Fujitsu AU*A45LCLU Series, AO*A45LBTL Series Design & Technical Data

DESIGN & TECHNICAL DATA
SINGLE INDOOR
OUTDOOR
AOA45LBTL
AUA45LCLU
AIR CONDITIONER
Cassette type
1. INDOOR UNIT
D2D_AU041E/02
2009.08.21
CASSETTE TYPE :
AUA45LCLU
CONTENTS
1. INDOOR UNIT
1-1. FEATURE
.............................................................................................................. 01-01
1-2. WIRED REMOTE CONTROLLER
..................................................... 01-04
1-3. SPECIFICATIONS
.......................................................................................... 01-06
1-4. DIMENSIONS
..................................................................................................... 01-07
1-5. WIRING DIAGRAMS
.................................................................................... 01-09
1-6. CAPACITY TABLE
......................................................................................... 01-10
1-6-1. COOLING CAPACITY
.................................................................................. 01-10
1-6-2. HEATING CAPACITY
................................................................................... 01-11
1-7. FAN PERFORMANCE
................................................................................ 01-12
1-7-1. AIR VELOCITY DISTRIBUTION
................................................................. 01-12
1-7-1-1. STANDARD MODE .................................................................................... 01-12
1-7-1-2. SPECIAL UPWARD MODE ....................................................................... 01-14
1-7-2. AIR FLOW
...................................................................................................... 01-15
1-7-2-1. 4-WAY OUTLET ......................................................................................... 01-15
1-7-2-2. 3-WAY OUTLET ......................................................................................... 01-16
1-7-3. FRESH AIR
..................................................................................................... 01-17
1-7-4. DUCT CONNECTION
................................................................................... 01-18
1-8. OPERATION NOISE
..................................................................................... 01-20
1-8-1. NOISE LEVEL CURVE
................................................................................. 01-20
1-8-2. SOUND LEVEL CHECK POINT
.................................................................01-21
1-9. ELECTRIC CHARACTERISTICS
....................................................... 01-22
1-10. SAFETY DEVICES
......................................................................................... 01-23
1-11. EXTERNAL INPUT & OUTPUT
........................................................... 01-24
1-12. FUNCTION SETTING
.................................................................................. 01-27
1-12-1. INDOOR UNIT
............................................................................................... 01-27
1-12-2. WIRED REMOTE CONTROLLER
.............................................................. 01-28
1-13. OPTIONAL PARTS
........................................................................................ 01-31
- (01 - 01) -
CASSETTE TYPE
AU
A45L
CASSETTE TYPE
AU
A45L
FEATURE1-1.
MODEL (INDOOR/OUTDOOR/
DECORATION PANEL)
AUA45LCLU / AOA45LBTL / UTG-UGA-W
FEATUR ES
Energy saving
z
All DC design • Heat exchange efciency increased and larger air ow by adoption of new type turbo fan
Advancement in comfort
z
Quiet operation was realized by adoption of new type turbo fan Improvement of air stream
Adoption of high efficiency turbo fan
High efciency achieved by equaling the performance of the wing and air passing the heat exchanger
Important of the flap
Making space between the ceiling, the air ows far wide and ceiling does not get dirty.
500mm
Wind
velocity
Fast
Slow
3-dimensional wing
: Spin direction : Airflow direction
No airflow separation
Quiet
< Motor side >
Heat exchanger
Rear part
Front part
Ceiling
Round Flap
Much less temperature irregularity
happens by spreading air flow widely
Bottom view
- (01 - 02) -
CASSETTE TYPE
AU
A45L
CASSETTE TYPE
AU
A45L
High lift drain pump
z
850mm
Ceiling panel
Simplication of drain water check
z
Drain and contamination check are possible without removing the decoration panel.
Can be easily checked by removing the drain cover.
Easy installation
z
Easy setting by wired remote controller
Improvement of installation & maintenance
z
Adjustment of nut is possible after installation
Mounting position of body can be ne adjusted after Decoration panel mounting.
Grille corner
Adjustment
can be done just taking off the corner part
1.5
3
7 5 3 73 5
Side view
Airflow range of 2m / s
120120
Wide & powerful airflow
The wind is widely delivered by a high efciency fan and round ap.
[m]
DRAIN CAP
DRAIN COVER
- (01 - 03) -
CASSETTE TYPE
AU
A45L
CASSETTE TYPE
AU
A45L
FUNCTION SETTING
Other functions
z
Performs operation matched to the number of outlets when 4 directions are unnecessary and outlets are blocked when the ceiling cassette is installed in a corner, etc.
Ceiling switching function
z
Also delivers air to high ceilings by selecting the mode and raising the air ow according to the height of the ceiling.
Low ceiling (Mode 1)
4.2m
3.2m
2.7m
High ceiling (Mode 2) Standard ceiling (Standard)
Standard ...Operates at normal air ow. Mode 1 ...Air ow becomes smaller than normal. Mode 2 ...Air ow becomes greater than normal.
Filter sign
z
The indoor unit has sign to inform the user that it is time to clean the lter
Cooling room temperature correction
z
Heating room temperature correction
z
Auto restart
z
The units restart automatically when the current was returned even when there was a power interruption during operation.
Room temperature sensor switching
z
Switches from room temperature judgment by room temperature sensor attached to indoor unit body to room temperature judgment by room temperature sensor attached to wired remote controller.
Economy operation
z
The power consumption can be reduced.
Powerful mode ...Standard Soft mode ...Performs operation which reduces the power consumption
4-way direction 3-way direction
4-way direction mode: Set when there are 4 outlets
(shipped state).
3-way direction mode: Set when there are 3 outlets.
- (01 - 04) -
CASSETTE TYPE
AU
A45L
CASSETTE TYPE
AU
A45L
WIRED REMOTE CONTROLLER1-2.
FEATUR ES
Various timer setup (ON / OFF / WEEKLY) are possible.
Equipped with weekly timer as standard function.
(2 times Start / Stop per day for a week)
When setting up a timer, operation mode and a temperature
setup can be changed.
When a failure occurs,the error code is displayed. (Maximum of 16)
Error indication.(A maximum of 16 error histories are memorizable.)
Up to 16 indoor units can be simultaneously controlled.
Economy operation are possible.
Easy installation with a slim shape with no bulge in the back.
The room temperature can be controlled by being detected the
temperature accurately with built-in thermo sensor.
Simple function setting
z
Setting of the air conditioner selection function is performed by remote controller.
High performance and compact size
z
Three functions are combined in one unit.
Built-in timers
z
Wired
remote
controller
Weekly
timer
Setback
timer
+ +
Weekly timer Setback timer
At "Weekly timer" + "Set back timer" setup
Easy-to-understand operation
z
[Variable timer control]
The operation/display sections are zoned according to time and operation, enabling variable programming to match application.
Simple installation
z
Components are compatible with standard switch boxes. Flat back construction allows equipment to be installed wherever it is
needed.
European switch box
JIS box
SUMOTUWETH FR SA
7
3126 9
15 18 21
SUMOTUWETH FR SA
7
3126 9
15 18 21
SUMOTUWETH FR SA
3126 9
15 18 21
Possible to set ON/OFF time to operate twice each day of the week.
Setup scr een examp le (Set to Wednes day: 8:00 to 20:00.)
Screen after setup
Setup scr een examp le (Set from Su nday to Satu rday: 12:00 to 15:00, 28 °C.)
Possible to set temperature for two time spans and for each day of the week.
Easy-to-understand time bar display
24°C
0 3 6 9 12 15 18 21 Time
28°C
0 3 6 9 12 15 18 21 Time
28°C
24°C
0 3 6 9 12 15 18 21 Time
24°C 28°C 24°C
Timer area
Operation area
- (01 - 05) -
CASSETTE TYPE
AU
A45L
CASSETTE TYPE
AU
A45L
FUNCTIONS
Display panel
DIMENSION
SPECIFICATION
15
11
10
9
8
2
1
3
5
14
4
12
13
6 7
17
16
18
19
20
21
120
17
120
SIZE (H x W x D mm) 120 x 120 x 17
WEIGHT ( g ) 160
CABLE LENGTH ( m ) 10
POWER ( V ) 12
1
START/STOP button
Pressed to start and stop operation.
2
Set temperature button
Selects the setting temperature.
3
Master control button
Selects the operating mode (AUTO, HEAT, FAN, COOL, DRY).
4
Fan control button
Selects the fan speed (AUTO, QUIET, LOW, MED, HIGH).
5
Economy button
Turns the economy efcient mode on and off.
6
Timer mode (CLOCK ADJUST) button
Selects the timer mode (OFF TIM ER, ON TIMER, WEEKLY TIMER). Set the current time.
7
Day (DAY OFF) button
Temporarily cancels of one day timer.
8
Set back button
Pressed to select the set back timer.
9
Set time button
Pressed to set time.
10
Delete button
The schedule of a weekly timer is deleted.
11
Set button
Sets the date, hour, minute and on -of f time.
12
Vertical airow direction and swing button
Push for two seconds to change the swing mode.
13
Horizontal airow direction and swing button
Push for two seconds to change the swing mode.
14
Filter button
15
Operation lamp
Lights during operation and when the timer is on.
16
Timer and clock display
17
Operation mode display
18
Fan speed display
19
Operation lock display
20
Temperature display
21
Function display
Defrost display
Thermo sensor display
Economy display
Vertical swing display
Horizontal swing display
Filter display
Functions will be di fferent due to type of indoor unit . For detail s, pleas e see operation manual.
[ Unit : mm ]
Front View
- (01 - 06) -
CASSETTE TYPE
AU
A45L
CASSETTE TYPE
AU
A45L
SPECIFICATIONS1-3.
Note : Speci cations are base d on the fol lowing c onditi ons. Coolin g : Indoor t emperat ure of 27 °CD B / 19 °CWB. and outdo or tempe rature of 3 5 °CDB/ 24 °CWB. Heating : I ndoor te mperat ure of 20 °CD B / 15 °CWB.a nd outdo or temper ature of 7 °C DB/6 °C WB. Pipe leng th : 7.5 m, Height di ffere nce : 0 m.(Out door uni t - Indoor u nit) The maxi mum cur rent is the m aximum v alue when o perate d within t he operat ion range (tempera ture)
Typ e
CASSE TTE MO DEL
INVER TER HE ATPUMP
Model na me AUA45LC LU
Power sou rce 230V ~ 50 Hz
Availabl e voltag e range 198-2 64V ~ 50H z
Europea n energy l abel
Cooling A
Heating A
Capacity
Cooling
Rated
kW 12.5
BTU/h 42700
Min-Max
kW 4.0-14.0
BTU/h 13700-47800
Heating
Rated
kW 14.0
BTU/h 4780 0
Min-Max
kW 4.2-16.2
BTU/h 14300-55300
Input pow er
Cooling
Rated
kW
3.89
Max 4.56
Heating
Rated 3.77
Max 4.56
Current
Cooling
Rated
A
17.0
Max 20.0
Heating
Rated 16.5
Max 20.0
EER Cooling
kW/kW
3.21
COP Heating 3.71
Moistu re remova l l/h (pin ts/h) 4.5(9.5)
Fan
Airow rate
Cooling
High
m
3
/h
1900
Med 1640
Low 1460
Quiet 125 0
Heating
High 1900
Med 1640
Low 1460
Quiet 125 0
Type × Q'ty Turbo × 1
Motor ou tput W 80
Sound pr essure l evel
Cooling
High
dB(A)
46
Med 42
Low 40
Quiet 36
Heating
High 46
Med 42
Low 40
Quiet 36
Heat excha nger t ype
Dimens ions (H × W × D)
mm
252×2021×13.3 252×2087×13.3 252×2153×13.3
Fin pitch 1.3
Rows x Sta ges 3 x 12
Pipe ty pe Copper
Fin typ e Aluminium
Enclos ure (Pane l)
Material Steel (HIPS)
Colour
WHITE
Approx imate co lour of M UNSEL L N 9.25/
Dimens ions ( H×W×D)
Net
Unit
mm
288×840×840
Panel 50×950×950
Gross
Unit 360×960×9 85
Panel 115×1120×100 0
Weight
Net
Unit
kg(lb.)
27(6 0)
Panel 5. 5(12)
Gross
Unit 33( 73)
Panel 8.5 (19)
Connec tion pi pe
Size
Liquid
mm
Ø 9.52 (3/8 in .)
Gas Ø 15.88 (5/8 in .)
Method Flare
Operat ion ran ge
Cooling
°C 18- 32
%RH 80 or les s
Heating °C 16-3 0
Remote co ntrol ler typ e Wired
Drain pi pe
Material PVC(V P25)
Size mm Outer dia meter : 32 .0 / Inner d iameter : 2 5.0
- (01 - 07) -
CASSETTE TYPE
AU
A45L
CASSETTE TYPE
AU
A45L
DIMENSIONS1-4.
MODEL : AUA45L
Ceiling opening and hanging bolt pitch
z
(Unit : mm)
Refrigerant piping and drain piping positions
z
Airow split-ow duct and fresh air inlet positions
z
288 mm
298 mm
40 mm
10 mm
140 - 145 mm
50 - 100 mm
950 mm(Panel frame)
mm 54 - 02mm 54 - 02
50 mm
80 mm
130 mm
130 mm
130 mm
200 mm
840 mm(Body frame)
795 mm(Hanging bolt pitch)
699 mm(Hanging bolt pitch)
860 - 910 mm(Ceiling opening)
950 mm(Panel frame)
mm 54 - 02mm 54 - 02
840 mm(Body frame)
860 - 910 mm(Ceiling opening)
60 mm278 mm358 mm
140 mm
180 mm
200 mm
Drain pipe (Connect the attached drain hose)
88 mm
70 mm
2.5 mm hole
2.5 mm hole
250 mm
352 mm
100 mm
83 mm83 mm
90 mm
100 mm
mm 581mm 581
Airflow split-flow duct connecting port
Airflow split-flow duct connecting port
Airflow split-flow duct connecting port
Fresh air inlet position
Fresh air inlet position
Drain pipe
Refrigerant pipe
Detailed diagram of branched duct connecting port (4 sides)
Knockout hole pitch
Cut out
Cut out
Airflow split-flow duct connecting port
10
4
- (01 - 08) -
CASSETTE TYPE
AU
A45L
CASSETTE TYPE
AU
A45L
INSTALLATION PLACE
(Unit : mm)
3-way directions setting
z
To set “3-way directions”, the air outlet shutter plate (UTR-YDZC) sold separately must be installed and “outlet-direction” switched to “3-way” by remote controller.
1,500 mm or more
1,000 mm or more
2,500 mm or more
Obstruction
3,000 mm or more
Strong and durable ceiling
Floor
Ceiling mode “Low” : to 2.7 m
Ceiling mode “Standard” : to 3.2 m
Ceiling mode “High” : to 4.2 m
100 or more
- (01 - 09) -
CASSETTE TYPE
AU
A45L
CASSETTE TYPE
AU
A45L
WIRING DIAGRAMS1-5.
MODEL : AUA45L
- (01 - 10) -
CASSETTE TYPE
AU
A45L
CASSETTE TYPE
AU
A45L
CAPACITY TABLE1-6.
1-6-1. COOLING CAPACITY
This table is created using the maximum capacity.
MODEL : AUA45L
AFR : Air  ow rate (m3/min) TC : Total capaci ty (kW ) SHC : Sens ible Hea t capaci ty (kW ) PI : Power Inpu t (kW)
AFR 31.7
Indoor t empera ture
°CDB 18 21 23 25 27 29 32
°CWB 12 15 16 18 19 21 23
Outdoo r temper ature
°CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
-15 11.00 8.83 1.99 12.26 8 .88 2.03 12.68 9.65 2.04 13.51 9. 68 2.06 13.93 10.46 2.07 14.76 10.42 2.09 15.60 11.10 2.11
-10 10.95 8.78 1.99 12.19 8.83 2.03 12.61 9.6 0 2.04 13.44 9. 63 2.06 13.86 10.40 2.07 14.69 10.36 2.09 15.52 11.04 2.11
0 10.88 8.51 2.00 12.11 8 .56 2.04 12.53 9.31 2.05 13.35 9. 34 2.07 13.77 10.08 2.08 14.59 10.04 2.10 15.42 10.70 2.12
5 10.83 8.61 2.05 12.06 8 .66 2.08 12.47 9.41 2.09 13.30 9.44 2 .11 13.71 10.2 0 2.12 14.53 10.16 2 .15 15.3 5 10.82 2.17
10 10.81 8.73 2.1 2 12.05 8.79 2.16 12.46 9.55 2.17 13. 28 9.58 2.19 13.69 10.35 2.20 14.51 10.31 2.22 15. 33 10.98 2.25
15 10.75 8.71 2.23 11.97 8.76 2 .26 12.38 9.53 2.27 13.20 9. 56 2.29 13.61 10.32 2.31 14.42 10.28 2.33 15.24 10.95 2.35
20 11.01 8 .69 2.74 12.26 8.74 2.78 12.68 9. 50 2.79 13.51 9.53 2.82 13. 93 10.29 2.84 14.77 10.25 2.87 15.60 10.92 2.89
25 11.09 8 .80 3.18 12.35 8.85 3.23 12.77 9. 62 3.25 13.62 9.65 3.28 14. 04 10.42 3.30 14.88 10.38 3.33 15.72 11.06 3.36
30 11.36 8.84 4.30 12.66 8.89 4.36 13.09 9 .67 4.38 13.95 9.70 4.43 14.38 10 .47 4.45 15.24 10.43 4.50 16.11 11.11 4.54
35 11.06 8.98 4.29 12.32 9.03 4.35 12.74 9 .82 4.38 13.58 9.85 4.42 14.00 10.64 4.44 14. 84 10.60 4.49 15.68 11.29 4.53
40 8.64 7. 71 3.59 9.63 7.75 3.65 9.96 8.43 3.67 10.61 8.46 3.71 10. 94 9.13 3.72 11.60 9.10 3.76 12.26 9.69 3.80
46 5.97 6.37 2.71 6.65 6.41 2.76 6.88 6.97 2.77 7.33 6.9 9 2.80 7.56 7.55 2.81 8.01 7.52 2.84 8.47 8.01 2.87
- (01 - 11) -
CASSETTE TYPE
AU
A45L
CASSETTE TYPE
AU
A45L
1-6-2. HEATING CAPACITY
This table is created using the maximum capacity.
MODEL : AUA45L
AFR : Air o w rate (m3/min) TC : Total capaci ty (kW) PI : Power Inpu t (kW)
AFR 31.7
Indoor temperature
°CDB 16 18 20 22 24
Outdoo r temper ature
°CDB °CWB TC PI TC PI TC PI TC PI TC PI
-15 -16 11.43 4.49 11.16 4.58 10.89 4.67 10.62 4.77 10.35 4.86
-10 -11 12.38 4.49 12.08 4.58 11.79 4.67 11.49 4.77 11 .20 4.86
-5 -7 13 .18 4.48 12.87 4.57 12.55 4.67 12.24 4.76 11.93 4.85
0 -2 14.10 4.48 13.77 4.58 13.4 3 4.67 13.09 4.76 12.76 4.86
5 3 16.02 4.49 15.64 4.58 15.25 4.67 14.87 4.77 14.49 4.86
7 6 17.01 4.49 16.61 4.58 16.20 4.67 15.80 4.77 15.39 4.86
10 8 17.19 4.35 16.78 4.44 16.37 4.53 15.96 4.62 15.5 5 4.71
15 10 1 7.3 2 4.10 16.91 4.19 16.50 4.28 16.09 4.36 15.67 4.43
20 15 17. 46 3.06 1 7.0 5 3.12 16.63 3.19 16.22 3.25 15.80 3.30
24 18 17. 51 3.00 17. 10 3.06 16.68 3.12 16.26 3.19 15.84 3.24
- (01 - 12) -
CASSETTE TYPE
AU
A45L
CASSETTE TYPE
AU
A45L
FAN PERFORMANCE1-7.
1-7-1. AIR VELOCITY DISTRIBUTION
1-7-1-1. STANDARD MODE
MODEL : AUA45L
4-way air outlet
z
Note:
Condition
Fan speed : High
Operation mode : FAN
Ceiling mode : Standard
5
4
3
2
1
0
1
2
3
4
5
Unit : m/s(m)
(m)
TOP VIEW VERTICA L LOUVER
: Upward
3.2
2
1
0
Unit : m/s(m)
(m)
SIDE VIE W VERTICA L LOUVER
: Upward
3.2
2
1
0
Unit : m/s(m)
(m)
SIDE VIE W VERTICA L LOUVER
: D ownward
10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10
10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10
10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10
0.25 0.25
11
0.5 0.5
2 2
0.25 0.25
1 1
0.5 0.5
2 2
0.25
0.25
0.5
0.5
1
1
10.5 0.51
2
2 2
2
- (01 - 13) -
CASSETTE TYPE
AU
A45L
CASSETTE TYPE
AU
A45L
MODEL : AUA45L
3-way air outlet
z
Note:
Condition
Fan speed : High
Operation mode : FAN
Ceiling mode : Standard
5
4
3
2
1
0
1
2
3
4
5
Unit : m/s(m)
(m)
TOP VIEW VERTICA L LOUVER
: Upward
3.2
2
1
0
Unit : m/s(m)
(m)
SIDE VIE W VERTICA L LOUVER
: Upward
3.2
2
1
0
Unit : m/s(m)
(m)
SIDE VIE W VERTICA L LOUVER
: D ownward
10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10
10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10
10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10
0.25 1
0.5
0.25
0.5
2
1
2
0.25
1 1
0.5
0.25
0.5
2 2
0.25
0.25
1
1
0.5
0.5
2
2
0.251 0.52
- (01 - 14) -
CASSETTE TYPE
AU
A45L
CASSETTE TYPE
AU
A45L
1-7-1-2. SPECIAL UPWARD MODE
MODEL : AUA45L
4-way air outlet
z
Note:
Condition
Fan speed : High
Operation mode : FAN
Ceiling mode : Standard
10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10
(m)
SIDE VIE W VERTICA L LOUVER
: Speci al upward
Unit : m/s(m)
3.2
2
1
0
0.25
1
0.5
2
- (01 - 15) -
CASSETTE TYPE
AU
A45L
CASSETTE TYPE
AU
A45L
1-7-2. AIR FLOW
1-7-2-1. 4-WAY OUTLET
MODEL : AUA45L
Cooling / Heating
z
Fan speed
Number of
rotations
(r.p.m.)
Air ow
HIGH 690
m
3
/h 1900
l/s 528
CFM 1118
MED 610
m
3
/h 1640
l/s 456
CFM 965
LOW 550
m
3
/h 1460
l/s 406
CFM 859
QUIET 470
m
3
/h 1250
l/s 3 47
CFM 736
- (01 - 16) -
CASSETTE TYPE
AU
A45L
CASSETTE TYPE
AU
A45L
1-7-2-2. 3-WAY OUTLET
MODEL : AUA45L
Cooling / Heating
z
Fan speed
Number of
rotations
(r.p.m.)
Air ow
HIGH 720
m
3
/h 1690
l/s 469
CFM 995
MED 640
m
3
/h 1490
l/s 414
CFM 877
LOW 580
m
3
/h 1340
l/s 372
CFM 789
QUIET 500
m
3
/h 1140
l/s 317
CFM 671
- (01 - 17) -
CASSETTE TYPE
AU
A45L
CASSETTE TYPE
AU
A45L
1-7-3. FRESH AIR
MODEL : AUA45L
Installation
z
250 mm
185 mm
2.5 mm hole4
70 mm
62 mm
62 mm
Refrigerant pipe
Fresh air inlet position(A)
Fresh air inlet position
View(A)
Drain pipe
Duct frange *2
Flexible duct *2
Fan *2
Flexible duct *2
Insulation *1
*1 : In case of fresh air intake, please remove the insulation.
*2 : Locally procured parts
Fresh air Inlet position
Duct
(Inside Dia. ø70mm)
Static pressure required to take in fresh air
Duct Fan
98
49
0
10
8
6
4
2
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
Air ow (m3/min)
Duct static pressure (Pa)
Duct static pressure (mmAq)
- (01 - 18) -
CASSETTE TYPE
AU
A45L
CASSETTE TYPE
AU
A45L
1-7-4. DUCT CONNECTION
MODEL : AUA45L
Outlet air
z
L
Duct (Inside size. 350mm×100mm)
Duct static pressure (mmAq)
L=10m
L=5m
L=1m
Fan Speed Quiet 2-way
Fan Speed Quiet 1-way
Fan Speed High 1-way
Fan Speed High 2-way
98
49
0
10
9
8
7
6
5
4
3
2
1
0
0 2 4 6 8 10 12 14
Air ow (m3/min)
Duct static pressure (Pa)
- (01 - 19) -
CASSETTE TYPE
AU
A45L
CASSETTE TYPE
AU
A45L
PRECAUTIONS WHILE CONNECTING AIR OUTLET DUCT
z
Connect the air outlet duct at up to two locations among the four duct connection locations. (Do not connect ducts at three or more locations.)
z
Blow-off pattern when a branch duct is installed Bi-directional branching, main unit bi-directional branching
z
Once the location where the duct is to be connected is decided, always be sure to close the outlets in the same direction.
A
B
C
D
Close Close
Branch
Branch
Close
Close
Branch
Branch
DUCT (Locally procured parts)
Close the outlet here.
* Use only af ter closing the outlet of the cassette on the
side on which the duct is used, using the “Air outlet shutter plate (UTR-YDZC)”.
- (01 - 20) -
CASSETTE TYPE
AU
A45L
CASSETTE TYPE
AU
A45L
OPERATION NOISE1-8.
1-8-1. NOISE LEVEL CURVE
MODEL : AUA45L
Condition
Ceiling mode : Standard
Air outlet : 4-way air outlet
QUIET
HIGH
Heating
z
Octave ba nd soun d pressu re level, d B:(0dB= 0.00 02µba r)
Octave ba nd cent er frequ ency,Hz
80
70
60
50
40
30
20
10
0
63 125 2 50 500 1,00 0 2,000 4,000 8,00 0
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
QUIET
HIGH
Cooling
z
Octave ba nd soun d pressu re level, d B:(0dB= 0.00 02µba r)
Octave ba nd cent er frequ ency,Hz
80
70
60
50
40
30
20
10
0
63 125 2 50 500 1,00 0 2,000 4,000 8,00 0
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
- (01 - 21) -
CASSETTE TYPE
AU
A45L
CASSETTE TYPE
AU
A45L
1-8-2. SOUND LEVEL CHECK POINT
Microphone
Microphone
CENTER
1.5m
- (01 - 22) -
CASSETTE TYPE
AU
A45L
CASSETTE TYPE
AU
A45L
ELECTRIC CHARACTERISTICS1-9.
Model name AUA45L
Power supply
Voltage V 230 ~
Frequency Hz 50
Max. operating current (Indoor unit) A 1.2
Wiring spec. (Indoor unit to outdoor unit)
Connection cable mm
2
1.5 (Min.)
Limited wiring length m 50
- (01 - 23) -
CASSETTE TYPE
AU
A45L
CASSETTE TYPE
AU
A45L
SAFETY DEVICES1-10.
Protection form
Model
AUA45L
Circuit protection Current fuse (PCB) 3.15A 250V
Fan motor protection
Thermal protection program
110±15°C OFF
105±15°C ON
- (01 - 24) -
CASSETTE TYPE
AU
A45L
CASSETTE TYPE
AU
A45L
EXTERNAL INPUT & OUTPUT1-11.
EXTERNAL INPUT
You can control air conditioner ON/OFF operation by external input.
Note) Only ON / OFF external input can be set up. Use the remote controller to set MODE, AIR FLOW
RATE, SET TEMPERATURE and other values. When the air conditioner starts operating, it operates with the settings used when it stopped previously.
[Example]
Parts (Optional)
Model name Parts No.
UT Y-XWZ X 902 8 6510 03
Wire (External input) : Orange / Yellow
Connector INPUT OUTPUT REMARKS
CN102
CONTROL OPERATION
(ON / OFF)
See external
input/output settings
for details.
CN103 OPERATION DISPLAY
CN6 FRESH AIR CONTROL
Indoor unit
Printed circuit
board
EX T.
IN
EX T.
OUT
CN102
1
3
+
-
External device (Field supplied)
Signal Specication
Non-voltage contact ON/OFF continuous signal Contact capacity: 12VDC, 10mA
external input signal
ON
STOP
OPERATION
OFF
ON O FF ON OFF
remote controller signal
indoor unit status
- (01 - 25) -
CASSETTE TYPE
AU
A45L
CASSETTE TYPE
AU
A45L
EXTERNAL OUTPUT
You can display air conditioner ON/OFF operation by external output.
Note) Only ON/OFF is output as external output. Regarding MODE, AIR FLOW RATE, SET
TEMPERATURE, error signals and others, please check the display on the main unit or the remote controller.
[Example]
Parts (Optional)
Model name Parts No.
UT Y-XWZ X 902 8 6510 03
Wire (External output) : Blue / Purple
Indoor unit
Printed
circuit board
EX T.
IN
EX T.
OUT
CN103
1
2
+
-
External device (Field supplied)
Signal Specication
Non-voltage contact Contact capacity: Max. 24VDC, 10mA to less than 1A
indoor unit status
OPERATION
OPEN
SHORT
STOP
external output signal
- (01 - 26) -
CASSETTE TYPE
AU
A45L
CASSETTE TYPE
AU
A45L
FRESH AIR CONTROL OUTPUT
You can control sub fan by synchronizaton with fan operation of indoor unit.
[Example]
Parts (Optional)
Model name Parts No.
UTD-ECS5A 9077359004
Wire (Fresh air output)
Indoor unit
Field supplied
1
+
2
-
Power
Fuse
Fan, other
CN6
Indoor unit fan
Operation
0V
12V
Stop
CN6 (Output)
- (01 - 27) -
CASSETTE TYPE
AU
A45L
CASSETTE TYPE
AU
A45L
FUNCTION SETTING1-12.
1-12-1. INDOOR UNIT
SWITCH POSITION
JUMPER WIRE SETTING
Remote control unit signal code
INDOOR UNIT
DIP SW
1
Forbidden
2
3
4
Jumper Wire
JM1
Remote control unit signal code
JM2
JM3 Fan delay setting
JM3
JM2
JM1
Indoor unit Printed circuit board
MAIN PCB
Indoor unit setting
(

Factory setting)
Jumper wire
Remote control unit
signal code
JM 1 JM 2
Connect Connect A
Disconnect Connect B
Connect Disconnect C
Disconnect Disconnect D
- (01 - 28) -
CASSETTE TYPE
AU
A45L
CASSETTE TYPE
AU
A45L
1-12-2. WIRED REMOTE CONTROLLER
SWITCH POSITION
DIP SWITCH SETTING
1. Dual remote controller setting
Set the remote controller DIP switch No.2 according to the following table.
2. Memory backup setting
Set to ON to use batteries for the memory backup. If batteries are not used, all of the settings stored in memory will be deleted if there is a power failure.
DIP SW
1 Can not be used. (Do not change)
2 Dual remote controller setting
3 Can not be used. (Do not change)
4 Can not be used. (Do not change)
5 Can not be used. (Do not change)
6 Memory backup setting
ON
ON
OFF
1 2 3 4 5 6
Front case (back side)
Do not use this DIP Switch
DIP Switch
(

Factory setting)
Number
of remote
controller
Master unit Slave unit
DIP-SW No.2 DIP-SW No.2
1 (Normal) OFF
2 (Dual) OFF ON
(

Factory setting)
DIP-SW
No.6
Memory backup
OFF Invalidity
ON Validity
- (01 - 29) -
CASSETTE TYPE
AU
A45L
CASSETTE TYPE
AU
A45L
!
CAUTION
• Conrm whether the wiring work for outdoor unit has been nished.
• Conrm whether the ccover for electric control box on the outdoor unit is close.
1. Turning on the power
(1) Check the remote controller wiring and DIP switch settings.
(2) Install the front case.
When installing the front case, connect the connector to the front case.
(3) Check the indoor and outdoor unit wiring and circuit board
switch settings, and then turn on the indoor and outdoor units. After "
" has ashed on the set temperature display for several seconds, the clock display will appear in the center of the remote controller display.
The clock display will appear in the center of the remote
controller display.
SUMOTUWETH FR
SA
2. Function setting
• This procedure changes to the function settings used to control the indoor unit according to the installation conditions. Incorrect settings can cause the indoor unit malfunction.
• After the power is turned on, perform the “FUNCTION SETTING” according to the installation conditions using the remote controller.
• The settings may be selected between the following two: Function Number or Setting Value.
• Settings will not be changed if invalid numbers or setting values are selected.
Operation Method
(1) Press the set temperature buttons ( ) ( ) and fan control
button simultaneously for more than 5 seconds to enter the function setting mode.
SU
MO
TU
WE
TH FR
SA
(2) Press the SET BACK button to select the indoor unit number.
SET BACK
SUMOTUWETH FR
SA
Unit numb er of IND OOR UNIT
(3)Press the set time buttons to select the function number.
Function number
SUMOTUWETH FR
SA
(4) Press the set temperature buttons ( ) ( ) to select the setting
value.
The display ashes as shown to the right during setting value
selection.
(5) Press the TIMER SET button to conrm the setting. Press the
TIMER SET button for a few seconds until the setting value stops ashing.
If the setting value display changes or if “- -” is displayed when
the ashing stops, the set ting value has not been set correctly. (An invalid setting value may have been selected for the indoor unit.)
Settin g value
SUMOTUWETH FR
SA
(6) Repeat steps 2 to 5 to perform additional settings. Press
the set temperature buttons ( ) ( ) and fan control button simultaneously again for more than 5 seconds to cancel the function setting mode. In addition, the function setting mode will be automatically canceled after 1 minute if no operation is performed.
(7) After completing the FUNCTION SET TING, be sure to turn off
the power and turn it on again.
Setting the Ceiling Height
• Select the setting values in the table below according to the height of the ceiling. (The unit is factory-set to “00”.)
Setting Description [m] Funct ion Number Setting Value
Standard
(3. 2m)
20
00
Low ceiling
(2.7m)
01
High ceiling
(4. 2m)
02
The ceiling height values are for the 4-way outlet.
Do not change this setting in the 3 -way outlet mode.
Setting the vertical direction adjusting scope
• To prevent from draft, we recommend using “upward mode”. (The unit is factory-set to “00”.)
Setting Description Func tion Number Setting Value
Standard
23
00
Upward 01
UP
Ceiling
Standard
Upward
Swing ra nge
Outlet cross section
- (01 - 30) -
CASSETTE TYPE
AU
A45L
CASSETTE TYPE
AU
A45L
Setting the Outlet Directions
• Select the setting values in the table below for using a 3-way outlet. (The unit is factory-set to “0 0”.)
Setting Description Func tion Number Setting Value
4-way
22
00
3-way 01
Setting the Filter Sign
• The indoor unit has a sign to inform the user that it is time to clean the lter.
• Select the time setting for the lter sign display interval in the table below according to the amount of dust or debris in the room. (The unit is factory-set to “00”.)
• If you do not wish the lter sign to be displayed, select the setting value for “No indication”.
Setting Description Func tion Number Setting Value
Standard
(2,500 hours)
11
00
Long inter val
(4,400 hours)
01
Short interval
(1,250 hours)
02
No indication 03
Setting the Cooler Room Temperature Correction
• Depending on the installed environment, the room temperature sensor may require a correction. The settings may be selected as shown in the table below. (The unit is factory-set to “0 0”.)
Setting Description Func tion Number Setting Value
Standard
30
00
Lower control 01
Setting the Heater Room Temperature Correction
• Depending on the installed environment, the room temperature sensor may require a correction. The settings may be changed as shown in the table below. (The unit is factoryset to “00”.)
Setting Description Function Numbe Setting Value
Standard
31
00
Lower control 01
Slightly warmer control 02
Warmer control 03
Setting Other Functions
• The following settings are also possible, depending on the operating conditions. (The unit is factory-set to “00”.)
Auto Restart
Setting Description Function Number Setting Value
Yes
40
00
No 01
Indoor Room Temperature Sensor Switching Function
(Wired remote controller only)
Setting Description Func tion Number Setting Value
No
42
00
Yes 01
• If setting value is “00”, room temperature is controlled by the indoor unit temperature sensor.
• If setting value is “01”, room temperature is controlled by either indoor unit temperature sensor or remote control unit sensor.
Setting record
• Record any changes to the settings in the following table.
Setting Setting Value
Ceiling height
Vertical direction adjusting scope
Outlet directions
Filter sign
Cooler room temperature correction
Heater room temperature correction
Auto restart
Indoor room temperature sensor switching function
After completing the FUNCTION SETTING, be sure to turn off the power and turn it on again.
3. Setting the room temperature detection location
The detection location of the room temperature can be selected from the following two examples. Choose the detection location that is best for the installation location.
A. Indoor unit setting (factory setting)
The room temperature is detected by the indoor unit temperature se nso r.
(1) When the THERMO SENSOR but ton is pressed, the lock
display ashes because the function is locked at the factory.
A
Indoor unit
B. Indoor unit/remote controller setting (room
temperature sensor selection)
The temperature sensor of the indoor unit or the remote controller can be used to detect the room temperature.
(1) Enable the room temperature sensor selection in FUNCTION
SETTING, which will be described later.
(2) Press the THERMO SENSOR button for 5 seconds or more to
select the temperature sensor of the indoor unit or the remote controller.
B
Indoor unit
NOTE
If the function to change the temperature sensor is used as shown in examples A (other than example B), be sure to lock the detection location. If the function is locked, the lock display will ash when the THERMO SENSOR button is pressed.
- (01 - 31) -
CASSETTE TYPE
AU
A45L
CASSETTE TYPE
AU
A45L
OPTIONAL PARTS1-13.
Exterior Parts name Model No. Summary
Air outlet
shutter plate
UTR-YDZC
Air outlet shutter plate is installed at the air outlet when 3-way direction is performed.
Wide panel UTG-AGYA-W
Wide panel hides the gap between the ceiling hole and the Decoration panel.
Panel spacer UTG-BGYA-W
Installation in a space of 256mm or greater is possible by using panel spacer when the height behind the ceiling is low. (Normal behind the ceiling installation height is 298mm.)
IR Receiver kit UTY-LRHA1
Unit control is performed by wireless remote controller
Wired remote
controller
UTB-UD
Unit control is performed by wired remote controller
Insulation kit
for high humidity
UTZ-KXGA
Install when the under roof condition is expected to be the humidity of over 80% and the temperature of over 30 °C
External
connect kit
UTY-XWZX
Use to connect with various peripheral devices and air conditioner PC board.
External
control set
UTD-ECS5A
Use to connect with various peripheral devices and air conditioner PC board.
- (01 - 32) -
CASSETTE TYPE
AU
A45L
CASSETTE TYPE
AU
A45L
Exterior Parts name Model No. Summary
Fresh air intake
kit
UT Z-V XGA
It can be taken in fresh air of up to 10% of “high” air volume of the indoor unit by attaching Fresh Air Intake Kit to cassette type indoor unit.
D2D_AO052E/01
2009.04.30
SINGLE TYPE :
AOA45LBTL
2. OUTDOOR UNIT
CONTENTS
2. OUTDOOR UNIT
2-1. SPECIFICATIONS
.......................................................................................... 02-01
2-2. DIMENSIONS
..................................................................................................... 02-02
2-3. REFRIGERANT CIRCUIT
......................................................................... 02-03
2-4. WIRING DIAGRAMS
.................................................................................... 02-04
2-5. CAPACITY COMPENSATION RATE FOR PIPE LENGTH
AND HEIGHT DIFFERENCE
................................................................. 02-05
2-6. ADDITIONAL CHARGE CALCULATION
..................................... 02-06
2-7. AIR FLOW
............................................................................................................02-07
2-8. OPERATION NOISE
..................................................................................... 02-08
2-8-1. NOISE LEVEL CURVE
................................................................................. 02-08
2-8-2. SOUND LEVEL CHECK POINT
.................................................................02-09
2-9. ELECTRIC CHARACTERISTICS
....................................................... 02-10
2-10. SAFETY DEVICES
......................................................................................... 02-11
- (02 - 01) -
OUTDOOR UNIT
AO
A45L
OUTDOOR UNIT
AO
A45L
SPECIFICATIONS2-1.
Note :
Specicati ons are based on the f ollowing conditions. Coolin g : Indoor temperature of 27 ˚CD B / 19 ˚CWB.an d outdoo r temper ature of 35 ˚CDB / 24 ˚CWB. Heating : Indoor temperature of 20 ˚CD B / 15 ˚CWB.and outdoor temperature of 7 ˚CD B / 6 ˚CWB. Pipe leng th : 7.5 m, Height differe nce : 0 m.(Out door uni t - Indoor unit)
Type INVERTER HEATPUMP
Model name AOA45LBTL
Power source 230V ~ 50Hz
Available voltage range 198-264V ~ 50Hz
Starting current A 15.0
Fan
Airow rate
Cooling
m3/h
6600
Heating 6600
Type × Q'ty Propeller × 2
Motor output W 103 × 2
Sound pressure level
Cooling
dB(A)
55
Heating 56
Heat exchanger type
Dimensions (H × W × D)
mm
1260 × 900 × 36.4
Fin pitch 1.30
Rows x Stages 2 × 60
Pipe type Copper
Fin type Aluminium
Compressor
Type × Q'ty Twin Rotary × 1
Motor output W 3750
Refrigerant
Type R410A
Charge g 3350
Refrigerant oil Type POE
Enclosure
Material Steel sheet
Colour
BEIGE
( Approximate colour of MUNSELL 10 YR 7.5 / 1.0 )
Dimensions ( H×W×D)
Net
mm
1290 × 900 × 330
Gross 1430 × 1050 × 445
Weight
Net
kg (lb.)
98 ( 216 )
Gross 107 ( 236 )
Connection
pipe
Size
Liquid
mm
Ø 9.52 (Ø 3/8 in.)
Gas Ø 15.88 (Ø 5/8 in.)
Method Flare
Max. length
m
50(chargeless:20)
Max. height difference 30
Operation range
Cooling
˚C
-15 to 46
Heating -15 to 24
- (02 - 02) -
OUTDOOR UNIT
AO
A45L
OUTDOOR UNIT
AO
A45L
DIMENSIONS2-2.
MODEL : AOA45L
(Unit : mm)
MOUNTING POSITION
900
1290
77 31
21
370
9
400
650
151
99
196
170
4-Ø12mm hole
12330
Air flow
Drain cap mounting places
Top view
Side view
Bottom view
Front view
When there are obstacles at the back or front side.
When there are obstacles at the back and front sides.
When there are obstacles at the back, side(s), and
top.
When there are obstacles at the back side with the installation of more than one unit.
100 mm or more
600 mm or more
250 mm or more
250 mm or more
300 mm or more
250 mm or more
(Service space)
300 mm or more
100 mm or more
100 to 300 mm *
600 to 1000 mm
* If the spac e is larg er than th at is stated, the co nditio n will be the same as t hat there are no obstacles.
- (02 - 03) -
OUTDOOR UNIT
AO
A45L
OUTDOOR UNIT
AO
A45L
REFRIGERANT CIRCUIT2-3.
MODEL : AOA45L
- (02 - 04) -
OUTDOOR UNIT
AO
A45L
OUTDOOR UNIT
AO
A45L
WIRING DIAGRAMS2-4.
MODEL : AOA45L
- (02 - 05) -
OUTDOOR UNIT
AO
A45L
OUTDOOR UNIT
AO
A45L
CAPACITY COMPENSATION RATE FOR PIPE LENGTH 2-5. AND HEIGHT DIFFERENCE
This table is created using the maximum capacity.
MODEL : AOA45L
COOLING
Pipe length (m)
5 7.5 10 20 30 40 50
Height
difference H
(m)
1
Indoor unit is upper
than outdoor unit.
30 0.893 0.890 0.870
20 0.919 0.908 0.905 0.885
10 0.979 0.934 0.923 0.920 0.899
7.5 0.988 0.983 0.938 0.927 0.924 0.903
5 1.001 0.992 0.987 0.942 0.931 0.927 0.907
0 1.009 1.000 0.995 0.949 0.938 0.935 0.914
2
Indoor unit is under
than outdoor unit
-5 1.009 1.000 0.995 0.949 0.938 0.935 0.914
-7.5 1.000 0.995 0.949 0.938 0.935 0.914
-10 0.995 0.949 0.938 0.935 0.914
-20 0.949 0.938 0.935 0.914
-30 0.938 0.935 0.914
HEATING
Pipe length (m)
5 7.5 10 20 30 40 50
Height
difference H
(m)
1
Indoor unit is upper
than outdoor unit.
30 0.971 0.950 0.927
20 0.985 0.971 0.950 0.927
10 1.016 0.985 0.971 0.950 0.927
7.5 1.000 1.016 0.985 0.971 0.950 0.927
5 0.978 1.000 1.016 0.985 0.971 0.950 0.927
0 0.978 1.000 1.016 0.985 0.971 0.950 0.927
2
Indoor unit is under
than outdoor unit
-5
0.973 0.995
1.011
0.980 0.966
0.945 0.923
-7.5
0.993
1.009
0.978 0.963
0.943 0.920
-10 1.006 0.975 0.961 0.940 0.918
-20 0.966 0.951 0.931 0.909
-30 0.942 0.921 0.899
Outdoor unit
Indoor unit
Connec tion pipe
2 Indoor unit is under than outdoor unit.
H
Indoor unit
Outdoor unit
Connec tion pipe
1 Indoor unit is upper than outdoor unit.
H
Height difference H
- (02 - 06) -
OUTDOOR UNIT
AO
A45L
OUTDOOR UNIT
AO
A45L
ADDITIONAL CHARGE CALCULATION2-6.
MODEL : AO
A45L
Refrigerant charge
z
Refrigerant type R410A
Refrigerant amount g 3350
Pipe length m ~ 20 30 40 50
50g/m
Additional charge g 0 (Chargeless) +500 +1000 +1500
- (02 - 07) -
OUTDOOR UNIT
AO
A45L
OUTDOOR UNIT
AO
A45L
AIR FLOW2-7.
MODEL : AOA45L
Cooling
z
Heating
z
Number of
rotations
(r.p.m)
Air ow
Upper fan 850
m
3
/h 6600
l/s 1833
Lower fan 750
CFM 3884
Number of
rotations
(r.p.m)
Air ow
Upper fan 850
m
3
/h 6600
l/s 1833
Lower fan 750
CFM 3884
- (02 - 08) -
OUTDOOR UNIT
AO
A45L
OUTDOOR UNIT
AO
A45L
OPERATION NOISE2-8.
2-8-1. NOISE LEVEL CURVE
MODEL : AOA45L
Heating
z
Octave ba nd soun d pressu re level, d B:(0dB= 0.00 02µba r)
Octave ba nd center frequ ency,Hz
80
70
60
50
40
30
20
10
0
63 125 2 50 500 1,00 0 2,000 4,000 8,00 0
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
Cooling
z
Octave ba nd soun d pressu re level, d B:(0dB= 0.00 02µba r)
Octave ba nd center frequ ency,Hz
80
70
60
50
40
30
20
10
0
63 125 2 50 500 1,00 0 2,000 4,000 8,00 0
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
- (02 - 09) -
OUTDOOR UNIT
AO
A45L
OUTDOOR UNIT
AO
A45L
2-8-2. SOUND LEVEL CHECK POINT
Microphone
Microphone
Air Fiow
1m
- (02 - 10) -
OUTDOOR UNIT
AO
A45L
OUTDOOR UNIT
AO
A45L
ELECTRIC CHARACTERISTICS2-9.
*1) Wiring Spec. :
Selected Sample (Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
*2) Limited Wiring length :
This is the wiring length in case voltage descent is less than 2%. When the wiring length becomes long, please select the wiring of a more larger diameter.
Model Name AOA45L
Power Supply
Voltage V 230 ~
Frequency Hz 50
Max. Operating Current A 20.0
Starting Current A 15.0
*1) Wiring Spec.
Main Fuse (Circuit breaker) Current A 30
Power Cable mm
2
5.3 - 6.0
*2)Limited wiring length m 17
- (02 - 11) -
OUTDOOR UNIT
AO
A45L
OUTDOOR UNIT
AO
A45L
SAFETY DEVICES2-10.
Protection form
Model
AOA45L
Circuit protection
Current fuse (NEAR THE TERMINAL) 25A 250V
Current fuse (NEAR THE TERMINAL) 10A 250V
Current fuse (MAIN PRINTED CIRCUIT BOARD) 5A 250V
Current fuse (MAIN PRINTED CIRCUIT BOARD) 3.15A 250V
Fan motor protection Thermal protection program
OFF : 130±20°C
ON : 100±20°C
High Pressure Protection High Pressure Switch
OFF : 4.2±0.1MPa ON : 3.2±0.15MPa
Compressor protection
Thermal protection program (COMPRESSOR TEMP.)
OFF : 110°C
ON : 80°C
Thermal protection program (DISCHARGE TEMP.)
OFF : 115°C
ON : After 7 minutes