• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Maximum current is maximum value when operated within the operation range.
• *2: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
Airflow rate
Type × Q'tyCross flow fan × 1
Motor outputW272727
Heating
Fan
Cooling
Heating3.23.85.6
Cooling
Heating859089
Cooling
Heating9.09.09.0
Cooling
Heating
Cooling
Heating
Dimensions (H × W × D)
Fin pitch1.3
Rows × Stages2 × 10
Pipe typeCopper tube
Fin typeAluminum
MaterialPolystyrene
Power supply230 V ~ 50 Hz
Power supply intakeOutdoor unit
Available voltage range198—264 V
Starting currentA3.23.85.6
Fan
Airflow rate
Cooling
Heating1,4501,4501,470
3
m
/h
Type × Q'tyPropeller fan × 1
1,6501,6501,700
Motor outputW23
Sound pressure level *1
Sound power level
Cooling
Heating464751
Cooling
Heating585962
dB (A)
dB (A)
Dimensions
(H × W × D)
mm
454749
575962
504 × 650 × 18.2504 × 630 × 36.4
Fin pitch1.3
Heat exchanger type
Rows × Stages1 × 242 × 24
Pipe typeCopper
Type (Material)Corrugate (Aluminum)
Surface treatmentPC Fin
3
cm
240
Compressor
Refrigerant
Refrigerant oil
Fin type
Type × Q'tyDC Rotary × 1
Motor outputW850
Type (Global warming potential)R32 (675)
Chargeg550590
TypePOE
Amount
MaterialSteel sheet
Enclosure
Dimensions
(H × W × D)
Weight
Connection pipe
Color
Net
Gross596 × 798 × 369
Net
Gross2527
Size
Liquid
GasØ 9.52 (3/8)
mm
kg
mm (in)
Approximate color of Munsell 10YR 7.5/1.0
2325
MethodFlare
Pre-charge length
Max. length20
m
Beige
541 × 663 × 290
Ø 6.35 (1/4)
15
Max. height difference15
Operation range
Drain hose
Cooling
Heating-15 to 24
°C
MaterialPP
SizemmØ 13.0 (I. D.), Ø 16.0 to Ø 16.8 (O. D.)
-10 to 46
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 5 m, Height difference: 0 m.
• Protective function might work when using it outside the operation range.
• *1: Sound pressure level
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
- 3 -
Dimensions
Unit: mm
422487
Outline of indoor unit
for pipe inlet Ø65
for pipe inlet Ø65
43
43
29213329267
10432148311
94
84
270
Models: ASHG07KPCA, ASHG09KPCA, and ASHG12KPCA
- 4 -
Installation space requirement
Unit: mm
Wall hook bracket
Outline of the indoor unit
50 or more
67 or more
The flare connection
part should be installed
outdoors.
40 or more
30 or more
107 or more
1,500 or more
1,800 or more
163 or more
Provide sufficient installation space for product safety.
- 5 -
Models: AOHG07KPCA, AOHG09KPCA, and AOHG12KPCA
Unit: mm
)trap bluB( weiv ediSweiv mottoB
353
353
4-
M1
0 hole
Pitch of bolts for installation
330
Pitch of bolts
for installation
106450
Top view
618636691
541
20
290
0333
Side viewSide viewFront view
Drain port Ø42
Airflow
184
120
37
331
170
- 6 -
Refrigerant circuit
Heat exchanger
Th
: Thermistor (Pipe temperature)
Th
3-way
valve
(INDOOR)
Th
PI
2-way
Muffler
Th
R
D
valve
4-way valve
Compressor
Expansion valve
Heat exchanger
Strainer
Strainer
(OUTDOOR)
Th
Th
Th
Th
Cooling
Heating
D
: Thermistor (Discharge temperature)
: Thermistor (Outdoor temperature)
O
HO
: Thermistor (Heat exchanger out temperature)
: Thermistor (Room temperature)
R
PI
Th
Th
HO
O
- 7 -
PCB circuit diagram
Models : ASHG07KPCA
ASHG09KPCA
ASHG12KPCA
CONTROL UNIT
ASHG07KPCA : EZ-0180BHSE
ASHG09KPCA : EZ-0180CHSE
ASHG12KPCA : EZ-0180DHSE
If you use a wireless remote controller, the lamp on the photo detector unit will output error
codes by way of blinking patterns. If you use a wired remote controller, error codes will appear on the remote control display. See the lamp blinking patterns and error codes in the
table. An error display is displayed only during operation.
[Troubleshooting with the indoor unit display]
OPERATION indicator lamp (green)
TIMER indicator lamp (orange)
ECONOMY indicator lamp (green)
- 10 -
Error display
OPERATION
lamp
(green)
(1)
(1)
(1)
(1)
(2)
TIMER
lamp
(orange)
(1)
(2)
(5)
(8)
(2)
ECONOMY
lamp
(green)
Error codeDescription
Serial communication error
• Wired remote controller communication error
• Server room control communication error
Check run unfinished
Automatic airflow adjustment error
External communication error
Indoor unit capacity error
(2)
(2)
(2)
(3)
(3)
(3)
(3)
(3)
(3)
Combination error
Indoor unit address setting error
(6)
Connection unit number error in
(9)
wired remote controller system
Power supply interruption error
(1)
Indoor unit PCB model information
(2)
error
Indoor unit motor electricity
(3)
consumption detection error
Manual auto switch error
(5)
Indoor unit power supply error for
(9)
fan motor
(3)
(4)
Display mode
(10)
(1)
: 0.5s ON / 0.5s OFF
●
◊
: 0.1s ON / 0.1s OFF
( ) : Number of flashing
Indoor unit communication circuit
(wired remote controller) error
Room temp. sensor error
- 11 -
Error display
OPERATION
lamp
(green)
(4)
(5)
(5)
(6)
(6)
(6)
TIMER
lamp
(orange)
(2)
(1)
(15)
(2)
(3)
(4)
ECONOMY
lamp
(green)
Error codeDescription
Indoor unit heat ex. middle temp.
sensor error
Indoor unit fan motor error
Indoor unit error
Outdoor unit main PCB
model information error or
communication error
Inverter error
Active filter error, PFC circuit error
(6)
(6)
(6)
(7)
(7)
(7)
(7)
(7)
(5)
Trip terminal L error
Outdoor unit rush current limiting
(8)
resister temp. rise error
Display PCB microcomputers
(10)
communication error
Discharge temp. sensor error
(1)
Compressor temp. sensor error
(2)
Outdoor unit Heat Ex. liquid temp.
(3)
sensor error
Outdoor temp. sensor error
(4)
Suction Gas temp. sensor error
(5)
(7)
(7)
Display mode
(6)
(7)
: 0.5s ON / 0.5s OFF
●
◊
: 0.1s ON / 0.1s OFF
( ) : Number of flashing
• 2-way valve temp. sensor error
• 3-way valve temp. sensor error
Heat sink temp. sensor error
- 12 -
Error display
OPERATION
lamp
(green)
(8)
(8)
(8)
(8)
(9)
TIMER
lamp
(orange)
(2)
(3)
(4)
(6)
(4)
ECONOMY
lamp
(green)
Error codeDescription
• Sub-cool Heat Ex. gas inlet
temp. sensor error
• Sub-cool Heat Ex. gas outlet
temp. sensor error
Liquid pipe temp. sensor error
Current sensor error
• Discharge pressure sensor error
• Suction pressure sensor error
• High pressure switch error
Trip detection
(9)
(9)
(9)
(9)
(10)
(10)
(10)
(10)
(5)
Compressor rotor position
detection error (permanent stop)
Outdoor unit fan motor 1 error
(7)
Outdoor unit fan motor 2 error
(8)
4-way valve error
(9)
Discharge temp. error
(1)
Compressor temp. error
(3)
High pressure error
(4)
Low pressure error
(5)
Display mode
: 0.5s ON / 0.5s OFF
●
◊
: 0.1s ON / 0.1s OFF
( ) : Number of flashing
- 13 -
Accessories
Part nameExteriorQ’tyPart nameExteriorQ’ty
Operating manual
Operating manual
(CD-ROM)
Installation manual
Wall hook bracket
1Battery2
1Cloth tape1
1Tapping screw5
1Remote controller1
- 14 -
Part nameExteriorQ’tyPart nameExteriorQ’ty
Drain pipe
1
- 15 -
Optional parts
ExteriorPart nameModel nameSummary
Remote
controller holder
Wireless LAN
adapter
UTZ-RXLA
UTY-TFSXF2
Wall or pillar mountable, and holds the
wireless remote controller.
Remotely manage an air conditioning
system using mobile devices such as
smartphones and tablets.
- 16 -
1902G4799