(ft)
7
20
89
10
0
3
10
13 16
23 26 29
32
2
1
0
1
2
(m)
(m)
Unit: ft/s (m/s)
0
12 3
456
7
(ft)
7
20
7
3
0
3
7
(ft)
7 (2)
3 (1)
2 (0.5)
5
4
3
16
13
10
89
10
0
3
10
13 16
23 26 29
32
5
4
3
16
13
10
3 (1)
2 (0.5)
7 (2)
2
1
0
(m)
Unit: ft/s (m/s)
7
3
0
(ft)
7 (2)
3 (1)
2 (0.5)
(m)
0
12 3
456
7
(ft)
7
20
89
10
0
3
10
13 16
23 26 29
32
2.58
310
Page 80
- 74 -
MULTI TYPE
5 rooms type
• Air velocity distribution
• Air temperature distribution
Measuring conditions
Fan speed Operation mode
HIGH HEAT
Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center
Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center
2
1
0
(m)
Unit: ft/s (m/s)
7
3
0
(ft)
7 (2)
3 (1)
2 (0.5)
(m)
0
12 3
456
7
(ft)
7
20
89
10
0
3
10
13 16
23 26 29
32
2.58
310
2
1
0
(m)
Unit: °F (°C)
7
3
0
(ft)
86 (30)
(m)
0
12 3
456
7
(ft)
7
20
89
10
0
3
10
13 16
23 26 29
32
2.58
310
82 (28)
79 (26)
75 (24)
72 (22)
Page 81
- 75 -
MULTI TYPE
5 rooms type
Model: ARU9RLF
NOTE: This data is measured after installing optional Auto louver grille kit.
• Air velocity distribution
Measuring conditions
Fan speed Operation mode
HIGH FAN
Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center
Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right
Side view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center
2
1
0
1
2
(m)
Unit: f t/s (m/s)
7
3
0
3
7
(ft)
7 (2)
3 (1)
2 (0.5)
(m)
0
12 3
456
7
(ft)
7
20
89
10
0
3
10
13 16
23 26 29
32
2
1
0
1
2
(m)
(m)
Unit: f t/s (m/s)
0
12 3
456
7
(ft)
7
20
7
3
0
3
7
(ft)
7 (2)
3 (1)
2 (0.5)
5
4
3
16
13
10
89
10
0
3
10
13 16
23 26 29
32
5
4
3
16
13
10
3 (1)
2 (0.5)
7 (2)
2
1
0
(m)
Unit: f t/s (m/s)
7
3
0
(ft)
7 (2)
3 (1)
2 (0.5)
(m)
0
12 3
456
7
(ft)
7
20
89
10
0
3
10
13 16
23 26 29
32
2.5
8
310
Page 82
- 76 -
MULTI TYPE
5 rooms type
• Air velocity distribution
• Air temperature distribution
Measuring conditions
Fan speed Operation mode
HIGH HEAT
Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center
Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center
2
1
0
(m)
Unit: f t/s (m/s)
7
3
0
(ft)
7 (2)
3 (1)
2 (0.5)
(m)
0
12 3
456
7
(ft)
7
20
89
10
0
3
10
13 16
23 26 29
32
2.5
8
3
10
2
1
0
(m)
Unit: °F (°C)
7
3
0
(ft)
86 (30)
(m)
0
12 3
456
7
(ft)
7
20
89
10
0
3
10
13 16
23 26 29
32
2.58
310
82 (28)
79 (26)
75 (24)
72 (22)
Page 83
- 77 -
MULTI TYPE
5 rooms type
Model: ARU12RLF
NOTE: This data is measured after installing optional Auto louver grille kit.
• Air velocity distribution
Measuring conditions
Fan speed Operation mode
HIGH FAN
Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center
Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right
Side view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center
2
1
0
1
2
(m)
Unit: ft/s (m/s)
7
3
0
3
7
(ft)
7 (2)
3 (1)
2 (0.5)
(m)
0
12 3
456
7
(ft)
7
20
89
10
0
3
10
13 16
23 26 29
32
2
1
0
1
2
(m)
(m)
Unit: f t/s (m/s)
0
12 3
456
7
(ft)
7
20
7
3
0
3
7
(ft)
7 (2)
3 (1)
2 (0.5)
5
4
3
16
13
10
89
10
0
3
10
13 16
23 26 29
32
5
4
3
16
13
10
3 (1)
2 (0.5)
7 (2)
2
1
0
(m)
Unit: f t/s (m/s)
7
3
0
(ft)
7 (2)
3 (1)
2 (0.5)
(m)
0
12 3
456
7
(ft)
7
20
89
10
0
3
10
13 16
23 26 29
32
2.58
3
10
Page 84
- 78 -
MULTI TYPE
5 rooms type
• Air velocity distribution
• Air temperature distribution
Measuring conditions
Fan speed Operation mode
HIGH HEAT
Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center
Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center
2
1
0
(m)
Unit: f t/s (m/s)
7
3
0
(ft)
7 (2)
3 (1)
2 (0.5)
(m)
0
12 3
456
7
(ft)
7
20
89
10
0
3
10
13 16
23 26 29
32
2.5
8
310
2
1
0
(m)
Unit: °F (°C)
7
3
0
(ft)
86 (30)
(m)
0
12 3
456
7
(ft)
7
20
89
10
0
3
10
13 16
23 26 29
32
2.58
310
82 (28)
79 (26)
75 (24)
72 (22)
Page 85
- 79 -
MULTI TYPE
5 rooms type
Model: ARU18RLF
NOTE: This data is measured after installing optional Auto louver grille kit.
• Air velocity distribution
Measuring conditions
Fan speed Operation mode
HIGH FAN
Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center
Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right
Side view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center
2
1
0
1
2
(m)
Unit: f t/s (m/s)
7
3
0
3
7
(ft)
7 (2)
3 (1)
2 (0.5)
(m)
0
12 3
456
7
(ft)
7
20
89
10
0
3
10
13 16
23 26 29
32
2
1
0
1
2
(m)
(m)
Unit: f t/s (m/s)
0
12 3
456
7
(ft)
7
20
7
3
0
3
7
(ft)
7 (2)
3 (1)
2 (0.5)
5
4
3
16
13
10
89
10
0
3
10
13 16
23 26 29
32
5
4
3
16
13
10
3 (1)
2 (0.5)
7 (2)
2
1
0
(m)
Unit: f t/s (m/s)
7
3
0
(ft)
7 (2)
3 (1)
2 (0.5)
(m)
0
12 3
456
7
(ft)
7
20
89
10
0
3
10
13 16
23 26 29
32
2.5
8
3
10
Page 86
- 80 -
MULTI TYPE
5 rooms type
• Air velocity distribution
• Air temperature distribution
Measuring conditions
Fan speed Operation mode
HIGH HEAT
Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center
Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center
2
1
0
(m)
Unit: f t/s (m/s)
7
3
0
(ft)
7 (2)
3 (1)
2 (0.5)
(m)
0
12 3
456
7
(ft)
7
20
89
10
0
3
10
13 16
23 26 29
32
2.58
3
10
2
1
0
(m)
Unit: °F (°C)
7
3
0
(ft)
86 (30)
(m)
0
12 3
456
7
(ft)
7
20
89
10
0
3
10
13 16
23 26 29
32
2.58
310
82 (28)
79 (26)
75 (24)
72 (22)
Page 87
- 81 -
MULTI TYPE
5 rooms type
Model: ARU24RLF
NOTE: This data is measured after installing optional Auto louver grille kit.
• Air velocity distribution
Measuring conditions
Fan speed Operation mode
HIGH FAN
Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center
Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right
Side view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center
2
1
0
1
2
(m)
Unit: f t/s (m/s)
7
3
0
3
7
(ft)
7 (2)
3 (1)
2 (0.5)
(m)
0
12 3
456
7
(ft)
7
20
89
10
0
3
10
13 16
23 26 29
32
2
1
0
1
2
(m)
(m)
Unit: f t/s (m/s)
0
12 3
456
7
(ft)
7
20
7
3
0
3
7
(ft)
7 (2)
3 (1)
2 (0.5)
5
4
3
16
13
10
89
10
0
3
10
13 16
23 26 29
32
5
4
3
16
13
10
3 (1)
2 (0.5)
7 (2)
2
1
0
(m)
Unit: f t/s (m/s)
7
3
0
(ft)
7 (2)
3 (1)
2 (0.5)
(m)
0
12 3
456
7
(ft)
7
20
89
10
0
3
10
13 16
23 26 29
32
2.5
8
3
10
Page 88
- 82 -
MULTI TYPE
5 rooms type
• Air velocity distribution
• Air temperature distribution
Measuring conditions
Fan speed Operation mode
HIGH HEAT
Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center
Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center
2
1
0
(m)
Unit: f t/s (m/s)
7
3
0
(ft)
7 (2)
3 (1)
2 (0.5)
(m)
0
12 3
456
7
(ft)
7
20
89
10
0
3
10
13 16
23 26 29
32
2.58
310
2
1
0
(m)
Unit: °F (°C)
7
3
0
(ft)
86 (30)
(m)
0
12 3
456
7
(ft)
7
20
89
10
0
3
10
13 16
23 26 29
32
2.5
8
3
10
82 (28)
79 (26)
75 (24)
72 (22)
Page 89
- 83 -
MULTI TYPE
5 rooms type
6-3. Wall mounted type
Model: ASU7RLF1
Measuring conditions
Fan speed Operation mode
HIGH FAN
Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center
Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right
Side view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center
Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center
7 (2.0)
3 (1.0) 2 (0.5)
2
1
0
1
2
Unit: ft/s (m/s)
(m)
(m)
01234567
8
7
3
0
3
7
(ft)
(ft)
0 3 7 10 13 16 20 23
26
9
29
7 (2.0)
7 (2.0)
2 (0.5)
2 (0.5)
3 (1.0)
3 (1.0)
10
7
3
0
3
7
10
(ft)
(ft)
0 3 7 10 13 16 20 23
26
3
2
1
0
1
2
3
Unit: ft/s (m/s)
(m)
(m)
01234567
8
9
29
7 (2.0)
2 (0.5)
3 (1.0)
3
2
1
0
Unit: ft/s (m/s)
(m)
(m)
012345678
10
7
3
0
(ft)
(ft)
0 3 7 10 13 16 20 23 26
9
29
2 (0.5)
7 (2.0)
3 (1.0)
3
2
1
0
Unit: ft/s (m/s)
(m)
(m)
012345678
10
7
3
0
(ft)
(ft)
0 3 7 10 13 16 20 23 26
9
29
Page 90
- 84 -
MULTI TYPE
5 rooms type
Model: ASU9RLF1
Measuring conditions
Fan speed Operation mode
HIGH FAN
Top vi e w Vertical airflow direction louver: Up Horizontal airflow direction louver: Center
Top vi e w Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right
Side view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center
Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center
7 (2.0)
3 (1.0) 2 (0.5)
2
1
0
1
2
Unit: ft/s (m/s)
(m)
(m)
01234567
8
7
3
0
3
7
(ft)
(ft)
0 3 7 10 13 16 20 23
26
9
29
7 (2.0)
7 (2.0)
2 (0.5)
2 (0.5)
3 (1.0)
3 (1.0)
10
7
3
0
3
7
10
(ft)
(ft)
0 3 7 10 13 16 20 23
26
3
2
1
0
1
2
3
Unit: ft/s (m/s)
(m)
(m)
01234567
8
9
29
3 (1.0) 2 (0.5)
7 (2.0)
3
2
1
0
Unit: ft/s (m/s)
(m)
(m)
012345678
10
7
3
0
(ft)
(ft)
0 3 7 10 13 16 20 23 26
9
29
3 (1.0)
2 (0.5)
7 (2.0)
3
2
1
0
Unit: ft/s (m/s)
(m)
(m)
012345678
10
7
3
0
(ft)
(ft)
0 3 7 10 13 16 20 23 26
9
29
Page 91
- 85 -
MULTI TYPE
5 rooms type
Model: ASU12RLF1
Measuring conditions
Fan speed Operation mode
HIGH FAN
Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center
Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right
Side view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center
Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center
3 (1.0) 2 (0.5)
7 (2.0)
2
1
0
1
2
Unit: ft/s (m/s)
(m)
(m)
01234567
8
7
3
0
3
7
(ft)
(ft)
0 3 7 10 13 16 20 23
26
9
29
7 (2.0)
7 (2.0)
2 (0.5)
2 (0.5)
3 (1.0)
3 (1.0)
10
7
3
0
3
7
10
(ft)
(ft)
0 3 7 10 13 16 20 23
26
3
2
1
0
1
2
3
Unit: ft/s (m/s)
(m)
(m)
01234567
8
9
29
3 (1.0)
2 (0.5)
7 (2.0)
3
2
1
0
Unit: ft/s (m/s)
(m)
(m)
012345678
10
7
3
0
(ft)
(ft)
0 3 7 10 13 16 20 23 26
9
29
7 (2.0)
3 (1.0)
2 (0.5)
3
2
1
0
Unit: ft/s (m/s)
(m)
(m)
012345678
10
7
3
0
(ft)
(ft)
0 3 7 10 13 16 20 23 26
9
29
Page 92
- 86 -
MULTI TYPE
5 rooms type
Model: ASU15RLF1
Measuring conditions
Fan speed Operation mode
HIGH FAN
Top vi e w Vertical airflow direction louver: Up Horizontal airflow direction louver: Center
Top vi e w Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right
Side view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center
Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center
7 (2.0)
3 (1.0)
2 (0.5)
2
1
0
1
2
Unit: ft/s (m/s)
(m)
(m)
0123456
78
7
3
0
3
7
(ft)
(ft)
03710131620
23
26
9
29
3 (1.0)
3 (1.0)
2 (0.5)
2 (0.5)
7 (2.0)
7 (2.0)
10
7
3
0
3
7
10
(ft)
(ft)
03
710 13162023
26
3
2
1
0
1
2
3
Unit: f t/s (m/s)(m)
(m)
01
23 4567
8
9
29
7 (2.0)
3 (1.0)
2 (0.5)
3
2
1
0
Unit: f t/s (m/s)
(m)
(m)
012345678
10
7
3
0
(ft)
(ft)
037101316202326
9
29
7 (2.0)
3 (1.0)
2 (0.5)
3
2
1
0
Unit: ft/s (m/s)
(m)
(m)
012 34 5 67 8
10
7
3
0
(ft)
(ft)
0 3 7 10 13 16 20 23 26
9
29
Page 93
- 87 -
MULTI TYPE
5 rooms type
Model: ASU18RLF
Measuring conditions
Fan speed Operation mode
HIGH FAN
Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center
Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right
Side view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center
Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center
Unit: ft/s (m/s)
(m)(ft)
0
0
3
3
7
7
1
1
2
2
(m) (ft)
0 0
1 3 7 10 13 16 20 23 26
2345678
7 (2.0)
3 (1.0)
2 (0.5)
7 (2.0)
7 (2.0)
3 (1.0)
3 (1.0)
2 (0.5)
2 (0.5)
Unit: ft/s (m/s)
(m) (ft)
0 0
1 3 7 10 13 16 2 0 23 26
2345678
(m)(ft)
00
3
3
7
7
1
1
2
2
3310
10
3
2
1
0
Unit: ft/s (m/s)
(m)
(m)
012345678
10
7
3
0
(ft)
(ft)
0 3 7 101316202326
7 (2.0)
3 (1.0)
2 (0.5)
7 (2.0)
3 (1.0)
2 (0.5)
3
2
1
0
Unit: ft/s (m/s)
(m)
(m)
012345678
10
7
3
0
(ft)
(ft)
0 3 7 101316202326
Page 94
- 88 -
MULTI TYPE
5 rooms type
Model: ASU24RLF
Measuring conditions
Fan speed Operation mode
HIGH FAN
Top vi e w Vertical airflow direction louver: Up Horizontal airflow direction louver: Center
Top vi e w Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right
Side view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center
7 (2.0)
3 (1.0)
2 (0.5)
(m)(ft)
0
0
3
3
7
7
1
1
2
2
(m) (ft)
0
0
1
3 7 10 13 16 20 23 26
2345678
Unit: ft/s (m/s)
7 (2.0)
7 (2.0)
3 (1.0)
3 (1.0)
2 (0.5)
2 (0.5)
Unit: ft/s (m/s)
(m) (ft)
0
0
1
3 7 10 13 16 20 23 26
2345678
(m)(ft)
00
3
3
7
7
1
1
2
2
3310
10
7 (2.0)
3 (1.0)
2 (0.5)
Unit: ft/s (m/s)
(m) (ft)
0
0
1
3 7 10 13 16 20 23 26
2345678
(m)(ft)
0
0
3
7
10
1
2
3
Page 95
- 89 -
MULTI TYPE
5 rooms type
Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center
7 (2.0)
3 (1.0)
2 (0.5)
Unit: ft/s (m/s)
(m) (ft)
0
0
1
3 7 10 13 16 20 23 26
2345678
(m)(ft)
0
0
3
7
10
1
2
3
Page 96
- 90 -
MULTI TYPE
5 rooms type
6-4. Floor type
Models: AGU9RLF, AGU12RLF, and AGU15RLF
Measuring conditions
Fan speed Operation mode Fan select
HIGH FAN Upper and lower
Top vi e w Vertical airflow direction louver: Up Horizontal airflow direction louver: Center
Top vi e w Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right
Side view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center
Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center
3(1.0)
2(0.5)
UPPER LOWER
2
1
0
1
2
(m)
7
3
0
3
7
(ft)
(m)
1
2
3
(ft)
3
7
10
4
13
Unit: ft/s (m/s)
3(1.0)
2(0.5)
3(1.0)
2(0.5)
Unit: ft/s (m/s)
2
1
0
1
2
(m)
7
3
0
3
7
(ft)
(m)
1
2
3
(ft)
3
7
10
4
13
3(1.0)
2(0.5)
3
2
1
0
Unit: ft/s (m/s)
(m)
10
7
3
0
(ft)
(m)
1
2
3
(ft)
3
7
10
4
13
3(1.0)
2(0.5)
3
2
1
0
(m)
10
7
3
0
(ft)
(m)
1
2
3
(ft)
3
7
10
4
13
Unit: ft/s (m/s)
Page 97
- 91 -
MULTI TYPE
5 rooms type
7. Fan performance
7-1. Slim duct type
Model: ARU7RLF
Hi (SP mode 09)
Hi (Normal SP)
Hi (SP mode 00)
SP mode 09 upper limit
SP mode 09 lower limit
Quiet (SP mode 09)
Normal SP upper limit
Quiet (Normal SP)
SP mode 00 upper limit
Quiet (SP mode 00)
0.44 (110)
0.40 (100)
0.36 (90)
0.32 (80)
0.28 (70)
0.24 (60)
0.20 (50)
0.16 (40)
0.12 (30)
0.08 (20)
0.04 (10)
0 (0)
177
235
294
353 412
(300)
(400)
(500)
(600) (700)
External static pressure (inWG [Pa])
Airflow (CFM [m3/h])
0.44 (110)
0.40 (100)
0.36 (90)
0.32 (80)
0.28 (70)
0.24 (60)
0.20 (50)
0.16 (40)
0.12 (30)
0.08 (20)
0.04 (10)
0 (0)
177
235
294
353 412
(300)
(400)
(500)
(600) (700)
External static pressure (inWG [Pa])
Airflow (CFM [m3/h])
Hi (SP mode 09)
Hi (SP mode 08)
Hi (SP mode 07)
Hi (SP mode 06)
Hi (SP mode 05)
Hi (SP mode 04)
Hi (SP mode 03)
Hi (Normal SP)
Hi (SP mode 02)
Hi (SP mode 01)
Hi (SP mode 00)
*1
Available airflow rate range (High level)
*1: Available airflow rate range when Auto louver grille (option) is installed.
Fan speed : HIGH Vertical airflow direction louver : Up
Page 98
- 92 -
MULTI TYPE
5 rooms type
Characteristics of air volume and capacity
Cooling
Heating
0
20
40
60
80
100
120
235
294
353
471
(400)
(500)
(600)
(800)
412
(700)
Capacitty
Capacity (%)
Airflow (CFM [m3/h])
0
20
40
60
80
100
120
235
294
353
471
(400)
(500)
(600)
(800)
412
(700)
Capacitty
Capacity (%)
Airflow (CFM [m3/h])
Page 99
- 93 -
MULTI TYPE
5 rooms type
Model: ARU9RLF
Hi (SP mode 09)
Hi (Normal SP)
SP mode 09 upper limit
SP mode 09 lower limit
Quiet (SP mode 09)
Normal SP upper limit
Quiet (Normal SP)
SP mode 00 upper limit
Quiet (SP mode 00)
0.44 (110)
0.40 (100)
0.36 (90)
0.32 (80)
0.28 (70)
0.24 (60)
0.20 (50)
0.16 (40)
0.12 (30)
0.08 (20)
0.04 (10)
0 (0)
177
235
294
353
412
(300)
(400)
(500)
(600)
(700)
External static pressure (inWG [Pa])
Airflow (CFM [m3/h])
471
(800)
*1
0.44 (110)
0.40 (100)
0.36 (90)
0.32 (80)
0.28 (70)
0.24 (60)
0.20 (50)
0.16 (40)
0.12 (30)
0.08 (20)
0.04 (10)
0 (0)
177
(300)
External static pressure (inWG [Pa])
Airflow (CFM [m3/h])
Hi (SP mode 09)
Hi (SP mode 08)
Hi (SP mode 07)
Hi (SP mode 06)
Hi (SP mode 05)
Hi (SP mode 04)
Hi (SP mode 03)
Hi (Normal SP)
Hi (SP mode 02)
Hi (SP mode 01)
Hi (SP mode 00)
Available airflow rate range (High level)
*1
235
294
353
471
(400)
(500)
(600)
(800)
412
(700)
*1: Available airflow rate range when Auto louver grille (option) is installed.
Fan speed : HIGH Vertical airflow direction louver : Up
Page 100
- 94 -
MULTI TYPE
5 rooms type
Characteristics of air volume and capacity
Cooling
Heating
0
20
40
60
80
100
120
235
294
353
471
(400)
(500)
(600)
(800)
412
(700)
Capacitty
Capacity (%)
Airflow (CFM [m3/h])
0
20
40
60
80
100
120
235
294
353
471
(400)
(500)
(600)
(800)
412
(700)
Capacitty
Capacity (%)
Airflow (CFM [m3/h])
Loading...