Fujitsu AS*G24LFCA, AS*G30LFCA, AS*G24LFCC, AO*G30LFT, AO*G24LFLAO*G24LFCC Service Instruction

SPLIT TYPE ROOM AIR CONDITIONER
WALL MOUNTED
type
Models Indoor unit Outdoor unit
AS*G24LFCA AS*G24LFCC AS*G30LFCA
INVERTER
SERVICE
INSTRUCTION
R410A
CONTENTS
1. DESCRIPTION OF EACH CONTROL OPERATION
1. COOLING OPERATION................................................................................................
3. DRY OPERATION.........................................................................................................
2. HEATING OPERATION.................................................................................................
5. INDOOR FAN CONTROL..............................................................................................
4. AUTO CHANGEOVER OPERATION............................................................................
7. LOUVER CONTROL.....................................................................................................
6. OUTDOOR FAN CONTROL..........................................................................................
9. TIMER OPERATION CONTROL...................................................................................
8. COMPRESSOR CONTROL..........................................................................................
11. TEST OPERATION CONTROL...................................................................................
10. ELECTRONIC EXPANSION VALVE CONTROL........................................................
13. FOUR-WAY VALVE EXTENSION SELECT................................................................
12. PREVENT TO RESTART FOR 3 MINUTES (3 MINUTES ST)...................................
15. MANUAL AUTO OPERATION (Indoor unit body operation).......................................
14. AUTO RESTART.........................................................................................................
16. FORCED COOLING OPERATION..............................................................................
18. 10°C HEAT OPERATION............................................................................................
17. COMPRESSOR PREHEATING..................................................................................
19. ECONOMY OPERATION............................................................................................
21. OFF DEFROST OPERATION CONTROL...................................................................
20.
DEFROST OPERATION CONTROL...........................................................................
01-01 01-02 01-02 01-03 01-04 01-06 01-07 01-08 01-09 01-12 01-12
01-12 01-13 01-13 01-13 01-14 01-14 01-14 01-15 01-17
01-12
2. TROUBLE SHOOTING
2-1 ERROR DISPLAY.......................................................................................................
2-1-1 INDOOR UNIT AND WIRED RMOTE CONTROLLER DISPLAY (OPTION)......
3. APPENDING DATA
2-1-2 WIRED REMOTE CONTROLLER DISPLAY (OPTION).....................................
2-2 TROUBLE SHOOTING WITH ERROR CODE............................................................
2-3 TROUBLE SHOOTING WITH NO ERROR CODE......................................................
02-01 02-01 02-02 02-03 02-26
2-4 SERVICE PARTS INFORMATION.............................................................................. 02-31
22. VARIOUS PROTECTIONS.......................................................................................... 01-18
23. COMPRESSOR STOP CONTROL.............................................................................. 01-20
3-1 FUNCTION SETTING.................................................................................................
3-1-1 INDOOR UNIT....................................................................................................
3-1-2 Procedures to change the Function Setting for wireless RC..............................
03-01 03-01 03-03
3-2 Outdoor unit Pressure Value and Total Electric Current Curve................................... 03-05
3-3 Thermistor Resistance Values..................................................................................... 03-09
1 . DESCRIPTION OF EACH CONTROL OPERATION
R410A
WALL MOUNTED type
INVERTER
( Fig.1 : Limit of Maximum Frequency based on Outdoor Temperature )
1. COOLING OPERATION
1-1 COOLING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor. * If the room temperature is 2°C higher than a set temperature, the compressor operation frequency will attain to maximum performance.
minimum frequency
maximum frequency
maximum frequency
AO*G24LFL 15rps 88rps 95rps AO*G24LFCC 13rps 80rps 111rps
Outside air Outside air temperature temperature
36°C
A zone
34°C
32°C
B zone
30°C
21°C
C zone
19°C
D zone
Hi Me Lo Quiet A zone 95rps 74rps 62rps 38rps B zone 95rps 74rps 62rps 38rps C zone 95rps 74rps 62rps 38rps
24LFL
30LFT
D zone 68rps 51rps 42rps 26rps E zone 68rps 51rps 42rps 26rps F zone 68rps 51rps 42rps 26rps
( Table 1 : Compressor Frequency Range )
When the compressor operates for 30 minutes continuously at over the maximum frequency , the maximum frequency is changed from Maximum Frequency to Maximum Frequency .
01-01
E zone
F zone
10°C
0°C
12°C
2°C
* When the room temperature is between +2°C to -2.5°C of the setting temperature, the compressor frequency is controlled within the range shown in Table1. However, the maximum frequency is limited in the range shown in Fig.1 based on the fan speed mode and the outdoor temperature.
* If the room temperature is some degrees lower than a set temperature, the compressor will be stopped.
A zone 72rps 49rps 41rps 29rps B zone 72rps 49rps 41rps 29rps C zone 55rps 41rps 36rps 29rps D zone 41rps 36rps 31rps 20rps E zone 41rps 36rps 31rps 20rps F zone 41rps 36rps 31rps 20rps
AO*G30LFT 16rps 51rps 72rps
A zone 111rps 67rps 56rps 34rps B zone 111rps 67rps 56rps 34rps C zone 111rps 67rps 56rps 34rps
24LFCC
D zone 62rps 47rps 40rps 25rps E zone 62rps 47rps 40rps 25rps F zone 62rps 47rps 40rps 25rps
2. HEATING OPERATION
2-1 HEATING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor. * If the room temperature is lower by 3°C than a set temperature, the compressor operation frequency will attain to maximum performance. * If the room temperature is some degrees higher than a set temperature, the compressor will be stopped. * When the room temperature is between +2.5°C to -3°C of the setting temperature, the compressor frequency is controlled within the range shown in Table2.
( Table 2 : Compressor Frequency Range )
01-02
minimum frequency
maximum frequency
AO*G24LFL
AO*G30LFT
16rps 133rps
16rps 90rps
3. DRY OPERATION
3-1 INDOOR UNIT CONTROL
The compressor rotation frequency shall change according to the temperature, set temperature, and room temperature variation which the room temperature sensor of the indoor unit body has detected as shown in the Table3. However, after the compressor is driven, the indoor unit shall run at operation frequency of 68rps (24L), 43rps (30L), for a minute.
Ts+0.5°C
Ts -1.5°C
Ts -0.5°C
Ts+1.5°C
( Table3 : Compressor frequency )
( Fig.2 : Compressor Control based on Room Temperature )
Operating frequency
38rps 18rps
0rps
24LFL
X zone J zone Y zone
Operating frequency
J zone Y zone
X zone 34rps
16rps
0rps
24LFCC
Room Room temperature temperature
X zone
J zone
Y zone
AO*G24LFCC
14rps 120rps
Operating frequency
J zone Y zone
X zone 29rps
16rps
0rps
30LFT
4. AUTO CHANGEOVER OPERATION
01-03
Operation flow chart
START
Room temp.
Room temp.
>Ts+2°C ?
COOLING OPERATION
HEATING OPERATION
YES
YES
NO
NO
NO
NO
YES
YES
TS : Setting temperature
<Ts- 2°C ?
Thermostat remains
in OFF state for 6 minutes or
longer?
System stops
or operation command other than
auto changeover operation?
NO
NO
Thermostat remains
in OFF state for 6 minutes or
longer?
System stops
or operation command other than
auto changeover operation?
YES
YES
When the air conditioner is set to the AUTO mode by remote control, operation starts in the optimum mode from among the HEATING, COOLING, DRY and MONITORING modes. During operation, the optimum mode is automatically switched in accordance with temperature changes. The temperature can be set between 18°C and 30°C in 1°C steps.
5. INDOOR FAN CONTROL
The airflow can be switched in 5 steps such as AUTO, QUIET, LOW, MED, HIGH, while the indoor fan only runs. When Fan mode is set at [AUTO], it operates on [MED] Fan Speed.
01-04
2. FAN OPERATION
3. COOLING OPERATION
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature, as shown in Fig. 3. On the other hand, if switched in [HIGH] [QUIET], the indoor motor will run at a constant airflow of [COOL] operation modes QUIET, LOW, MED, HIGH, as shown in Table5.
( Fig.3 : Airflow change - over ( Cooling : AUTO ) )
When the room temperature rises
When the room temperature drops
TR : Room temperature Ts : Setting temperature
TR-Ts > 2°C
1°C > TR-Ts
2°C > TR-Ts > C
=
TR-Ts > 2.5°C
=
1.5°C > TR-Ts
2.5°C > TR-Ts > 1.5°C
=
HIGH mode
MED mode
LOW mode
1. Fan speed
( Table4 : Indoor Fan Speed )
Operation mode Air flow mode
Speed (rpm)
1480 1320
1220 1020
Cooling/ Fan
Hi
Hi
860 680 270 (480)
1430 (1480)
Me+ Me
Me
Heating
Lo
Lo
1220 1020
Quiet
Quiet
860
1530 1320 1220 1020
900 720
270 1430 1220 1020
900
Dry
S-Lo
X zone: 860
J zone: 780
X zone: 900
J zone: 780
Cool air prevention
AS*G24LFCA(LFCC) AS*G30LFCA
4. DRY OPERATION
Refer to the Table4. During the dry mode operation, the fan speed setting can not be changed.
The maximum value of the indoor fan speed is set as shown in Fig.5, based on the detected temperature by the indoor heat exchanger sensor on heating mode.
( Fig.5 : Cool Air Prevention Control )
01-05
5. HEATING OPERATION
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature, as shown in Fig.4. On the other hand, if switched in [HIGH] [QUIET], the indoor motor will run at a constant airflow of [HEAT] operation modes QUIET, LOW, MED, HIGH, as shown in Table5.
6. COOL AIR PREVENTION CONTROL (Heating mode)
( Fig.4 : Airflow change - over ( Heating : AUTO ) )
TR-Ts > -1.5°C
=
-2.5°C > TR-Ts
-1.5°C > TR-Ts > -2.5°C
=
TR-Ts > -1°C
=
-2°C > TR-Ts
-1°C > TR-Ts > -2°C
=
When the room temperature rises
When the room temperature drops
TR : Room temperature Ts : Setting temperature
LOW mode
MED mode
MED+ mode
42°C
30°C
34°C
Indoor heat exchanger temperature
Indoor heat exchanger temperature
Hi
Me+
Lo
Cool air prevention
39°C 37°C
37°C
32°C
28°C
S-Lo
Switch the airflow [AUTO] at cooling mode, and the indoor fan motor will run as shown in Fig.6.
7. MOISTURE RETURN PREVENTION CONTROL (Cooling mode& Dry mode)
( Fig.6 : Indoor Fan Control )
Compressor
ON
OFF
Indoor fan Setting air flow
Indoor fan (as shown in Table 5)
S-Lo
OFF
10 30 60 180 60 180 60 10 30
(SEC)
( Table5 : Indoor fan speed )
X zone J zone
AS*G24LFCA / LFCC 860rpm 780rpm
Y zone
0 270rpm ( 24LFCC: 480rpm) 860rpm
AS*G30LFCA 900rpm 780rpm 0 270rpm 900rpm
Dry
Cooling
Switch the airflow at cooling mode, and the indoor fan motor will run as shown in Fig.6. It depends on the function setting "Indoor unit fancontrol for energy saving"
8. INDOOR UNIT FAN CONTROL FOR ENEGY SAVING (Cooling mode)
6. OUTDOOR FAN CONTROL
01-06
( Table7 : Outdoor fan speed )
*
The outdoor fan speed mentioned above depends on the compressor frequency. (When the compressor frequency increases, the outdoor fan speed also changes to the higher speed. When the compressor frequency decreases, the outdoor fan speed also changes to the lower speed.)
*
After the defrost control is operated on the heating mode, the fan speed keeps at the higher speed as table8 without relating to the compressor frequency.
( Table8 : Outdoor fan speed after the defrost )
1. Outdoor Fan Motor
2. Fan Speed
AC Motor DC Motor
AO*G24LFL / LFCC / 30LFT
Following table shows the type of the outdoor fan motor. The control method is different between AC motor and DC motor.
( Table6 : Type of Motor )
AO*G24LFL / LFCC 1100rpm
Cooling Heating
AO*G24LFL
AO*G30LFT
D F
Zone
1050/ 820/ 720/ 500
1100/ 820/ 720/ 550/ 450
900/ 850/ 800/ 620/ 550/ 450
Refer to Fig.7
(rpm)
430/ 350/ 300 G 350/ 290/ 260 H 280/ 250/ 230
D F
500/ 320/ 250
850/ 800/ 620/ 500/ 400
300/ 230 /200
G H
220/ 200
Dry
500
550/ 450
AO*G30LFT 900rpm
( Fig.7 : Outside air temperature zone selection )
12°C
C
Outside air temperature
Outside air temperature
F zone
D zone
G zone
H zone
2°C
- 8°C
10°C
- 10°C
(AS*G24L is nonaction)
AO*G24LFCC
1100/ 1050/ 780/ 720/ 590/ 480
D F
430/ 370/ 300
1100/ 870/ 720/ 500
350/ 300 /260
G H
250/ 200
530
7. LOUVER CONTROL
01-07
1. VERTICAL LOUVER CONTROL
Each time the button is pressed, the air direction range will change as follow:
(Function Range)
Types of Airflow Direction Setting:
Use the air direction adjustments within the ranges shown above.
The Remote Controller's display does not change.
The Remote Controller's display does not change.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
During Cooling / Dry mode : Horizontal flow During Heating mode : Downward flow
During AUTO mode operation, for the first a few minutes after beginning operation, airflow will be horizontal ; the air direction cannot be adjusted during this period.
Only the direction of the Airflow Direction Louver changes; the direction of the Power Diffuser does not change. The airflow direction setting will temporarily become when the temperature of the airflow is low at the start of the Heating mode.
Direction
After beginning of AUTO/HEAT mode operated and automatic defrosting operation time, the air flow will be horizontal . However, the Airflow Direction cannot be adjusted at beginning AUTO operation mode.
: During Heating/ Cooling/ Dry modes
Cooling mode / Dry mode / Fan mode( ) : Heating mode / Fan mode( ) :
3. SWING OPERATION
When the swing signal is received from the remote controller, the vertical louver starts to swing.
(Swinging Range)
1 3
1
4
4
6
36
To select Vertical Airflow Swing Operation
To select Horizontal Airflow Swing Operation
When the swing signal is received from the remote controller, the horizontal louver starts to swing.
All mode :
(Swinging Range)
5
1
To select Vertical and Horizontal Airflow Swing Operation
When the indoor fan is S-Lo or Stop mode, the swing operation is interrupted and it stops at either upper end or bottom end.
When the indoor fan is S-Lo or Stop mode, the swing operation is interrupted and it stops at either upper end or bottom end.
When the horizontal swing signal is input from remote control, the combination of the vertical and horizontal swing operation is performed.
2. HORIZONTAL LOUVER CONTROL
Each time the button is pressed, the air direction range will change as follows.
(Function Range)
Cooling / Heating / Dry mode / Fan mode
1 2
3
4
5
6
,,,,,
1
2
3
4
5
8. COMPRESSOR CONTROL
01-08
1. OPEARTION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as shown in the table9.
Cooling Heating
Min Max Min Max Min Max
Dry
AO*G24LFL
AO*G30LFT
15rps 95rps 16rps 133rps 18rps 38rps
16ps 72rps 16rps 90rps 16rps 29rps
AO*G24LFL
40rps 60rps 75rps 93rps 120rps
AO*G30LFT
30rps 47rps 60rps
(Table 9 : Compressor Operation Frequency Range)
2. OPEARTION FREQUENCY CONTROL AT NORMAL START UP
The compressor frequency soon after the start-up is controlled as shown in the Fig.8.
(Fig.8 : Compressor Control at Start-up)
Time
Time Time Time
Time
(Frequency)
Frequency
Frequency
Frequency Frequency
Frequency
Frequency
Frequency
Frequency
Frequency
Frequency
Time
Time Time Time
Time
AO*G24LFL
70sec 180sec 320sec 500sec 550sec
AO*G30LFT
60sec 120sec 180sec
(Time)
AO*G24 LFCC 13rps 111rps 14rps 120rps 16rps 34rps
AO*G24LFCC
35rps 53rps 66rps 82rps 106rps
AO*G24 LFCC
80sec 160sec 300sec 400sec 500sec
9. TIMER OPEARTION CONTROL
1. OPEARTION FREQUENCY RANGE
The table10 shows the available timer setting based on the product model.
ON TIMER / OFF TIMER PROGRAM TIMER SLEEP TIMER
AS*G24 / LFCC / 30LFCA
OFF timer : When the clock reaches the set time, the air conditioner will be turned off.
Operation mode
Stop mode
Set time of timer
ON timer : When the clock reaches the set time, the air conditioner will be turned on.
Operation mode
Stop mode
Set time of timer
The program timer allows the OFF timer and ON timer to be used in combination one time.
Operation mode
Operation will start from the timer setting (either OFF timer or ON timer) whichever is closest to the clock's current timer setting. The order of operations is indicated by the arrow in the remote control unit's display.
SLEEP timer operation cannot be combined with ON timer operation.
( Table 10 : Timer Setting )
2. PROGRAM TIMER
Stop mode
Stop mode
Stop mode
Operation mode
Operation mode
Set time Set time Set time Set time
01-09
9-1 WIRELESS REMOTE CONTROLLER
3. SLEEP TIMER
If the sleep is set, the room temperature is monitored and the operation is stopped automatically. If the operation mode or the set temperature is change after the sleep timer is set, the operation is continued according to the changed setting of the sleep timer from that time ON.
Set temperature rises
( Ts : Set temperature )
Stop of operation
Set temperature lowers
( Ts : Set temperature )
Ts
Stop of operation
In the cooling operation mode
When the sleep timer is set, the setting temperature is increased 1°C. It increases the setting temperature another 1°C after 1 hour. After that, the setting temperature is not changed and the operation is stopped at the time of timer setting.
Ts
+1°C
+2°C
Set
60min
In the heating operation mode
When the sleep timer is set, the setting temperature is decreased 1°C. It decreases the setting temperature another 1°C every 30 minutes. Upon lowering 4°C, the setting temperature is not changed and the operation stops at the time of timer setting.
-4°C
-3°C
-2°C
-1°C
Set
30min
30min
30min
01-10
01-11
9-2 WIRED REMOTE CONTROLLER (OPTION)
The table11 shows the available timer setting based on the product model.
ON TIMER / OFF TIMER WEEKLY TIMER TEMPERATURE SET BACK TIMER
AS*G24 / LFCC / 30LFCA
( Table11 : Timer Setting )
1. ON TIMER / OFF TIMER
Same to 8-1 1.ON TIMER / OFF TIMER and shown in those.
2. WEEKLY TIMER
This timer function can set operation times of the each day of the week. All days can be set together,the weekly timer can be used to repeat the timer setting for all of the days.
3. TEMPERATURE SET BACK TIMER
This timer function can change setting temperature of setting operation times of the each day of the week. This can be together with other timer setting.
Normal tmp.
ON
OFF
Setting day Setting day Setting day
ON OFF ON OFF ON OFF
Set time Set time
Set back tmp.
Set time Set time
10. ELECTRONIC EXPANSION VALVE CONTROL
The most proper opening of the electronic expansion valve is calculated and controlled under the present operating condition based on the Table12. The compressor frequency, the temperatures detected by the discharge temperature sensor, the indoor heat exchanger sensor, the outdoor heat exchanger sensor, and the outdoor temperature sensor.
The expansion valve is set at 480 pulses after 110seconds(24L), 120seconds(30L), of stopping compressor.
At the time of supplying the power to the outdoor unit, the initialization of the electronic expansion valve is operated (528 pulses are input to the closing direction).
11. TEST OPERATION CONTROL
[ Wireless remote controller ]
Under the condition where the air conditioner runs, press the test run button of the remote control, and the test operation control mode will appear. During test running, the operation lamp and timer lamp of the air conditioner body twinkle simultaneously.
[ Wired remote controller (Option) ]
If the operation lamp is on, press the Start/Stop button to turn it off. Press the Master Control and Fan Control buttons at the same time for more than two seconds to start the test operation. The operation lamp will light up and "o1" will be displayed on the set temperature display.
[ Release ]
Perform the test operation for 60 minutes. Pressing the Start/Stop button will stop the test operation.
The compressor won't enter operation status for 3 minutes after the compressor is stopped, even if any operation is given.
At the time when the air conditioner is switched from the cooling mode to heating mode, the compressor is stopped, and the four-way valve is switched in 3 minutes later after the compressor stopped.
12. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST )
13. FOUR-WAY VALVE EXTENSION SELECT
01-12
( Table12 : The pulse range of the electronic expansion valve control )
Cooling / Dry mode Heating mode Cooling / Dry mode Heating mode
AO*G24LFL / LFCC
AO*G30LFT
Operation mode Pulse range
between 60 to 480 pulses. between 60 to 480 pulses. between 53 to 480 pulses. between 40 to 480 pulses.
15. MANUAL AUTO OPERATION (Indoor unit body operation)
If MANUAL AUTO Button is set, the operation is controlled as shown in Table13. If the remote control is lost or battery power dissipated, this function will work without the remote control.
OPERATION MODE Auto changeover FAN CONT. MODE Auto TIMER MODE Continuous (No timer setting available) SETTING TEMP. 24°C SETTING LOUVER Standard SWING OFF
(Table13)
01-13
16. FORCED COOLING OPERATION
Forced cooling operation is started when pressing MANUAL AUTO button for 10 seconds or more. During the forced cooling operation, it operates regardless of room temperature sensor. Operation LED and timer LED blink during the forced cooling operation. They blink for 1 second ON and 1 second OFF on both operation LED and timer LED (same as test operation). Forced cooling operation is released after 60 minutes of starting operation. The FORCED COOLING OPERATION will start as shown in Table14.
Manual auto operation
OPERATION MODE FAN CONT. MODE TIMER MODE SETTING TEMP. SETTING LOUVER
SWING
( Table14 )
Forced cooling operation Cooling Hi
Initial : Horizontal (It is changed follow as setting of remote controller)
OFF
Room Temp is not controlled
-
If cooling operation is set, the operation is controlled as shown in Table14.
When the power was interrupted by a power failure, etc. during operation, the operation contents at that time are memorized and when power is recovered, operation is automatically started with the memorized operation contents. When the power is interrupted and recovered during timer operation, since the timer operation time is shifted by the time the power was interrupted, an alarm is given by blinking (7 sec ON/2 sec OFF) the indoor unit body timer lamp.
[ Operation contents memorized when the power is interrupted ]
Operation mode Set temperature Set air flow Timer mode and timer time Set air flow Direction Swing ECONOMY operation 10°C HEAT operation
14. AUTO RESTART
01-14
When the outdoor heat exchanger temperature is lower than 0°C and the heating operation has been stopped for 30 minutes, power is applied to the compressor and the compressor is heated. (By heating the compressor, warm air is quickly discharged when operation is started.) When operation was started and when the outdoor heat exchanger temperature rises to 2°C or greater, preheating is ended.
17. COMPRESSOR PREHEATING
( Fig.9 : Compressor Preheating )
ON
0°C
2°C
OFF
18. 10°C HEAT OPERATION
The 10°C HEAT operation functions by pressing 10°C HEAT button on the remote controller. The 10°C HEAT operation is almost the same operation as below settings.
Mode Heating Setting temperature 10°C Fan mode AUTO
( Table15 )
19. ECONOMY OPERATION
The ECONOMY operation functions by pressing ECONOMY button on the remote controller. The ECONOMY operation is almost the same operation as below settings.
Mode Cooling/ Dry Heating Target temperature Setting temp.+1°C Setting temp.-1°C
( Table16 )
20. DEFROST OPERATION CONTROL
01-15
1. CONDITION OF STARTING THE DEFROST OPERATION
The defrost operation starts when the outdoor heat exchanger temperature sensor (Tn) detects the temperature lower than the values shown in Table17.
2. CONDITION OF THE DEFROST OPERATION COMPLETION
Defrost operation is released when the conditions become as shown in Table18.
( Table18 : Defrost Release Condition )
Release Condition
Outdoor heat exchanger temperature sensor value is higher than
+13°C
or Compressor operation time has passed 15 minutes.
( Table 17 : Condition of starting Defrost Operation )
1 time defrosting after starting operation
ST
Defrosting after 2 time upon starting operation
ND
Compressor integrating operation time
Compressor integrating operation time
Compressor integrating operation time
Less than 17 min. 17 to 57 min. More than 57 min.
Does not operate
- 9°C
(Ta*1 - Tn > 5°C)
- 5°C
Less than 35 min. More than 35min.
Does not operate
Integrating defrost (Constant monitoring)
More than 210 min. (For long continuous operation)
Less than 10min.*1 (For intermittent operation)
- 3°C
(and after 30 minutes, if the - 3°C)
More than 210 min. (For long continuous operation)
- 5°C
(and after 5 minutes, if the - 5°C)
OFF count of the compressor 40 times.
*1 : If the compressor continuous operation time is less than 10 minutes and outdoor air temperature is less than 2°C once while operating the compressor, the OFF number of the compressor is counted. If any defrost operated, the compressor OFF count is cleared.
Tn-Tn10 < - 5deg Tn-Tnb < - 2deg However, Tn - 6°C
Tn10 : Temperature of continuous operation at 10minutes. Tnb : Back 5minutes temperature
=
*1 : Ta (Outdoor air temperature)
Tn - 25°C
01-16
Compressor OFF Outdoor fan motor OFF 30 sec later four - way valve OFF 35 sec later compressor ON
3. Defrost Flow Chart
The defrosting shall proceed by the integrating operation time, outdoor temperature and outdoor heat exchanger temperature as follows.
(Not defrosted for 10 minutes)
Heating operation start : Compressor ON
Outdoor heat exchanger temperature:
Over +13°C
or
Compressor ON time: Maximum 15 minutes
Defrost end
Compressor integrating operation: Over 17 min.
Outdoor heat exchanger temperature: Below - 9°C
Outdoor heat exchanger temperature: Below - 5°C
Compressor integrating operation: Over 35 min.
2nd and later defrost
Integrating defrost
(Constant monitoring)
Defrost Indicator: [Operation lamp] 7 sec ON / 2 sec O FF
Defrost start
Tn-Tn10 < - 5deg Tn-Tnb < - 2deg However, Tn <- 6°C
Compressor OFF count : 40 times (Less than 10min.)
1st defrost
Compressor integrating operation: Over 57 min.
Compressor integrating operation: Over 210 min.
Outdoor heat exchanger temperature: Below - 3°C
Compressor integrating operation: Over 210 min.
Outdoor heat exchanger temperature: Below - 5°C
=
(Ta - Tn > 5°C)
=
(and after 5 minutes, if the - 5°C)
(and after 30 minutes, if the - 3°C)
Tn - 25°C
21. OFF DEFROST OPEARTION CONTROL
1. OFF DEFROST OPERATION CONDITION
When operation stops in the [Heating operation] mode, if frost is adhered to the outdoor unit heat exchanger, the defrost operation will proceed automatically. In this time, if indoor unit operation lamp flashes slowly (7 sec ON / 2 sec OFF), the outdoor unit will allow the heat exchanger to defrost, and then stop.
In heating operation, the outdoor heat exchanger temperature is less than -4°C, compressor continuous operation more than 10 minutes, and compressor operation integrating time lasts for more than 30 minutes.
OFF Defrost Flow Chart
Heating operation stop
Outdoor heat exchanger temperature : Below -4°C Compressor continuous operation : Over 10 minutes Compressor integrating operation : Over 30 minutes
Defrost start
Defrost Indicater: [Operation lamp] 7 sec ON / 2 sec OFF
Outdoor heat exchanger temperature :
Over +13°C
or
Compressor ON time : Maximum 15 minutes
Defrost end
2. OFF DEFROST END CONDITION
Release Condition
Outdoor heat exchanger temperature sensor value is higher than +13°C or Compressor operation time has passed 15 minutes.
01-17
22. VARIOUS PROTECTIONS
1. DISCHARGE GAS TEMPERATURE OVERRISE PREVENSION CONTROL
The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas temperature. When the discharge temperature becomes higher than Temperature , the compressor frequency is decreased 20rps (24L) or 10rps (30L), and it continues to decrease the frequency for 20rps (24L) or 10rps (30L) every 120 seconds until the temperature becomes lower than Temperature . When the discharge temperature becomes lower than Temperature , the control of the control of the compressor frequency is released. When the discharge temperature becomes higher than Temperature , the compressor is stopped and the indoor unit LED starts blinking.
AO*G24LFL / LFCC / 30LFT
104°C 101°C 110°C
( Table 19 : Discharge Temperature Over Rise Prevension Control / Release Temperature )
Temperature
Temperature
Temperature
2. CURRENT RELEASE CONTROL
The compressor frequency is controlled so that the outdoor unit input current does not exceeds the current limit velue that was set up with the outdoor temperature. The compressor frequency returns to the designated frequency of the indoor unit at the time when the frequency becomes lower than the release value.
( Table 20-1 : Current Release Operation Value / Release Value for AO*G24LFL / LFCC / 30LFT )
01-18
[ Heating ]
OT : Outdoor Temperature
[ Cooling ]
AO*G24LFL
OT (Control / Release)
7.0A / 6.5A
7.0A / 6.5A
9.5A / 9.0A
12.0A / 11.5A
50°C 46°C 40°C
OT : Outdoor Temperature
AO*G24LFL
OT (Control / Release)
10.5A / 10.0A
13.0A / 12.5A
15.0A / 14.5A
17.0A / 16.5A
17°C 12°C
C
[ Heating ]
OT : Outdoor Temperature
[ Cooling ]
AO*G24LFCC
OT (Control / Release)
7.0A / 6.5A
7.0A / 6.5A
9.5A / 9.0A
12.0A / 11.5A
50°C 46°C 40°C
OT : Outdoor Temperature
AO*G24LFCC
OT (Control / Release)
10.5A / 10.0A
13.0A / 12.5A
15.0A / 14.5A
17.0A / 16.5A
17°C 12°C
C
[ Heating ]
OT : Outdoor Temperature
[ Cooling ]
AO*G30LFT
OT (Control / Release)
9.0A / 8.5A
10.0A / 9.5A
13.0A / 12.5A
16.0A / 15.5A
50°C 46°C 40°C
OT : Outdoor Temperature
AO*G30LFT
OT (Control / Release)
11.0A / 10.5A
13.0A / 12.5A
15.0A / 14.5A
18.0A / 17.5A
17°C 12°C
C
01-19
3. ANTIFREEZING CONTROL (Cooling and Dry mode)
The compressor frequency is decrease on cooling & dry mode when the indoor heat exchanger temperature sensor detects the temperature lower than Temperature . Then, the anti-freezing control is released when it becomes higher than Temperature .
( Table 21 : Anti-freezing Protection Operation / Release Temperature )
Outdoor temperature
Over than 10°C *2
or 12°C *1
Less than 10°C *2
or 12°C *1
*1. When the temperature rises. *2. When the temperature drops.
4°C
7°C
13°C
Temperature
Temperature
01-20
4. COOLING PRESSURE OVERRISE PROTECTION
When the outdoor unit heat exchange sensor temperature rises to 67°C or greater, the compressor is stopped and trouble display is performed.
5. HIGH TEMPERATURE AND HIGH PRESSURE RELEASE CONTROL ( HEATING MODE )
On heating mode, the compressor frequency is controlled as following based on the detection value of the indoor heat exchanger temperature sensor.
Indoor heat exchange temperature
[ Control System ]
It returns to the normal operation
Compressor is stopped
53°C
55°C
63°C
50°C
The compressor frequency is decreased 4rps(24L), 2rps(30L) every 120seconds.
The compressor frequency is decreased 25rps(24L), 15rps(30L) every 120seconds.
6. COMPRESSOR TEMPERATURE PROTECTION
When the compressor temperature sensor detects higher than 110°C(24L),108°C(30L), the compressor is stopped. The protection is released when the compressor temperature sensor detects 80°C after 3 minutes of compressor stop.
7. HIGH PRESSURE PROTECTION
When the pressure switch becomes OFF (Open : higher than 4.2 MPa), the compressor is stopped. It is released when the pressure switch becomes ON (Close : lower than 3.2 MPa) after 3 minutes of compressor stop.
For AO*G24LFL / LFCC / 30LFT
23. COMPRESSOR STOP CONTROL
When the detection value of outdoor temperature sensor is lower than Temp in the table below, the compressor is stopped.
( Table 22 : Operation temperature of compressor stop control )
Temperature
AO*G24LFL / LFCC / 30LFT
Cooling Heating
-15°C
Stable zone
2 . TROUBLE SHOOTING
R410A
WALL MOUNTED type
INVERTER
Manual Auto Switch Error
Indoor Room Thermistor Error
Indoor Unit Model Information Error EEPROM Access Abnormal
Wired Remote Controller Communication Error
Error Contents
Continuous
Continuous
4 times
Continuous2 times
3 times
3 times
5 times
Continuous2 times1 times
Continuous1 times1 times
Trouble shooting
Economy (Green)
Timer (Orange)
Operation (Green)
02-01
2-1 ERROR DISPLAY
2-1-1 INDOOR UNIT AND WIRED REMOTE CONTROLLER DISPLAY
1 times
Serial Communication Error
Indoor Unit Fan Motor Error
Indoor Heat Ex. Thermistor Error
Continuous4 times 2 times
Continuous1 times5 times
Continuous
Continuous4 times
7 times
6 times
1 times
Continuous
7 times 3 times
Continuous
7 times 4 times
Continuous
2 times
7 times
A. F. Voltage Error
Discharge Thermistor Error
Heat Ex. Liquid Outlet Thermistor Error
Outdoor Thermistor Error
Compressor Thermistor Error
Please refer the flashing pattern as follows. Indoor Unit : AS*G24/ 30LFCA, 24LFCC The OPERATION, TIMER, ECONOMY lamps operate as follows according to the error contents.
1,2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
Continuous8 times 4 times
Current Sensor Error
Continuous8 times 6 times
High Pressure Switch Error
Continuous10 times 3 times
Compressure Temp. Error
Continuous10 times 5 times
Low Pressure Error
Continuous
Continuous5 times
9 times
9 times
7 times
Compressor Control Error
Outdoor Unit Fan Motor Error
Continuous4 times9 times
Continuous9 times 9 times
4 Way Valve Error
Continuous1 times10 times
Discharge Temp. Error
Over Current Error
Continuous5 times6 times
IPM Error
Indoor Unit Display
Wired Remote Controller Display
11
12
32
35
41
42
51
64
65
71
72
73
74
84
86
94
95
97
99
A1
A3
A5
02-02
When " " in Temperature Display is displayed, inspection of the air conditioning system is necessary. Please consult authoilzed servise personnel.
2-1-2 WIRED REMOTE CONTROLLER DISPLAY (OPTION)
1. SELF - DIAGNOSIS
SUMOTU WETH FR SA
Unit number (usually 0)
Error code
ex. Self-diagnosis check
2. ERROR CODE HISTORY DISPLAY
Up to 16 memorized error codes may be displayed for the indoor unit connected to the remote controller.
1. Stop the air conditioner operation.
2. Press the SET TEMPERATURE buttons , simultaneously for 3 seconds or more to start the self-diagnosis.
4. Press the SET TEMPERATURE buttons , simultaneously for 3 seconds or more or there is no key input for 60 seconds to stop the display.
3. Press the SET TEMPERATURE button to select the error history number.
SU MO TU WETH FR SA
Error code
Error history number
01234567
FEdcbA98
ı
ı
Lower
Raise
Trouble shooting 1 OUTDOOR UNIT Error Method:
Detective Actuators: Detective details:
Forecast of Cause:
OK
Indicate or Display:
Refer to error code table.
YESYES
NO
Serial Communication Error (Serial Reverse Transfer Error)
Outdoor unit Main PCB Outdoor unit Fan motor
1. Connection failure 2. External cause 3. Main PCB failure 4. Active filter module failure
5. Transistor PCB (IPM) failure 6. Filter PCB failure 7. Outdoor unit Fan motor failure
Check Point 1-1 : Reset the power and operate
Does error indication reappear?
Check Point 1-2 : Check external cause such as noise
Check if the ground connection is proper. Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
Check Point 2 : Check connection
Check any loose or removed connection line of between indoor unit and outdoor unit.
>> If there is an abnormal condition, correct it by referring to Installation Manual or Data & Technical Manual.
Check connection condition in control unit. (If there is loose connector, open cable or mis-wiring)
Check Point 3 : Check the voltage of power supply
Check the voltage of power supply
>> Check if AC216V(AC240V-10%) - 264V(AC240V+10%) appears at outdoor unit terminal L - N.
When the indoor unit cannot receive the serial signal from Outdoor unit more than 2minutes after power ON, or the indoor unit cannot receive the serial signal more than 15seconds during normal operation.
02-03
2-2 TROUBLE SHOOTING WITH ERROR CODE
OK
Check Point 4 : Check serial signal (Reverse transfer signal)
Check serial signal (Reverse transfer signal)
>> Check if indicated value swings between AC90V and AC270V at outdoor unit terminal 1 - 3. >> If it is abnormal, Check the parts as follows.
- Outdoor unit fan motor (PARTS INFORMATION 5)
- Active filter module (PARTS INFORMATION 4)
- Transistor PCB (IPM) (PARTS INFORMATION 7)
- Filter PCB (Check the wire of CN110) >> If Outdoor fan motor is abnormal, replace Outdoor unit fan motor and Main PCB. >> If Active filter module or IPM is abnormal, replace it. >> If the parts are normal, replace Main PCB.
1 2
3 L N
RED
WHITE
BLACK
BLACK WHITE
+
-
Trouble shooting 2 INDOOR UNIT Error Method:
Detective Actuators: Detective details:
Forecast of Cause:
OK
Indicate or Display:
Refer to error code table.
YESYES
NO
OK
Serial Communication Error (Serial Forward Transfer Error)
Indoor unit Controller PCB
1. Connection failure 2. External cause 3. Controller PCB failure
Check Point 1-1 : Reset the power and operate
Does error indication reappear?
Check Point 1-2 : Check external cause such as noise
Check if the ground connection is proper. Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
Check Point 2 : Check connection
Check any loose or removed connection line of between indoor unit and outdoor unit.
>> If there is an abnormal condition, correct it by referring to Installation Manual or Data & Technical Manual.
Check connection condition in control unit. (If there is loose connector, open cable or mis-wiring)
Check Point 3 : Check the voltage of power supply
Check the voltage of power supply
>> Check if AC216V(AC240V-10%) - 264V(AC240V+10%) appears at outdoor unit terminal L - N.
Check Point 4 : Check serial signal (Forward transfer signal)
Check serial signal (Forward transfer signal)
>> Check if indicated value swings between AC30V and AC130V at outdoor unit terminal 2 - 3. >> If it is abnormal, replace Controller PCB.
When the outdoor unit cannot properly receive the serial signal from indoor unit for 10 seconds or more.
02-04
1 2
3 L N
RED
WHITE
BLACK
BLACK WHITE
+
-
Trouble shooting 3 INDOOR UNIT Error Method:
Detective Actuators: Detective details:
Forecast of Cause:
Check Point 2 : Check Wired Remote Controller and Controller PCB
Check Point 1 : Check the connection of terminal
OKOK
Indicate or Display:
Wired Remote Controller Communication Error
Indoor unit Controller PCB Wired Remote Controller (Option)
1. Connection failure 2. Wired Remote Controller failure 3. Controller PCB failure
Check & correct the followings. Check the connection of terminal between Wired Remote Controller and indoor unit, and check if there is a disconnection of the cable.
When the indoor unit cannot properly receive the signal from Wired Remote Controller for 1 minute or more.
02-05
Refer to error code table.
>> If it is DC12V, Remote Control is failure. (Controller PCB is normal) >> Replace Remote Control >> If it is DC 0V, Controller PCB is failure. (Check Remote Control once again) >> Replace Controller PCB
Check Voltage at CN6 (terminal 1-3) of Controller PCB. (Power supply to Remote Control)
02-06
Trouble shooting 4 INDOOR UNIT Error Method:
Indicate or Display:
Indoor Unit Model Information Error EEPROM Access Abnormal
Refer to error code table.
Detective Actuators:
Detective details:
Forecast of Cause:
Check Point 3 : Replace Controller PCB
Check Point 2 : Check Indoor unit electric components
YESYES
NO
Indoor unit Controller PCB
1. External cause 2. Defective connection of electric components 3. Controller PCB failure
Check Point 1-1 : Reset Power Supply and operate
Does Error indication show again?
Check Point 1-2 : Check external cause such as noise
Check if the ground connection is proper. Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
Note : EEPROM
EEPROM(Electronically Erasable and Programmable Read Only Memory) is a non­volatile memory which keeps memorized information even if power is turned off. It can change the contents electronically. To change the contents, it uses higher voltage than normal, and it can not change a partial contents. (Rewriting shall be done upon erasing the all contents.) There is a limit in a number of rewriting.
Change Controller PCB.
Check all connectors. (loose connector or incorrect wiring)
Check any shortage or corrosion on PCB.
When power is on and there is some below case.
1. When model information of EEPROM is incorrect.
2. When the access to EEPROM failed.
Trouble shooting 5 INDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators: Detective details:
Forecast of Cause :
OKOK
Manual Auto Switch Error
Indoor Unit Controller PCB Indicator PCB Manual Auto Switch
When the Manual Auto Switch becomes ON for consecutive 30 or more seconds.
1. Manual Auto Switch failure 2. Controller PCB and Indicator PCB failure
Check Point 1 : Check the Manual Auto Switch
Check if Manual Auto Switch is kept pressed. Check ON/OFF switching operation by using a meter.
>> If Manual Auto Switch is disabled (on/off switching), replace it.
Check Point 2 : Replace Controller PCB and Indicator PCB
If Check Point 1 do not improve the symptom, replace Controller PCB and Indicator PCB and execute the check operation again.
02-07
Refer to error code table.
Detective Actuators:
Indoor unit Controller PCB Room temperature thermistor
Detective details:
Room temperature thermistor is open or short is detected always.
Forecast of Cause :
1. Connector failure connection 2. Thermistor failure 3. Controller PCB failuer
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Rough value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 1 : Check connection of Connector
Check if connector is loose or removed Check erroneous connection Check if thermisto r cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
6.58.010.012.515.820.225.933.6
3.594.355.3Resistance value (k )
OK
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of each indoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Controller PCB and execute the check operation again.
DC
BLACK
BLACK
BLACK BLACK
1 2
1 2
CN3
CN1
1 2 3
1 2 3
RED
WHITE
H/E Thermistor
Room Temp. Thermistor
02-08
Trouble shooting 6 INDOOR UNIT Error Method:
Indicate or Display:
Indoor Room Thermistor Error
Refer to error code table.
Temperature (°C )
Temperature (°C )
0
40 45 50
51015202530
0.931.271.762.47
60 70 80 90
35
0.70
100
Resistance value (k )
Thermistor Characteristics (Rough value)
If Thermistor is either open or shorted, replace it and reset the power.
Detective Actuators:
Indoor unit Controller PCB Heat exchanger (MID) Thermistor
Detective details:
Heat exchanger (MID) thermistor is open or short is detected always.
Forecast of Cause :
1. Connector failure connection 2. Thermistor failure 3. Controller PCB failuer
Check Point 1 : Check connection of Connector
Check if connector is loose or removed Check erroneous connection Check if thermisto r cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
OK
Check Point 2 : Remove connector and check Thermistor resistance value
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of each indoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Controller PCB and execute the check operation again.
DC
BLACK
BLACK
BLACK BLACK
1 2
1 2
CN3
CN1
1 2 3
1 2 3
RED
WHITE
H/E Thermistor
Room Temp. Thermistor
02-09
Trouble shooting 7 INDOOR UNIT Error Method:
Indicate or Display:
Indoor Heat Ex. Thermistor Error
Refer to error code table.
31.739.649.762.980.3103134176
17.120.925.6Resistance value (k )
Temperature (°C )
Temperature (°C )
0
40 45 50
5101520253035
3.094.195.788.1211.6
60 70 80 90 100
Resistance value (k )
02-10
Trouble shooting 8 INDOOR UNIT Error Method:
Indicate or Display:
Indoor unit Fan Motor Error
Refer to error code table.
Detective Actuators:
Detective details:
Forecast of Cause:
Check Point 1 : Check rotation of Fan
Check Point 2 : Check ambient temp. around motor
OK
OK
OK
Indoor unit Controller PCB Indoor unit fan motor
1. Fan rotation failure 2. Fan motor winding open 3. Motor protection by surrounding temperature rise
4. Control PCB failure 5. Indoor unit fan motor failure
Rotate the fan by hand when operation is off. (Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
Check excessively high temperature around the motor. (If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation.
When the condition that actual frequency of Indoor Fan is below 1/3 of target frequency is continued more than 56 seconds.
Check Point 4 : Replace Controller PCB
If Check Point 1- 3 do not improve the symptom, replace Controller PCB.
Check Point 3 : Check Indoor unit fan motor
Check Indoor unit fan motor. (PARTS INFORMATION 4)
>>If Indoor unit fan motor is abnormal, replace Indoor unit fan motor.
Trouble shooting 9 OUTDOOR UNIT Error Method:
A.F Voltage Error
02-11
Indicate or Display:
Refer to error code table.
Detective Actuators:
Detective details:
Forecast of Cause :
OKOK
OKOK
Outdoor unit Main PCB Active filter module
1. External cause 2. Connector connection failure 3. Main PCB failure 4. Active filter module failure
Check Point 2 : Check connection of Connector
Check if connector is removed.
Check erroneous connection. Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 4 : Replace Main PCB
If Check Point 1 - 3 do not improve the symptom, change Main PCB.
Check Point 1 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop : Check if there is a large load electric apparatus in the same circuit.
Momentary power failure : Check if there is a defective contact or leak current in the power supply circuit.
Noise : Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
OKOK
Check Point 3 : Check Active filter module
Check Active filter module. (PARTS INFORMATION 6)
>>If Active filter module is abnormal, replace it.
When inverter input DC voltage is higher than 425V or lower than 80V. When a momentary power cut off occurred on low voltage
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 3 : Check Outdoor Fan
OK
OK
Check Point 6 : Replace Main PCB
OKOK
Check Point 1 : Check connections of Outdoor Unit Electrical Components
Outdoor unit Main PCB Compressor
1. Defective connection of electric components 2. Outdoor Fan Operation failure
3. Outdoor Heat Exchanger clogged 4. Compressor failure 5. Transistor PCB failure
6. Main PCB failure
Check if connector is removed.
Check if the terminal connection is loose. Check erroneous connection.
Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Check Outdoor Fan, Heat Exchanger
Is there anything obstructing the air distribution circuit? Is there any clogging of Outdoor Heat Exchanger? Is the Fan rotating by hand when operation is off ?
>> If the Fan Motor is locked, replace it.
Check Outdoor Fan Motor. (Refer to Trouble shooting 19)
>> If the Fan Motor is failure, replace it.
Check Point 4 : Check Compressor
(PARTS INFORMATION 2)
Check Compressor.
If Check Point 1 5 do not improve the symptom, change Main PCB.
When more than normal operating current to IPM in Main PCB flows, the compressor stops. After the compressor restarts, if the same operation is repeated within 40sec, the compressor stops again. If and repeats 5 times, the compressor stops permanently.
02-12
Trouble shooting 10 OUTDOOR UNIT Error Method:
IPM Error
Indicate or Display:
Refer to error code table.
Check Point 5 : Check Transistor PCB
OK
OK
(PARTS INFORMATION 7)
Check
Transistor PCB.
Trouble shooting 11 OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators: Detective details:
Forecast of Cause :
OKOK
OKOK
17.826.3
20
40.062.679.1101130169Resistance value (k )
151050Temperature (°C )
12.3
30 5040 60
2.003.434.606.278.70Resistance value (k )
120100908070Temperature (°C )
Discharge Thermistor Error
Outdoor unit Main PCB Discharge pipe temperature thermistor
When Discharge pipe temperature thermistor open or short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2. Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of connector
Check if connector is removed. Check if connector is erroneous connection. Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check thermistor resistance value
Thermistor characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
02-13
Refer to error code table.
BLACK BLACK BLACK BLACK
BROWN
BROWN
BLACK
BLACK
Thermistor (Discharge pipe)
Thermistor (Heat exchanger)
Thermistor (Outdoor temp.)
Thermistor (Compressor temp.)
4 3 2 1
3 2 1
3 2 1
3 2 1
3 2 1
4 3 2 1
CN61
CN62
CN64
BROWN
BROWN
BLUE
BLUE
Thermistor (Discharge pipe)
Thermistor (Heat exchanger)
Thermistor (Outdoor temp.)
Thermistor (Compressor temp.)
3 2 1
3 2 1
3 2 1
3 2 1
CN62
BLACK
BLACK
3 2 1
3 2 1
CN65
BROWN
BROWN
3 2 1
3 2 1
CN63
CN64
AO*G24LFL
BLACK BLACK BLACK BLACK
BLACK
BLACK
BLACK
BLACK
Thermistor (Discharge pipe)
Thermistor (Heat exchanger)
Thermistor (Outdoor temp.)
Thermistor (Compressor temp.)
4 3 2 1
3 2 1
3 2 1
3 2 1
3 2 1
4 3 2 1
CN71
CN70
CN73
AO*G24LFCC AO*G30LFT
Trouble shooting 12 OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators: Detective details:
Forecast of Cause :
OKOK
OKOK
Compressor Thermistor Error
Outdoor unit Main PCB Compressor temperature thermistor
When Compressor temperature thermistor open or short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2. Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of connector
Check if connector is removed. Check if connector is erroneous connection. Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check thermistor resistance value
Thermistor characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
02-14
Refer to error code table.
17.826.3
20
40.062.679.1101130169Resistance value (k )
151050Temperature (°C )
12.3
30 5040 60
2.003.434.606.278.70Resistance value (k )
120100908070Temperature (°C )
BLACK BLACK BLACK BLACK
BROWN
BROWN
BLACK
BLACK
Thermistor (Discharge pipe)
Thermistor (Heat exchanger)
Thermistor (Outdoor temp.)
Thermistor (Compressor temp.)
4 3 2 1
3 2 1
3 2 1
3 2 1
3 2 1
4 3 2 1
CN61
CN62
CN64
BROWN
BROWN
BLUE
BLUE
Thermistor (Discharge pipe)
Thermistor (Heat exchanger)
Thermistor (Outdoor temp.)
Thermistor (Compressor temp.)
3 2 1
3 2 1
3 2 1
3 2 1
CN62
BLACK
BLACK
3 2 1
3 2 1
CN65
BROWN
BROWN
3 2 1
3 2 1
CN63
CN64
AO*G24LFL
BLACK BLACK BLACK BLACK
BLACK
BLACK
BLACK
BLACK
Thermistor (Discharge pipe)
Thermistor (Heat exchanger)
Thermistor (Outdoor temp.)
Thermistor (Compressor temp.)
4 3 2 1
3 2 1
3 2 1
3 2 1
3 2 1
4 3 2 1
CN71
CN70
CN73
AO*G24LFCC AO*G30LFT
Trouble shooting 13 OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators: Detective details:
Forecast of Cause :
OKOK
OKOK
3.844.77
15
5.987.569.6316.121.027.8Resistance value (k )
100-5-10Temperature (°C )
20
3025
Heat Ex. Liquid Outlet Thermistor Error
Outdoor unit Main PCB
Heat exchanger temperature thermistor
When Heat exchanger temperature thermistor open or short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2. Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of connector
Check if connector is removed. Check if connector is erroneous connection. Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check thermistor resistance value
Thermistor characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
02-15
Refer to error code table.
3.11
35
12.4
5
BLACK BLACK BLACK BLACK
BROWN
BROWN
BLACK
BLACK
Thermistor (Discharge pipe)
Thermistor (Heat exchanger)
Thermistor (Outdoor temp.)
Thermistor (Compressor temp.)
4 3 2 1
3 2 1
3 2 1
3 2 1
3 2 1
4 3 2 1
CN61
CN62
CN64
BROWN
BROWN
BLUE
BLUE
Thermistor (Discharge pipe)
Thermistor (Heat exchanger)
Thermistor (Outdoor temp.)
Thermistor (Compressor temp.)
3 2 1
3 2 1
3 2 1
3 2 1
CN62
BLACK
BLACK
3 2 1
3 2 1
CN65
BROWN
BROWN
3 2 1
3 2 1
CN63
CN64
AO*G24LFL
BLACK BLACK BLACK BLACK
BLACK
BLACK
BLACK
BLACK
Thermistor (Discharge pipe)
Thermistor (Heat exchanger)
Thermistor (Outdoor temp.)
Thermistor (Compressor temp.)
4 3 2 1
3 2 1
3 2 1
3 2 1
3 2 1
4 3 2 1
CN71
CN70
CN73
AO*G24LFCC AO*G30LFT
Trouble shooting 14 OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators: Detective details:
Forecast of Cause :
OKOK
OKOK
12.616.1
5
20.726.935.246.662.3115Resistance value (k )
0-5-10-20Temperature (°C )
10 2015
1.652.363.455.187.97Resistance value (k )
7060504030Temperature (°C )
Outdoor Thermistor Error
Outdoor unit Main PCB Outdoor temperature thermistor
When Outdoor temperature thermistor open or short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2. Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of connector
Check if connector is removed. Check if connector is erroneous connection. Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check thermistor resistance value
Thermistor characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
02-16
Refer to error code table.
BLACK BLACK BLACK BLACK
BROWN
BROWN
BLACK
BLACK
Thermistor (Discharge pipe)
Thermistor (Heat exchanger)
Thermistor (Outdoor temp.)
Thermistor (Compressor temp.)
4 3 2 1
3 2 1
3 2 1
3 2 1
3 2 1
4 3 2 1
CN61
CN62
CN64
BROWN
BROWN
BLUE
BLUE
Thermistor (Discharge pipe)
Thermistor (Heat exchanger)
Thermistor (Outdoor temp.)
Thermistor (Compressor temp.)
3 2 1
3 2 1
3 2 1
3 2 1
CN62
BLACK
BLACK
3 2 1
3 2 1
CN65
BROWN
BROWN
3 2 1
3 2 1
CN63
CN64
AO*G24LFL
BLACK BLACK BLACK BLACK
BLACK
BLACK
BLACK
BLACK
Thermistor (Discharge pipe)
Thermistor (Heat exchanger)
Thermistor (Outdoor temp.)
Thermistor (Compressor temp.)
4 3 2 1
3 2 1
3 2 1
3 2 1
3 2 1
4 3 2 1
CN71
CN70
CN73
AO*G24LFCC AO*G30LFT
Trouble shooting 15 OUTDOOR UNIT Error Method:
Current Sensor Error
02-17
Indicate or Display:
Refer to error code table.
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 4 : Replace Main PCB
YES
NO
OK
Outdoor unit Main PCB
Check Point 2 : Check connections of Outdoor Unit Electrical Components
Check if connector is removed.
Check if the terminal connection is loose.
Check erroneous connection. Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 1-2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
1. Defective connection of electric components 2. External cause 3. Main PCB failure
Instant drop : Check if there is a large load electric apparatus in the same circuit.
Momentary power failure : Check if there is a defective contact or leak current in the power supply circuit.
Noise : Check if there is any equipment causing harmonic wave near electric line.(Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
Check Point 1-1 : Reset Power Supply and operate
Does Error indication show again?
When Input Current Sensor has detected 0A, while Inverter Compressor is
operating at higher than 56rps,
after 1minute upon starting the Compressor. (Except during the defrost operation)
If Check Point 1, 2 do not improve the symptom, change Main PCB.
Trouble shooting 16 OUTDOOR UNIT Error Method:
Detective Actuators: Detective details:
Indicate or Display:
02-18
Refer to error code table.
High Pressure Switch Error
Forecast of Cause :
Check Point 1 : Check the high pressure switch connection state
OK
Outdoor unit Main PCB High Pressure Switch
1. High pressure switch connector disconnection, open
2. High pressure switch characteristics failure
3. Main PCB failure
When pressure switch open is detected in 10 seconds after the power is turned on.
Connector and wiring connection state check Cable open check
Check Point 2 : Check the high pressure switch characteristics
Switch characteristics check * For the characteristics of high pressure switch, refer to below.
OK
Check Point 3 : Replace Main PCB
Change Main PCB, and execute the check operation again.
Type of contact
Characteristics of pressure switch
C
H
Pressure
Pressure switch 1
4.2 0.1MPa
3.2 0.15MPa
Contact : Short Open Contact : Open Short
(24LFL/LFCC/30LFT : CN90 )
02-19
Trouble shooting 17 OUTDOOR UNIT Error Method:
Indicate or Display:
Over Current Error
Refer to error code table.
Detective Actuators:
Detective details:
Forecast of Cause :
OKOK
OKOK
Check Point 3: Replace Main PCB
Outdoor unit Main PCB Compressor Transistor PCB (IPM)
If Check Point 1 or 1,2 do not improve the symptom, change Main PCB.
Check Point 2: Check Transistor PCB (IPM)
>> If IPM is abnormal, replace Transistor PCB.
OKOK
Check Point 4: Replace Compressor
If Check Point 3 do not improve the symptom, change Compressor.
1. Outdoor unit fan operation defective, foreign matter on hear exchanger, excessive rise of ambient temperature
2. Main PCB
3. Inverter compressor failure (lock, winding short)
4. Transistor PCB (IPM) failure
"Protection stop by overcurrent generation after inverter compressor start processing completed'' generated consecutively 10 times. * The number of generations is reset if the start-up of the compressor succeeds.
No obstructions in air passages? Heat exchange fins clogged Outdoor unit fan motor check Ambient temperature not raised by the effect of other heat sources? Discharged air not sucked in?
Check Point 1 : Check the outdoor unit fan operation, heat exchanger, ambient temperature
Check IPM. (PARTS INFORMATION 7)
Trouble shooting 18 OUTDOOR UNIT Error Method:
Compressor Control Error
02-20
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 : Check connection of around the Compressor components
OKOK
Check Point 4: Replace Main PCB
Outdoor unit Main PCB Compressor Transistor PCB (IPM)
1. Defective connection of electric components 2. Main PCB failure 3. Compressor failure
4. Transistor PCB (IPM) failure
If Check Point 1,2 or 1 3 do not improve the symptom, change Main PCB.
Check if connector is removed. Check erroneous connection. Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
(Refer to PARTS INFORMATION 2)
For Compressor Terminal, Main PCB
While running the compressor, if the detected rotor location is out of phase with actual rotor location more than 90°, the compressor stops. After the compressor restarts, if the same operation is repeated within 40sec, the compressor stops again. If and repeats 5 times, the compressor stops permanently.
Check Point 1 : Check Noise from Compressor
Turn on Power and check operation noise.
If an abnormal noise show, replace Compressor.
OKOK
Check Point 5: Replace Compressor
If Check Point 4 do not improve the symptom, change Compressor.
OKOK
OKOK
Check Point 3: Check Transistor PCB (IPM)
>> If IPM is abnormal, replace Transistor PCB.
Check IPM. (PARTS INFORMATION 7)
Indicate or Display:
Refer to error code table.
02-21
Trouble shooting 19
OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause:
Check Point 3 : Check Outdoor unit fan motor
OK
OK
Outdoor Unit Fan Motor Error
Outdoor unit Main PCB Outdoor unit fan motor
1. Fan rotation failure 2. Motor protection by surrounding temperature rise 3. Main PCB failure
4. Outdoor unit fan motor failure
Check Point 1 : Check rotation of Fan
Rotate the fan by hand when operation is off. (Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
Check Outdoor unit fan motor. (PARTS INFORMATION 5) >>If Outdoor Fan Motor is abnormal, replace Outdoor fan motor and Main PCB.
Check Point 4 : Check Output Voltage of Main PCB
Check outdoor unit circuit diagram and the voltage. (Measure at Main PCB side connector)
If the voltage is not correct, replace Main PCB.
When outdoor fan rotation speed is less than 100rpm in 20 seconds after fan motor starts, fan motor stops. After fan motor restarts, if the same operation within 60sec is repeated 3 times in a row, compressor and fan motor stops. If and repeats 5 times in a row, compressor and fan motor stops permanently.
Check Point 2 : Check ambient temp. around motor
OK
Check excessively high temperature around the motor. (If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation.
Indicate or Display:
Refer to error code table.
Read wire DC voltage Red - Black
240 ~ 400V (24L) 300 ~ 400V (30L)
White - Black
15 1.5V
CN800 (For 24LFL/ LFCC) CN801 (For 30LFT)
1 2 3 4 5 6 7
BLACK WHITE YELLOW BROWN
RED
FM
FAN MOTOR
AO*G24LFL / LFCC / 30LFT
Detective Actuators:
Detective details:
Forecast of Cause :
OKOK
OKOK
1. Connector connection failure 2. Thermistor failure 3. Coil failure 4. 4-way valve failure
5. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed. Check erroneous connection. Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 3 : Check the solenoid coil and 4-way valve
02-22
[ Solenoid coil ] Remove CN500 from PCB and check the resistance value of coil. Resistance value is about 1.4k
>> If it is Open or abnormal resistance value, replace Solenoid Coil.
[ 4-way valve ] Check each piping temperature, and the location of the valve by the temperature difference. >> If the value location is not proper, replace 4-way valve.
OKOK
Check Point 4 : Replace Main PCB
If Check Point 1- 3 do not improve the symptom, replace Main PCB.
Check Point 2 : Check thermistor of Indoor unit
Isn’t it fallen off the holder? Is there a cable pinched?
>> Check characteristics of thermistor, (Refer to Trouble shooting 6,7), If defective, replace the thermistor.
Indoor unit Controller PCB Heat exchanger temperature thermistor Room temperature thermistor 4-way valve
When the indoor heat exchanger temperature is compared with the room temperature, and either following condition is detected continuously two times, the compressor stops. Cooling or Dry operation [Indoor heat exchanger temp.] - [Room temp.] > 20degC Heating operation [indoor heat exchanger temp.] - [Room temp.] < -20degC If the same operation is repeated 5 times, the compressor stops permanently.
Trouble shooting 20 OUTDOOR UNIT Error Method:
4-Way Valve Error
Indicate or Display:
Refer to error code table.
<Cooling operation>
OK
OK
OK
OK
OK
OK
<Heating operation>
Discharge temperature thermistor Outdoor unit Main PCB
"Protection stop by "discharge temperature 110degC during compressor operation"" generated 2 times within 24 hours.
Check Point 1 : Check if 3-way valve(gas side) is open.
Discharger thermistor characteristics check (Check by disconnecting thermistor from PCB.)
* For the characteristics of the thermistor, refer to the "Trouble shooting 11".
Check Point 4 : Check the discharge thermistor
EEV open? Strainer clogging check
(Refer to PARTS INFORMATION 3)
Check Point 3 : Check the outdoor unit fan,heat exchanger
Check for foreign object at heat exchanger Check if fan can be rotated by hand. Motor check (PARTS INFORMATION 5)
Check Point 2 : Check the EEV, strainer
Check Point 5 : Check the refrigerant amount
Leak check
EEV open? Strainer clogging check
(Refer to PARTS INFORMATION 3)
Check Point 2 : Check the EEV, strainer
If the 3-way valve(gas side) was closed, open the 3-way valve(gas side) and check operation.
02-23
Check Point 1 : Check if 3-way valve(liquid side) is open.
If the 3-way valve(liquid side) was closed, open the 3-way valve(liquid side) and check operation.
OK
1. 3-way valve not opened 2. EEV defective, strainer clogged
3. Outdoor unit operation failure, foreign matter on heat exchanger
4. Discharge temperature thermistor failure 5. Insufficient refrigerant
6. Main PCB failure
Detective Actuators:
Detective details:
Forecast of Cause :
Trouble shooting 21 OUTDOOR UNIT Error Method:
Discharge Temp. Error
Indicate or Display:
Refer to error code table.
Check Point 6 : Replace Main PCB
If Check Point 1- 5 do not improve the symptom, replace Main PCB.
<Cooling operation>
OK
OK
OK
OK
OK
OK
<Heating operation>
Compressor temperature thermistor Outdoor unit Main PCB
"Protection stop by "compressor temperature 110degC(24L), 108degC(30L) during compressor operation"" generated 2 times within 24 hours.
Check Point 1 : Check if 3-way valve(gas side) is open.
Discharger thermistor characteristics check (Check by disconnecting thermistor from PCB.)
* For the characteristics of the thermistor, refer to the "Trouble shooting 12".
Check Point 4 : Check the discharge thermistor
EEV open? Strainer clogging check
(Refer to PARTS INFORMATION 3)
Check Point 3 : Check the outdoor unit fan,heat exchanger
Check for foreign object at heat exchanger Check if fan can be rotated by hand. Motor check (PARTS INFORMATION 5)
Check Point 2 : Check the EEV, strainer
Check Point 5 : Check the refrigerant amount
Leak check
EEV open? Strainer clogging check
(Refer to PARTS INFORMATION 3)
Check Point 2 : Check the EEV, strainer
If the 3-way valve(gas side) was closed, open the 3-way valve(gas side) and check operation.
02-24
Check Point 1 : Check if 3-way valve(liquid side) is open.
If the 3-way valve(liquid side) was closed, open the 3-way valve(liquid side) and check operation.
OK
Detective Actuators:
Detective details:
Forecast of Cause :
Trouble shooting 22 OUTDOOR UNIT Error Method:
Compressor Temp. Error
Indicate or Display:
Refer to error code table.
1. 3-way valve not opened 2. EEV defective, strainer clogged
3. Outdoor unit operation failure, foreign matter on heat exchanger
4. Compressor temperature thermistor
failure 5. Insufficient refrigerant
6. Main PCB failure
Check Point 6 : Replace Main PCB
If Check Point 1- 5 do not improve the symptom, replace Main PCB.
<Cooling operation>
<Heating operation>
Suction pressure sensor Outdoor unit Main PCB
"Protection stop by suction pressure 0.02MPaG continued for 5 minutes repeats 5 times within 2 hours.
Check Point 1 : Check if 3-way valve(gas side) is open.
Suction pressure sensor characteristics check * For the characteristics of the suction pressure sensor.
(Refer to PARTS INFORMATION 8)
Check Point 5 : Check the suction pressure sensor
Check Point 6 : Check the refrigerant amount
Leak check
If the 3-way valve(gas side) was closed, open the 3-way valve(gas side) and check operation.
02-25
Check Point 1 : Check if 3-way valve(liquid side) is open.
If the 3-way valve(liquid side) was closed, open the 3-way valve(liquid side) and check operation.
OK
OK
OK
OK
OK
OK
OK
Detective Actuators:
Detective details:
Forecast of Cause :
Trouble shooting 23 OUTDOOR UNIT Error Method:
Low Pressure Error
Indicate or Display:
Refer to error code table.
EEV operation check Strainer not clogged?
(Refer to PARTS INFORMATION 3)
Check Point 4 : Check the EEV, strainer clogging
EEV operation check Strainer not clogged?
Refer to PARTS INFORMATION 3
Check Point 2 : Check the EEV, strainer clogging
Check Point 2 : Check the outdoor unit ambient temperature
Outdoor ambient temperature lower than operating range?
Check Point 3 : Check the outdoor unit fan operation, heat exchanger
For AOTG34LFT
1. 3-way valve not opened 2. Outdoor unit ambient temperature too low
3. Outdoor unit fan operation defective, foreign matter at heat exchanger
4. EEV defective, strainer clogged 5. Solenoid valve defective
6. Low pressure sensor characteristics defective 7. Insufficient refrigerant
8. Main PCB failure
No foreign object in air passage? Heat exchange fins clogged Fan rotates? Outdoor unit fan motor check
Check Point 7 : Replace Main PCB
If Check Point 1- 6 do not improve the symptom, replace Main PCB.
Trouble shooting 24
Forecast of Cause:
OKOK
Indoor Unit - No Power
1. Power Supply failure 2. External cause
3. Electrical Components defective
Check Point 1 : Check Installation Condition
Isn’t the breaker down?
Check loose or removed connection cable.
>>If abnormal condition is found, correct it by referring to Installation Manual or Data & Technical Manual.
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
02-26
2-3 TROUBLE SHOOTING WITH NO ERROR CODE
Check Point 3 : Check Electrical Components
YESYES
NO
Check the voltage of power supply.
>> Check if AC216 - 264V appears at Outdoor Unit Terminal L - N.
Check Varistor in Filter PCB.
>> If Varistor is defective, there is a possibility of an abnormal power supply. Check the correct power supply and replace Varistor. Upon checking the normal power supply, replace Varistor.
OK
Check Fuse in Filter PCB.
>> If Fuse is open, check if the wiring between Terminal and Filter PCB is loose, and replace Fuse.
Trouble shooting 25
Forecast of Cause:
Check Point 3 : Check Electrical Components
OKOK
OKOK
YESYES
YESYES
OK
NO
Check Point 1 : Check Installation Condition
Outdoor Unit - No Power
1. Power Supply failure 2. External cause
3. Electrical Components defective
Isn’t the breaker down?
Check loose or removed connection cable.
>>If abnormal condition is found, correct it by referring to Installation Manual or Data & Technical Manual.
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit. Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit. Noise ----- Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
Check the voltage of power supply.
>> Check if AC216 - 264V appears at Outdoor Unit Terminal L - N.
Check Fuse in Main PCB.
>> If Fuse is open, check if the wiring between Terminal and Main PCB is loose, and replace Fuse.
Check Active Filter Module and IPM. (PARTS INFORMATION 6 and 7)
>> If Active Filter Module or IPM is abnormal, replace it.
If the symptom does not change by above Check 3, replace Main PCB.
02-27
Trouble shooting 26
Forecast of Cause:
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Check Point 1 : Check indoor and outdoor installation condition
Check Point 3 : Check Wired Remote Controller and Controller PCB
OK
OK
OKOK
No Operation (Power is ON)
1. Setting/ Connection failure 2. External cause
3. Electrical Component defective
Indoor Unit - Check incorrect wiring between Indoor Unit - Remote Control. Or, check if there is an open cable connection. Are these Indoor Unit, Outdoor Unit, and Remote Control suitable model numbers to connect?
>> If there is some abnormal condition, correct it by referring to Installation manual and
Data & Technical Manual.
Turn off Power and check/ correct followings.
Is there loose or removed communication line of Indoor Unit and Outdoor Unit?
Instant drop ----- Check if there is a large load electric apparatus in the same circuit. Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit. Noise ----- Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave) Check the complete insulation of grounding.
>> If it is DC12V, Remote Control is failure. (Controller PCB is normal) >> Replace Remote Control
>> If it is DC 0V, Controller PCB is failure. (Check Remote Control once again) >> Replace Controller PCB
>> If the symptom does not change by above Check 1, 2, 3, replace Main PCB of Outdoor unit.
02-28
Check Voltage at CN6 (terminal 1-3) of Controller PCB. (Power supply to Remote Control)
Attention
Trouble shooting 27
Forecast of Cause:
Check Point 2 : Check Outdoor Unit Operation
Check Point 1 : Check Indoor Unit
Check Point 3 : Check Site Condition
Check Point 5 : Check Refrigeration cycle
Check Point 4 : Check Indoor/ Outdoor Installation Condition
Pipe (In) Pipe (Out)
Pipe (In) Pipe (Out)
OKOK
OKOK
OKOK
OKOK
MPa MPa
No Cooling / No Heating
1. Indoor Unit error 2. Outdoor Unit error
3. Effect by Surrounding environment
4. Connection Pipe / Connection Wire failure 5. Refrigeration cycle failure
Does Indoor unit FAN run on HIGH FAN?
Is Air Filter dirty? Is Heat Exchanger clogged?
Check if Energy save function is operated.
Check if Outdoor Unit is operating Check any objects that obstruct the air flow route. Check clogged Heat Exchanger.
Is the Valve open?
Is capacity of Indoor unit fitted to Room size? Any windows open? Or direct sunlight ?
Check connection pipe (specified pipe length & Pipe diameter?)
Check any loose or removed communication line.
>> If there is an abnormal condition, correct it by referring to Installation Manual or Data & Technical Manual.
Check if Strainer is clogged (Refer to the figure at right).
Measure Gas Pressure and if there is a leakage, correct it.
>> When recharging the refrigerant, make sure to perform vacuuming, and recharge the specified amount.
Check EEV (PARTS INFORMATION 3) Check Compressor (PARTS INFORMATION 1,2)
Strainer normally does not have temperature difference between inlet and outlet as shown in , but if there is a difference like shown in , there is a possibility of inside clogged. In this case, replace Strainer.
02-29
Trouble shooting 28
Forecast of Cause :
Trouble shooting 29
Forecast of Cause:
OK
OK
OK
OK
OKOK
OKOK
OKOK
MPa MPa
Abnormal Noise
1. Abnormal installation (Indoor/ Outdoor)
2. Fan failure (Indoor/ Outdoor)
3. Compressor failure (Outdoor)
Diagnosis method when Abnormal Noise is occurred
Abnormal noise is coming from Indoor Unit. (Check and correct followings)
Abnormal noise is coming from Outdoor Unit. (Check and correct followings)
Is Fan broken or deformed? Is the screw of Fan loose? Is there any object which obstruct the Fan rotation?
Is Main unit installed in stable condition? Is the installation of air suction grille and front panel normal?
Is Fan broken or deformed? Is the screw of Fan loose?
Is there any object which obstruct the Fan rotation?
Is Main Unit installed in stable condition? Is Fan Guard installed normally?
Check if vibration noise by loose bolt or contact noise of piping is happening.
Is Compressor locked?
>> Check Compressor (PARTS INFORMATION 1,2)
Water Leaking
1. Erroneous installation 2. Drain hose failure
Diagnosis method when water is spitting out.
Is the filter clogged?
Check Gas Pressure and correct it if there was a gas leak.
Diagnosis method when water leak occurs
Is Drain Hose connection loose?
Is there a trap in Drain Hose?
Is Drain Hose clogged?
Is Main Unit installed in stable condition?
Is Main Unit broken or deformed at the time of
transportation or maintenance?
Is Fan rotating?
02-30
SERVICE PARTS INFORMATION 1
MPa MPa
Compressor
Diagnosis method of Compressor ( If Outdoor Unit LED displays Error, refer to Trouble shooting )
Does not start up
Is there open or loose connection cable?
Check Main PCB, connection of
Compressor, and winding resistance.
(Refer to the next page).
Check Main PCB, connection of Compressor,and winding resistance. (Refer to the next page).
>> If there is no failure, the defect of Compressor is considered (Locked compressor due to clogged dirt or less oil)
Replace Compressor
Replace Compressor
Replace Compressor
Stops soon after starting up
Is there open or loose connection cable?
Is Gas Pipe Valve open? (Low Pressure is too low)
Check if Refrigerant is leaking. (Recharge Refrigerant)
Check if Strainer is clogged. (PARTS INFORMATION 3)
>> If there is no failure, the defect of Compressor can be considered. (Compression part broken or valve defective.)
Abnormal noise
Defective Compressor can be considered. (due to inside dirt clogging or broken component)
Check if vibration noise by loose bolt or contact noise of piping is happening.
02-31
2-4 SERVICE PARTS INFORMATION
SERVICE PARTS INFORMATION 2
Inverter Compressor
02-32
Check Point 1 : Check connection
Check Point 2 : Check winding resistance
Check Point 3 : Replace Inverter PCB
U(R)
V(S)
W(C)(T)
Check terminal connection of Compressor (Loose or incorrect wiring)
Check winding resistance of each terminal
If the resistance value is 0 or infinite, replace Compressor.
If Check Point 1, 2 do not improve the symptom, replace Main PCB.
U(R)
(RED)
V(S)
(WHITE)
W(C)(T)
(BLACK)
Transistor PCB (IPM)
Check connection of Transisitor PCB(IPM). (Loose or incorrect wiring)
TM303TM304
TM305
RED
WHITE
BLACK
Compressor
Transistor PCB (IPM)
Resistance Value :
0.921 at 25°C
AO*G24LFL / LFCC
Resistance Value :
0.642 at 20°C
AO*G30LFT
SERVICE PARTS INFORMATION 3
Check Point 2 : Check Coil of EEV
Yellow - Red Orange - Red Blue - Red
White - Red
Read wire
46 4
Resistance value
Check Point 1 : Check Connections
Check Point 5 : Check Opening and Closing Operation of Valve
Check Point 3 : Check Voltage from Main PCB.
Check Point 4 : Check Noise at start up
Pipe (In)
Pipe (Out)
Hi TEMP.
Pipe (In)
Hi TEMP.
Normal TEMP.
CLOSE Example : Hot Gas
OPEN Example : Hot Gas
Pipe (Out)
Hi TEMP.
Pipe (In) Pipe (Out)
Pipe (In) Pipe (Out)
Check Point 6 : Check Strainer
DC
at 20°C
Outdoor unit Electronic Expansion Valve ( EEV )
Check connection of connector ( Loose connector or open cable )
Remove connector, check each winding resistance of Coil.
If Resistance value is abnormal, replace EEV.
Remove Connector and check Voltage (DC12V)
If it does not appear, replace Main PCB.
Turn on Power and check operation noise.
If an abnormal noise does not show, replace Main PCB.
When Valve is closed, it has a temp. difference between Inlet and Outlet.
If it is open, it has no temp. difference between Inlet and Outlet.
Strainer normally does not have temperature difference between inlet and outlet as shown in ,
but if there is a difference as shown in , there is a possibility of inside clogged. In this case, replace Strainer.
02-33
AO*G24LFL / LFCC / 30LFT
CN700
EXPANSION VALVE COIL
EV
RED BLUE ORANGE YELLOW WHITE
1 2 3 4 5
SERVICE PARTS INFORMATION 5
Check Point 1 : Check rotation of Fan
Outdoor unit fan motor
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
Check Point 2 : Check resistance of Outdoor Fan Motor
Refer to below. Circuit-test "Vm" and "GND" terminal.
(Vm: DC voltage, GND: Earth terminal)
>>If they are short-circuited (below 300 k ), replace Outdoor fan motor and Main PCB.
Pin number (wire color)
Terminal function (symbol)
1 (Red) 2 3 4 (Black) 5 (White) 6 (Yellow) 7 (Brown)
DC voltage (Vm) No function No function Earth terminal (GND) Control voltage (Vcc) Speed command (Vsp) Feed back (FG)
SERVICE PARTS INFORMATION 4
Check Point 1 : Check rotation of Fan
Indoor unit fan motor
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
Check Point 2 : Check resistance of Indoor Fan Motor
Refer to below. Circuit-test "Vm" and "GND" terminal.
(Vm: DC voltage, GND: Earth terminal)
>>If they are short-circuited (below 300 k ), replace Indoor fan motor and Controller PCB.
Pin number (wire color)
Terminal function (symbol)
1 (Blue) 2 (Yellow) 3 (White) 4 (Black) 5 6 (Red)
Feed back (FG) Speed command (Vsp) Control voltage (Vcc) Earth terminal (GND) No function DC voltage (Vm)
02-34
SERVICE PARTS INFORMATION 6
Active filter module
02-35
Check Point 1 : Check Open or Short-circuit and Diode (D1)
Check Point 2 : Check the Output DC voltage (between P and N)
L2L1
P
N
+IN
Check the Output DC voltage (between P and N) of compressor stopping and operating.
If it is abnormal,replace ACTIVE FILTER MODULE
Remove connector, check the open or short-circuit and the diode in the module
>> If the output voltage of compressor operating is less than the output voltage of compressor stopping, Active Filter Module is detective. >> Replace Active Filter Module
Terminal
Resistance value
L2
L1
L1,L2
P
P
Control Box
N
N
(+IN)
(+IN)
( IN)
( IN)
Tester(+) Tester(-)
Check the open or short-circuit
L2
P
P
N
L2
L2
Check the diode
0
360k
720k
1.69M /
20%
+
-
360k
20%
+
-
20%
+
-
(Ref. value 1)
1.88M
(Ref. value 2)
1.40M /
(Ref. value 1)
2.28M
(Ref. value 2)
Terminal
Resistance value
Tester(+) Tester(-)
1.32M /
(Ref. value 1)
1.50M
(Ref. value 2)
1.40M /
(Ref. value 1)
1.51M
(Ref. value 2)
Ref. value 1 Specifications for Multimeter Manufacturer : HIOKI Model name : 3804 Power source : DC9V.
Ref. value 2 Specifications for Multimeter Manufacturer : YOKOGAWA Model name : 7534 Power source : DC3V.
-IN
SERVICE PARTS INFORMATION 7
IPM (
Mounted on Transistor PCB)
02-36
Check Point 1
Check Point 2
Terminal
Resistance value
Tester(+) Tester(-)
 Disconnect the connection wires between the Transistor PCB - Capacitor PCB and Transistor PCB - Inverter Compressor.
 Set the tester to the "Resistance" mode, and measure the resistance between the following terminals.
Set the tester to the "Diode" mode, and measure the voltage value between the following terminals.
 Judge the result of as follows:
Judge the result of as follows:
TM301 (P) - TM305(U) / TM304(V) / TM303(W) TM302 (N) - TM305(U) / TM304(V) / TM303(W)
P P P U V W N N N U V W
U V W P P P U V W N N N
Over 2k (Including )
Over 2k (Including )
Over 20k (Including )
Terminal
Tester display
Tester(+) Tester(-)
P P P U V W N N N U V W
U V W P P P U V W N N N
0.3V 0.7V
SERVICE PARTS INFORMATION 8
Suction Pressure Sensor
02-37
Check Point 1 : Check Voltage from Main PCB
With the connector connected to the PCB, measure the voltage between CN91(terminal 3-4) of the Main PCB.
DC
DC
Characteristics of pressure sensor
4.5
5.0
0.5 0
Output [DCV]
Pressure [MPa]
1 2 3 4
1 2 3 4
WHITE
PRESSURE SENSOR
BLACK
RED
PS
CN91
2.5
2.5
3 . APPENDING DATA
R410A
WALL MOUNTED type
INVERTER
03-01
3-1. FUNCTION SETTING
Follow the instructions in the Local Setup Procedure, which is supplied with the remote control, in accordance with the installed condition. After the power is turned on, perform the Function Setting on the remote control.
The settings may be selected between the following two: Function Number or Setting Value. Settings will not be changed if invalid numbers or setting values are selected.
3-1-1 INDOOR UNIT
( Factory setting)
Setting Description
Function Number Setting Value Standard (400 hours) Long interval (1000 hours) Short interval ( 200 hours) No indication
11
00 01 02 03
1-1. Setting the Filter Sign
The indoor unit has a sign to inform the user that it is time to clean the filter. Select the time setting for the filter sign display interval in the table below according to the amount of dust or debris in the room. If you do not wish the filter sign to be displayed, select the setting value for "No indication".
( Factory setting)
Setting Description
Function Number Setting Value Standard Slightly lower control Lower control Warmer control
30
00 01 02 03
1-2. Setting the Cooling Room Temperature Correction
Depending on the installed environment, the room temperature sensor may require a correction. The settings may be selected as shown in the table below.
( Factory setting)
Setting Description
Function Number Setting Value Standard Lower control Slightly warmer control Warmer control
31
00 01 02 03
1-3. Setting the Heating Room Temperature Correction
Depending on the installed environment, the room temperature sensor may require a correction. The settings may be selected as shown in the table below.
03-02
( Factory setting)
Setting Description
Function Number Setting Value
Yes No
40
00 01
( Factory setting)
Setting Description
Function Number Setting Value
No Yes
42
00 01
1-4. Setting the Auto Restart
Enable or disable automatic system restart after a power outage.
( Factory setting)
Setting Description
Function Number Setting Value
No Yes
49
00 01
1-8. Indoor unit fan control for energy saving
Enable or disable indoor unit fan control when the outdoor unit is stopped.
1-5. Setting the Indoor room temperature sensor switching function (Only for Wired remote controller)
The following settings are needed when use the control by Wired remote controller temperature sensor.
( Factory setting)
Setting Description
Function Number Setting Value
A B C D
44
00 01 02 03
1-6. Setting the Remote controller signal code
Change the indoor unit Signal Code, depending on the remote controllers.
( Factory setting)
Setting Description
Function Number Setting Value
Operation/Stop mode (Setting forbidden) Forced stop mode
46
00 01 02
1-7. Setting the External input control
"Operation/Stop" mode or "Forced stop" mode can be elected.
* If setting value is "00" : Room temperature is controlled by the indoor unit temperature sensor. * If setting value is "01" : Room temperature is controlled by either indoor unit temperature sensor or remote controller unit sensor.
* If setting value is "00": When the outdoor unit is stopped, the indoor unit fan operates following the setting on the remote controller continuously. * If setting value is "01": When the outdoor unit stopped, the indoor unit fan operates at very low speed intermittently.
*AS*A24LFCA does not have this function. Factry setting: No
10°C HEAT
10°C HEAT
10°C HEAT
03-03
Settings will not be changed if invalid numbers or setting values are selected.
After the power is turned on, perform the "FUNCTION SETTING" according to the installation conditions using the remote controller.
This procedure changes to the function settings used to control the indoor unit according to the installation conditions. Incorrect settings can cause the indoor unit malfunction.
Entering the Function Setting Mode
While pressing the FAN button and SET TEMP.( ) simultaneously, press the RESET button to enter the function setting mode.
3-1-2 Procedures to change the Function Setting for wireless RC
(2) Press the SET TEMP. ( ) ( ) buttons to select the Function Number. (Press the MODE button to switch between the left and right digits.)
(3) Press the FAN button to proceed to Setting Value. (Press the FAN button again to return to the Function Number selection.)
Selecting the Function Number and Setting Value
(6) Press the START/STOP button. It makes a signal to indoor unit. (Indoor unit run the setting.)
(7) Press the RESET button to cancel the function setting mode. (8) After completing the FUNCTION SETTING, be sure to turn of the
power and turn it on again.
CAUTION
After turning off the power, wait 10 seconds or more before turning on it again. The FUNCTION SETTING doesn't become effective if it doesn't do so.
(4) Press the SET TEMP. ( ) ( ) buttons to select the Setting Value. (Press the MODE button to switch between the left and right digits.)
Function Number
Setting Value
(1) Press the MODE button, and proceed to Fanction Number and Setting Value. (There is no necessity for setting remote control signal code. Because signal code is setting by Fanction Number and Setting Value.)
(5) Press the TIMER MODE button. It makes a signal to indoor unit. (Indoor unit recognize the setting.)
10°C HEAT
1 0 °
C H
E A T
03-04
(1) Press the MODE button for more then 5 seconds.
(3) Press the MODE button. (Return to normal display)
Custom code setting for remote controller
(2) Press the SET TEMP. ( ) ( ) buttons to change the signal code between . Match the code on the display to the air conditioner signal code. (initially set to )
If you change the setting of Fanction Number and Setting Value after setting custom code in remote controller, please set custom code in remote controller again. The remote control unit resets to signal code A when the batteries in the remote control unit are replaced. If you use a signal code other than signal code A, reset the signal code after replacing the batteries. If you do not know the air conditioner signal code setting, try each of the signal codes ( ) until you find the code which operates the air conditioner.
CAUTION
Outdoor Unit Low Pressure Value and Outdoor Total Electric Current Curve (Cooling)
Model Name : AS*G24LFCA / LFCC
[Condition] Ambient
temperature
Indoor / Outdoor - Same temperature
Refrigerant
amount
Standard amount
Piping
length
7.5m * (Height difference 1m)˴AS*G24LFCC: 5m
Power
voltage
50Hz - 240V
Operation
condition
TEST mode (Cooling), Hi Fan, Horizontal direction, Front air flow
Measuring
m
ethod
Caution
Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Cooling mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor Low Pressure Curve
AS*G24LFCA
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
AS*G24LFCA
Measure the low pressure with the pressure meter at the service valve. Measure the outdoor
unit overall current with the current clamp meter at Power Cable.
03-05
0.5
0.6
0.7
0.8
0.9
1.0
1.1
16 18 20 22 24 26 28 30 32
Low-pressure of outdoor unit [MPa]
[50Hz-240V]
RH70% RH60% RH50%
In/Outdoor ambient temperature [ C]
7.0
7.5
8.0
8.5
9.0
9.5
10.0
10.5
11.0
16 18 20 22 24 26 28 30 32
In/Outdoor ambient temperature [ C]
Outdoor total electric current [A]
RH70% RH60% RH50%
[50Hz-240V]
3-2. Outdoor unit Pressure Value and Total Electric Current Curve
AS*G24LFCC
0.6
0.7
0.8
0.9
1.0
1.1
1.2
16 18 20 22 24 26 28 30 32
Low-pressure of outdoor unit [MPa]
[50Hz-240V]
RH70% RH60% RH50%
In/Outdoor ambient temperature [ C]
AS*G24LFCC
7.0
7.5
8.0
8.5
9.0
9.5
10.0
10.5
11.0
16 18 20 22 24 26 28 30 32
In/Outdoor ambient temperature [ C]
Outdoor total electric current [A]
RH70% RH60% RH50%
[50Hz-240V]
Outdoor Unit High Pressure Value and Outdoor Total Electric Current Curve (Heating)
Model Name : AS*G24LFCA / LFCC
[Condition] Ambient
temperatur
e
Indoor 15, 20, 23 C, Outdoor 2, 7, 12 C
Refrigerant
amount
Standard amount
Piping
7.5m * (Height difference 1m)˴AS*G24LFCC: 5m
Power
voltage
50Hz - 240V
Operation
con
diti
on
TEST mode (Heating), Hi Fan, One step up from lower direction, Front air flow
Measuring
method
Caution
Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Heating mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor High Pressure Curve
AS*G24LFCA
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
outdoor unit overall current with the current clamp meter at Power Cable.
length
03-06
2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
3.0
3.1
02468101214
High-pressure of outdoor unit [MPa]
[50Hz-240V]
Outdoor ambient temperature [ C]
8.0
8.5
9.0
9.5
10.0
10.5
11.0
11.5
12.0
[50Hz-240V]
23 C 20 C 15 C
Indoor ambient temperature[ C]
Outdoor ambient temperature [ C]
Outdoor total electric current [A]
02468101214
13.0
12.5
AS*G24LFCA
23 C 20 C 15 C
Indoor ambient temperature[ C]
AS*G24LFCC
2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
3.0
3.1
02468101214
High-pressure of outdoor unit [MPa]
[50Hz-240V]
Outdoor ambient temperature [ C]
7.0
7.5
8.0
8.5
9.0
9.5
10.0
10.5
11.0
[50Hz-240V]
23 C 20 C 15 C
Indoor ambient temperature[ C]
Outdoor ambient temperature [ C]
Outdoor total electric current [A]
02468101214
12.0
11.5
AS*G24LFCC
23 C 20 C 15 C
Indoor ambient temperature[ C]
Outdoor Unit Low Pressure Value and Outdoor Total Electric Current Curve (Cooling)
Model Name : AS*G30LFCA
[Condition] Ambient
temperature
Indoor / Outdoor - Same temperature
Refrigerant
amount
Standard amount
Piping
length
7.5m (Height difference 1m)
Power
voltage
50Hz - 240V
Operation
condition
TEST mode (Cooling), Hi Fan, Horizontal direction, Front air flow
Measuring
m
ethod
Caution
Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Cooling mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor Low Pressure Curve
AS*G30LFCA
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
AS*G30LFCA
Measure the low pressure with the pressure meter at the service valve. Measure the outdoor unit overall current with the current clamp meter at Power Cable.
03-07
0.7
0.8
0.9
1.0
1.1
1.2
1.3
16 18 20 22 24 26 28 30 32
Low-pressure of outdoor unit [MPa]
[50Hz-240V]
RH70% RH60% RH50%
In/Outdoor ambient temperature [ C]
7.0
7.5
8.0
8.5
9.0
9.5
10.0
10.5
11.0
16 18 20 22 24 26 28 30 32
In/Outdoor ambient temperature [ C]
Outdoor total electric current [A]
RH70% RH60% RH50%
[50Hz-240V]
Outdoor Unit High Pressure Value and Outdoor Total Electric Current Curve (Heating)
Model Name : AS*G30LFCA
[Condition] Ambient
temperatur
e
Indoor 15, 20, 23 C, Outdoor 2, 7, 12 C
Refrigerant
amount
Standard amount
Piping 7.5m (Height difference 1m)
Power
voltage
50Hz - 240V
Operation
con
diti
on
TEST mode (Heating), Hi Fan, One step up from lower direction, Front air flow
Measuring
method
Caution
Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Heating mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor High Pressure Curve
AS*G30LFCA
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
outdoor unit overall current with the current clamp meter at Power Cable.
length
03-08
2.4
2.5
2.6
2.7
2.8
2.9
3.0
3.1
3.2
3.3
3.4
02468101214
High-pressure of outdoor unit [MPa]
[50Hz-240V]
Outdoor ambient temperature [ C]
9.0
9.5
10.0
10.5
11.0
11.5
12.0
12.5
13.0
[50Hz-240V]
23 C 20 C 15 C
Indoor ambient temperature[ C]
Outdoor ambient temperature [ C]
Outdoor total electric current [A]
02468101214
14.0
13.5
AS*G30LFCA
23 C 20 C 15 C
Indoor ambient temperature[ C]
Characteristics of room temperature thermistor
0.00
5.00
10.00
15.00
20.00
25.00
30.00
35.00
40.00
(0.00) (10.00) (20.00) (30.00) (40.00) (50.00) (60.00)
Resistance(k )
Temperature F( C)
32
50
68 86
104 122
140
0.00
20.00
40.00
60.00
80.00
100.00
120.00
140.00
160.00
180.00
(0.00) (20.00) (40.00) (60.00) (80.00)
Resistance(k )
32
68
104
140
176
Temperature F( C)
Characteristics of heat exchanger thermistor (Indoor)
Characteristics of discharge thermistor
03-09
32.0
41.0
50.0
59.0
68.0
77.0
86.0
95.0
104.0
113.0
122.0
131.0
140.0
149.0
158.0
167.0
176.0
185.0
194.0
203.0
212.0
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
60.0
65.0
70.0
75.0
80.0
85.0
90.0
95.0
100.0
33.62
25.93
20.18
15.84
12.54
10.00
8.04
6.51
5.30
4.35
3.59
2.98
2.47
2.09
1.76
1.49
1.27
1.09
0.93
0.81
0.70
1.15
1.39
1.66
1.94
2.22
2.50
2.77
3.03
3.27
3.48
3.68
3.85
4.00
4.14
4.25
4.35
4.44
4.51
4.57
4.63
4.67
Room temperature thermistor
Voltage(V)Resistance(K )Tempe F Tempe C
32.0
41.0
50.0
59.0
68.0
77.0
86.0
95.0
104.0
113.0
122.0
131.0
140.0
149.0
158.0
167.0
176.0
185.0
194.0
203.0
212.0
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
60.0
65.0
70.0
75.0
80.0
85.0
90.0
95.0
100.0
176.03
134.23
103.34
80.28
62.91
49.70
39.57
31.74
25.64
20.85
17.06
14.10
11.64
9.69
8.12
6.83
5.78
4.91
4.19
3.59
3.09
1.10
1.36
1.63
1.92
2.21
2.51
2.79
3.06
3.30
3.53
3.73
3.90
4.55
4.19
4.30
4.40
4.48
4.55
4.61
4.66
4.71
Indoor heat exchanger thermistor
Voltage(V)Resistance(K )Tempe F Tempe C
-22.0
-13.0
-4.0
5.0
14.0
23.0
32.0
41.0
50.0
59.0
68.0
77.0
86.0
95.0
104.0
113.0
122.0
131.0
140.0
149.0
158.0
167.0
176.0
185.0
194.0
203.0
212.0
221.0
230.0
239.0
248.0
-30.0
-25.0
-20.0
-15.0
-10.0
-5.0
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
60.0
65.0
70.0
75.0
80.0
85.0
90.0
95.0
100.0
105.0
110.0
115.0
120.0
Discharge thermistor
Voltage(V)Resistance(K )Tempe F Tempe C
-22.0
-13.0
-4.0
5.0
14.0
23.0
32.0
41.0
50.0
59.0
68.0
77.0
86.0
95.0
104.0
113.0
122.0
131.0
140.0
149.0
158.0
167.0
176.0
185.0
194.0
203.0
212.0
221.0
230.0
239.0
248.0
-30.0
-25.0
-20.0
-15.0
-10.0
-5.0
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
60.0
65.0
70.0
75.0
80.0
85.0
90.0
95.0
100.0
105.0
110.0
115.0
120.0
Compressor temperature thermistor
Voltage(V)Resistance(K )Tempe F Tempe C
0.00
200.00
400.00
600.00
800.00
1000.00
(-30.00) (0.00) (30.00) (60.00) (90.00) (120.00)
-22
32
86 140
194
248
Temperature F( C)
Characteristics of compressor thermistor
Resistance(k )
0.00
200.00
400.00
600.00
800.00
1000.00
(-30.00) (0.00) (30.00) (60.00) (90.00) (120.00)
-22
32
86 140
194
248
Temperature F( C)
Resistance(k )
3-3. Thermistor Resistance Values
1013.11 0.06
729.09 0.09
531.56 0.12
392.31 0.16
392.91
0.21
221.09 0.28
168.60 0.36
129.84 0.46
100.91 0.57
79.12 0.71
62.55 0.86
49.84
1.03
40.01 1.23
32.35 1.43
26.34 1.65
21.58 1.88
17.79 2.11
14.75 2.34
12.30
2.57
10.32 2.79
8.70 3.00
7.36 3.19
6.27
3.37
5.36
3.54
4.60
3.69
3.96
3.83
3.43
3.96
2.98
4.07
2.60
4.17
2.27 4.26
2.00 4.33
1013.11 0.06
729.09 0.09
531.56 0.12
392.31 0.16
392.91
0.21
221.09 0.28
168.60 0.36
129.84 0.46
100.91 0.57
79.12 0.71
62.55 0.86
49.84
1.03
40.01 1.23
32.35 1.43
26.34 1.65
21.58 1.88
17.79 2.11
14.75 2.34
12.30
2.57
10.32 2.79
8.70 3.00
7.36 3.19
6.27
3.37
5.36
3.54
4.60
3.69
3.96
3.83
3.43
3.96
2.98
4.07
2.60
4.17
2.27 4.26
2.00 4.33
0.00
20.00
40.00
60.00
80.00
100.00
(-30.00) (-10.00) (10.00) (30.00) (50.00) (70.00)
Characteristics of heat exchanger thermistor (Outdoor)
Resistance(k )
Temperature F( C)
-22
14
50 86
122 158
03-10
-22.0
-13.0
-4.0
5.0
14.0
23.0
32.0
41.0
50.0
59.0
68.0
77.0
86.0
95.0
104.0
113.0
122.0
131.0
140.0
149.0
158.0
167.0
176.0
-30.0
-25.0
-20.0
-15.0
-10.0
-5.0
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
60.0
65.0
70.0
75.0
80.0
-22.0
-13.0
-4.0
5.0
14.0
23.0
32.0
41.0
50.0
59.0
68.0
77.0
86.0
95.0
104.0
113.0
122.0
131.0
140.0
149.0
158.0
167.0
176.0
-30.0
-25.0
-20.0
-15.0
-10.0
-5.0
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
60.0
65.0
70.0
75.0
80.0
Outdoor heat exchanger thermistor
Voltage(V)Resistance(K )Tempe F Tempe C
Outdoor Temprature thermistor
Voltage(V)Resistance(K )Tempe F Tempe C
0.00
40.00
80.00
120.00
160.00
200.00
(-30.00) (-10.00) (10.00) (30.00) (50.00)
Characteristics of outdoor temperature thermistor
Resistance(k )
Temperature F( C)
-22
14
50 86
122
95.58 0.24 224.33 0.73
159.71 0.97
115.24 1.25
84.21 1.56
62.28 1.90
46.58 2.26
35.21 2.61
26.88 2.94
20.72 3.25
16.12 3.52
12.64 3.76
10.00 3.97
7.97 4.14
6.40 4.28
5.18 4.41
4.21 4.51
3.45 4.59
2.85 4.65
2.36 4.71
1.97 4.76
1.65 4.79
1.39 4.83
1.18 4.85
68.90 0.32
50.31 0.43
37.19 0.57
27.81 0.73
21.02 0.92
16.05 1.14
12.38 1.39
9.63 1.65
7.56 1.93
5.98 2.21
4.77 2.49
3.84 2.77
3.11 3.02
2.53 3.26
2.08 3.48
1.71 3.68
1.42 3.85
1.19 4.00
1.00 4.13
0.84 4.25
0.71 4.35
0.61 4.43
1116,Suenaga,Takatsu-ku,Kawasaki 213-8502,Japan
Oct. 2012 Printed in Japan
Loading...