Fujitsu AR*G36LMLA, AU*G54LRLA, ARTG36LHTB, AU*G45LRLA, AR*G45LMLA Service Instruction

...
Models Indoor unit
Single type
Outdoor unit
AU*G36LRLA AU*G45LRLA AU*G54LRLA
AR*G36LMLA ARTG36LHTB AR*G45LMLA AR*G45LHTA ARTG45LHTB AR*G54LHTA ARTG54LHTB ARTG60LHTA
AB*G36LRTA AB*G45LRTA AB*G54LRTA
SERVICE INSTRUCTION
R410A
3 PHASE TYPE ROOM AIR CONDITIONER
Single / Simultaneous operation multi type
Simultaneous operation multi type
AU*G18LVLB AU*G22LVLA AU*G24LVLA
AR*G18LLLA AR*G22LMLA AR*G24LMLA
AB*G18LVTB AB*G22LVTA AB*G24LVTA
CONTENTS
1. DESCRIPTION OF EACH CONTROL OPERATION
1-1 COOLING OPERATION............................................................................................ 01-01
1-2 HEATING OPERATION............................................................................................ 01-02
1-3 DRY OPERATION..................................................................................................... 01-03
1-4 AUTO CHANGEOVER OPERATION........................................................................ 01-04
1-5 INDOOR FAN CONTROL.......................................................................................... 01-06
1-6 OUTDOOR FAN CONTROL...................................................................................... 01-10
1-7 LOUVER CONTROL.................................................................................................. 01-11
1-8 COMPRESSOR CONTROL....................................................................................... 01-17
1-9 TIMER OPERATION CONTROL............................................................................... 01-18
1-10 ELECTRONIC EXPANSION VALVE CONTROL.................................................... 01-22
1-11 TEST OPERATION CONTROL............................................................................... 01-22
1-12 PREVENT TO RESTART FOR 3 MINUTES............................................................ 01-22
1-13 4-WAY VALVE EXTENSION SELECT.................................................................... 01-23
1-14 AUTO RESTART..................................................................................................... 01-23
1-15 MANUAL AUTO OPERATION................................................................................ 01-23
1-16 PUMP DOWN........................................................................................................... 01-24
1-17 COMPRESSOR PREHEATING............................................................................... 01-25
1-18 DEFROST OPERATION CONTROL....................................................................... 01-25
1-19 OFF DEFROST OPERATION CONTROL............................................................... 01-27
1-20 ECONOMY OPERATION........................................................................................ 01-28
1-21 10°C HEAT OPERATION........................................................................................ 01-28
1-22 VARIOUS PROTECTIONS...................................................................................... 01-28
1-23 FORCED COOLING OPERATION.......................................................................... 01-31
1-24 COMPRESSOR STOP OPERATION...................................................................... 01-31
1-25 FRESH AIR CONTROL........................................................................................... 01-31
1-26 EXTERNAL ELECTRICAL HEATER CONTROL.................................................... 01-31
1-27 DRAIN PUMP OPERATION..................................................................................... 01-32
1-28 LOW NOISE OPERATION....................................................................................... 01-33
1-29 PEAK CUT OPERATION......................................................................................... 01-33
1-31 DEMAND RESPONSE OPERATION....................................................................... 01-39
1-30 DESCRIPTION OF DISPLAY UNIT......................................................................... 01-34
1-9-1 WIRELESS REMOTE CONTROLLER................................................................
01-18
1-30-1 LAYOUT OF DISPLAY UNIT............................................................................
01-34
1-30-2 DISPLAY MODE...............................................................................................
01-35
1-30-3 ERROR HISTORY MODE.................................................................................
01-38
1-30-4 ERROR CHECK MODE....................................................................................
01-39
1-9-2 WIRED REMOTE CONTROLLER.......................................................................
01-20
2-1-1 INDOOR UNIT AND WIRED REMOTE CONTROLLER DISPLAY.....................
2-1 ERROR DISPLAY......................................................................................................
2. TROUBLE SHOOTING
2-2 TROUBLE SHOOTING WITH ERROR CODE..........................................................
2-3 TROUBLE SHOOTING WITH NO ERROR CODE....................................................
2-4 SERVICE PARTS INFORMATION............................................................................
02-01 02-01
2-1-2 WIRED REMOTE CONTROLLER DISPLAY......................................................
02-02
02-34
02-03
02-39
3. DISASSEMBLY PROCESS
1 . DESCRIPTION OF EACH CONTROL OPERATION
AIR CONDITIONER
3 phase type
Single / Simultaneous operation multi type
1-1. COOLING OPERATION
1-1-1 COOLING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor. The maximum frequency is limited in the range shown in Figure 1 based on the fan speed mode and the outdoor temperature. If the room temperature is 2 °C higher than a set temperature, the compressor operation frequency will attain to maximum frequency.
If the room temperature is 2.5 °C lower than a set temperature, the compressor will be stopped.
When the room temperature is between +2 °C to -2.5 °C of the setting temperature, the compressor frequency is controlled within the range shown in Table1.
Minimum frequency
Maximum frequency
AO *G36LATT AO *G45LATT AO *G54LATT AOTG60LATT
15rps 15rps 15rps 15rps
55rps 80rps 80rps 80rps
( Table 1 : Compressor Frequency Range )
01-01
AO *G36LATT
A zone B zone C zone D~ F zone
Med Low Quiet
Fan speed mode
High
55 55 47 38 77 77 57 47 80 80 64 55
DC indoor unit connection
A zone B zone C zone D~ F zone A zone B zone C zone D~ F zone A zone B zone C zone D~ F zone A zone B zone C zone D~ F zone A zone B zone C zone D~ F zone A zone B zone C zone D~ F zone
AO *G36LATT
45 45 38 33 53 53 46 41 59 59 52 46
38 38 36 29 46 46 41 37 52 52 46 40
29 29 29 23 35 35 35 28 38 38 38 29
55 55 53
45 64 64
57(56)
46 72
72 64(62) 52(55)
78 78 67 59
53 53 45
40 56 56
46(47)
45
64(62) 64(62)
55 47
67
67
59
55
45 45 38
36 54(47) 54(47) 46(41) 41(39) 61(55) 61(55) 52(46) 46(45)
59
59
52
47
AO *G45LATT
AO *G54LATT
AOTG60LATT
AO *G54LATT (AOTG54LATT)
AO *G45LATT (AOTG45LATT)
AC indoor unit connection (High static pressure)
[ rps ]
( Fig 1-1 : Limit of Maximum Frequency based on Outdoor Temperature for Single type )
A zone
B zone C zone D zone E zone F zone
36°C 32°C
21°C 12°C
2°C
When the room temperature rises
Outdoor air temperature
34°C 30°C 19°C 10°C
0°C
When the room temperature drops
.
.
.
1-2. HEATING OPERATION
1-2-1 HEATING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor. The maximum frequency is limited in the range shown in Figure 2 based on the outdoor temperature. If the room temperature is lower 3 °C than a set temperature, the compressor operation frequency will attain to maximum frequency.
If the room temperature is higher 2.5 °C than a set temperature, the compressor will be stopped.
When the room temperature is between +2.5 °C to -3 °C of the setting temperature, the compressor frequency is controlled within the range shown in Table 2.
01-02
Minimum frequency
Maximum frequency
AO *G36LATT AO *G45LATT AO *G54LATT AOTG60LATT
18rps 18rps 18rps 18rps
80rps 85rps 85rps 85rps
( Table 2 : Compressor Frequency Range )
.
.
.
AO *G36LATT
AO *G36LATT
A zone B zone C zone D~ F zone
Med Low Quiet
Fan speed mode
High
55 55 55 41 55 55 53 41 77 77 59 46 80 80 65 52 80 80 62 52
A zone B zone C zone D~ F zone A zone B zone C zone D~ F zone
53 53 41 38 53 53 41 38 56 56 46 41 62 62 52 46 62 62 52 46
41 41 38 33 53 53 41 33 46 46 41 37 52 52 46 40 62 62 52 40
31 31 31 27 31 31 31 27 35 35 35 30 38 38 38 33 38 38 38 33
AO *G45LATT
AO *G54LATT
AO *G54LATT
[ rps ]
( Fig 1-2 : Limit of Maximum Frequency based on Outdoor Temperature for Multi type )
A zone
B zone C zone D zone E zone F zone
36°C 32°C
21°C 12°C
2°C
When the room temperature rises
Outdoor air temperature
34°C 30°C 19°C 10°C
0°C
When the room temperature drops
A zone B zone C zone D~ F zone A zone B zone C zone D~ F zone
Recital
In the case of the Indoor unit of Duct or Ceiling type
In the case of the Indoor unit of Duct or Ceiling type
1-3. DRY OPERATION
1-3-1 INDOOR UNIT CONTROL
The compressor rotation frequency shall change according to set temperature and room temperature variation which the room temperature sensor of the indoor unit has detected as shown in the Fig 2.
01-03
Room temperature
Room
temperature
Compressor ON
Ts+1.5 °C
Ts+0.5 °C
Compressor OFF
( Fig.2 : Compressor Control based on Room Temperature )
Ts : Setting temperature
Compressor
ON
OFF
Indoor fan
DRY air flow
OFF
( Fig 3 : Indoor Fan Control for DC indoor unit )
10 30 60 180 60 180 60 10 30
(sec)
X zone
Y zone
( Table 3 : Compressor Frequency Range )
AO *G36LATT
AO *G36LATT
X zone Y zone X zone Y zone X zone Y zone X zone Y zone
Frequency
DC indoor unit connection
AO *G54LATT
AC indoor unit connection (High static pressure)
[ rps ]
AO *G45LATT
AO *G36LATT
AO *G45LATT
AO *G54LATT
AOTG60LATT
X zone Y zone X zone Y zone
31
0
29
0
35
0
38
0
31
0
35
0
38
0
41
0
X zone Y zone X zone Y zone
Recital
In the case of the Indoor unit of Duct type
S-LOW
Compressor
ON
OFF
LOW
OFF
30 180 120 180 30
(sec)
Indoor fan
ON
530 5
( Fig 4 : Indoor Fan Control for AC indoor unit )
*It is different by model
(about *300rpm)
1-4. AUTO CHANGEOVER OPERATION
01-04
When the air conditioner is set to the Auto mode by remote controller, operation starts in the optimum mode from among the Heating, Cooling, Dry and Monitoring mode. During operation, the optimum mode is automatically switched in accordance with temperature changes. The temperature can be set between 18°C and 30°C in 1°C steps.
When operation starts, indoor fan and outdoor fan are operated for around 2 minutes or 3 minutes. (This time is different for different types of indoor unit.) Room temperature and outdoor temperature are sensed, and the operation mode is selected in accordance with the table below. <Monitoring mode>
Cooling mode
25°C
Heating mode
( Table 4 : Operation mode selection table )
Room temperature (TR)
TR> Ts + 2°C
Ts + 2°C TR Ts - 2°C
*Middle zone
TR < Ts - 2°C Heating
When Cooling or Dry mode was selected at and air flow mode is Auto, the air conditioner operates as follow.
The same operation as COOLING OPERATION AND DRY OPERATION. When the room temperature has remained at set temperature -1.5°C, operation is automatically switched to Dry mode. If the room temperature reaches set temperature +2°C during Dry mode, operation returns to Cooling.
1
1
2
( Fig. 5 : Outdoor temperature zone selection )
Cooling
(Autmatic dry)
Operation mode
*If it's Middle zone, operation mode of indoor unit is selected as below.
(1). Same operation mode is selected as outdoor unit.
If outdoor unit is operating in Cooling, Dry, and Heating mode, indoor unit will be operated by the same operation mode.
(2). Selected by the outdoor temperature.
If outdoor unit is operating in other than Cooling, Dry, and Heating mode, indoor unit will be operated according to the outdoor temperature as below.
Cooling
Cooling
Dry
Dry
Compressor stop
When the room temperature drops
When the room temperature rises
Ts + 2°C
Ts - 0.5°C
Ts - 1.5°C
Ts + 1°C
Ts - 1.5°C
Ts - 2.5°C
( Fig.6 : Auto changeover : Cooling - Dry )
TR : Room temperature Ts : Setting temperature
TR : Room temperature Ts : Setting temperature
( Air flow mode : Auto )
When Heating was selected at , the same operation as HEATING OPERATION of page 01-02 is performed.
When the compressor was stopped for 6 consecutive minutes by the temperature control function after the Cooling(Auto:Dry) or Heating mode was selected at above, operation is switched to Monitoring and the operation mode is selected again.
3
1
4
1
01-05
START
Room temp.
Ts + 2
°C?
COOLING (AUTO:DRY)
OPERATION
HEATING OPERATION
YES
YES
NO
NO
NO
AUTO CHANGEOVER operation flow chart
TS : Setting temperature
Room temp.
Ts - 2
°C?
Thermostat remains
in OFF state for 6 minutes or
longer?
System stops
or operation command other than
auto changeover operation?
NO
Thermostat remains
in OFF state for 6 minutes or
longer?
System stops
or operation command other than
auto changeover operation?
Middle zone
NO
Operation mode
of outdoor unit : Cooling or Dry?
YES
NO
Operation mode
of outdoor unit : Heating?
YES
NO
YES
Outdoor temperature
25°C?
NO
YES
YES
NO
YESYES
1-5. INDOOR FAN CONTROL
1. Fan speed
(Table 5 : Indoor Fan Speed)
01-06
Operation mode Air flow mode Speed (rpm)
Cooling Fan
Heating
Dry
Hi
Me+
Me
Lo
Quiet
Cool air prevention
Hi
Me
Lo
Quiet
*Soft Quiet
Auto S-Lo
840 800 750 650 500 400 790 660 570 460 400 460 300
AU *G18LVLB
*Note, during Economy operation and operation mode is Fan, air flow is 1 step downs. (Hi > Me, Me > Lo, Lo > Quiet, Quiet > Soft Quiet)
*Note, during Economy operation and operation mode is Fan, air flow is 1 step downs. (Hi > Me, Me > Lo, Lo > Quiet, Quiet > Soft Quiet)
960 930 880 740 580 400 960 850 650 500 400 500 300
AU *G22/ 24LVLA
Operation mode Air flow mode Speed (rpm)
Cooling Fan
Heating
Dry
Hi
Me+
Me
Lo
Quiet
Cool air prevention
Hi
Me
Lo
Quiet
*Soft Quiet
Auto
S-Lo
1040 1000
950 800 740 500
1040
950 800 740 500 740 300
AB *G18LVTB
1300 1200 1150 1000
780
500 1330 1150 1000
780
500
780
300
AB *G22/ 24LVTA
Operation mode Air flow mode Speed (rpm)
Cooling Fan
Heating
Dry
Hi
Me+
Me
Lo
Quiet
Cool air prevention
Hi
Me
Lo
Quiet
*Soft Quiet
Auto
S-Lo
1380 1300
1220 1140
1380 1300 1220 1140
600
1140
600
AR *G18LLLA (Normal static pressure: 25Pa)
Operation mode Air flow mode Speed (rpm)
Cooling Fan
Heating
Dry
Hi
Me+
Me
Lo
Quiet
Cool air prevention
Hi
Me
Lo
Quiet
*Soft Quiet
Auto S-Lo
Operation mode Air flow mode Speed (rpm)
Cooling Fan
Heating
Dry
Hi
Me+
Me
Lo
Quiet
Cool air prevention
Hi
Me
Lo
Quiet
*Soft Quiet
Auto S-Lo
Operation mode Air flow mode Speed (rpm)
Cooling Fan
Heating
Dry
Hi
Me+
Me
Lo
Quiet
Cool air prevention
Hi
Me
Lo
Quiet
*Soft Quiet
Auto S-Lo
830 700
600 550
830 700 600 550 350 550 350
AR *G22/ 24LMLA (Normal static pressure: 35Pa)
[Multi type]
[Single type]
Operation mode Air flow mode Speed (rpm)
Cooling Fan
Heating
Dry
Hi
Me+
Me
Lo
Quiet
Cool air prevention
Hi
Me
Lo
Quiet
*Soft Quiet
Auto S-Lo
660 600 540 470 430 300 660 540 470 430 300 430 270
AU *G36LRLA
690 650 610 550 470 300 690 610 550 470 300 470 270
AU *G45LRLA Operation mode Air flow mode Speed (rpm)
Cooling Fan
Heating
Dry
Hi
Me+
Me
Lo
Quiet
Cool air prevention
Hi
Me
Lo
Quiet
*Soft Quiet
Auto S-Lo
720 680 630 570 480 300 720 630 570 480 300 480 270
AU *G54LRLA Operation mode Air flow mode Speed (rpm)
Cooling Fan
Heating
Dry
Hi
Me+
Me
Lo
Quiet
Cool air prevention
Hi
Me
Lo
Quiet
*Soft Quiet
Auto S-Lo
01-07
Operation mode Air flow mode Speed (rpm)
Heating Cooling Fan
Hi
Me
Lo
1300 1150 1000
AR *G45/ 54LHTA (Normal static pressure: 100Pa)
Operation mode Air flow mode Speed (rpm)
Cooling Fan
Heating
Dry
Hi
Me+
Me
Lo
Quiet
Cool air prevention
Hi
Me
Lo
Quiet
*Soft Quiet
Auto S-Lo
1100 1000
910 750 650 500
1100
910 750 650 500 650 250
AB *G36LRTA
1200 1100 1000
830
680
500 1200 1000
830
680
500
680
250
AB *G45LRTA Operation mode Air flow mode Speed (rpm)
Cooling Fan
Heating
Dry
Hi
Me+
Me
Lo
Quiet
Cool air prevention
Hi
Me
Lo
Quiet
*Soft Quiet
Auto S-Lo
1340 1250 1150
950 790
500 1360 1150
950
790
500
790
250
AB *G54LRTA Operation mode Air flow mode Speed (rpm)
Cooling Fan
Heating
Dry
Hi
Me+
Me
Lo
Quiet
Cool air prevention
Hi
Me
Lo
Quiet
*Soft Quiet
Auto S-Lo
Operation mode Air flow mode Speed (rpm)
Cooling Fan
Heating
Dry
Hi
Me+
Me
Lo
Quiet
Cool air prevention
Hi
Me
Lo
Quiet
*Soft Quiet
Auto S-Lo
1220 1020
840 670
1200 1020
840 670 420 670 420
AR *G36LMLA (Normal static pressure: 47Pa)
1300 1020
840 670
1310 1020
840 670 420 670 420
AR *G45LMLA (Normal static pressure: 30Pa)
Operation mode Air flow mode Speed (rpm)
Cooling Fan
Heating
Dry
Hi
Me+
Me
Lo
Quiet
Cool air prevention
Hi
Me
Lo
Quiet
*Soft Quiet
Auto S-Lo
*Note, during Economy operation and operation mode is Fan, air flow is 1 step downs. (Hi > Me, Me > Lo, Lo > Quiet, Quiet > Soft Quiet)
Operation mode Air flow mode Speed (rpm)
Cooling Fan
Heating
Dry
Hi
Me+
Me
Lo
Quiet
Cool air prevention
Hi
Me
Lo
Quiet
*Soft Quiet
Auto S-Lo
990 850
700
990 850 700
370 700 370
ARTG36LHTB (Normal static pressure: 60Pa)
1040/ 1000
880/ 840 740/ 700 740/ 700 420/ 380 420/ 380
ARTG45LHTB (Normal static pressure: 60Pa)
Operation mode Air flow mode Speed (rpm)
Heating Cooling Fan Dry
Hi
Me
Lo Lo
Intermittent
S-Lo
1090/ 1050
900/ 860 780/ 740 780/ 740 420/ 380 420/ 380
ARTG54LHTB/ 60LHTA (Normal static pressure: 60Pa)
Operation mode Air flow mode Speed (rpm)
Heating Cooling Fan Dry
Hi
Me
Lo Lo
Intermittent
S-Lo
2. FAN OPERATION
The airflow can be switched in 5 steps such as Auto, Quiet, Low, Med, High, while the indoor fan only runs. The High Static Pressure Duct type is 4 steps such as Auto, Low, Med, High.
3. COOLING OPERATION (Auto : Cooling)
Switch the airflow [Auto], and the indoor fan motor will run according to a room temperature, as shown in Figure 7. On the other hand, if switched in [High] [Quiet], the indoor motor will run at a constant airflow of [Cool] operation modes Quiet, Low, Med, High, as shown in Table 5.
( Fig 7 : Airflow change - over ( Cooling : Auto ) )
When the room temperature rises
When the room temperature drops
Tr : Room temperature Ts : Setting temperature
Tr-Ts > 2 °C
=
1 °C > Tr-Ts
2 °C > Tr-Ts > 1 °C
=
Tr-Ts > 2.5 °C
=
1.5 °C > Tr-Ts
2.5 °C > Tr-Ts > 1.5 °C
=
High
Med
Low
01-08
4. HEATING OPERATION (Auto : Heating)
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature, as shown in Figure 8. On the other hand, if switched in [High] [Quiet], the indoor motor will run at a constant airflow of [Heat] operation modes Quiet, Low, Med, High, as shown in Table 5.
( Fig 8 : Airflow change - over ( Heating : Auto ) )
Tr-Ts > - 1.5 °C
=
- 2.5 °C> Tr-Ts
- 1.5 °C> Tr-Ts > - 2.5 °C
=
Tr-Ts > - 1 °C
=
- 2 °C> Tr-Ts
- 1 °C> Tr-Ts > - 2 °C
=
When the room temperature rises
When the room temperature drops
Tr : Room temperature Ts : Setting temperature
Low
Med
High
The High Static Pressure Duct type is 4 steps such as Auto, Low, Med, High.
The High Static Pressure Duct type is 4 steps such as Auto, Low, Med, High.
6. DRY OPERATION
Refer to the Fig 3,4. During the DRY mode operation, the fan speed setting can not be changed.
01-09
5. COOL AIR PREVENTION CONTROL (Heating mode)
The maximum value of the indoor fan speed is set as shown in Figure 9, based on the detected temperature by the indoor heat exchanger sensor on heating mode. When the compressor does not operate, the indoor fan motor operates [S-Lo] or [Stop] mode.
( Fig 9 : Cool Air Prevention Control )
[ Cassette, Ceiling type ]
[ Duct type ]
*Hi or setting fan mode
*Lo or setting fan mode
37°C
29°C
32°C
24°C
Indoor heat exchanger temperature rises
Indoor heat exchanger temperature drops
Cool air prevention
S-Lo
S-Lo
42°C
30°C
34°C
Indoor heat exchanger temperature rises
Indoor heat exchanger temperature drops
Hi
*Me+ or setting fan mode
*Lo or setting fan mode
*Lo or setting fan mode
*Lo or setting fan mode
39°C
37°C
37°C
32°C
24°C
*Lower speed is selected.
42°C
30°C
34°C
Indoor heat exchanger temperature rises
Indoor heat exchanger temperature drops
Hi
*Me+ or setting fan mode
*Lo or setting fan mode
39°C
37°C
37°C
32°C
24°C
*Lower speed is selected.
*Lower speed is selected.
Hi
*Lo or setting fan mode
*Lo or setting fan mode
37°C
29°C
32°C
24°C
Indoor heat exchanger temperature rises
Indoor heat exchanger temperature drops
*Lower speed is selected.
13 min. later
13 min. later
[ High Static Duct type ]
Setting fan mode
S-Lo
27°C
24°C
Indoor heat exchanger temperature
S-Lo or stop
Setting fan mode
Lo
27°C
24°C
Indoor heat exchanger temperature
Lo
13 min. later
1-6. OUTDOOR FAN CONTROL
1. Outdoor Fan Motor
Following table shows the fan speed of the outdoor unit.
(Table 6 : Fan speed of the outdoor unit)
Upper fan Lower fan Upper fan Lower fan
The outdoor fan speed is decided depending on the compressor and the outdoor temperature. The compressor and the fan start-up at the same time,
and the fan stops after the compressor stops and 60 seconds has passed. The fan doesn't operates for 10 seconds after the fan stops. The upper fan and the lower fan operates at 500 rpm for 20 seconds after the start-up. However, the fan operates at 200rpm when the initial rotation speed is 300rpm or less.
Cooling
850/ 780/ 520/ 480/ 400/ 350/ 280 rpm 800/ 750/ 520/ 350/ 280/ 0 rpm 900/ 850/ 780/ 520/ 480/ 400/ 350/ 280 rpm 800/ 750/ 520/ 350/ 280/ 0 rpm
AO *G36/ 45LATT
01-10
AO *G54LATT AOTG60LATT
Upper fan Lower fan Upper fan Lower fan
Heating
870/ 780/ 520/ 350/ 200/ 170/ 150 rpm 840/ 750/ 520/ 350/ 200/ 170/ 150 rpm 900/ 870/ 780/ 520/ 350/ 200/ 170/ 150 rpm 900/ 840/ 750/ 520/ 350/ 200/ 170/ 150 rpm
AO *G36/ 45LATT
AO *G54LATT AOTG60LATT
. .
. . .
1-7. LOUVER CONTROL
01-11
1-1. VERTICAL LOUVER CONTROL
Each time the button is pressed, the air direction range will change as follows:
Use the air direction adjustments within the ranges shown above.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
Cooling / Dry / Fan mode Horizontal flow Heating mode Downward flow
(Function Range)
(Fig 10 : Air Direction Range)
(Operation Range)
1-2. SWING OPERATION
When the swing signal is received from the remote controller, the vertical louver starts to swing. The range of swing depends on the set airflow direction.
When the indoor fan is either at S-Low or Stop mode, the swinging operation is interrupted and the louver stops at the memorized position. ( Stop mode means Operation stop.)
During Cooling / Heating / Dry / Fan mode :
During Auto mode operation, for the first minute after the start-up, air-flow will be horizontal ; the air direction cannot be adjusted during this period.
The type of operation
Cooling / Dry
Range of swing
to
Heating
to
Fan( )
to
to
to
Fan( )
to
1. For Floor / Ceiling type < AB *G18LVTB, AB *G22/ 24LVTA >
1
2
3
4
5
6
7
12345
67
1
2345
67
1 7
7
5
41
1 4 3
7
1
4
3 7
1
During Heating start-up and Defrost operation, to prevent the thing that the cool air blows to the person directly, the louver is set to .
7
5
During Cooling and Dry mode operation, if the Vertical Louvers are left in the to ,
4
4
they will automatically return to position .
<Operation continues for 30 minutes>
<Operation stops within 30 minutes>
they will automatically return to position in next Cooling start-up.
For the dew condensation prevention of the Vertical Louvers.
01-12
1-3. HORIZONTAL LOUVER CONTROL
Each time the button is pressed, the air direction range will change as follows:
(Function Range)
(Fig 11 : Air Direction Range)
1-4. SWING OPERATION
When the swing signal is received from the remote controller, the horizontal louver starts to swing. The range of swing depends on the set airflow direction.
When the indoor fan is either at S-Low or Stop mode, the swinging operation is interrupted and the louver stops at the memorized position. ( Stop mode means Operation stop.)
The type of operation
Cooling / Heating / Dry / Fan
Range of swing
RIGHT/LEFT air direction louvers
Use the air direction adjustments within the ranges shown above. The remote control unit's display does not change.
(All range)
1
2
3
4
5
12345
to
15
01-13
2-1. VERTICAL LOUVER CONTROL
Each time the button is pressed, the air direction range will change as follows:
Use the air direction adjustments within the ranges shown above.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
Cooling / Dry / Fan mode Horizontal flow Heating mode Downward flow
(Function Range)
(Fig 12 : Air Direction Range)
(Operation Range)
2-2. SWING OPERATION
When the swing signal is received from the remote controller, the vertical louver starts to swing. The range of swing depends on the set airflow direction.
When the indoor fan is either at S-Low or Stop mode, the swinging operation is interrupted and the louver stops at the memorized position. ( Stop mode means Operation stop.)
During Cooling / Heating / Dry / Fan mode :
During Auto mode operation, for the first minute after start-up, air -flow will be horizontal ; the air direction cannot be adjusted during this period.
The type of operation
Cooling / Dry
Range of swing
to
Heating
to
2. For Ceiling Type < AB *G36/ 45/ 54LRTA >
12345
12345
5
1
1
1
5
4
3
to
5
5
4
1
During Heating start-up and Defrost operation, to prevent the thing that the cool air blows to the person directly, the louver is set to .
During Cooling and Dry operation, if the Vertical Louvers are left in the to ,
3
3
they will automatically return to position .
<Operation continues for 30 minutes>
<Operation stops within 30 minutes>
they will automatically return to position in next Cooling start-up.
For the dew condensation prevention of the Vertical Louvers.
Fan
01-14
2-3. HORIZONTAL LOUVER CONTROL
Each time the button is pressed, the air direction range will change as follows:
(Function Range)
(Fig 13 : Air Direction Range)
2-4. SWING OPERATION
When the swing signal is received from the remote controller, the horizontal louver starts to swing. The range of swing depends on the set airflow direction.
When the indoor fan is either at S-Low or Stop mode, the swinging operation is interrupted and the louver stops at the memorized position. ( Stop mode means Operation stop.)
The type of operation
Cooling / Heating / Dry / Fan
Range of swing
to
Use the air direction adjustments within the ranges shown above. The remote control unit's display does not change.
(All range)
12345
15
01-15
3-1. VERTICAL LOUVER CONTROL
Each time the button is pressed, the air direction range will change as follows:
Use the air direction adjustments within the ranges shown above.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
(Function Range)
(Fig 14 : Air Direction Range)
(Operation Range)
During Cooling / Heating / Dry / Fan mode :
Cooling / Dry / Fan mode Horizontal flow Heating mode Downward flow
3-2. SWING OPERATION
When the swing signal is received from the remote controller, the vertical louver starts to swing. The range of swing depends on the set airflow direction.
When the indoor fan is either at S-Low or Stop mode, the swinging operation is interrupted and the louver stops at the memorized position. ( Stop mode means Operation stop.)
During Auto mode operation, for the first minute after start-up, air-flow will be horizontal ; the air direction cannot be adjusted during this period.
The type of operation
Cooling / Heating / Dry / Fan
Range of swing
to
3. For Compact Cassette Type < AU *G18LVLB, AU *G22/ 24LVLA >
1234
1234
1
14
4
During Heating operation, to prevent the thing that the cool air blows to the person directly, the louver is set to .
1
1
2
3
4
01-16
4-1. VERTICAL LOUVER CONTROL
Each time the button is pressed, the air direction range will change as follows:
Use the air direction adjustments within the ranges shown above.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
(Function Range)
(Fig 15 : Air Direction Range)
(Operation Range)
During Cooling / Dry / Fan mode :
Cooling / Dry / Fan mode Horizontal flow Heating mode
Downward flow
4-2. SWING OPERATION
When the swing signal is received from the remote controller, the vertical louver starts to swing. The range of swing depends on the set airflow direction.
When the indoor fan is either at S-Low or Stop mode, the swinging operation is interrupted and the louver stops at the memorized position. ( Stop mode means Operation stop.)
During Auto mode operation, for the first minute after start-up, air-flow will be horizontal ; the air direction cannot be adjusted during this period.
The type of operation
Cooling / Heating / Dry / Fan
Range of swing
to
4. For Cassette Type < AU *G36/ 45/ 54LRLA >
1234
1234
During Heating mode :
234
1
14
4
During Heating operation, to prevent the thing that the cool air blows to the person directly, the louver is set to .
1
1-8. COMPRESSOR CONTROL
1. OPERATION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as shown in Table 7.
(Table 7 : Compressor Operation Frequency Range)
2. OPERATION FREQUENCY CONTROL AT START UP (Common in all models)
The compressor frequency soon after the start-up is controlled as shown in Figure 16.
(Fig 16 : Compressor Control at Start-up)
28rps
180sec 270sec
40rps
01-17
90sec
AO *G36LATT AO *G45LATT AO *G54LATT AOTG60LATT
15rps 15rps 15rps 15rps
55rps 80rps 80rps 80rps
< Normal start-up >
54rps
70rps
360sec
25rps
480sec270sec
40rps
30sec
54rps
70rps
650sec
16rps
28rps
620sec560sec
< Cold start at Heating mode (Compressor start after long time.)>
Upper Limit Frequency
Upper Limit Frequency
25rps
120sec
30sec
54rps
70rps
650sec
16rps
300sec
< Cold start at Heating mode (Compressor start after long time.)>
Upper Limit Frequency
Min
Max
Cooling
18rps 18rps 18rps 18rps
80rps 85rps 85rps 85rps
Min
Max
Heating
31 (29)rps
35rps 38rps
Dry
DC indoor unit
AC indoor unit
31rps 35rps 38rps 41rps
[Outdoor air temp.< 10°C]
[Outdoor air temp.> 10°C]
=
01-18
1-9. TIMER OPERATION CONTROL
AR- RAH1E, RAH2E
1. ON / OFF TIMER
OFF timer : When the clock reaches the set time, the air conditioner will be turned off.
Operation mode
Stop mode
Set time of timer
ON timer : When the clock reaches the set time, the air conditioner will be turned on.
Operation mode
Stop mode
Set time of timer
2. PROGRAM TIMER
ON / TIMER OFF / TIMER PROGRAM TIMER SLEEP TIMER
The program timer allows the OFF timer and ON timer to be used in combination one time.
Operation mode
Operation will start from the timer setting (either OFF timer or ON timer) whichever is closest to the clock's current timer setting. The order of operations is indicated by the arrow in the remote control unit's display.
SLEEP timer operation cannot be combined with ON timer operation.
Stop mode
Stop mode
Stop mode
Operation mode
Operation mode
Set time
Set time Set time Set time
1-9-1 Wireless Remote Controller
01-19
3. SLEEP TIMER
If the sleep timer is set, the room temperature is monitored and the operation is stopped automatically. If the operation mode or the set temperature is change after the sleep timer is set, the operation is continued according to the changed setting of the sleep timer from that time ON.
Set temperature rises
( Ts : Set temperature )
Stop of operation
Set temperature lowers
( Ts : Set temperature )
Ts
Stop of operation
In the COOLING operation mode
When the sleep timer is set, the setting temperature is increased 1 degC. It increases the setting temperature another 1 degC after 1 hour. After that, the setting temperature is not changed and the operation is stopped at the time of timer setting.
Ts
+1degC
+2degC
-2degC
-1degC
-4degC
-3degC
Set
60min
In the HEATING operation mode
When the sleep timer is set, the setting temperature is decreased 1 degC. It decreases the setting temperature another 1 degC every 30 minutes. Upon lowering 4 degC, the setting temperature is not changed and the operation stops at the time of timer setting.
Set
30min
60min
90min
01-20
AR- WAE1E
1. ON / OFF TIMER
OFF timer : When the clock reaches the set time, the air conditioner will be turned off.
Operation mode
Stop mode
Set time of timer
ON timer : When the clock reaches the set time, the air conditioner will be turned on.
Operation mode
Stop mode
Set time of timer
The weekly timer allows up to two ON and OFF time to set up per day.
Use this timer function to set operating time for each day of the week.
Operation mode
The operating time can be set in 30 min increments only. The OFF time can be carried over to next day. The ON timer and the OFF timer functions cannot be set with using the weekly timer.
Both ON and OFF time must be set.
2. WEEKLY TIMER
2-1. WEEKLY TIMER
Stop mode
Stop mode
Stop mode
Operation mode
Operation mode
Set time
Set time Set time Set time
1-9-2 Wired Remote Controller
ON / TIMER OFF / TIMER
WEEKLY TIMER
TEMPERATURE SET BACK TIMER
01-21
The DAY OFF setting is only available for days for which weekly settings already exist.
The SET BACK timer only changes the set temperature for 7 days, it cannot be used to start or stop air conditioner operation.
The SET BACK timer can be set to operate up to two times per day but only one temperature setting can be used.
During COOLING/DRY mode, the air conditioner will operate at a minimum of 18°C even if the SET BACK temperature is set to 17°C or lower.
The DAY OFF setting can only be set one time. The DAY OFF setting is cancelled automatically after the set day has passed.
Normal
Next day setting
If the operating time carries over to the next day (during a next day setting), the effective DAY OFF range will be set as shown below.
2-2. DAY OFF setting
3. TEMPERATURE SET BACK TIMER
Stop mode
Stop mode
Operation mode
Stop mode
Operation mode
Preceding day Next day
DAY OFF
Stop mode
Stop mode
Operation mode
Stop mode
Operation mode
DAY OFF
Setting day
Preceding day Next daySetting day
Case of SET BACK timer on the Cooling operation. ( Setting temperature :22°C, SET BACK temperature :26°C)
SET BACK setting
Operation temperature
Operation temperature
26°C
22°C 26°C
22°C
24°C
*1
ON OFF OFFON
*1: During the SET BACK function, the setting temperature is changed.
Chenge the setting temperature: 22°C 24°C
1-10. ELECTRONIC EXPANSION VALVE CONTROL
1-11. TEST OPERATION CONTROL
Under the condition where the air conditioner stops, press the MASTER CONTROL button and the FAN CONTROL button simultaneously for 2 seconds or more, and the test operation control mode will appear. During test running, " " will display on the remote controller display. Set the test operation mode, and the compressor will continue to run regardless of whatever the room temperature sensor detects. The test operation mode is released if 60 minutes have passed after setting up the test operation.
The compressor won't enter operation status for 3 minutes after the compressor is stopped, even if any operation is given.
1-12. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST )
01-22
With Wired Remote Controller
The most proper opening of the electronic expansion valve is calculated and controlled under the present operating condition based on the following values. The compressor frequency, the temperatures detected by the discharge temperature sensor, the indoor heat exchanger sensor, the outdoor heat exchanger sensor, and the outdoor temperature sensor.
Pulse range
50 480 pulse
(1) Pulse range of EEV
(2) The EEV is set up at 480 pulses when the compressor is stopped. (3) Initialization (Input of 528 pulses toward closing direction) is operated under the following condition.
* When the power is turned on. * 4 hours has passed since the last initialization, and 3 minutes has passed after the compressor stop.
(If 12 hours has passed since the last initialization, the compressor is compulsorily stopped.)
All Models
Cooling / Dry Heating
Operation
Under the condition where the air conditioner runs, press the TEST RUN button, and the test operation control mode will appear. During test running, the Operation LED and Timer LED of the air conditioner body blinks simultaneously. Set the test operation mode, and the compressor will continue to run regardless of whether the room temperature sensor detects. The test operation mode is released if 60 minutes have passed after setting up the test operation.
With Wireless Remote Controller
40 480 pulse
With Outdoor Unit
Operate [ENTER](TEST RUN) switch on the display board.
1. Set the operation mode to "COOL" or "HEAT" by DIP-SW before power-on.
2. Press [ENTER](TEST RUN) switch for more than 3 seconds "TEST RUN" LED will light on, If the compressor is operating at starting the test run, the compressor will stop, and a while , the test run will start.
At the time when the air conditioner is switched from the Cooling mode to Heating mode, the compressor is stopped, and the 4-way valve is switched in 3 minutes later after the compressor stopped.
1-13. 4-WAY VALVE EXTENSION SELECT
1-14. AUTO RESTART
01-23
1-15. MANUAL AUTO OPERATION (When using the Wireless RC)
If MANUAL / AUTO Button is pushed for less than 10 seconds, the operation is controlled as shown in Table 9. If the remote control is lost or battery power dissipated, this function will work without the remote control.
Operation mode
Auto changeover
Auto
Normal Normal
Continuous (No timer setting available)
24°C
(Table 9)
Setting temp.
Vertical louver Horizontal louver
OFF
Economy
OFF
Swing
Fan control mode Timer mode
When the power was interrupted by a power failure, etc. during operation, the operation contents at that time are memorized and when power is recovered, operation is automatically resumed with the memorized operation contents.
(Table 8 : Operation contents memorized when the power is interrupted)
Operation mode Set temperature Set air flow Set air flow direction Swing Economy operation 10°C Heat operation
Thermistor detected position
Timer mode
Wireless remote controller
Wired remote controller (Memory Backup : Disable)
Wired remote controller (Memory Backup : Enable)
OFF Timer ON Timer WEEKLY Timer Temperature
: Memorize : Not memorize
*It is necessary to set on the DIP-SW1-No,6 of the wired remote controller, to enable the memory backup. Refer to the installation manual of wired remote controller for details.
SET BACK Timer
01-24
1-16. PUMP DOWN
Operate [PUMP DOWN] switch on the display board.
(1) Confirm that power is off, and open the service panel. (2) Turn the power on.
LED display lights on as shown in the above figure, and the fans and the compressor start operating. If the [PUMP DOWN] switch is pressed while the compressor is operating, the compressor will stop then
start again in about 3 minutes.
(4) LED display will change as shown as below about 3 minutes after the compressor starts. Fully close the 3-way valve on the liquid pipe side at this stage.
(5) When LED display changes as shown in the below figure, close the 3-way valve on the gas pipe side tightly.
(6) LED display changes after 1 minute as shown in the figure below.
Fans and compressor stop automatically.
(7) Turn the power off.
PUMP DOWN is completed.
(3) Press [PUMP DOWN] switch for 3 seconds or more after 3 minutes after power on.
POWER
MODE
ERROR
TEST
RUN
PUMP
DOWN
LOW NOISE PEAK CUT
(L1) (L2) (L3) (L4) (L5) (L6) (L7)
ERROR
TEST
RUN
PUMP DOWN
LOW NOISE PEAK CUT
POWER
MODE
(L1) (L2) (L3) (L4) (L5) (L6) (L7)
ERROR
TEST
RUN
PUMP DOWN
LOW NOISE PEAK CUT
POWER
MODE
(L1) (L2) (L3) (L4) (L5) (L6) (L7)
ERROR
TEST
RUN
PUMP DOWN
LOW NOISE PEAK CUT
POWER
MODE
(L1) (L2) (L3) (L4) (L5) (L6) (L7)
ERROR
TEST
RUN
PUMP DOWN
LOW NOISE PEAK CUT
POWER
MODE
(L1) (L2) (L3) (L4) (L5) (L6) (L7)
ERROR
TEST
RUN
PUMP DOWN
LOW NOISE PEAK CUT
POWER
MODE
(L1) (L2) (L3) (L4) (L5) (L6) (L7 )
< PUMP DOWN Procedure >
Step (5)
Closing direction
Step (4)
Hexagon wrench
Liquid pipe
Gas pipe
Closing direction
: Light ON: Light OFF
01-25
1-18. DEFROST OPERATION CONTROL
1. CONDITION OF STARTING THE DEFROST OPERATION
The defrost operation starts when the outdoor heat exchanger temperature sensor detects the temperature lower than the values shown in Table 10.
1-17. COMPRESSOR PREHEATING
When the outdoor heat exchanger temperature is lower than 0°C and after 30 minutes has passed after power-on or operation stop, power is applied to the compressor and the compressor is heated. (By heating the compressor, warm air is quickly discharged when operation is started.)
When operation was started, and when the outdoor temperature rises to 2°C or greater, preheating is ended.
2. CONDITION OF THE DEFROST OPERATION COMPLETION
Release Condition
Outdoor heat exchanger temperature sensor value is higher than +10°C or Compressor operation time has passed 15 minutes.
(Table 10 : Condition of starting Defrost Operation)
1st time defrosting after starting operation
Less than 17 min.
17 to 62 min.
62 min. to 4 hours
More than 4 hours
Does not operate
- 9°C
- 5°C
- 3°C
Compressor integrating operation time
Compressor contiguous operation time
Defrost operation is released when the conditions become as shown in Table 11.
(Table 11 : Defrost Release Condition)
Operation temperature
Below 10 min.
Above 10 min.
Less than 35 min.
35 min. to 215min
215 min. to 4 hours
Does not operate
- 6°C
- 5°C
More than 4 hours
- 3°C
Compressor integrating operation time
Compressor contiguous operation time
Operation temperature
Below 10 min.
Above 10 min.
Defrosting after 2nd time upon starting operation
Compressor integrating operation time
Operating condition
Integrating defrost for intermittent operation
Less than 10 min.
If the compressor continuous operation time is less than 10 minutes, the OFF number of the compressor is counted. If any defrost operated, the compressor OFF count is cleared.
OFF count of the compressor
40 times
More than 210 min.
Compressor OFF
(at outside air temp.< 2°C)
=
01-26
3. Defrost Flow Chart
The defrosting shall proceed by the integrating operation time and outdoor heat exchanger emperature as follows.
(Not defrosted for 10 minutes)
Outdoor fan : OFF Compressor : OFF EEV : 400pulse 4-way valve : OFF Compressor: ON Frequency : 65rps (36 type) : 70rps (45/54/60 type) EEV : 350pulse (Outdoor HEX temp.> 2°C)
Heating operation start : Compressor ON
Defrost Indicator: [Operation lamp] 7 sec ON / 2 sec OFF
Outdoor heat exchanger temperature: Over 10°C or Compressor ON time: Over 15 minutes
Defrost end
Compressor integrating operation: Over 17 minutes to below 62 minutes
Compressor integrating operation: Over 240 minutes
Compressor integrating operation: Over 62 minutes to below 240 minutes
Outdoor HEX temp.: Below - 9°C
Outdoor HEX temp.: Below - 5°C
Outdoor HEX temp.: Below - 3°C
In case of 1st defrost
In case of 2nd and later defrost
Outdoor temp ­Outdoor HEX temp. : Above 5 degC
Compressor integrating operation: Over 35 minutes to below 215 minutes
Outdoor HEX temp.: Below - 6°C
Compressor integrating operation: Over 215 minutes to below 240 minutes
Outdoor HEX temp.: Below - 5°C
Compressor integrating operation: Over 240 minutes
Outdoor HEX temp.: Below - 3°C
Compressor OFF: Outside air temp.< 2°C (More than 210 min.)
Compressor OFF count : 40 times (Less than 10min.)
In case of Integrating defrost for intermittent operation
Defrost start
=
=
01-27
Release Condition
Outdoor heat exchanger temperature sensor value is higher than +10°C or Compressor operation time has passed 15 minutes.
1-19. OFF DEFROST OPERATION CONTROL
1. OFF DEFROST OPERATION CONDITION
When operation stops in the HEATING mode, if frost is adhered to the outdoor unit heat-exchanger, the defrost operation will proceed automatically. In this time, if indoor unit operation lamp flashes slowly (7 sec ON / 2 sec OFF), the outdoor unit will allow the heat-exchanger to defrost, and then stop.
In heating operation, the outdoor heat exchanger temperature is less than - 4°C, and compressor operation integrating time lasts for more than 30 minutes. and compressor operation contiguous time lasts for more than 10 minutes.
OFF Defrost Flow Chart
HEATING operation stops
2. OFF DEFROST END CONDITION
Outdoor heat exchanger temperature: Over 10°C or Compressor ON time: Over 15 minutes
Outdoor heat exchanger temperature: Below - 4°C and Compressor integrating operation: Over 30 minutes and Compressor contiguous operation: Over 10 minutes
Defrost start
Defrost Indicator: [Operation lamp] 7 sec ON / 2 sec OFF
Defrost end
01-28
1-20. ECONOMY OPERATION
1 -22. VARIOUS PROTECTIONS
1. DISCHARGE GAS TEMPERATURE OVER RISE PREVENTION CONTROL
The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas temperature. When the discharge temperature becomes more than 105°C, the compressor frequency -10rps, and it continues the frequency -10rps every 2 minutes until the temperature becomes less than 105°C.
When the discharge temperature becomes less than 100°C, the control of the compressor frequency is released.
When the discharge temperature becomes more than 115°C, the compressor is stopped.
2. COMPRESSOR TEMPERATURE PROTECTION CONTROL
When the compressor temperature thermistor detects more than 110°C, the compressor is stopped at once.
115°C
105°C
100°C
Release of protection
Hold
Compressor stop
-10rps every 2 minutes
Discharge temperature
(Fig 17 : Discharge temperature control)
The ECONOMY operation functions by pressing ECONOMY button on the remote controller. At the maximum output, ECONOMY Operation is approximately 70% of normal air conditioner operation for cooling and heating. The ECONOMY operation is almost the same operation as below settings.
Mode Cooling/ Dry Heating Target temperature Setting temp.+1°C Setting temp.-1°C
(Table 12 )
Operation mode
Heating
Auto
Operate as normal
Economy
10°C
(Table 13)
Setting temp.
Defrost operation
Fan control mode LED display
1-21. 10°C HEAT OPERATION
10°C HEAT operation performs as below when pressing 10°C HEAT button.
01-29
5. ANTI FREEZING PROTECTION <Cooling / Dry mode>
The compressor frequency is decrease on Cooling and Dry mode when the indoor heat exchanger temperature sensor detects the temperature lower than Temperature . Then, the anti-freezing protection is released when it becomes higher than Temperature .
(Table 12 : Anti-freezing Protection Operation / Release Temperature)
Outdoor temperature
Over than 10°C *1
or 12°C
*2
Less than 10°C *1
or 12°C *2
*1. When the temperature rises. *2. When the temperature drops.
4°C
7°C
13°C
Temperature Temperature
4. PRESSURE OVER RISE PROTECTION <Cooling mode>
When the outdoor unit heat-exchange temperature rises to temperature or greater, the compressor is stopped and trouble display is performed. After 3 minutes ST, release of protection.
3. LOW PRESSURE PROTECTION CONTROL <Cooling mode>
When the pressure sensor detected value is 0.68MPaG or less continues for 1minute, the compressor frequency -8rps.
<After the compressor start-up and 10 minutes has passed>
<After the frequency of the compressor -8rps and 1 minute has passed>
When the detected value becomes more than 0.78MPaG, this protection is released.
<After the compressor start-up and 1 minute has passed> The detected value of pressure sensor is 0.02MPaG or less, continues for 5 minutes, the compressor is stopped.
When the pressure sensor detected value is 0.68MPaG or less, continues for 1 minute, the compressor continues frequency
-8rps every 1 minute until the detected value becomes more than 0.68MPaG.
0.78MPaG
0.68MPaG
0.02MPaG
Release of protection
Hold
Compressor stop
-8rps every 1 minute
Pressure
(When continues for 5 minutes)
(Fig 18 : Low pressure protection control)
7. CURRENT RELEASE CONTROL
The compressor frequency is controlled so that the outdoor unit input current does not exceeds the current limit value that was set up with the outdoor temperature. The compressor frequency returns to the designated frequency of the indoor unit at the time when the frequency becomes lower than the release value.
(Table 13 : Current Release Operation Value / Release Value)
AO *G36LATT AO *G45LATT AO *G54LATT AOTG60LATT
Cooling
6.0A / 5.5A
7.0A / 6.5A
8.0A / 7.5A
8.5A / 8.0A
Heating
6.0A / 5.5A
7.0A / 6.5A
8.0A / 7.5A
8.5A / 8.0A
01-30
6-1. HIGH TEMPERATURE RELEASE CONTROL <Heating mode>
6. HEATING OVERLOAD PROTECTION
In Heating mode, the compressor frequency is controlled as following based on the detection value of the indoor heat-exchanger temperature sensor and pressure sensor.
On heating mode, the compressor frequency is controlled as following based on the detection value of the indoor heat exchanger temperature sensor.
(Fig.19 : Heating Overload Protection Control)
Indoor heat exchange temperature
65°C
Compressor is OFF
The compressor frequency is decreased 7rps every 60 seconds.
55°C
50°C
48°C
Stable range
Release
The compressor frequency is decreased 1rps every 60 seconds.
Release
Indoor heat exchange temperature
65°C
Compressor is OFF
The compressor frequency is decreased 10rps every 60 seconds.
57°C
55°C
50°C
Stable range
Release
The compressor frequency is decreased 2rps every 60 seconds.
Release
[ High Static Pressure Duct model ] [ Excluding High Static Pressure Duct model ]
- 20°C
The FORCED COOLING OPERATION starts up when MANUAL / AUTO button is pressed more than 10 seconds. During the FORCED COOLING OPERATION, it keeps operation regardless of detection value of room temperature sensor. Operation LED and Timer LED blinks simultaneously while the unit is on the FORCED COOLING OPERATION. It is released after 60 minutes from starting time.
Cooling
Heating
1-23. FORCED COOLING OPERATION (When using the Wireless RC)
1-24. COMPRESSOR STOP CONTROL
When the detection value of outdoor temperature sensor is lower than temperature in the table below, the compressor is stopped.
(Table 14 : Operation temperature of compressor stop control)
Operation temperature
Temperature
01-31
The fan motor for Fresh Air is operated in synchronization with the indoor fan operation as shown in Figure 20.
The External Electrical Heater is operated as shown in Figure 21.
1-25. FRESH AIR CONTROL (For AU/ AR type)
1-26. EXTERNAL ELECTRICAL HEATER CONTROL (For AR type)
(Fig 20 : Fresh Air control)
(Fig 21 : External Electrical Heater control)
Operation Stop
Operation Stop
Fan motor (Indoor unit)
Fan motor (for Fresh Air)
When the room temperature rises
When the room temperature drops
Ts : Setting temperature
Heater : OFF
Heater : ON
Heater : OFF
Ts -10°C
Ts -1°C
Ts -3°C
Ts -12°C
When the compressor stop, External Electrical Heater is OFF.
It operates only in Heating mode and when the indoor fan operates. (However, S-Low is excluded)
01-32
1-27. DRAIN PUMP OPERATION (For AU/ AR type)
1. When the compressor starts, the drain pump starts simultaneously.
2. The drain pump operates continuously for 3 minutes after the compressor is turned off.
3. When the compressor stops by the "Anti- freezing protection", the drain pump is turned off in 1 hour after the compressor stops.
4. When the water level in the drain pan rises up and then the float switch functions: The compressor, indoor and outdoor fan motor operation are stopped. Drain pump operates continuously for 3 minutes after the float switch is turned off. (Almost condensing water may be drained)
5. When the float switch turns ON continuously for 3 minutes, "FAILURE INDICATION" operates.
(It is necessary to turn off power for release it. )
6. When the float switch turns OFF less than 3 minutes, the unit starts Cooling operation.
1 2
1.When the water level in the drain pan rises up and then the float switch functions: Drain pump operates continuously for 3 minutes after the float switch is turned off. (Almost condensing water may be drained)
2. When the float switch turns ON continuously for 3 minutes, "FAILURE INDICATION" operates. Thereafter, even if the float switch turns OFF, the "FAILURE INDICATION" is not released. (It is necessary to turn off power for release it. )
1
During Cooling / Dry mode
3 minutes
ON OFF
ON OFF
Compressor
Drain Pump
3 minutes
3 minutes ST
ON OFF
ON OFF
ON OFF
ON OFF
Float Switch
Compressor
Indoor Fan
Drain Pump
3 minutes
ON OFF
ON OFF
Float Switch
Drain Pump
During Heating / Fan mode / Stop operation
<Float Switch turns OFF less than 3 minutes>
Less than 3 minutes
.
.
The indoor unit fan motor operates after the float switch is turned off.
3
(Fig 22 : Detail of Drain Pump Operation)
1-28. LOW NOISE OPERATION
1-29. PEAK CUT OPERATION
01-33
(Table 16 : Outline of PEAK CUT OPERATION)
Low Noise Mode
MODE1
MODE2
Cooling
Heating
Cooling
Heating
Upper fan Lower fan Upper fan Lower fan Upper fan Lower fan Upper fan Lower fan
520 520 520 520 520 520 520 520
40
46
29
36
52
52
32
37
57
55
36
38
58
58
37
39
Outdoor Fan Speed ( rpm )
Compressor Frequency ( rps )
AO *G36LATT AO *G45LATT AO *G54LATT AOTG60LATT
MODE1 MODE2 MODE3 MODE4
100%75%50%
0%
Forced thermostat-OFF
*The performance drops when operating in the LOW NOISE OPERATION.
The Current Value is limited to reduce the power consumption by External Input. During the PEAK CUT OPERATION, "CURRENT OVERLOAD OPERATION", "ECONOMY OPERATION" and "LOW NOISE OPERATION" are effective, and the outdoor unit operates by lowest current of them. However, this function becomes invalid during DEFROST OPERATION.
*Percentage is rated electrical power ratio
The compressor frequency and the outdoor unit fan speed are limited to reduce the operation noise by External Input. During the LOW NOISE OPERATION, "CURRENT OVERLOAD OPERATION", "ECONOMY OPERATION" and "PEAK CUT OPERATION" are effective, and the outdoor unit operates by lowest current of them. However, during the DEFROST OPERATION, the compressor operates by the frequency for DEFROST OPERATION.
( Table 15 : Detail of LOW NOISE OPERATION)
01-34
1-30. DESCRIPTION OF DISPLAY UNIT
Display lamp
Function or operation method
(1) POWER / MODE
Green
Lights on while power on Local setting in outdoor unit or error code is displayed with blink.
(2) ERROR
Red
Blinks during abnormal air-conditioner operation. Number of blinks indicates kind of error and error code is displayed.
(3) TEST RUN (L1) Orange Lights on during test operation.
(4) PUMP DOWN (L2)
Orange
Lights on during pump down operation.
(5) LOW NOISE MODE (L3, L4)
Orange
Lights on during “Low noise” function when local setting is activated. (Lighting pattern of L3 and L4 indicates low noise level)
(6) PEAK CUT (L5, L6, L7)
Orange
Lights on during “Peak cut” function when local setting is activated. (Lighting pattern of L5, L6 and L7 indicates peak cut level)
SW1 (DIP-SW) SW2 SW3 SW4 SW5 SW6
(1) (2) (3) (4) (5) (6)
LED DISPLAY
Various settings can be adjusted by changing Dip switches and Push switches on the board of the outdoor unit. ( Excerpt from the "INSTALATION MANUAL" )
Switch
Function or operation method
SW1DIP-SWITCH
For selecting COOLING or HEATING during test operation. Positions 2 to 4 of Dip switch are not used.
SW2 To switch between “Local setting” and “Error code display”.
SW3
To switch between the individual “Local settings” and the “Error code displays”.
SW4
To fix the individual “Local settings ” and the “Error code displays”.
SW5
EXIT
SW6 To start the pump down operation.
Dip switches 1 to 4 at shipment from the factory are set as follows.
DIP switch
1 2 3 4
COOL OFF OFF OFF
MODE
SELECT
ENTER / TEST RUN
EXIT / INITIALIZE
PUMP DOWN
PUSH SWITCH
1-30-1 Layout of Display Unit
01-35
In this mode, the "Operation Condition" and "Error Code" can be displayed by Push Switch on outdoor unit PCB
LED
NO.
Power / Mode
LED
Display Item
L1
L2 L3 L4
Compressor frequency Upper fan speed (Outdoor unit) Lower fan speed (Outdoor unit) EEV pulse Pressure sensor value (Low pressure range) Pressure sensor value (High pressure range) Outdoor air temperature sensor value Discharge temperature sensor value Heat-exchanger temperature sensor value (Middle) Current value
1
Present Value Of Each Item
1
Compressor accumulated time Newest error code Error code before 1 time
2
Error Code
2
Error code before 2 times
(Table :18 Procedure for Present Value)
Procedure
Operation
Power Mode
Error L1 L2 L3 L7L6L5L4
1
2
3
4
During status display, press the MODE SWITCH 1 time. (Status display : Outdoor unit is stopping and no error)
When the EXIT SWITCH is pressed, this mode ends and returns to the status display.
Selecting display items can be done by pressing the SELECT SWITCH. (Return to Procedure 3)
Press the ENTER SWITCH. (Data is displayed by lighting LED. Refer to Table : 19)
When the POWER / MODE LED blinking 1 time, press the ENTER SWITCH.
1
1
1
1
DATA
: Light ON: Light OFF : Blinking
: Blinking
1 : 1 Time Blinking
1-30-2 Display mode
(Table :17 Display pattern)
: Light ON: Light OFF n : n Time Blinking
5
1
Press the SELECT SWITCH and adjust to DISPLAY ITEM (from L1 to L4) that you want to confirm. (Refer to Table 17)
(Table 19 : Detail of LED Display Data)
: Light ON: Light OFF 1 : 1 Time Blinking
Item No,
Display Item
Power Mode
Error L1 L2 L3 L7L6L5L4
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Compressor Frequency ( 0 ~ 95rps )
Outdoor Unit Upper Fan Speed ( 0 ~ 900rpm )
Outdoor Unit Lower Fan Speed ( 0 ~ 900rpm )
EEV Pulse ( 0 ~ 480pulse )
Pressure sensor value <Low pressure range> ( 0 ~ 2.1MPa )
Pressure sensor value <High pressure range> ( 2.1 ~ 4.2MPa )
Check the Low Pressure Range if it is displayed [ ~ 2.1 ]
Check the High Pressure Range if it is displayed [ 1.81 ~ 2.1 ]
0 1 ~ 15 16 ~ 30 31 ~ 45 46 ~ 60 61 ~ 75 76 ~ 90 90 ~ 95
0 1 ~ 150 151 ~ 300 301 ~ 450 451 ~ 600 601 ~ 750 751 ~ 900 901 ~ 0 1 ~ 150 151 ~ 300 301 ~ 450 451 ~ 600 601 ~ 750 751 ~ 900 901 ~ 0 1 ~ 80 81 ~ 160 161 ~ 240 241 ~ 320 321 ~ 400 401 ~ 480 481 ~
~ 0.0
0.01 ~ 0.3
0.31 ~ 0.6
0.61 ~ 0.9
0.91 ~ 1.2
1.21 ~ 1.5
1.51 ~ 1.8
1.81 ~ 2.1 ~ 2.1
2.11 ~ 2.4
2.41 ~ 2.7
2.71 ~ 3.0
3.01 ~ 3.3
3.31 ~ 3.6
3.61 ~ 3.9
3.91 ~ 4.2
01-36
1
2
3
4
5
6
: Light ON: Light OFF 1 : 1 Time Blinking
Item No,
Display Item
Power Mode
Error L1 L2 L3 L7L6L5L4
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Outdoor Air Temperature ( -30 ~ 70°C )
Discharge Temperature ( -30 ~ 120°C )
Heat-exchanger Temperature <Middle> ( -30 ~ 80°C )
Current ( 0 ~ 10A )
Compressor Accumulated Time ( H )
~ -15
-15 ~ -5
-5 ~ 5 5 ~ 15 15 ~ 25 25 ~ 35 35 ~ 45
45 ~ ~ 55 55 ~ 65 65 ~ 75 75 ~ 85 85 ~ 95 95 ~ 105 105 ~ 115 115 ~ ~ 53 53 ~ 55 55 ~ 57 57 ~ 59 59 ~ 61 61 ~ 63 63 ~ 65 65 ~
~ 0.0
0.0 ~ 1.5
1.5 ~ 3.0
3.0 ~ 4.5
4.5 ~ 6.0
6.0 ~ 7.5
7.5 ~ 9.0
9.0 ~ 0 0 ~ 10000 10000 ~ 20000 20000 ~ 30000 30000 ~ 40000 40000 ~ 50000 50000 ~ 60000 60000 ~
7
8
9
01-37
<Round up by 1 hour>
10
11
01-38
In this mode, the history of abnormality that occurred in the past can be confirmed.
(Table : 20 Procedure for History Mode )
Procedure Operation
Power Mode
1
2
3
4
During status display, press the MODE SWITCH 2 times. (Status display : Outdoor unit is stopping and no error)
Press the ENTER SWITCH, Error code is displayed by lighting LED. (Refer to Table : 21)
When the POWER / MODE LED blinking 2 times, press the ENTER SWITCH.
: Light ON: Light OFF
: Light ON
: Blinking 2 : 2 Times Blinking
n : n Times Blinking
1 ~ : 1~ 15 Times Blinking 15
1-30-3 Error history mode
(Table : 21 Error Code)
Error L1 L2 L3 L7L6L5L4
2
2
2
2
n n
2
Press the SELECT SWITCH and adjust to DISPLAY ITEM (from L1 to L4) that you want to confirm. (Refer to Table : 17)
POWER
ERROR
TEST
RUN
PUMP DOWN
LOW NOISE PEAK CUT
Description
MODE
(L1) (L2) (L3) (L4) (L5) (L6) (L7)
1 1
Serial forward transmission error immediately after operation Serial forward transmission error during operation
2 2
Indoor unit capacity error
5 15
Indoor unit error
6 1
Over voltage Power supply frequency error
2
Outdoor unit PCB model information error PFC communication error
3
Inverter error
4
PFC AD detection error PFC hardware error
5
IPM error (Trip terminal L error)
8
Rush current limiting resister temp rise protection
7 1
Discharge temp. sensor error
2
Compressor temp. sensor error
3
Heat Ex. middle temp. sensor error Outdoor unit Heat Ex. liquid temp. sensor error
4
Outdoor temp. sensor error
7
Heat sink temp. sensor error PFC heat sink temp. sensor error
8 4
Current sensor 1 error (stoppage permanently)
6
High pressure switch 1 error Pressure sensor error
9 4
Trip detection (stoppage permanently)
5
Compressor motor control error (stoppage permanently) Compressor motor loss of synchronization (stoppage permanently)
7
Outdoor unit fan motor 1 error (Duty error)
8
Outdoor unit fan motor 2 error (Duty error)
9
4-way valve error
10 1
Discharge temp. 1 error (stoppage permanently)
3
Compressor 1 temp. error (stoppage permanently)
5
Low pressure error
Note. Selecting display items can be done by pressing the SELECT SWITCH. (Return to Procedure 3) When the EXIT SWITCH is pressed, this mode ends and returns to the status display.
01-39
1-30-4 ERROR CHECK MODE
In this mode, abnormality that is occurring now can be confirmed.
Confirm Chapter 2 " TROUBLE SHOOTING" in detail.
(Table : 22 Procedure for Error Check Mode )
(Table : 23 Demand Response Mode )
Procedure Operation
Power Mode
1
2
3
Check that the "ERROR" LED blinking (Hi-speed), and then short press the ENTER SWITCH 1 time.
When the MODE SWITCH is pressed for more than 3 seconds, the Error history is cleared.
Error code is displayed by lighting LED. (Refer to Table : 21)
: Light ON: Light OFF 2 : 2 Times Blinking
n : n Times Blinking
Error L1 L2 L3 L7L6L5L4
2
2 2 2 2 2 2 2 2 2
n n
Blinking Hi-speed
1-31. DEMAND RESPONSE OPERATION (For Aust model)
This product is designed to be compatible with Air Conditioning Demand Response program. To utilize the function, Demand Response (DR) adapter kit that interconnects your air conditioner and Demand Response Enabling Device (DRED) needs to be installed in your air conditioning system, and you need a separate arrangement.
When your electricity supplier activates one of the following 3 DR modes, the air conditioner switches over to the appropriate operation, and the OPERATION indicator (green) on the indoor unit blinks to inform you it has been entered to the DR mode.
DR mode Description of operation in this mode
DR mode 1
Compressor off.
DR mode 2
The air conditioner continues to cool or heat during the Demand Response event, but the electrical energy consumed by the air conditioner in a half hour period is not more than 50% of the total electrical energy that would be consumed if operating at the rated capacity in a half hour period.
DR mode 3
The air conditioner continues to cool or heat during the Demand Response event, but the electrical energy consumed by the air conditioner in a half hour period is not more than 75% of the total electrical energy that would be consumed if operating at the rated capacity in a half hour period.
OPERATION indicator (Indoor unit)
Blinking pattern and the interval are as follows:
The indicator will keep blinking until the unit finishes the function.
Shape, number, and the arrangement of the indicators are unit-dependent. Some indoor units may not have the indicators unless the optional control panel or IR receiver kit has been installed.
Notes:
ON (4 seconds) OFF (0.5 seconds)
ON (0.5 seconds)OFF (0.5 seconds)
Note. When the EXIT SWITCH is pressed, this mode ends and returns to the status display.
2. TROUBLE SHOOTING
AIR CONDITIONER
3 phase type
Single / Simultaneous operation multi type
2. TROUBLE SHOOTING
02-01
2-1 ERROR DISPLAY
2-1-1 INDOOR UNIT AND WIRED REMOTE CONTROLLER DISPLAY
1. ERROR DISPLAY Please refer the blinking pattern as follows. The Operation, Timer, Economy lamps operate as follows according to the error contents.
Manual auto switch error
Room temp. sensor error
Indoor unit PCB model information error
Wired remote controller communication error
Error Contents
4 times
2 times
3 times
3 times
5 times
2 times1 time
Blinking Hi-speed
Blinking Hi-speed
Blinking Hi-speed
Blinking Hi-speed
Blinking Hi-speed
Blinking Hi-speed
Blinking Hi-speed
Blinking Hi-speed
Blinking Hi-speed
Blinking Hi-speed
Blinking Hi-speed
Blinking Hi-speed
Blinking Hi-speed
Blinking Hi-speed
Blinking Hi-speed
Blinking Hi-speed
Blinking Hi-speed
Blinking Hi-speed
Blinking Hi-speed
Blinking Hi-speed
Blinking Hi-speed
Blinking Hi-speed
Blinking Hi-speed
Blinking Hi-speed
Blinking Hi-speed
Blinking Hi-speed
Blinking Hi-speed
Blinking Hi-speed
Blinking Hi-speed
Blinking Hi-speed
Blinking Hi-speed
Blinking Hi-speed
1 time1 time
Trouble shooting
Economy
(Green)
Timer (Orange)
Operation
(Green)
1 time
Serial communication error
Indoor unit fan motor error
Indoor unit Heat Ex. middle temp. sensor error
4 times 2 times
1 time5 times
4 times
7 times
6 times
1 time
7 times 3 times
7 times 4 times
2 times
7 times
PFC circuit error
Discharge temp. sensor error
Outdoor unit Heat Ex. liquid temp. sensor error
Outdoor temp. sensor error
Compressor temp. sensor error
1,2
3
4
5
6
7
8
9
10
11
12
13
4,5,6,7,9,12,13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
7 times 7 times
Heat sink temp. sensor error
8 times 4 times
Current sensor error
8 times 6 times
Pressure sensor error
10 times 3 times
Compressure temp. error
10 times 5 times
Low pressure error
5 times
9 times
9 times
7 times
Compressor rotor position detection error (permanent stop)
Outdoor unit fan motor 1 error
9 times 8 times
Outdoor unit fan motor 2 error
4 times9 times
9 times 9 times
4-way valve error
1 time10 times
Discharge temp. error
Trip detection
5 times6 times
Trip terminal L error
Indoor Unit Display
Wired Remote Controller Display
11
12
21
22
24
27
32
35
41
42
51
53
5U
62
63
64
65
71
72
73
74
77
84
86
94
95
97
98
99
A1
A3
A5
Indoor unit capacity error
2 times2 times
Primary unit, secondary unit setup error
7 times2 times
Connection unit number error (indoor secondary unit)
4 times2 times
Unit number or Refrigerant circuit address setting error
1 time2 times
2 times6 times
Outdoor unit main PCB model information error or communication error
3 times5 times
Drain pump error
15 times5 times
Indoor unit error
3 times
6 times
Inverter error
02-02
When " Er " in Temperature Display is displayed, inspection of the air conditioning system is necessary. Please consult authorized service personnel.
2-1-2 WIRED REMOTE CONTROLLER DISPLAY
1. SELF - DIAGNOSIS
SUMOTUWETHFR SA
Unit number (usually 0)
Error code
ex. Self-diagnosis check
2. ERROR CODE HISTORY DISPLAY
Up to 16 memorized error codes may be displayed for the indoor unit connected to the remote controller.
1. Stop the air conditioner operation.
2. Press the SET TEMPERATURE buttons , simultaneously for 3 seconds or more to start the self-diagnosis.
4. Press the SET TEMPERATURE buttons , simultaneously for 3 seconds or more or there is no key input for 60 seconds to stop the display.
3. Press the SET TEMPERATURE button to select the error history number.
SU MO TU WE TH FR SA
Error code
Error history number
01234567
FEdcbA98
ı
ı
Lower
Raise
Trouble shooting 1 OUTDOOR UNIT Error Method:
Detective Actuators: Detective details:
Forecast of Cause:
OK
Indicate or Display:
Refer to error code table.
YESYES
NO
OK
Serial communication error (Serial reverse transfer error)
Outdoor unit Main PCB Outdoor unit fan motor
1. Connection failure 2. External cause 3. Main PCB failure 4. Outdoor unit fan motor failure
Check Point 1-1 : Reset the power and operate
Does error indication reappear?
Check Point 1-2 : Check external cause such as noise
Check if the ground connection is proper. Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
Check Point 2 : Check connection
Check any loose or removed connection line of between indoor unit and outdoor unit.
>> If there is an abnormal condition, correct it by referring to Installation Manual or Data & Technical Manual.
Check connection condition in control unit. (If there is loose connector, open cable or mis-wiring)
Check Point 3 : Check the voltage of power supply
Check the voltage of power supply
>> Check if AC198(AC220V-10%) - 264V(AC240V+10%) appears at outdoor unit terminal 1 - 2, L1 - N, L2 - N, L3 - N.
Check Point 4 : Check serial signal (Reverse transfer signal)
Check serial signal (Reverse transfer signal)
>> Check if indicated value swings between AC70V and AC130V at outdoor unit terminal 2 - 3. >> If it is abnormal, Check the parts as follows.
- Outdoor unit fan motor (PARTS INFORMATION 5) >> If Outdoor fan motor is abnormal, replace Outdoor unit fan motor and Main PCB. >> If the parts are normal, replace Main PCB.
When the indoor unit cannot receive the serial signal from Outdoor unit more than 2minutes after power ON, or the indoor unit cannot receive the serial signal more than 15seconds during normal operation.
02-03
1 2 3
WHITE
BLACK
+
-
2-2 TROUBLE SHOOTING WITH ERROR CODE
RED
Trouble shooting 2 INDOOR UNIT Error Method:
Detective Actuators: Detective details:
Forecast of Cause:
OK
Indicate or Display:
Refer to error code table.
YESYES
NO
OK
Serial communication error (Serial forward transfer error)
Indoor unit Controller PCB Indoor unit Power PCB
1. Connection failure 2. External cause 3. Controller PCB failure 4. Power PCB failure
Check Point 1-1 : Reset the power and operate
Does error indication reappear?
Check Point 1-2 : Check external cause such as noise
Check if the ground connection is proper. Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
Check Point 2 : Check connection
Check any loose or removed connection line of between indoor unit and outdoor unit.
>> If there is an abnormal condition, correct it by referring to Installation Manual or Data & Technical Manual.
Check connection condition in control unit. (If there is loose connector, open cable or mis-wiring)
Check Point 3 : Check the voltage of power supply
Check the voltage of power supply
>> Check if AC198(AC220V-10%) - 264V(AC240V+10%) appears at outdoor unit terminal 1 - 2, L1 - N, L2 - N, L3 - N.
Check Point 4 : Check serial signal (Forward transfer signal)
Check serial signal (Forward transfer signal)
>> Check if indicated value swings between AC70V and AC130V at outdoor unit terminal 2 - 3. >> If it is abnormal, replace Controller PCB and Power PCB.
When the indoor unit cannot properly receive the serial signal from outdoor unit for 10 seconds or more.
02-04
1 2 3
WHITE
BLACK
+
-
RED
Trouble shooting 3 INDOOR UNIT Error Method:
Detective Actuators: Detective details:
Forecast of Cause:
Check Point 2 : Check Wired Remote Controller and Controller PCB
Check Point 1 : Check the connection of terminal
OKOK
Indicate or Display:
Wired remote controller communication error
Indoor unit Controller PCB Wired remote controller
1. Connection failure 2. Wired remote controller failure 3. Controller PCB failure
Check & correct the followings. Check the connection of terminal between Wired Remote Controller and indoor unit, and check if there is a disconnection of the cable.
Check voltage at connector of Wired remote controller of Controller PCB. (Power supply to Wired remote controller) >> AR* G45/ 54LHTA : CN6, 1 - 3 pin >> ARTG45/ 54LHTB, 60LHTA : CN140, 1 - 3 pin >> Other models : CN14, 1 - 3 pin
If it is DC12V, Wired Remote Controller is failure. (Controller PCB is normal)
>> Replace Wired Remote Controller
If it is DC 0V, Controller PCB is failure.
>> Replace Controller PCB
Upon receiving the signal more than 1 time from Wired remote controller, but the same signal has not been received more than 1 minute.
02-05
Refer to error code table.
Trouble shooting 4 INDOOR UNIT Error Method:
Detective Actuators: Detective details:
Forecast of Cause :
OK
Indicate or Display:
Unit number or Refrigerant circuit address setting error
Indoor unit Controller PCB
Check the DIP-SW of controller setting.
>> If there is an abnormal condition, correct it by referring to Installation Manual or Data & Technical Manual. >> Upon correcting incorrect setting, reset the power.
1. Dip SW incorrect setting 2. Controller PCB failure
Check Point 1 : Check the DIP-SW of Controller PCB setting
When the addresses set in indoor units are not consecutive in the same refrigerant circuit.
02-06
Refer to error code table.
Check Point 2 : Replace Controller PCB
If Check Point 1 do not improve the symptom, replace Controller PCB.
02-07
Trouble shooting 5 OUTDOOR UNIT Error Method:
Indicate or Display:
Indoor unit capacity error
Refer to error code table.
Detective Actuators: Detective details:
Forecast of Cause :
OKOK
Outdoor Unit Main PCB
When the total capacity of indoor units does not match outdoor capacity while 3 minutes after power-on.
1. The selection of indoor units is incorrect 2. Main PCB failure
Check Point 1 : Check the total capacity of indoor unit
Check the total capacity of the connected indoor units.
>> If abnormal condition is found, correct it by referring to Installation Manual or Data & Technical Manual.
Check Point 2 : Replace Main PCB
If Check Point 1 do not improve the symptom, replace Main PCB.
Trouble shooting 6 INDOOR UNIT Error Method:
Detective Actuators: Detective details:
Forecast of Cause :
Indicate or Display:
Connection unit number error (indoor secondary unit)
Indoor unit
Check the indoor unit number connection.
>> If there is an abnormal condition, correct it by referring to Installation Manual or Data & Technical Manual. >> Upon correcting incorrect setting, reset the power.
1. Indoor unit connection failure
Check Point 1 : Check the indoor unit number connection
When there are 4 or more indoor units in the same refrigerant system.
02-08
Refer to error code table.
Trouble shooting 7 INDOOR UNIT Error Method:
Detective Actuators: Detective details:
Forecast of Cause :
OK
Indicate or Display:
Primary unit, secondary unit setup error
Indoor unit Controller PCB
Check wiring connection condition of all slave indoor units. Check wiring connection condition in same refrigerant system.
>> If there is an abnormal condition, correct it by referring to Installation Manual or Data & Technical Manual. >> Upon correcting incorrect setting, reset the power.
1. Mis-wiring 2.Indoor unit address setting incorrect 3. Controller PCB failure
Check Point 1 : Check wiring connection condition
When there is no master unit in the same refrigerant system. When 2 or more master units are connected in the same reffigerant system. When slave indoor unit receives serial reverse transfer signal. When address [0] indoor unit is set as slave unit.
02-09
Refer to error code table.
Check Point 3 : Replace Controller PCB
If Check Point 1, 2 do not improve the symptom, replace Controller PCB.
Check the DIP-SW of controller setting.
>> If there is an abnormal condition, correct it by referring to Installation Manual or Data & Technical Manual. >> Upon correcting incorrect setting, reset the power.
Check Point 2 : Check the DIP-SW of Controller PCB setting
OK
Detective Actuators: Detective details:
Forecast of Cause:
Check Point 3 : Replace Controller PCB
Check Point 2 : Check connections condition in control unit
YESYES
NO
Trouble shooting 8 INDOOR UNIT Error Method:
Indicate or Display:
Indoor unit PCB model information error
Indoor unit Controller PCB
1. External cause 2. Defective for connection in controller unit 3. Controller PCB failure
Check Point 1-1 : Reset power supply and operate
Does error indication show reappear?
Check all connectors. (loose connector or incorrect wiring) Check any shortage or corrosion on PCB.
If Check Point 1, 2 do not improve the symptom, replace Controller PCB.
When power is on and there is some below case.
1. When model information of EEPROM is incorrect
2. When the access to EEPROM failed
02-10
Refer to error code table.
Check Point 1-2 : Check external cause such as noise
Check if the ground connection is proper. Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
OK
02-11
Trouble shooting 9 INDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators: Detective details:
Forecast of Cause :
OKOK
Manual auto switch Error
Indoor unit Controller PCB Indicator PCB Manual auto switch
When the Manual Auto Switch becomes ON for consecutive 60 or more seconds.
1. Manual auto switch failure 2. Controller PCB and Indicator PCB failure
Check Point 1 : Check the Manual auto switch
Check if Manual auto switch is kept pressed. Check ON/OFF switching operation by using a meter.
>> If Manual auto switch is disabled (on/off switching), replace it.
Check Point 2 : Replace Controller PCB and Indicator PCB
If Check Point 1 do not improve the symptom, replace Controller PCB and Indicator PCB.
Refer to error code table.
Trouble shooting 10 INDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators: Detective details:
Forecast of Cause :
Check Point 2 : Remove connector and check thermistor resistance value
Check Point 1 : Check connection of connector
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
OK
OK
Room temp. sensor error
Indoor unit Controller PCB Room temperature thermistor
When Room Temperature Thermistor open or short-circuit is detected at power ON.
1. Connector connection failure 2.Thermistor failure 3. Controller PCB failure
Check if connector is removed. Check if connector is erroneous connection. Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
Thermistor characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Make sure circuit diagram of indoor unit and check terminal voltage at thermistor (DC5.0V)
If the voltage does not appear, replace Controller PCB.
02-12
Refer to error code table.
6.5
35
8.0
30
10.012.515.820.225.933.6
Resistance Value ( )
2520151050
58.2
-10
44.0
-5
Temperature (°C)
Resistance Value ( )
4.35.3
4540
Temperature (°C)
H/E (MID) Thermistor
Room Temp. Thermistor
Other model
BLACK BLACK
121
2
11 22
11 22
CN5
CN8
GRAY GRAY
1 2
CN7
H/E (MID) Thermistor
Room Temp. Thermistor
AR*G45/ 54LHTA
BLACK BLACK
121
2
11 22
CN8
GRAY GRAY
CN7
H/E (MID) Thermistor
Room Temp. Thermistor
ARTG45/ 54LHTB, 60LHTA
BLACK
BLACK BLACK
BLACK
121
2
11 22
CN114
CN110
H/E (MID) Thermistor
Room Temp. Thermistor
AU*G36/ 45/ 54LRLA
RED RED
121
2
11 22
CN5
CN8
BLACK BLACK
1 2
CN7
121
2
121
2
1 2
H/E (MID) Thermistor
Room Temp. Thermistor
BLACK BLACK
CN5
CN8
GRAY GRAY
CN7
BLACK BLACK
AB*G18LVTB, 22/ 24LVTA
Trouble shooting 11 INDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators: Detective details:
Forecast of Cause :
Check Point 2 : Remove connector and check thermistor resistance value
Check Point 1 : Check connection of connector
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
OK
OK
Indoor unit Heat Ex. middle temp. sensor error
Indoor unit Controller PCB
Heat exchanger temperature thermistor (Middle)
When Heat exchanger temperature thermistor (Middle) open or short-circuit is detected at power ON.
1. Connector connection failure 2.Thermistor failure 3. Controller PCB failure
Check if connector is removed. Check if connector is erroneous connection. Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
Thermistor characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Make sure circuit diagram of indoor unit and check terminal voltage at thermistor (DC5.0V)
If the voltage does not appear, replace Controller PCB.
02-13
Refer to error code table.
Resistance Value ( )
Temperature (°C)
Resistance Value ( )
Temperature (°C)
1131.9 579.6 312.3 233.2 176.0 134.2 103.3 80.3 62.9
49.7 39.6 31.7 25.6 20.8 17.1 14.1 11.6 10.4
-30 -20 -10 -5 0 5 10 15 20
25 30 35 40 45 50 55 60 63
H/E (MID) Thermistor
Room Temp. Thermistor
Other model
BLACK BLACK
121
2
11 22
11 22
CN5
CN8
GRAY GRAY
1 2
CN7
H/E (MID) Thermistor
Room Temp. Thermistor
AR*G45/ 54LHTA
BLACK BLACK
121
2
11 22
CN8
GRAY GRAY
CN7
H/E (MID) Thermistor
Room Temp. Thermistor
ARTG45/ 54LHTB, 60LHTA
BLACK
BLACK BLACK
BLACK
121
2
11 22
CN114
CN110
H/E (MID) Thermistor
Room Temp. Thermistor
AU*G36/ 45/ 54LRLA
RED RED
121
2
11 22
CN5
CN8
BLACK BLACK
1 2
CN7
121
2
121
2
1 2
H/E (MID) Thermistor
Room Temp. Thermistor
BLACK BLACK
CN5
CN8
GRAY GRAY
CN7
BLACK BLACK
AB*G18LVTB, 22/ 24LVTA
Detective Actuators: Detective details:
Forecast of Cause:
Check Point 1 : Check rotation of Fan
Check Point 2 : Check ambient temp. around motor
OK
OK
Indoor unit Controller PCB Indoor unit Power PCB Indoor fan motor
1. Fan motor failure 2. Motor protection by surrounding temperature rise
3. Power PCB failure 4. Controller PCB failure
Check if the Fan motor is lock. (Can the Fan be rotated by hand when operation is off.) Check the Fan loosening. (Lock-nut loosening, defective propeller fan)
>> If Fan motor or bearing is abnormal, replace it.
Check excessively high temperature around the motor. (If there is any surrounding equipment that causes heat)
>> Upon the temperature coming down, restart operation.
When the condition that actual rev. of Indoor Fan is 1/3 or less. Or the condition of fan speed is 0rpm is continued more than 56 seconds.
02-14
Trouble shooting 12 INDOOR UNIT Error Method:
Indicate or Display:
Indoor unit fan motor error
Refer to error code table.
OK
Check Point 4 : Replace Power PCB and Controller PCB
If Check Point 1~3 do not improve the symptom, replace Power PCB and Controller PCB.
Check Point 3 : Check Indoor unit fan motor
Check Indoor unit fan motor. (PARTS INFORMATION 4)
>>If Indoor unit fan motor is abnormal, replace Indoor unit fan motor.
Check Point 2 : Check connector (CN9) and wire
Check Point 1 : Check Float switch
Check Point 3 : Check Drain hose
ONON OFFOFF
OKOK
OKOK
Trouble shooting 13 INDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators: Detective details:
Forecast of Cause :
Drain pump error
Indoor unit Controller PCB Float switch
When Float switch is ON for more than 3 minutes.
1. Float switch failure 2. Shorted connector and wire 3. Drain hose clog 4. Controller PCB failure
Check operation of float switch. (Any blocking by dust, etc.)
>> If Float switch does not operate, replace it.
Check loose contact of CN9 and shorted wire (Pinched wire).
>> Replace Float switch if the wire is shorted (Pinched wire)
If clogged, clear the clog.
02-15
Refer to error code table.
Check Point 4 : Replace Controller PCB
OKOK
If Check Point 1 ~ 3 do not improve the symptom, replace Controller PCB.
Check clogged Drain hose.
02-16
Trouble shooting 14 INDOOR UNIT Error Method:
Indicate or Display:
Outdoor unit main PCB model information error or communication error
Refer to error code table.
Detective Actuators:
Detective details:
Forecast of Cause:
Check Point 3 : Replace Main PCB
Check Point 2 : Check Indoor unit electric components
YESYES
NO
Outdoor unit Main PCB
1. External cause 2. Defective connection of electric components 3. Main PCB failure
Check Point 1-1 : Reset Power Supply and operate
Does Error indication show again?
Check Point 1-2 : Check external cause such as noise
Check if the ground connection is proper. Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
Note : EEPROM
EEPROM(Electronically Erasable and Programmable Read Only Memory) is a non­volatile memory which keeps memorized information even if power is turned off. It can change the contents electronically. To change the contents, it uses higher voltage than normal, and it can not change a partial contents. (Rewriting shall be done upon erasing the all contents.) There is a limit in a number of rewriting.
If Check Point 1,2 do not improve the symptom, replace Main PCB.
Check all connectors. (loose connector or incorrect wiring)
Check any shortage or corrosion on PCB.
When power is on and there is some below case. When model information of EEPROM is incorrect. When the access to EEPROM failed.
OK
Trouble shooting 15 OUTDOOR UNIT Error Method:
Detective Actuators: Detective details:
Forecast of Cause :
OK
Indicate or Display:
Inverter error
Outdoor unit Main PCB Outdoor unit Inverter PCB
Check if the terminal connection is loose. Check if connector is removed. Check if connector is erroneous connection. Check if cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
1. Connection failure 2. Main PCB failure 3. Inverter PCB failure
Check Point 1 : Check connections in control unit
When there is communication error between Main PCB and Inverter PCB. When "Inverter PCB cement resistor difference voltage between both ends" detects 18 V and above twice continuously.
02-17
Refer to error code table.
Check Point 2 : Replace Main PCB and Inverter PCB
If Check Point 1 do not improve the symptom, replace Main PCB and Inverter PCB.
Trouble shooting 16 OUTDOOR UNIT Error Method:
Detective Actuators: Detective details:
Forecast of Cause :
OK
Indicate or Display:
PFC circuit Error
Outdoor unit Main PCB Outdoor unit PFC PCB
Check if the terminal connection is loose. Check if connector is removed. Check if connector is erroneous connection. Check if cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
1. Connector connection failure 2. Main PCB failure 3. PFC PCB failure
Check Point 1 : Check connections of between Main PCB and PFC PCB
When communication error between Main PCB and PFC PCB continues for 10 seconds. When PFC PCB circuit error continues for 10 seconds. When PFC PCB output voltage is more than DC760V for 30 seconds.
02-18
Refer to error code table.
Check Point 2 : Check output voltage of Main PCB
Check voltage of Main PCB. (Measure at Main PCB side connector)
>>1 pin(Brown) - 2 pin(Red) DC15V 5%
If the voltage is not correct, replace Main PCB.
OK
Check Point 3 : Replace PFC PCB
If Check Point 1, 2 do not improve the symptom, replace PFC PCB.
02-19
Trouble shooting 17 OUTDOOR UNIT Error Method:
Trip terminal L error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 1 : Replace Inverter PCB
Outdoor unit Inverter PCB
1. Inverter PCB failure
Change Inverter PCB.
When the signal from FO terminal of IPM in Inverter PCB is "L"(=0V) while the compressor stops.
Trouble shooting 18 OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators: Detective details:
Forecast of Cause :
OKOK
OKOK
Discharge temp. sensor error
Outdoor unit Main PCB Discharge pipe temperature thermistor
When Discharge pipe temperature thermistor open or short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2. Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of connector
Check if connector is removed. Check if connector is erroneous connection. Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check thermistor resistance value
Thermistor characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
02-20
Refer to error code table.
CN22
BLACK BLACK
BLACK BLACK
BLACK
BLACK
BROWN
BROWN
BROWN
BROWN
BLUE
BLUE
CN23
CN24
CN25
CN26
CN27
123
123
123
12312
1212
12
123 123
123 123
THERMISTOR ( HEAT EXCHANGER MID. )
THERMISTOR ( HEATSINK PFC )
THERMISTOR ( DISCHARGE PIPE )
THERMISTOR ( HEAT EXCHANGER OUT )
THERMISTOR ( OUTDOOR TEMP. )
THERMISTOR ( COMPRESSOR TEMP. )
Resistance Value (k )
Temperature(°C)
Resistance Value (k )
Temperature(°C)
-30 -20 -10 0 10 20 30 40 50
60 70 80 90 100 110 120
1013.1 531.6 292.9 168.6 100.9 62.5 40.0 26.3 17.8
12.3 8.7 6.3 4.6 3.4 2.6 2.0
Trouble shooting 19 OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators: Detective details:
Forecast of Cause :
OKOK
OKOK
Compressor temp. sensor error
Outdoor unit Main PCB Compressor temperature thermistor
When Compressor temperature thermistor open or short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2. Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of connector
Check if connector is removed. Check if connector is erroneous connection. Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check thermistor resistance value
Thermistor characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
02-21
Refer to error code table.
BLACK BLACK
BLACK
BLACK
BLACK
BLACK
BROWN
BROWN
BROWN
BROWN
BLUE
BLUE
123
123
123
12312
1212
12
123 123
123 123
THERMISTOR ( HEAT EXCHANGER MID. )
THERMISTOR ( HEATSINK PFC )
THERMISTOR ( DISCHARGE PIPE )
THERMISTOR ( HEAT EXCHANGER OUT )
THERMISTOR ( OUTDOOR TEMP. )
THERMISTOR ( COMPRESSOR TEMP. )
Resistance Value (k )
Temperature(°C)
Resistance Value (k )
Temperature(°C)
-30 -20 -10 0 10 20 30 40 50
60 70 80 90 100 110 120
1013.1 531.6 292.9 168.6 100.9 62.5 40.0 26.3 17.8
12.3 8.7 6.3 4.6 3.4 2.6 2.0
CN22
CN23
CN24
CN25
CN26
CN27
Trouble shooting 20 OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators: Detective details:
Forecast of Cause :
OKOK
OKOK
Outdoor unit Heat Ex. liquid temp. sensor error
Outdoor unit Main PCB
Heat exchanger temperature thermistor (MID) Heat exchanger temperature thermistor (OUT)
When Heat exchanger temperature thermistor open or short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2. Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of connector
Check if connector is removed. Check if connector is erroneous connection. Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check thermistor resistance value
Thermistor characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
02-22
Refer to error code table.
BLACK BLACK
BLACK BLACK
BLACK
BLACK
BROWN
BROWN
BROWN
BROWN
BLUE
BLUE
123
123
123
12312
1212
12
123 123
123 123
THERMISTOR ( HEAT EXCHANGER MID. )
THERMISTOR ( HEATSINK PFC )
THERMISTOR ( DISCHARGE PIPE )
THERMISTOR ( HEAT EXCHANGER OUT )
THERMISTOR ( OUTDOOR TEMP. )
THERMISTOR ( COMPRESSOR TEMP. )
CN22
CN23
CN24
CN25
CN26
CN27
Resistance Value (k )
Temperature(°C)
Resistance Value (k )
Temperature(°C)
-30 -20 -10 0 10 20 30 40 50
60 70 80
95.6 50.3 27.8 16.1 9.6 6.0 3.8 2.5 1.7
1.2 0.8 0.6
Trouble shooting 21 OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators: Detective details:
Forecast of Cause :
OKOK
OKOK
Outdoor temp. sensor error
Outdoor unit Main PCB Outdoor temperature thermistor
When Outdoor temperature thermistor open or short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2. Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of connector
Check if connector is removed. Check if connector is erroneous connection. Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check thermistor resistance value
Thermistor characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
02-23
Refer to error code table.
BLACK BLACK
BLACK BLACK
BLACK
BLACK
BROWN
BROWN
BROWN
BROWN
BLUE
BLUE
123
123
123
12312
1212
12
123 123
123 123
THERMISTOR ( HEAT EXCHANGER MID. )
THERMISTOR ( HEATSINK PFC )
THERMISTOR ( DISCHARGE PIPE )
THERMISTOR ( HEAT EXCHANGER OUT )
THERMISTOR ( OUTDOOR TEMP. )
THERMISTOR ( COMPRESSOR TEMP. )
50
Resistance Value (k )
403020100-30 -20 -10Temperature(°C)
Resistance Value (k )
70 8060Temperature(°C)
224.3 115.2 62.3 35.2 20.7 12.6 8.0 5.2
3.5 2.4 1.6 1.2
CN22
CN23
CN24
CN25
CN26
CN27
Trouble shooting 22 OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators: Detective details:
Forecast of Cause :
OKOK
OKOK
Heat sink temp. sensor error
Outdoor unit Inverter PCB Heat sink temperature thermistor (PFC) Heat sink temperature thermistor (INV)
When Heat sink temperature thermistor open or short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2. Thermistor failure 3. Inverter PCB failure
Check Point 1 : Check connection of connector
Check if connector is removed. Check if connector is erroneous connection. Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check thermistor resistance value
Thermistor characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 3 : Check voltage of Inverter PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
If the voltage does not appear, replace Inverter PCB.
02-24
Refer to error code table.
BLACK BLACK
CN803
121
2
THERMISTOR ( HEATSINK INV.)
94.3 49.6 27.4 15.8 9.5 5.9 3.8 2.5
1.7 1.2 0.8 0.6 0.4
50
Resistance Value (k )
403020100-30 -20 -10Temperature(°C)
Resistance Value (k )
70 80 89.560Temperature(°C)
BLACK BLACK
BLACK BLACK
BLACK
BLACK
BROWN
BROWN
BROWN
BROWN
BLUE
BLUE
123
123
123
12312
1212
12
123 123
123 123
THERMISTOR ( HEAT EXCHANGER MID. )
THERMISTOR ( HEATSINK PFC )
THERMISTOR ( DISCHARGE PIPE )
THERMISTOR ( HEAT EXCHANGER OUT )
THERMISTOR ( OUTDOOR TEMP. )
THERMISTOR ( COMPRESSOR TEMP. )
CN22
CN23
CN24
CN25
CN26
CN27
Trouble shooting 23 OUTDOOR UNIT Error Method:
Detective Actuators: Detective details:
Forecast of Cause :
Check Point 3 : Check Filter PCB
YES
NO
OK
Indicate or Display:
Current sensor error
Outdoor unit Inverter PCB Outdoor unit Filter PCB
Check Point 2 : Check connections condition in control unit
Check if the terminal connection is loose. Check if connector is removed. Check if connector is erroneous connection. Check if cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
1. Connection failure 2. External cause 3. Filter PCB failure 4. Inverter PCB failure
Check Point 1-1 : Reset power supply and operate
Does error indication reappear?
After compressor runs for 1 minute or more, and while it runs in 50Hz or more. When outdoor current value (A/D data) of Input Current Sensor has detected [00H].
02-25
Refer to error code table.
Check Point 1-2 : Check external cause such as noise
Check if the ground connection is proper. Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
Check Filter PCB : CN200, 1 - 3 pin >> 40 seconds after compressor starts. If it is higher than 0.2V, Inverter PCB is failure.
>> Replace Inverter PCB
If it is lower than 0.2V, Filter PCB is failure.
>> Replace Filter PCB
Trouble shooting 24 OUTDOOR UNIT Error Method:
Detective Actuators: Detective details:
Forecast of Cause :
OK
Indicate or Display:
Pressure sensor error
Outdoor unit Main PCB Pressure sensor
Check if the terminal connection is loose. Check if connector is removed. Check if connector is erroneous connection. Check if cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
1. Connector connection failure 2. Pressure sensor failure 3. Main PCB failure
Check Point 1 : Check connection of the Pressure sensor
30 seconds or more after power-on, when pressure sensor detection value detects the condition below continuously for 30 seconds or more. Ps -0.26 or Ps 5.63 [MPa]
02-26
Refer to error code table.
Check Point 2 : Check output voltage of Main PCB
Check voltage of Main PCB. (Measure at Main PCB side connector)
>>1 pin(Red) - 3 pin(Black) DC5V 5%
BLACK
WHITE
RED
CN16
1 2 3
1 2 3
PS
PRESSURE SENSOR
If the voltage is not correct, replace Main PCB.
OK
Check Point 3 : Check output voltage of Pressure Sensor
Check voltage of Main PCB. (Measure at Main PCB side connector)
>>2 pin(White) - 3 pIn(Black) Voltage is refer to the following graph.
If the voltage is not correct, replace Presure Sensor.
4.5
0.5 05
Pressure [MPa]
Voltage [V]
>
=
>
=
Trouble shooting 25 OUTDOOR UNIT Error Method:
Detective Actuators: Detective details:
Forecast of Cause :
Check Point 4 : Check Compressor
OK
OK
Indicate or Display:
Check Point 5 : Replace Inverter PCB
OKOK
Check Point 1 : Check connections condition in control unit
Trip detection
Outdoor unit Inverter PCB Compressor
1. Connection failure 2. Outdoor fan operation failure
3. Outdoor heat exchanger clogged 4. Compressor failure 5. Inverter PCB failure
Check if the terminal connection is loose. Check if connector is removed. Check if connector is erroneous connection. Check if cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
If Check Point 1 ~ 4 do not improve the symptom, replace Inverter PCB.
When over current flows in Inverter PCB, the compressor stops. After the compressor restarts, if the same error is repeated within 40sec, the compressor stops reappear. If and repeats 5 times, the compressor stops permanently.
02-27
Refer to error code table.
Compressor check is refer to SERVICE PARTS INFORMATION 2.
>> If it is abnormal, replace compressor.
Check Point 2 : Check Outdoor heat exchanger
Is there any obstructing the air flow route? Is there any clogging of outdoor unit Heat exchanger?
>> If clogged, clear the clog.
Check Point 3 : Check Outdoor fan
OK
Check Outdoor fan motor. (Refer to Trouble shooting 27)
>> If the Fan motor is failure, replace it.
Trouble shooting 26 OUTDOOR UNIT Error Method:
Detective Actuators: Detective details:
Forecast of Cause :
Indicate or Display:
Compressor rotor position detection error (permanent stop)
Outdoor unit Inverter PCB Compressor
Check if the terminal connection is loose. Check if connector is removed. Check if connector is erroneous connection. Check if cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
1. Connector connection failure 2. Inverter PCB failure 3. Compressor failure
Check Point 1 : Check connections condition in control unit
When "compressor location detection error" is detected consecutively 5 times, within 40 seconds after start-up.
02-28
Refer to error code table.
Check Point 3 : Replace Inverter PCB
If Check Point 1 and 2 do not improve the symptom, replace Inverter PCB.
OKOK
Check Point 2 : Check Compressor
Compressor check is refer to SERVICE PARTS INFORMATION 2.
>> If it is abnormal, replace compressor.
OKOK
Trouble shooting 27 OUTDOOR UNIT Error Method:
Detective Actuators: Detective details:
Forecast of Cause:
Check Point 2 : Check ambient temp. around motor
OK
OK
OK
Indicate or Display:
Outdoor unit fan motor error
Outdoor unit Main PCB Outdoor fan motor
1. Fan motor failure 2. Motor protection by surrounding temperature rise 3. Main PCB failure
Check Point 1 : Check rotation of Fan
Check if the Fan motor is lock. (Can the Fan be rotated by hand when operation is off.) Check the Fan loosening. (Lock-nut loosening, defective propeller fan)
>> If Fan Motor or bearing is abnormal, replace it.
Check excessively high temperature around the motor. (If there is any surrounding equipment that causes heat)
>> Upon the temperature coming down, restart operation.
Check Point 3 : Check output voltage of Main PCB
If the voltage is not correct, replace Main PCB.
When outdoor fan rotation speed is less than 100rpm in 20 seconds after fan motor starts, fan motor stops. After fan motor restarts, if the same operation within 60sec is repeated consecutively 3 times, compressor and fan motor stops. If repeats 5 times in a row, compressor and fan motor stops permanently.
02-29
Refer to error code table.
BLACK
BLACK
BROWN
BROWN
RED
WHITE
YELLOW
YELLOW
WHITE
RED
CN81
CN82
12
3456
12
3456
12
3456
12
3456
FM FM
FAN MOTOR 1
( UPPER )
FAN MOTOR 2
( LOWER )
Check outdoor unit circuit diagram and the voltage. (Measure at Main PCB side connector)
Check Point 3 : Check Outdoor unit fan motor
Check Outdoor unit fan motor. (PARTS INFORMATION 5)
>>If Outdoor fan motor is abnormal, replace Outdoor fan motor and Main PCB.
Read wire DC voltage Red - Black
White - Black
15 1.5V
280V (AC220V-10%) ~ 373V (AC240+10%)
Detective Actuators:
Detective details:
Forecast of Cause :
OKOK
1. Connector connection failure 2. Thermistor failure 3. Coil failure 4. 4-way valve failure
5. Main PCB failure 6. Controller PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed. Check erroneous connection. Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 3 : Check the solenoid coil and 4-way valve
02-30
[ Solenoid coil ] Remove CN30 from PCB and check the resistance value of coil. Resistance value is about 1.4k
>> If it is Open or abnormal resistance value, replace Solenoid Coil.
[ 4-way valve ] Check each piping temperature, and the location of the valve by the temperature difference. >> If the value location is not proper, replace 4-way valve.
Check Point 5 : Replace Controller PCB
If Check Point 1- 4 do not improve the symptom, replace Controller PCB of Indoor unit .
Check Point 2 : Check thermistor of Indoor unit
Isn’t it fallen off the holder? Is there a cable pinched?
>> Check characteristics of thermistor, (Refer to Trouble shooting 10,11), If defective, replace the thermistor.
Indoor unit Controller PCB Heat exchanger temperature thermistor Room temperature thermistor 4-way valve
When the indoor heat exchanger temperature is compared with the room temperature, and either following condition is detected continuously two times, the compressor stops. Cooling or Dry operation [Indoor heat exchanger temp.] - [Room temp.] > 10
°C
Heating operation [indoor heat exchanger temp.] - [Room temp.] < -10
°C
If the same operation is repeated 5 times, the compressor stops permanently.
Trouble shooting 28 OUTDOOR UNIT Error Method:
4-way valve error
Indicate or Display:
Refer to error code table.
Check Point 4 : Check the voltage of 4-way valve
Check the CN 30 voltage of Main PCB
Check if AC198V(AC220V-10%) - 264V(AC240V+10%) appears at CN 103 of Main PCB.
[ Heating operation ]
>> If it is not voltage, Replace Main PCB.
[ Cooling operation ]
>> If it is voltage, Replace Main PCB.
OKOK
OKOK
OKOK
Trouble shooting 29 OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators: Detective details:
Forecast of Cause :
Discharge temp. error
Outdoor unit Main PCB Discharge pipe temperature thermistor
02-31
When the discharge temperature becomes higher than 115°C. When detecting it 2 times within 24 hours, the compressor stops.
Check Point 1 : Check if gas valve is open
If it is not open, open it and check the operation.
Check Point 3 : Check if gas leak or less gas
Measure gas pressure, if there is a leak, correct it.
>> If recharging refrigerant, make sure to perform vacuuming and
recharge the specified amount.
Check Point 5 : Check Outdoor heat exchanger
Is there any obstructing the air flow route? Is there any clogging of outdoor unit Heat exchanger?
>> If clogged, clear the clog.
Check Point 4 : Check Discharge pipe thermistor
Is it on the holder? Is there a cable pinched?
>> Check characteristics of thermistor (Refer to Trouble shooting 18), If defective, replace the thermistor
Check Point 2 : Check EEV and Strainer
Are EEV and Strainer open? (Refer to PARTS INFORMATION 3)
>> If EEV or Strainer is defective, replace it.
OK OK
OK
OK
OK
OK
MPa MPa
1. Valve is close 2. EEV failure 3. Gas leak, less 4. Discharge thermistor failure
5. Outdoor fan operation failure 6. Outdoor heat exchanger clogged
< Cooling mode >
< Heating mode >
Check Point 1 : Check if liquid valve is open
If it is not open, open it and check the operation.
Check Point 2 : Check EEV and Strainer
Are EEV and Strainer open? (Refer to PARTS INFORMATION 3)
>> If EEV or Strainer is defective, replace it.
Refer to error code table.
Check Point 6 : Check Outdoor fan
OK
Check Outdoor fan motor. (Refer to Trouble shooting 27)
>> If the Fan motor is failure, replace it.
Trouble shooting 30 OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators: Detective details:
Forecast of Cause :
Compressure temp. error
Outdoor unit Main PCB Compressor temperature thermistor
02-32
When the compressor temperature becomes 110°C or more. When detecting it 2 times within 24 hours, the compressor stops permanently.
Check Point 1 : Check if gas valve is open
If it is not open, open it and check the operation.
Check Point 3 : Check if gas leak or less gas
Measure Gas pressure, if there is a leak, correct it.
>> If recharging refrigerant, make sure to perform vacuuming and recharge the specified amount.
Check Point 4 : Check Compressor temperature thermistor
Is it on the holder? Is there a cable pinched?
>> Check characteristics of thermistor (Refer to Trouble shooting 19), If defective, replace the thermistor.
Check Point 2 : Check EEV and Strainer
Are EEV and Strainer open? (Refer to PARTS INFORMATION 3)
>> If EEV or Strainer is defective, replace it.
OK
OK
OK
OK
OK
OK
1. Valve is close 2. EEV failure 3. Gas leak, less 4. Compressor thermistor failure
5. Outdoor fan failure 6. Outdoor heat exchanger clogged
< Cooling mode >
< Heating mode >
Check Point 1 : Check if liquid valve is open
If it is not open, open it and check the operation.
Check Point 2 : Check EEV and Strainer
Are EEV and Strainer open? (Refer to PARTS INFORMATION 3)
>> If EEV or Strainer is defective, replace it.
MPa MPa
Refer to error code table.
Check Point 7 : Replace Main PCB
If Check Point 1 ~ 6 do not improve the symptom, replace Main PCB.
Check Point 5 : Check Outdoor heat exchanger
Is there any obstructing the air flow route? Is there any clogging of outdoor unit Heat exchanger?
>> If clogged, clear the clog.
Check Point 6 : Check Outdoor fan
OK
Check Outdoor fan motor. (Refer to Trouble shooting 27)
>> If the Fan motor is failure, replace it.
OK
Trouble shooting 31 OUTDOOR UNIT Error Method:
Detective Actuators: Detective details:
Forecast of Cause :
OK
Indicate or Display:
Low pressure error
Outdoor unit Main PCB Pressure sensor
Check if the terminal connection is loose. Check if connector is removed. Check if connector is erroneous connection. Check if cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
1. Connector connection failure 2. Pressure sensor failure 3. Main PCB failure 4. Gas leak, less
Check Point 1 : Check connections of the Pressure sensor
In cooling operation, 1 minute or more after compressor's start-up, when pressure sensor detects 0.12 MPa or less for consecutive 5 minutes.
02-33
Refer to error code table.
Check Point 2 : Check output voltage of Main PCB
Check voltage of Main PCB. (Measure at Main PCB side connector)
>>1 pin(Red) - 3 pin(Black) DC5V 5%
If the voltage is not correct, replace Main PCB.
Check Point 3 : Check if gas leak or less gas
Measure Gas pressure, if there is a leak, correct it.
>> If recharging refrigerant, make sure to perform vacuuming and recharge the specified amount.
MPa MPa
OK
OK
Check Point 4 : Replace Pressure sensor
If Check Point 1 ~ 3 do not improve the symptom, replace Pressure sensor.
BLACK
WHITE
RED
CN16
1 2 3
1 2 3
PS
PRESSURE SENSOR
Trouble shooting 32
Forecast of Cause:
NO
OK
OK
OKOK
Indoor Unit - No Power
1. Power supply failure 2. External cause
3. Electrical components defective
Check Point 1 : Check installation condition
Isn’t the breaker down? Check loose or removed connection cable.
>> If abnormal condition is found, correct it by referring to manual.
Check Point 2 : Check external cause at indoor unit and outdoor unit(Voltage drop or noise)
Instant voltage drop of ----- Check if there is abnormally large load in the same power supply power supply system. Momentary power failure ----- Check if there is a defective contact or leak current in the power supply system. Noise ----- Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or electric equipment that may cause harmonic wave) Check whether the ground connection is proper.
Check Point 3 : Check electrical components
02-34
2-3 TROUBLE SHOOTING WITH NO ERROR CODE
Check the voltage of power supply.
>> Check if AC198(AC220V-10%) - 264V(AC240V+10%) appears at indoor unit Terminal 1 - 2(Power supply).
Check Fuse on Power PCB.
>> If Fuse is open, check loose terminal, and replace Fuse.
Check Varistor on Power PCB (VA101, VA102).
>> If Varistor is defective, there is a possibility of an abnormal power supply. Check the correct power voltage and replace Power PCB.
OK
Trouble shooting 33
Forecast of Cause:
NO
OK
OK
OKOK
Outdoor Unit - No Power
1. Power supply failure 2. External cause
3. Electrical components defective
Check Point 1 : Check installation condition
Isn’t the breaker down? Check loose or removed connection cable.
>> If abnormal condition is found, correct it by referring to manual.
Check Point 2 : Check external cause at indoor unit and outdoor unit(Voltage drop or noise)
Instant voltage drop of ----- Check if there is a abnomally large load in the same power supply power supply system. Momentary power failure ----- Check if there is a defective contact or leak current in the power supply system. Noise ----- Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or electric equipment that may cause harmonic wave) Check whether the ground connection is proper.
Check Point 3 : Check electrical components
If Check Point 1 ~ 3 do not improve the symptom, replace Filter PCB, Main PCB, Inverter PCB and PFC PCB.
02-35
Check the voltage of power supply.
>> Check if AC198(AC220V-10%) - 264V(AC240V+10%) appears at outdoor unit terminal , L1 - N, L2 - N, L3 - N.
Check Fuse(F1, F3) on Main PCB.
>> If Fuse is open, check loose terminal, and replace Fuse.
Check Varistor on Main PCB (VA1 - VA5).
>> If Varistor is defective, there is a possibility of an abnormal power supply. Check the correct power voltage and replace Main PCB.
OK
Trouble shooting 34
Forecast of Cause:
Check Point 2 : Check external cause at indoor unit and outdoor unit(Voltage drop or noise)
Check Point 1 : Check indoor and outdoor installation condition
Check Point 3 : Check electrical components at indoor unit and outdoor unit
OK
OK
OK
No Operation (Power is ON)
1. Setting / Connection failure 2. External cause
3. Electrical component defective
Indoor unit - Check incorrect wiring between indoor unit - remote controller, or terminals between indoor units. Or, check if there is an open cable connection. Are these indoor unit, outdoor unit, and remote controller suitable model to connect?
>> If there is some abnormal condition, correct it by referring to manual.
Is there loose or removed serial communication line of between indoor unit and outdoor unit?
Instant voltage drop of power supply ----- Check if there is abnormally large load in the same power supply system. Momentary power failure ----- Check if there is a defective contact or leak current in the power supply system. Noise ----- Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or electric equipment that may cause harmonic wave) Check whether the ground connection is proper.
Check voltage at CN6 (AR*G45/ 54LHTA), CN140 (ARTG45/ 54LHTB,60LHTA), and CN14 (Other indoor unit).
>> If it is DC12V, Wired Remote Controller is failure. >> Replace Wired Remote Controller >> If it is DC 0V, Controller PCB is fallure. >> Replace Controller PCB
>> If Check Point 1, 2 do not improve the symptom, replace control parts of outdoor unit.
02-36
Attention
Trouble shooting 35
Forecast of Cause:
Check Point 2 : Check outdoor unit operation
Check Point 1 : Check indoor unit
Check Point 3 : Check site condition
Check Point 5 : Check refrigeration cycle
Check Point 4 : Check indoor unit / outdoor unit installation condition
Pipe (In) Pipe (Out)
Pipe (In) Pipe (Out)
OKOK
OKOK
OKOK
OKOK
No Cooling / No Heating
1. Indoor unit error 2. Outdoor unit error
3. Effect by surrounding environment
4. Connection pipe / Connection wire failure 5. Refrigeration cycle failure
Does indoor unit Fan run on high fan? Is Air filter dirty? Is Heat exchanger clogged? Check if energy save function is operated.
Is outdoor unit is operating? (If not, refer to Trouble shooting 33) Is there any obstructing the air flow route? Is there any clogging on outdoor unit Hert exchanger? Is the valve open?
Is capacity of indoor unit fitted to room size? Any windows open? Or direct sunlight?
Check connection pipe. (Specified pipe length and pipe diameter?) Check any loose or removed communication line.
>> If there is an abnormal condition, correct it by referring to Installation Manual or Data & Technical Manual.
Check if Strainer is clogged (Refer to the figure at right). Measure gas pressure and if there is a leakage, correct it.
>>
When recharging the refrigerant, make sure to perform
vacuuming, and recharge the specified amount.
Check EEV Check Compressor
Strainer normally does not have temperature difference between inlet and outlet as shown in , but if there is a difference like shown in , there is a possibility of inside clogged. In this case, replace Strainer.
02-37
MPa MPa
Trouble shooting 36
Forecast of Cause :
Trouble shooting 37
Forecast of Cause:
OK
OK
OK
OK
OK
OK
OK
Abnormal Noise
1. Abnormal installation(Indoor unit / outdoor unit)
2. Fan failure(Indoor unit / outdoor unit)
3. Compressor failure (Outdoor unit)
Diagnosis method when abnormal noise is occurred
Abnormal noise is coming from indoor unit. (Check and correct followings)
Abnormal noise is coming from outdoor unit. (Check and correct followings)
Is Fan broken or deformed? Is the screw of Fan loose? Is there any object which obstruct the Fan rotation?
Is main unit installed in stable condition? Is the installation of air suction grille and front panel normal?
Is Fan broken or deformed? Is the screw of Fan loose? Is there any object which obstruct the Fan rotation?
Is main unit installed in stable condition? Is Fan guard installed normally?
Check if vibration noise by loose bolt or contact noise of piping is happening.
Is Compressor locked? >> Check Compressor
Water Leaking
Diagnosis method when water is spitting out.
Is the filter clogged?
Check gas pressure and correct it if there was a gas leak.
Diagnosis method when water leak occurs
Is Drain hose connection loose? Is there a trap in Drain hose? Is Drain hose clogged?
Is main unit installed in stable condition? Is main unit broken or deformed at the time of transportation or maintenance?
Is Fan rotating? >> Check Fan motor
02-38
1. Erroneous installation 2. Drain hose failure
MPa MPa
SERVICE PARTS INFORMATION 1
MPa
Compressor
Diagnosis method of Compressor (If outdoor unit LED displays error, refer to Trouble shooting )
Does not start up
Is there open or loose connection cable?
Check connection of Compressor, and winding resistance. (Refer to the next page).
Check Inverter PCB connection of Compressor, and winding resistance. (Refer to the next page).
>> If there is no failure, the defect of Compressor can be considered. (Compression part broken or valve defective.)
>> If there is no failure, the defect of Compressor is considered (Locked compressor due to clogged dirt or less oil)
Replace Compressor
Replace Compressor
Replace Compressor
Stops soon after starting up
Is there open or loose connection cable?
Is Gas pipe valve open? (Low Pressure is too low)
Check if Refrigerant is leaking. (Recharge Refrigerant)
Check if Strainer is clogged. (PARTS INFORMATION 3)
Abnormal noise
Defective Compressor can be considered. (due to inside dirt clogging or broken component)
Check if vibration noise by loose bolt or contact noise of piping is happening.
02-39
2-4 SERVICE PARTS INFORMATION
MPa
SERVICE PARTS INFORMATION 2
Inverter Compressor
02-40
Check Point 1 : Check connection
Check Point 2 : Check winding resistance
Check Point 3 : Replace Inverter PCB
U(R)
V(S)
W(C)
Check terminal connection of Compressor (Loose or incorrect wiring)
Check winding resistance of each terminal
If the resistance value is 0 or infinite, replace Compressor.
If Check Point 1, 2 do not improve the symptom, replace Inverter PCB.
Resistance value : 0.79 (at 20°C)
U(R)
(RED)
V(S)
(WHITE)
W(C)
(BLACK)
Inverter PCB
Check connection of Inverter PCB (Loose or incorrect wiring)
TM806 (W)
TM805 (V)
TM804 (U)
RED
WHITE
BLACK
Compressor
Inverter PCB
SERVICE PARTS INFORMATION 3
Check Point 1 : Check Connections
Outdoor unit Electronic Expansion Valve ( EEV )
Check connection of connector ( Loose connector or open cable )
02-41
Check Point 5 : Check Opening and Closing operation of valve
Pipe (In)
Pipe (Out)
Pipe (In)
CLOSE Example : Hot gas
OPEN Example : Hot gas
Pipe (Out)
Pipe (In) Pipe (Out)
Pipe (In) Pipe (Out)
Check Point 6 : Check strainer
When Valve is closed, it has a temp. difference between Inlet and Outlet.
If it is open, it has no temp. difference between Inlet and Outlet.
Strainer normally does not have temperature difference between inlet and outlet as shown in , but if there is a difference as shown in , there is a possibility of inside clogged. In this case, replace Strainer.
Check Point 2 : Check Coil of EEV
Yellow - Brown Orange - Red Blue - Brown
White - Red
Read wire
46 4
Resistance value
Check Point 4 : Check voltage from Main PCB.
Check Point 3 : Check noise at start up
DC
at 20°C
Remove connector, check each winding resistance of Coil.
If resistance value is abnormal, replace EEV.
Remove connector and check voltage (DC12V)
If it does not appear, replace Main PCB.
Turn on Power and check operation noise.
If an abnormal noise does not show, replace Main PCB.
12V
RED BROWN BLUE ORANGE YELLOW WHITE
1 2 3 4 5 6
1 2 3 4 5 6
EV
CN17
CN17
BROWN BLUE
RED
ORANGE YELLOW WHITE
12 3456123
45 6
EV
EXPANSION VALVE COIL
SERVICE PARTS INFORMATION 4
Check Point 1 : Check rotation of fan
Indoor unit fan motor
Rotate the fan by hand when operation is off. (Check if fan is caught, dropped off or locked motor)
>>If fan or bearing is abnormal, replace it.
Check Point 2 : Check resistance of indoor fan motor
Refer to below. Circuit-test "Vm" and "GND" terminal. (Vm: DC voltage, GND: Ground terminal)
>>If they are short-circuited (below 300 k ), replace Indoor fan motor and Controller PCB.
02-42
Pin number (wire color)
Terminal function (symbol)
1 (Brown) 2 (Yellow) 3 (White) 4 (Black) 5 6 (Red)
Feed back (FG) Speed command (Vsp) Control voltage (Vcc) Ground terminal (GND) No function DC voltage (Vm)
Check Point 1 : Check resistance of indoor fan motor
Check each winding resistance of the motor
>>If Resistance value is abnormal, replace motor.
Lead wire color
Resistance value (20°C)
White - Red Red - Black Red - Violet Violet - Blue
7.73 + 7%
7.08 + 7%
3.80 + 7%
3.80 + 7%
-
-
-
-
For AR *G45/ 54LHTA
For other indoor unit
(AC)
Thermal protector
Pr
Violet (Int.1)
Blue (Low)
Red (Hi) Black White
°C
SERVICE PARTS INFORMATION 5
Check Point 1 : Check rotation of fan
Outdoor unit fan motor
Rotate the fan by hand when operation is off. (Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
Check Point 2 : Check resistance of outdoor fan motor
Refer to below. Circuit-test "Vm" and "GND" terminal. (Vm: DC voltage, GND: Ground terminal)
>>If they are short-circuited (below 300 k ), replace Outdoor fan motor and Main PCB.
Pin number (wire color)
Terminal function (symbol)
1 (Red) 2 3 (Black) 4 (White) 5 (Yellow) 6 (Brown)
DC voltage (Vm) No function Ground terminal (GND) Control voltage (Vcc) Speed command (Vsp) Feed back (FG)
02-43
3. DISASSEMBLY PROCESS
AIR CONDITIONER
3 phase type
Single / Simultaneous operation multi type
03-01
3. DISASSEMBLY PROCESS
WARNING
Before servicing the unit, turn the power supply switch OFF, Then, do not touch electric parts for 10 minutes due to the risk of electric shock.
1. Appearance
2. SERVICE PANEL removal
3. INSULATION SHEET removal
screw (serrated)
Hook (3 places)
Remove the mounting screws.
Remove the Hook. (6 places) Remove the INSULATION SHEET by sliding upward.
Remove the SERVICE PANEL by sliding downward.
INSULATION SHEET
Hook (6 places)
Remove the connectors, codes and screw.
Remove the mounting screws.
Remove the locking spacers.
03-04
screw
screw
Locking spacers
CAPACITOR PCB
Hook
5-4. CAPACITOR PCB removal
Remove the CONDENSER CASE by sliding rightward.
Remove the CONDENSER COVER by sliding toward.
03-11
16. Precautions for exchange of refrigerant-cycle-parts
EXPANSION VALVE
4WAY VALVE
3WAY VALVE (GAS)
PRESSURE SENSOR
3WAY VALVE (LIQUID)
(1) During exchange the following parts shall be protected by wet rag and not make the allowable temperature or more. (2) Remove the heat insulation when there is the heat insulation near the welding place. Move and cool it when its detaching is difficult. (3) Cool the parts when there are parts where heat might be transmitted besides the replacement part. (4) Interrupt the flame with the fire-retardant board when the flame seems to hit the following parts directly. (5) Do not allow moisture or debris to get inside refrigerant pipes during work. (6) When brazing, be sure to replace the air in the pipe with nitrogen gas to prevent forming oxidization scale.
Part name
Allowable temperature
Precautions in work
Remove the coil before brazing. And install the coil after brazing.
Tighten the flare part gripping it. (Tightening torque :12 1.5N m) Do the static electricity measures.
Remove the suction temp. sensor before brazing. And install the suction temp. sensor after brazing.
120°C
120°C
100°C
UNION JOINT
Remove the pressure sensor before brazing. And install the pressure sensor after brazing.
100°C
100°C
+
-
.
Loading...